4. Overview on FM200
• Water less Fire Suppression system
• Automatic Fire Suppression system
• Designed to be discharged within 10 seconds
• Uses Heptafluoropropane Gas
• Will eliminate Heat elements from the fire triangle (fire triangle-
Oxygen, Heat & Fuel)
• Installed in high flammable/intensive area
• Can be used for Electrical room, Fuel room, Server room etc..
6. List of Component
Smoke Detector
• Is a device that senses
smoke.
• Detects fire at initial stage
Manual Gas Release
Pull Station
• Used to release FM200 Agent
instantly
Sounder Flasher
• Audible and visual fire alarm
devices
• Activated during 2nd stage Fire
alarm
Alarm Bell
• Audible fire alarm devices
• Activates during 1st stage Fire
alarm
7. List of Component
Solenoid Coil head
• Triggers Cylinder to discharge
FM200 Agent
• Option to Manually release FM200
agent even if Panel was in OFF
condition
Abort Switch
• Used to Stop FM200 from
releasing
• Need to Push and Hold
FM200 control panel
• Control Releasing of FM200
agent
• Minimum 2 Zone & Minimum 1
detector per zone
9. FM200 Operation
• Typical Layout with Zone
• Stage 1 Fire Alarm
• Stage 2 Fire Alarm
• Manual Release
10. FM200 Operation – Typical Layout 2 Zone 2 Detector
Zone 1 Zone 2
Input to Panel
Output from Panel
11. FM200 Operation – Typical Layout 2 Zone 4 Detector
Zone 1 Zone 2
Zone 1Zone 2
Zone 1 Connection
Zone 2 Connection
Other Connection
12. FM200 Operation
Detector 1
Zone 1
Zone 2
FM200
Control
Panel
Detector 2
Detector 3
Detector 4
Sounder &
Flasher
Main FACP
Alarm
Alarm Bell
FM200
Cylinder
Manual Pull
Station
T-30 Sec
Time
DelayAbort Switch
(Push and Hold )
13. FM200 Operation - Stage 1 fire alarm
Detector 1
Zone 1
Zone 2
FM200
Control
Panel
Detector 2
Detector 3
Detector 4
Sounder &
Flasher
Main FACP
Alarm
Alarm Bell
FM200
Cylinder
Manual Pull
Station
T-30 Sec
Time
DelayAbort Switch
(Push and Hold )
14. FM200 Operation - Stage 2 fire alarm
Detector 1
Zone 1
Zone 2
FM200
Control
Panel
Detector 2
Detector 3
Detector 4
Sounder &
Flasher
Main FACP
Alarm
Alarm Bell
FM200
Cylinder
Manual Pull
Station
T-30 Sec
Time
DelayAbort Switch
(Push and Hold )
15. FM200 Operation – Manual Gas Release
Detector 1
Zone 1
Zone 2
FM200
Control
Panel
Detector 2
Detector 3
Detector 4
Sounder &
Flasher
Main FACP
Alarm
Alarm Bell
FM200
Cylinder
Manual Pull
Station
Abort Switch
(Push and Hold )
16. Isolation During False Alarm
• Press & hold Abort switch or Press reset button
• Remove Solenoid Coil from cylinder
FM200
Control
Panel
FM200
Cylinder
Remove
Solenoid
Coil
Abort Switch
(Push and Hold )
Press Reset
T-30 Sec
Time
Delay