Electrical Power Supply System
The conveyance of electric power
from a power station to consumer,s
premises is known as electrical
Power supply system.
An electric supply system consists of three principal components .
1-Power Station
2-Transmission lines
3-Distribution
Power factor
The cosine of angle between voltage
and current in ac circuit is known as
power factor.
Power factor (Cos )= KW/KVA
Electrical Power
1. Active Power (kw = kva cos ( 3 V I Cos )
2. Reactive Power (kvar = kva sin
3. Apparent Power (kva = (kw2+kvar2)
KVA
KW
KVAR
Types Of Loads
1-Incandescent Lamp 0.98-1.0
2-Flourescent Lamp 0.6-0.8
3-Neon Lamp used for advertisement 0.4-0.5
4-Arc lamps used in cienema 0.3-0.7
5-Fans 0.5-0.8
6-Induction Heaters 0.85
7-Resistance Furnaces 0.6-0.9
8-Arc Furnaces 0.85
9-Induction Furnaces 0.6
10-Arc welders 0.3-0.4
11-Resistances Welders 0.65
12-Induction Motors 0.5-0.85
13-Fractional h.p.motors 0.4-0.75
Effect of low Power Factor
Heat = I*2 R T
I ά to 1/ cosø
H ά (1/ cosø)*2
A low P.F. would mean increased heat losses.
Causes of Low Power factor
1.Induction Motors
2.Arc Lamps, electrical discharge Lamps
3.Industrial Heating furnace at low lagging
power factor
4.From power system.
Power factor Improvement
Equipment
1.Static capacitor
Advantage-
1.They have low losses
2.They require little maintenance as there are no rotating parts
3.They can be easily installed as they are light and require no foundation
4.They can work under ordinary atmospheric conditions
Disadvantages
1.They have short services life ranging from 8 to 10 years.
2.They are easily damaged if the voltage exceeds the rated value.
3. Once the capacitors are damaged, there repair is uneconomical.
Static Capacitor
Asynchronous motor takes a leading current when over excited and
,therefore,they acts as a capacitor.An overexcited synchronous motor running
on no load is known as synchronous condensor.
Advantage-
1.By varying the field excitation ,the magnitude of current drawn by
motor can be changed by any amount.this helps in achieving step less
control of power factor.
2.The motor winding have high thermal stability to short circuit currents
3.The faults can be removed easily
Disadvantages
1.There are considerable losses in the motor.
2.The maintenance cost is high.
3.It produces noise .
4.Except in sizes above 500kva ,the cost is greater than that of static
capacitors of the same ratings.
5.As a synchronous motor has no self starting torque,therefore,an
auxiliary equipment has to be provided for this purpose
Synchronus Condensor
Synchronous Condenser
Phase advancer is a simple AC exciter which is connected on the main shaft of the
motor and operates with the motor’s rotor circuit for power factor improvement. Phase
advancer is used to improve the power factor of induction motor in industries.
As the stator windings of induction motor takes lagging current 90° out of phase with
Voltage, therefore the power factor of induction motor is low. If the exciting ampere-
turns are excited by external AC source, then there would be no effect of exciting
current on stator windings. Therefore, the power factor of induction motor will be
improved. This process is done by Phase advancer.
Advantages:
1-Lagging kVAR (Reactive component of Power or reactive power) drawn by the motor
is sufficiently reduced because the exciting ampere turns are supplied at slip frequency
(fs).
2-The phase advancer can be easily used where the use of synchronous motors is
Unacceptable
Disadvantage:
1-Using Phase advancer is not economical for motors below 200 H.P. (About 150 KW)
Phase advancer
Phase Advancer
Reduction in
Transformer Rating
Reduction in KVAR
Demand
Advantages of P.F
Correction
Reduction in KVA
Demand
Reduction in Line
Current
Reduction in Line
loss
Reduction in
Cable / Bus-bar
size
Reduction in
Switchgear
Rating
REDUCTION IN KVA DEMAND
LOAD - 900 KW
EXISTING P.F. (COS - 0.6
DESIRED P.F. (COS ) - 0.92
KW
Ø.
KVA 1 = 900 / 0.6 = 1500
KVA2 = 900 / 0.92 = 978
Ø 1)
Ø2
kW
kVA
COS =
KVA =
Ø.
kW
cosØ.
Reduction in KVA
1500 - 978 = 522
REDUCTION IN KVAR
DEMAND
kVA =
KVAR1 =
=
KVAR 2 =
KW2 + KVAR2
KVA1
2 - KW2
1500 2 - 900 2 = 1200
978 2 - 900 2 = 382
KW - 900
KVA1 - 1500
KVA2 - 978
KW
Ø.
KVAR
Reduction in KVAR
1200 - 382 = 818
REDUCTION IN LINE
CURRENT
KVA =
I =
I1 =
=
I2 =
=
3 V I
1000
KVA x 1000
3 x 415
1500 x 1000
3 x 415
2087 Amp
978 x 1000
3 x 415
1361 Amp
KVA1 - 1500
KVA2 - 978
Reduction in Current
2087 - 1361 = 726
0
10
20
30
40
50
60
70
80
90
100
1 0.9 0.8 0.7 0.6 0.5
% Rise in Current w.r.t.
decrease in Power Factor
% Rise in I n
P.F.
% of saving in losses = 1-
Cos
Cos
Ø1
Ø2
2
1-
0.6
0.92
2
X 100
X 100
= 57.46
Cable Losses
0
10
20
30
40
50
60
70
80
0.5 0.6 0.7 0.8 0.9 1
Saving in Cable Losses
P.F.
1.0
0.95
0.9
0.85
0.8
Initial P.F.
Saving in losses = Wr x K1
Wr = Full load copper loss of the transformer
connected load in Kw
k1
KVA rating of the transformer
1
CosØ1
1
CosØ2
-
Transformer Losses
Graph Transformer Losses
Transformer Losses
0
5000
10000
15000
20000
25000
30000
35000
40000
0 500 1000 1500 2000 2500 3000 3500
Transformer KVA
cu
Loss
Copper losses
Transformer Losses
Saving in losses = Wr x K1
1
CosØ1
1
CosØ2
-
=
900
1500
1 1
0.6 0.92
= 6260 Watts
Annual Saving = 6260 x 300 x 12
1000
= 22536 KWH
18000 x x
Power Savings
KVA X'MER CURRENT ACB
RAT I NG
1500
978
1500
1000
2086
1360
2500
0
500
1000
1500
2000
2500
3000
KVA X'MER CURRENT ACB
AT 0.6 PF AT 0.92 PF
1600
What are the effects of harmonics on motor operation
and performance?
Harmonics increase motor losses, and can adversely affect the operation of
sensitive auxiliary equipment. The non-sinusoidal supply results in
harmonic currents in the stator which increases the total current drawn. In
addition, the rotor resistance (or more precisely, impedance) increases
significantly at harmonic frequencies, leading to less efficient operation.
Also, stray load losses can increase significantly at harmonic frequencies.
Overall motor losses increase by about 20% with a six-step voltage
waveform compared to operation with a sinusoidal supply. In some cases
the motor may have to be de-rated as a result of the losses. Alternatively,
additional circuitry and switching devices can be employed to minimize
losses.
Instability can also occur due to the interaction between the motor and the
converter. This is especially true of motors of low rating, which have low
inertia. Harmonics can also contribute to low power factor.
Correction of Poor power factor
Write some strategies for correcting poor power factor in motors?
The following are strategies for correcting power factor in motors:
1. Minimise operation of idling or lightly loaded motors
2. Ensuring correct supply of rated voltage and phase balance
3. Installing capacitors to decrease reactive power loads
Capacitor rating
The size of capacitor required for a particular motor depends upon
the no-load reactive kVA (kVAR) drawn by the motor, which can be
determined only from no-load testing of the motor. In general, for
full loading operating motor, the capacitor selected to not exceed
90 % of the no-load
kVAR of the motor. (Higher capacities could result in over-voltages
and motor burn-outs).
What is the thumb rule for installing capacitors to motor
terminal?
The size of capacitor required for a particular motor depends upon
the no-load reactive kVA (kVAR) drawn by the motor, which can be
determined only from no-load testing of the motor. In general, the
capacitor is then selected to not exceed 90 % of the no-load kVAR
of the motor. (Higher capacities could result in over-voltages and
motor burn-outs). Alternatively, typical power factors of standard
motors can provide the basis for conservative estimates of capacitor
ratings to use for different size motors.
Star Connected motors
Why is it beneficial to operate motors in star mode for under loaded
motors?
For motors which consistently operate at loads below 50 % of
rated capacity, an inexpensive and effective measure might be to
operate in star mode. A change from the standard delta operation
to star operation involves re-configuring the wiring of the three
phases of power input at the terminal box.
Operating in the star mode leads to a voltage reduction by a factor of
‘square root of 3’. Motor output falls to one-third of the value in the
delta mode, but performance characteristics as a function of load remain
unchanged. Thus, full-load operation in star mode gives higher efficiency
and power factor than partial load operation in the delta mode. However,
motor operation in the star mode is possible only for applications where
the torque-to-speed requirement is lower at reduced load.
Efficiency Of Electricity
Name the two important parameters that attribute to efficiency of
electricity use by AC induction Motors?
The important parameters that attribute to efficiency of electricity use by
AC induction Motors are
1. Efficiency of the motor
2. Power Factor
Measurements of Capacitor KVAR Ratings
MCC Details
Before Power Factor Improvement
After Power Factor
Improvement
Location
Line
Voltag
e VL Line Current IL
Reactive power
KVAr
Apparent
Power KVA
Active
Power KW
Cos #
P.F.
Multipling
Factor
Required
Kvar
KVA
Requiremen
t
Load
Current
Reduction In
KVA
Demand
Reduction
In current
% Saving
In Cable
Losses
Budgetry Cost of APFC
Panel alongwith Reactors
Paste Plant 415.00 152.00 60.00 84.00 69.00 0.75 0.74 51.02 69.70 96.97 14.30 55.03 42.61 112244.69
Paste Plant 437.80 199.80 92.14 163.47 129.84 0.83 0.53 68.75 131.15 172.96 32.32 26.84 29.71 151253.99
Paste Plant 431.00 261.00 105.00 182.00 150.00 0.82 0.56 83.33 151.52 202.97 30.48 58.03 31.39 183318.96
Paste Plant 417.00 182.00 85.50 129.00 97.00 0.75 0.74 71.72 97.98 135.66 31.02 46.34 42.61 157793.26
R/R Shift elec room 421.00 153.04 70.00 110.00 78.00 0.70 0.88 68.46 78.79 108.05 31.21 44.99 50.01 150615.34
Pot line 3 421.00 61.00 23.00 42.30 35.50 0.84 0.50 17.87 35.86 49.18 6.44 11.82 28.01 39318.97
Pot line 3 431.00 68.81 23.47 33.26 23.64 0.71 0.85 20.08 23.88 31.99 9.38 36.82 48.57 44172.53
Pot line 2 421.00 58.99 29.47 45.27 34.28 0.76 0.71 24.43 34.63 47.49 10.64 11.50 41.07 53746.69
Pot line 2 431.00 86.93 49.29 63.35 39.76 0.63 1.09 43.35 40.16 53.80 23.19 33.13 59.50 95361.83
Pot line 1 420.00 52.00 21.00 37.10 30.70 0.83 0.54 16.66 31.01 42.63 6.09 9.37 30.56 36641.60
Pot line 1 431.00 87.28 46.52 62.59 41.92 0.67 0.97 40.47 42.34 56.72 20.25 30.56 54.20 89043.13
Above G shift office 421.00 426.00 220.00 311.00 242.00 0.73 0.79 192.08 244.44 335.24 66.56 90.76 45.63 422585.41
Rodding Room 424.00 175.29 100.23 120.07 65.99 0.55 1.38 90.80 66.66 90.77 53.41 84.52 69.14 199763.32
Cathode MCC 411.00 129.00 45.50 90.00 76.50 0.86 0.45 34.69 77.27 108.55 12.73 20.45 24.71 76327.62
Cathode MCC 431.00 18.00 7.50 11.10 8.10 0.75 0.74 5.99 8.18 10.96 2.92 7.04 42.61 13176.55
Paste Plant 416.00 200.00 33.70 48.00 33.00 0.72 0.82 27.10 33.33 46.26 14.67 153.74 47.11 59630.78
Paste Plant 422.00 156.89 84.91 113.02 73.69 0.66 1.00 73.38 74.43 101.84 38.59 55.05 55.56 161435.31
Paste Plant 426.00 172.28 85.83 130.86 98.89 0.76 0.71 70.48 99.89 135.38 30.97 36.90 41.07 155046.98
Paste Plant 423.00 96.73 49.18 56.36 27.70 0.49 1.64 45.33 27.98 38.19 28.38 58.54 75.50 99730.33
Paste Plant 421.00 238.68 89.20 169.38 143.62 0.85 0.48 68.54 145.07 198.95 24.31 39.73 26.28 150794.47
B/F NO 5 431.00 7.10 4.60 5.10 2.20 0.42 2.02 4.44 2.22 2.98 2.88 4.12 82.00 9768.47
Near inst office 426.00 52.60 31.90 30.50 23.00 0.43 1.96 45.01 23.23 31.49 7.27 21.11 81.13 99029.75
Near inst office 426.00 62.40 29.70 32.60 13.20 0.41 2.06 27.14 13.33 18.07 19.27 44.33 82.51 59713.33
R/R 423.00 55.00 25.30 36.10 25.80 0.71 0.84 21.70 26.06 35.57 10.04 19.43 48.13 47729.91
Near W Shop 421.00 175.75 90.60 132.42 96.34 0.73 0.79 76.47 97.31 133.46 35.11 42.29 45.63 168230.90
Near W Shop 423.00 132.46 63.99 97.03 73.72 0.75 0.74 54.51 74.46 101.64 22.57 30.82 42.61 119922.88
Near W Shop 417.00 127.58 69.00 91.70 68.00 0.34 2.62 178.40 68.69 95.10 23.01 32.48 88.21 392470.35
B/F NO 5 427.00 128.61 57.43 83.72 63.25 0.73 0.79 50.20 63.89 86.39 19.83 42.22 45.63 110448.46
B/F NO 5 423.00 220.42 106.81 168.13 129.65 0.77 0.69 88.96 130.96 178.75 37.17 41.67 39.51 195706.61
Total 3937.63 1800.77 2679.43 1994.29 1661.37 2014.43 2748.00 665.00 1189.64 3655022.43
Present Annual KvaH
Requirement = 2,34,71,806.80
After Power Factor
Improvement = 1,76,46,444.85
Total Saving in KvaH = 58,25,361.95
Annual saving Kvah Charged
@ Rs 4 Per Unit = 2,33,01,447.81 Two crore thirty three lakh only
Monthly saving = 1941787.32
Total Investment = 36,55,022.43
Payback period = 1.88( Approx two Months)
The End
Vidya Sagar
vidya.sagar@adityabirla.com
B.Tech Electrical (JMI Delhi)
Hindalco Industries LTD.
PH-9795456393

More Related Content

What's hot

POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION moiz89
 
Automatic Generation Control
Automatic Generation ControlAutomatic Generation Control
Automatic Generation ControlBirju Besra
 
Different method of frequency and voltage control
Different method of frequency and voltage controlDifferent method of frequency and voltage control
Different method of frequency and voltage control8141245710
 
Multilevel inverter
Multilevel  inverterMultilevel  inverter
Multilevel inverterSyed Lateef
 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Dr. Rohit Babu
 
Firing angle control
Firing angle controlFiring angle control
Firing angle controljawaharramaya
 
Pulse width modulated inverter
Pulse width modulated inverterPulse width modulated inverter
Pulse width modulated inverterVSRAGHU
 
Power Electronic Converter
Power Electronic ConverterPower Electronic Converter
Power Electronic ConverterAli
 
Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)RP6997
 
Protection schemes and zones
Protection schemes and zonesProtection schemes and zones
Protection schemes and zonesSlides Hub
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptMamta Bagoria
 
DISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYDISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYRaviraj solanki
 

What's hot (20)

POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
 
Pole Placement in Digital Control
Pole Placement in Digital ControlPole Placement in Digital Control
Pole Placement in Digital Control
 
SYNCHRONOUS MACHINES
SYNCHRONOUS MACHINESSYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES
 
Hvdc notes
Hvdc notesHvdc notes
Hvdc notes
 
Automatic Generation Control
Automatic Generation ControlAutomatic Generation Control
Automatic Generation Control
 
Different method of frequency and voltage control
Different method of frequency and voltage controlDifferent method of frequency and voltage control
Different method of frequency and voltage control
 
Multilevel inverter
Multilevel  inverterMultilevel  inverter
Multilevel inverter
 
Faults on Power System
Faults on Power SystemFaults on Power System
Faults on Power System
 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)
 
Firing angle control
Firing angle controlFiring angle control
Firing angle control
 
Pulse width modulated inverter
Pulse width modulated inverterPulse width modulated inverter
Pulse width modulated inverter
 
Cooling of power transformer
Cooling of power transformerCooling of power transformer
Cooling of power transformer
 
Power Electronic Converter
Power Electronic ConverterPower Electronic Converter
Power Electronic Converter
 
Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)
 
Alternator
AlternatorAlternator
Alternator
 
Power factor
Power factorPower factor
Power factor
 
Protection schemes and zones
Protection schemes and zonesProtection schemes and zones
Protection schemes and zones
 
PWM RECTIFIER
PWM RECTIFIERPWM RECTIFIER
PWM RECTIFIER
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
 
DISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYDISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAY
 

Similar to Power Factor.ppt

Power Factor : Basics and Benefits of Improvement
Power Factor : Basics and  Benefits of ImprovementPower Factor : Basics and  Benefits of Improvement
Power Factor : Basics and Benefits of ImprovementBijadhar Pandey
 
Electrical energy issues presented by arshad khan chiniot power limited
Electrical energy issues presented by arshad khan chiniot  power limitedElectrical energy issues presented by arshad khan chiniot  power limited
Electrical energy issues presented by arshad khan chiniot power limitedarshadkhanmarwat
 
power factor correction soham+niraj
power factor correction soham+nirajpower factor correction soham+niraj
power factor correction soham+nirajsoham patel
 
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...Staco Energy
 
Chapter 1 ac commutator motors1
Chapter 1 ac commutator motors1Chapter 1 ac commutator motors1
Chapter 1 ac commutator motors1Souvik Dutta
 
How Power Factor corection works.pdf
How Power Factor corection works.pdfHow Power Factor corection works.pdf
How Power Factor corection works.pdfChristinaBoyd12
 
Power factor improvement
Power factor improvementPower factor improvement
Power factor improvementharshal567
 
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUESpower factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUESEMERSON EDUARDO RODRIGUES
 
Product: Power Factor Harmonics
Product: Power Factor HarmonicsProduct: Power Factor Harmonics
Product: Power Factor HarmonicsStaco Energy
 
Improvement of Load Power Factor by Using Capacitor
Improvement of Load Power Factor by Using CapacitorImprovement of Load Power Factor by Using Capacitor
Improvement of Load Power Factor by Using CapacitorIOSRJEEE
 
Machines dc motors
Machines   dc motorsMachines   dc motors
Machines dc motorssld1950
 
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdfasprilla mangombe
 
Single phase compensated motor
Single phase compensated motorSingle phase compensated motor
Single phase compensated motorSayanSarkar55
 
Power factor improvement of an induction motor
Power factor improvement of an induction motorPower factor improvement of an induction motor
Power factor improvement of an induction motorIIT Roorkee
 
IRJET- Variable Frequency Drive Used in Treadmill
IRJET- Variable Frequency Drive Used in TreadmillIRJET- Variable Frequency Drive Used in Treadmill
IRJET- Variable Frequency Drive Used in TreadmillIRJET Journal
 

Similar to Power Factor.ppt (20)

Power Factor : Basics and Benefits of Improvement
Power Factor : Basics and  Benefits of ImprovementPower Factor : Basics and  Benefits of Improvement
Power Factor : Basics and Benefits of Improvement
 
Electrical energy issues presented by arshad khan chiniot power limited
Electrical energy issues presented by arshad khan chiniot  power limitedElectrical energy issues presented by arshad khan chiniot  power limited
Electrical energy issues presented by arshad khan chiniot power limited
 
power factor correction soham+niraj
power factor correction soham+nirajpower factor correction soham+niraj
power factor correction soham+niraj
 
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
 
chapter 7.pdf
chapter 7.pdfchapter 7.pdf
chapter 7.pdf
 
Field test
Field test Field test
Field test
 
Chapter 1 ac commutator motors1
Chapter 1 ac commutator motors1Chapter 1 ac commutator motors1
Chapter 1 ac commutator motors1
 
How Power Factor corection works.pdf
How Power Factor corection works.pdfHow Power Factor corection works.pdf
How Power Factor corection works.pdf
 
APFC AMTL 30.01.2015
APFC  AMTL  30.01.2015APFC  AMTL  30.01.2015
APFC AMTL 30.01.2015
 
Power factor improvement
Power factor improvementPower factor improvement
Power factor improvement
 
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUESpower factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
 
Product: Power Factor Harmonics
Product: Power Factor HarmonicsProduct: Power Factor Harmonics
Product: Power Factor Harmonics
 
Improvement of Load Power Factor by Using Capacitor
Improvement of Load Power Factor by Using CapacitorImprovement of Load Power Factor by Using Capacitor
Improvement of Load Power Factor by Using Capacitor
 
Machines dc motors
Machines   dc motorsMachines   dc motors
Machines dc motors
 
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
 
Single phase compensated motor
Single phase compensated motorSingle phase compensated motor
Single phase compensated motor
 
Power factor improvement of an induction motor
Power factor improvement of an induction motorPower factor improvement of an induction motor
Power factor improvement of an induction motor
 
boost driver
boost driverboost driver
boost driver
 
ELEKTRA_new
ELEKTRA_newELEKTRA_new
ELEKTRA_new
 
IRJET- Variable Frequency Drive Used in Treadmill
IRJET- Variable Frequency Drive Used in TreadmillIRJET- Variable Frequency Drive Used in Treadmill
IRJET- Variable Frequency Drive Used in Treadmill
 

Recently uploaded

Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 

Recently uploaded (20)

Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 

Power Factor.ppt

  • 1. Electrical Power Supply System The conveyance of electric power from a power station to consumer,s premises is known as electrical Power supply system. An electric supply system consists of three principal components . 1-Power Station 2-Transmission lines 3-Distribution
  • 2.
  • 3. Power factor The cosine of angle between voltage and current in ac circuit is known as power factor. Power factor (Cos )= KW/KVA
  • 4. Electrical Power 1. Active Power (kw = kva cos ( 3 V I Cos ) 2. Reactive Power (kvar = kva sin 3. Apparent Power (kva = (kw2+kvar2) KVA KW KVAR
  • 5. Types Of Loads 1-Incandescent Lamp 0.98-1.0 2-Flourescent Lamp 0.6-0.8 3-Neon Lamp used for advertisement 0.4-0.5 4-Arc lamps used in cienema 0.3-0.7 5-Fans 0.5-0.8 6-Induction Heaters 0.85 7-Resistance Furnaces 0.6-0.9 8-Arc Furnaces 0.85 9-Induction Furnaces 0.6 10-Arc welders 0.3-0.4 11-Resistances Welders 0.65 12-Induction Motors 0.5-0.85 13-Fractional h.p.motors 0.4-0.75 Effect of low Power Factor Heat = I*2 R T I ά to 1/ cosø H ά (1/ cosø)*2 A low P.F. would mean increased heat losses.
  • 6. Causes of Low Power factor 1.Induction Motors 2.Arc Lamps, electrical discharge Lamps 3.Industrial Heating furnace at low lagging power factor 4.From power system.
  • 7. Power factor Improvement Equipment 1.Static capacitor Advantage- 1.They have low losses 2.They require little maintenance as there are no rotating parts 3.They can be easily installed as they are light and require no foundation 4.They can work under ordinary atmospheric conditions Disadvantages 1.They have short services life ranging from 8 to 10 years. 2.They are easily damaged if the voltage exceeds the rated value. 3. Once the capacitors are damaged, there repair is uneconomical.
  • 9. Asynchronous motor takes a leading current when over excited and ,therefore,they acts as a capacitor.An overexcited synchronous motor running on no load is known as synchronous condensor. Advantage- 1.By varying the field excitation ,the magnitude of current drawn by motor can be changed by any amount.this helps in achieving step less control of power factor. 2.The motor winding have high thermal stability to short circuit currents 3.The faults can be removed easily Disadvantages 1.There are considerable losses in the motor. 2.The maintenance cost is high. 3.It produces noise . 4.Except in sizes above 500kva ,the cost is greater than that of static capacitors of the same ratings. 5.As a synchronous motor has no self starting torque,therefore,an auxiliary equipment has to be provided for this purpose Synchronus Condensor
  • 11. Phase advancer is a simple AC exciter which is connected on the main shaft of the motor and operates with the motor’s rotor circuit for power factor improvement. Phase advancer is used to improve the power factor of induction motor in industries. As the stator windings of induction motor takes lagging current 90° out of phase with Voltage, therefore the power factor of induction motor is low. If the exciting ampere- turns are excited by external AC source, then there would be no effect of exciting current on stator windings. Therefore, the power factor of induction motor will be improved. This process is done by Phase advancer. Advantages: 1-Lagging kVAR (Reactive component of Power or reactive power) drawn by the motor is sufficiently reduced because the exciting ampere turns are supplied at slip frequency (fs). 2-The phase advancer can be easily used where the use of synchronous motors is Unacceptable Disadvantage: 1-Using Phase advancer is not economical for motors below 200 H.P. (About 150 KW) Phase advancer
  • 13. Reduction in Transformer Rating Reduction in KVAR Demand Advantages of P.F Correction Reduction in KVA Demand Reduction in Line Current Reduction in Line loss Reduction in Cable / Bus-bar size Reduction in Switchgear Rating
  • 14. REDUCTION IN KVA DEMAND LOAD - 900 KW EXISTING P.F. (COS - 0.6 DESIRED P.F. (COS ) - 0.92 KW Ø. KVA 1 = 900 / 0.6 = 1500 KVA2 = 900 / 0.92 = 978 Ø 1) Ø2 kW kVA COS = KVA = Ø. kW cosØ. Reduction in KVA 1500 - 978 = 522
  • 15. REDUCTION IN KVAR DEMAND kVA = KVAR1 = = KVAR 2 = KW2 + KVAR2 KVA1 2 - KW2 1500 2 - 900 2 = 1200 978 2 - 900 2 = 382 KW - 900 KVA1 - 1500 KVA2 - 978 KW Ø. KVAR Reduction in KVAR 1200 - 382 = 818
  • 16. REDUCTION IN LINE CURRENT KVA = I = I1 = = I2 = = 3 V I 1000 KVA x 1000 3 x 415 1500 x 1000 3 x 415 2087 Amp 978 x 1000 3 x 415 1361 Amp KVA1 - 1500 KVA2 - 978 Reduction in Current 2087 - 1361 = 726
  • 17. 0 10 20 30 40 50 60 70 80 90 100 1 0.9 0.8 0.7 0.6 0.5 % Rise in Current w.r.t. decrease in Power Factor % Rise in I n P.F.
  • 18. % of saving in losses = 1- Cos Cos Ø1 Ø2 2 1- 0.6 0.92 2 X 100 X 100 = 57.46 Cable Losses
  • 19. 0 10 20 30 40 50 60 70 80 0.5 0.6 0.7 0.8 0.9 1 Saving in Cable Losses P.F. 1.0 0.95 0.9 0.85 0.8 Initial P.F.
  • 20. Saving in losses = Wr x K1 Wr = Full load copper loss of the transformer connected load in Kw k1 KVA rating of the transformer 1 CosØ1 1 CosØ2 - Transformer Losses
  • 22. Transformer Losses 0 5000 10000 15000 20000 25000 30000 35000 40000 0 500 1000 1500 2000 2500 3000 3500 Transformer KVA cu Loss Copper losses
  • 23. Transformer Losses Saving in losses = Wr x K1 1 CosØ1 1 CosØ2 - = 900 1500 1 1 0.6 0.92 = 6260 Watts Annual Saving = 6260 x 300 x 12 1000 = 22536 KWH 18000 x x
  • 24. Power Savings KVA X'MER CURRENT ACB RAT I NG 1500 978 1500 1000 2086 1360 2500 0 500 1000 1500 2000 2500 3000 KVA X'MER CURRENT ACB AT 0.6 PF AT 0.92 PF 1600
  • 25. What are the effects of harmonics on motor operation and performance? Harmonics increase motor losses, and can adversely affect the operation of sensitive auxiliary equipment. The non-sinusoidal supply results in harmonic currents in the stator which increases the total current drawn. In addition, the rotor resistance (or more precisely, impedance) increases significantly at harmonic frequencies, leading to less efficient operation. Also, stray load losses can increase significantly at harmonic frequencies. Overall motor losses increase by about 20% with a six-step voltage waveform compared to operation with a sinusoidal supply. In some cases the motor may have to be de-rated as a result of the losses. Alternatively, additional circuitry and switching devices can be employed to minimize losses. Instability can also occur due to the interaction between the motor and the converter. This is especially true of motors of low rating, which have low inertia. Harmonics can also contribute to low power factor.
  • 26. Correction of Poor power factor Write some strategies for correcting poor power factor in motors? The following are strategies for correcting power factor in motors: 1. Minimise operation of idling or lightly loaded motors 2. Ensuring correct supply of rated voltage and phase balance 3. Installing capacitors to decrease reactive power loads
  • 27. Capacitor rating The size of capacitor required for a particular motor depends upon the no-load reactive kVA (kVAR) drawn by the motor, which can be determined only from no-load testing of the motor. In general, for full loading operating motor, the capacitor selected to not exceed 90 % of the no-load kVAR of the motor. (Higher capacities could result in over-voltages and motor burn-outs). What is the thumb rule for installing capacitors to motor terminal? The size of capacitor required for a particular motor depends upon the no-load reactive kVA (kVAR) drawn by the motor, which can be determined only from no-load testing of the motor. In general, the capacitor is then selected to not exceed 90 % of the no-load kVAR of the motor. (Higher capacities could result in over-voltages and motor burn-outs). Alternatively, typical power factors of standard motors can provide the basis for conservative estimates of capacitor ratings to use for different size motors.
  • 28. Star Connected motors Why is it beneficial to operate motors in star mode for under loaded motors? For motors which consistently operate at loads below 50 % of rated capacity, an inexpensive and effective measure might be to operate in star mode. A change from the standard delta operation to star operation involves re-configuring the wiring of the three phases of power input at the terminal box. Operating in the star mode leads to a voltage reduction by a factor of ‘square root of 3’. Motor output falls to one-third of the value in the delta mode, but performance characteristics as a function of load remain unchanged. Thus, full-load operation in star mode gives higher efficiency and power factor than partial load operation in the delta mode. However, motor operation in the star mode is possible only for applications where the torque-to-speed requirement is lower at reduced load.
  • 29. Efficiency Of Electricity Name the two important parameters that attribute to efficiency of electricity use by AC induction Motors? The important parameters that attribute to efficiency of electricity use by AC induction Motors are 1. Efficiency of the motor 2. Power Factor
  • 30. Measurements of Capacitor KVAR Ratings MCC Details Before Power Factor Improvement After Power Factor Improvement Location Line Voltag e VL Line Current IL Reactive power KVAr Apparent Power KVA Active Power KW Cos # P.F. Multipling Factor Required Kvar KVA Requiremen t Load Current Reduction In KVA Demand Reduction In current % Saving In Cable Losses Budgetry Cost of APFC Panel alongwith Reactors Paste Plant 415.00 152.00 60.00 84.00 69.00 0.75 0.74 51.02 69.70 96.97 14.30 55.03 42.61 112244.69 Paste Plant 437.80 199.80 92.14 163.47 129.84 0.83 0.53 68.75 131.15 172.96 32.32 26.84 29.71 151253.99 Paste Plant 431.00 261.00 105.00 182.00 150.00 0.82 0.56 83.33 151.52 202.97 30.48 58.03 31.39 183318.96 Paste Plant 417.00 182.00 85.50 129.00 97.00 0.75 0.74 71.72 97.98 135.66 31.02 46.34 42.61 157793.26 R/R Shift elec room 421.00 153.04 70.00 110.00 78.00 0.70 0.88 68.46 78.79 108.05 31.21 44.99 50.01 150615.34 Pot line 3 421.00 61.00 23.00 42.30 35.50 0.84 0.50 17.87 35.86 49.18 6.44 11.82 28.01 39318.97 Pot line 3 431.00 68.81 23.47 33.26 23.64 0.71 0.85 20.08 23.88 31.99 9.38 36.82 48.57 44172.53 Pot line 2 421.00 58.99 29.47 45.27 34.28 0.76 0.71 24.43 34.63 47.49 10.64 11.50 41.07 53746.69 Pot line 2 431.00 86.93 49.29 63.35 39.76 0.63 1.09 43.35 40.16 53.80 23.19 33.13 59.50 95361.83 Pot line 1 420.00 52.00 21.00 37.10 30.70 0.83 0.54 16.66 31.01 42.63 6.09 9.37 30.56 36641.60 Pot line 1 431.00 87.28 46.52 62.59 41.92 0.67 0.97 40.47 42.34 56.72 20.25 30.56 54.20 89043.13 Above G shift office 421.00 426.00 220.00 311.00 242.00 0.73 0.79 192.08 244.44 335.24 66.56 90.76 45.63 422585.41 Rodding Room 424.00 175.29 100.23 120.07 65.99 0.55 1.38 90.80 66.66 90.77 53.41 84.52 69.14 199763.32 Cathode MCC 411.00 129.00 45.50 90.00 76.50 0.86 0.45 34.69 77.27 108.55 12.73 20.45 24.71 76327.62 Cathode MCC 431.00 18.00 7.50 11.10 8.10 0.75 0.74 5.99 8.18 10.96 2.92 7.04 42.61 13176.55 Paste Plant 416.00 200.00 33.70 48.00 33.00 0.72 0.82 27.10 33.33 46.26 14.67 153.74 47.11 59630.78 Paste Plant 422.00 156.89 84.91 113.02 73.69 0.66 1.00 73.38 74.43 101.84 38.59 55.05 55.56 161435.31 Paste Plant 426.00 172.28 85.83 130.86 98.89 0.76 0.71 70.48 99.89 135.38 30.97 36.90 41.07 155046.98 Paste Plant 423.00 96.73 49.18 56.36 27.70 0.49 1.64 45.33 27.98 38.19 28.38 58.54 75.50 99730.33 Paste Plant 421.00 238.68 89.20 169.38 143.62 0.85 0.48 68.54 145.07 198.95 24.31 39.73 26.28 150794.47 B/F NO 5 431.00 7.10 4.60 5.10 2.20 0.42 2.02 4.44 2.22 2.98 2.88 4.12 82.00 9768.47 Near inst office 426.00 52.60 31.90 30.50 23.00 0.43 1.96 45.01 23.23 31.49 7.27 21.11 81.13 99029.75 Near inst office 426.00 62.40 29.70 32.60 13.20 0.41 2.06 27.14 13.33 18.07 19.27 44.33 82.51 59713.33 R/R 423.00 55.00 25.30 36.10 25.80 0.71 0.84 21.70 26.06 35.57 10.04 19.43 48.13 47729.91 Near W Shop 421.00 175.75 90.60 132.42 96.34 0.73 0.79 76.47 97.31 133.46 35.11 42.29 45.63 168230.90 Near W Shop 423.00 132.46 63.99 97.03 73.72 0.75 0.74 54.51 74.46 101.64 22.57 30.82 42.61 119922.88 Near W Shop 417.00 127.58 69.00 91.70 68.00 0.34 2.62 178.40 68.69 95.10 23.01 32.48 88.21 392470.35 B/F NO 5 427.00 128.61 57.43 83.72 63.25 0.73 0.79 50.20 63.89 86.39 19.83 42.22 45.63 110448.46 B/F NO 5 423.00 220.42 106.81 168.13 129.65 0.77 0.69 88.96 130.96 178.75 37.17 41.67 39.51 195706.61 Total 3937.63 1800.77 2679.43 1994.29 1661.37 2014.43 2748.00 665.00 1189.64 3655022.43 Present Annual KvaH Requirement = 2,34,71,806.80 After Power Factor Improvement = 1,76,46,444.85 Total Saving in KvaH = 58,25,361.95 Annual saving Kvah Charged @ Rs 4 Per Unit = 2,33,01,447.81 Two crore thirty three lakh only Monthly saving = 1941787.32 Total Investment = 36,55,022.43 Payback period = 1.88( Approx two Months)
  • 31. The End Vidya Sagar vidya.sagar@adityabirla.com B.Tech Electrical (JMI Delhi) Hindalco Industries LTD. PH-9795456393