—STATIC MONITORING RELAY
Trip circuit supervision relay
TCS
Product Guide
2 TRIP CIRCUIT SUPERVISON REL AY PRODUCT GUIDE
—
The supervision relay type TCS is
intended for a continuous
supervision of circuit breaker trip
circuit and gives an alarm for loss
of auxiliary supply, faults on the
trip coil or its wires independent of
the breaker position.
3
—
Table of contents
TABLE OF CONTENTS
004 -005	Features
005	 Design and principle of operation
006-007	 Technical data
008	Dimensions and mounting
009	Selection and ordering data
010	Connection and terminal diagram
011	References
4 TRIP CIRCUIT SUPERVISON REL AY PRODUCT GUIDE4
—
Trip circuit supervision relay
TCS
—
1. Application and supported functions
Features
•	 Continuous supervision of trip circuit indepen-
dent of the circuit breaker position
•	 Extremely low burden on auxiliary source
•	 Complete range of rated AC/DC voltage
•	 Operation indication for trip circuit healthy and
unhealthy
•	 Low level measuring current enables application
of relay for high burden circuits
•	 Delayed operation to avoid spurious signals
during circuit breaker operation
•	 Galvanic isolation between auxiliary supply and
supervision circuit
Application
In a protection system the tripping of circuit
breaker is crucial. Should an interruption occur in
trip circuit, possible network fault would not be
disconnected and the fault would have to be
cleared by another upstream protections in the
power system. The supervision function is
particularly important when there is only one
tripping coil and CB tripping is vital or important
circuit breaker in distribution networks.
The supervision relay type TCS is intended for a
continuous supervision of circuit breaker trip
circuit and gives an alarm for loss of auxiliary
supply, faults on the trip coil or its wires
independent of the breaker position.
The relay supports functions as indicated in Table 1.
Design and principle of operation
The supervision relay TCS is designed to be used
for the supervision of trip circuits and other
important control and monitoring circuits. Block
diagram of the relay is shown in Fig. 1. The
supervision function is based on low-level
(~ 3 mA) current injection principle.
The injected current is sensed by two opto-
couplers. The supervision function in three
steady states of circuit breaker trip circuit can be
seen from fig.2, 3 and 4. In normal condition the
indicator LED glows green and output relays are
in picked up condition.
If in the event of a fault in the measuring circuit,
the measuring current goes below the operating
value of the relay (0.3 - 0.7 mA) or completely
stops flowing, the supervision relay operates
(drops-off) after a delay of 0.6 sec and the
indicator LED turns red. The supervision relay, for
its functioning requires auxiliary voltage (AC or
DC) of rated value to be connected to the
terminals.
This voltage can be the same as that of the
supervised circuit or it could be a separate source
with same magnitude (AC or DC). Should a fault
occur in the auxiliary voltage supply the LED does
not glow and the output relay drops off.
Functionality ANSI IEC
Trip circuit supervision 95 TCS
55TRIP CIRCUIT SUPERVISION REL AY
Fig 1: Block diagram of TCS Relay
Fig 2: Supervision in
pre-close condition
Fig 3: Supervision in
post -close condition
Fig 4: Supervision with
latched trip relay
6 TRIP CIRCUIT SUPERVISON REL AY PRODUCT GUIDE
—
Table 3. Auxiliary power supply
—
Table 4. Output contact details
—
Table 5. Degree of protection of relay
Description Value
Width Frame
Case
108.0 mm
088.0 mm
Height Frame
Case
164.0 mm
112.0 mm
Depth Case 149.5.0 mm (124.5 mm + 25 mm)
Weight Relay 1.00 kg
Description Value
Uaux
nominal 24, 30, 48, 110-125, 220-250 V DC
110-125, 220-250 V AC, 50Hz
Uaux
variation 80...110% of Uaux
Pick-up and Drop-off currentat rated voltage Uaux
and 25° C
0.3 - 0.7 mA
Operate (Drop-off) time at rated voltage Uaux
and 25° C
0.6 –1 sec
Burden at rated voltage
- Auxiliary voltage (W)
- Supervision voltage (W)
24
1.15
0.92
30
1.5
0.10
48
1.7
0.18
110-125
2.9
0.37
220-250
4.1
0.81
Application with AC auxiliary voltage In case relay is supplied through UPS step-wave or square wave,
interposing transformer / surge suppressor is needed to limit aux.
supply peak voltage below the upper limit of the relay
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 0.5 sec 10 A
Make and carry for 3.0 sec 8 A
Breaking capacity when the control-circuit time
constant L/R40 ms, at 48 / 110 / 220 V DC
1.0 A/ 0.25 A / 0.15 A
Electrical endurance as per IEC 60255-23 10,000 operations at 110V DC, 0.35A resistive ,360 op/hr
Description Value
Front side IP 54
Rear side, connection terminals IP 20
—
Technical data
—
Table 2. Dimensions
7
Description Value
Operating temperature range -100
...+550
C
Relative humidity  93%, non-condensing
Atmospheric pressure 86...106kPa
Altitude up to 2000 m
Description Type test value Reference
Dry heat test (humidity  50% )
• Working
• Storing
16h at +550
C
4h at +700
C
IEC 60068-2-2
Dry cold test
• Working
• Storing
16h at - 100
C
4h at - 250
C
IEC 60068-2-1
Damp heat test, cyclic 6 cycles (12 h + 12 h) at
+25°C…+55°C,6 days
Rh  93%
IEC 60068-2-30
Storage temperature test 72h at -400
C
72h at +700
C
IEC 60068-2-1
IEC 60068-2-2
Description Type test value Reference
Dielectric test
• Test voltage 2 kV, 50 Hz, 1 min IEC 60255-27
Impulse voltage test
• Test voltage 5 kV, 1.2/50 μs, 0.5 J IEC 60255-27
Insulation resistance test
• Insulation resistance  100 M Ω at 500 V DC IEC 60255-27
Description Type test value Reference
Vibration tests
• Response
• Endurance / Withstand
10...150 Hz, 0.075 mm / 0.5g,
1 sweep / axis
10...150 Hz, 1.0 g,
20 sweeps / axis
IEC 60255-21-1, class I
Shock tests
• Response
• Endurance / Withstand
5 g, 3 pulses in each direction
15 g, 3 pulses in each direction
IEC 60255-21-2, class I
Bump tests 10 g, 1000 bumps in each direction IEC 60255-21-2, class I
—
Table 6. Environmental conditions
—
Table 7. Environmental tests
—
Table 8. Insulation tests
—
Table 9. Mechanical tests
TECHNIC AL DATA
8 TRIP CIRCUIT SUPERVISON REL AY PRODUCT GUIDE8
TCS relay is equipped with flush mounting
arrangement.
—
Dimensions and mounting
The panel cut-out for flush mounting:
•	 Height : 112.0 + 1.0 mm ( 140.0 + 0.3 mm between
center of mounting holes)
•	 Width : 88.0 + 1.0 mm
108
164
102
Ls
REAR VIESIDE VIEWFRONT VIEW
a) Relay type TCS
REAR VIEW
88
140 + 0.3
112
VIEW CUTOUT
Legend
Aa : Terminal Socket
Db : Mounting hole
Ob : Mounting screw
Ls : Operation signal
+1
-0
+1
-0
Fig 5: Dimesion and mounting
99
Your ordering code:
The relay type and serial number label
identifies the relay. An order number label
is placed on the side of the relay. The
order number consists of a string of codes
generated from auxiliary supply of the relay.
# Description
1-7 Product type
Static 1MYN569
8-10 Relay type
TCS 697
11 Vacant digit
Vacant -
12 Auxiliary supply
24 V DC A
30 V DC B
48 V DC C
110-125V AC/DC E
220-250V AC/DC G
Digit (#) 1-7 8-10 11 12
Code
—
Selection and ordering data
—
Example code
—
Example order code: 1MYN569697-E
Use the ordering key information in Fig.
6 to generate the order number when
ordering complete protection relay.
DIMENSIONS AND MOUNTING
Fig 6: Ordering key for relay
10 TRIP CIRCUIT SUPERVISON REL AY PRODUCT GUIDE10
—
Connection and terminal diagram
Fig 7: Terminal diagram of TCS relay
References
The http://new.abb.com/
mediumvoltage/ distribution-
automation portal offers you
information about the
medium voltage distribution
automation products and solutions.
You will find the latest relevant
information on the trip circuit
supervision relay on product page.
The download area contains the latest
documentation such as product guide
and so on. The selection toll on the web
page find the document category and
language.
Disclaimer
The information in this document is
subject to change without notice and
should not be construed as a
commitment by ABB. ABB assumes no
responsibility for any errors that may
appear in this document.
© Copyright 2017 ABB.
All rights reserved.
ABB is registered trademark of ABB
Group. All other brand or product names
mentioned in this document may be
trademarks or registered trademarks of
their respective holders.
11
© Copyright 2017 ABB. All rights reserved.
Specifications subject to change without notice.
1MDB10213-YN22.9.2017#
—
ABB India Limited
Distribution Automation
Maneja Works
Vadodara-390013, India
Phone: +91 265 6724402
Fax: +91 265 6724407
Email: IN-da.sales@abb.com
http://new.abb.com/mediumvoltage/ distribution-automation

More Related Content

What's hot

Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersSARAVANAN A
 
cable ampacity calculations- IEC
cable ampacity calculations- IECcable ampacity calculations- IEC
cable ampacity calculations- IECJoe Khan
 
Protection settings calculation
Protection settings calculationProtection settings calculation
Protection settings calculationLANOGWA RODGERS
 
basics of busbar and lbb protection
basics of busbar and lbb protection basics of busbar and lbb protection
basics of busbar and lbb protection Salim Palayi
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current ProtectionSARAVANAN A
 
Line differential protection 7 sd52x 7sd610. siemens
Line differential protection 7 sd52x  7sd610. siemensLine differential protection 7 sd52x  7sd610. siemens
Line differential protection 7 sd52x 7sd610. siemensshervin shokri
 
Fundamentals of Microprocessor Based Relays
Fundamentals of Microprocessor Based RelaysFundamentals of Microprocessor Based Relays
Fundamentals of Microprocessor Based Relaysmichaeljmack
 
Relay coordination
Relay coordinationRelay coordination
Relay coordinationD Målîk
 
RELAY ETTING CALCULATION REV-A (DG-298).pdf
RELAY ETTING CALCULATION REV-A (DG-298).pdfRELAY ETTING CALCULATION REV-A (DG-298).pdf
RELAY ETTING CALCULATION REV-A (DG-298).pdfJayWin2
 
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...jbpatel7290
 
Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1Md Irshad Ahmad
 
Line Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relayLine Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relaydavid roy
 
Lightning and Surge Protection Strategy for Instrumentation
Lightning and Surge Protection Strategy for InstrumentationLightning and Surge Protection Strategy for Instrumentation
Lightning and Surge Protection Strategy for InstrumentationRekaNext Capital
 
03-Non-Dir. Overcurrent.ppt
03-Non-Dir. Overcurrent.ppt03-Non-Dir. Overcurrent.ppt
03-Non-Dir. Overcurrent.pptssuserce455a1
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)J. FR
 

What's hot (20)

Autoreclose
AutorecloseAutoreclose
Autoreclose
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineers
 
cable ampacity calculations- IEC
cable ampacity calculations- IECcable ampacity calculations- IEC
cable ampacity calculations- IEC
 
Protection
ProtectionProtection
Protection
 
Power System Protection
Power System ProtectionPower System Protection
Power System Protection
 
Protection settings calculation
Protection settings calculationProtection settings calculation
Protection settings calculation
 
basics of busbar and lbb protection
basics of busbar and lbb protection basics of busbar and lbb protection
basics of busbar and lbb protection
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current Protection
 
Line differential protection 7 sd52x 7sd610. siemens
Line differential protection 7 sd52x  7sd610. siemensLine differential protection 7 sd52x  7sd610. siemens
Line differential protection 7 sd52x 7sd610. siemens
 
Sld for pmcc
Sld for pmccSld for pmcc
Sld for pmcc
 
Fundamentals of Microprocessor Based Relays
Fundamentals of Microprocessor Based RelaysFundamentals of Microprocessor Based Relays
Fundamentals of Microprocessor Based Relays
 
Relay coordination
Relay coordinationRelay coordination
Relay coordination
 
RELAY ETTING CALCULATION REV-A (DG-298).pdf
RELAY ETTING CALCULATION REV-A (DG-298).pdfRELAY ETTING CALCULATION REV-A (DG-298).pdf
RELAY ETTING CALCULATION REV-A (DG-298).pdf
 
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
 
Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1
 
Earthing
EarthingEarthing
Earthing
 
Line Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relayLine Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relay
 
Lightning and Surge Protection Strategy for Instrumentation
Lightning and Surge Protection Strategy for InstrumentationLightning and Surge Protection Strategy for Instrumentation
Lightning and Surge Protection Strategy for Instrumentation
 
03-Non-Dir. Overcurrent.ppt
03-Non-Dir. Overcurrent.ppt03-Non-Dir. Overcurrent.ppt
03-Non-Dir. Overcurrent.ppt
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
 

Similar to Abb trip ckt supervision relay

Esv 300 sxxxst-2017060905595765811.pdf
Esv 300 sxxxst-2017060905595765811.pdfEsv 300 sxxxst-2017060905595765811.pdf
Esv 300 sxxxst-2017060905595765811.pdfLuminhome Lighting
 
RK Engineering ATS (2).pdf
RK Engineering ATS (2).pdfRK Engineering ATS (2).pdf
RK Engineering ATS (2).pdfRK Engineering
 
Catalog bộ nguồn omron S8 FS-C Beeteco.com
Catalog bộ nguồn omron S8 FS-C Beeteco.comCatalog bộ nguồn omron S8 FS-C Beeteco.com
Catalog bộ nguồn omron S8 FS-C Beeteco.comBeeteco
 
Hoja de datos lm 555 y configuraciones
Hoja de datos lm 555 y configuraciones Hoja de datos lm 555 y configuraciones
Hoja de datos lm 555 y configuraciones Marlon Torres
 
Original Opto ACPL-T350 AT350 T350 350 DIP-8 New AVAGO
Original Opto ACPL-T350 AT350 T350 350 DIP-8 New AVAGOOriginal Opto ACPL-T350 AT350 T350 350 DIP-8 New AVAGO
Original Opto ACPL-T350 AT350 T350 350 DIP-8 New AVAGOAUTHELECTRONIC
 
UE One Series Safety Transmitter
UE One Series Safety TransmitterUE One Series Safety Transmitter
UE One Series Safety TransmitterIves Equipment
 
LIFTING PROJECT. ENGINEERING PROJECTpptx
LIFTING PROJECT. ENGINEERING PROJECTpptxLIFTING PROJECT. ENGINEERING PROJECTpptx
LIFTING PROJECT. ENGINEERING PROJECTpptxtryvibesocial
 
ICL7660 Monolithic CMOS Voltage Converters
ICL7660 Monolithic CMOS Voltage ConvertersICL7660 Monolithic CMOS Voltage Converters
ICL7660 Monolithic CMOS Voltage ConvertersGeorgage Zim
 
Advanced motion controls s60a40ac
Advanced motion controls s60a40acAdvanced motion controls s60a40ac
Advanced motion controls s60a40acElectromate
 
Advanced motion controls s30a40ac
Advanced motion controls s30a40acAdvanced motion controls s30a40ac
Advanced motion controls s30a40acElectromate
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersThorne & Derrick International
 

Similar to Abb trip ckt supervision relay (20)

1MDB08202-YN_UVT92m.pdf
1MDB08202-YN_UVT92m.pdf1MDB08202-YN_UVT92m.pdf
1MDB08202-YN_UVT92m.pdf
 
ABB Relay
ABB RelayABB Relay
ABB Relay
 
Lm555
Lm555Lm555
Lm555
 
Esv 300 sxxxst-2017060905595765811.pdf
Esv 300 sxxxst-2017060905595765811.pdfEsv 300 sxxxst-2017060905595765811.pdf
Esv 300 sxxxst-2017060905595765811.pdf
 
Lm555
Lm555Lm555
Lm555
 
Electronic relays
Electronic relaysElectronic relays
Electronic relays
 
RK Engineering ATS (2).pdf
RK Engineering ATS (2).pdfRK Engineering ATS (2).pdf
RK Engineering ATS (2).pdf
 
Catalog bộ nguồn omron S8 FS-C Beeteco.com
Catalog bộ nguồn omron S8 FS-C Beeteco.comCatalog bộ nguồn omron S8 FS-C Beeteco.com
Catalog bộ nguồn omron S8 FS-C Beeteco.com
 
Ref 615
Ref 615Ref 615
Ref 615
 
Air Damper Actuators GSD
Air Damper Actuators GSDAir Damper Actuators GSD
Air Damper Actuators GSD
 
Hoja de datos lm 555 y configuraciones
Hoja de datos lm 555 y configuraciones Hoja de datos lm 555 y configuraciones
Hoja de datos lm 555 y configuraciones
 
Original Opto ACPL-T350 AT350 T350 350 DIP-8 New AVAGO
Original Opto ACPL-T350 AT350 T350 350 DIP-8 New AVAGOOriginal Opto ACPL-T350 AT350 T350 350 DIP-8 New AVAGO
Original Opto ACPL-T350 AT350 T350 350 DIP-8 New AVAGO
 
UE One Series Safety Transmitter
UE One Series Safety TransmitterUE One Series Safety Transmitter
UE One Series Safety Transmitter
 
LIFTING PROJECT. ENGINEERING PROJECTpptx
LIFTING PROJECT. ENGINEERING PROJECTpptxLIFTING PROJECT. ENGINEERING PROJECTpptx
LIFTING PROJECT. ENGINEERING PROJECTpptx
 
18824156
1882415618824156
18824156
 
18824156
1882415618824156
18824156
 
ICL7660 Monolithic CMOS Voltage Converters
ICL7660 Monolithic CMOS Voltage ConvertersICL7660 Monolithic CMOS Voltage Converters
ICL7660 Monolithic CMOS Voltage Converters
 
Advanced motion controls s60a40ac
Advanced motion controls s60a40acAdvanced motion controls s60a40ac
Advanced motion controls s60a40ac
 
Advanced motion controls s30a40ac
Advanced motion controls s30a40acAdvanced motion controls s30a40ac
Advanced motion controls s30a40ac
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment Designers
 

Recently uploaded

Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesPrabhanshu Chaturvedi
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 

Recently uploaded (20)

Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 

Abb trip ckt supervision relay

  • 1. —STATIC MONITORING RELAY Trip circuit supervision relay TCS Product Guide
  • 2. 2 TRIP CIRCUIT SUPERVISON REL AY PRODUCT GUIDE — The supervision relay type TCS is intended for a continuous supervision of circuit breaker trip circuit and gives an alarm for loss of auxiliary supply, faults on the trip coil or its wires independent of the breaker position.
  • 3. 3 — Table of contents TABLE OF CONTENTS 004 -005 Features 005 Design and principle of operation 006-007 Technical data 008 Dimensions and mounting 009 Selection and ordering data 010 Connection and terminal diagram 011 References
  • 4. 4 TRIP CIRCUIT SUPERVISON REL AY PRODUCT GUIDE4 — Trip circuit supervision relay TCS — 1. Application and supported functions Features • Continuous supervision of trip circuit indepen- dent of the circuit breaker position • Extremely low burden on auxiliary source • Complete range of rated AC/DC voltage • Operation indication for trip circuit healthy and unhealthy • Low level measuring current enables application of relay for high burden circuits • Delayed operation to avoid spurious signals during circuit breaker operation • Galvanic isolation between auxiliary supply and supervision circuit Application In a protection system the tripping of circuit breaker is crucial. Should an interruption occur in trip circuit, possible network fault would not be disconnected and the fault would have to be cleared by another upstream protections in the power system. The supervision function is particularly important when there is only one tripping coil and CB tripping is vital or important circuit breaker in distribution networks. The supervision relay type TCS is intended for a continuous supervision of circuit breaker trip circuit and gives an alarm for loss of auxiliary supply, faults on the trip coil or its wires independent of the breaker position. The relay supports functions as indicated in Table 1. Design and principle of operation The supervision relay TCS is designed to be used for the supervision of trip circuits and other important control and monitoring circuits. Block diagram of the relay is shown in Fig. 1. The supervision function is based on low-level (~ 3 mA) current injection principle. The injected current is sensed by two opto- couplers. The supervision function in three steady states of circuit breaker trip circuit can be seen from fig.2, 3 and 4. In normal condition the indicator LED glows green and output relays are in picked up condition. If in the event of a fault in the measuring circuit, the measuring current goes below the operating value of the relay (0.3 - 0.7 mA) or completely stops flowing, the supervision relay operates (drops-off) after a delay of 0.6 sec and the indicator LED turns red. The supervision relay, for its functioning requires auxiliary voltage (AC or DC) of rated value to be connected to the terminals. This voltage can be the same as that of the supervised circuit or it could be a separate source with same magnitude (AC or DC). Should a fault occur in the auxiliary voltage supply the LED does not glow and the output relay drops off. Functionality ANSI IEC Trip circuit supervision 95 TCS
  • 5. 55TRIP CIRCUIT SUPERVISION REL AY Fig 1: Block diagram of TCS Relay Fig 2: Supervision in pre-close condition Fig 3: Supervision in post -close condition Fig 4: Supervision with latched trip relay
  • 6. 6 TRIP CIRCUIT SUPERVISON REL AY PRODUCT GUIDE — Table 3. Auxiliary power supply — Table 4. Output contact details — Table 5. Degree of protection of relay Description Value Width Frame Case 108.0 mm 088.0 mm Height Frame Case 164.0 mm 112.0 mm Depth Case 149.5.0 mm (124.5 mm + 25 mm) Weight Relay 1.00 kg Description Value Uaux nominal 24, 30, 48, 110-125, 220-250 V DC 110-125, 220-250 V AC, 50Hz Uaux variation 80...110% of Uaux Pick-up and Drop-off currentat rated voltage Uaux and 25° C 0.3 - 0.7 mA Operate (Drop-off) time at rated voltage Uaux and 25° C 0.6 –1 sec Burden at rated voltage - Auxiliary voltage (W) - Supervision voltage (W) 24 1.15 0.92 30 1.5 0.10 48 1.7 0.18 110-125 2.9 0.37 220-250 4.1 0.81 Application with AC auxiliary voltage In case relay is supplied through UPS step-wave or square wave, interposing transformer / surge suppressor is needed to limit aux. supply peak voltage below the upper limit of the relay Description Value Rated voltage 250 V AC/DC Continuous contact carry 5 A Make and carry for 0.5 sec 10 A Make and carry for 3.0 sec 8 A Breaking capacity when the control-circuit time constant L/R40 ms, at 48 / 110 / 220 V DC 1.0 A/ 0.25 A / 0.15 A Electrical endurance as per IEC 60255-23 10,000 operations at 110V DC, 0.35A resistive ,360 op/hr Description Value Front side IP 54 Rear side, connection terminals IP 20 — Technical data — Table 2. Dimensions
  • 7. 7 Description Value Operating temperature range -100 ...+550 C Relative humidity 93%, non-condensing Atmospheric pressure 86...106kPa Altitude up to 2000 m Description Type test value Reference Dry heat test (humidity 50% ) • Working • Storing 16h at +550 C 4h at +700 C IEC 60068-2-2 Dry cold test • Working • Storing 16h at - 100 C 4h at - 250 C IEC 60068-2-1 Damp heat test, cyclic 6 cycles (12 h + 12 h) at +25°C…+55°C,6 days Rh 93% IEC 60068-2-30 Storage temperature test 72h at -400 C 72h at +700 C IEC 60068-2-1 IEC 60068-2-2 Description Type test value Reference Dielectric test • Test voltage 2 kV, 50 Hz, 1 min IEC 60255-27 Impulse voltage test • Test voltage 5 kV, 1.2/50 μs, 0.5 J IEC 60255-27 Insulation resistance test • Insulation resistance 100 M Ω at 500 V DC IEC 60255-27 Description Type test value Reference Vibration tests • Response • Endurance / Withstand 10...150 Hz, 0.075 mm / 0.5g, 1 sweep / axis 10...150 Hz, 1.0 g, 20 sweeps / axis IEC 60255-21-1, class I Shock tests • Response • Endurance / Withstand 5 g, 3 pulses in each direction 15 g, 3 pulses in each direction IEC 60255-21-2, class I Bump tests 10 g, 1000 bumps in each direction IEC 60255-21-2, class I — Table 6. Environmental conditions — Table 7. Environmental tests — Table 8. Insulation tests — Table 9. Mechanical tests TECHNIC AL DATA
  • 8. 8 TRIP CIRCUIT SUPERVISON REL AY PRODUCT GUIDE8 TCS relay is equipped with flush mounting arrangement. — Dimensions and mounting The panel cut-out for flush mounting: • Height : 112.0 + 1.0 mm ( 140.0 + 0.3 mm between center of mounting holes) • Width : 88.0 + 1.0 mm 108 164 102 Ls REAR VIESIDE VIEWFRONT VIEW a) Relay type TCS REAR VIEW 88 140 + 0.3 112 VIEW CUTOUT Legend Aa : Terminal Socket Db : Mounting hole Ob : Mounting screw Ls : Operation signal +1 -0 +1 -0 Fig 5: Dimesion and mounting
  • 9. 99 Your ordering code: The relay type and serial number label identifies the relay. An order number label is placed on the side of the relay. The order number consists of a string of codes generated from auxiliary supply of the relay. # Description 1-7 Product type Static 1MYN569 8-10 Relay type TCS 697 11 Vacant digit Vacant - 12 Auxiliary supply 24 V DC A 30 V DC B 48 V DC C 110-125V AC/DC E 220-250V AC/DC G Digit (#) 1-7 8-10 11 12 Code — Selection and ordering data — Example code — Example order code: 1MYN569697-E Use the ordering key information in Fig. 6 to generate the order number when ordering complete protection relay. DIMENSIONS AND MOUNTING Fig 6: Ordering key for relay
  • 10. 10 TRIP CIRCUIT SUPERVISON REL AY PRODUCT GUIDE10 — Connection and terminal diagram Fig 7: Terminal diagram of TCS relay References The http://new.abb.com/ mediumvoltage/ distribution- automation portal offers you information about the medium voltage distribution automation products and solutions. You will find the latest relevant information on the trip circuit supervision relay on product page. The download area contains the latest documentation such as product guide and so on. The selection toll on the web page find the document category and language. Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. © Copyright 2017 ABB. All rights reserved. ABB is registered trademark of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
  • 11. 11
  • 12. © Copyright 2017 ABB. All rights reserved. Specifications subject to change without notice. 1MDB10213-YN22.9.2017# — ABB India Limited Distribution Automation Maneja Works Vadodara-390013, India Phone: +91 265 6724402 Fax: +91 265 6724407 Email: IN-da.sales@abb.com http://new.abb.com/mediumvoltage/ distribution-automation