A CIRCUIT FOR MEASUREMENT OF HIGH VOLTAGE
CORONA PUISES IN COAXIAL CYLINDRICAL
GEOMETRY
CONTENT
 INTRODUCTION
 HISTORICAL RETROSPECT
 THE BASIC CIRCUIT
 CONTINUED DEVELOPMENT
 THE NEW CIRCUIT
 CONCLUSION
1. INTRODUCTION
 In recent years the use of higher voltage levels for power transmission has
caused renewed interest by the electric power industry in the problems
associated with increased potentials.
 The cause of many of these problems is the corona discharge occurring on
transmission line conductors and hardware.
 Efforts to study the electrical characteristics of the phenomenon in the
laboratory have met with difficulties due to undesirable distortions of the
measured wave shapes.
 A new circuit is developed which eliminates distortion of the observed
waveforms and thus enables meaningful, quantitative measurement of the
electrical characteristics of coronas active in the coaxial cylindrical
geometry.
2. HISTORICAL RETROSPECT
 With the advancement of EHV power transmission in the early
sixties, interest developed in the study of coronas generated on
transmission lines.
 The coaxial cylindrical geometry was selected by the majority of
workers as being the most convenient for laboratory studies of
corona on transmission line conductors, because this configuration
re produces satisfactorily the electric field intensity in the vicinity of
the conductors on actual transmission lines.
3. THE BASIC CIRCUIT
FIGURE 1
 High voltage is applied to some form of electrode through a current limiting
resistance and a radio frequency choke.
 The arbitrarily-shaped low-voltage electrode is connected to ground through a
low impedance. An oscilloscope is used to display the wave shape of voltage
developed across this impedance.
 Usually, in corona studies, one of the two electrodes is physically much smaller
than the other. A region of high electric field intensity will exist near the smaller
electrode.
 Corona discharges will occur at high potential difference between electrodes.
 The partial discharge process of high voltage corona includes avalanche
mechanisms in which rapidly moving electrons are involved in inelastic col-
lisions with gas molecules.
 The movements of electrons and ions in the inter-electrode gap causes currents
to be induced in both electrodes according to the relationship.
𝐼𝐼=𝐸1.𝑉 (1)
𝐼𝐼= induced current in electrode i due to motion of a unit point charge
𝐸1= electric field at the charged particle due to an applied potential of 1 volt on
the 𝑖 𝑡ℎ
electrode, the other electrodes being grounded
𝑉 = velocity of particle
 Two broad classifications of high-voltage coronas have been recognized.
 The first group, positive corona, are partial-discharge processes active when the
highly stressed electrode is the positive electrode of the system.
 The second, negative corona, are those processes occurring at the highly stressed
negative electrode.
 Both positive and negative discharge events occur at random intervals of time.
But again with different mean repetition rates.
 Since measurement of negative corona pulses constitutes the more severe
problem, the case of negative corona will be dis cussed primarily from this point
on.
3.1 The Effect of Stray Capacitance
 When the insignificant effect of the high voltage supply circuit is neglected and
when distributed stray capacitances are lumped, the approximate equivalent
circuit of Figure 2 results. From elementary circuit analysis, the following
relationships apply:
FIGURE 2
𝑇𝑟 = 2.2𝑅𝐶 𝑇 (2)
𝐹1 =
1
2𝜋𝑅𝐶 𝑇
(3)
𝑇𝑟 =rise time for unit step of current
𝐹1= frequency bandwidth of the circuit given by 3db down frequency of the low-
pass filter
These two equations indicates that, for faithful reproduction of high-frequency
current pulses, stray capacitance must be minimized.
3.2 Matching and Reflections
 For faithful display on the oscilloscope, the currents induced in the measuring
electrode must be provided a reflection-free path to the recording instrument.
 Reflections may be caused, by impedance discontinuities in the measuring
electrode itself, or at the connections of the measuring instrument.
 The difficulty arises from the choice of electrode geometry. If the electrodes are
physic ally large, such that the corona-generated current pulses must be
transmitted along their length, the impedance of this path must be matched with
that of the measuring circuit.
 If this is not accomplished then oscillation of the currents within the measuring
electrodes results and the measured waveforms are distorted.
4. CONTINUED DEVELOPMENT
 The circuit configuration shown in Figure 3 illustrates the form typical of the initial studies in technical
laboratories.
Fundamental coaxial cylindrical con figuration.
FIGURE 3
 The outer cylinder is at essentially ground potential, while the inner highly
stressed electrode is energized through a current-limiting resistance.
 It has the disadvantage of impedance discontinuities, and is characterized by
relatively high stray capacitance.
 The current waveforms typical for this configuration are shown in the
oscilloscope of Figure 4.
Output waveform obtained from configuration of Figure 3.
 The pulse rise time is approximately 40 ns.
FIGURE 4
 According to equation (2), measured rise time can be improved by reducing the stray
capacitance between the measuring electrode and ground.
 It can be seen by inspection of the configuration in Figure 3 , that stray capacitance in
this arrangement is larger than that present when the outer cylinder is energized and the
inner conductor used as the measuring electrode.
 A further slight reduction in stray capacitance has been obtained by Denholm through
mounting the cylinder with its axis in a vertical position as shown in Figure 5.
FIGURE 5
 The out put pulse shown in Figure 6 displays a reduced rise time of 14 ns,
however oscillation on the tail of the pulse persists.
 Efforts were then made to improve the pulse shape by matching the impedance at
the end of the central conductor to the impedance of the measuring circuit. The
circuit shown in Figure 7 reported by Rakoshdas illustrates this development.
 The waveforms obtained from this circuit, as seen in Figure 8, show
improvement, however, some undesirable oscillations are evident on the tail of
the corona pulses.
FIGURE 6
FIGURE 7
FIGURE 8
 An attempt has been made in 1963 by Reinsborugh to terminate the cylinder at
both ends using the arrangement shown in Figure 9.
 The circuit showed some promise, however, difficulties in achieving purely
resistive terminations with low inductance could not be entirely overcome and the
results were not completely satisfactory as seen in Figure 10.
FIGURE 9 FIGURE 10
5. THE NEW CIRCUIT
 The methods described in Section IV employed various forms of impedance
matching circuitry, however, the impedance discontinuity at the ends of the outer
cylinder could not be entirely overcome. The circuit technique illustrated in
Figures 11 and 12 provides the required reflection-free path.
FIGURE 11
FIGURE 12
 As can be seen, the transmission line, connecting the corona-generating electrode to the
measuring instrument, is terminated in its characteristic impedance and connected
directly to the point in Figure 11 or the internal conductor in Figure 12, within the
cylindrical configuration.
 The output of the coaxial point circuit is shown in the oscillogram of Figure 13. It can be
seen that the waveforms are essentially reflection free, and display a rise time of 5 ns.
This rise time is the lowest observed thus far for a negative corona pulse.
FIGURE 13
 The developed system was also used to display the circuit current resulting from a
positive corona discharge. The result is shown in Figure 14.
 The stray capacitance of the point to ground (geometry of Figure 11) was measured to be
0.5 pF . Using equations (2) and (3), the rise time and the frequency response are
calculated to be:
𝑇𝑟=.0275ns
𝐹1=12700MHz
FIGURE 14
 For the measurements reported in Figures 13 and 14, a Tektronix type 585
oscilloscope, having a specified bandwidth of 85 MHz and a measured rise time
of 4 ns, as shown in Figure 15, was used.
 The observation suggests that the actual rise time of negative corona pulses may
be below the observed value of 5 ns.
 The measuring circuit itself is most satisfactory for the study of high voltage
corona pulses of both polarities.
FIGURE 15
6. CONCLUSION
 The developed pulse-measuring circuit has an estimated rise time of better than
30ps and the corresponding bandwidth of 12.7 GHz.
 Consequently the display instrument used, a Tektronix 585 oscilloscope, type 82
plug-in, having a bandwidth of only 85 MHz, was the limiting element in the
developed system.
 With the system limitation of 85 MHz, it was possible to faithfully observe the
current waveform associated with the discharge process of positive corona,
however, there is evidence that faster rise time oscilloscopes with millivolt
sensitivity, are required for correct reproduction of electrode currents caused by
negative corona discharges.

More Related Content

What's hot

Ppt of ehv ac transmission
Ppt of ehv ac transmissionPpt of ehv ac transmission
Ppt of ehv ac transmission
Sumit Kumar
 

What's hot (20)

Corona1
Corona1Corona1
Corona1
 
Impulse voltage
Impulse voltageImpulse voltage
Impulse voltage
 
High voltage technology & insulation testing
High voltage technology & insulation testingHigh voltage technology & insulation testing
High voltage technology & insulation testing
 
Module 6part1
Module 6part1Module 6part1
Module 6part1
 
high voltage engineering module1(EE369)-KTU
high voltage engineering module1(EE369)-KTUhigh voltage engineering module1(EE369)-KTU
high voltage engineering module1(EE369)-KTU
 
Chapter 06 - Generation of High Direct Current Voltages
Chapter 06 - Generation of High Direct Current VoltagesChapter 06 - Generation of High Direct Current Voltages
Chapter 06 - Generation of High Direct Current Voltages
 
Chapter 5 corona
Chapter 5  coronaChapter 5  corona
Chapter 5 corona
 
Bundle conductors in transmission line
Bundle conductors in transmission line Bundle conductors in transmission line
Bundle conductors in transmission line
 
Transmission Line
Transmission LineTransmission Line
Transmission Line
 
Question bank on t & d
Question bank on t & dQuestion bank on t & d
Question bank on t & d
 
Seminar
SeminarSeminar
Seminar
 
Impulse current
Impulse currentImpulse current
Impulse current
 
measurement of high voltage and high currents
 measurement of high voltage and high currents  measurement of high voltage and high currents
measurement of high voltage and high currents
 
Conductor material and ferranti effect
Conductor material and ferranti effectConductor material and ferranti effect
Conductor material and ferranti effect
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Technotoy stage 4
Technotoy stage 4Technotoy stage 4
Technotoy stage 4
 
Overvoltage phenomenon
Overvoltage phenomenonOvervoltage phenomenon
Overvoltage phenomenon
 
Resistance potential divider
Resistance potential dividerResistance potential divider
Resistance potential divider
 
Ppt of ehv ac transmission
Ppt of ehv ac transmissionPpt of ehv ac transmission
Ppt of ehv ac transmission
 
Short circuit test in brief
Short circuit test in briefShort circuit test in brief
Short circuit test in brief
 

Similar to A circuit for measurement of high voltage corona

A photomultiplier high voltage power supply irtcorporating a ceramic transfor...
A photomultiplier high voltage power supply irtcorporating a ceramic transfor...A photomultiplier high voltage power supply irtcorporating a ceramic transfor...
A photomultiplier high voltage power supply irtcorporating a ceramic transfor...
Love Kiss
 
Scattering of Electrons in a Gas (The Franck-Hertz Experiment and the Ionizat...
Scattering of Electrons in a Gas (The Franck-Hertz Experiment and the Ionizat...Scattering of Electrons in a Gas (The Franck-Hertz Experiment and the Ionizat...
Scattering of Electrons in a Gas (The Franck-Hertz Experiment and the Ionizat...
Daniel Bulhosa Solórzano
 
635Project
635Project635Project
635Project
Yang He
 

Similar to A circuit for measurement of high voltage corona (20)

Transient Absorption Spectrometry in Photoelectrochemical Splitting of Water
Transient Absorption Spectrometry  in Photoelectrochemical Splitting of Water Transient Absorption Spectrometry  in Photoelectrochemical Splitting of Water
Transient Absorption Spectrometry in Photoelectrochemical Splitting of Water
 
A photomultiplier high voltage power supply irtcorporating a ceramic transfor...
A photomultiplier high voltage power supply irtcorporating a ceramic transfor...A photomultiplier high voltage power supply irtcorporating a ceramic transfor...
A photomultiplier high voltage power supply irtcorporating a ceramic transfor...
 
Modeling of solar array and analyze the current transient response of shunt s...
Modeling of solar array and analyze the current transient response of shunt s...Modeling of solar array and analyze the current transient response of shunt s...
Modeling of solar array and analyze the current transient response of shunt s...
 
Modeling of solar array and analyze the current transient
Modeling of solar array and analyze the current transientModeling of solar array and analyze the current transient
Modeling of solar array and analyze the current transient
 
Interaction of the secondary arc
Interaction of the secondary arcInteraction of the secondary arc
Interaction of the secondary arc
 
780170
780170780170
780170
 
Physics Sample Paper with General Instruction for Class - 12
Physics Sample Paper with General Instruction for Class - 12Physics Sample Paper with General Instruction for Class - 12
Physics Sample Paper with General Instruction for Class - 12
 
Presentation
PresentationPresentation
Presentation
 
A011120106
A011120106A011120106
A011120106
 
Em waves lab assignment converted
Em waves lab assignment  convertedEm waves lab assignment  converted
Em waves lab assignment converted
 
BACK to BASIC 5.pdf
BACK to BASIC 5.pdfBACK to BASIC 5.pdf
BACK to BASIC 5.pdf
 
MW&OCOM LAB.pdf
MW&OCOM LAB.pdfMW&OCOM LAB.pdf
MW&OCOM LAB.pdf
 
4R6Notes3_GasFilled_Detectors.pdf
4R6Notes3_GasFilled_Detectors.pdf4R6Notes3_GasFilled_Detectors.pdf
4R6Notes3_GasFilled_Detectors.pdf
 
Sinusoidal Response of RC & RL Circuits
Sinusoidal Response of RC & RL CircuitsSinusoidal Response of RC & RL Circuits
Sinusoidal Response of RC & RL Circuits
 
High direct current measurement
High direct current measurementHigh direct current measurement
High direct current measurement
 
Cro (emmi) (1)
Cro (emmi) (1)Cro (emmi) (1)
Cro (emmi) (1)
 
CRO and FG.ppt
CRO and FG.pptCRO and FG.ppt
CRO and FG.ppt
 
Scattering of Electrons in a Gas (The Franck-Hertz Experiment and the Ionizat...
Scattering of Electrons in a Gas (The Franck-Hertz Experiment and the Ionizat...Scattering of Electrons in a Gas (The Franck-Hertz Experiment and the Ionizat...
Scattering of Electrons in a Gas (The Franck-Hertz Experiment and the Ionizat...
 
635Project
635Project635Project
635Project
 
2nd year iv sem emi lab manual
2nd year iv sem emi lab manual2nd year iv sem emi lab manual
2nd year iv sem emi lab manual
 

Recently uploaded

VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
dharasingh5698
 

Recently uploaded (20)

Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 

A circuit for measurement of high voltage corona

  • 1. A CIRCUIT FOR MEASUREMENT OF HIGH VOLTAGE CORONA PUISES IN COAXIAL CYLINDRICAL GEOMETRY
  • 2. CONTENT  INTRODUCTION  HISTORICAL RETROSPECT  THE BASIC CIRCUIT  CONTINUED DEVELOPMENT  THE NEW CIRCUIT  CONCLUSION
  • 3. 1. INTRODUCTION  In recent years the use of higher voltage levels for power transmission has caused renewed interest by the electric power industry in the problems associated with increased potentials.  The cause of many of these problems is the corona discharge occurring on transmission line conductors and hardware.  Efforts to study the electrical characteristics of the phenomenon in the laboratory have met with difficulties due to undesirable distortions of the measured wave shapes.  A new circuit is developed which eliminates distortion of the observed waveforms and thus enables meaningful, quantitative measurement of the electrical characteristics of coronas active in the coaxial cylindrical geometry.
  • 4. 2. HISTORICAL RETROSPECT  With the advancement of EHV power transmission in the early sixties, interest developed in the study of coronas generated on transmission lines.  The coaxial cylindrical geometry was selected by the majority of workers as being the most convenient for laboratory studies of corona on transmission line conductors, because this configuration re produces satisfactorily the electric field intensity in the vicinity of the conductors on actual transmission lines.
  • 5. 3. THE BASIC CIRCUIT FIGURE 1
  • 6.  High voltage is applied to some form of electrode through a current limiting resistance and a radio frequency choke.  The arbitrarily-shaped low-voltage electrode is connected to ground through a low impedance. An oscilloscope is used to display the wave shape of voltage developed across this impedance.  Usually, in corona studies, one of the two electrodes is physically much smaller than the other. A region of high electric field intensity will exist near the smaller electrode.  Corona discharges will occur at high potential difference between electrodes.  The partial discharge process of high voltage corona includes avalanche mechanisms in which rapidly moving electrons are involved in inelastic col- lisions with gas molecules.
  • 7.  The movements of electrons and ions in the inter-electrode gap causes currents to be induced in both electrodes according to the relationship. 𝐼𝐼=𝐸1.𝑉 (1) 𝐼𝐼= induced current in electrode i due to motion of a unit point charge 𝐸1= electric field at the charged particle due to an applied potential of 1 volt on the 𝑖 𝑡ℎ electrode, the other electrodes being grounded 𝑉 = velocity of particle
  • 8.  Two broad classifications of high-voltage coronas have been recognized.  The first group, positive corona, are partial-discharge processes active when the highly stressed electrode is the positive electrode of the system.  The second, negative corona, are those processes occurring at the highly stressed negative electrode.  Both positive and negative discharge events occur at random intervals of time. But again with different mean repetition rates.  Since measurement of negative corona pulses constitutes the more severe problem, the case of negative corona will be dis cussed primarily from this point on.
  • 9. 3.1 The Effect of Stray Capacitance  When the insignificant effect of the high voltage supply circuit is neglected and when distributed stray capacitances are lumped, the approximate equivalent circuit of Figure 2 results. From elementary circuit analysis, the following relationships apply: FIGURE 2
  • 10. 𝑇𝑟 = 2.2𝑅𝐶 𝑇 (2) 𝐹1 = 1 2𝜋𝑅𝐶 𝑇 (3) 𝑇𝑟 =rise time for unit step of current 𝐹1= frequency bandwidth of the circuit given by 3db down frequency of the low- pass filter These two equations indicates that, for faithful reproduction of high-frequency current pulses, stray capacitance must be minimized.
  • 11. 3.2 Matching and Reflections  For faithful display on the oscilloscope, the currents induced in the measuring electrode must be provided a reflection-free path to the recording instrument.  Reflections may be caused, by impedance discontinuities in the measuring electrode itself, or at the connections of the measuring instrument.  The difficulty arises from the choice of electrode geometry. If the electrodes are physic ally large, such that the corona-generated current pulses must be transmitted along their length, the impedance of this path must be matched with that of the measuring circuit.  If this is not accomplished then oscillation of the currents within the measuring electrodes results and the measured waveforms are distorted.
  • 12. 4. CONTINUED DEVELOPMENT  The circuit configuration shown in Figure 3 illustrates the form typical of the initial studies in technical laboratories. Fundamental coaxial cylindrical con figuration. FIGURE 3
  • 13.  The outer cylinder is at essentially ground potential, while the inner highly stressed electrode is energized through a current-limiting resistance.  It has the disadvantage of impedance discontinuities, and is characterized by relatively high stray capacitance.  The current waveforms typical for this configuration are shown in the oscilloscope of Figure 4. Output waveform obtained from configuration of Figure 3.  The pulse rise time is approximately 40 ns. FIGURE 4
  • 14.  According to equation (2), measured rise time can be improved by reducing the stray capacitance between the measuring electrode and ground.  It can be seen by inspection of the configuration in Figure 3 , that stray capacitance in this arrangement is larger than that present when the outer cylinder is energized and the inner conductor used as the measuring electrode.  A further slight reduction in stray capacitance has been obtained by Denholm through mounting the cylinder with its axis in a vertical position as shown in Figure 5. FIGURE 5
  • 15.  The out put pulse shown in Figure 6 displays a reduced rise time of 14 ns, however oscillation on the tail of the pulse persists.  Efforts were then made to improve the pulse shape by matching the impedance at the end of the central conductor to the impedance of the measuring circuit. The circuit shown in Figure 7 reported by Rakoshdas illustrates this development.  The waveforms obtained from this circuit, as seen in Figure 8, show improvement, however, some undesirable oscillations are evident on the tail of the corona pulses. FIGURE 6
  • 17.  An attempt has been made in 1963 by Reinsborugh to terminate the cylinder at both ends using the arrangement shown in Figure 9.  The circuit showed some promise, however, difficulties in achieving purely resistive terminations with low inductance could not be entirely overcome and the results were not completely satisfactory as seen in Figure 10. FIGURE 9 FIGURE 10
  • 18. 5. THE NEW CIRCUIT  The methods described in Section IV employed various forms of impedance matching circuitry, however, the impedance discontinuity at the ends of the outer cylinder could not be entirely overcome. The circuit technique illustrated in Figures 11 and 12 provides the required reflection-free path. FIGURE 11 FIGURE 12
  • 19.  As can be seen, the transmission line, connecting the corona-generating electrode to the measuring instrument, is terminated in its characteristic impedance and connected directly to the point in Figure 11 or the internal conductor in Figure 12, within the cylindrical configuration.  The output of the coaxial point circuit is shown in the oscillogram of Figure 13. It can be seen that the waveforms are essentially reflection free, and display a rise time of 5 ns. This rise time is the lowest observed thus far for a negative corona pulse. FIGURE 13
  • 20.  The developed system was also used to display the circuit current resulting from a positive corona discharge. The result is shown in Figure 14.  The stray capacitance of the point to ground (geometry of Figure 11) was measured to be 0.5 pF . Using equations (2) and (3), the rise time and the frequency response are calculated to be: 𝑇𝑟=.0275ns 𝐹1=12700MHz FIGURE 14
  • 21.  For the measurements reported in Figures 13 and 14, a Tektronix type 585 oscilloscope, having a specified bandwidth of 85 MHz and a measured rise time of 4 ns, as shown in Figure 15, was used.  The observation suggests that the actual rise time of negative corona pulses may be below the observed value of 5 ns.  The measuring circuit itself is most satisfactory for the study of high voltage corona pulses of both polarities. FIGURE 15
  • 22. 6. CONCLUSION  The developed pulse-measuring circuit has an estimated rise time of better than 30ps and the corresponding bandwidth of 12.7 GHz.  Consequently the display instrument used, a Tektronix 585 oscilloscope, type 82 plug-in, having a bandwidth of only 85 MHz, was the limiting element in the developed system.  With the system limitation of 85 MHz, it was possible to faithfully observe the current waveform associated with the discharge process of positive corona, however, there is evidence that faster rise time oscilloscopes with millivolt sensitivity, are required for correct reproduction of electrode currents caused by negative corona discharges.