1. TAZ Engineering & Trading Co. Ltd
3rd Floor, Kim Thanh Building, No.13, Street 3, Binh An Ward, District 2, Ho Chi Minh City, Vietnam
Phone: (+84)28 36361901 Email: salessgn01@tazetco.com
Website: www.tazetco.com
5. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
• Introduction Overview
• Pre-Engineered System
• UL 300
• R-102 Fire Suppression System
• Related Codes & Standards
• Product & System Liability
Introduction
6. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
Pre-engineered System (NFPA 17A)
A-2.9.2, Pre-engineered systems do not need
calculations for flow-rate, pressure drop, and nozzle
pressure since they have been tested for fire
extinguishment with minimum and maximum piping
limitations.
These limitations have been (PERFORMANCE TESTED)
& verified by testing laboratories (UL) and are
published in the manufacturer’s (UL 300) listed
installation and maintenance manual (Part No. 418087)
7. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
Pre-engineered System (UL 300)
The UL 300 approved Ansul R-102 Fire Suppression
System has specific pipe sizes with maximum number
of fittings.
The system also includes maximum and minimum pipe
lengths, numbers of fittings, temperatures, discharge
heights, and number and types of nozzles needed for
each hazard.
8. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
Pre-engineered System (UL 300)
The hazards protected by the R-102 system are
specifically limited as to type and size based on actual
fire tests, splash tests, and flow testing.
All approved hazard protection & piping & nozzle
configurations are contained in the UL 300 listed R-102
Design, Installation, and Maintenance manual (Part No.
418087), UL File Number (UN EX 2470).
9. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
NFPA 10
Standard for
Portable
Fire
Extinguishers
XXXX Edition
NFPA 17A
Standard for
Wet Chemical
Extinguishing
Systems
XXXX Edition
NFPA 96
Standard for
Ventilation Control
and Fire Protection
of Commercial
Cooking Operations
XXXX Edition
• DESIGN
• INSTALLATION
• OPERATION
• TESTING
• MAINTENANCE
Codes & Standards
10. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
NFPA 17A
Standard for
Wet Chemical
Extinguishing
Systems
XXXX Edition
NFPA 17A
1. Administration
2. Reference Publications
3. Definitions
4. Components
5. System Requirements
6. Plans & Acceptance Tests
7. Inspection, Maintenance, &
Recharging
A. Appendix
Codes & Standards
11. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
NFPA 96
Chapter 10
Specifically Addresses Fire
Extinguishing Systems &
Hand Portables
Chapter 11
Addresses Fire
Extinguishing System
Maintenance
Chapter 13 & 14
Addresses Fire Protection for
Recirculating Systems & Solid
Fuel Cooking Operations
NFPA 96
Standard for
Wet Chemical
Extinguishing
Systems
XXXX Edition
Codes & Standards
12. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
NFPA 96
Chapter 12.1.2.2
Cooking appliances requiring protection shall
not be moved, modified, or rearranged without
prior re-evaluation of the fire-extinguishing
system by the system installer or servicing
agent, unless otherwise allowed by the design
of the fire-extinguishing system.
NFPA 96
Standard for
Wet Chemical
Extinguishing
Systems
XXXX Edition
Codes & Standards
13. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
NFPA 10
Standard for
Portable
Fire
Extinguishers
XXXX Edition
NFPA 10
1. Administration
2. Referenced Publications
3. Definitions
4. Selection of Fire
Extinguishers
5. Distribution of Fire
Extinguishers
6. Inspection, Maintenance, &
Recharging
7. Hydrostatic Testing
A. Appendix
Codes & Standards
14. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
Codes & Standards
Hand Portable Extinguishers
NFPA 10
5.7 Fire Extinguisher Size and
Placement for Class K Fires
Class K fire extinguishers shall be
provided for hazards where there is a
potential for fires involving combustible
cooking media (vegetable or animal oils
and fats).
18. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
• Commercially Available Gas
Fryer With 12 oF/Minute Min. Heat
Rate ( During 500 oF - 600 oF)
• Vegetable Oil To Be Used
• Auto-ignition 685 oF Min.
• 2 Minute Pre-burn With Fuel On
• Cooling Rate Not To Exceed
5oF/Minute With No Re-ignition
for 20 Minutes
UL 300 Revisions - Fryers
40. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
2. Heat, generated from the fire, follows the air flow into
the plenum, transfers to the fusible link causing it to
separate, resulting in slack in the detection cable.
R-102 Fire Suppression
Sequence Of Operation
41. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
3. Spring tension trips the AUTOMAN
Regulated Release Mechanism,
puncturing a seal in the cartridge. N2
or CO2 flows from the cartridge and
pressurizes the tank.
R-102 Fire Suppression
Sequence Of Operation
42. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
4. N2 or CO2 gas pressurizes the tank, causing
agent to discharge through piping & nozzles
into pre-determined hazard areas.
R-102 Fire Suppression
Sequence Of Operation
43. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
5. Gas pressure from the cartridge, and/or
a snap action switch may operate or
de-energize other equipment.
R-102 Fire Suppression
Sequence Of Operation
48. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
Additional ANSUL
AUTOMAN Functions
• Fusible Link Detection
• Manual Pull Station
• Electric & Gas Shutoff
Manual Pull Station
Fusible Link Detection
Gas Shutoff
Electrical Shutoff
Components
54. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
24 VDC Electrical Regulated
Release - ULC Only!
• 24 VDC Electric Solenoid
• Uses The Release Mechanism
From the ANSUL AUTOMAN IIC
• Can Be Used With a Control
Panel In Accordance With
NFPA 72
Components
55. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
Double Tank System
• Add-On 1.5 or 3 Gallon Tank In Stainless Steel Enclosure or
Painted Bracket (Packaged Separately)
• (1) Add-On Tank Connected to Regulator in ANSUL AUTOMAN
Regulated Release or Regulated Actuator Assembly
Components
56. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
Double Tank System
• Add-On 1.5 or 3 Gallon Tank In Stainless Steel Enclosure or Painted
Bracket (Packaged Separately)
• (1) Add-On Tank Connected to Regulator in ANSUL AUTOMAN Regulated
Release or Regulated Actuator Assembly
Add-On Tank In
Enclosure or
Bracket
Components
57. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
Multiple Tank System (Three or More Tanks)
• (1) Regulated Actuator Assembly
• Up to (2) Regulated Actuator Assemblies can be used with an ANSUL
AUTOMAN Regulated Release Assembly
• Each Regulated Actuator Can Accommodate Up To (3) Three Gallon Tanks
Components
59. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
Actuation
Line
Expellant
Gas Line
Expellant / Actuation Gas Piping
Max. (2) Regulated Actuators
Assemblies Per AUTOMAN Regulated
Release Assembly = (8) Tanks
Components
60. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
ANSUL AUTOMAN -
Cartridge Receiver
Regulated Actuator Assembly
• Must Be Connected To High
Pressure Side of ANSUL AUTOMAN
Regulated Release Mechanism
Components
62. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
Double Tank Enclosure
Three-Tank System
• (1) Double Tank Enclosure Assembly
Utilizing (2) Three Gallon Tanks
• Both Add-On Tanks Connected to
Regulator in ANSUL AUTOMAN
Regulated Release or Regulated
Actuator Assembly
Components
66. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
Agent Storage Tank Label
& Manufacturing Date
Manufacturing Date
The R-102 Tank Label
Indicates That The System
Meets The Requirements Of
UL 300, NFPA 17A, & NFPA 96
Components
70. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
Expellant / Actuation Gas Piping
• Up To (5) Remote Release Assemblies
Can Be Used To Actuate Up To (5)
Regulated Actuators = 15 Tanks
Maximum
Actuation Line
o
o
Components
71. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
CO2 And N2 Cartridges
• Used as Expellant Gas to
Pressurize and Discharge
Agent From Each Tank.
• Also Used for Actuation
Pressure When Additional
Regulated Actuators Are
Needed
Components
83. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
Schedule 40
• Black Iron
• Chrome Plated
• Stainless Steel
• Hot-Dipped Galvanized (Actuation &
Expellant ONLY)
Pipe & Fittings
• Distribution Piping - 3/8” NPT
• Actuation & Expellant Gas
Piping - 1/4” NPT
Components
84. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
Additional Regulated
Release Functions:
• Fusible Link Detection
• Manual Pull Station
• Electric & Gas Shutoff
Manual Pull Station
Fusible Link Detection
Gas Shutoff
Components
92. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
Conduit Offset Assembly
• Change Direction of Wire
Rope
• Release Assembly Only
• 1/2” EMT Conduit
• Can Only Be Used With High
Temperature Pulley Elbows
Components
94. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
Remote Pull Station
• Available With or Without 50 ft.
of Stainless Steel Cable
• Optional Aluminum Trim Ring
is Available
• Required for Manual Actuation
• Installed at Point of Egress
Components
100. www.tazetco.com
Fire Protection
Solutions
TAZ Engineering & Trading Co., Ltd
COM
NC
NO
Electrical Switches
• Alarm Initiating Switch
(Use With Fire Alarm Control
Panels To Meet NFPA 72
Supervision Requirements)
Screw
Terminals
Components