SlideShare a Scribd company logo
1 of 110
GGEL
50MW SOLAR THERMAL POWER PLANT
POWER
DISTRIBUTION
PREPARED BY:
BANWARI LAL
INTRODUCTION
 GODAWARI GREEN ENERGY LIMITED (GGEL) IS
A FLAGSHIP COMPANY OF THE HIRA GROUP IN
THE RENEWABLE ENERGY SECTOR.
 GGEL’S FOCUS AREA IS POWER GENERATION
USING RENEWABLE SOURCES SUCH AS SOLAR
ENERGY, GEOTHERMAL ENERGY, WIND ENERGY
ETC.
 THE COMPANY WAS INCORPORATED AS A 100%
SUBSIDIARY OF THE GODAWARI POWER & ISPAT
LTD IN THE YEAR 2009.
VISION
 TO BE THE MOST ADMIRED POWER
GENERATION COMPANY DELIVERING SUPERIOR
VALUE TO INVESTORS, CUSTOMERS,
COMMUNITIES AND EMPLOYEES THROUGH
INNOVATION AND LEADERSHIP IN OPERATION
EXCELLENCE.
MISSION
 WE AIM TO GENERATE SUPERIOR RETURN FOR
OUR INVESTORS BY BEING THE LEADING
SOLAR THERMAL POWER GENERATING
COMPANY IN INDIA WITHIN 2022 AND BY BEING
THE FIRST COMPANY TO ACHIEVE GRID-PARITY
IN SOLAR POWER IN INDIA.
 WE COMMIT OURSELVES TO IMPROVING THE
QUALITY OF LIFE OF COMMUNITIES WE
INFLUENCE BY STRIKING A BALANCE BETWEEN
PROFIT, PEOPLE AND PLANET.
POWER DISTRIBUTION BLOCK DIAGRAM
GEN.
70.5 MVA
10.5 KV
GSU T/F
75 MVA
10.5/132 KV
UAT
7.5 MVA
10.5/6.6 KV
SST-1
2.5 MVA
10.5/0.440 KV
SST-2
2.5 MVA
10.5/0.440 KV
SST-3
1.5 MVA
6.6/0.440 KV
SST-4
750 KVA
6.6/0.440 KV
HV MOTORS
1.BFP-1/2/3
2.HTF PUMP-1/2/3/4
3.CWP-1/2/3
LV MOTORS
1. CEP 8. VACUUM PUMP 15. SEAL WATER PUMP
2. MOP 9. OIL MIST FAN 16. HTF SEAL PUMP
3. AOP 10. CONTROL OIL PUMP 17. LUBE OIL PURIFIER
4. EOP 11. AIR COMPRESSOR 18. CONTROL
5. JOP 12. CT FAN OFFLINE PUMP
6. CCWP 13. TURBINE GEAR
7. ACWP 14. GSC
GEN. BREAKER
UAT
BREAKER
BREAKER
BREAKER
HTF HEATER PUMP RW SUPPLY PUMP
R
Y
B
SWITCHIN
G YARD
POWER DISTRIBUTION TO THE TRANSFORMERS
UAT
GEN.
SST-1 SST-2
POWER
T/F
1. TURBINE IS NOT RUNNING.(GRID IS AVAILABLE)
2. TURBINE IS RUNNING.(GRID IS NOT AVAILABLE)
SG
SGPOWER
T/F
UAT SST-1 SST-2
GEN.
132KV
132KV
10.5KV
10.5KV
BLOCK DIAGRAM
LP
TURBINE
LP STEAM
DIRECT CONNECTION
INDIRECT
CONNECTION HP STEAM
ALTERNA
TOR
GEAR BOX
HP
TURBINE
GENERATOR
 IT IS A DEVICE THAT CONVERTS MECHANICAL
ENERGY INTO ELECTRICAL ENERGY.
 IT WORKS ON THE PRINCIPLE OF EMI(ELECTRO-
MAGNETIC INDUCTION) OF FARADAY.
 IT IS CONNECTED TO LP AND HP TURBINE DIRECT
AND INDIRECT RESPECTIVELY.
 HERE THE ELECTRICITY IS GENERATED AT 10.5KV.
RATED
POWER-
70.590MVA
RATED
VOLTAGE –
10500V+/- 10% V
RATED
CURRENT –
3881 A
ACTIVE POWER
-50 MW
SPEED – 3000rpm
GENERATOR SPECIFICATIONS
MACHINE CODE SGEN5-100A-2P
RATED VOLTAGE 10500V +/- 10%
RATED POWER 70590 KVA
PHASES 3
CONNECTION STAR
FREQUENCY 50 Hz
P.F.(COSF) 0.708
RATED CURRENT 3881 A
EXCITATION SELF
RATED SPEED 3000 rpm
INSULATION
CLASS
F
AMBIENT TEMP. 50C
PHASE SEQUENCE U1 V1 W1
IP 54
IM 7216
ACTIVE POWER 50 MW
TOTAL WEIGHT 116.800 Kg
COOLING TYPE AIR
TRANSFORMER – 75 MVA (10.5KV/132KV)
 IT IS AN ELECTRICAL
DEVICE THAT TRANSFER
ELECTRICAL ENERGY
FROM ONE SIDE TO
ANOTHERSIDE WITHOUT
CHANGE IN ITS
FREQUENCY.
 TRANSFORMER IS USED
TO CONVERT 10.5KV INTO
132KV FOR
TRANSMISSION TO
GSS(GRID SUB-STATION).
MARSHAILING
BOX
10.5 KV
INPUT
132KV
OUTPUT
GSU TRANSFORMER
COOLING
FAN
RATED OUTPUT
75 MVA
RATED VOLTAGE
10.5KV/132KV
RATED
CURRENT
328.04/4123.93 A
FREQUENCY
50Hz
PHASES
3
CONNECTION HV-STAR
LV-DELTA
NO. OF TAP
CHANGER 4
NO LOAD LOSS AT
RATED VOLTAGE 34 KW
LOAD LOSS AT
RATED CURRENT 275 KW
EFFICIENCY AT
UPF
100% LOAD-99.58%
25% LOAD-99.73%
AUXILARY LOSS 3 KW(max)
INSULATION LEVEL
HV WDG -
230/550 (KVrms/KVp)
LV WDG - 28/110 (KVrms/KVp)
TAP RATIO(N1/N2) 12.57
GSU TRANSFORMER ELECTRICAL
SPECIFICATIONS
REFERENCE
STANDARD
IS:2026
CORE & WDG MASS 38900Kg
TANK & FITTING
MASS
14900Kg
OIL MASS 17200Kg
TOTAL T/F MASS 71000Kg
TRANSPORT MASS 66000Kg
TOTAL OIL
QUANTITY
20200 Liters
OVERALL
DIMENSIONS
6.754.205.90 m
TRANSPORT
DIMENSIONS
5.302.503.75 m
GSU TRANSFORMER PHYSICAL
SPECIFICATIONS
TEMP. RISE OF
OIL
60C
TEMP. RISE OF
WDG
65C
AMBIENT TEMP. 50C
TYPE OF
COOLING
ONAN/ONAF
TANK PLATE THICKNESS
COVER 12 mm
BOTTOM 16 mm
SIDE 8 mm
SWITCHING YARD
 THE APPLICATION OF SWITCHYARDS IS TO
DELIVER THE GENERATED POWER FROM
POWER PLANT AT DESIRED VOLTAGE LEVEL TO
THE NEAREST GRID OR TRANSMISSION LINE.
 THE SWITCHYARD IS PROVIDED WITH NECESSARY
ISOLATORS, CIRCUIT BREAKERS, CURRENT
TRANSFORMER, POTENTIAL TRANSFORMERS,
SURGE ARRESTORS, WAVE TRAPS, PROTECTIVE
RELAYS, PLCC ETC.
 SWITCHYARD IS CONTROLLED FROM DCS WHICH
WILL BE LOCATED IN POWER BLOCK CONTROL
ROOM.
ABBREVIATIONS
 UAT – UNIT AUXILIARY TRANSFORMER
 SST – STATION SERVICE TRANSFORMER
 BFP – BOILER FEED PUMP
 CCWP – CLOSE COOLING WATER PUMP
 ACWP – AUXILIARY COOLING WATER PUMP
 HTF – HEAT TRANSFER FLUID
 JOP – JACKING OIL PUMP
 GSC – GLAND STEAM CONDENSOR
ABBREVIATIONS
 MOP – MAIN OIL PUMP
 AOP – AUXILIARY OIL PUMP
 EOP – EMERGENCY OIL PUMP
 CEP – CONDENSATE EXTRACTING PUMP
 CT FAN – COOLING TOWER FAN
 CWP – CIRCULATING WATER PUMP
 MOG – MAGNETIC OIL GAUGE
 PRV – PRESSURE RELEAVE VALVE
CONNECTION OF T/F’S
UAT – 7.5KVA(10.5KV/6.6KV)
 UAT – UNIT AUXILIARY T/F.
 IT CONNECT THE GENERATOR DIRECTLY TO
THE GENERATOR AUXILIARY LOAD VIA UAT
BREAKER.
 IT IS STEP DOWN T/F THAT CONVERTS 10.5KV
INTO 6.6KV.
 IT DELIVER THE POWER TO THE HIGH VOLTAGE
MOTOR LIKE BFP , HTF AND CWP ETC.
UAT CONNECTION
UAT
7.5 MVA
10.5KV/6.6KV
SST-3
1.5 MVA
6.6KV/0.440KV
SST-4
750KVA
6.6KV/0.440KV
BFP(3)
875 KW
6300V
96A
3071rpm
HTFP(4)
900KW
6300V
101A
2970rpm
CWP(3)
510KW
6300V
58A
986rpm
RAW WATER
PUMP SUPPLY
HTF HEATER
SPARE
MOTOR
FEEDER
CONSEVATOR
TANK
RADIATOR
COOLING
FAN
MOG
HT
TERMINAL
BOX
UAT
UAT SPECIFICATIONS
 COOLING – ONAN/ONAF
 RATING KVA – 7500/9375
 RATED VOLTAGE – HV V -1O500
LV V -6600
 FULL LOAD CURRENT – HV A -515.51
LV A -820.08
 GTD TEMP RISE – OIL -50C
WDG -55C
 BASIC INSULATION LEVEL - HV - 110/40
LV - 95/38
 FREQUENCY – 50Hz
 PHASES - 3
SST
 SST – STATION SERVICE T/F.
 IT CONNECT THE SYSTEM DIRECTLY TO THE
GENERATOR AUXILIARY LOAD.
 IT IS ALSO STEP DOWN T/F THAT CONVERTS 10.5KV
INTO 0.440KV.
 IT PROVIDE THE SUPPLY FOR LOW VOLTAGE
MOTORS USED IN THE PLANT LIKE CEP , CCWP , MOP
, AOP , EOP CWP ETC.
 HERE 4 SST’S ARE USED SUCH AS SST-1 , SST-2 , SST-3
, SST-4.
SST-1 CONNECTION TO LOADS
SST-1
2.5 MVA
10.5/0.440 KV
CONDENSAT
E PUMP 1&3
220 KW
415 V
193 A
1488 rpm
JOP 1&2
30 KW
415 V
27.1 A
1455 rpm
CT FAN 1&3
150 KW
415 V
132 A
1482rpm
VACUUM
PUMP-1
55 KW
415 V
96 A
CCWP 1&2
90 KW
415 V
78 A
2955 rpm
AOP 2
45 KW
415 V
78.4 A
1470 rpm
ACWP-1
55 KW
415 V
95.6 A
1475 rpm
AUXILIARY
LOAD
150 KW
AIR
COMPRESSOR
-2
37 KW
400 V
2965 rpm
COP
16 KW
415 V
TOTAL LOAD
= 848 KW
SST-2 CONNECTION TO LOADS
SST-2
2.5 MVA
10.5/0.440 KV
CT FAN-2
75 KW
415 V
132 A
1482 rpm
MOP
45 KW
415 V
78.4 A
1470 rpm
AIR
COMPRESSOR
-1
37 KW
400 V
2965 rpm
VACUUM
PUMP-2
55 KW
415 V
96 A
CONDENSAT
E PUMP-2
110 KW
415 V
193 A
1488 rpm
ACWP-2
55 KW
415 V
95.6 A
1475 rpm
COP
16 KW
AUXILIARY
LOAD
88.6 KW
TOTAL LOAD
= 481.6 KW
SST-4 CONNECTED LOAD
SST-4
750KVA
6.6/0.440KV
RAW WATER
MAKEUP
PUMP (2)
18.5KW
415V
31.5A
2929rpm
WASTE
WATER
PUMP (2)
1.5KW
415V
3.4A
1410rpm
TOTAL
LOAD = 40
KW
SST-1 CONNECTED LOADS
1. STREET LIGHT
2. JACKING OIL PUMP-2
3. SEAL WATER PUMP-1
4. COMDENSATE PUMP-1
5. WAREHOUSE BUILDING
6. OIL MIST FAN-1
7. ISOLATION T/F-1
8. CONDENSATE PUMP-3
9. HTF SEAL PUMP-1
10.CT FAN-1
11.HTF SEAL FAN-3
12.CT FAN-3
13.ISOLATION T/F-3
14.VENTILATION BACK
15.VENTILATION FRONT
16.VACUUM PUMP-1
17.ISOLATION T/F-5
18.BATTERY CHARGER-1
19.GLAND STEAM BLOWER—1
20.CCW-A
21.ETHERNET POWER SUPPLY
22.HVAC
23.ACWP-1
24.FCB-1
25.MCC 1-A INCOMMER
26.BUS COUPLER
SST-1 CONNECTED LOAD
1.ELECTRONIC BUILDING PANNEL
2.SEAL WATER PUMP-2
3.220KVA UPS
4.HEAT TRACE T/F
5.TURNING GEAR.
6.CONTROL OFFLINE PUMP-2
7.CCWP-B
8.TURBINE BUILDING PANEL
9.JOP-1
10.ETHERNET POWER SUPPLY
11.CONTROL OIL PUMP-2
12.AOP-2
13.LUBE OIL TANK HEATER
14.GENERATOR SPACE HEATER
15.ADMIN BUILDING FEEDER
16.EXCITATION(AVR) PANNEL
17.HTF HEATER PUMP
18.BATTERY CHARGER-2
19.CONTROL OIL HEATER
20.AIR COMPRESSOR
21.DG INCOMMER
SST-2 CONNECTED LOAD
1.MCC-1B
2.FCB-2
3.OIL MIST FAN-2
4.CT FAN-2
5.HTF SEAL PUMP-2
6.WTP-MCC
7.AIR COMPRESSOR-1
8.HTF SEAL PUMP-4
9.UPS BYPASS(220KVA)
10.ULLAGE PRIM. COND. FAN
11.MOP(AOP-1)
12.VACUUM PUMP-2
13.ULLAGE DISCHARGE PUMP
14.ISOLATION T/F-2
15.GLAND STEAM BLOWER-2
16.CONDENSATE PUMP-2
17.ISOLATING T/F-4
18.ULLAGE LOAD PUMP
19.ACWP-2
20.HOSTEL BUILDING LIGHT
21.ETHERNET POWER SUPPLY
22.ISOLATION T/F-6
23.CONTROL OIL PUMP-1
24.POWER BLOCK LIGHT PANNEL
25.CONTROL OFFLINE PUMP-1
HT
TERMINAL
BOX
RADIATOR
CONSEVATOR
TANK
PRV
BUCHHOLZ
RELAY
COOLING
FAN
MOG
SST 1 - 2.5MVA(10.5KV/0.440KV)
SST–1 SPECIFICATIONS
 COOLING – ONAN/ONAF
 RATING KVA – 2500/3125
 RATED VOLTAGE – HV V -1O500
LV V - 440
 FULL LOAD CURRENT – HV A -171.84
LV A -4100.38
 GTD TEMP RISE – OIL -50C
WDG -55C
 BASIC INSULATION LEVEL - HV - 110/40
LV - -/3
 FREQUENCY – 50Hz
 PHASES - 3
PRV
MOG
COOLING
FAN
BUCHHOLZ
RELAY
RADIATOR
HT
TERMINAL
BOX
CONSERVATOR
TANK
SST 2 - 2.5MVA(10.5KV/0.440KV)
SST-2 SPECIFICATIONS
 COOLING – ONAN/ONAF
 RATING KVA – 2500/3125
 RATED VOLTAGE – HV V -1O500
LV V - 440
 FULL LOAD CURRENT – HV A -171.84
LV A -4100.38
 GTD TEMP RISE – OIL -50C
WDG -55C
 BASIC INSULATION LEVEL - HV - 110/40
LV - -/3
 FREQUENCY – 50Hz
 PHASES - 3
CONSERVATOR
TANK
BUCHHOLZ
RELAY
MOG
RADIATOR
HT
TERMINAL
BOX
COOLING FAN
SST 3 - 1.5MVA(6.6KV/0.440KV)
SST-3 SPECIFICATIONS
 COOLING – ONAN/ONAF
 RATING KVA – 1500/1725
 RATED VOLTAGE – HV V -6600
LV V -440
 FULL LOAD CURRENT – HV A -131.21/150.89
LV A -1968.24/2263.41
 GTD TEMP RISE – OIL -50C
WDG -55C
 BASIC INSULATION LEVEL - HV - 110/40
LV - -/3
 FREQUENCY – 50Hz
 PHASES - 3
SST 4 – 750KVA(6.6KV/0.440KV
COOLING FAN
HT
TERMINAL
BOX
CONSERVATOR
TANK
RADIATOR
SST-4 SPECIFICATIONS
 COOLING – ONAN/ONAF
 RATING KVA – 750/863
 RATED VOLTAGE – HV V -6600
LV V -440
 FULL LOAD CURRENT – HV A -65.61/75.50
LV A -984.12/1132.36
 GTD TEMP RISE – OIL -50C
WDG -55C
 BASIC INSULATION LEVEL - HV - 60/20
LV - -/3
 FREQUENCY – 50Hz
 PHASES - 3
BFP
 BFP – BOILER FEED PUMP.
 IT IS USED TO FEED WATER TO STEAM
GENERATOR BOILER DRUM AT DESIRED
PRESSURE AND TEMPERATURE.
 IT EXTRACT WATER FROM DE-AERATOR AND
FEED IT TO THE BOILER DRUM VIA H.P. HEATERS
AND ECONOMIZER.
 NO. OF BFP ARE USED – 3.
PUMP
MOTOR
BFP
BFP SPECIFICATIONS
TYPE AMI400L2ABAFI
MOTOR TYPE SQUIRREL CAGE
CONNECTION STAR
RATED OUTPUT 875 KW
RATED VOLTAGE 6300V +/- 10%
FREQUENCY 50Hz +/- 5%
SPEED 3071 rpm
CURRENT 96 A
P.F.(COSF) 0.88
EFFICIENCY 95.3%
RATED TORQUE 2797 Nm
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS F
IP 55
IM 1001
IC 611
WEIGHT 3660 Kg
HTF PUMP
 HTF PUMP – HEAT TRANSFER FLUID PUMP.
 HTF SYSTEM'S MAIN FUNCTION IS TO
TRANSMIT THE HEAT RECEIVED BY THE
PARABOLIC TROUGH CONCENTRATORS TO THE
WATER STEAM CYCLE, IN ORDER TO GENERATE
STEAM THAT ACTIVATES THE TURBINE.
 NO. OF HTF PUMP ARE USED – 4.
MOTOR
PUMP
HTF PUMP
HTF PUMP SPECIFICATIONS
TYPE AMI400L2ABANI
MOTOR TYPE SQUIRREL CAGE
CONNECTION STAR
RATED OUTPUT 900 KW
RATED VOLTAGE 6300V +/- 10%
FREQUENCY 50Hz +/- 5%
SPEED 2970 rpm
CURRENT 101 A
P.F.(COSF) 0.85
EFFICIENCY 95.2%
AMBIENT TEMP. 50C
PHASES 3
INSULATION
CLASS
F
IP 55
IM 1001
IC 611
TOTAL WEIGHT 3470 Kg
DUTY S1
CWP
 CWP – COOLING WATER PUMP.
 IT IS USED TO CIRCULATE COOLING WATER
TO THE CONDENSER; SO THAT HIGH
PRESSURE LEFT OUT STEAM IN THE L.P.
CYLINDER CAN BE CONVERTED INTO WATER.
 NO. OF CWP ARE USED – 3.
CWP
MOTOR
PUMP
CWP SPECIFICATIONS
TYPE CODE AMI 400L6A
VAI
MOTOR TYPE SQUIRREL
CAGE
CONNECTION STAR
RATED OUTPUT 510 KW
RATED VOLTAGE 6300V +/- 10%
FREQUENCY 50Hz +/- 5%
SPEED 985 rpm
CURRENT 60 A
P.F.(COSF) 0.82
EFFICIENCY 93.7%-94.3%
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS F
IP 55
RATED TORQUE 4946 Nm
IC 611
IM 4011
TOTAL WEIGHT 3160 Kg
DUTY S1
CEP
 CEP – CONDENSATE EXTRACTING PUMP.
 C.E.P. PUMP IS USED TO EXTRACT THE
CONDENSATE WATER FROM THE HOT WELL
AND SUPPLY TO THE DEAREATOR AFTER
PASSING THROUGH L.P. HEATER AND
ECONOMIZER, SO THAT HIGH PRESSURE STEAM
IN THE CYLINDER CAN BE CREATED.
 NO. OF CEP ARE USED – 3.
MOTOR PUMP
CEP
CEP SPECIFICATIONS
MOTOR TYPE SQUIRREL
CAGE
CONNECTION DELTA
RATED OUTPUT 110 KW
RATED VOLTAGE 415V +/- 10%
FREQUENCY 50Hz +/- 5%
SPEED 1480 rpm
CURRENT 193 A
P.F.(COSF) 0.84
EFFICIENCY 94.6%
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS F
IP 55
DUTY S1
WEIGHT 885 Kg
CCWP
 CCWP – CLOSE COOLING WATER PUMP.
 IT TRANSFER HEAT REJECTED FROM
REACTOR AUXILIARY EQUIPMENT
AND COMPONENTS OF POWER
CONVERSION SYSTEM TO THE ACCP.
 IT PROVIDE COOLING WATER THE
REACTOR ,AUXILIARY AND POWER
CONVERSION EQUIPMENT DURING ALL
MODES OF NORMAL OPERATION.
 NO. OF CCWP ARE USED – 2.
MOTOR
PUMP
CCWP
CCWP SPECIFICATIONS
TYPE EHX225SMB2
MOTOR TYPE SQUIRREL CAGE
CONNECTION DELTA
RATED OUTPUT 45 KW / 60 HP
RATED VOLTAGE 415 +/- 10% V
FREQUENCY 50 +/- 5% Hz
SPEED 2955 rpm
CURRENT 78 A
P.F.(COSF) 0.81-0.89
EFFICIENCY 93%-94%
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS F
IP 55
DUTY S1
RATED TORQUE 145 Nm
WEIGHT 310 Kg
ACWP
 ACWP – AUXILIARY COOLING WATER PUMP.
 IT PROVIDES A CONTINUOUS SUPPLY OF
COOLING WATER FOR REMOVING HEAT
REJECTED BY THE CCWP.
 THE WASTE HEAT IS TRANSPORTED BY ACCP
TO THE CONDENSER COOING WATER OUTLET
BLOCK, WHERE THE HOT SERVICE WATER IS
COMBINED WITH HOT WATER.
 NO. OF ACWP ARE USED – 2.
MOTOR
PUMP
ACWP
ACWP SPECIFICATIONS
TYPE EHXF250MB4
MOTOR TYPE SQUIRREL CAGE
CONNECTION DELTA
RATED OUTPUT 55 KW/ 75 HP
RATED VOLTAGE 415V +/- 10%
FREQUENCY 50Hz +/- 5%
SPEED 1475 rpm
CURRENT 95.6 A
EFFICIENCY 94.2%
P.F.(COSF) 0.85
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS F
IP 55
DUTY S1
WEIGHT 435 Kg
VACUUM PUMP
 A VACUUM PUMP IS A DEVICE THAT REMOVES
GAS MOLECULES FROM A SEALED VOLUME IN
ORDER TO LEAVE BEHIND A PARTIAL VACUUM.
 IT COLLECT THE WASTE STEAM REMAINING AT
LAST.
 NO. OF VACUUM PUMP ARE USED – 2.
MOTOR
PUMP
VACUUME PUMP
VACCUME PUMP SPECIFICATIONS
V Hz A KW COSF NOR. EFFI. IE-CL SPEED(rpm)
415 50 96 55 0.86 93.1% IE-2 985
480 60 99 66 0.86 93% IE-1 1185
480 60 83 55 0.85 93.6% IE-2 1188
CONNECTION DELTA
DUTY S1
SPACE HEATER 230V
AMBIENT TEMP. -20C - 40 C
IP 65
IM B3
WEIGHT 510 Kg
VIBRATION CLASS A
INSULATION CLASS F
IC 411
MOP
 MOP – MAIN OIL PUMP.
 IT IS THE ONE THAT DELIVERS ALL THE OIL
REQUIREMENTS FOR THE TURBINE-GENERATOR
AT HIGH PRESSURE DURING NORMAL
OPERATION.
 IT IS DIRECT-DRIVEN FROM THE TURBINE
SHAFT.
PUMP
MOTOR
MOP
MOP SPECIFICATIONS
TYPE EHX225SMC4
MOTOR TYPE SQUIRREL CAGE
CONNECTION DELTA
RATED OUTPUT 45 KW/60 HP
RATED VOLTAGE 415V +/- 10%
FREQUENCY 50 Hz +/- 5%
SPEED 1470 rpm
CURRENT 78.4 A
P.F.(COSF) 0.85
EFFICIENCY 93.9%
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS F
IP 55
IM B3
RATED TORQUE 292 Nm
DUTY S1
WEIGHT 340 Kg
AOP
 AOP – AUXILIARY OIL PUMP.
 IT OPERATES DURING STARTUP AND SHUT
DOWN WHEN THE TURBINE
SHAFT IS NOT ROTATING FAST ENOUGH
FOR THE MAIN OIL PUMP TO DELIVER THE
REQUIRED PRESSURE AND FLOW.
 IT ACTS AS A STANDBY LUBE OIL PUMP IN THE
EVENT OF MAIN OIL PUMP FAILURE.
PUMP
MOTOR
AOP
AOP SPECIFICATIONS
TYPE EHX225SMC4
MOTOR TYPE SQUIRREL CAGE
CONNECTION DELTA
RATED OUTPUT 45 KW/60 HP
RATED VOLTAGE 415V +/- 10%
FREQUENCY 50 Hz +/- 5%
SPEED 1470 rpm
CURRENT 78.4 A
P.F.(COSF) 0.85
EFFICIENCY 93.9%
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS F
IP 55
IM B3
RATED TORQUE 292 Nm
DUTY S1
WEIGHT 340 Kg
EOP
 EOP – EMERGENCY OIL PUMP.
 IT PROVIDE OIL TO THE SHAFT AND
BEARING OF THE TURBINE IF MOP AND AOP
FAILS.
 THE EMERGENCY LUBE OIL PUMP GENERALLY
PUTS OUT INSUFFICIENT PRESSURE TO KEEP
THE EMERGENCY STOP VALVES AND
GOVERNOR STEAM VALVES OPEN.
DC SHUNT
MOTOR
PUMP
EOP
EOP SPECIFICATIONS
TYPE SHUNT
RATED OUTPUT 18.5 KW
ARMATURE VOLTAGE 110V DC
ARMATURE CURRENT 192 A
SPEED 1500 rpm
FIELD VOLTAGE 110 V
FIELD CURRENT 4.5 A DC
RATED TORQUE 12 KgF.m
DUTY S1
EFFICIENCY 86%
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS H
COOLING 7C0041
IM B3
WEIGHT 690 Kg
IP 55
JOP
 JOP – JACKING OIL PUMP.
 THISPUMP IS GENERALLY USED ONLY FOR
LARGE TURBINE-GENERATORS, AND THEN
ONLY DURING THE PERIOD WHEN THE SHAFT IS
ROTATED BY THE TURNING GEAR.
 IT PROVIDE THE FREE MOVEMENT TO THE
SHAFT AT STARTING.
MOTOR
PUMP
JOP
JOP SPECIFICATIONS
TYPE EHX160MLE4
MOTOR TYPE SQUIRREL
CAGE
CONNECTION DELTA
RATED OUTPUT 15 KW/20 HP
RATED VOLTAGE 415V +/- 10%
FREQUENCY 50Hz +/- 5%
SPEED 1455 rpm
CURRENT 27.1 A
P.F.(COSF) 0.84
EFFICIENCY 91.8%
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS F
DUTY S1
IP 55
IM B3
WEIGHT 165 Kg
RATED TORQUE 98 Nm
CT FAN
 IT IS A HEAT REJECTION DEVICE WHICH
EXTRACT WASTE HEAT TO THE
ATMOSPHERE THROUGH COOLING OF
WATER STREAM TO A LOWER TEMP.
 NO. OF CT FANS ARE USED – 3.
COOLING TOWER MOTOR
CT FAN
CT FAN SPECIFICATIONS
FRAME SIZE D280M
CONNECTION DELTA
RATED OUTPUT 75KW / 15KW
RATED VOLTAGE 415V +/- 10%
FREQUENCY 50Hz +/- 5%
SPEED 1480 / 780 rpm
CURRENT 132A /50.1A
P.F.(COSF) 0.85 / 0.49
EFFICIENCY 93% / 85%
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS F
TORQUE 49.24/19.83 KgFm
IM B3
DUTY S1
WEIGHT 758 Kg
HTF SEAL PUMP
 IT PROVIDES A LAYER OF OIL AT LOWER
POSITION OF HTF PUMP IN ORDER TO SEAL IT
FROM THE ENTRY OF ATMOSPHERIC AIR.
 IT ALSO PROVIDES COOLING TO THE BEARING
OF THE HTF PUMP DURING OPERATION.
 NO. OF HTF SEAL PUMP ARE USED – 4.
MOTOR
PUMP
HTF SEAL PUMP
HTF SEAL PUMP SPECIFICATIONS
TYPE MD10L432
MOTOR TYPE SQUITTEL CAGE
CONNECTION DELTA
RATED OUTPUT 2.20-3.00 KW
RATED VOLTAGE 415V +/- 10%
FREQUENCY 50Hz +/- 5%
SPEED 1420 rpm
CURRENT 4.550 A
P.F.(COSF) 0.82
EFFICIENCY 82.0%
AMBIENT TEMP. -20C - 45C
PHASES 3
INSULATION CLASS F
IP 50
DUTY S1
IC 411
WEIGHT 60 Kg
GSC
 GSC – GLAND STEAM CONDENSOR.
 ELIMINATE STEAM VAPORS IN THE VICINITY OF THE
MACHINE WHICH ARE USUALLY TOXIC DUE TO
ADDITIVES FOUND IN THE MACHINE.
 REDUCE HUMIDITY IN THE VICINITY OF THE
MACHINE RESULTING IN SAFER AND MORE
RELIABLE OPERATION OF ALL ELECTRIC DEVICES
INSTALLED IN THE AREA.
 ELIMINATE LUBE OIL CONTAMINATION FROM THE
MIGRATION OF WATER CONDENSATE INTO THE SEAL
OIL THEREBY EXTENDING THE PERIOD BETWEEN
OIL CHANGES.
 NO. OF GSC USED – 2.
MOTOR
PUMP
GSC
GSC SPECIFICATIONS
TYPE M2BA100LB2
MOTOR TYPE SQUIRREL
CAGE
CONNECTION DELTA
RATED OUTPUT 3.7 KW/5 HP
RATED VOLTAGE 415V +/- 10%
FREQUENCY 50Hz +/- 5%
SPEED 2855 rpm
CURRENT 6.7 A
EFFICIENCY 84.7%
P.F.(COSF) 0.91
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS F
IP 65
DUTY S1
WEIGHT 36 Kg
TURNING GEAR
 DURING TURBINE STARTUP, THE TURBINE
GEAR IS USED IN ORDER TO ROLL OUT
SHAFT DEFORMATION BEFORE RUNUP BIGINS
AND TO ENABLE UNIFOM PREWARMING OF
TURBINE GENERATOR.
 TO ACHIEVE THIS OBJECTIVE TURNING GEAR
IS STARTED EARLY DURING UNIT STARTUP.
MOTOR
TURNING GEAR
TURNING GEAR SPECIFICATIONS
MOTOR TYPE SQUIRREL
CAGE
CONNECTION DELTA
RATED OUTPUT 15 KW
RATED VOLTAGE 415V +/- 10%
FREQUENCY 50Hz +/- 5%
SPEED 1455rpm
P.F.(COSF) 0.82
CURRENT 27.9 A
EFFICIENCY 86%
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS F
IP 55
OIL MIST FAN
 IT REMOVES THE MOISTURE AND FUMES
PRESENT IN THE OIL.
 THE OIL MIST FILTER UNIT IS PROVIDED WITH A
DEMISTER SO THAT OIL DROPS IN THE AIR-
STREAM ARE COLLECTED AND CARRIED BACK
TO THE TANK.
 IT PROTECT THE MOT(MAIN OIL TANK) FROM
CORROSION AND SLUDGE.
PUMP MOTOR
OIL MIST FAN
OIL MIST FAN SPECIFICATIONS
FRAME M3BA90L2
CONNECTION STAR
RATED OUTPUT 1.5 KW/2 HP
RATED VOLTAGE 415V +/- 10%
FREQUENCY 50Hz +/- 5%
SPEED 2890 rpm
CURRENT 2.8 A
P.F.(COSF) 0.89
EFFICIENCY 85.8%
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS F
IP 55
IM B3
DUTY S1
RATED TORQUE 5 Nm
WEIGHT 24 Kg
LUBRICANT OIL PURIFIER
 IT REMOVES GAS, PARTICULATE AND
SIGNIFICANT AMOUNT OF FREE WATER
CONTAMINATION.
 IT REMOVE METAL FRAGMENTS WHICH COME
FROM WEAR PRODUCTS IN THE BEARINGS AND
LUBE OIL PUMPS.
 IT USES HIGH EFFICIENCY VACCUME
DEHYDRATION PROCESS.
MOTOR
PUMP
LUBRICANT OIL PURIFIER
LUBRICANT OIL PURIFIER SPECIFICATIONS
FRAME CD90L
MOTOR TYPE SQUIRREL CAGE
CONNECTION STAR
RATED OUTPUT 2.20 KW
RATED VOLTAGE 415V +/- 10%
FREQUENCY 50Hz +/- 5%
SPEED 2850 rpm
CURRENT 4.24 A
EFFICIENCY 84%
P.F.(COSF) 0.85
AMBIENT TEMP. 45C
PHASES 3
INSULATION CLASS F
IP 55
IC 411
SEAL WATER PUMP
 IT PROVIDES A LAYER OF WATER TO THE
LOWER POSITION OF BOILER IN ORDER TO
SEAL IT FROM THE ENTERY OF ATMOSPHERIC
AIR.
 IT ALSO PROVIDES COOLING TO THE BEARING
OF THE COOLING WATER PUMP DURING
OPERATION.
MOTOR
PUMP
SEAL WATER PUMP
SEAL WATER PUMP SPECIFICATIONS
TYPE MD10L432
MOTOR TYPE SQUIRREL CAGE
CONNECTION DELTA
RATED OUTPUT 2.20 KW / 3 HP
RATED VOLTAGE 373/456 V
FREQUENCY 50Hz +/- 5%
SPEED 1420 rpm
CURRENT 4.550 A
EFFICIENCY 82%
P.F.(COSF) 0.82
AMBIENT TEMP. -20C - 40C
PHASES 3
INSULATION
CLASS
F/B
IP 55
IM V1
WEIGHT 12 Kg
CONTROL OIL PUMP
 IT CONTROL THE ON/OFF OPERATION OF
CONTROL/GOVERNOR VALVE OF THE TURBINE.
 NO.OF CONTROL OIL PUMP USED – 2.
MOTOR
CONTROL OIL PUMP
CONTROL OIL PUMP SPECIFICATIONS
MOTOR TYPE SQUIRREL CAGE
CONNECTION DELTA
RATED OUTPUT 11 KW
RATED VOLTAGE 415V +/- 10%
FREQUENCY 50Hz +/- 5%
SPEED 1460 rpm
CURRENT 20.2 A
P.F.(COSF) 0.85
EFFICIENCY 89.8%
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS F
IP 55
IM B35
IC 411
WEIGHT 93 Kg
CONTROL OIL PUMP OFFLINE
 IT CONTROL THE TEMPERATURE OF THE OIL
USED IN TURBINE.
 IT IS ALSO USED FOR PROTECTION PURPOSE OF
TURBINE SYSTEM.
 NO.OF COP OFFLINE – 2.
MOTOR
PUMP
CONTROL OIL PUMP OFFLINE
CONTROL OIL PUMP OFFLINE
SPECIFICATIONS
MOTOR TYPE SQUIRREL CAGE
CONNECTION DELTA
RATED OUTPUT 5 KW
RATED VOLTAGE 415V +/- 10%
FREQUENCY 50Hz +/- 5%
SPEED 1440 rpm
CURRENT 3.25 A
EFFICIENCY 82.8%
P.F.(COSF) 0.77
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS F
IP 55
IM B5
AIR COMPRESSOR
 IT IS A DEVICE THAT CONVERTS POWER
KINETIC ENERGY BY COMPRESSING OR
PRESSURIZING AIR.
 IT SUPPLIES HIGH PRESSURE CLEAN
AIR TO FILL GAS CYLINDER.
 NO. OF AIR COMPRESSOR ARE USED – 2.
AIR COMPRESSOR
AIR COMPRESSOR SPECIFICATIONS
MACHINE MODEL SIERRA SM37
MAX. ALLOWABLE WORKING PRESSURE 8.5 bar
INPUT SHAFT POWER 37 KW
RATED VOLTAGE 400 V
FREQUENCY 50 Hz
MOTOR ENGINE SPEED 2965 rpm
CURRENT 72 A
GROSS MASS 2387 Kg
WASTE WATER PUMP
 IT IS USED FOR PUMPING THE WASTE WATER
FROM PLANT TO THE NEARER SEWAGE POND.
 WASTE WATER IS SUPPLIED TO THE SEWAGE
POND AFTER THE WASTE WATER TREATMET
PROCESS.
 NO. OF WASTE WATER PUMP ARE USED – 2.
WASTE WATER PUMP(MOTOR)
SPECIFICATIONS
FRAME KI90L
MOTOR TYPE SQUIRREL CAGE
RATED OUTPUT 1.5 KW
RATED VOLTAGE 6300V +/- 10%
FREQUENCY 50Hz +/- 5%
SPEED 1410 rpm
CURRENT 3.4 A
RATED TORQUE 1.04 KgF.m
P.F.(COSF) 0.78
EFFICIENCY 81%
POLE 4
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS F
IP 55
IM V1
IC 411
WEIGHT 26 Kg
RAW WATER PUMP
 RAW WATER PUMPS IS PROVIDED TO DELIVER
WATER FROM THE ONSITE STORAGE POND TO
THE RAW WATER TREATMENT SYSTEM.
 RAW WATER PUMPS IS HOUSED IN A PUMPING
STRUCTURE LOCATED AT THE RAW WATER
STORAGE POND.
 NO. OF WASTE WATER PUMP ARE USED – 2.
RW MAKEUP SPECIFICATIONS
TYPE EHX160MLE2
MOTOR TYPE SQUIRREL CAGE
CONNECTION STAR
RATED OUTPUT 18.5 KW
RATED VOLTAGE 415V +/- 10%
FREQUENCY 50Hz +/- 5%
SPEED 2920 rpm
CURRENT 31.5 A
P.F.(COSF) 0.89
EFFICIENCY 91.8%
RATED TORQUE 60.5 Nm
AMBIENT TEMP. 50C
PHASES 3
INSULATION CLASS F
IP 55
DUTY S1
IC 141
WEIGHT 165 Kg
LOAD DISTRIBUTION FROM UAT
 THE HV MOTORS(HTF, BFP & CWP) ARE CONNECTED
TO UAT TRANSFORMER.
 THE TOTAL POWER DISTRIBUTED TO HT MOTORS IN
BOTH CASES ARE:
 IN NORMAL CONDITION – 5470 KW
 TOTAL LOAD CONNECTED – 7755 KW
LOAD DISTRIBUTION FROM SST
 THE LV MOTORS(CEP, CCWP, ACWP & VACUUM PUMP etc.) ARE
CONNECTED TO SST TRANSFORMERS.
 THERE ARE 4 SST TRANSFORMER - SST-1, SST-2, SST-3, SST-4.
 THE TOTAL LOAD CONNECTED TO EACH OF THE SST IN BOTH
CASE ARE:
 SST-1
 IN NORMAL CONDITION – 545.6 KW
 THE TOTAL LOAD CONNECTED – 848KW
LOAD DISTRIBUTION FROM SST
 SST-2
 IN NORMAL LOAD CONDITION – 364.2 KW
 TOTAL LOAD CONNECTED – 481.6 KW
 SST-4
 IN NORMAL LOAD CONDITION – 20 KW
 TOTAL LOAD CONNECTED – 40 KW
 SST-3 - ISOLATE
TOTAL LOAD DISTRIBUTION FROM ALL
TRANSFORMERS
 TOTAL LOAD AT HV MOTORS –
 IN NORMAL CONDITION – 5470 KW
 TOTAL LOAD CONNECTED – 7755 KW
 TOTAL LOAD AT LV MMOTORS –
 IN NORMAL CONDITION – 909.8 KW
 TOTAL LOAD CONNECTED – 1329.6 KW
 TOTAL LOAD –
 IN NORMAL CONDITION – 6399.8 KW
 TOTAL LOAD CONNECTED – 9124.6 KW
 LOAD DURING NON-GENERATING HOURS – 205.5 KW
Ggel power distribution

More Related Content

What's hot

BPSCL Vocational Training report
BPSCL Vocational Training report BPSCL Vocational Training report
BPSCL Vocational Training report Rahul Raj
 
Emergency Generator - Paralleling Switchgear Power Switching Control
Emergency Generator - Paralleling Switchgear Power Switching ControlEmergency Generator - Paralleling Switchgear Power Switching Control
Emergency Generator - Paralleling Switchgear Power Switching Controlmichaeljmack
 
Ramendra summer training presentation
Ramendra summer training presentationRamendra summer training presentation
Ramendra summer training presentationRamendra Dhiman
 
PRASHANT SEMINAR REPORT CONTENT TABLE NTPC ANTA
PRASHANT SEMINAR REPORT CONTENT TABLE NTPC ANTAPRASHANT SEMINAR REPORT CONTENT TABLE NTPC ANTA
PRASHANT SEMINAR REPORT CONTENT TABLE NTPC ANTAprashant shukla
 
Avdhehs kumar presention kstps kota
Avdhehs kumar presention kstps kotaAvdhehs kumar presention kstps kota
Avdhehs kumar presention kstps kotaAvdhesh kumar NIET
 
STUDY OF VARIOUS SYSTEMS IN 500MW THERMAL POWER PLANT
STUDY OF VARIOUS SYSTEMS IN 500MW THERMAL POWER PLANTSTUDY OF VARIOUS SYSTEMS IN 500MW THERMAL POWER PLANT
STUDY OF VARIOUS SYSTEMS IN 500MW THERMAL POWER PLANTRajashekar Gurrala
 
Ntpc ppt for single student persentation
Ntpc ppt for single student persentationNtpc ppt for single student persentation
Ntpc ppt for single student persentationVinit Kumar
 
Power plants in bangladesh
Power plants in bangladeshPower plants in bangladesh
Power plants in bangladeshImran Hossain
 
Effect of converter dc fault on the transient stability of a multi machine po...
Effect of converter dc fault on the transient stability of a multi machine po...Effect of converter dc fault on the transient stability of a multi machine po...
Effect of converter dc fault on the transient stability of a multi machine po...Indra S Wahyudi
 
power station in bangladesh
power station in bangladeshpower station in bangladesh
power station in bangladeshjubaraj baidya
 
Summer Training Report Ntpc barh (ajeet)
Summer Training Report Ntpc barh (ajeet)Summer Training Report Ntpc barh (ajeet)
Summer Training Report Ntpc barh (ajeet)Ajeet Chaurasia
 
Industrail training report by -Sashikant Tiwari
Industrail training report by -Sashikant TiwariIndustrail training report by -Sashikant Tiwari
Industrail training report by -Sashikant TiwariSashikant Tiwari
 

What's hot (20)

EVS 29 EV Regenerative Acceleration Demonstration Performance Test Data
EVS 29 EV Regenerative Acceleration Demonstration Performance Test DataEVS 29 EV Regenerative Acceleration Demonstration Performance Test Data
EVS 29 EV Regenerative Acceleration Demonstration Performance Test Data
 
BPSCL Vocational Training report
BPSCL Vocational Training report BPSCL Vocational Training report
BPSCL Vocational Training report
 
Emergency Generator - Paralleling Switchgear Power Switching Control
Emergency Generator - Paralleling Switchgear Power Switching ControlEmergency Generator - Paralleling Switchgear Power Switching Control
Emergency Generator - Paralleling Switchgear Power Switching Control
 
Shivesh ntpc ppt
Shivesh ntpc pptShivesh ntpc ppt
Shivesh ntpc ppt
 
V.T ppt
V.T pptV.T ppt
V.T ppt
 
Ramendra summer training presentation
Ramendra summer training presentationRamendra summer training presentation
Ramendra summer training presentation
 
PRASHANT SEMINAR REPORT CONTENT TABLE NTPC ANTA
PRASHANT SEMINAR REPORT CONTENT TABLE NTPC ANTAPRASHANT SEMINAR REPORT CONTENT TABLE NTPC ANTA
PRASHANT SEMINAR REPORT CONTENT TABLE NTPC ANTA
 
Ntpc barh (bstpp)
Ntpc barh (bstpp)Ntpc barh (bstpp)
Ntpc barh (bstpp)
 
Avdhehs kumar presention kstps kota
Avdhehs kumar presention kstps kotaAvdhehs kumar presention kstps kota
Avdhehs kumar presention kstps kota
 
STUDY OF VARIOUS SYSTEMS IN 500MW THERMAL POWER PLANT
STUDY OF VARIOUS SYSTEMS IN 500MW THERMAL POWER PLANTSTUDY OF VARIOUS SYSTEMS IN 500MW THERMAL POWER PLANT
STUDY OF VARIOUS SYSTEMS IN 500MW THERMAL POWER PLANT
 
Ntpc ppt for single student persentation
Ntpc ppt for single student persentationNtpc ppt for single student persentation
Ntpc ppt for single student persentation
 
Power plants in bangladesh
Power plants in bangladeshPower plants in bangladesh
Power plants in bangladesh
 
Effect of converter dc fault on the transient stability of a multi machine po...
Effect of converter dc fault on the transient stability of a multi machine po...Effect of converter dc fault on the transient stability of a multi machine po...
Effect of converter dc fault on the transient stability of a multi machine po...
 
power station in bangladesh
power station in bangladeshpower station in bangladesh
power station in bangladesh
 
236 rakhi
236 rakhi236 rakhi
236 rakhi
 
Summer Training Report Ntpc barh (ajeet)
Summer Training Report Ntpc barh (ajeet)Summer Training Report Ntpc barh (ajeet)
Summer Training Report Ntpc barh (ajeet)
 
NTPC BARH, BIHAR
NTPC BARH, BIHARNTPC BARH, BIHAR
NTPC BARH, BIHAR
 
Industrail training report by -Sashikant Tiwari
Industrail training report by -Sashikant TiwariIndustrail training report by -Sashikant Tiwari
Industrail training report by -Sashikant Tiwari
 
CESC LTD. TRAINING REPORT
CESC LTD. TRAINING REPORTCESC LTD. TRAINING REPORT
CESC LTD. TRAINING REPORT
 
Power factor
Power factorPower factor
Power factor
 

Similar to Ggel power distribution

Ht and lt scheme dc system
Ht and lt scheme dc systemHt and lt scheme dc system
Ht and lt scheme dc systemShashi Katiyar
 
ETAP - Transformer sizing using etap
ETAP - Transformer sizing using etapETAP - Transformer sizing using etap
ETAP - Transformer sizing using etapHimmelstern
 
ETAP - Transformer sizing using etap
ETAP - Transformer sizing using etapETAP - Transformer sizing using etap
ETAP - Transformer sizing using etapHimmelstern
 
NTPC Barh Training Report .pptx
NTPC Barh Training Report .pptxNTPC Barh Training Report .pptx
NTPC Barh Training Report .pptxRahulRaj598351
 
THERMAL POWER PLANT (COAL TO POWER)
THERMAL POWER PLANT (COAL TO POWER)THERMAL POWER PLANT (COAL TO POWER)
THERMAL POWER PLANT (COAL TO POWER)Baibhav Saha
 
Power Factor.ppt
Power Factor.pptPower Factor.ppt
Power Factor.pptVidya Sagar
 
Enertronic high voltage, power & automatism v01
Enertronic high voltage, power & automatism v01Enertronic high voltage, power & automatism v01
Enertronic high voltage, power & automatism v01Christian Moreau
 
Industrial Training Presentation
Industrial Training PresentationIndustrial Training Presentation
Industrial Training Presentationkumarmayursinha
 
BASICS+OF+ASM+WITH+VSD.ppt
BASICS+OF+ASM+WITH+VSD.pptBASICS+OF+ASM+WITH+VSD.ppt
BASICS+OF+ASM+WITH+VSD.pptKhairulBashar83
 
Transformer maintenance
Transformer maintenance Transformer maintenance
Transformer maintenance Molla Morshad
 

Similar to Ggel power distribution (20)

electrical.ppt
electrical.pptelectrical.ppt
electrical.ppt
 
ppt on kstps 2016
ppt on kstps 2016ppt on kstps 2016
ppt on kstps 2016
 
Ht and lt scheme dc system
Ht and lt scheme dc systemHt and lt scheme dc system
Ht and lt scheme dc system
 
Dev
DevDev
Dev
 
lift ppt
lift pptlift ppt
lift ppt
 
220 kv gss renwal ppt
220 kv gss renwal ppt220 kv gss renwal ppt
220 kv gss renwal ppt
 
ETAP - Transformer sizing using etap
ETAP - Transformer sizing using etapETAP - Transformer sizing using etap
ETAP - Transformer sizing using etap
 
ETAP - Transformer sizing using etap
ETAP - Transformer sizing using etapETAP - Transformer sizing using etap
ETAP - Transformer sizing using etap
 
J DJ
J DJJ DJ
J DJ
 
NTPC Barh Training Report .pptx
NTPC Barh Training Report .pptxNTPC Barh Training Report .pptx
NTPC Barh Training Report .pptx
 
THERMAL POWER PLANT (COAL TO POWER)
THERMAL POWER PLANT (COAL TO POWER)THERMAL POWER PLANT (COAL TO POWER)
THERMAL POWER PLANT (COAL TO POWER)
 
Power Factor.ppt
Power Factor.pptPower Factor.ppt
Power Factor.ppt
 
powerfactor.pdf
powerfactor.pdfpowerfactor.pdf
powerfactor.pdf
 
Enertronic high voltage, power & automatism v01
Enertronic high voltage, power & automatism v01Enertronic high voltage, power & automatism v01
Enertronic high voltage, power & automatism v01
 
Power Management in BMS
Power Management in BMSPower Management in BMS
Power Management in BMS
 
Industrial Training Presentation
Industrial Training PresentationIndustrial Training Presentation
Industrial Training Presentation
 
BASICS+OF+ASM+WITH+VSD.ppt
BASICS+OF+ASM+WITH+VSD.pptBASICS+OF+ASM+WITH+VSD.ppt
BASICS+OF+ASM+WITH+VSD.ppt
 
132 kV uppcl
132 kV uppcl132 kV uppcl
132 kV uppcl
 
Transformer maintenance
Transformer maintenance Transformer maintenance
Transformer maintenance
 
CESC PROJECT
CESC PROJECTCESC PROJECT
CESC PROJECT
 

Recently uploaded

VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesPrabhanshu Chaturvedi
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 

Recently uploaded (20)

VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 

Ggel power distribution

  • 1. GGEL 50MW SOLAR THERMAL POWER PLANT POWER DISTRIBUTION PREPARED BY: BANWARI LAL
  • 2. INTRODUCTION  GODAWARI GREEN ENERGY LIMITED (GGEL) IS A FLAGSHIP COMPANY OF THE HIRA GROUP IN THE RENEWABLE ENERGY SECTOR.  GGEL’S FOCUS AREA IS POWER GENERATION USING RENEWABLE SOURCES SUCH AS SOLAR ENERGY, GEOTHERMAL ENERGY, WIND ENERGY ETC.  THE COMPANY WAS INCORPORATED AS A 100% SUBSIDIARY OF THE GODAWARI POWER & ISPAT LTD IN THE YEAR 2009.
  • 3. VISION  TO BE THE MOST ADMIRED POWER GENERATION COMPANY DELIVERING SUPERIOR VALUE TO INVESTORS, CUSTOMERS, COMMUNITIES AND EMPLOYEES THROUGH INNOVATION AND LEADERSHIP IN OPERATION EXCELLENCE.
  • 4. MISSION  WE AIM TO GENERATE SUPERIOR RETURN FOR OUR INVESTORS BY BEING THE LEADING SOLAR THERMAL POWER GENERATING COMPANY IN INDIA WITHIN 2022 AND BY BEING THE FIRST COMPANY TO ACHIEVE GRID-PARITY IN SOLAR POWER IN INDIA.  WE COMMIT OURSELVES TO IMPROVING THE QUALITY OF LIFE OF COMMUNITIES WE INFLUENCE BY STRIKING A BALANCE BETWEEN PROFIT, PEOPLE AND PLANET.
  • 5. POWER DISTRIBUTION BLOCK DIAGRAM GEN. 70.5 MVA 10.5 KV GSU T/F 75 MVA 10.5/132 KV UAT 7.5 MVA 10.5/6.6 KV SST-1 2.5 MVA 10.5/0.440 KV SST-2 2.5 MVA 10.5/0.440 KV SST-3 1.5 MVA 6.6/0.440 KV SST-4 750 KVA 6.6/0.440 KV HV MOTORS 1.BFP-1/2/3 2.HTF PUMP-1/2/3/4 3.CWP-1/2/3 LV MOTORS 1. CEP 8. VACUUM PUMP 15. SEAL WATER PUMP 2. MOP 9. OIL MIST FAN 16. HTF SEAL PUMP 3. AOP 10. CONTROL OIL PUMP 17. LUBE OIL PURIFIER 4. EOP 11. AIR COMPRESSOR 18. CONTROL 5. JOP 12. CT FAN OFFLINE PUMP 6. CCWP 13. TURBINE GEAR 7. ACWP 14. GSC GEN. BREAKER UAT BREAKER BREAKER BREAKER HTF HEATER PUMP RW SUPPLY PUMP R Y B SWITCHIN G YARD
  • 6. POWER DISTRIBUTION TO THE TRANSFORMERS UAT GEN. SST-1 SST-2 POWER T/F 1. TURBINE IS NOT RUNNING.(GRID IS AVAILABLE) 2. TURBINE IS RUNNING.(GRID IS NOT AVAILABLE) SG SGPOWER T/F UAT SST-1 SST-2 GEN. 132KV 132KV 10.5KV 10.5KV
  • 7. BLOCK DIAGRAM LP TURBINE LP STEAM DIRECT CONNECTION INDIRECT CONNECTION HP STEAM ALTERNA TOR GEAR BOX HP TURBINE
  • 8. GENERATOR  IT IS A DEVICE THAT CONVERTS MECHANICAL ENERGY INTO ELECTRICAL ENERGY.  IT WORKS ON THE PRINCIPLE OF EMI(ELECTRO- MAGNETIC INDUCTION) OF FARADAY.  IT IS CONNECTED TO LP AND HP TURBINE DIRECT AND INDIRECT RESPECTIVELY.  HERE THE ELECTRICITY IS GENERATED AT 10.5KV.
  • 9. RATED POWER- 70.590MVA RATED VOLTAGE – 10500V+/- 10% V RATED CURRENT – 3881 A ACTIVE POWER -50 MW SPEED – 3000rpm
  • 10. GENERATOR SPECIFICATIONS MACHINE CODE SGEN5-100A-2P RATED VOLTAGE 10500V +/- 10% RATED POWER 70590 KVA PHASES 3 CONNECTION STAR FREQUENCY 50 Hz P.F.(COSF) 0.708 RATED CURRENT 3881 A EXCITATION SELF RATED SPEED 3000 rpm INSULATION CLASS F AMBIENT TEMP. 50C PHASE SEQUENCE U1 V1 W1 IP 54 IM 7216 ACTIVE POWER 50 MW TOTAL WEIGHT 116.800 Kg COOLING TYPE AIR
  • 11. TRANSFORMER – 75 MVA (10.5KV/132KV)  IT IS AN ELECTRICAL DEVICE THAT TRANSFER ELECTRICAL ENERGY FROM ONE SIDE TO ANOTHERSIDE WITHOUT CHANGE IN ITS FREQUENCY.  TRANSFORMER IS USED TO CONVERT 10.5KV INTO 132KV FOR TRANSMISSION TO GSS(GRID SUB-STATION).
  • 13. RATED OUTPUT 75 MVA RATED VOLTAGE 10.5KV/132KV RATED CURRENT 328.04/4123.93 A FREQUENCY 50Hz PHASES 3 CONNECTION HV-STAR LV-DELTA NO. OF TAP CHANGER 4 NO LOAD LOSS AT RATED VOLTAGE 34 KW LOAD LOSS AT RATED CURRENT 275 KW EFFICIENCY AT UPF 100% LOAD-99.58% 25% LOAD-99.73% AUXILARY LOSS 3 KW(max) INSULATION LEVEL HV WDG - 230/550 (KVrms/KVp) LV WDG - 28/110 (KVrms/KVp) TAP RATIO(N1/N2) 12.57 GSU TRANSFORMER ELECTRICAL SPECIFICATIONS
  • 14. REFERENCE STANDARD IS:2026 CORE & WDG MASS 38900Kg TANK & FITTING MASS 14900Kg OIL MASS 17200Kg TOTAL T/F MASS 71000Kg TRANSPORT MASS 66000Kg TOTAL OIL QUANTITY 20200 Liters OVERALL DIMENSIONS 6.754.205.90 m TRANSPORT DIMENSIONS 5.302.503.75 m GSU TRANSFORMER PHYSICAL SPECIFICATIONS TEMP. RISE OF OIL 60C TEMP. RISE OF WDG 65C AMBIENT TEMP. 50C TYPE OF COOLING ONAN/ONAF TANK PLATE THICKNESS COVER 12 mm BOTTOM 16 mm SIDE 8 mm
  • 15. SWITCHING YARD  THE APPLICATION OF SWITCHYARDS IS TO DELIVER THE GENERATED POWER FROM POWER PLANT AT DESIRED VOLTAGE LEVEL TO THE NEAREST GRID OR TRANSMISSION LINE.  THE SWITCHYARD IS PROVIDED WITH NECESSARY ISOLATORS, CIRCUIT BREAKERS, CURRENT TRANSFORMER, POTENTIAL TRANSFORMERS, SURGE ARRESTORS, WAVE TRAPS, PROTECTIVE RELAYS, PLCC ETC.  SWITCHYARD IS CONTROLLED FROM DCS WHICH WILL BE LOCATED IN POWER BLOCK CONTROL ROOM.
  • 16.
  • 17. ABBREVIATIONS  UAT – UNIT AUXILIARY TRANSFORMER  SST – STATION SERVICE TRANSFORMER  BFP – BOILER FEED PUMP  CCWP – CLOSE COOLING WATER PUMP  ACWP – AUXILIARY COOLING WATER PUMP  HTF – HEAT TRANSFER FLUID  JOP – JACKING OIL PUMP  GSC – GLAND STEAM CONDENSOR
  • 18. ABBREVIATIONS  MOP – MAIN OIL PUMP  AOP – AUXILIARY OIL PUMP  EOP – EMERGENCY OIL PUMP  CEP – CONDENSATE EXTRACTING PUMP  CT FAN – COOLING TOWER FAN  CWP – CIRCULATING WATER PUMP  MOG – MAGNETIC OIL GAUGE  PRV – PRESSURE RELEAVE VALVE
  • 20. UAT – 7.5KVA(10.5KV/6.6KV)  UAT – UNIT AUXILIARY T/F.  IT CONNECT THE GENERATOR DIRECTLY TO THE GENERATOR AUXILIARY LOAD VIA UAT BREAKER.  IT IS STEP DOWN T/F THAT CONVERTS 10.5KV INTO 6.6KV.  IT DELIVER THE POWER TO THE HIGH VOLTAGE MOTOR LIKE BFP , HTF AND CWP ETC.
  • 21. UAT CONNECTION UAT 7.5 MVA 10.5KV/6.6KV SST-3 1.5 MVA 6.6KV/0.440KV SST-4 750KVA 6.6KV/0.440KV BFP(3) 875 KW 6300V 96A 3071rpm HTFP(4) 900KW 6300V 101A 2970rpm CWP(3) 510KW 6300V 58A 986rpm RAW WATER PUMP SUPPLY HTF HEATER SPARE MOTOR FEEDER
  • 23. UAT SPECIFICATIONS  COOLING – ONAN/ONAF  RATING KVA – 7500/9375  RATED VOLTAGE – HV V -1O500 LV V -6600  FULL LOAD CURRENT – HV A -515.51 LV A -820.08  GTD TEMP RISE – OIL -50C WDG -55C  BASIC INSULATION LEVEL - HV - 110/40 LV - 95/38  FREQUENCY – 50Hz  PHASES - 3
  • 24. SST  SST – STATION SERVICE T/F.  IT CONNECT THE SYSTEM DIRECTLY TO THE GENERATOR AUXILIARY LOAD.  IT IS ALSO STEP DOWN T/F THAT CONVERTS 10.5KV INTO 0.440KV.  IT PROVIDE THE SUPPLY FOR LOW VOLTAGE MOTORS USED IN THE PLANT LIKE CEP , CCWP , MOP , AOP , EOP CWP ETC.  HERE 4 SST’S ARE USED SUCH AS SST-1 , SST-2 , SST-3 , SST-4.
  • 25. SST-1 CONNECTION TO LOADS SST-1 2.5 MVA 10.5/0.440 KV CONDENSAT E PUMP 1&3 220 KW 415 V 193 A 1488 rpm JOP 1&2 30 KW 415 V 27.1 A 1455 rpm CT FAN 1&3 150 KW 415 V 132 A 1482rpm VACUUM PUMP-1 55 KW 415 V 96 A CCWP 1&2 90 KW 415 V 78 A 2955 rpm AOP 2 45 KW 415 V 78.4 A 1470 rpm ACWP-1 55 KW 415 V 95.6 A 1475 rpm AUXILIARY LOAD 150 KW AIR COMPRESSOR -2 37 KW 400 V 2965 rpm COP 16 KW 415 V TOTAL LOAD = 848 KW
  • 26. SST-2 CONNECTION TO LOADS SST-2 2.5 MVA 10.5/0.440 KV CT FAN-2 75 KW 415 V 132 A 1482 rpm MOP 45 KW 415 V 78.4 A 1470 rpm AIR COMPRESSOR -1 37 KW 400 V 2965 rpm VACUUM PUMP-2 55 KW 415 V 96 A CONDENSAT E PUMP-2 110 KW 415 V 193 A 1488 rpm ACWP-2 55 KW 415 V 95.6 A 1475 rpm COP 16 KW AUXILIARY LOAD 88.6 KW TOTAL LOAD = 481.6 KW
  • 27. SST-4 CONNECTED LOAD SST-4 750KVA 6.6/0.440KV RAW WATER MAKEUP PUMP (2) 18.5KW 415V 31.5A 2929rpm WASTE WATER PUMP (2) 1.5KW 415V 3.4A 1410rpm TOTAL LOAD = 40 KW
  • 28. SST-1 CONNECTED LOADS 1. STREET LIGHT 2. JACKING OIL PUMP-2 3. SEAL WATER PUMP-1 4. COMDENSATE PUMP-1 5. WAREHOUSE BUILDING 6. OIL MIST FAN-1 7. ISOLATION T/F-1 8. CONDENSATE PUMP-3 9. HTF SEAL PUMP-1 10.CT FAN-1 11.HTF SEAL FAN-3 12.CT FAN-3 13.ISOLATION T/F-3 14.VENTILATION BACK 15.VENTILATION FRONT 16.VACUUM PUMP-1 17.ISOLATION T/F-5 18.BATTERY CHARGER-1 19.GLAND STEAM BLOWER—1 20.CCW-A 21.ETHERNET POWER SUPPLY 22.HVAC 23.ACWP-1 24.FCB-1 25.MCC 1-A INCOMMER 26.BUS COUPLER
  • 29. SST-1 CONNECTED LOAD 1.ELECTRONIC BUILDING PANNEL 2.SEAL WATER PUMP-2 3.220KVA UPS 4.HEAT TRACE T/F 5.TURNING GEAR. 6.CONTROL OFFLINE PUMP-2 7.CCWP-B 8.TURBINE BUILDING PANEL 9.JOP-1 10.ETHERNET POWER SUPPLY 11.CONTROL OIL PUMP-2 12.AOP-2 13.LUBE OIL TANK HEATER 14.GENERATOR SPACE HEATER 15.ADMIN BUILDING FEEDER 16.EXCITATION(AVR) PANNEL 17.HTF HEATER PUMP 18.BATTERY CHARGER-2 19.CONTROL OIL HEATER 20.AIR COMPRESSOR 21.DG INCOMMER
  • 30. SST-2 CONNECTED LOAD 1.MCC-1B 2.FCB-2 3.OIL MIST FAN-2 4.CT FAN-2 5.HTF SEAL PUMP-2 6.WTP-MCC 7.AIR COMPRESSOR-1 8.HTF SEAL PUMP-4 9.UPS BYPASS(220KVA) 10.ULLAGE PRIM. COND. FAN 11.MOP(AOP-1) 12.VACUUM PUMP-2 13.ULLAGE DISCHARGE PUMP 14.ISOLATION T/F-2 15.GLAND STEAM BLOWER-2 16.CONDENSATE PUMP-2 17.ISOLATING T/F-4 18.ULLAGE LOAD PUMP 19.ACWP-2 20.HOSTEL BUILDING LIGHT 21.ETHERNET POWER SUPPLY 22.ISOLATION T/F-6 23.CONTROL OIL PUMP-1 24.POWER BLOCK LIGHT PANNEL 25.CONTROL OFFLINE PUMP-1
  • 32. SST–1 SPECIFICATIONS  COOLING – ONAN/ONAF  RATING KVA – 2500/3125  RATED VOLTAGE – HV V -1O500 LV V - 440  FULL LOAD CURRENT – HV A -171.84 LV A -4100.38  GTD TEMP RISE – OIL -50C WDG -55C  BASIC INSULATION LEVEL - HV - 110/40 LV - -/3  FREQUENCY – 50Hz  PHASES - 3
  • 34. SST-2 SPECIFICATIONS  COOLING – ONAN/ONAF  RATING KVA – 2500/3125  RATED VOLTAGE – HV V -1O500 LV V - 440  FULL LOAD CURRENT – HV A -171.84 LV A -4100.38  GTD TEMP RISE – OIL -50C WDG -55C  BASIC INSULATION LEVEL - HV - 110/40 LV - -/3  FREQUENCY – 50Hz  PHASES - 3
  • 36. SST-3 SPECIFICATIONS  COOLING – ONAN/ONAF  RATING KVA – 1500/1725  RATED VOLTAGE – HV V -6600 LV V -440  FULL LOAD CURRENT – HV A -131.21/150.89 LV A -1968.24/2263.41  GTD TEMP RISE – OIL -50C WDG -55C  BASIC INSULATION LEVEL - HV - 110/40 LV - -/3  FREQUENCY – 50Hz  PHASES - 3
  • 37. SST 4 – 750KVA(6.6KV/0.440KV COOLING FAN HT TERMINAL BOX CONSERVATOR TANK RADIATOR
  • 38. SST-4 SPECIFICATIONS  COOLING – ONAN/ONAF  RATING KVA – 750/863  RATED VOLTAGE – HV V -6600 LV V -440  FULL LOAD CURRENT – HV A -65.61/75.50 LV A -984.12/1132.36  GTD TEMP RISE – OIL -50C WDG -55C  BASIC INSULATION LEVEL - HV - 60/20 LV - -/3  FREQUENCY – 50Hz  PHASES - 3
  • 39. BFP  BFP – BOILER FEED PUMP.  IT IS USED TO FEED WATER TO STEAM GENERATOR BOILER DRUM AT DESIRED PRESSURE AND TEMPERATURE.  IT EXTRACT WATER FROM DE-AERATOR AND FEED IT TO THE BOILER DRUM VIA H.P. HEATERS AND ECONOMIZER.  NO. OF BFP ARE USED – 3.
  • 41. BFP SPECIFICATIONS TYPE AMI400L2ABAFI MOTOR TYPE SQUIRREL CAGE CONNECTION STAR RATED OUTPUT 875 KW RATED VOLTAGE 6300V +/- 10% FREQUENCY 50Hz +/- 5% SPEED 3071 rpm CURRENT 96 A P.F.(COSF) 0.88 EFFICIENCY 95.3% RATED TORQUE 2797 Nm AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F IP 55 IM 1001 IC 611 WEIGHT 3660 Kg
  • 42. HTF PUMP  HTF PUMP – HEAT TRANSFER FLUID PUMP.  HTF SYSTEM'S MAIN FUNCTION IS TO TRANSMIT THE HEAT RECEIVED BY THE PARABOLIC TROUGH CONCENTRATORS TO THE WATER STEAM CYCLE, IN ORDER TO GENERATE STEAM THAT ACTIVATES THE TURBINE.  NO. OF HTF PUMP ARE USED – 4.
  • 44. HTF PUMP SPECIFICATIONS TYPE AMI400L2ABANI MOTOR TYPE SQUIRREL CAGE CONNECTION STAR RATED OUTPUT 900 KW RATED VOLTAGE 6300V +/- 10% FREQUENCY 50Hz +/- 5% SPEED 2970 rpm CURRENT 101 A P.F.(COSF) 0.85 EFFICIENCY 95.2% AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F IP 55 IM 1001 IC 611 TOTAL WEIGHT 3470 Kg DUTY S1
  • 45. CWP  CWP – COOLING WATER PUMP.  IT IS USED TO CIRCULATE COOLING WATER TO THE CONDENSER; SO THAT HIGH PRESSURE LEFT OUT STEAM IN THE L.P. CYLINDER CAN BE CONVERTED INTO WATER.  NO. OF CWP ARE USED – 3.
  • 47. CWP SPECIFICATIONS TYPE CODE AMI 400L6A VAI MOTOR TYPE SQUIRREL CAGE CONNECTION STAR RATED OUTPUT 510 KW RATED VOLTAGE 6300V +/- 10% FREQUENCY 50Hz +/- 5% SPEED 985 rpm CURRENT 60 A P.F.(COSF) 0.82 EFFICIENCY 93.7%-94.3% AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F IP 55 RATED TORQUE 4946 Nm IC 611 IM 4011 TOTAL WEIGHT 3160 Kg DUTY S1
  • 48. CEP  CEP – CONDENSATE EXTRACTING PUMP.  C.E.P. PUMP IS USED TO EXTRACT THE CONDENSATE WATER FROM THE HOT WELL AND SUPPLY TO THE DEAREATOR AFTER PASSING THROUGH L.P. HEATER AND ECONOMIZER, SO THAT HIGH PRESSURE STEAM IN THE CYLINDER CAN BE CREATED.  NO. OF CEP ARE USED – 3.
  • 50. CEP SPECIFICATIONS MOTOR TYPE SQUIRREL CAGE CONNECTION DELTA RATED OUTPUT 110 KW RATED VOLTAGE 415V +/- 10% FREQUENCY 50Hz +/- 5% SPEED 1480 rpm CURRENT 193 A P.F.(COSF) 0.84 EFFICIENCY 94.6% AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F IP 55 DUTY S1 WEIGHT 885 Kg
  • 51. CCWP  CCWP – CLOSE COOLING WATER PUMP.  IT TRANSFER HEAT REJECTED FROM REACTOR AUXILIARY EQUIPMENT AND COMPONENTS OF POWER CONVERSION SYSTEM TO THE ACCP.  IT PROVIDE COOLING WATER THE REACTOR ,AUXILIARY AND POWER CONVERSION EQUIPMENT DURING ALL MODES OF NORMAL OPERATION.  NO. OF CCWP ARE USED – 2.
  • 53. CCWP SPECIFICATIONS TYPE EHX225SMB2 MOTOR TYPE SQUIRREL CAGE CONNECTION DELTA RATED OUTPUT 45 KW / 60 HP RATED VOLTAGE 415 +/- 10% V FREQUENCY 50 +/- 5% Hz SPEED 2955 rpm CURRENT 78 A P.F.(COSF) 0.81-0.89 EFFICIENCY 93%-94% AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F IP 55 DUTY S1 RATED TORQUE 145 Nm WEIGHT 310 Kg
  • 54. ACWP  ACWP – AUXILIARY COOLING WATER PUMP.  IT PROVIDES A CONTINUOUS SUPPLY OF COOLING WATER FOR REMOVING HEAT REJECTED BY THE CCWP.  THE WASTE HEAT IS TRANSPORTED BY ACCP TO THE CONDENSER COOING WATER OUTLET BLOCK, WHERE THE HOT SERVICE WATER IS COMBINED WITH HOT WATER.  NO. OF ACWP ARE USED – 2.
  • 56. ACWP SPECIFICATIONS TYPE EHXF250MB4 MOTOR TYPE SQUIRREL CAGE CONNECTION DELTA RATED OUTPUT 55 KW/ 75 HP RATED VOLTAGE 415V +/- 10% FREQUENCY 50Hz +/- 5% SPEED 1475 rpm CURRENT 95.6 A EFFICIENCY 94.2% P.F.(COSF) 0.85 AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F IP 55 DUTY S1 WEIGHT 435 Kg
  • 57. VACUUM PUMP  A VACUUM PUMP IS A DEVICE THAT REMOVES GAS MOLECULES FROM A SEALED VOLUME IN ORDER TO LEAVE BEHIND A PARTIAL VACUUM.  IT COLLECT THE WASTE STEAM REMAINING AT LAST.  NO. OF VACUUM PUMP ARE USED – 2.
  • 59. VACCUME PUMP SPECIFICATIONS V Hz A KW COSF NOR. EFFI. IE-CL SPEED(rpm) 415 50 96 55 0.86 93.1% IE-2 985 480 60 99 66 0.86 93% IE-1 1185 480 60 83 55 0.85 93.6% IE-2 1188 CONNECTION DELTA DUTY S1 SPACE HEATER 230V AMBIENT TEMP. -20C - 40 C IP 65 IM B3 WEIGHT 510 Kg VIBRATION CLASS A INSULATION CLASS F IC 411
  • 60. MOP  MOP – MAIN OIL PUMP.  IT IS THE ONE THAT DELIVERS ALL THE OIL REQUIREMENTS FOR THE TURBINE-GENERATOR AT HIGH PRESSURE DURING NORMAL OPERATION.  IT IS DIRECT-DRIVEN FROM THE TURBINE SHAFT.
  • 62. MOP SPECIFICATIONS TYPE EHX225SMC4 MOTOR TYPE SQUIRREL CAGE CONNECTION DELTA RATED OUTPUT 45 KW/60 HP RATED VOLTAGE 415V +/- 10% FREQUENCY 50 Hz +/- 5% SPEED 1470 rpm CURRENT 78.4 A P.F.(COSF) 0.85 EFFICIENCY 93.9% AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F IP 55 IM B3 RATED TORQUE 292 Nm DUTY S1 WEIGHT 340 Kg
  • 63. AOP  AOP – AUXILIARY OIL PUMP.  IT OPERATES DURING STARTUP AND SHUT DOWN WHEN THE TURBINE SHAFT IS NOT ROTATING FAST ENOUGH FOR THE MAIN OIL PUMP TO DELIVER THE REQUIRED PRESSURE AND FLOW.  IT ACTS AS A STANDBY LUBE OIL PUMP IN THE EVENT OF MAIN OIL PUMP FAILURE.
  • 65. AOP SPECIFICATIONS TYPE EHX225SMC4 MOTOR TYPE SQUIRREL CAGE CONNECTION DELTA RATED OUTPUT 45 KW/60 HP RATED VOLTAGE 415V +/- 10% FREQUENCY 50 Hz +/- 5% SPEED 1470 rpm CURRENT 78.4 A P.F.(COSF) 0.85 EFFICIENCY 93.9% AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F IP 55 IM B3 RATED TORQUE 292 Nm DUTY S1 WEIGHT 340 Kg
  • 66. EOP  EOP – EMERGENCY OIL PUMP.  IT PROVIDE OIL TO THE SHAFT AND BEARING OF THE TURBINE IF MOP AND AOP FAILS.  THE EMERGENCY LUBE OIL PUMP GENERALLY PUTS OUT INSUFFICIENT PRESSURE TO KEEP THE EMERGENCY STOP VALVES AND GOVERNOR STEAM VALVES OPEN.
  • 68. EOP SPECIFICATIONS TYPE SHUNT RATED OUTPUT 18.5 KW ARMATURE VOLTAGE 110V DC ARMATURE CURRENT 192 A SPEED 1500 rpm FIELD VOLTAGE 110 V FIELD CURRENT 4.5 A DC RATED TORQUE 12 KgF.m DUTY S1 EFFICIENCY 86% AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS H COOLING 7C0041 IM B3 WEIGHT 690 Kg IP 55
  • 69. JOP  JOP – JACKING OIL PUMP.  THISPUMP IS GENERALLY USED ONLY FOR LARGE TURBINE-GENERATORS, AND THEN ONLY DURING THE PERIOD WHEN THE SHAFT IS ROTATED BY THE TURNING GEAR.  IT PROVIDE THE FREE MOVEMENT TO THE SHAFT AT STARTING.
  • 71. JOP SPECIFICATIONS TYPE EHX160MLE4 MOTOR TYPE SQUIRREL CAGE CONNECTION DELTA RATED OUTPUT 15 KW/20 HP RATED VOLTAGE 415V +/- 10% FREQUENCY 50Hz +/- 5% SPEED 1455 rpm CURRENT 27.1 A P.F.(COSF) 0.84 EFFICIENCY 91.8% AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F DUTY S1 IP 55 IM B3 WEIGHT 165 Kg RATED TORQUE 98 Nm
  • 72. CT FAN  IT IS A HEAT REJECTION DEVICE WHICH EXTRACT WASTE HEAT TO THE ATMOSPHERE THROUGH COOLING OF WATER STREAM TO A LOWER TEMP.  NO. OF CT FANS ARE USED – 3.
  • 74. CT FAN SPECIFICATIONS FRAME SIZE D280M CONNECTION DELTA RATED OUTPUT 75KW / 15KW RATED VOLTAGE 415V +/- 10% FREQUENCY 50Hz +/- 5% SPEED 1480 / 780 rpm CURRENT 132A /50.1A P.F.(COSF) 0.85 / 0.49 EFFICIENCY 93% / 85% AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F TORQUE 49.24/19.83 KgFm IM B3 DUTY S1 WEIGHT 758 Kg
  • 75. HTF SEAL PUMP  IT PROVIDES A LAYER OF OIL AT LOWER POSITION OF HTF PUMP IN ORDER TO SEAL IT FROM THE ENTRY OF ATMOSPHERIC AIR.  IT ALSO PROVIDES COOLING TO THE BEARING OF THE HTF PUMP DURING OPERATION.  NO. OF HTF SEAL PUMP ARE USED – 4.
  • 77. HTF SEAL PUMP SPECIFICATIONS TYPE MD10L432 MOTOR TYPE SQUITTEL CAGE CONNECTION DELTA RATED OUTPUT 2.20-3.00 KW RATED VOLTAGE 415V +/- 10% FREQUENCY 50Hz +/- 5% SPEED 1420 rpm CURRENT 4.550 A P.F.(COSF) 0.82 EFFICIENCY 82.0% AMBIENT TEMP. -20C - 45C PHASES 3 INSULATION CLASS F IP 50 DUTY S1 IC 411 WEIGHT 60 Kg
  • 78. GSC  GSC – GLAND STEAM CONDENSOR.  ELIMINATE STEAM VAPORS IN THE VICINITY OF THE MACHINE WHICH ARE USUALLY TOXIC DUE TO ADDITIVES FOUND IN THE MACHINE.  REDUCE HUMIDITY IN THE VICINITY OF THE MACHINE RESULTING IN SAFER AND MORE RELIABLE OPERATION OF ALL ELECTRIC DEVICES INSTALLED IN THE AREA.  ELIMINATE LUBE OIL CONTAMINATION FROM THE MIGRATION OF WATER CONDENSATE INTO THE SEAL OIL THEREBY EXTENDING THE PERIOD BETWEEN OIL CHANGES.  NO. OF GSC USED – 2.
  • 80. GSC SPECIFICATIONS TYPE M2BA100LB2 MOTOR TYPE SQUIRREL CAGE CONNECTION DELTA RATED OUTPUT 3.7 KW/5 HP RATED VOLTAGE 415V +/- 10% FREQUENCY 50Hz +/- 5% SPEED 2855 rpm CURRENT 6.7 A EFFICIENCY 84.7% P.F.(COSF) 0.91 AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F IP 65 DUTY S1 WEIGHT 36 Kg
  • 81. TURNING GEAR  DURING TURBINE STARTUP, THE TURBINE GEAR IS USED IN ORDER TO ROLL OUT SHAFT DEFORMATION BEFORE RUNUP BIGINS AND TO ENABLE UNIFOM PREWARMING OF TURBINE GENERATOR.  TO ACHIEVE THIS OBJECTIVE TURNING GEAR IS STARTED EARLY DURING UNIT STARTUP.
  • 83. TURNING GEAR SPECIFICATIONS MOTOR TYPE SQUIRREL CAGE CONNECTION DELTA RATED OUTPUT 15 KW RATED VOLTAGE 415V +/- 10% FREQUENCY 50Hz +/- 5% SPEED 1455rpm P.F.(COSF) 0.82 CURRENT 27.9 A EFFICIENCY 86% AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F IP 55
  • 84. OIL MIST FAN  IT REMOVES THE MOISTURE AND FUMES PRESENT IN THE OIL.  THE OIL MIST FILTER UNIT IS PROVIDED WITH A DEMISTER SO THAT OIL DROPS IN THE AIR- STREAM ARE COLLECTED AND CARRIED BACK TO THE TANK.  IT PROTECT THE MOT(MAIN OIL TANK) FROM CORROSION AND SLUDGE.
  • 86. OIL MIST FAN SPECIFICATIONS FRAME M3BA90L2 CONNECTION STAR RATED OUTPUT 1.5 KW/2 HP RATED VOLTAGE 415V +/- 10% FREQUENCY 50Hz +/- 5% SPEED 2890 rpm CURRENT 2.8 A P.F.(COSF) 0.89 EFFICIENCY 85.8% AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F IP 55 IM B3 DUTY S1 RATED TORQUE 5 Nm WEIGHT 24 Kg
  • 87. LUBRICANT OIL PURIFIER  IT REMOVES GAS, PARTICULATE AND SIGNIFICANT AMOUNT OF FREE WATER CONTAMINATION.  IT REMOVE METAL FRAGMENTS WHICH COME FROM WEAR PRODUCTS IN THE BEARINGS AND LUBE OIL PUMPS.  IT USES HIGH EFFICIENCY VACCUME DEHYDRATION PROCESS.
  • 89. LUBRICANT OIL PURIFIER SPECIFICATIONS FRAME CD90L MOTOR TYPE SQUIRREL CAGE CONNECTION STAR RATED OUTPUT 2.20 KW RATED VOLTAGE 415V +/- 10% FREQUENCY 50Hz +/- 5% SPEED 2850 rpm CURRENT 4.24 A EFFICIENCY 84% P.F.(COSF) 0.85 AMBIENT TEMP. 45C PHASES 3 INSULATION CLASS F IP 55 IC 411
  • 90. SEAL WATER PUMP  IT PROVIDES A LAYER OF WATER TO THE LOWER POSITION OF BOILER IN ORDER TO SEAL IT FROM THE ENTERY OF ATMOSPHERIC AIR.  IT ALSO PROVIDES COOLING TO THE BEARING OF THE COOLING WATER PUMP DURING OPERATION.
  • 92. SEAL WATER PUMP SPECIFICATIONS TYPE MD10L432 MOTOR TYPE SQUIRREL CAGE CONNECTION DELTA RATED OUTPUT 2.20 KW / 3 HP RATED VOLTAGE 373/456 V FREQUENCY 50Hz +/- 5% SPEED 1420 rpm CURRENT 4.550 A EFFICIENCY 82% P.F.(COSF) 0.82 AMBIENT TEMP. -20C - 40C PHASES 3 INSULATION CLASS F/B IP 55 IM V1 WEIGHT 12 Kg
  • 93. CONTROL OIL PUMP  IT CONTROL THE ON/OFF OPERATION OF CONTROL/GOVERNOR VALVE OF THE TURBINE.  NO.OF CONTROL OIL PUMP USED – 2.
  • 95. CONTROL OIL PUMP SPECIFICATIONS MOTOR TYPE SQUIRREL CAGE CONNECTION DELTA RATED OUTPUT 11 KW RATED VOLTAGE 415V +/- 10% FREQUENCY 50Hz +/- 5% SPEED 1460 rpm CURRENT 20.2 A P.F.(COSF) 0.85 EFFICIENCY 89.8% AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F IP 55 IM B35 IC 411 WEIGHT 93 Kg
  • 96. CONTROL OIL PUMP OFFLINE  IT CONTROL THE TEMPERATURE OF THE OIL USED IN TURBINE.  IT IS ALSO USED FOR PROTECTION PURPOSE OF TURBINE SYSTEM.  NO.OF COP OFFLINE – 2.
  • 98. CONTROL OIL PUMP OFFLINE SPECIFICATIONS MOTOR TYPE SQUIRREL CAGE CONNECTION DELTA RATED OUTPUT 5 KW RATED VOLTAGE 415V +/- 10% FREQUENCY 50Hz +/- 5% SPEED 1440 rpm CURRENT 3.25 A EFFICIENCY 82.8% P.F.(COSF) 0.77 AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F IP 55 IM B5
  • 99. AIR COMPRESSOR  IT IS A DEVICE THAT CONVERTS POWER KINETIC ENERGY BY COMPRESSING OR PRESSURIZING AIR.  IT SUPPLIES HIGH PRESSURE CLEAN AIR TO FILL GAS CYLINDER.  NO. OF AIR COMPRESSOR ARE USED – 2.
  • 101. AIR COMPRESSOR SPECIFICATIONS MACHINE MODEL SIERRA SM37 MAX. ALLOWABLE WORKING PRESSURE 8.5 bar INPUT SHAFT POWER 37 KW RATED VOLTAGE 400 V FREQUENCY 50 Hz MOTOR ENGINE SPEED 2965 rpm CURRENT 72 A GROSS MASS 2387 Kg
  • 102. WASTE WATER PUMP  IT IS USED FOR PUMPING THE WASTE WATER FROM PLANT TO THE NEARER SEWAGE POND.  WASTE WATER IS SUPPLIED TO THE SEWAGE POND AFTER THE WASTE WATER TREATMET PROCESS.  NO. OF WASTE WATER PUMP ARE USED – 2.
  • 103. WASTE WATER PUMP(MOTOR) SPECIFICATIONS FRAME KI90L MOTOR TYPE SQUIRREL CAGE RATED OUTPUT 1.5 KW RATED VOLTAGE 6300V +/- 10% FREQUENCY 50Hz +/- 5% SPEED 1410 rpm CURRENT 3.4 A RATED TORQUE 1.04 KgF.m P.F.(COSF) 0.78 EFFICIENCY 81% POLE 4 AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F IP 55 IM V1 IC 411 WEIGHT 26 Kg
  • 104. RAW WATER PUMP  RAW WATER PUMPS IS PROVIDED TO DELIVER WATER FROM THE ONSITE STORAGE POND TO THE RAW WATER TREATMENT SYSTEM.  RAW WATER PUMPS IS HOUSED IN A PUMPING STRUCTURE LOCATED AT THE RAW WATER STORAGE POND.  NO. OF WASTE WATER PUMP ARE USED – 2.
  • 105. RW MAKEUP SPECIFICATIONS TYPE EHX160MLE2 MOTOR TYPE SQUIRREL CAGE CONNECTION STAR RATED OUTPUT 18.5 KW RATED VOLTAGE 415V +/- 10% FREQUENCY 50Hz +/- 5% SPEED 2920 rpm CURRENT 31.5 A P.F.(COSF) 0.89 EFFICIENCY 91.8% RATED TORQUE 60.5 Nm AMBIENT TEMP. 50C PHASES 3 INSULATION CLASS F IP 55 DUTY S1 IC 141 WEIGHT 165 Kg
  • 106. LOAD DISTRIBUTION FROM UAT  THE HV MOTORS(HTF, BFP & CWP) ARE CONNECTED TO UAT TRANSFORMER.  THE TOTAL POWER DISTRIBUTED TO HT MOTORS IN BOTH CASES ARE:  IN NORMAL CONDITION – 5470 KW  TOTAL LOAD CONNECTED – 7755 KW
  • 107. LOAD DISTRIBUTION FROM SST  THE LV MOTORS(CEP, CCWP, ACWP & VACUUM PUMP etc.) ARE CONNECTED TO SST TRANSFORMERS.  THERE ARE 4 SST TRANSFORMER - SST-1, SST-2, SST-3, SST-4.  THE TOTAL LOAD CONNECTED TO EACH OF THE SST IN BOTH CASE ARE:  SST-1  IN NORMAL CONDITION – 545.6 KW  THE TOTAL LOAD CONNECTED – 848KW
  • 108. LOAD DISTRIBUTION FROM SST  SST-2  IN NORMAL LOAD CONDITION – 364.2 KW  TOTAL LOAD CONNECTED – 481.6 KW  SST-4  IN NORMAL LOAD CONDITION – 20 KW  TOTAL LOAD CONNECTED – 40 KW  SST-3 - ISOLATE
  • 109. TOTAL LOAD DISTRIBUTION FROM ALL TRANSFORMERS  TOTAL LOAD AT HV MOTORS –  IN NORMAL CONDITION – 5470 KW  TOTAL LOAD CONNECTED – 7755 KW  TOTAL LOAD AT LV MMOTORS –  IN NORMAL CONDITION – 909.8 KW  TOTAL LOAD CONNECTED – 1329.6 KW  TOTAL LOAD –  IN NORMAL CONDITION – 6399.8 KW  TOTAL LOAD CONNECTED – 9124.6 KW  LOAD DURING NON-GENERATING HOURS – 205.5 KW