ASHRAE Thermal Guidelines
2
Agenda
•  ASHRAE and TC9.9
•  Thermal Guidelines (Third Edition)
•  Air-cooling
•  Liquid-cooling
•  Air-cooling thermal guidelines in practice
•  Performance
•  Reliability
3
ASHRAE and TC 9.9
• ASHRAE
•  American Society of Heating, Refrigeration and Air-
Conditioning Engineers
• Technical Committee 9.9
•  Technical Committee 9.9 – Mission Critical Facilities, Data
Centers, Technology Spaces, & Electronic Equipment
(http://tc99.ashraetcs.org/index.html)
•  Environment – thermal, structural, design, testing of data
centers and technology spaces for IT equipment
• Committee Members
•  IT equipment manufacturers
•  Environmental equipment manufacturers
•  Data center designers
•  End users
4
TC 9.9 Datacom Book Series
1.  Thermal Guidelines for Data Processing Environments 3rd Edition
2.  Datacom Equipment Power Trends & Cooling Applications 2nd Edition
(2012)
3.  Design Considerations for Datacom Equipment Centers (2006)
4.  Liquid Cooling Guidelines for Datacom Equipment Centers 2nd Edition
(2014)
5.  Structural & Vibration Guidelines for Datacom Equipment Centers
(2008)
6.  Best Practices for Datacom Facility Energy Efficiency (2008)
7.  High Density Data Centers – Case Studies & Best Practices (2008)
8.  Particulate & Gaseous Contamination in Datacom Environments (2009)
9.  Real-Time Energy Consumption Measurements in Data Centers (2009)
10. Green Tips for Data Centers (2011)
5
Thermal Guidelines for Data Processing
Environments
Chapter 1 – Introduction
Chapter 2 – Environmental Guidelines
for Air-Cooled Equipment
Chapter 3 – Environmental Guidelines
for Liquid-Cooled Equipment
Chapter 4 – Facility Temperature & Humidity
Measurement
Chapter 5 – Equipment Placement & Airflow
Patterns
Chapter 6 – Equipment Manufacturers Heat
& Airflow Reporting
6
Air-Cooled IT Equipment Class Ranges
•  Allowable Range – ITE designed to function within this
range
•  Recommended Range – Guidance from ITE
manufacturers for high reliability, minimal power
consumption (of ITE) and maximum performance
•  Operating Range – Actual limits for an individual
datacenter
•  Can begin with the recommended range
•  Dependent upon datacenter operator’s evaluation of
ITE factors described in the whitepaper in
combination with knowledge of the datacenter
design
7
2011 ASHRAE Thermal Guidelines
Recommended	
  
8
Operating
Envelope
ITE
Allowable
Envelope
ITE
Corrosion
ITE
Acoustical
Noise
ITE
Reliability
ITE Power
ITE
Performance
ITE Cost
ITE
Airflow
Datacenter
operational
knowledge
Operating Envelope
9
Liquid-Cooling Environments
IT EquipmentFacility
Atmosphere ← Building ← Room ← Aisle ← Rack ← System ← Board ← Chip
Reference
Point
10
2011 ASHRAE Liquid-Cooled Guidelines
Classes	
  
Main Cooling
Equipment	
  
Supplemental
Cooling
Equipment	
  
Facility
Supply Water
Temp (°C)	
  
W1	
  
Chiller/Cooling Tower	
  
Water-side
Economizer
(w/ drycooler or
cooling tower)	
  
2 – 17 	
  
W2	
   2 – 27 	
  
W3	
   Cooling Tower	
   Chiller	
   2 – 32 	
  
W4	
  
Water-side Economizer
(w/ drycooler or
cooling tower)	
  
N/A	
   2 – 45 	
  
W5	
   Building heating system Cooling tower > 45 	
  
11
Optimize Performance, Power, Acoustics
ITE Thermal Design
Damage
Limit
Shutdown
Functional
Limit
Performance
and Power
Management
Reliability
Limit
Manage
Cooling
ComponentTemperature
12
Damage Protection
Turbo
Design
PowerSaving,
LowerFrequency
PO
P1
P2
Pn
• 
• 
• 
CPU Performance – Light Load
21°C
A4Workload-tuned
35°C
A2server
45°C
A4server
A2server
T
A4Workload-tuned
A4server
A2server
A4Workload-tuned
A4server
Unpredictable performance, memory follows a similar trend
although throttling mechanism is different
13
Damage Protection
PO
P1
P2
Pn
• 
• 
• 
Turbo
Design
PowerSaving,
LowerFrequency
CPU Performance – Heavy Load
A4Workload-tuned
A2server
A2server
T
Performance – dependent on adequacy of thermal design
A2server
A4Workload-tuned
A4server
A4server
A4Workload-tuned
A4server
21°C 35°C 45°C
14
Reliability ‘X-Factor’
Assumes	
  con*nuous	
  (7	
  x	
  24	
  x	
  365)	
  opera*on	
  with	
  Dry	
  Bulb	
  Temp.	
  at	
  ITE	
  inlet.	
  	
  
15
Server Reliability Trend vs. Ambient Temperature
(cont.)
Ÿ  2010 dry bulb temp for Chicago with air mixing to maintain 59°F min. temp.
16
Ÿ  Cross referencing the hardware failure rates with the dry bulb data for
Chicago, we can establish the Net X-Factor across the whole year.
Application of X-Factor (Chicago example)
 The	
  Net	
  X-­‐Factor	
  for	
  in	
  Chicago	
  IT	
  hardware	
  failure	
  with	
  compressor-­‐less	
  
cooling	
  and	
  a	
  variable	
  data	
  center	
  temperature	
  is	
  almost	
  exactly	
  the	
  SAME	
  
as	
  if	
  the	
  data	
  center	
  was	
  operaDng	
  at	
  a	
  Dghtly	
  controlled	
  temp.	
  of	
  68°F.	
  
17
Ÿ  Average Net Failure Rate Comparison for Air-side
Economization (US Cities)
City Comparison: Reliability
18
Ÿ  Chiller Hours Per Year for Air-side Economization (US Cities)
City Comparison: Chiller Hours
19
Backup
20
ETSI
21
ASHRAE Environmental Classes
2011 2008 Applications IT Equipment Environmental Control
A1 1
Datacenter
Enterprise servers, storage
products
Tightly controlled
A2 2
Volume servers, storage products,
personal computers, workstations
Some control
A3 NA
Volume servers, storage products,
personal computers, workstations
Some control
A4 NA
Volume servers, storage products,
personal computers, workstations
Some control
B 3
Office, home,
transportable
environment, etc.
Personal computers,
workstations, laptops, and
printers
Minimal control
C 4
Point-of-sale,
industrial,
factory, etc.
Point-of-sale equipment,
ruggedized controllers, or
computers and PDAs
No control
22
2011 Thermal Guidelines – Power and Airflow
–  Power – ITE thermal management drives air movers to cool components
–  Air movers, some silicon devices consume more power with elevated temperature
–  Airflow required not linear with temperature
Ambient Temperature- C
10 15 20 25 30 35 40
ServerPowerIncrease-xfactor
1.00
1.05
1.10
1.15
1.20
1.25
Ambient Temperature - C
10 15 20 25 30 35 40
ServerPowerIncrease-xfactor
1.00
1.05
1.10
1.15
1.20
1.25
Ambient Temperature - degrees C
10 15 20 25 30 35
ServerAirFlowrateIncrease
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
2.6
2.8
Server	
  Power	
   Server	
  Airflow	
  

More Related Content

What's hot

Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...Upsite Technologies
 
Cooling Optimization 101: A Beginner's Guide to Data Center Cooling
Cooling Optimization 101: A Beginner's Guide to Data Center CoolingCooling Optimization 101: A Beginner's Guide to Data Center Cooling
Cooling Optimization 101: A Beginner's Guide to Data Center CoolingUpsite Technologies
 
Data Center Cooling Design - Datacenter-serverroom
Data Center Cooling Design - Datacenter-serverroomData Center Cooling Design - Datacenter-serverroom
Data Center Cooling Design - Datacenter-serverroommarlisaclark
 
Data Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationData Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationGreg Stover
 
DataCenter:: Infrastructure Presentation
DataCenter:: Infrastructure PresentationDataCenter:: Infrastructure Presentation
DataCenter:: Infrastructure PresentationMuhammad Asad Rashid
 
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICESASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICESglenioleonel
 
For Most Data Centers, Liquid and Air Cooling Will Not be Mutually Exclusive
For Most Data Centers, Liquid and Air Cooling Will Not be Mutually ExclusiveFor Most Data Centers, Liquid and Air Cooling Will Not be Mutually Exclusive
For Most Data Centers, Liquid and Air Cooling Will Not be Mutually ExclusiveUpsite Technologies
 
Tia 942 Data Center Standards
Tia 942 Data Center StandardsTia 942 Data Center Standards
Tia 942 Data Center StandardsSri Chalasani
 
4 steps to quickly improve pue through airflow management
4 steps to quickly improve pue through airflow management4 steps to quickly improve pue through airflow management
4 steps to quickly improve pue through airflow managementUpsite Technologies
 
Data center cooling infrastructure slide
Data center cooling infrastructure slideData center cooling infrastructure slide
Data center cooling infrastructure slideLivin Jose
 
Datacenter101
Datacenter101Datacenter101
Datacenter101tarundua
 
Hot Aisle & Cold Aisle Containment Solutions & Case Studies
Hot Aisle & Cold Aisle Containment Solutions & Case StudiesHot Aisle & Cold Aisle Containment Solutions & Case Studies
Hot Aisle & Cold Aisle Containment Solutions & Case Studies42U Data Center Solutions
 
Implementing Hot and Cold Air Containment in Existing Data Centers
Implementing Hot and Cold Air Containment in Existing Data CentersImplementing Hot and Cold Air Containment in Existing Data Centers
Implementing Hot and Cold Air Containment in Existing Data CentersSchneider Electric
 
Data Center Tiers Explained
Data Center Tiers ExplainedData Center Tiers Explained
Data Center Tiers ExplainedData Cave
 
Essential elements of data center operations
Essential elements of data center operationsEssential elements of data center operations
Essential elements of data center operationsSchneider Electric
 
Datacenter best practices design and implementation
Datacenter best practices design and implementationDatacenter best practices design and implementation
Datacenter best practices design and implementationAnton An
 
Murphy Data Center Services Infographic
Murphy Data Center Services InfographicMurphy Data Center Services Infographic
Murphy Data Center Services InfographicGary Woodcock
 

What's hot (20)

Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
 
Cooling Optimization 101: A Beginner's Guide to Data Center Cooling
Cooling Optimization 101: A Beginner's Guide to Data Center CoolingCooling Optimization 101: A Beginner's Guide to Data Center Cooling
Cooling Optimization 101: A Beginner's Guide to Data Center Cooling
 
Data Center Cooling Design - Datacenter-serverroom
Data Center Cooling Design - Datacenter-serverroomData Center Cooling Design - Datacenter-serverroom
Data Center Cooling Design - Datacenter-serverroom
 
Modular Data Center Design
Modular Data Center DesignModular Data Center Design
Modular Data Center Design
 
Data Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationData Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure Optimization
 
DataCenter:: Infrastructure Presentation
DataCenter:: Infrastructure PresentationDataCenter:: Infrastructure Presentation
DataCenter:: Infrastructure Presentation
 
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICESASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
ASHRAE TC9.9 - DATA CENTER STANDARD AND BEST PRACTICES
 
For Most Data Centers, Liquid and Air Cooling Will Not be Mutually Exclusive
For Most Data Centers, Liquid and Air Cooling Will Not be Mutually ExclusiveFor Most Data Centers, Liquid and Air Cooling Will Not be Mutually Exclusive
For Most Data Centers, Liquid and Air Cooling Will Not be Mutually Exclusive
 
Tia 942 Data Center Standards
Tia 942 Data Center StandardsTia 942 Data Center Standards
Tia 942 Data Center Standards
 
4 steps to quickly improve pue through airflow management
4 steps to quickly improve pue through airflow management4 steps to quickly improve pue through airflow management
4 steps to quickly improve pue through airflow management
 
Data center cooling infrastructure slide
Data center cooling infrastructure slideData center cooling infrastructure slide
Data center cooling infrastructure slide
 
Datacenter101
Datacenter101Datacenter101
Datacenter101
 
Hot Aisle & Cold Aisle Containment Solutions & Case Studies
Hot Aisle & Cold Aisle Containment Solutions & Case StudiesHot Aisle & Cold Aisle Containment Solutions & Case Studies
Hot Aisle & Cold Aisle Containment Solutions & Case Studies
 
Implementing Hot and Cold Air Containment in Existing Data Centers
Implementing Hot and Cold Air Containment in Existing Data CentersImplementing Hot and Cold Air Containment in Existing Data Centers
Implementing Hot and Cold Air Containment in Existing Data Centers
 
Data Center Cooling Study on Liquid Cooling
Data Center Cooling Study on Liquid CoolingData Center Cooling Study on Liquid Cooling
Data Center Cooling Study on Liquid Cooling
 
Data Center Tiers Explained
Data Center Tiers ExplainedData Center Tiers Explained
Data Center Tiers Explained
 
Essential elements of data center operations
Essential elements of data center operationsEssential elements of data center operations
Essential elements of data center operations
 
HVAC for Data Centers
HVAC for Data CentersHVAC for Data Centers
HVAC for Data Centers
 
Datacenter best practices design and implementation
Datacenter best practices design and implementationDatacenter best practices design and implementation
Datacenter best practices design and implementation
 
Murphy Data Center Services Infographic
Murphy Data Center Services InfographicMurphy Data Center Services Infographic
Murphy Data Center Services Infographic
 

Similar to Ashrae thermal guidelines svlg 2015 (1)

Slides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingSlides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingGraybar
 
Optimize power and cooling final
Optimize power and cooling finalOptimize power and cooling final
Optimize power and cooling finalViridity Software
 
Optimize power and cooling final 1
Optimize power and cooling final 1Optimize power and cooling final 1
Optimize power and cooling final 1Viridity Software
 
How IT Decisions Impact Facilities: The Importance of Mutual Understanding
How IT Decisions Impact Facilities: The Importance of Mutual UnderstandingHow IT Decisions Impact Facilities: The Importance of Mutual Understanding
How IT Decisions Impact Facilities: The Importance of Mutual UnderstandingUpsite Technologies
 
Virtualization for efficiency: by Kathrin Winkler, The green grid
Virtualization for efficiency: by Kathrin Winkler, The green gridVirtualization for efficiency: by Kathrin Winkler, The green grid
Virtualization for efficiency: by Kathrin Winkler, The green gridDCC Mission Critical
 
Bits, Bytes and BTUs: Warm Water Liquid Cooling at NREL
Bits, Bytes and BTUs: Warm Water Liquid Cooling at NRELBits, Bytes and BTUs: Warm Water Liquid Cooling at NREL
Bits, Bytes and BTUs: Warm Water Liquid Cooling at NRELinside-BigData.com
 
What's Next in Cooling: Capacity, Containment, & More
What's Next in Cooling: Capacity, Containment, & MoreWhat's Next in Cooling: Capacity, Containment, & More
What's Next in Cooling: Capacity, Containment, & MoreUpsite Technologies
 
Thermal Management of Edge Data Centers
Thermal Management of Edge Data Centers Thermal Management of Edge Data Centers
Thermal Management of Edge Data Centers Raptor Power Systems
 
Pmdc Smdc Technical Overview 24 Mar2010
Pmdc Smdc Technical Overview 24 Mar2010Pmdc Smdc Technical Overview 24 Mar2010
Pmdc Smdc Technical Overview 24 Mar2010Tony Bentivegna
 
OCP liquid direct to chip temperature guideline.pdf
OCP liquid direct to chip temperature guideline.pdfOCP liquid direct to chip temperature guideline.pdf
OCP liquid direct to chip temperature guideline.pdfbui thequan
 
Cooling & Power Issues
Cooling & Power IssuesCooling & Power Issues
Cooling & Power Issuesinstor
 
Cirrascale forest container march 2011
Cirrascale forest container march 2011Cirrascale forest container march 2011
Cirrascale forest container march 2011Muchamad Jainuri
 
Apc cooling solutions
Apc cooling solutionsApc cooling solutions
Apc cooling solutionspeperoca
 
Datwyler data center presentation info tech middle east
Datwyler data center presentation info tech middle eastDatwyler data center presentation info tech middle east
Datwyler data center presentation info tech middle eastAli Shoaee
 
Data Center Free Cooling in the Middle East
Data Center Free Cooling in the Middle EastData Center Free Cooling in the Middle East
Data Center Free Cooling in the Middle EastSyskaHennessy
 
LEED 301 - ASE,WSE,Kyoto,Munters
LEED 301 - ASE,WSE,Kyoto,MuntersLEED 301 - ASE,WSE,Kyoto,Munters
LEED 301 - ASE,WSE,Kyoto,MuntersNorival Corrêa
 

Similar to Ashrae thermal guidelines svlg 2015 (1) (20)

Data center m&e
Data center  m&eData center  m&e
Data center m&e
 
Slides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingSlides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for Cooling
 
Optimize power and cooling final
Optimize power and cooling finalOptimize power and cooling final
Optimize power and cooling final
 
Optimize power and cooling final 1
Optimize power and cooling final 1Optimize power and cooling final 1
Optimize power and cooling final 1
 
EnergyPlus
EnergyPlusEnergyPlus
EnergyPlus
 
How IT Decisions Impact Facilities: The Importance of Mutual Understanding
How IT Decisions Impact Facilities: The Importance of Mutual UnderstandingHow IT Decisions Impact Facilities: The Importance of Mutual Understanding
How IT Decisions Impact Facilities: The Importance of Mutual Understanding
 
Tcc cooling
Tcc coolingTcc cooling
Tcc cooling
 
Virtualization for efficiency: by Kathrin Winkler, The green grid
Virtualization for efficiency: by Kathrin Winkler, The green gridVirtualization for efficiency: by Kathrin Winkler, The green grid
Virtualization for efficiency: by Kathrin Winkler, The green grid
 
Bits, Bytes and BTUs: Warm Water Liquid Cooling at NREL
Bits, Bytes and BTUs: Warm Water Liquid Cooling at NRELBits, Bytes and BTUs: Warm Water Liquid Cooling at NREL
Bits, Bytes and BTUs: Warm Water Liquid Cooling at NREL
 
What's Next in Cooling: Capacity, Containment, & More
What's Next in Cooling: Capacity, Containment, & MoreWhat's Next in Cooling: Capacity, Containment, & More
What's Next in Cooling: Capacity, Containment, & More
 
Thermal Management of Edge Data Centers
Thermal Management of Edge Data Centers Thermal Management of Edge Data Centers
Thermal Management of Edge Data Centers
 
Pmdc Smdc Technical Overview 24 Mar2010
Pmdc Smdc Technical Overview 24 Mar2010Pmdc Smdc Technical Overview 24 Mar2010
Pmdc Smdc Technical Overview 24 Mar2010
 
Eliminating Data Center Hot Spots
Eliminating Data Center Hot SpotsEliminating Data Center Hot Spots
Eliminating Data Center Hot Spots
 
OCP liquid direct to chip temperature guideline.pdf
OCP liquid direct to chip temperature guideline.pdfOCP liquid direct to chip temperature guideline.pdf
OCP liquid direct to chip temperature guideline.pdf
 
Cooling & Power Issues
Cooling & Power IssuesCooling & Power Issues
Cooling & Power Issues
 
Cirrascale forest container march 2011
Cirrascale forest container march 2011Cirrascale forest container march 2011
Cirrascale forest container march 2011
 
Apc cooling solutions
Apc cooling solutionsApc cooling solutions
Apc cooling solutions
 
Datwyler data center presentation info tech middle east
Datwyler data center presentation info tech middle eastDatwyler data center presentation info tech middle east
Datwyler data center presentation info tech middle east
 
Data Center Free Cooling in the Middle East
Data Center Free Cooling in the Middle EastData Center Free Cooling in the Middle East
Data Center Free Cooling in the Middle East
 
LEED 301 - ASE,WSE,Kyoto,Munters
LEED 301 - ASE,WSE,Kyoto,MuntersLEED 301 - ASE,WSE,Kyoto,Munters
LEED 301 - ASE,WSE,Kyoto,Munters
 

Recently uploaded

办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书
办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书
办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书zdzoqco
 
办理(UC毕业证书)查尔斯顿大学毕业证成绩单原版一比一
办理(UC毕业证书)查尔斯顿大学毕业证成绩单原版一比一办理(UC毕业证书)查尔斯顿大学毕业证成绩单原版一比一
办理(UC毕业证书)查尔斯顿大学毕业证成绩单原版一比一z xss
 
办理(USYD毕业证书)澳洲悉尼大学毕业证成绩单原版一比一
办理(USYD毕业证书)澳洲悉尼大学毕业证成绩单原版一比一办理(USYD毕业证书)澳洲悉尼大学毕业证成绩单原版一比一
办理(USYD毕业证书)澳洲悉尼大学毕业证成绩单原版一比一diploma 1
 
Architecture case study India Habitat Centre, Delhi.pdf
Architecture case study India Habitat Centre, Delhi.pdfArchitecture case study India Habitat Centre, Delhi.pdf
Architecture case study India Habitat Centre, Delhi.pdfSumit Lathwal
 
Cosumer Willingness to Pay for Sustainable Bricks
Cosumer Willingness to Pay for Sustainable BricksCosumer Willingness to Pay for Sustainable Bricks
Cosumer Willingness to Pay for Sustainable Bricksabhishekparmar618
 
Call Girls Satellite 7397865700 Ridhima Hire Me Full Night
Call Girls Satellite 7397865700 Ridhima Hire Me Full NightCall Girls Satellite 7397865700 Ridhima Hire Me Full Night
Call Girls Satellite 7397865700 Ridhima Hire Me Full Nightssuser7cb4ff
 
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)jennyeacort
 
PORTAFOLIO 2024_ ANASTASIYA KUDINOVA
PORTAFOLIO   2024_  ANASTASIYA  KUDINOVAPORTAFOLIO   2024_  ANASTASIYA  KUDINOVA
PORTAFOLIO 2024_ ANASTASIYA KUDINOVAAnastasiya Kudinova
 
办理学位证(TheAuckland证书)新西兰奥克兰大学毕业证成绩单原版一比一
办理学位证(TheAuckland证书)新西兰奥克兰大学毕业证成绩单原版一比一办理学位证(TheAuckland证书)新西兰奥克兰大学毕业证成绩单原版一比一
办理学位证(TheAuckland证书)新西兰奥克兰大学毕业证成绩单原版一比一Fi L
 
Abu Dhabi Call Girls O58993O4O2 Call Girls in Abu Dhabi`
Abu Dhabi Call Girls O58993O4O2 Call Girls in Abu Dhabi`Abu Dhabi Call Girls O58993O4O2 Call Girls in Abu Dhabi`
Abu Dhabi Call Girls O58993O4O2 Call Girls in Abu Dhabi`dajasot375
 
Call In girls Bhikaji Cama Place 🔝 ⇛8377877756 FULL Enjoy Delhi NCR
Call In girls Bhikaji Cama Place 🔝 ⇛8377877756 FULL Enjoy Delhi NCRCall In girls Bhikaji Cama Place 🔝 ⇛8377877756 FULL Enjoy Delhi NCR
Call In girls Bhikaji Cama Place 🔝 ⇛8377877756 FULL Enjoy Delhi NCRdollysharma2066
 
Call Girls Meghani Nagar 7397865700 Independent Call Girls
Call Girls Meghani Nagar 7397865700  Independent Call GirlsCall Girls Meghani Nagar 7397865700  Independent Call Girls
Call Girls Meghani Nagar 7397865700 Independent Call Girlsssuser7cb4ff
 
'CASE STUDY OF INDIRA PARYAVARAN BHAVAN DELHI ,
'CASE STUDY OF INDIRA PARYAVARAN BHAVAN DELHI ,'CASE STUDY OF INDIRA PARYAVARAN BHAVAN DELHI ,
'CASE STUDY OF INDIRA PARYAVARAN BHAVAN DELHI ,Aginakm1
 
call girls in Harsh Vihar (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
call girls in Harsh Vihar (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️call girls in Harsh Vihar (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
call girls in Harsh Vihar (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
西北大学毕业证学位证成绩单-怎么样办伪造
西北大学毕业证学位证成绩单-怎么样办伪造西北大学毕业证学位证成绩单-怎么样办伪造
西北大学毕业证学位证成绩单-怎么样办伪造kbdhl05e
 
VIP Call Girls Service Bhagyanagar Hyderabad Call +91-8250192130
VIP Call Girls Service Bhagyanagar Hyderabad Call +91-8250192130VIP Call Girls Service Bhagyanagar Hyderabad Call +91-8250192130
VIP Call Girls Service Bhagyanagar Hyderabad Call +91-8250192130Suhani Kapoor
 
办理学位证(NUS证书)新加坡国立大学毕业证成绩单原版一比一
办理学位证(NUS证书)新加坡国立大学毕业证成绩单原版一比一办理学位证(NUS证书)新加坡国立大学毕业证成绩单原版一比一
办理学位证(NUS证书)新加坡国立大学毕业证成绩单原版一比一Fi L
 
在线办理ohio毕业证俄亥俄大学毕业证成绩单留信学历认证
在线办理ohio毕业证俄亥俄大学毕业证成绩单留信学历认证在线办理ohio毕业证俄亥俄大学毕业证成绩单留信学历认证
在线办理ohio毕业证俄亥俄大学毕业证成绩单留信学历认证nhjeo1gg
 
8377877756 Full Enjoy @24/7 Call Girls in Nirman Vihar Delhi NCR
8377877756 Full Enjoy @24/7 Call Girls in Nirman Vihar Delhi NCR8377877756 Full Enjoy @24/7 Call Girls in Nirman Vihar Delhi NCR
8377877756 Full Enjoy @24/7 Call Girls in Nirman Vihar Delhi NCRdollysharma2066
 
Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Service
Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts ServiceCall Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Service
Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Servicejennyeacort
 

Recently uploaded (20)

办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书
办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书
办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书
 
办理(UC毕业证书)查尔斯顿大学毕业证成绩单原版一比一
办理(UC毕业证书)查尔斯顿大学毕业证成绩单原版一比一办理(UC毕业证书)查尔斯顿大学毕业证成绩单原版一比一
办理(UC毕业证书)查尔斯顿大学毕业证成绩单原版一比一
 
办理(USYD毕业证书)澳洲悉尼大学毕业证成绩单原版一比一
办理(USYD毕业证书)澳洲悉尼大学毕业证成绩单原版一比一办理(USYD毕业证书)澳洲悉尼大学毕业证成绩单原版一比一
办理(USYD毕业证书)澳洲悉尼大学毕业证成绩单原版一比一
 
Architecture case study India Habitat Centre, Delhi.pdf
Architecture case study India Habitat Centre, Delhi.pdfArchitecture case study India Habitat Centre, Delhi.pdf
Architecture case study India Habitat Centre, Delhi.pdf
 
Cosumer Willingness to Pay for Sustainable Bricks
Cosumer Willingness to Pay for Sustainable BricksCosumer Willingness to Pay for Sustainable Bricks
Cosumer Willingness to Pay for Sustainable Bricks
 
Call Girls Satellite 7397865700 Ridhima Hire Me Full Night
Call Girls Satellite 7397865700 Ridhima Hire Me Full NightCall Girls Satellite 7397865700 Ridhima Hire Me Full Night
Call Girls Satellite 7397865700 Ridhima Hire Me Full Night
 
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)
 
PORTAFOLIO 2024_ ANASTASIYA KUDINOVA
PORTAFOLIO   2024_  ANASTASIYA  KUDINOVAPORTAFOLIO   2024_  ANASTASIYA  KUDINOVA
PORTAFOLIO 2024_ ANASTASIYA KUDINOVA
 
办理学位证(TheAuckland证书)新西兰奥克兰大学毕业证成绩单原版一比一
办理学位证(TheAuckland证书)新西兰奥克兰大学毕业证成绩单原版一比一办理学位证(TheAuckland证书)新西兰奥克兰大学毕业证成绩单原版一比一
办理学位证(TheAuckland证书)新西兰奥克兰大学毕业证成绩单原版一比一
 
Abu Dhabi Call Girls O58993O4O2 Call Girls in Abu Dhabi`
Abu Dhabi Call Girls O58993O4O2 Call Girls in Abu Dhabi`Abu Dhabi Call Girls O58993O4O2 Call Girls in Abu Dhabi`
Abu Dhabi Call Girls O58993O4O2 Call Girls in Abu Dhabi`
 
Call In girls Bhikaji Cama Place 🔝 ⇛8377877756 FULL Enjoy Delhi NCR
Call In girls Bhikaji Cama Place 🔝 ⇛8377877756 FULL Enjoy Delhi NCRCall In girls Bhikaji Cama Place 🔝 ⇛8377877756 FULL Enjoy Delhi NCR
Call In girls Bhikaji Cama Place 🔝 ⇛8377877756 FULL Enjoy Delhi NCR
 
Call Girls Meghani Nagar 7397865700 Independent Call Girls
Call Girls Meghani Nagar 7397865700  Independent Call GirlsCall Girls Meghani Nagar 7397865700  Independent Call Girls
Call Girls Meghani Nagar 7397865700 Independent Call Girls
 
'CASE STUDY OF INDIRA PARYAVARAN BHAVAN DELHI ,
'CASE STUDY OF INDIRA PARYAVARAN BHAVAN DELHI ,'CASE STUDY OF INDIRA PARYAVARAN BHAVAN DELHI ,
'CASE STUDY OF INDIRA PARYAVARAN BHAVAN DELHI ,
 
call girls in Harsh Vihar (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
call girls in Harsh Vihar (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️call girls in Harsh Vihar (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
call girls in Harsh Vihar (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
 
西北大学毕业证学位证成绩单-怎么样办伪造
西北大学毕业证学位证成绩单-怎么样办伪造西北大学毕业证学位证成绩单-怎么样办伪造
西北大学毕业证学位证成绩单-怎么样办伪造
 
VIP Call Girls Service Bhagyanagar Hyderabad Call +91-8250192130
VIP Call Girls Service Bhagyanagar Hyderabad Call +91-8250192130VIP Call Girls Service Bhagyanagar Hyderabad Call +91-8250192130
VIP Call Girls Service Bhagyanagar Hyderabad Call +91-8250192130
 
办理学位证(NUS证书)新加坡国立大学毕业证成绩单原版一比一
办理学位证(NUS证书)新加坡国立大学毕业证成绩单原版一比一办理学位证(NUS证书)新加坡国立大学毕业证成绩单原版一比一
办理学位证(NUS证书)新加坡国立大学毕业证成绩单原版一比一
 
在线办理ohio毕业证俄亥俄大学毕业证成绩单留信学历认证
在线办理ohio毕业证俄亥俄大学毕业证成绩单留信学历认证在线办理ohio毕业证俄亥俄大学毕业证成绩单留信学历认证
在线办理ohio毕业证俄亥俄大学毕业证成绩单留信学历认证
 
8377877756 Full Enjoy @24/7 Call Girls in Nirman Vihar Delhi NCR
8377877756 Full Enjoy @24/7 Call Girls in Nirman Vihar Delhi NCR8377877756 Full Enjoy @24/7 Call Girls in Nirman Vihar Delhi NCR
8377877756 Full Enjoy @24/7 Call Girls in Nirman Vihar Delhi NCR
 
Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Service
Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts ServiceCall Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Service
Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Service
 

Ashrae thermal guidelines svlg 2015 (1)

  • 2. 2 Agenda •  ASHRAE and TC9.9 •  Thermal Guidelines (Third Edition) •  Air-cooling •  Liquid-cooling •  Air-cooling thermal guidelines in practice •  Performance •  Reliability
  • 3. 3 ASHRAE and TC 9.9 • ASHRAE •  American Society of Heating, Refrigeration and Air- Conditioning Engineers • Technical Committee 9.9 •  Technical Committee 9.9 – Mission Critical Facilities, Data Centers, Technology Spaces, & Electronic Equipment (http://tc99.ashraetcs.org/index.html) •  Environment – thermal, structural, design, testing of data centers and technology spaces for IT equipment • Committee Members •  IT equipment manufacturers •  Environmental equipment manufacturers •  Data center designers •  End users
  • 4. 4 TC 9.9 Datacom Book Series 1.  Thermal Guidelines for Data Processing Environments 3rd Edition 2.  Datacom Equipment Power Trends & Cooling Applications 2nd Edition (2012) 3.  Design Considerations for Datacom Equipment Centers (2006) 4.  Liquid Cooling Guidelines for Datacom Equipment Centers 2nd Edition (2014) 5.  Structural & Vibration Guidelines for Datacom Equipment Centers (2008) 6.  Best Practices for Datacom Facility Energy Efficiency (2008) 7.  High Density Data Centers – Case Studies & Best Practices (2008) 8.  Particulate & Gaseous Contamination in Datacom Environments (2009) 9.  Real-Time Energy Consumption Measurements in Data Centers (2009) 10. Green Tips for Data Centers (2011)
  • 5. 5 Thermal Guidelines for Data Processing Environments Chapter 1 – Introduction Chapter 2 – Environmental Guidelines for Air-Cooled Equipment Chapter 3 – Environmental Guidelines for Liquid-Cooled Equipment Chapter 4 – Facility Temperature & Humidity Measurement Chapter 5 – Equipment Placement & Airflow Patterns Chapter 6 – Equipment Manufacturers Heat & Airflow Reporting
  • 6. 6 Air-Cooled IT Equipment Class Ranges •  Allowable Range – ITE designed to function within this range •  Recommended Range – Guidance from ITE manufacturers for high reliability, minimal power consumption (of ITE) and maximum performance •  Operating Range – Actual limits for an individual datacenter •  Can begin with the recommended range •  Dependent upon datacenter operator’s evaluation of ITE factors described in the whitepaper in combination with knowledge of the datacenter design
  • 7. 7 2011 ASHRAE Thermal Guidelines Recommended  
  • 9. 9 Liquid-Cooling Environments IT EquipmentFacility Atmosphere ← Building ← Room ← Aisle ← Rack ← System ← Board ← Chip Reference Point
  • 10. 10 2011 ASHRAE Liquid-Cooled Guidelines Classes   Main Cooling Equipment   Supplemental Cooling Equipment   Facility Supply Water Temp (°C)   W1   Chiller/Cooling Tower   Water-side Economizer (w/ drycooler or cooling tower)   2 – 17   W2   2 – 27   W3   Cooling Tower   Chiller   2 – 32   W4   Water-side Economizer (w/ drycooler or cooling tower)   N/A   2 – 45   W5   Building heating system Cooling tower > 45  
  • 11. 11 Optimize Performance, Power, Acoustics ITE Thermal Design Damage Limit Shutdown Functional Limit Performance and Power Management Reliability Limit Manage Cooling ComponentTemperature
  • 12. 12 Damage Protection Turbo Design PowerSaving, LowerFrequency PO P1 P2 Pn •  •  •  CPU Performance – Light Load 21°C A4Workload-tuned 35°C A2server 45°C A4server A2server T A4Workload-tuned A4server A2server A4Workload-tuned A4server Unpredictable performance, memory follows a similar trend although throttling mechanism is different
  • 13. 13 Damage Protection PO P1 P2 Pn •  •  •  Turbo Design PowerSaving, LowerFrequency CPU Performance – Heavy Load A4Workload-tuned A2server A2server T Performance – dependent on adequacy of thermal design A2server A4Workload-tuned A4server A4server A4Workload-tuned A4server 21°C 35°C 45°C
  • 14. 14 Reliability ‘X-Factor’ Assumes  con*nuous  (7  x  24  x  365)  opera*on  with  Dry  Bulb  Temp.  at  ITE  inlet.    
  • 15. 15 Server Reliability Trend vs. Ambient Temperature (cont.) Ÿ  2010 dry bulb temp for Chicago with air mixing to maintain 59°F min. temp.
  • 16. 16 Ÿ  Cross referencing the hardware failure rates with the dry bulb data for Chicago, we can establish the Net X-Factor across the whole year. Application of X-Factor (Chicago example)  The  Net  X-­‐Factor  for  in  Chicago  IT  hardware  failure  with  compressor-­‐less   cooling  and  a  variable  data  center  temperature  is  almost  exactly  the  SAME   as  if  the  data  center  was  operaDng  at  a  Dghtly  controlled  temp.  of  68°F.  
  • 17. 17 Ÿ  Average Net Failure Rate Comparison for Air-side Economization (US Cities) City Comparison: Reliability
  • 18. 18 Ÿ  Chiller Hours Per Year for Air-side Economization (US Cities) City Comparison: Chiller Hours
  • 21. 21 ASHRAE Environmental Classes 2011 2008 Applications IT Equipment Environmental Control A1 1 Datacenter Enterprise servers, storage products Tightly controlled A2 2 Volume servers, storage products, personal computers, workstations Some control A3 NA Volume servers, storage products, personal computers, workstations Some control A4 NA Volume servers, storage products, personal computers, workstations Some control B 3 Office, home, transportable environment, etc. Personal computers, workstations, laptops, and printers Minimal control C 4 Point-of-sale, industrial, factory, etc. Point-of-sale equipment, ruggedized controllers, or computers and PDAs No control
  • 22. 22 2011 Thermal Guidelines – Power and Airflow –  Power – ITE thermal management drives air movers to cool components –  Air movers, some silicon devices consume more power with elevated temperature –  Airflow required not linear with temperature Ambient Temperature- C 10 15 20 25 30 35 40 ServerPowerIncrease-xfactor 1.00 1.05 1.10 1.15 1.20 1.25 Ambient Temperature - C 10 15 20 25 30 35 40 ServerPowerIncrease-xfactor 1.00 1.05 1.10 1.15 1.20 1.25 Ambient Temperature - degrees C 10 15 20 25 30 35 ServerAirFlowrateIncrease 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 Server  Power   Server  Airflow