Tropical Rooftop Packaged Air To Air Unit
DAACPT 10 - 190
Cooling capacity: 9.6 - 188.5 kW
FEATURES
STRUCTURE
Panels and frame are made from galvanized steel
protected with polyester powder painting to ensure total
resistance to atmospheric agents.
Direct expansion coils with condensate drain tray.
HERMETIC COMPRESSOR
Compressors used in the DAACPT series Packaged units
are hermetically sealed, high - efficiency, low noise, Scroll
type. Compressors conform to internationally recognized
standards like EN, CE & ENISO.
All compressors are refrigerant gas cooled. Each is
provided with a check valve to prevent the compressor
from running backward once the power has been switched
off. Ultimately, the discharge gas leaves the compressor at
the discharge connection.
All compressors are provided with the motor protection. All
compressor models are equipped with internal line break
protectors mounted on their windings. These protection are
to prevent against excessive current and temperature
caused by overloading, low refrigerant flow, phase lose and
incorrect motor rotation. The motor protector comprises a
control module and PTC sensors embedded in the motor
winding. The close contact between thermostats and
windings ensures a very low level thermal inertia. The
motor temperature is being constantly measured by a
thermostat loop. The compressors are selected for their
extremely high energy efficiency and heavy duty industrial/
commercial usage with economy of operation in addition to
high technology and low noise.
EVAPORATOR FAN & DRIVE
Forward curve centrifugal fans for air treatment section and
axial fans for condensation section.
Front, side and underside air discharge of the treatment
unit. High external pressure, long air supply distance.
CONDENSER FANS
Condenser fans are propeller type with aluminum alloy blades
and are directly driven by electric motors. Motors are internally
protected for overloads six-pole with Class F insulation and
minimum IP55 protection.
The Class F insulation features ensure long life and are unique
to Dekon. The condenser fans are individually statically and
dynamically balanced at the factory. Complete fan assembly is
mounted downward on the strong and acrylic coated fan guard
for the smaller units. For larger units fan, assembly is separate
and provided with suitable acrylic coated fan guard. Motors are
wired to the control panel to control the operation of these
motors along with the compressors.
ELECTRIC PANEL
Electric panel consists of breakers and contactors for
compressors and fan motors, phase sequence relay and other
necessary protection devices for the main components.
Easy operation line controller:
Cooling/Auto
Error indication
Timing On/Off
OPTIONAL
High & Low Pressure Gauges
Liquid Line Sight Glass
1" (25mm) / 2" (50mm) Flat Filter Section
Double Skin Insulation
External Overload Protection
ACCESSORIES
Air pressure switch for indoor fan.
High Static condenser fan option with sealed +
drain condensing section.
Optional water heating coil
Metal or plastic mesh on condenser coil.
Optional supply / return air configurations
Upgraded evaporator fan motor drives.
TECHNICAL DATA
Model 10 12 14 17 20 22 25 28
Cooling
Cooling capacity * kW 9.6 11.3 13.1 17.2 19.2 22.5 24.4 26.2
Total power input * kW 4.01 4.43 5.25 6.65 7.49 8.66 9.14 10.56
Compressors Hermetically sealed scroll compressor
Qty/refrigerant circuit Nr. 1/1 1/1 1/1 1/1 2/1 2/1 2/1 2/1
Energy control steps step 1 1 1 1 2 2 3 2
Air treatment section
Centrifugal fans number Nr. 1 1 1 1 1 1 1 1
Drive type / Direct Direct Direct Direct Direct Direct Belt Belt
Air flow m
3
/h 1800 2124 2520 2916 3600 4248 4500 5400
External static pressure Pa 160 150 180 175 225 185 260 240
Motor power kW 0.55 0.55 0.55 0.76 0.93 0.93 1.22 1.22
Condensation section
Axial fans number Nr. 1 1 1 1 1 1 1 1
Air flow m3
/h 3961 3781 5509 7021 8641 8641 9434 9434
Motor power kW 0.16 0.16 0.33 0.38 0.38 0.48 0.61 0.61
Net weight kg 240 240 243 360 402 420 461 461
Sound pressure level ** dB(A) 67 67 68 71.7 72.6 72.6 70.0 70.0
Model 30 32 35 42 45 52 63 75
Cooling
Cooling capacity * kW 29.3 31.4 34.5 40.4 45.8 51.6 61.4 69.3
Total power input * kW 11.43 11.57 13.03 15.05 17.08 19.14 24.07 27.83
Compressors Hermetically sealed scroll compressor
Qty/refrigerant circuit Nr. 2/1 2/1 2/2 2/2 2/2 2/2 2/2 2/2
Energy control steps step 3 2 2 3 3 3 3 3
Air treatment section
Centrifugal fans number Nr. 1 1 1 1 1 1 1 1
Drive type / Belt Belt Belt Belt Belt Belt Belt Belt
Air flow m
3
/h 5688 6300 6804 7920 9360 10440 12672 14400
External static pressure Pa 260 250 260 250 260 350 320 360
Motor power kW 1.5 1.5 2.2 2.2 3 3 3 4
Condensation section
Axial fans number Nr. 1 1 2 2 2 2 2 2
Air flow m3
/h 11234 12314 15000 17600 18800 21420 24620 30000
Motor power kW 0.80 0.80 2x0.37 2x0.45 2x0.55 2x0.55 2x0.75 2x1.1
Net weight kg 503 505 650 725 801 884 890 980
Sound pressure level ** dB(A) 72.0 72.0 72.0 72.0 75 75 75 75
⑥ T: T3 Rooftops
⑦ Model
③ C: Cooling only
H: Heat pump
④ Refrigerant type
--: R22
A: R410a
B: R134a
C: R407c
⑤ Type of unit
P: Packaged type
S: Split type
NOMENCLATURE
D AA C A P T 10
① ② ③ ④ ⑤ ⑥ ⑦
① D: DEKON air product
② Unit type
AA: Air to Air
AW: Air to Water
WA: Water to Air
WW: Water to Water
Model 90 105 120 140 155 170 190
Cooling
Cooling capacity * kW 87.2 103.1 118.8 131.2 153.4 168.6 188.5
Total power input * kW 31.40 38.30 46.10 49.70 56.70 65.40 75.48
Compressors Hermetically sealed scroll compressor
Qty/refrigerant circuit Nr. 2/2 2/2 4/2 4/2 4/2 4/2 4/2
Energy control steps step 2 2 4 4 4 4 4
Air treatment section
Centrifugal fans number Nr. 1 1 1 1 1 1 1
Drive type / Belt Belt Belt Belt Belt Belt Belt
Air flow m3
/h 16560 19440 22032 24300 29160 33120 36720
External static pressure Pa 350 350 460 450 410 410 460
Motor power kW 4 5.5 7.5 7.5 7.5 11 15
Condensation section
Axial fans number Nr. 2 2 4 4 4 4 4
Air flow m3
/h 40000 40000 49240 49240 60000 80000 80000
Motor power kW 2x1.5 2x1.5 4x0.75 4x0.75 4x1.5 4x1.5 4x1.5
Net weight kg 1160 1450 1910 2010 2280 2460 2530
Sound pressure level ** dB(A) 75 75 80 80 80 82 82 .5
* Performance values refer to the following conditions:
Cooling: Outdoor working conditions temperature DB:46 (℃114F), WB: 24 (℃75F); Indoor working conditions: temperature DB:
29 (℃84F), WB: 19 (℃66F)
** Noise level measured by adopting average value in the noise lab with background noise of 25 dB(A), at a distance of 1.5m high
fan speed.
OVERALL DIMENSION
Model DAACPT 10 12 14 17
Mod. A B C D
10 1282 1041 895 1230
12 1282 1041 895 1230
14 1282 1041 895 1230
17 1282 1041 895 1230
Model DAACPT 20 22 25 28 30 32
Mod. A B C D
20 1770 1390 1030 1730
22 1770 1390 1030 1730
25 1940 1390 1030 1900
28 1940 1390 1030 1900
30 2240 1390 1030 2200
32 2240 1390 1030 2200
OVERALL DIMENSIONS
Model DAACPT 35 42 45
Model DAACPT 52 63 75 90 105
Model DAACPT 120 140 155 170 190
Mod. A B C D Mod. A B C D
35 2540 1860 1030 2500 105 3412 2210 1810 3320
42 2540 1860 1180 2500 120 4700 2230 1615 2000
45 2540 1860 1180 2500 140 5200 2230 1615 2000
52 2490 2050 1370 2400 155 5500 2230 1810 2000
63 2490 2210 1472 2400 170 5500 2230 1810 2000
75 2840 2200 1490 2750 190 5800 2230 1810 2000
90 2840 2200 1665 2750
The technical data in this documents are not binding. Dekon reserves the right to make
whatever modifications it deems necessary to improve the product at any time.

More Related Content

What's hot

Ap 23 7900 001 (package air conditioning units) 2011 1206
Ap 23 7900 001 (package air conditioning units) 2011 1206Ap 23 7900 001 (package air conditioning units) 2011 1206
Ap 23 7900 001 (package air conditioning units) 2011 1206Dr. Haider alsenisal
 
Daikin fan coils
Daikin fan coilsDaikin fan coils
Daikin fan coilsEeu SC
 
Air Accessories - ELGi USA
Air Accessories - ELGi USAAir Accessories - ELGi USA
Air Accessories - ELGi USAelgiusa
 
Physical Product Catalog-Dual Compressor Screw Chiller 2015
Physical Product Catalog-Dual Compressor Screw Chiller 2015Physical Product Catalog-Dual Compressor Screw Chiller 2015
Physical Product Catalog-Dual Compressor Screw Chiller 2015Bustruck Cooling
 
Air & flue gas system
Air & flue gas system Air & flue gas system
Air & flue gas system Kushjani1
 
AERMEC 2013 Presentation
AERMEC 2013 PresentationAERMEC 2013 Presentation
AERMEC 2013 PresentationBritton Wallace
 
FEAM Lighting - Hazardous Area & Explosion Proof Lighting
FEAM Lighting - Hazardous Area & Explosion Proof Lighting FEAM Lighting - Hazardous Area & Explosion Proof Lighting
FEAM Lighting - Hazardous Area & Explosion Proof Lighting Thorne & Derrick International
 
Industrial Refrigeration - dual flow Unit Cooler
Industrial Refrigeration - dual flow Unit CoolerIndustrial Refrigeration - dual flow Unit Cooler
Industrial Refrigeration - dual flow Unit CoolerGiuseppe Visentini
 
Hazloc AEU1 Air Heater - Hazardous Area Explosion Proof ATEX Zone 1 Certified
Hazloc AEU1 Air Heater - Hazardous Area Explosion Proof ATEX Zone 1 CertifiedHazloc AEU1 Air Heater - Hazardous Area Explosion Proof ATEX Zone 1 Certified
Hazloc AEU1 Air Heater - Hazardous Area Explosion Proof ATEX Zone 1 CertifiedThorne & Derrick International
 
Rittal Pano Isıtıcıları
Rittal Pano IsıtıcılarıRittal Pano Isıtıcıları
Rittal Pano Isıtıcılarıerdinc klima
 
Microsoft word ms11 chapter 2 equipment selection-tcm135-60924
Microsoft word   ms11 chapter 2 equipment selection-tcm135-60924Microsoft word   ms11 chapter 2 equipment selection-tcm135-60924
Microsoft word ms11 chapter 2 equipment selection-tcm135-60924Yacine Gorary
 
Dry Coolers - liquid coolers by Thermokey
Dry Coolers - liquid coolers  by ThermokeyDry Coolers - liquid coolers  by Thermokey
Dry Coolers - liquid coolers by ThermokeyGiuseppe Visentini
 
1999 subaru forester service repair manual
1999 subaru forester service repair manual1999 subaru forester service repair manual
1999 subaru forester service repair manualfhjsjkdmemm
 

What's hot (20)

Ap 23 7900 001 (package air conditioning units) 2011 1206
Ap 23 7900 001 (package air conditioning units) 2011 1206Ap 23 7900 001 (package air conditioning units) 2011 1206
Ap 23 7900 001 (package air conditioning units) 2011 1206
 
Daikin fan coils
Daikin fan coilsDaikin fan coils
Daikin fan coils
 
Rte 1 en
Rte 1 enRte 1 en
Rte 1 en
 
Air Accessories - ELGi USA
Air Accessories - ELGi USAAir Accessories - ELGi USA
Air Accessories - ELGi USA
 
chiller166
chiller166chiller166
chiller166
 
Physical Product Catalog-Dual Compressor Screw Chiller 2015
Physical Product Catalog-Dual Compressor Screw Chiller 2015Physical Product Catalog-Dual Compressor Screw Chiller 2015
Physical Product Catalog-Dual Compressor Screw Chiller 2015
 
Unidades condensadoras tecumseh
Unidades condensadoras tecumsehUnidades condensadoras tecumseh
Unidades condensadoras tecumseh
 
general-sabcool
general-sabcoolgeneral-sabcool
general-sabcool
 
Air & flue gas system
Air & flue gas system Air & flue gas system
Air & flue gas system
 
AERMEC 2013 Presentation
AERMEC 2013 PresentationAERMEC 2013 Presentation
AERMEC 2013 Presentation
 
FEAM Lighting - Hazardous Area & Explosion Proof Lighting
FEAM Lighting - Hazardous Area & Explosion Proof Lighting FEAM Lighting - Hazardous Area & Explosion Proof Lighting
FEAM Lighting - Hazardous Area & Explosion Proof Lighting
 
Industrial Refrigeration - dual flow Unit Cooler
Industrial Refrigeration - dual flow Unit CoolerIndustrial Refrigeration - dual flow Unit Cooler
Industrial Refrigeration - dual flow Unit Cooler
 
Fracaro ponuda
Fracaro ponudaFracaro ponuda
Fracaro ponuda
 
Hazloc AEU1 Air Heater - Hazardous Area Explosion Proof ATEX Zone 1 Certified
Hazloc AEU1 Air Heater - Hazardous Area Explosion Proof ATEX Zone 1 CertifiedHazloc AEU1 Air Heater - Hazardous Area Explosion Proof ATEX Zone 1 Certified
Hazloc AEU1 Air Heater - Hazardous Area Explosion Proof ATEX Zone 1 Certified
 
Rittal Pano Isıtıcıları
Rittal Pano IsıtıcılarıRittal Pano Isıtıcıları
Rittal Pano Isıtıcıları
 
Mono block refrigeration unit(YTK)
Mono block refrigeration unit(YTK)Mono block refrigeration unit(YTK)
Mono block refrigeration unit(YTK)
 
Microsoft word ms11 chapter 2 equipment selection-tcm135-60924
Microsoft word   ms11 chapter 2 equipment selection-tcm135-60924Microsoft word   ms11 chapter 2 equipment selection-tcm135-60924
Microsoft word ms11 chapter 2 equipment selection-tcm135-60924
 
Dry Coolers - liquid coolers by Thermokey
Dry Coolers - liquid coolers  by ThermokeyDry Coolers - liquid coolers  by Thermokey
Dry Coolers - liquid coolers by Thermokey
 
Chapter8
Chapter8Chapter8
Chapter8
 
1999 subaru forester service repair manual
1999 subaru forester service repair manual1999 subaru forester service repair manual
1999 subaru forester service repair manual
 

Similar to Dekon Rooftop units t3 conditions

42GWC Hydronic Cassette Fan Coil Units.pdf
42GWC Hydronic Cassette Fan Coil Units.pdf42GWC Hydronic Cassette Fan Coil Units.pdf
42GWC Hydronic Cassette Fan Coil Units.pdfCarrier Singapore
 
Sb ls screw-inverter_ver.3.0_en
Sb ls screw-inverter_ver.3.0_enSb ls screw-inverter_ver.3.0_en
Sb ls screw-inverter_ver.3.0_enYury Naumov
 
Crac precision climate_control_units_for_data_centres
Crac precision climate_control_units_for_data_centresCrac precision climate_control_units_for_data_centres
Crac precision climate_control_units_for_data_centresEeu SC
 
Sb ls screw-fixed-speed_ver.3.0_en
Sb ls screw-fixed-speed_ver.3.0_enSb ls screw-fixed-speed_ver.3.0_en
Sb ls screw-fixed-speed_ver.3.0_enYury Naumov
 
Sb ls scroll_ver.3.0_en
Sb ls scroll_ver.3.0_enSb ls scroll_ver.3.0_en
Sb ls scroll_ver.3.0_enYury Naumov
 
FanCoil-VRF-Midea-PD-CP-Technical Specifications.pdf
FanCoil-VRF-Midea-PD-CP-Technical Specifications.pdfFanCoil-VRF-Midea-PD-CP-Technical Specifications.pdf
FanCoil-VRF-Midea-PD-CP-Technical Specifications.pdfAlan Brito
 
Rittal top therm_chiller
Rittal top therm_chillerRittal top therm_chiller
Rittal top therm_chillerEeu SC
 
Boge screw air compressors--oil free solutions
Boge screw air compressors--oil free solutionsBoge screw air compressors--oil free solutions
Boge screw air compressors--oil free solutionsdaisy Airmax
 
Powerstream Turbo chiller
Powerstream Turbo chillerPowerstream Turbo chiller
Powerstream Turbo chillerKaltra_DE
 
Ventilation
VentilationVentilation
VentilationDantherm
 
Product bulletin ametek 116515 13
Product bulletin ametek 116515 13Product bulletin ametek 116515 13
Product bulletin ametek 116515 13Eddy Suwito AS
 
Nrp 0800-1800-hp-t y-un50_00
Nrp 0800-1800-hp-t y-un50_00Nrp 0800-1800-hp-t y-un50_00
Nrp 0800-1800-hp-t y-un50_00Oliverh Kalprit
 
Compressed Air Dryer Supplier
Compressed Air Dryer SupplierCompressed Air Dryer Supplier
Compressed Air Dryer SupplierMansiKhurana14
 

Similar to Dekon Rooftop units t3 conditions (20)

42GWC Hydronic Cassette Fan Coil Units.pdf
42GWC Hydronic Cassette Fan Coil Units.pdf42GWC Hydronic Cassette Fan Coil Units.pdf
42GWC Hydronic Cassette Fan Coil Units.pdf
 
Delta ia pq-afe2000_c_en_20160323_web
Delta ia pq-afe2000_c_en_20160323_webDelta ia pq-afe2000_c_en_20160323_web
Delta ia pq-afe2000_c_en_20160323_web
 
Sb ls screw-inverter_ver.3.0_en
Sb ls screw-inverter_ver.3.0_enSb ls screw-inverter_ver.3.0_en
Sb ls screw-inverter_ver.3.0_en
 
Crac precision climate_control_units_for_data_centres
Crac precision climate_control_units_for_data_centresCrac precision climate_control_units_for_data_centres
Crac precision climate_control_units_for_data_centres
 
Sb ls screw-fixed-speed_ver.3.0_en
Sb ls screw-fixed-speed_ver.3.0_enSb ls screw-fixed-speed_ver.3.0_en
Sb ls screw-fixed-speed_ver.3.0_en
 
Sb ls scroll_ver.3.0_en
Sb ls scroll_ver.3.0_enSb ls scroll_ver.3.0_en
Sb ls scroll_ver.3.0_en
 
FanCoil-VRF-Midea-PD-CP-Technical Specifications.pdf
FanCoil-VRF-Midea-PD-CP-Technical Specifications.pdfFanCoil-VRF-Midea-PD-CP-Technical Specifications.pdf
FanCoil-VRF-Midea-PD-CP-Technical Specifications.pdf
 
Rittal top therm_chiller
Rittal top therm_chillerRittal top therm_chiller
Rittal top therm_chiller
 
Boge screw air compressors--oil free solutions
Boge screw air compressors--oil free solutionsBoge screw air compressors--oil free solutions
Boge screw air compressors--oil free solutions
 
Powerstream Turbo chiller
Powerstream Turbo chillerPowerstream Turbo chiller
Powerstream Turbo chiller
 
Komfort ec d5b180_een2
Komfort ec d5b180_een2Komfort ec d5b180_een2
Komfort ec d5b180_een2
 
Nlc co y-na60_02
Nlc co y-na60_02Nlc co y-na60_02
Nlc co y-na60_02
 
Ventilation
VentilationVentilation
Ventilation
 
Cpg 2010
Cpg 2010Cpg 2010
Cpg 2010
 
Product bulletin ametek 116515 13
Product bulletin ametek 116515 13Product bulletin ametek 116515 13
Product bulletin ametek 116515 13
 
Intro To Evaporative Cooling
Intro To Evaporative CoolingIntro To Evaporative Cooling
Intro To Evaporative Cooling
 
Air cooled condenser
Air cooled condenserAir cooled condenser
Air cooled condenser
 
Nrp 0800-1800-hp-t y-un50_00
Nrp 0800-1800-hp-t y-un50_00Nrp 0800-1800-hp-t y-un50_00
Nrp 0800-1800-hp-t y-un50_00
 
Breezair tbs580
Breezair tbs580 Breezair tbs580
Breezair tbs580
 
Compressed Air Dryer Supplier
Compressed Air Dryer SupplierCompressed Air Dryer Supplier
Compressed Air Dryer Supplier
 

More from Simon MECO FanCoil Unit

More from Simon MECO FanCoil Unit (14)

Fcu catalog meco 2019
Fcu catalog meco 2019Fcu catalog meco 2019
Fcu catalog meco 2019
 
Ekon fcu thermostat catalog
Ekon fcu thermostat catalogEkon fcu thermostat catalog
Ekon fcu thermostat catalog
 
Ekon Fan Coil Unit Thermostat catalog
Ekon Fan Coil Unit Thermostat catalogEkon Fan Coil Unit Thermostat catalog
Ekon Fan Coil Unit Thermostat catalog
 
Dekon marin air conditioner
Dekon marin air conditionerDekon marin air conditioner
Dekon marin air conditioner
 
Dekon vrf system brief introduction
Dekon vrf system brief introductionDekon vrf system brief introduction
Dekon vrf system brief introduction
 
DEKON VRF Air conditioner installation tips
DEKON VRF Air conditioner installation tipsDEKON VRF Air conditioner installation tips
DEKON VRF Air conditioner installation tips
 
DEKON VRF System Catalog
DEKON VRF System CatalogDEKON VRF System Catalog
DEKON VRF System Catalog
 
Air cooled scroll chiller-Big capacity single unit
Air cooled scroll chiller-Big capacity single unitAir cooled scroll chiller-Big capacity single unit
Air cooled scroll chiller-Big capacity single unit
 
Dekon Air cooled screw chiller 2017
Dekon Air cooled screw chiller 2017Dekon Air cooled screw chiller 2017
Dekon Air cooled screw chiller 2017
 
Ceiling type ahu
Ceiling type ahuCeiling type ahu
Ceiling type ahu
 
Dekon Horizontal,vertical modular ahu
Dekon Horizontal,vertical modular ahuDekon Horizontal,vertical modular ahu
Dekon Horizontal,vertical modular ahu
 
Dekon Water cooled screw chiller
Dekon Water cooled screw chillerDekon Water cooled screw chiller
Dekon Water cooled screw chiller
 
Air cooled modular chiller dekon 2017
Air cooled modular chiller dekon 2017Air cooled modular chiller dekon 2017
Air cooled modular chiller dekon 2017
 
Dc inverter vrf installation instructions and Tips
Dc inverter vrf installation instructions and TipsDc inverter vrf installation instructions and Tips
Dc inverter vrf installation instructions and Tips
 

Recently uploaded

Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
EduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIEduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIkoyaldeepu123
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEroselinkalist12
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)Dr SOUNDIRARAJ N
 
DATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage exampleDATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage examplePragyanshuParadkar1
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHC Sai Kiran
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...asadnawaz62
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .Satyam Kumar
 

Recently uploaded (20)

Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
POWER SYSTEMS-1 Complete notes examples
POWER SYSTEMS-1 Complete notes  examplesPOWER SYSTEMS-1 Complete notes  examples
POWER SYSTEMS-1 Complete notes examples
 
EduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIEduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AI
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
Design and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdfDesign and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdf
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
 
DATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage exampleDATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage example
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECH
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .
 

Dekon Rooftop units t3 conditions

  • 1. Tropical Rooftop Packaged Air To Air Unit DAACPT 10 - 190 Cooling capacity: 9.6 - 188.5 kW FEATURES STRUCTURE Panels and frame are made from galvanized steel protected with polyester powder painting to ensure total resistance to atmospheric agents. Direct expansion coils with condensate drain tray. HERMETIC COMPRESSOR Compressors used in the DAACPT series Packaged units are hermetically sealed, high - efficiency, low noise, Scroll type. Compressors conform to internationally recognized standards like EN, CE & ENISO. All compressors are refrigerant gas cooled. Each is provided with a check valve to prevent the compressor from running backward once the power has been switched off. Ultimately, the discharge gas leaves the compressor at the discharge connection. All compressors are provided with the motor protection. All compressor models are equipped with internal line break protectors mounted on their windings. These protection are to prevent against excessive current and temperature caused by overloading, low refrigerant flow, phase lose and incorrect motor rotation. The motor protector comprises a control module and PTC sensors embedded in the motor winding. The close contact between thermostats and windings ensures a very low level thermal inertia. The motor temperature is being constantly measured by a thermostat loop. The compressors are selected for their extremely high energy efficiency and heavy duty industrial/ commercial usage with economy of operation in addition to high technology and low noise. EVAPORATOR FAN & DRIVE Forward curve centrifugal fans for air treatment section and axial fans for condensation section. Front, side and underside air discharge of the treatment unit. High external pressure, long air supply distance. CONDENSER FANS Condenser fans are propeller type with aluminum alloy blades and are directly driven by electric motors. Motors are internally protected for overloads six-pole with Class F insulation and minimum IP55 protection. The Class F insulation features ensure long life and are unique to Dekon. The condenser fans are individually statically and dynamically balanced at the factory. Complete fan assembly is mounted downward on the strong and acrylic coated fan guard for the smaller units. For larger units fan, assembly is separate and provided with suitable acrylic coated fan guard. Motors are wired to the control panel to control the operation of these motors along with the compressors. ELECTRIC PANEL Electric panel consists of breakers and contactors for compressors and fan motors, phase sequence relay and other necessary protection devices for the main components. Easy operation line controller: Cooling/Auto Error indication Timing On/Off OPTIONAL High & Low Pressure Gauges Liquid Line Sight Glass 1" (25mm) / 2" (50mm) Flat Filter Section Double Skin Insulation External Overload Protection ACCESSORIES Air pressure switch for indoor fan. High Static condenser fan option with sealed + drain condensing section. Optional water heating coil Metal or plastic mesh on condenser coil. Optional supply / return air configurations Upgraded evaporator fan motor drives.
  • 2. TECHNICAL DATA Model 10 12 14 17 20 22 25 28 Cooling Cooling capacity * kW 9.6 11.3 13.1 17.2 19.2 22.5 24.4 26.2 Total power input * kW 4.01 4.43 5.25 6.65 7.49 8.66 9.14 10.56 Compressors Hermetically sealed scroll compressor Qty/refrigerant circuit Nr. 1/1 1/1 1/1 1/1 2/1 2/1 2/1 2/1 Energy control steps step 1 1 1 1 2 2 3 2 Air treatment section Centrifugal fans number Nr. 1 1 1 1 1 1 1 1 Drive type / Direct Direct Direct Direct Direct Direct Belt Belt Air flow m 3 /h 1800 2124 2520 2916 3600 4248 4500 5400 External static pressure Pa 160 150 180 175 225 185 260 240 Motor power kW 0.55 0.55 0.55 0.76 0.93 0.93 1.22 1.22 Condensation section Axial fans number Nr. 1 1 1 1 1 1 1 1 Air flow m3 /h 3961 3781 5509 7021 8641 8641 9434 9434 Motor power kW 0.16 0.16 0.33 0.38 0.38 0.48 0.61 0.61 Net weight kg 240 240 243 360 402 420 461 461 Sound pressure level ** dB(A) 67 67 68 71.7 72.6 72.6 70.0 70.0 Model 30 32 35 42 45 52 63 75 Cooling Cooling capacity * kW 29.3 31.4 34.5 40.4 45.8 51.6 61.4 69.3 Total power input * kW 11.43 11.57 13.03 15.05 17.08 19.14 24.07 27.83 Compressors Hermetically sealed scroll compressor Qty/refrigerant circuit Nr. 2/1 2/1 2/2 2/2 2/2 2/2 2/2 2/2 Energy control steps step 3 2 2 3 3 3 3 3 Air treatment section Centrifugal fans number Nr. 1 1 1 1 1 1 1 1 Drive type / Belt Belt Belt Belt Belt Belt Belt Belt Air flow m 3 /h 5688 6300 6804 7920 9360 10440 12672 14400 External static pressure Pa 260 250 260 250 260 350 320 360 Motor power kW 1.5 1.5 2.2 2.2 3 3 3 4 Condensation section Axial fans number Nr. 1 1 2 2 2 2 2 2 Air flow m3 /h 11234 12314 15000 17600 18800 21420 24620 30000 Motor power kW 0.80 0.80 2x0.37 2x0.45 2x0.55 2x0.55 2x0.75 2x1.1 Net weight kg 503 505 650 725 801 884 890 980 Sound pressure level ** dB(A) 72.0 72.0 72.0 72.0 75 75 75 75 ⑥ T: T3 Rooftops ⑦ Model ③ C: Cooling only H: Heat pump ④ Refrigerant type --: R22 A: R410a B: R134a C: R407c ⑤ Type of unit P: Packaged type S: Split type NOMENCLATURE D AA C A P T 10 ① ② ③ ④ ⑤ ⑥ ⑦ ① D: DEKON air product ② Unit type AA: Air to Air AW: Air to Water WA: Water to Air WW: Water to Water
  • 3. Model 90 105 120 140 155 170 190 Cooling Cooling capacity * kW 87.2 103.1 118.8 131.2 153.4 168.6 188.5 Total power input * kW 31.40 38.30 46.10 49.70 56.70 65.40 75.48 Compressors Hermetically sealed scroll compressor Qty/refrigerant circuit Nr. 2/2 2/2 4/2 4/2 4/2 4/2 4/2 Energy control steps step 2 2 4 4 4 4 4 Air treatment section Centrifugal fans number Nr. 1 1 1 1 1 1 1 Drive type / Belt Belt Belt Belt Belt Belt Belt Air flow m3 /h 16560 19440 22032 24300 29160 33120 36720 External static pressure Pa 350 350 460 450 410 410 460 Motor power kW 4 5.5 7.5 7.5 7.5 11 15 Condensation section Axial fans number Nr. 2 2 4 4 4 4 4 Air flow m3 /h 40000 40000 49240 49240 60000 80000 80000 Motor power kW 2x1.5 2x1.5 4x0.75 4x0.75 4x1.5 4x1.5 4x1.5 Net weight kg 1160 1450 1910 2010 2280 2460 2530 Sound pressure level ** dB(A) 75 75 80 80 80 82 82 .5 * Performance values refer to the following conditions: Cooling: Outdoor working conditions temperature DB:46 (℃114F), WB: 24 (℃75F); Indoor working conditions: temperature DB: 29 (℃84F), WB: 19 (℃66F) ** Noise level measured by adopting average value in the noise lab with background noise of 25 dB(A), at a distance of 1.5m high fan speed. OVERALL DIMENSION Model DAACPT 10 12 14 17 Mod. A B C D 10 1282 1041 895 1230 12 1282 1041 895 1230 14 1282 1041 895 1230 17 1282 1041 895 1230 Model DAACPT 20 22 25 28 30 32 Mod. A B C D 20 1770 1390 1030 1730 22 1770 1390 1030 1730 25 1940 1390 1030 1900 28 1940 1390 1030 1900 30 2240 1390 1030 2200 32 2240 1390 1030 2200
  • 4. OVERALL DIMENSIONS Model DAACPT 35 42 45 Model DAACPT 52 63 75 90 105 Model DAACPT 120 140 155 170 190 Mod. A B C D Mod. A B C D 35 2540 1860 1030 2500 105 3412 2210 1810 3320 42 2540 1860 1180 2500 120 4700 2230 1615 2000 45 2540 1860 1180 2500 140 5200 2230 1615 2000 52 2490 2050 1370 2400 155 5500 2230 1810 2000 63 2490 2210 1472 2400 170 5500 2230 1810 2000 75 2840 2200 1490 2750 190 5800 2230 1810 2000 90 2840 2200 1665 2750 The technical data in this documents are not binding. Dekon reserves the right to make whatever modifications it deems necessary to improve the product at any time.