Submit Search
Upload
Line differential protection 7 sd52x 7sd610. siemens
•
Download as PPT, PDF
•
0 likes
•
335 views
S
shervin shokri
Follow
Setting calculate of siemens line diff protection 7SD610
Read less
Read more
Engineering
Report
Share
Report
Share
1 of 46
Download now
Recommended
Bus Bar protection
Bus Bar protection
srini09
7SA522 Distance Protection Relay For Transmission Lines
7SA522 Distance Protection Relay For Transmission Lines
ashwini reliserv
LBB & BUSBAR PPT Rev 4.5.pdf
LBB & BUSBAR PPT Rev 4.5.pdf
KriteshKumar12
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]
moiz89
Overcurrent protection
Overcurrent protection
Vincent Wedelich, PE MBA
ALSTOM – Micom
ALSTOM – Micom
Meysam Ghasemi
Basics of busbar protection
Basics of busbar protection
Power System Operation
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting Calculations
Power System Operation
Recommended
Bus Bar protection
Bus Bar protection
srini09
7SA522 Distance Protection Relay For Transmission Lines
7SA522 Distance Protection Relay For Transmission Lines
ashwini reliserv
LBB & BUSBAR PPT Rev 4.5.pdf
LBB & BUSBAR PPT Rev 4.5.pdf
KriteshKumar12
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]
moiz89
Overcurrent protection
Overcurrent protection
Vincent Wedelich, PE MBA
ALSTOM – Micom
ALSTOM – Micom
Meysam Ghasemi
Basics of busbar protection
Basics of busbar protection
Power System Operation
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting Calculations
Power System Operation
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
Power System Operation
Digital transformer protection systems
Digital transformer protection systems
michaeljmack
Power transformer protection
Power transformer protection
michaeljmack
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
J. FR
substation protection basics.ppt
substation protection basics.ppt
Salim Palayi
RELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATION
Md Sarowar Alam
Protection of power transformer
Protection of power transformer
Ritesh Verma
Power line carrier communication,ETL41/42
Power line carrier communication,ETL41/42
Sreenivas Gundu
Protection of transformer
Protection of transformer
Sumeet Ratnawat
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over Current Protection
SARAVANAN A
A2.34+transformer+maintenance+tutorial
A2.34+transformer+maintenance+tutorial
Jack Duff
Pole mounted substaion in kerala
Pole mounted substaion in kerala
sebinkb
Relay
Relay
Waqas Ashraf
Underground cables
Underground cables
Abhinay Potlabathini
Power System Protection basics
Power System Protection basics
Rajan Singh Tanwar
protection and relay scheme
protection and relay scheme
infosaneeshss
Line Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relay
david roy
Understanding and testing_the_abb_red670
Understanding and testing_the_abb_red670
طه محمد
7UT612 Transformer Differential Protection relay
7UT612 Transformer Differential Protection relay
ashwini reliserv
Transformer Protection.pdf
Transformer Protection.pdf
RusmanLumbantoruan
7SR23 High Impedance Bus Bar Protection Relay
7SR23 High Impedance Bus Bar Protection Relay
ashwini reliserv
Acs712 datasheet
Acs712 datasheet
Felipe Mejia
More Related Content
What's hot
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
Power System Operation
Digital transformer protection systems
Digital transformer protection systems
michaeljmack
Power transformer protection
Power transformer protection
michaeljmack
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
J. FR
substation protection basics.ppt
substation protection basics.ppt
Salim Palayi
RELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATION
Md Sarowar Alam
Protection of power transformer
Protection of power transformer
Ritesh Verma
Power line carrier communication,ETL41/42
Power line carrier communication,ETL41/42
Sreenivas Gundu
Protection of transformer
Protection of transformer
Sumeet Ratnawat
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over Current Protection
SARAVANAN A
A2.34+transformer+maintenance+tutorial
A2.34+transformer+maintenance+tutorial
Jack Duff
Pole mounted substaion in kerala
Pole mounted substaion in kerala
sebinkb
Relay
Relay
Waqas Ashraf
Underground cables
Underground cables
Abhinay Potlabathini
Power System Protection basics
Power System Protection basics
Rajan Singh Tanwar
protection and relay scheme
protection and relay scheme
infosaneeshss
Line Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relay
david roy
Understanding and testing_the_abb_red670
Understanding and testing_the_abb_red670
طه محمد
7UT612 Transformer Differential Protection relay
7UT612 Transformer Differential Protection relay
ashwini reliserv
Transformer Protection.pdf
Transformer Protection.pdf
RusmanLumbantoruan
What's hot
(20)
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
Digital transformer protection systems
Digital transformer protection systems
Power transformer protection
Power transformer protection
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
substation protection basics.ppt
substation protection basics.ppt
RELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATION
Protection of power transformer
Protection of power transformer
Power line carrier communication,ETL41/42
Power line carrier communication,ETL41/42
Protection of transformer
Protection of transformer
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over Current Protection
A2.34+transformer+maintenance+tutorial
A2.34+transformer+maintenance+tutorial
Pole mounted substaion in kerala
Pole mounted substaion in kerala
Relay
Relay
Underground cables
Underground cables
Power System Protection basics
Power System Protection basics
protection and relay scheme
protection and relay scheme
Line Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relay
Understanding and testing_the_abb_red670
Understanding and testing_the_abb_red670
7UT612 Transformer Differential Protection relay
7UT612 Transformer Differential Protection relay
Transformer Protection.pdf
Transformer Protection.pdf
Similar to Line differential protection 7 sd52x 7sd610. siemens
7SR23 High Impedance Bus Bar Protection Relay
7SR23 High Impedance Bus Bar Protection Relay
ashwini reliserv
Acs712 datasheet
Acs712 datasheet
Felipe Mejia
7SR18 Solkor Protection Relay
7SR18 Solkor Protection Relay
ashwini reliserv
5 FINAL PROJECT REPORT
5 FINAL PROJECT REPORT
Debojyoti Majumdar
7SR220 Overcurrent Relay
7SR220 Overcurrent Relay
ashwini reliserv
Acs712 sensor-arus
Acs712 sensor-arus
Yosafat Indra Inasa
Ls catalog thiet bi tu dong dpr e_dienhathe.vn
Ls catalog thiet bi tu dong dpr e_dienhathe.vn
Dien Ha The
7SR210 Overcurrent Relay
7SR210 Overcurrent Relay
ashwini reliserv
7SR242 Transformer Protection Relay
7SR242 Transformer Protection Relay
ashwini reliserv
7SR11 Overcurrent Relay
7SR11 Overcurrent Relay
ashwini reliserv
Transformerprotectionrelaycalculations.doc
Transformerprotectionrelaycalculations.doc
MdAbdullahAlMamun258178
Netzer DS 37 16 Specsheet
Netzer DS 37 16 Specsheet
Electromate
7SR158 Argus Relay
7SR158 Argus Relay
ashwini reliserv
7SR110 Argus Relay
7SR110 Argus Relay
ashwini reliserv
7SR120 Argus Relay
7SR120 Argus Relay
ashwini reliserv
7SR10 Overcurrent Relay
7SR10 Overcurrent Relay
ashwini reliserv
Optically Isolated Sigma-Delta Modulator ACPL-796J
Optically Isolated Sigma-Delta Modulator ACPL-796J
Premier Farnell
Netzer DS-247-128 Specsheet
Netzer DS-247-128 Specsheet
Electromate
7SR12 Directional Over Current Relay
7SR12 Directional Over Current Relay
ashwini reliserv
2019 Local I/O ESD protection for 28Gbps to 112Gbps SerDes interfaces in adva...
2019 Local I/O ESD protection for 28Gbps to 112Gbps SerDes interfaces in adva...
Sofics
Similar to Line differential protection 7 sd52x 7sd610. siemens
(20)
7SR23 High Impedance Bus Bar Protection Relay
7SR23 High Impedance Bus Bar Protection Relay
Acs712 datasheet
Acs712 datasheet
7SR18 Solkor Protection Relay
7SR18 Solkor Protection Relay
5 FINAL PROJECT REPORT
5 FINAL PROJECT REPORT
7SR220 Overcurrent Relay
7SR220 Overcurrent Relay
Acs712 sensor-arus
Acs712 sensor-arus
Ls catalog thiet bi tu dong dpr e_dienhathe.vn
Ls catalog thiet bi tu dong dpr e_dienhathe.vn
7SR210 Overcurrent Relay
7SR210 Overcurrent Relay
7SR242 Transformer Protection Relay
7SR242 Transformer Protection Relay
7SR11 Overcurrent Relay
7SR11 Overcurrent Relay
Transformerprotectionrelaycalculations.doc
Transformerprotectionrelaycalculations.doc
Netzer DS 37 16 Specsheet
Netzer DS 37 16 Specsheet
7SR158 Argus Relay
7SR158 Argus Relay
7SR110 Argus Relay
7SR110 Argus Relay
7SR120 Argus Relay
7SR120 Argus Relay
7SR10 Overcurrent Relay
7SR10 Overcurrent Relay
Optically Isolated Sigma-Delta Modulator ACPL-796J
Optically Isolated Sigma-Delta Modulator ACPL-796J
Netzer DS-247-128 Specsheet
Netzer DS-247-128 Specsheet
7SR12 Directional Over Current Relay
7SR12 Directional Over Current Relay
2019 Local I/O ESD protection for 28Gbps to 112Gbps SerDes interfaces in adva...
2019 Local I/O ESD protection for 28Gbps to 112Gbps SerDes interfaces in adva...
Recently uploaded
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
9953056974 Low Rate Call Girls In Saket, Delhi NCR
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
DeelipZope
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Dr.Costas Sachpazis
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
ranjana rawat
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
null - The Open Security Community
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
britheesh05
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
vipinkmenon1
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
wendy cai
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
KurinjimalarL3
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
Asst.prof M.Gokilavani
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
Call Girls in Nagpur High Profile
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
PoojaBan
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
ranjana rawat
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
ssuser7cb4ff
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
Suhani Kapoor
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
jennyeacort
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
Suhani Kapoor
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
srsj9000
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
ranjana rawat
microprocessor 8085 and its interfacing
microprocessor 8085 and its interfacing
jaychoudhary37
Recently uploaded
(20)
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
microprocessor 8085 and its interfacing
microprocessor 8085 and its interfacing
Line differential protection 7 sd52x 7sd610. siemens
1.
Copyright © Siemens
AG 2008. All rights reserved. Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD Using numerical protetction devices V4 Siemens Power Academy TD Line Differential Protection 7SD52x / 7SD610 Presentation
2.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 2 07.1 Differential relay 7SD Using numerical protetction devices V4 Line differential relays 87L- SIPROTEC 4 Universal Line Differential Relays 87L - 7SD610 (2 ends) - 7SD522 (2 ends , additional I/O) - 7SD523 (2 up to 6 ends) 7SD610 7SD522/523 7SD522/523
3.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 3 07.1 Differential relay 7SD Using numerical protetction devices V4 Customer Benefits The protection adapts its characteristic by itself. Adaptive measurement reduces the setting complexity and ensures maximum sensitivity. Multi terminal applications up to 6 line ends and redundant Relay to Relay communication. A transformer inside the feeder zone of protection is fully accommodated by the feeder differential protection and configured with a few simple settings. Current transformer mismatch 1:8 without matching transformers. Different CT classes possible. Flexible protection data communication uses a variety of communication media. Secure operation at unsymmetrical propagation times in Communication networks. High speed measurement supervision Simplified commissioning by application of WEB- technology
4.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 4 07.1 Differential relay 7SD Using numerical protetction devices V4 Hardware options 7SD610 1/3 19’’ (3 / 1)* 3 / 1 7 5 1 4 Lines 1 7SD522 ½ 19’’ (3 / 1)* 3 / 1 8 15 1 4 Lines 1 7SD523 ½ 19’’ (3 / 1)* 3 / 1 8 15 1 4 Lines 2 Device Current Inputs (Iph / IE) Voltage Inputs (Uph / UE) Binary Inputs Binary Outputs Life contact LC Display Protection Interfaces * 1A, 5A changeable (jumper position) // depending on ordering data ** 5 high-speed relays 7SD522 1/1 19’’ (3 / 1)* 3 / 1 16 // 24 (23 // 31)** 1 4 Lines 1 7SD523 1/1 19’’ (3 / 1)* 3 / 1 16 // 24 (23 // 31)** 1 4 Lines 2
5.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 5 07.1 Differential relay 7SD Using numerical protetction devices V4 Protection and communication join together Three benefits of 87L-SIPROTEC Differential protection for the universal use with easy to handle settings Two up to six line ends , for serial and parallel compensated lines, handles transformers and compensation coils within the protection zone, tripping time approx. 12 ms with fast high set element Adaptive differential measurement Automatic consideration of CT errors and communication-errors Increased set point during switching-on conditions Direct and modular connection to fibre optic and digital communication networks
6.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 6 07.1 Differential relay 7SD Using numerical protetction devices V4 Main protection function 87: Features of the differential function Phase selective multi-end differential protection (2 - 6 ends). Fundamental vector comparison for the sensitive trip stage (Setting of IDiff> = 0.2- 0.3 IN). Suppress decaying DC-components and harmonics. Therefore allows a sensitive setting. Tripping time 12 ms with fast current comparison protection (Setting of IDiff>> > 1.2 ILoad.max) Dynamic increase of differential set point IDiff> during switch-on of long lines / cables CT saturation detector (only 5 ms saturation free time due to external faults necessary) Phase selective intertrip Settable delay time for single phase faults (feature for inductive compensated networks) Transformer option: Inrush 2nd harmonic restraint with vector group adaptation. Undelayed trip for high fault currents Lockout function (Seal in of trip command)
7.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 7 07.1 Differential relay 7SD Using numerical protetction devices V4 Switch On to Fault protection (SOFT) (with breaker position from remote) 3 stage backup- or emergency O/C protection (IEC /ANSI) 50, 50N, 51, 51N Runs in parallel (backup) or in emergency mode, if 87L is blocked. (from external or due to communication-failure) Three pole and single pole AR (Single pole AR during 2pole fault without earth possible, Adaptive AR - Switch on from one side) Breaker Failure protection 50BF Thermal Overload function (Thermal replica with IOperation) User definable logic and control functions also with signals from remote (AND, OR, NOT, Timer, Flip-Flop) 4 remote commands via binary input or logic inputs (destination relay is addressable), 24 remote signals (only 7SD522/523) Operational values: Currents I, Voltages V, Active/Reactive Power, Delay time, Differential-/Restraint current - Remote end I/V-values Exactly time synchronized fault records with voltages, currents, binary traces and differential and restraint current per phase Fast monitoring functions Fast broken current-wire supervision blocks 87L and avoids malfunction Additional functions in the relay
8.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 8 07.1 Differential relay 7SD Using numerical protetction devices V4 Communication features Front interface DIGSI4 WEB Monitor Service interface (s) DIGSI4 operation modem connection Flexibility due to plug in modules Compatibility to international standards System interface IEC60870-5-103 Profibus DP DNP3.0 Time synchronising IRIG-B (GPS) DCF77 RS232/RS485 electricalmodule Fibre-optic module Opticaldouble-ringmodule
9.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 9 07.1 Differential relay 7SD Using numerical protetction devices V4 IDiff>: Vector comparison Vector comparison offers high sensitivity for high-resistive faults DC components and harmonics are suppressed by Advanced Fourier Filters Suppress decaying DC-component 4 times better then a classical Fourier Filter. Different types of Ct´s allowed, even with a sensitive setting. Relative slow, because of 1 cycle (20 ms,50Hz) filtering window Results in a tripping time from 30-50 ms for high resistive faults (IDiff < 1.2 .. 2 IN)
10.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 10 07.1 Differential relay 7SD Using numerical protetction devices V4 IDiff>: Vector comparison with Advanced Fourier filters (Basic principle) Complex vector I = 2/N ( IC + jIS) Optimized filtering coefficients for 7SD52 / 7SD610 designed for suppressing decaying DC-components 4 times better then conventional Fourier-filters. Overcome stability problems with decaying DC-components Sine component: Cosine component: ωt IC jIS t= 0 I 20 1...N i Δt) n sin(ω N 2 I 1 N 1 n n S 20 N ... 1 i Δt) n cos(ω 2 i 2 i N 2 I 1 N 1 n n N 0 C ∆t i0 i1 i2 0 1 2 N 3 . . . . i N 0 1 2 N 3 . . . . samples from AD-converter n n 7SD52./610: N=20 samples / cycle weight factors
11.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 11 07.1 Differential relay 7SD Using numerical protetction devices V4 Setting: IDiff> = 2 - 3·IC or: 0.2 - 0.3· INCT Assumption: Equal CT type, currents are exactly synchronized (given through analogue measurement ), equal CT-ratio IRest= │I1│+│I2│ IDiff = IDiff> + εCT ·│I1│ + εCT ·│I2│ (IDIFF> =trip threshold) IDiff = IDiff> + εCT ·(│I1│+│I2│) = IDiff> + εCT ·│IRest│ 0 1.0 2.0 4.0 5.0 3.0 6.0 0 1.0 0.5 2.0 1.5 IRest Idiff TripCharacteristic Trip Area BlockArea εCT,1 · │I1│ slope 1 considers linear CT-errors (0.2 – 0.3) slope 2 considers higher CT-errors and CT-saturation (0.4 – 0.6) IDiff> εCT,1 · │I2│ εCT,2 ·│I1│ εCT,2·│I2│ IDiff= │I1+I2│ I1 I2 IC εCT εCT I2 I1 maximum measurement error (ε) due to CT - error IDiff>: Theory of the classical differential tripping characteristic
12.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 12 07.1 Differential relay 7SD Using numerical protetction devices V4 Example: CT class 10P10, Sn = 10VA , Isn= 1A 10% tolerance at KSSC (= 10 = kALF_N ) (in case of nominal burden is connected) Thumb rule: Rct 0.1...0.2 · Rb Nominal burden : If less then rated burden is connected to the CT, the CT- error for load conditions (εLoad) can be used for calculations with currents higher than the nominal current of the CT (Ipn) ! (In the example here: εLoad could be taken for currents up to 4·Ipn ' _ ' _ b ct b ct N ALF b ct b ct N ALF ALF R R R R k P P P P k k 2 10 1 10 2 2 2 ct sn n b R A VA I S R 4 1 2 10 2 _ N ALF ALF k k with: KSSC: rated symmetrical short-circuit current factor (IEC 60044-6) KALF_N: rated Accuracy Limit Factor KALF: actual Accuracy Limit Factor Rct: secondary winding resistance Rb: rated resistive burden R’b: actual resistive burden (RLEADS + RRelay) IDiff>: Settings for the “CT – parameters” (1 of 2)
13.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 13 07.1 Differential relay 7SD Using numerical protetction devices V4 Resulting Relay Parameter (with exact calculation) kALF / kALF_N = 1.5 (calculation as above = 4 , 4 > 1.5 Setting: 1.5) [remains 1 if CT-data's are unknown] IEC 60044 -1: tolerance in load area up to kALF / kALF_N : <2% for 5P (TPY), <3% for 10P (TPX) Ct´s Recommended setting in the relay: 3% for 5P, 5% for 10P total error at accuracy limit kALF_N = 5% for class 5P and 10% for class 10 P Recommended setting in the relay: 10% for 5P, 15% for 10P As the IDiff> step must be (very) sensitive for high resistive faults at maximum Load, for usual applications there is no need to set the parameter 0251 (kALF/KALF_N) higher than 1.5 !! IDiff>: Settings for the “CT – parameters” (2 of 2)
14.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 14 07.1 Differential relay 7SD Using numerical protetction devices V4 Settingsin DIGSI 4 1 ε in % of INCT Example: CT class 5P5 10VA, Rct = 2Ω, Isn = 1A εLoad < 2%, εFault at kALF_N = 5% actual burden Rb’ = 60% of Rb Max. errorof the realCT 5 10 20 0 30 40 2 3 5 8 0 NCT 1 I I 3 50 0254= 10% 0253= 3% kALF 1.5 0251 1.5 k k ALF_N ALF 4 6 7 7.5 kALF_N 1.5 25 Basis for the adaptive restraint current calculation (max. expected differential current due to CT-errors) is the estimated error of each CT from the CT-data's IDiff>: Approximation of the CT- error
15.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 15 07.1 Differential relay 7SD Using numerical protetction devices V4 IDiff>: Example for a setting at nominal current Assumption: CT-ratio is 100/1A, real error of Ct´s is 2% (0.02) up to 1.5 INCT Diff. due to charge + real CT error: IDiff = 0.1 A + 0.02 • │1A│+ 0.02 ·│1A│ = 0.14 A Max. estimated error = Restraint current : IError = 0.25 A + 0.05 • (│1A│+ │1 A│) = 0.35 A I1 =100.5A I2 = -100A IC =10 A εCT1=0.02 εCT2 = -0.02 I1 =1.02 A I2 = - 0.98 A IDiff> = 0.25 =2.5·IC 0 0.5 1.0 2.0 2.5 1.5 3.0 0 0.4 0.2 0.6 IRest =│I1│+│I2│ Idiff =│I1+I2│ Trip Area Block Area 0.35 IError - maximum estimated error at INCT 0.05 0.05 max. CT-error for I < 1.5 INCT ( 5%) CT- error for 1.5·INCT I kALF·INCT (10%) I2 I1 IC maximum measurement error
16.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 16 07.1 Differential relay 7SD Using numerical protetction devices V4 IDiff>: Adaptive differential relaying Restraint current with consideration of the CT- errors IError = ∆IRest*) = IDiff> + εCT1 ·I1 + εCT2 ·I2 = IDiff> + estimated CT- errors Current summation: Max. error summation: Trip, if differential current IDiff exceeds the restraint current (max. error) IDiff = │I1+ I2│ 0 0.1 0.2 0.4 0.5 0.3 0 0.2 0.1 0.4 0.3 ∆IRest IDiff Trip Characteristic 7SD52x / 7SD610 Trip Area Block Area IDiff> Maximum allowed differential current without trip: IDiff = 0.35 A Estimat. CT-error 0.1A Fixed 45° slope – no slope settings required Same example as before! Assumption: Currents are exactly synchronized I2 I1 IC maximum measurement error *) ∆IRest = adaptive restraint current
17.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 17 07.1 Differential relay 7SD Using numerical protetction devices V4 IDiff>: New differential method compared with a classical differential characteristic Classical: IDiff = 0.3 + 0.25·IRest = 0.3 + 0.25·2 = 0.8 (sensitivity under full load) New: IDiff = 0.3 + 0.05·IRest = 0.3 + 0.05·2 = 0.4 (double sensitivity under full load) Assumption: Equal Ct´s on both side, no effects from comms-system, standard settings - Rated burden connected at the Ct´s - Less then rated burden connected (kALF/ kALF_N = 2) 0 1.0 2.0 4.0 5.0 3.0 6.0 0 1.0 0.5 2.0 1.5 IRest Idiff Trip Characteristic Trip Area BlockArea Gain of sensitivity classicalcharacteristic Tripcharacteristic with rated burden Tripcharacteristicwith kALF/ kALF_N = 2 IDiff> = 0.3
18.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 18 07.1 Differential relay 7SD Using numerical protetction devices V4 5P20, 20 VA 1600/1A kALF/ kALF_N = 5 **) εLoad = 3% (0.03) εFault = 10% (0.1) IDiff> = Differential-Setting = 2.5 · IC = 250 A ∆IRest = IDiff> + sum of estimated Ct- errors IDiff = Differential current due to vector summation of the individual currents Case 1 (normal operation) ∆IRest = 2.5·100A + 0.03·800A + 0.03·1200A + 0.05·400A = 330A ∆IRest / IN = 0.206 IDiff = 100 A (=IC) IDiff / IN = 0.0625 IC = 100 A 800 A 4800 A 400 A 800 A 1200 A 5600 A IN = 1600 A Case 2 (External Fault) ∆IRest = 2.5·100A + 0.03·4800A + 0.1·5600A + 0.15·800A = 1074A ∆IRest / IN = 0.671 IDiff = 40 A (due to lower voltage ) IDiff / IN = 0.025 5P20, 20 VA 1600/1A kALF/ kALF_N = 2 **) εLoad = 3% (0.03) εFault = 10% (0.1) 10P10, 10 VA 400/1A kALF/ kALF_N = 1 εLoad = 5% (0.05) εFault = 15% (0.15) **) Settingsforthisexample. Ina realcasebothsettingswouldbe 1.5 IDiff>: Example 1: Adaptive (self-) restraining
19.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 19 07.1 Differential relay 7SD Using numerical protetction devices V4 IDiff>: CT- saturation detector based on harmonic analysis of the current wave form - Signal analysis Differential Current due to saturation I1 I2 - Wave form detector recognize saturation from DC, f2, f3, f4, f5…. rated to the fundamental f1 Factor = 1 - no saturation Factor > 1 - saturation Increase of CT- error with a factor fSat. Results in higher restraint current. More differential current is required for tripping.
20.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 20 07.1 Differential relay 7SD Using numerical protetction devices V4 Trip, if differential current exceeds the estimated error (= increased restraint) IDiff = │I1+I2│ IError =∆IRest = IDiff> +εCT1 ·I1 + fSat· εCT2 ·I2 Current summation: Max. error summation: I2 I1 Maximum measurement error (ε) due to normal CT - error Maximum measurement error (ε) due to saturation. Higher CT - error I1 I2 External Fault 0 0 ∆IRest IDiff TripCharacteristic 7SD52x/ 7SD610 Trip Area Block-Area IDiff> Tripping threshold without saturation Increased tripping threshold with saturation. Required fSat is calculated from the wave-form, so the diff. current caused by saturation does not lead to a malfunction of the relay. IDiff>: Adaptive differential relaying Consideration of nonlinear CT- errors due to saturation
21.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 21 07.1 Differential relay 7SD Using numerical protetction devices V4 IDiff>: Test: max. asymmetrical offset , Ct saturation Settings: 1210/13 0.30 A 0251 1.0 0253 5 % 0254 15 % I1 I2 External Fault 10·INCT ≈3.5A (K1:iE = -K1:iL1)
22.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 22 07.1 Differential relay 7SD Using numerical protetction devices V4 IDiff>: Adaptive consideration of a permanent time difference in transmit- and receive direction 2 sync sync sync sync sync sync I ΔΦ I ΔΦ ΔI 0.06283 360 2π 3.6 3.6 20ms 360 0.2ms ΔΦ : here (50Hz) 20ms 360 Δt ΔΦ I1 I2 IC 0 2.0 ms 2.2 ms Average delay 2.1 ms (Formoredetails: referto7SD52Synchronisation) ∆Isync due to different times in transmit- and receive direction I1 I2 3.6°
23.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 23 07.1 Differential relay 7SD Using numerical protetction devices V4 IDiff>: Adaptive consideration of a permanent time difference. Total “Restraint Current” Diff. current:: IDiff = IC + ∆Isync Rest. current: ∆IRest = IDiff> + CT-errors + ∆Isync ∆Isync 0 0.1 0.2 0.3 0 0.1 0.3 ∆IRest IDiff Trip Characteristic 7SD52x / 7SD610 Trip Area Block Area IDiff>= 0.2 CT- errors Total “Restraint Current”: ∆IRest = IDiff> + fSat1· εCT1 ·I1 + fSat2· εCT2 ·I2 + ∆Isync
24.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 24 07.1 Differential relay 7SD Using numerical protetction devices V4 IDiff>: Sliding data windows after fault inception fault- inception 5 ms Fast current comparison (QDiff) data windows After fault inception the IDiff> step will set it’s values for several data windows to zero, but does not block! 20 ms Vector comparison (IDiff>) data windows
25.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 25 07.1 Differential relay 7SD Using numerical protetction devices V4 IDiff>> (QDiff) : Fast current comparison Fast Current comparison offers high speed tripping and a fast decision for internal or external fault condition Current comparison step doesn't suppress DC-components and harmonics. (simple integration) Therefore recommended setting is > ILoad,max (1.2 - 2 IN). Current comparison decides in 5 ms for internal or external faults (5 ms window) Internal: Immediate trip command (trip time typical 12 ms for 2 or 3 end topology) for differential currents IDiff > 1.2 - 2 IN External: If IFault > 2.5·IDiff>> setting: immediate blocking of the current comparison. Reason: CT-saturation possible. Avoids any risk for stability due to differential current from current comparison.
26.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 26 07.1 Differential relay 7SD Using numerical protetction devices V4 IDiff>> (QDiff) : Fast current comparison algorithm (Basic principle) Q2 0 0 ∆QRest QDiff= │Q1+Q2│ Trip Characteristic 7SD52x/ 7SD610 Trip Area Block Area IDiff>> Settable pick-up value Corrected time instants after end-to-end time synchronisation Calculated restraint values from CT-errors (always higher CT-error is taken). Similar principal as vector comparison for restraint current calculation. Setting IDiff>>: > ILoad,max Q1 Q2 t2 t3 t4 t5 t6 t1 t0 Summated current calculation Q by means of numerical integration Current Measuring window 5 ms (50 Hz) Q3 Q1
27.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 27 07.1 Differential relay 7SD Using numerical protetction devices V4 CT- requirements, mismatch of the primary CT currents 1200/1A, 10P10, 10VA Rct = 2.5Ω, R‘b = 1.1Ω (kALF = 34.7, k’n = 8.33) VT option Not required for differential function 150/5A, 5P20, 50VA Rct = 0.25Ω, R‘b = 0.4Ω (kALF = 69, k’n = 66.6) IP = 10 kA 87L 50/51 50 BF 49 ' b ct b ct ALF_N ALF R R R R k k NCTprim P ' n I I k Mismatch of the primary CT currents: 1A or 5A input selectable in the relay CT data's / errors are set in the relay and automatically considered in the restraint current calculation CT-requirements: 1st condition: kALF > k’n 2nd condition: kALF ≥ 30 or ¼ AC cycle saturation free time (5ms for 50Hz) IP = PrimarySymmetrical Shortcircuit Current 8 I I ) CTprim(min ) CTprim(max
28.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 28 07.1 Differential relay 7SD Using numerical protetction devices V4 Application - Transformer and line/cable in the protection zone 20 MVA, 110 kV/20 kV, YNd1 10P10, 10 VA, 200/1A 10P10, 10 VA, 500/5A Settings of the transformer winding data's in each relay with vector group matching, ratio adaptation and zero sequence elimination Differential set point is rated to the nominal current of the transformer Inrush restraint with second harmonic included (time limit for Cross block) High set element for immediate trip (12 ms) through heavy internal fault currents trip command 2 km 87T 50/51 50 BF 49 ∆
29.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 29 07.1 Differential relay 7SD Using numerical protetction devices V4 Examples for different Topologies 7SD 523 7SD 523 7SD 522 7SD 522 Chain topology with line in the protected zone 7SD 523 7SD 523 7SD 523 7SD 523 Ring topology with line in the protected zone 7SD 523 7SD 523 7SD 522 7SD 522 Chain topology with transformer in the protected zone
30.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 30 07.1 Differential relay 7SD Using numerical protetction devices V4 Synchronous data exchange with HDLC- protocols Very save through 32 bit CRC-checksum Permanent supervision of the data transmission Indication of disturbances and loss of connection Measurement and compensation of the telegram delay time Max. 30 ms per connection, automatic adaptation in that range Immediate detection of delay time changes through switching effects Monitors availability of the data connection Easy settings according the data link (FO or comms-system) (N·64 kBit/s, N settable from 1 - 8 for comms-system, N=8 for FO) Communication device addresses Protection devices are clearly assigned to a defined protection section. Each relay knows the addresses of remote. Detection of reflected telegrams in a loop back in a comms- network - Immediate blocking of 87L function Option: Microsecond exact time synchronisation via GPS 1s pulse input Independent measurement of transmit and receive delay time Hardware prepared for this feature 1) Fibre optic cables Relay to Relay Communication Designed for the use of Digital Communication Networks and FO 1) Main features of the relay to relay communication
31.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 31 07.1 Differential relay 7SD Using numerical protetction devices V4 Relay to Relay Communication (Overview) side 1 side 2 Communication- System or 7SD52x / 610 ISDN or Two (copper-) wires O E FO or 7SD52x / 610 Communication according existing possibilities, the relay remains the same ! O E O E E O E O E O
32.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 32 07.1 Differential relay 7SD Using numerical protetction devices V4 Relay to Relay Communication - Communication modules, Protection Interface (PI) Options for the Protection Interface internal 1.5 km 820 nm Multimode ST- connector O FO 5 internal 3.5 km 820 nm Multimode ST- connector O FO 6 internal 24 km 1300 nm Monomode ST- connector O FO 17 internal 60 km 1300 nm Monomode FC- connector O FO 18 Protection interface 2 Port E (7SD523 only) Synchronous N x 64kB/sec Protection interface 1 Port D Synchronous N x 64kB/sec Plug in modules Remoteline end 2 Remoteline end 1 internal 100 km 1300 nm Monomode FC- connector O FO 19
33.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 33 07.1 Differential relay 7SD Using numerical protetction devices V4 Relay to Relay Communication - Communication converter FO – Communication Net 7XV5662-0AA00 FO 5 820nm E O X.21 or G703.1 FO - ISDN 7XV5662-0AB00 ISDN FO 5 820nm E O FO – Copper wires 7XV5662-0AC00 Copper FO 5 820nm E O
34.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 34 07.1 Differential relay 7SD Using numerical protetction devices V4 Relay to Relay Communication - Application: Fibre optic connection Direct connection with fibre optic (FO) cables - Offers high speed tripping (12 ms), baud rate is 512 kBit/s - Flexible plug in modules for different fibre cables or distances
35.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 35 07.1 Differential relay 7SD Using numerical protetction devices V4 Relay to Relay Communication - Application: Digital communication network E O O E Communication- system Communication converter 7XV5662-0AA00 FO 5, 820 nm, 1.5 km Synchronous electrical interface X.21 (64/128/512 kBit/s) or G703.1 (64 kBit/s) Connection via a communication system with multiplexers - Automatic delay time measurement (adaptive correction from 0 ms - 30 ms) - Immediate detection of split-path condition in the transmit or receive path - Communication addresses clearly identify the relays
36.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 36 07.1 Differential relay 7SD Using numerical protetction devices V4 Relay to Relay Communication - Application: ISDN network E O O E ISDN Communication converter 7XV5662-0AB00 FO 5, 820 nm, 1.5 km Synchronous electrical interface S0 interface (2·64kBit/s) Connection via an ISDN Network - Automatic delay time measurement (adaptive correction from 0 ms - 30 ms) - Immediate detection of split-path condition in the transmit or receive path - Communication addresses clearly identify the relays
37.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 37 07.1 Differential relay 7SD Using numerical protetction devices V4 Relay to Relay Communication - Application: Leased telephone line or Pilot wire (1 of 2) Leased telephone line (standby or dial-up) - 2 wire telephone cable (max. 8 km) E O O E FO 5, 820 nm, 1.5 km Twisted telephone pair max. 8 km (5 miles) Communication converter 7XV5662-0AC00 5 kV insulation integrated, 20 kV Isolation-transformer 7XR9516 available!
38.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 38 07.1 Differential relay 7SD Using numerical protetction devices V4 Relay to Relay Communication - Application: Leased telephone line or Pilot wire (2 of 2) Serial communication New technology on existing (copper-) connection Side 1 Side 2 Transmission of analogue values via: 2 core pilot wire 3 core pilot wire Before: E O O E Digital Transmission, Telegrams via 2 core pilot wire Now:
39.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 39 07.1 Differential relay 7SD Using numerical protetction devices V4 Relay to Relay Communication - Application for a three terminal configuration with 7SD523 Monomode fibre optic cable up to 10 km (1300 nm module) SDH comms-network X21 G703.1 820 nm max. 1.5 km e o PCM multi- plexer Monomode fibre optic cable up to 35 km with 1300 nm interface Distance relay 7SA52 PCM multi- plexer o e o e Communication converter G703.1: 64 kBit X21: N·64 kBit (1≤N≤8) 7XV5662-0AA00 Option: GPS-Time synchronisation - Mixed configurations possible (FO and comms-network) - Ring offers redundant differential system (switching from ring chain takes 200 ms) - Exact time tagging in each relay (resolution 10 µs) - VT inputs as standard (87 function requires only Ct´s) - Connection to a comms-system with a device provided by SIEMENS FC- connector ST-connector ST- connector Option: GPS-Time synchronisation
40.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 40 07.1 Differential relay 7SD Using numerical protetction devices V4 Connection to further Diff. relays Closed ring Partial current summation I3+ I1 I1+ I2 I3 I2 I1 side 1 side 2 side 3 I3+ I1 I2 I1+ I2 I3 Automatic changeover from closed ring- to chain topology, if case of one connection is lost or not available I3 I2 I1 side 1 side 2 side 3 Relay to Relay Communication - Ring- and Chain topology, loss of one data connection tolerated
41.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 41 07.1 Differential relay 7SD Using numerical protetction devices V4 FO5 62.5/125 um side 2 I2 I1 Direct FO- connection. Main connection 512 kBit/s for the 87L function Closed ring side 1 Comms- converter X21 or G703.1 Hot standby connection. Permanent supervision. I2 I1 side 1 Comms- converter FO5 62.5/125 um X21 or G703.1 (64 kBit/s) Hot standby connection active now for 87 L. Switchover takes 20 ms Main connection is inter- rupted Loss of main connection Main connection re-established side 2 Relay to Relay Communication - Hot- Standby connection in a two terminal configuration
42.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 42 07.1 Differential relay 7SD Using numerical protetction devices V4 Commissioning and operating aids (1 of 5) WEB-Technology The homepage of the relay is:http://141.142.255.150 IP-address is set with DIGSI 4 on front- or rear service port WEB server in the relays firmware Server sends it´s HTML-pages and JAVA-code to the WEB Monitor after a DIAL-UP connection 2. HTML page view in a WEB Monitor with the IP-address of the relay http://141.142.255.150 Help system in INTRANET / INTERNET http://www.siprotec.com 1. Serial connection Direct or via modem with a standard DIAL-UP Network Access to the relay with a WEB Monitor
43.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 43 07.1 Differential relay 7SD Using numerical protetction devices V4 Commissioning and operating aids (2 of 5)
44.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 44 07.1 Differential relay 7SD Using numerical protetction devices V4 Commissioning and operating aids (3 of 5)
45.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 45 07.1 Differential relay 7SD Using numerical protetction devices V4 Commissioning and operating aids (4 of 5)
46.
Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power
Academy TD Version: C 4_Page 46 07.1 Differential relay 7SD Using numerical protetction devices V4 Commissioning and operating aids (5 of 5)
Download now