A liquid, gas, or solid that exhibits
explosive flammable characteristics such
as LPG, butane, gunpowder, paint storage,
fuel, oil, etc.
Tyco Fire & Building Products is a leading
manufacturer and distributor of water-based fire
suppression systems and components for special hazard
risks, offering one of the broadest lines of fire
protection system equipment worldwide for Special
Hazard Systems to meet your needs.
Our complete line of standard sprinklers have a
fantastic record of performance, consistency, and
dependability. However, many plants and buildings
contain fire hazards that standard automatic sprinklers
cannot control or extinguish. These are termed
"Special Hazards". In general, a special hazard is an
area, process, piece of equipment, or building that a
normal sprinkler system will not effectively protect.
Generally the following “Special Hazards” fall under these criteria:
Special Hazards systems are sometimes found
within plants or areas that are protected by
traditional sprinkler systems. With the advent of
new and different synthetics, sophisticated paint
lines, flammable liquid handling, and critical
process equipment, the risk of serious fire scenarios
looms greater and greater. These circumstances
dictate the need for Special Hazards protection. A
company should never assume that they do not
have a high hazard that requires additional special
hazards protection.
Tyco Fire & Building Products is available
worldwide under the leading brand names:
CENTRAL®
, GEM®
, STAR™
, and GRINNELL®
.
3
The nature of a piece of equipment that is a hazard,
or exposes nearby vital equipment, personnel, or
structures to a fire risk. Examples are cooling
towers, process pumps, transformers, mill stands,
storage tanks, turbines, conveyors, etc.
NOZZLES & NOZZLE
ACCESSORIES. . . . . . . . . . . . . 6
RED-E CABINET®
. . . . . . . . . 9
SINGLE INTERLOCK
PREACTION SYSTEMS . . . . . . 10
DOUBLE INTERLOCK
PREACTION SYSTEMS . . . . . . 11
DELUGE VALVE &
DELUGE SYSTEMS . . . . . . . . 12
DELUGE VALVES . . . . . . . . . 13
AQUAMIST®
SYSTEMS & NOZZLES. . . . . . 14
4 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.
Breadth of Line
Tyco Fire & Building Products (TFBP) offers more than 250 fire protection
products and over 1,200 items used in the fabrication of fire protection
systems, including sprinklers, nozzles, valves, devices, CPVC pipe, fittings and
hangers, and sprinkler system accessories.
Research and Development
TFBP is backed by one of the largest research, design, development
group and facilities in the industry. Our experienced staff of
engineers is continually working to develop new types of sprinklers
and valves, as well as special hazard fire protection devices to fill
present and future market needs. TFBP customers can contact
R&D directly for technical assistance in unusual applications that
are outside our literature or existing situations.
Listings and Approvals
Products offered by TFBP are listed and approved by various fire
protection product approval laboratories and organizations. General
listing and approval information for the following organizations is
provided for each product in the specification charts. Refer to the application
Technical Data Sheets for specific listing and approval information.
Customer Service
Serving a diverse group of specifiers, including architects, engineers,
contractors, and associated industries, TFBP distributes its manufactured
products through TFBP locations and independent distributors that are strate-
gically located to provide our customers with the quickest delivery possible of
their complete order.
Leadership
TFBP offers the widest selection of special hazards
nozzles and valve packages. TFBP is committed to
continuing our role as a leader in the development,
manufacture, and marketing of quality fire protection
products.
Underwriters
Laboratories Inc.
Underwriters
Laboratories Inc.
for use in Canada
Underwriters
Laboratories Inc.
of Canada
Scientific
Services
Laboratory
Verband der
Schadenversicherer
Factory Mutual
Research
Corporation
Loss Prevention
Certification Board
in association with
AB & Lloyds
FM
5
Power Plants
Chemical Plants
Offshore Platforms
Aircraft Hangars
Cooling Towers
Computer Rooms
Switchgear Rooms
Transformers
Wet Benches
Ammunition Plants
Engine Test Cells
LPG Storage
Spray Paint Booths
Battery Rooms
Oil Quenching Pits
Petrochemical Storage
Records Vaults
Electronic/Telephone Rooms
Solvent Tanks and Storage
Shipboard Machinery Rooms
Flammable Liquid Storage
Hydraulic Oil, Lubricating Oil Rooms
Tank Farm/Truck Loading Facility
6 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.
Nozzles & Nozzle Accessories
are designed for use in a variety of special
hazards applications. Their uses include, but
are not limited to, exposure protection, fire
control, fire extinguishment, and explosion
prevention. Many types of nozzles may be
required to provide a properly designed
special hazard fire protection system.
D-3 Protectospray®
Nozzle
• Open orifice design for use in
deluge systems
• Nozzles are external deflector
types that discharge a filled cone
of water droplets at relatively
low velocity
• Spray angles available:
65°, 80°, 95°, 110°, 125°, 140°,
160°, and 180°
• UL, ULC, FM, LPCB, SSL
K=1.2 (17,3) • K=1.8 (25,9) 
K=2.3 (33,1) • K=3.0 (43,2)
K=4.1 (59,0) • K=5.6 (80,6)
K=7.2 (108,7)
1/2" 
 (15 mm)
Natural brass, chrome plated,
electroless nickel plated, lead
coated or Teflon coated.
Stainless steel, plain only.
K Factor

Thread Size
Finish

Tech Data TD620A
EA-1 Automatic Protectospray®
Nozzle
• Bulb type frangible element for
use in closed head systems
• Discharges a filled cone of
water droplets at relatively low
velocity
• Spray angles available:
65°, 80°, 95°, 110°, 125°, 140°,
160°, and 180°
• UL, ULC, FM, SSL
K=1.4 (20,2) • K=2.8 (40,3)
K=5.6 (80,6) 
1/2" 
 (15 mm)
Natural brass finish or chrome
plated finish in 135˚F/57˚C
through 500˚F/57˚C;
Corroproof® or lead coated in
135˚F/57˚C and
175˚F/79˚C
K Factor

Thread Size
Finish

Tech Data TD610A
Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. 7
F822 through F834 MULSIFYRE®
Nozzles
• Open, internal scroll type nozzles
• Six different orifice sizes and
spray angles afford a variety of design
options
K=2.3 (33,1) • K=2.6 (37,4)
K=2.7 (38,9) • K=4.6 (66,2)
K=5.1 (73,4) • 
3/4" (20 mm)
Natural Brass, Chrome Plated
K Factor

Thread Size
Finish
Tech Data TD675
• Designed to discharge a filled
cone of water droplets at a
relatively high velocity
• Used in either open or water
primed systems
• A blow-off cap is available with
the nozzle for a primed system
(chrome plated finish only)
• UL, ULC, FM
HV “High Velocity” Spray Nozzles
• Open, directional spray nozzles
• Designed for use in fixed water spray fire
protection systems where a high velocity
water application is needed, such as the
protection of flammable liquids, electrical
transformers, circuit breakers, oil-fired
boilers and lube oil systems
K=1.6 (23,0) • K=1.8 (26,0)
K=2.9 (41,8) • K=4.3 (62,0)
K=5.5 (79,2) • K=6.0 (86,4) 
1" 
 (30 mm) 
1 1/4" (38 mm) only K=6.0
Natural brass or stainless steel
K Factor

Thread Size

Finish
Tech Data TD680
• Available in six different orifice
sizes
• Produces a solid conical spray
pattern
• Available in six angle spray
patterns
• UL, ULC, FM, SSL
• Air aspirating foam-water nozzles
• For use with all types of foam
(required for Non-AFFF type
foams)
• Pendent & upright designs
• Open nozzle for use on foam-
water sprinkler systems
• UL
B-1 Foam-Water Sprinkler
K=3.0 (42,2)
1/2" 
 (15 mm) 
Brass
K Factor
Thread Size
Finish

Tech Data TD760
8 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.
F800 Nozzles
• Specifically designed to spray a
water pattern
• Typical application: F800 Nozzles
are used to protect the tops of
transformers and may also be used
in areas such as between rollers of
multi-tiered dryers
• Offered in a variety of orifices
• UL, FM
TI-MAX®
Nozzles & Sprinklers
Contact a TFBP distributor for details
• Unique discharge devices are made from
titanium and can be used in offshore and other
marine applications
• Designed for use where strength, low weight,
and salt water corrosion resistance are required
• Medium and high velocity type nozzles are
available in various orifice sizes and spray angles
• Standard spray sprinklers are available in upright
and pendent configurations
• Deluge valves, alarm valve, thermal valve, and
shutoff valve all produced from titanium which
is 45% lighter than steel
Cooling Tower Nozzles Type 1 and 2
• Intended for use in fire protection
systems for cross flow cooling
towers with combustible fill sections
• Open nozzle design for use in water
spray deluge system
• Installed under the distribution
basin, they discharge water in a
relatively narrow, elongated spray
pattern
• Type 1 has a waterway designed for
use in towers with diffusion decks,
Type 2 for those without diffusion
decks
• UL, FM
K=2.9 (41,8)
3/4" (20 mm)
K Factor
Thread Size
Tech Data TD730
K=1.8 (26,0)
K=2.6 (37,4)
K=4.1 (59,0)
1/2" 
 (15 mm) 
K Factor

Thread Size
Tech Data TD750
Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. 9
RED-E CABINET®
Integrated Fire Protection Packages
Tech Data TD1110
• Complete riser assembly enclosed
within a free-standing cabinet
• Package is preassembled with all
trim installed and electric switches
prewired, making the connections
for power, local, remote alarms, and
other external electrical functions
the only electrical connections
needed to complete the installation
• Cabinet is constructed from 14
gauge steel
• Door is hinged for easy access
• Windows are provided for viewing
system gauges and other functions
• Grooved connections are provided
on the supply and discharge sides
of the valve assembly for easy
connections to the supply and
system piping
• Available in deluge, single, and
double interlocked preaction system
configurations in a variety of valve
sizes
• Electrical control panel for the
systems is normally a Potter 4410
releasing panel, but other controls
are available upon request
• Can be piped from either
side for supply and drain
functions
• Discharge is vertical
• Available with DV-1,
DV-3, and DV-5 valves
• Listings and Approvals:
All components -
UL, C-UL, ULC, and FM
The aesthetically pleasing RED-E CABINET
provides all the mechanical controls, valves,
and electrical detection and actuation controls
in one unit for ease of installation.
Single interlock preaction systems are used to
protect areas where there is danger of serious water
damage that might result from damaged automatic
sprinklers or piping. Typically, such areas include
computer rooms, storage areas for valuable
artifacts, libraries and archives. Also, preaction
systems are effectively used to protect properties
where a prealarm of a possible fire condition may
allow time for fire extinguishment by alternate
suppression means, prior to a sprinkler discharge.
In the event the fire cannot otherwise be
extinguished, the preaction sprinkler system will
then perform as the primary fire protection system.
Single interlock preaction systems employ
automatic sprinklers attached to a piping system
containing 10 psi (0,7 bar) supervisory pressure,
with a supplemental electric fire detection system
installed in the same area as the sprinklers.
Preaction systems with 10 psi (0,7 bar) supervisory
pressure may also be activated by either wet or dry
pilot sprinklers instead of electric detectors.
Actuation of the fire detection system from a fire
opens the deluge valve, allowing water to flow into
the sprinkler piping system and to be discharged
only from those sprinklers that have been operated
by heat over the fire. Loss of supervisory pressure
from the system piping as a result of damaged
sprinklers or broken piping will activate a trouble
alarm to indicate impairment of the system. The
deluge valve will not open due to loss of
supervisory pressure.
Available with:
• DV-5 Valve (TFP1305)
• DV-1 Valve (TFP1330)
• DV-3 Valve (TFP1350)
10 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.
Trim Assemblies
WET PILOT DRY PILOT ELEC. ACTUATION
DV-5 TFP1410 TFP1415 TFP1420
DV-1 TD1125 TD1125 TD1125
DV-3 TD1120 TD1120 TD1120
Water Pressure
Atmospheric Pressure
Air Pressure
Automatic Sprinklers
Gate Valve

Water Motor
Alarm
Deluge Valve
w/Single Interlock Trim
Fire Alarm
Bell
Waterflow
Pressure Alarm
Switch
Electric
Releasing
Panel
Electric Detectors
Electric 
Manual Control
Station(s)
Low Air Pressure
Alarm Switch

Air/Nitrogen
Maintenance
Device
Solenoid Valve
normally closed

Check Valve
Single Interlock Preaction Systems Electric Shown
Double interlock preaction systems are designed
for applications such as refrigerated areas that require
the maximum degree of protection against an
inadvertent operation that could result in
unnecessary flooding of the sprinkler system piping.
The double interlock system consists of a deluge
valve and swing check valve with releasing trim
featuring both a solenoid valve and a dry pilot
actuator in a series configuration. The swing check
valve isolates the body of the deluge valve from the
system air or nitrogen pressure that holds the dry
pilot actuator closed. The solenoid valve remains
closed until it is electrically energized by a deluge
releasing panel that responds to the operation of a
fire detection device.
In order to actuate the double interlock preaction
system, two independent events, caused by a fire
condition, must occur. The sprinkler system piping
must lose air or nitrogen pressure due to the
operation of one or more sprinklers, and the deluge
releasing panel must energize and open the
solenoid valve upon the operation of a fire
detection device.
The double interlock system will operate only
when both the dry pilot actuator and the solenoid
valve are open at the same time. Opening of the
dry pilot actuator only (for example: a forklift
truck accidentally dislodges a sprinkler) or of the
solenoid valve only (for example: accidental
operation of an electric manual pull station) will
cause an alarm, and will not trip the system or
flood the sprinkler system piping.
Available with:
• DV-5 Valve (TFP1305)
• DV-1 Valve (TFP1330)
• DV-3 Valve (TFP1350)
Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. 11
Trim Assemblies
ELEC./ELEC. ELEC./PNEUM.
ACTUATION ACTUATION
DV-5 TFP1465 TFP1460
DV-1 TD1153 TD1151
DV-3 TD1148 TD1146
Automatic Sprinklers
Gate Valve

Water Motor
Alarm
Deluge Valve
w/Double Interlock Trim
Fire Alarm
Bell
Dry Pilot Actuator
normally closed
Waterflow
Pressure Alarm
Switch
Double Interlock
Electric
Releasing
Panel

Electric Detectors
Electric 
Manual Control
Station(s)
Low Air Pressure
Alarm Switch
Air/Nitrogen
Maintenance
Device
Solenoid Valve
normally closed

Check Valve
Water Pressure
Atmospheric Pressure
Air Pressure
System Shut-Off Valve
Double Interlock Preaction Systems Pneumatic/Electric Shown
12 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.
The “deluge valve” is the automatic water control
valve that is used to control water flow into deluge,
preaction, and special types of fire protection systems in
response to a fire.
Deluge fire protection systems are normally used in
special hazard installations where an entire area
application of water is required for protection. Typical
applications may include flammable liquid handling
and storage areas, aircraft hangars, and other high-
hazard installations where water is the most effective
extinguishing agent. Deluge systems employ open
sprinklers or spray nozzles attached to a piping system.
The system is connected to a water supply through the
deluge valve. This valve is opened by the operation of a
fire detection system installed in the same areas as the
open sprinklers or nozzles. Deluge systems may be
activated by wet or dry pilot sprinklers, or electric
detectors. When the deluge valve opens, water flows
into the piping system and discharges from all open
sprinklers and nozzles.
Trim Assemblies
WET PILOT DRY PILOT ELEC. ACTUATION
DV-5 TFP1310 TFP1315 TFP1320
DV-1 TFP1330 TFP1330 TFP1330
DV-3 TFP1350 TFP1350 TFP1350
Deluge Valve  Deluge Systems Electric Shown
DV-5 Deluge Valve, External Resetting Diaphragm Style – 1-1/2 through 8
Tech Data TFP1305
• Available sizes:1-1/2 (DN40), 2 (DN50),
3 (DN80), 4 (DN100), 6 (DN150),
8 (DN200)
• Vertical or horizontal installation
• One internal working part
• No linkage or clapper assembly
• Light weight ductile iron body
• Available with deluge and single  double
interlock preaction trim
• Internally  externally coated
• Features external resetting
• Diaphragm operation
• For most seawater  brackish
water supplies for deluge systems
• For deluge, preaction  foam
systems
• Available as Flange x Flange,
Flange x Groove, or
Groove x Groove body styles
• Rated for 250 psi (17,2 bar) service
• Listings and Approvals:
UL, C-UL, and FM
DV-1™
External Resetting Deluge Valve – 4  6
Tech Data TFP1330
• Available sizes:
4 (DN100) and 6 (DN150)
• Used as a system control valve in deluge,
and single and double interlock preaction
systems
• Can be reset externally without having to
remove the hand-hole cover and unlatch the
waterway clapper
• Positive mechanical latching style valve
• Available with three actuation
trim arrangements: wet pilot, dry
pilot, and electric
• Single and double interlock
preaction trims available
• Rated for 175 psi (12.1 bar)
maximum service pressure
• Listings and Approvals:
UL, ULC, FM, LPC, and SSL
DV-3™
Deluge Valve, Automatic Resetting – 2-1/2
Tech Data TFP1350
• 2-1/2 (DN65), right angle type deluge
valves
• Available with either a grooved or threaded
inlet and outlet
• For use as a control valve in deluge, or
single or double interlock preaction systems
• Can be reset externally without having to
open a hand-hole cover to manually unlatch
and set the center valve
• Trim arrangements provide wet
pilot, dry pilot, and electric
actuation
• Valves may be installed with the
outlet facing either left or right
• DV-3 (F445) – 175 psi (12,1 bar)
DV-3 (F446) – 250 psi (17,2 bar)
• Listings and Approvals:
UL, ULC, FM, LPC, and SSL.
CV-1F Riser Check Valve
Tech Data TFP950
• Available sizes: 2 through 8
(DN65) through (DN200)
• Intended for use in a preaction
system riser
• Furnished with grooved ends that are
compatible with grooved pipe and
couplings
• Can be installed with ANSI class
150 or 300 Flanges utilizing
flange adapters
• Designed with a removable cover
for ease of field maintenance
• Standard seal is grade “E” EPDM
• Maximum rated working pressure
is 300 psi (20,68 bar)
Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. 13
14 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.
AQUAMIST®
Systems utilize the newest and most
unique nozzles developed and approved for fire protection.
They offer an alternative to gas systems, foam systems, or
heavy density sprinkler systems. By utilizing a higher
pressure than a normal sprinkler system, but a 50-80%
lower water flow, the AquaMist Systems use less water
more effectively, reduce costs in pipe sizing and labor, and
minimize cleanup and water damage.
a) By using smaller droplet sizes, a larger droplet surface area to
volume is created. This larger surface area allows heat
extraction (evaporation).
b) Vapor is created that displaces, removes, and excludes oxygen
from the fire tetrahedral equation.
c) Flammable vapors are diluted by the entrainment of water
vapor, to the extent that the flammable vapor will not burn.
d) Larger droplets are designed to penetrate the fire plume and
cool the combustibles similar to a standard sprinkler system.
e) The suspended mist will cool and “pre-wet” other
combustibles in the area and cool any fuels and gases.
AquaMist Systems are used in total compartmentalized areas and
are pre-engineered systems that have specific guidelines as to the
availability of installation, design, and components. With the
advent of the publication of NFPA 750, the introduction and
awareness of mist technology has never been higher. These pages
highlight some of the products available in the AquaMist product
line from TFBP…the innovative leader in fire protection.
Typical Gas Turbine
Generator Room
AquaMist Systems operate differently from normal sprinkler or gaseous systems as follows:
3
PFC4410 –
Single zone, cross
zone, or sequential
cross zone releasing
panel
2
Variable Pressure
AquaMist Fire Pump
1
DV-5 Deluge Valve
4
Fire Pump Controller 5
Required Outlet Strainer –
The pipe, fittings, hangers and
AquaMist nozzles are to be
connected to the strainer outlet.
To System
Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design
parameters, installation instructions, care and maintenance guidelines, and our limited warranty. 15
AM10 AQUAMIST®
Open Type Mist Nozzle
AM4 AQUAMIST®
Open Type Mist Nozzle
• Open, directional spray nozzles
• Listed  Approved for the
protection of flammable liquid
hazards (UL/FM)
• Approved for protection of gas
turbines (FM)
• Maximum ceiling height,
26' 3 (8 m)
• Compartment volume
– UL - 56,500 ft3
(1,600 m3
)
– FM - 45,203 ft3
(1,280 m3
)
• Maximum utilization of water for
flammable liquid fire protection
• Nozzle coverage: maximum
172 ft2
(16 m2
)
• Nozzle pressure: 185 to 250 psi
(12,8 to 17,2 bar)
K=0.24 (3,5)
1/2 
 (15 mm) 
Stainless Steel
K Factor
Thread Size
Finish

Tech Data TD1173
AM15 AQUAMIST®
• Available for use in IMO Mandated
MSC 913 local application water
mist systems
• 0.33 gpm/psi0.5
• 175-250 psi
• 4.36 gpm @ 175 psi
Since the water droplet sizes are much
smaller, a larger surface area is created
to allow the water to absorb heat
more quickly than a conventional
sprinkler spray having larger
droplets.
The smaller droplets
will be suspended and
coat and cool any
combustibles in the room,
while pre-wetting the
combustibles and
thereby blocking them
from radiant heat.
The fire will receive the direct
impingement of the larger
droplets similar to a standard
sprinkler
• Open spray nozzles
• Designed for use in water mist
protection systems protecting
flammable liquids and turbine
bearings
• Minimal water demand,
approximately 3.1 GPM/nozzle at
170psi (11,73 lpm at 11,6 bar)
• Mist represents latest in fire
protection technology
• For use in “low pressure” mist
applications
• Minimum operating pressure is
170 psi (11,6 bar)
• Nozzle coverage: maximum
86 ft2
(8m2
)
• UL, FM
K=0.24 (3,5)
1/2 
 (15 mm) 
Stainless Steel
K Factor
Thread Size
Finish

Tech Data TD1174
When the mist comes in contact
with a fire, vapor (steam) is created
which displaces, and reduces the
oxygen level at the fire.
WORLDWIDE HEADQUARTERS
Tyco Fire  Building Products
451 N. Cannon Avenue
Lansdale, PA 19446
215-362-0700, 800-523-6512
Fax 215-362-5385
www.Tyco-Fire.com
UNITED STATES
Central Sprinkler Company
451 N. Cannon Avenue
Lansdale, PA 19446
215-362-0700, Fax 215-362-5385
Brea, CA: Tel: 714-993-6111, Fax 714-993-6043
Decatur, GA: Tel: 404-243-7336, Fax 404-244-7375
Norristown, PA: Tel: 610-239-9925, Fax 610-239-9936
Jessup, MD: Tel: 301-604-7133, Fax 301-604-7138
Carol Stream, IL: Tel: 630-871-7700, Fax 630-871-7464
Coppell, TX: Tel: 972-745-0043, Fax 972-745-8594
Kent, WA: Tel: 253-872-6030, Fax 253-872-6547
Avon, MA: Tel: 508-583-8447, Fax 508-583-0034
Pompano Beach, FL: Tel: 954-781-0866, Fax 954-781-1475
Murray UT: Tel: 801-269-0688, Fax 801-269-0733
Tigard, OR: Tel: 503-620-4203, Fax 503-620-3817
Parma, OH: Tel: 216-265-0505, Fax 216-265-8354
Kansas City, MO: Tel: 816-842-2424, Fax 816-842-4433
National Distribution Facility
PO Box 2806
Lubbock, TX 79408-2806
Gem Sprinkler Company  Star Sprinkler Inc.
7071 S. 13th Street, Ste. 103
Oak Creek, WI 53154
877-436-8926, Fax 877-866-9250
CANADA
Regional Headquarters
12-16715 Yonge Street, Suite 316
Newmarket, Ontario L3X 1X4
705-422-0010, Fax: 705-422-1396
© 2005 Tyco Fire Products LP. All rights reserved. /Printed in USA/TFP-SHz/2500/PP/07-05
LATIN AMERICA
Regional Headquarters
South America, Central America  Caribbean
1802 S.W. 2nd St.
Pompano Beach, FL 33069
954-781-0866, Fax 954-781-9330
Regional Headquarters - Mexico
Hamburgo 231A Piso 2
Colonia Juarez
Mexico, D.F. 06600 Mexico
525-55-2075766, Fax: 525-55-2077566
EUROPE  MIDDLE EAST
Regional Headquarters
Kopersteden 1, NL-7547 TJ Enschede
P.O. Box 198, 7500 AD
Enschede, The Netherlands
31-53-428-4444, Fax 31-53-428-3377
Stockport, UK: Tel: 44-161-477-1886, Fax 44-161-477-6729
Paris Nord II, France: Tel: 33-1-48-178-727 , Fax 33-1-48-178-720
Rodgau Germany: Tel: 49-6106-84455, Fax 49-6106-18177
Coslada Madrid, Spain: Tel: 34-1-669-3906, Fax 34-1-669-2018
Lørenskog, Norway: Tel: 47-67-91-77-00, Fax 47-67-91-77-15
Lammhult, Sweden: Tel: 46-472-269-980, Fax 46-472-269-989
Dublin, Ireland: Tel: 353-166-839-82, Fax 353-166-822-54
Bolzano,Italy: Tel: 39-0471-252-091, Fax 39-0471-254-058
Milano, Italy: Tel: 39-0293-548-736, Fax 39-0293-548-690
Dubai, United Arab Emirates: Tel: 971-488-38689, Fax 971-488-38674
Budapest, Hungary: Tel: 36-148-11-383, Fax 36-120-34-427
Wels/Thalheim, Austria: Tel: 43-072-42-65-054, Fax 43-072-42-74-393
ASIA
Regional Headquarters
No.45 Tuas Avenue 9,
Singapore 639189
Central Sprinkler Company
Singapore: 65- 6743-3212, Fax 65-6743-9181
Shanghai, China: 86-21-5868-3300, Fax 86-21-5868-1160
Beijing, China: 86-10-6515-6191, Fax 86-10-6515-6157
Chengdu, China: 86-28-689-9440, Fax 86-28-666-2538
Gem Sprinkler Company  Star Sprinkler Inc.
Singapore: 65-6861-1655, Fax 65-6861-1312
Kuala Lumpur, Malaysia: 60-3-8024-6773, Fax 60-3-8024-2180
Hong Kong: 852-2595-0686, Fax 852-2505-5826
Central, Gem, Star, Grinnell, G FOUNDED 1850 and Design, and Tyco are either
registered trademarks or trademarks of Tyco and/or its affiliates in the United
States and/or other countries. All other brand names, product names, or
trademarks belong to their respective owners. Tyco Fire  Building Products
reserves the right to change product design and specifications without notice.

More Related Content

What's hot

Fw pump basis nfpa
Fw pump basis   nfpaFw pump basis   nfpa
Fw pump basis nfpaKaruna karan
 
Fire Protection System Design
Fire Protection System DesignFire Protection System Design
Fire Protection System DesignMostafa Al Wakeel
 
Nfpa20 standard for the installation of stationary pumps for fire protection ...
Nfpa20 standard for the installation of stationary pumps for fire protection ...Nfpa20 standard for the installation of stationary pumps for fire protection ...
Nfpa20 standard for the installation of stationary pumps for fire protection ...Bowen Ngo
 
Fire hydrant system
Fire hydrant systemFire hydrant system
Fire hydrant systemFIRE KNOCK
 
Firewater pump presentation ntt
Firewater pump presentation nttFirewater pump presentation ntt
Firewater pump presentation nttThanh Tin Nguyen
 
Comparision between NFPA and TAc rules for Power plants
Comparision between NFPA and TAc rules for Power plantsComparision between NFPA and TAc rules for Power plants
Comparision between NFPA and TAc rules for Power plantsvakil jagdish
 
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptxFIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptxMEP ENGINEER'S SERVICES
 
Hazardous Area Classification
Hazardous Area ClassificationHazardous Area Classification
Hazardous Area Classificationguest81e1c7
 
Inspection, Testing and Maintenance of fire pump
Inspection, Testing and Maintenance of fire pumpInspection, Testing and Maintenance of fire pump
Inspection, Testing and Maintenance of fire pumpklsmani
 
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTFIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTMEP ENGINEER'S SERVICES
 
Basic training water based fire protection
Basic training  water based fire protectionBasic training  water based fire protection
Basic training water based fire protectionSabrul Jamil
 
Fire Protection Systems Unit-I
Fire Protection Systems Unit-IFire Protection Systems Unit-I
Fire Protection Systems Unit-IGAURAV. H .TANDON
 
Design of Sprinkler System and CO2 Total Flooding System of Given Plan I Gaur...
Design of Sprinkler System and CO2 Total Flooding System of Given Plan I Gaur...Design of Sprinkler System and CO2 Total Flooding System of Given Plan I Gaur...
Design of Sprinkler System and CO2 Total Flooding System of Given Plan I Gaur...Gaurav Singh Rajput
 
NFPA 2001,Clean Agent Fire Extinguishing Systems.pdf
NFPA 2001,Clean Agent Fire Extinguishing Systems.pdfNFPA 2001,Clean Agent Fire Extinguishing Systems.pdf
NFPA 2001,Clean Agent Fire Extinguishing Systems.pdfBhuiyan academy
 
Fire sprinkler systems
Fire sprinkler systemsFire sprinkler systems
Fire sprinkler systemsjosebolis
 

What's hot (20)

Fw pump basis nfpa
Fw pump basis   nfpaFw pump basis   nfpa
Fw pump basis nfpa
 
2. Hydrant System.pdf
2. Hydrant System.pdf2. Hydrant System.pdf
2. Hydrant System.pdf
 
Fire Protection System Design
Fire Protection System DesignFire Protection System Design
Fire Protection System Design
 
Wet Chemical vs. Water Sprinkler
Wet Chemical vs. Water SprinklerWet Chemical vs. Water Sprinkler
Wet Chemical vs. Water Sprinkler
 
Chapter 06
Chapter 06Chapter 06
Chapter 06
 
Nfpa20 standard for the installation of stationary pumps for fire protection ...
Nfpa20 standard for the installation of stationary pumps for fire protection ...Nfpa20 standard for the installation of stationary pumps for fire protection ...
Nfpa20 standard for the installation of stationary pumps for fire protection ...
 
Fire hydrant system
Fire hydrant systemFire hydrant system
Fire hydrant system
 
Firewater pump presentation ntt
Firewater pump presentation nttFirewater pump presentation ntt
Firewater pump presentation ntt
 
Comparision between NFPA and TAc rules for Power plants
Comparision between NFPA and TAc rules for Power plantsComparision between NFPA and TAc rules for Power plants
Comparision between NFPA and TAc rules for Power plants
 
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptxFIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
 
Hazardous Area Classification
Hazardous Area ClassificationHazardous Area Classification
Hazardous Area Classification
 
Inspection, Testing and Maintenance of fire pump
Inspection, Testing and Maintenance of fire pumpInspection, Testing and Maintenance of fire pump
Inspection, Testing and Maintenance of fire pump
 
fire fighting System
fire fighting Systemfire fighting System
fire fighting System
 
2 delugevalve a
2 delugevalve a2 delugevalve a
2 delugevalve a
 
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTFIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
 
Basic training water based fire protection
Basic training  water based fire protectionBasic training  water based fire protection
Basic training water based fire protection
 
Fire Protection Systems Unit-I
Fire Protection Systems Unit-IFire Protection Systems Unit-I
Fire Protection Systems Unit-I
 
Design of Sprinkler System and CO2 Total Flooding System of Given Plan I Gaur...
Design of Sprinkler System and CO2 Total Flooding System of Given Plan I Gaur...Design of Sprinkler System and CO2 Total Flooding System of Given Plan I Gaur...
Design of Sprinkler System and CO2 Total Flooding System of Given Plan I Gaur...
 
NFPA 2001,Clean Agent Fire Extinguishing Systems.pdf
NFPA 2001,Clean Agent Fire Extinguishing Systems.pdfNFPA 2001,Clean Agent Fire Extinguishing Systems.pdf
NFPA 2001,Clean Agent Fire Extinguishing Systems.pdf
 
Fire sprinkler systems
Fire sprinkler systemsFire sprinkler systems
Fire sprinkler systems
 

Similar to Turbine bearing fire fighting system

Tyco gen products
Tyco gen productsTyco gen products
Tyco gen productsHassan Tito
 
G & M Tex Brochure
G & M Tex Brochure G & M Tex Brochure
G & M Tex Brochure gmtex
 
Rocore overview web site version
Rocore overview   web site versionRocore overview   web site version
Rocore overview web site versionAnthony Coats
 
Abtech Hazardous Area Electrical Enclosures & Junction Boxes - High Voltage &...
Abtech Hazardous Area Electrical Enclosures & Junction Boxes - High Voltage &...Abtech Hazardous Area Electrical Enclosures & Junction Boxes - High Voltage &...
Abtech Hazardous Area Electrical Enclosures & Junction Boxes - High Voltage &...Thorne & Derrick International
 
Abtech - LV HV & Hazardous Area Electrical Enclosures and Junction Boxes
Abtech - LV HV & Hazardous Area Electrical Enclosures and Junction BoxesAbtech - LV HV & Hazardous Area Electrical Enclosures and Junction Boxes
Abtech - LV HV & Hazardous Area Electrical Enclosures and Junction BoxesThorne & Derrick International
 
Rsd engineering steam, superheated water and ethylene oxide (eto) steriliza...
Rsd engineering   steam, superheated water and ethylene oxide (eto) steriliza...Rsd engineering   steam, superheated water and ethylene oxide (eto) steriliza...
Rsd engineering steam, superheated water and ethylene oxide (eto) steriliza...cathy fernandez rendo
 
Product_Overview_04.05.2016_EN
Product_Overview_04.05.2016_ENProduct_Overview_04.05.2016_EN
Product_Overview_04.05.2016_ENTim Long
 
Tough performers - Industrial-grade Sensors for Extreme Conditions
Tough performers - Industrial-grade Sensors for Extreme ConditionsTough performers - Industrial-grade Sensors for Extreme Conditions
Tough performers - Industrial-grade Sensors for Extreme ConditionsManfred Muenzl
 
Introduction to Process Flares
Introduction to Process FlaresIntroduction to Process Flares
Introduction to Process FlaresKarl Kolmetz
 
Final 2017 Product Catalog
Final 2017 Product CatalogFinal 2017 Product Catalog
Final 2017 Product CatalogStephanie Wagner
 
Submicron brochure Teesing
Submicron brochure TeesingSubmicron brochure Teesing
Submicron brochure TeesingTeesing BV
 
Cortem Group Lighting and Signalling Catalogue - Hazardous Area Explosion Pr...
Cortem Group  Lighting and Signalling Catalogue - Hazardous Area Explosion Pr...Cortem Group  Lighting and Signalling Catalogue - Hazardous Area Explosion Pr...
Cortem Group Lighting and Signalling Catalogue - Hazardous Area Explosion Pr...Thorne & Derrick International
 
Techsil OverTEC 5FR
Techsil OverTEC 5FRTechsil OverTEC 5FR
Techsil OverTEC 5FRTechsil Ltd
 
Sealtec Metallic Gaskets from ERIKS
Sealtec Metallic Gaskets from ERIKSSealtec Metallic Gaskets from ERIKS
Sealtec Metallic Gaskets from ERIKSERIKS UK
 
Agitador Ekato Fluid Portrait
Agitador Ekato Fluid PortraitAgitador Ekato Fluid Portrait
Agitador Ekato Fluid PortraitVibropac
 

Similar to Turbine bearing fire fighting system (20)

Tyco gen products
Tyco gen productsTyco gen products
Tyco gen products
 
G & M Tex Brochure
G & M Tex Brochure G & M Tex Brochure
G & M Tex Brochure
 
Vam
VamVam
Vam
 
Product Catalog 2016
Product Catalog 2016Product Catalog 2016
Product Catalog 2016
 
Advanced Series
Advanced SeriesAdvanced Series
Advanced Series
 
Rocore overview web site version
Rocore overview   web site versionRocore overview   web site version
Rocore overview web site version
 
Abtech Hazardous Area Electrical Enclosures & Junction Boxes - High Voltage &...
Abtech Hazardous Area Electrical Enclosures & Junction Boxes - High Voltage &...Abtech Hazardous Area Electrical Enclosures & Junction Boxes - High Voltage &...
Abtech Hazardous Area Electrical Enclosures & Junction Boxes - High Voltage &...
 
Abtech - LV HV & Hazardous Area Electrical Enclosures and Junction Boxes
Abtech - LV HV & Hazardous Area Electrical Enclosures and Junction BoxesAbtech - LV HV & Hazardous Area Electrical Enclosures and Junction Boxes
Abtech - LV HV & Hazardous Area Electrical Enclosures and Junction Boxes
 
Rsd engineering steam, superheated water and ethylene oxide (eto) steriliza...
Rsd engineering   steam, superheated water and ethylene oxide (eto) steriliza...Rsd engineering   steam, superheated water and ethylene oxide (eto) steriliza...
Rsd engineering steam, superheated water and ethylene oxide (eto) steriliza...
 
Product_Overview_04.05.2016_EN
Product_Overview_04.05.2016_ENProduct_Overview_04.05.2016_EN
Product_Overview_04.05.2016_EN
 
unique-brochure final
unique-brochure finalunique-brochure final
unique-brochure final
 
Kammer Valve Product Overview - Control Valves
Kammer Valve Product Overview - Control ValvesKammer Valve Product Overview - Control Valves
Kammer Valve Product Overview - Control Valves
 
Tough performers - Industrial-grade Sensors for Extreme Conditions
Tough performers - Industrial-grade Sensors for Extreme ConditionsTough performers - Industrial-grade Sensors for Extreme Conditions
Tough performers - Industrial-grade Sensors for Extreme Conditions
 
Introduction to Process Flares
Introduction to Process FlaresIntroduction to Process Flares
Introduction to Process Flares
 
Final 2017 Product Catalog
Final 2017 Product CatalogFinal 2017 Product Catalog
Final 2017 Product Catalog
 
Submicron brochure Teesing
Submicron brochure TeesingSubmicron brochure Teesing
Submicron brochure Teesing
 
Cortem Group Lighting and Signalling Catalogue - Hazardous Area Explosion Pr...
Cortem Group  Lighting and Signalling Catalogue - Hazardous Area Explosion Pr...Cortem Group  Lighting and Signalling Catalogue - Hazardous Area Explosion Pr...
Cortem Group Lighting and Signalling Catalogue - Hazardous Area Explosion Pr...
 
Techsil OverTEC 5FR
Techsil OverTEC 5FRTechsil OverTEC 5FR
Techsil OverTEC 5FR
 
Sealtec Metallic Gaskets from ERIKS
Sealtec Metallic Gaskets from ERIKSSealtec Metallic Gaskets from ERIKS
Sealtec Metallic Gaskets from ERIKS
 
Agitador Ekato Fluid Portrait
Agitador Ekato Fluid PortraitAgitador Ekato Fluid Portrait
Agitador Ekato Fluid Portrait
 

More from Kamit Patel

Know how to solder and guide for Beginners
Know how to solder and guide for BeginnersKnow how to solder and guide for Beginners
Know how to solder and guide for BeginnersKamit Patel
 
anybus-gateways-wireless-concept.pdf
anybus-gateways-wireless-concept.pdfanybus-gateways-wireless-concept.pdf
anybus-gateways-wireless-concept.pdfKamit Patel
 
AB9006_Datasheet.pdf
AB9006_Datasheet.pdfAB9006_Datasheet.pdf
AB9006_Datasheet.pdfKamit Patel
 
MSC-300 series barriers.pdf
MSC-300 series barriers.pdfMSC-300 series barriers.pdf
MSC-300 series barriers.pdfKamit Patel
 
Enhanced pid pide
Enhanced pid pideEnhanced pid pide
Enhanced pid pideKamit Patel
 
Fire extinguisher chart
Fire extinguisher chartFire extinguisher chart
Fire extinguisher chartKamit Patel
 
Health and safety at work
Health and safety at workHealth and safety at work
Health and safety at workKamit Patel
 
Hazop guide to best practices
Hazop guide to best practicesHazop guide to best practices
Hazop guide to best practicesKamit Patel
 

More from Kamit Patel (10)

Know how to solder and guide for Beginners
Know how to solder and guide for BeginnersKnow how to solder and guide for Beginners
Know how to solder and guide for Beginners
 
anybus-gateways-wireless-concept.pdf
anybus-gateways-wireless-concept.pdfanybus-gateways-wireless-concept.pdf
anybus-gateways-wireless-concept.pdf
 
AB9006_Datasheet.pdf
AB9006_Datasheet.pdfAB9006_Datasheet.pdf
AB9006_Datasheet.pdf
 
MSC-300 series barriers.pdf
MSC-300 series barriers.pdfMSC-300 series barriers.pdf
MSC-300 series barriers.pdf
 
GP2000E.pdf
GP2000E.pdfGP2000E.pdf
GP2000E.pdf
 
Enhanced pid pide
Enhanced pid pideEnhanced pid pide
Enhanced pid pide
 
Anomaly
AnomalyAnomaly
Anomaly
 
Fire extinguisher chart
Fire extinguisher chartFire extinguisher chart
Fire extinguisher chart
 
Health and safety at work
Health and safety at workHealth and safety at work
Health and safety at work
 
Hazop guide to best practices
Hazop guide to best practicesHazop guide to best practices
Hazop guide to best practices
 

Recently uploaded

(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 

Recently uploaded (20)

(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 

Turbine bearing fire fighting system

  • 1.
  • 2. 2 A liquid, gas, or solid that exhibits explosive flammable characteristics such as LPG, butane, gunpowder, paint storage, fuel, oil, etc. Tyco Fire & Building Products is a leading manufacturer and distributor of water-based fire suppression systems and components for special hazard risks, offering one of the broadest lines of fire protection system equipment worldwide for Special Hazard Systems to meet your needs. Our complete line of standard sprinklers have a fantastic record of performance, consistency, and dependability. However, many plants and buildings contain fire hazards that standard automatic sprinklers cannot control or extinguish. These are termed "Special Hazards". In general, a special hazard is an area, process, piece of equipment, or building that a normal sprinkler system will not effectively protect. Generally the following “Special Hazards” fall under these criteria: Special Hazards systems are sometimes found within plants or areas that are protected by traditional sprinkler systems. With the advent of new and different synthetics, sophisticated paint lines, flammable liquid handling, and critical process equipment, the risk of serious fire scenarios looms greater and greater. These circumstances dictate the need for Special Hazards protection. A company should never assume that they do not have a high hazard that requires additional special hazards protection. Tyco Fire & Building Products is available worldwide under the leading brand names: CENTRAL® , GEM® , STAR™ , and GRINNELL® .
  • 3. 3 The nature of a piece of equipment that is a hazard, or exposes nearby vital equipment, personnel, or structures to a fire risk. Examples are cooling towers, process pumps, transformers, mill stands, storage tanks, turbines, conveyors, etc. NOZZLES & NOZZLE ACCESSORIES. . . . . . . . . . . . . 6 RED-E CABINET® . . . . . . . . . 9 SINGLE INTERLOCK PREACTION SYSTEMS . . . . . . 10 DOUBLE INTERLOCK PREACTION SYSTEMS . . . . . . 11 DELUGE VALVE & DELUGE SYSTEMS . . . . . . . . 12 DELUGE VALVES . . . . . . . . . 13 AQUAMIST® SYSTEMS & NOZZLES. . . . . . 14
  • 4. 4 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. Breadth of Line Tyco Fire & Building Products (TFBP) offers more than 250 fire protection products and over 1,200 items used in the fabrication of fire protection systems, including sprinklers, nozzles, valves, devices, CPVC pipe, fittings and hangers, and sprinkler system accessories. Research and Development TFBP is backed by one of the largest research, design, development group and facilities in the industry. Our experienced staff of engineers is continually working to develop new types of sprinklers and valves, as well as special hazard fire protection devices to fill present and future market needs. TFBP customers can contact R&D directly for technical assistance in unusual applications that are outside our literature or existing situations. Listings and Approvals Products offered by TFBP are listed and approved by various fire protection product approval laboratories and organizations. General listing and approval information for the following organizations is provided for each product in the specification charts. Refer to the application Technical Data Sheets for specific listing and approval information. Customer Service Serving a diverse group of specifiers, including architects, engineers, contractors, and associated industries, TFBP distributes its manufactured products through TFBP locations and independent distributors that are strate- gically located to provide our customers with the quickest delivery possible of their complete order. Leadership TFBP offers the widest selection of special hazards nozzles and valve packages. TFBP is committed to continuing our role as a leader in the development, manufacture, and marketing of quality fire protection products. Underwriters Laboratories Inc. Underwriters Laboratories Inc. for use in Canada Underwriters Laboratories Inc. of Canada Scientific Services Laboratory Verband der Schadenversicherer Factory Mutual Research Corporation Loss Prevention Certification Board in association with AB & Lloyds FM
  • 5. 5 Power Plants Chemical Plants Offshore Platforms Aircraft Hangars Cooling Towers Computer Rooms Switchgear Rooms Transformers Wet Benches Ammunition Plants Engine Test Cells LPG Storage Spray Paint Booths Battery Rooms Oil Quenching Pits Petrochemical Storage Records Vaults Electronic/Telephone Rooms Solvent Tanks and Storage Shipboard Machinery Rooms Flammable Liquid Storage Hydraulic Oil, Lubricating Oil Rooms Tank Farm/Truck Loading Facility
  • 6. 6 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. Nozzles & Nozzle Accessories are designed for use in a variety of special hazards applications. Their uses include, but are not limited to, exposure protection, fire control, fire extinguishment, and explosion prevention. Many types of nozzles may be required to provide a properly designed special hazard fire protection system. D-3 Protectospray® Nozzle • Open orifice design for use in deluge systems • Nozzles are external deflector types that discharge a filled cone of water droplets at relatively low velocity • Spray angles available: 65°, 80°, 95°, 110°, 125°, 140°, 160°, and 180° • UL, ULC, FM, LPCB, SSL K=1.2 (17,3) • K=1.8 (25,9) K=2.3 (33,1) • K=3.0 (43,2) K=4.1 (59,0) • K=5.6 (80,6) K=7.2 (108,7) 1/2" (15 mm) Natural brass, chrome plated, electroless nickel plated, lead coated or Teflon coated. Stainless steel, plain only. K Factor Thread Size Finish Tech Data TD620A EA-1 Automatic Protectospray® Nozzle • Bulb type frangible element for use in closed head systems • Discharges a filled cone of water droplets at relatively low velocity • Spray angles available: 65°, 80°, 95°, 110°, 125°, 140°, 160°, and 180° • UL, ULC, FM, SSL K=1.4 (20,2) • K=2.8 (40,3) K=5.6 (80,6) 1/2" (15 mm) Natural brass finish or chrome plated finish in 135˚F/57˚C through 500˚F/57˚C; Corroproof® or lead coated in 135˚F/57˚C and 175˚F/79˚C K Factor Thread Size Finish Tech Data TD610A
  • 7. Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. 7 F822 through F834 MULSIFYRE® Nozzles • Open, internal scroll type nozzles • Six different orifice sizes and spray angles afford a variety of design options K=2.3 (33,1) • K=2.6 (37,4) K=2.7 (38,9) • K=4.6 (66,2) K=5.1 (73,4) • 3/4" (20 mm) Natural Brass, Chrome Plated K Factor Thread Size Finish Tech Data TD675 • Designed to discharge a filled cone of water droplets at a relatively high velocity • Used in either open or water primed systems • A blow-off cap is available with the nozzle for a primed system (chrome plated finish only) • UL, ULC, FM HV “High Velocity” Spray Nozzles • Open, directional spray nozzles • Designed for use in fixed water spray fire protection systems where a high velocity water application is needed, such as the protection of flammable liquids, electrical transformers, circuit breakers, oil-fired boilers and lube oil systems K=1.6 (23,0) • K=1.8 (26,0) K=2.9 (41,8) • K=4.3 (62,0) K=5.5 (79,2) • K=6.0 (86,4) 1" (30 mm) 1 1/4" (38 mm) only K=6.0 Natural brass or stainless steel K Factor Thread Size Finish Tech Data TD680 • Available in six different orifice sizes • Produces a solid conical spray pattern • Available in six angle spray patterns • UL, ULC, FM, SSL • Air aspirating foam-water nozzles • For use with all types of foam (required for Non-AFFF type foams) • Pendent & upright designs • Open nozzle for use on foam- water sprinkler systems • UL B-1 Foam-Water Sprinkler K=3.0 (42,2) 1/2" (15 mm) Brass K Factor Thread Size Finish Tech Data TD760
  • 8. 8 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. F800 Nozzles • Specifically designed to spray a water pattern • Typical application: F800 Nozzles are used to protect the tops of transformers and may also be used in areas such as between rollers of multi-tiered dryers • Offered in a variety of orifices • UL, FM TI-MAX® Nozzles & Sprinklers Contact a TFBP distributor for details • Unique discharge devices are made from titanium and can be used in offshore and other marine applications • Designed for use where strength, low weight, and salt water corrosion resistance are required • Medium and high velocity type nozzles are available in various orifice sizes and spray angles • Standard spray sprinklers are available in upright and pendent configurations • Deluge valves, alarm valve, thermal valve, and shutoff valve all produced from titanium which is 45% lighter than steel Cooling Tower Nozzles Type 1 and 2 • Intended for use in fire protection systems for cross flow cooling towers with combustible fill sections • Open nozzle design for use in water spray deluge system • Installed under the distribution basin, they discharge water in a relatively narrow, elongated spray pattern • Type 1 has a waterway designed for use in towers with diffusion decks, Type 2 for those without diffusion decks • UL, FM K=2.9 (41,8) 3/4" (20 mm) K Factor Thread Size Tech Data TD730 K=1.8 (26,0) K=2.6 (37,4) K=4.1 (59,0) 1/2" (15 mm) K Factor Thread Size Tech Data TD750
  • 9. Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. 9 RED-E CABINET® Integrated Fire Protection Packages Tech Data TD1110 • Complete riser assembly enclosed within a free-standing cabinet • Package is preassembled with all trim installed and electric switches prewired, making the connections for power, local, remote alarms, and other external electrical functions the only electrical connections needed to complete the installation • Cabinet is constructed from 14 gauge steel • Door is hinged for easy access • Windows are provided for viewing system gauges and other functions • Grooved connections are provided on the supply and discharge sides of the valve assembly for easy connections to the supply and system piping • Available in deluge, single, and double interlocked preaction system configurations in a variety of valve sizes • Electrical control panel for the systems is normally a Potter 4410 releasing panel, but other controls are available upon request • Can be piped from either side for supply and drain functions • Discharge is vertical • Available with DV-1, DV-3, and DV-5 valves • Listings and Approvals: All components - UL, C-UL, ULC, and FM The aesthetically pleasing RED-E CABINET provides all the mechanical controls, valves, and electrical detection and actuation controls in one unit for ease of installation.
  • 10. Single interlock preaction systems are used to protect areas where there is danger of serious water damage that might result from damaged automatic sprinklers or piping. Typically, such areas include computer rooms, storage areas for valuable artifacts, libraries and archives. Also, preaction systems are effectively used to protect properties where a prealarm of a possible fire condition may allow time for fire extinguishment by alternate suppression means, prior to a sprinkler discharge. In the event the fire cannot otherwise be extinguished, the preaction sprinkler system will then perform as the primary fire protection system. Single interlock preaction systems employ automatic sprinklers attached to a piping system containing 10 psi (0,7 bar) supervisory pressure, with a supplemental electric fire detection system installed in the same area as the sprinklers. Preaction systems with 10 psi (0,7 bar) supervisory pressure may also be activated by either wet or dry pilot sprinklers instead of electric detectors. Actuation of the fire detection system from a fire opens the deluge valve, allowing water to flow into the sprinkler piping system and to be discharged only from those sprinklers that have been operated by heat over the fire. Loss of supervisory pressure from the system piping as a result of damaged sprinklers or broken piping will activate a trouble alarm to indicate impairment of the system. The deluge valve will not open due to loss of supervisory pressure. Available with: • DV-5 Valve (TFP1305) • DV-1 Valve (TFP1330) • DV-3 Valve (TFP1350) 10 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. Trim Assemblies WET PILOT DRY PILOT ELEC. ACTUATION DV-5 TFP1410 TFP1415 TFP1420 DV-1 TD1125 TD1125 TD1125 DV-3 TD1120 TD1120 TD1120 Water Pressure Atmospheric Pressure Air Pressure Automatic Sprinklers Gate Valve Water Motor Alarm Deluge Valve w/Single Interlock Trim Fire Alarm Bell Waterflow Pressure Alarm Switch Electric Releasing Panel Electric Detectors Electric Manual Control Station(s) Low Air Pressure Alarm Switch Air/Nitrogen Maintenance Device Solenoid Valve normally closed Check Valve Single Interlock Preaction Systems Electric Shown
  • 11. Double interlock preaction systems are designed for applications such as refrigerated areas that require the maximum degree of protection against an inadvertent operation that could result in unnecessary flooding of the sprinkler system piping. The double interlock system consists of a deluge valve and swing check valve with releasing trim featuring both a solenoid valve and a dry pilot actuator in a series configuration. The swing check valve isolates the body of the deluge valve from the system air or nitrogen pressure that holds the dry pilot actuator closed. The solenoid valve remains closed until it is electrically energized by a deluge releasing panel that responds to the operation of a fire detection device. In order to actuate the double interlock preaction system, two independent events, caused by a fire condition, must occur. The sprinkler system piping must lose air or nitrogen pressure due to the operation of one or more sprinklers, and the deluge releasing panel must energize and open the solenoid valve upon the operation of a fire detection device. The double interlock system will operate only when both the dry pilot actuator and the solenoid valve are open at the same time. Opening of the dry pilot actuator only (for example: a forklift truck accidentally dislodges a sprinkler) or of the solenoid valve only (for example: accidental operation of an electric manual pull station) will cause an alarm, and will not trip the system or flood the sprinkler system piping. Available with: • DV-5 Valve (TFP1305) • DV-1 Valve (TFP1330) • DV-3 Valve (TFP1350) Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. 11 Trim Assemblies ELEC./ELEC. ELEC./PNEUM. ACTUATION ACTUATION DV-5 TFP1465 TFP1460 DV-1 TD1153 TD1151 DV-3 TD1148 TD1146 Automatic Sprinklers Gate Valve Water Motor Alarm Deluge Valve w/Double Interlock Trim Fire Alarm Bell Dry Pilot Actuator normally closed Waterflow Pressure Alarm Switch Double Interlock Electric Releasing Panel Electric Detectors Electric Manual Control Station(s) Low Air Pressure Alarm Switch Air/Nitrogen Maintenance Device Solenoid Valve normally closed Check Valve Water Pressure Atmospheric Pressure Air Pressure System Shut-Off Valve Double Interlock Preaction Systems Pneumatic/Electric Shown
  • 12. 12 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. The “deluge valve” is the automatic water control valve that is used to control water flow into deluge, preaction, and special types of fire protection systems in response to a fire. Deluge fire protection systems are normally used in special hazard installations where an entire area application of water is required for protection. Typical applications may include flammable liquid handling and storage areas, aircraft hangars, and other high- hazard installations where water is the most effective extinguishing agent. Deluge systems employ open sprinklers or spray nozzles attached to a piping system. The system is connected to a water supply through the deluge valve. This valve is opened by the operation of a fire detection system installed in the same areas as the open sprinklers or nozzles. Deluge systems may be activated by wet or dry pilot sprinklers, or electric detectors. When the deluge valve opens, water flows into the piping system and discharges from all open sprinklers and nozzles. Trim Assemblies WET PILOT DRY PILOT ELEC. ACTUATION DV-5 TFP1310 TFP1315 TFP1320 DV-1 TFP1330 TFP1330 TFP1330 DV-3 TFP1350 TFP1350 TFP1350 Deluge Valve Deluge Systems Electric Shown
  • 13. DV-5 Deluge Valve, External Resetting Diaphragm Style – 1-1/2 through 8 Tech Data TFP1305 • Available sizes:1-1/2 (DN40), 2 (DN50), 3 (DN80), 4 (DN100), 6 (DN150), 8 (DN200) • Vertical or horizontal installation • One internal working part • No linkage or clapper assembly • Light weight ductile iron body • Available with deluge and single double interlock preaction trim • Internally externally coated • Features external resetting • Diaphragm operation • For most seawater brackish water supplies for deluge systems • For deluge, preaction foam systems • Available as Flange x Flange, Flange x Groove, or Groove x Groove body styles • Rated for 250 psi (17,2 bar) service • Listings and Approvals: UL, C-UL, and FM DV-1™ External Resetting Deluge Valve – 4 6 Tech Data TFP1330 • Available sizes: 4 (DN100) and 6 (DN150) • Used as a system control valve in deluge, and single and double interlock preaction systems • Can be reset externally without having to remove the hand-hole cover and unlatch the waterway clapper • Positive mechanical latching style valve • Available with three actuation trim arrangements: wet pilot, dry pilot, and electric • Single and double interlock preaction trims available • Rated for 175 psi (12.1 bar) maximum service pressure • Listings and Approvals: UL, ULC, FM, LPC, and SSL DV-3™ Deluge Valve, Automatic Resetting – 2-1/2 Tech Data TFP1350 • 2-1/2 (DN65), right angle type deluge valves • Available with either a grooved or threaded inlet and outlet • For use as a control valve in deluge, or single or double interlock preaction systems • Can be reset externally without having to open a hand-hole cover to manually unlatch and set the center valve • Trim arrangements provide wet pilot, dry pilot, and electric actuation • Valves may be installed with the outlet facing either left or right • DV-3 (F445) – 175 psi (12,1 bar) DV-3 (F446) – 250 psi (17,2 bar) • Listings and Approvals: UL, ULC, FM, LPC, and SSL. CV-1F Riser Check Valve Tech Data TFP950 • Available sizes: 2 through 8 (DN65) through (DN200) • Intended for use in a preaction system riser • Furnished with grooved ends that are compatible with grooved pipe and couplings • Can be installed with ANSI class 150 or 300 Flanges utilizing flange adapters • Designed with a removable cover for ease of field maintenance • Standard seal is grade “E” EPDM • Maximum rated working pressure is 300 psi (20,68 bar) Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. 13
  • 14. 14 Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. AQUAMIST® Systems utilize the newest and most unique nozzles developed and approved for fire protection. They offer an alternative to gas systems, foam systems, or heavy density sprinkler systems. By utilizing a higher pressure than a normal sprinkler system, but a 50-80% lower water flow, the AquaMist Systems use less water more effectively, reduce costs in pipe sizing and labor, and minimize cleanup and water damage. a) By using smaller droplet sizes, a larger droplet surface area to volume is created. This larger surface area allows heat extraction (evaporation). b) Vapor is created that displaces, removes, and excludes oxygen from the fire tetrahedral equation. c) Flammable vapors are diluted by the entrainment of water vapor, to the extent that the flammable vapor will not burn. d) Larger droplets are designed to penetrate the fire plume and cool the combustibles similar to a standard sprinkler system. e) The suspended mist will cool and “pre-wet” other combustibles in the area and cool any fuels and gases. AquaMist Systems are used in total compartmentalized areas and are pre-engineered systems that have specific guidelines as to the availability of installation, design, and components. With the advent of the publication of NFPA 750, the introduction and awareness of mist technology has never been higher. These pages highlight some of the products available in the AquaMist product line from TFBP…the innovative leader in fire protection. Typical Gas Turbine Generator Room AquaMist Systems operate differently from normal sprinkler or gaseous systems as follows: 3 PFC4410 – Single zone, cross zone, or sequential cross zone releasing panel 2 Variable Pressure AquaMist Fire Pump 1 DV-5 Deluge Valve 4 Fire Pump Controller 5 Required Outlet Strainer – The pipe, fittings, hangers and AquaMist nozzles are to be connected to the strainer outlet. To System
  • 15. Always refer to the Technical Data Sheet for complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty. 15 AM10 AQUAMIST® Open Type Mist Nozzle AM4 AQUAMIST® Open Type Mist Nozzle • Open, directional spray nozzles • Listed Approved for the protection of flammable liquid hazards (UL/FM) • Approved for protection of gas turbines (FM) • Maximum ceiling height, 26' 3 (8 m) • Compartment volume – UL - 56,500 ft3 (1,600 m3 ) – FM - 45,203 ft3 (1,280 m3 ) • Maximum utilization of water for flammable liquid fire protection • Nozzle coverage: maximum 172 ft2 (16 m2 ) • Nozzle pressure: 185 to 250 psi (12,8 to 17,2 bar) K=0.24 (3,5) 1/2 (15 mm) Stainless Steel K Factor Thread Size Finish Tech Data TD1173 AM15 AQUAMIST® • Available for use in IMO Mandated MSC 913 local application water mist systems • 0.33 gpm/psi0.5 • 175-250 psi • 4.36 gpm @ 175 psi Since the water droplet sizes are much smaller, a larger surface area is created to allow the water to absorb heat more quickly than a conventional sprinkler spray having larger droplets. The smaller droplets will be suspended and coat and cool any combustibles in the room, while pre-wetting the combustibles and thereby blocking them from radiant heat. The fire will receive the direct impingement of the larger droplets similar to a standard sprinkler • Open spray nozzles • Designed for use in water mist protection systems protecting flammable liquids and turbine bearings • Minimal water demand, approximately 3.1 GPM/nozzle at 170psi (11,73 lpm at 11,6 bar) • Mist represents latest in fire protection technology • For use in “low pressure” mist applications • Minimum operating pressure is 170 psi (11,6 bar) • Nozzle coverage: maximum 86 ft2 (8m2 ) • UL, FM K=0.24 (3,5) 1/2 (15 mm) Stainless Steel K Factor Thread Size Finish Tech Data TD1174 When the mist comes in contact with a fire, vapor (steam) is created which displaces, and reduces the oxygen level at the fire.
  • 16. WORLDWIDE HEADQUARTERS Tyco Fire Building Products 451 N. Cannon Avenue Lansdale, PA 19446 215-362-0700, 800-523-6512 Fax 215-362-5385 www.Tyco-Fire.com UNITED STATES Central Sprinkler Company 451 N. Cannon Avenue Lansdale, PA 19446 215-362-0700, Fax 215-362-5385 Brea, CA: Tel: 714-993-6111, Fax 714-993-6043 Decatur, GA: Tel: 404-243-7336, Fax 404-244-7375 Norristown, PA: Tel: 610-239-9925, Fax 610-239-9936 Jessup, MD: Tel: 301-604-7133, Fax 301-604-7138 Carol Stream, IL: Tel: 630-871-7700, Fax 630-871-7464 Coppell, TX: Tel: 972-745-0043, Fax 972-745-8594 Kent, WA: Tel: 253-872-6030, Fax 253-872-6547 Avon, MA: Tel: 508-583-8447, Fax 508-583-0034 Pompano Beach, FL: Tel: 954-781-0866, Fax 954-781-1475 Murray UT: Tel: 801-269-0688, Fax 801-269-0733 Tigard, OR: Tel: 503-620-4203, Fax 503-620-3817 Parma, OH: Tel: 216-265-0505, Fax 216-265-8354 Kansas City, MO: Tel: 816-842-2424, Fax 816-842-4433 National Distribution Facility PO Box 2806 Lubbock, TX 79408-2806 Gem Sprinkler Company Star Sprinkler Inc. 7071 S. 13th Street, Ste. 103 Oak Creek, WI 53154 877-436-8926, Fax 877-866-9250 CANADA Regional Headquarters 12-16715 Yonge Street, Suite 316 Newmarket, Ontario L3X 1X4 705-422-0010, Fax: 705-422-1396 © 2005 Tyco Fire Products LP. All rights reserved. /Printed in USA/TFP-SHz/2500/PP/07-05 LATIN AMERICA Regional Headquarters South America, Central America Caribbean 1802 S.W. 2nd St. Pompano Beach, FL 33069 954-781-0866, Fax 954-781-9330 Regional Headquarters - Mexico Hamburgo 231A Piso 2 Colonia Juarez Mexico, D.F. 06600 Mexico 525-55-2075766, Fax: 525-55-2077566 EUROPE MIDDLE EAST Regional Headquarters Kopersteden 1, NL-7547 TJ Enschede P.O. Box 198, 7500 AD Enschede, The Netherlands 31-53-428-4444, Fax 31-53-428-3377 Stockport, UK: Tel: 44-161-477-1886, Fax 44-161-477-6729 Paris Nord II, France: Tel: 33-1-48-178-727 , Fax 33-1-48-178-720 Rodgau Germany: Tel: 49-6106-84455, Fax 49-6106-18177 Coslada Madrid, Spain: Tel: 34-1-669-3906, Fax 34-1-669-2018 Lørenskog, Norway: Tel: 47-67-91-77-00, Fax 47-67-91-77-15 Lammhult, Sweden: Tel: 46-472-269-980, Fax 46-472-269-989 Dublin, Ireland: Tel: 353-166-839-82, Fax 353-166-822-54 Bolzano,Italy: Tel: 39-0471-252-091, Fax 39-0471-254-058 Milano, Italy: Tel: 39-0293-548-736, Fax 39-0293-548-690 Dubai, United Arab Emirates: Tel: 971-488-38689, Fax 971-488-38674 Budapest, Hungary: Tel: 36-148-11-383, Fax 36-120-34-427 Wels/Thalheim, Austria: Tel: 43-072-42-65-054, Fax 43-072-42-74-393 ASIA Regional Headquarters No.45 Tuas Avenue 9, Singapore 639189 Central Sprinkler Company Singapore: 65- 6743-3212, Fax 65-6743-9181 Shanghai, China: 86-21-5868-3300, Fax 86-21-5868-1160 Beijing, China: 86-10-6515-6191, Fax 86-10-6515-6157 Chengdu, China: 86-28-689-9440, Fax 86-28-666-2538 Gem Sprinkler Company Star Sprinkler Inc. Singapore: 65-6861-1655, Fax 65-6861-1312 Kuala Lumpur, Malaysia: 60-3-8024-6773, Fax 60-3-8024-2180 Hong Kong: 852-2595-0686, Fax 852-2505-5826 Central, Gem, Star, Grinnell, G FOUNDED 1850 and Design, and Tyco are either registered trademarks or trademarks of Tyco and/or its affiliates in the United States and/or other countries. All other brand names, product names, or trademarks belong to their respective owners. Tyco Fire Building Products reserves the right to change product design and specifications without notice.