General Application
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Southern States Types CSH and CSH-B
Horizontal Circuit Switchers provide an
economical, versatile, space saving solution
for transformer switching and protection.
The Southern States’ circuit switcher
design combines SF6 puffer interruption
and optional air break isolation functions
into a single compact unit for application on
systems with fault currents to 40 kA rms.
The three phase, group operated,
interrupting device is typically mounted on a
galvanized steel structure provided by
Southern States or by others. Pole
simultaneity is achieved through the use of
shunt trips on opening and through
mechanical interphase linkages on closing.
A motor mechanism supplies the power to
rotate the insulators and to reset both the
tripping and the closing springs.
Two versions of the Southern States
horizontal circuit switcher are available:
 The Type CSH non-blade model is
an end rotating insulator circuit
switcher that mounts independent of
an air disconnect switch.
 The Type CSH-B blade model is a
center rotating insulator circuit
switcher that mounts in series with
an integral vertical break air
disconnect switch.
Both models are offered at voltage ratings
of 38 kV through 170 kV and continuous
current ratings of 1200, 1600, and 2000
amperes.
> Transformer Protection > CIRCUIT SWITCHERS
C A T A L O G B U L L E T I N
Horizontal
Circuit Switchers
Types CSH & CSH-B
38 kV – 170 kV
1200, 1600, 2000 Amperes
Types CSH and CSH-B Horizontal Circuit Switchers
Key Features
 Interrupter design combines the use of SF6 gas
and the most advanced puffer technology.
 Full strength interrupter insulation:
• Maintains full BIL insulation across the
open interrupter.
• Permits use of the CSH non-blade model.
• Increases system reliability.
 Single gap interruption occurs without the use
of voltage grading resistors or capacitors.
 Fast interrupting speeds significantly reduce
system disturbance, minimizing damage to key
system components:
• 5 cycles at 170 kV and below
 Fault closing and circuit making are fully
contained within the interrupter unit:
• Provides superior equipment protection.
• Minimizes system disturbances.
Ratings
 Maximum Voltages
38, 48.3, 72.5, 123, 145,
and 170 kV.
 SF6 Interrupter - BIL
550, and 750 kV
 CSH-B Disconnect Blade - BIL
200, 250, 350, 550, 650, and
750 kV
 Continuous Current - Amperes
1200, 1600, and 2000
 Maximum Source Fault Level
25, 31.5, and 40 kA rms
 Transformer Thru Fault
4 kA rms
 Interrupting Times (60 Hz)
5 cycles
 Close and Latch (fault closing,
multiple duty)
108 kA peak
 3-Second Short Time Current
40 kA rms
Typical Assembly
and Testing
 Each three-phase circuit switcher
is factory pre-assembled,
adjusted, tested, and timed with
its own motor operator.
 After testing, the unit is match-
marked and disassembled in
preparation for shipment or is
shipped assembled on its
common subframe.
 Individual phases are shipped
assembled on insulators at all kV
ratings.
Warranty
 The CSH and CSH-B circuit
switchers are covered by
Southern States’ standard five
year warranty.
Typical Southern States CSH-B Circuit Switcher – Side View
Interrupter Design Features
 System Fault Current
Rated for systems up to 40 kA.
Switching of magnetizing current
occurs without restrikes.
 SF6 Interrupting Medium
Units are typically shipped with 5-
10 PSIG and are topped off to their
rated pressure in the field. It is
possible to ship fully pressurized
when using composite interrupters.
 Operating Temperature Range
-40º C to +40º C for 38 kV through
170 kV. (For applications at colder
or warmer temperatures contact
Southern States.)
 Interrupter Position Indicator
The position of the interrupter is
displayed in the driver window. A
colored indicator, directly connected to
the moving contact, visually indicates
the interrupter’s true position.
 Pressure Gauge
Each phase is equipped with a fill
valve, pressure gauge, and over-
pressure relief device. The pressure
gauge is color-coded and visible from
the ground.
 Full kV BIL
Full BIL across the interrupter permits
the switch blade to remain in the
closed position indefinitely. The single
gap design requires no dividing
resistors.
 Contained Closing
Closing takes place within the
interrupter, not on the blade. Erosion
of the switch blade contacts and jaw
contacts is eliminated, minimizing the
need for maintenance. There is no
prestrike arcing on the switch jaws to
cause system disturbance. No arc
products are released into the
atmosphere. The low noise level
permits installations in residential
areas.
Sequence of Operation
Opening Sequence
Steps 1 through 4 provide a brief
illustration of the opening
sequence, starting from the fully
closed position.
Rotation of the center insulator
12 degrees (by a shunt trip,
motor operator, or manual crank)
releases the opening springs in
the driver mechanism, resulting
in high speed opening of the
interrupter contacts.
An additional 114 degrees of
rotation fully opens the switch
blades as shown in Step 4.
Upon reaching the full open
blade position, the driver
mechanism is reset for a closing
sequence.
Charging of the shunt trip
equipped units occurs during the
last 12 degrees of opening
rotation.
Closing Sequence
Rotation of the center insulator
to close results in blade travel
and charging of the interrupter
closing springs in the driver
mechanism.
The closing springs are released
with the last few degrees of
insulator rotation, closing the
interrupter and charging the
opening springs.
With the CSH-B blade model,
the switch blade is closed first,
followed by closing of the
interrupter, making the circuit in
SF6 gas.
1. Interrupter trips with contacts “A” and “B” in the closed position.
“A” and “B” remain in contact as “B” travels over “A” and
compresses the gas. Gas is ready to flow when the contacts
part.
2. Contacts part – arcing begins – gas flows to extinguish the arc.
3. Gas divides the arc – interruption complete. Full BIL established.
Blade signaled to open.
4. Switch blade now in full open position.
Type CSH
Table 1 – Dimensions and Ratings
Maximum kV Rating 72.5 123 145 170
Interrupter BIL (kV) 550 550 750 750
Standard Insulator TR No. 276 286 288 291
Standard Phase Spacings (Inches)
60
84
--
84
96
102
84
96
102
102
120
--
Operator & Shunt Trip
Voltage (VDC)
48
125
48
125
48
125
48
125
Standard Structure Heights
8’-0”
10’-0”
12’-0”
8’-0”
10’-0”
12’-0”
8’-0”
10’-0”
12’-0”
8’-0”
10’-0”
12’-0”
Dimension “A” (Inches) 76.0 76.0 90.3 90.3
Dimension “B” (Inches) 68.9 83.9 92.9 100.9
Table 2 – Net Weight (Pounds)
Maximum kV Rating 72.5 123 145 170
Structure Height 8’-0” 5612 6174 6624 6976
Structure Height 10’-0” 5751 6313 6787 7115
Structure Height 12’-0” 5887 6449 6899 7251
For dimensions, ratings, and weights of 38 kV and 48.3 kV units contact Southern States.
NOTE:
All information contained herein is
general in nature and is not intended
for specific construction, installation, or
application purposes. Other structure
heights, phase spacings, column
spacings, mounting positions, and
anchor bolt spacings are available to
meet specific installation requirements.
Contact Southern States for details.
Typical Anchor Bolt
Detail Dimensions
Typical Anchor Bolt
Setting Plan
* Contact
Southern States
for detail.
2 anchor bolt setting
positions for 72.5 kV,
123 kV, 145 kV & 170 kV
(72.5 kV and below
ratings can also be
furnished on single
column structures.)
Type CSH-B
Table 1 – Dimensions and Ratings
Maximum kV Rating 72.5 123 145 170
Interrupter/Blade BIL (kV) 550/350 550/550 750/650 750/750
Standard Insulator TR No. 276 286 288 291
Standard Phase Spacings (Inches)
60
84
--
84
96
102
84
96
102
102
120
--
Operator & Shunt Trip
Voltage (VDC)
48
125
48
125
48
125
48
125
Standard Structure Heights
8’-0”
10’-0”
12’-0”
8’-0”
10’-0”
12’-0”
8’-0”
10’-0”
12’-0”
8’-0”
10’-0”
12’-0”
Dimension “A” (Inches) 112.0 127.0 154.5 166.5
Dimension “B” (Inches) 57.4 57.4 72.5 72.5
Dimension “C” (Inches) 45.0 60.0 72.0 84.0
Dimension “D” (Inches) 68.9 83.9 92.9 100.9
Dimension “E” (Inches) 126.5 156.5 177.5 196.5
Table 2 – Net Weight (Pounds)
Maximum kV Rating 72.5 123 145 170
Structure Height 8’-0” 6839 7821 8391 9994
Structure Height 10’-0” 6978 7960 8530 10234
Structure Height 12’-0” 7114 8096 8666 10474
For dimensions, ratings, and weights of 38 kV and 48.3 kV units contact Southern States.
NOTE:
All information contained
herein is general in nature
and is not intended for
specific construction,
installation, or application
purposes. Other structure
heights, phase spacings,
column spacings, mounting positions, and
anchor bolt spacings are available to meet
specific installation requirements. Contact
Southern States for details.
Typical Anchor Bolt
Detail Dimensions
Typical Anchor Bolt Setting Plan
* Contact Southern States
for detail.
2 Anchor Bolt Setting Positions
for 72.5 kV, 123 kV,145 KV &
170 kV (72.5 kV and below
ratings can also be furnished on
single column structures.)
3 Anchor Bolt Setting Positions
for 170 kV.
3 Column
Structure
Circuit Switcher Application Guide
Types CSH and CSH-B Ratings
Application Duty Maximum Amperes
Transformer
Switching and
Protection
Load Breaking 
Parallel Switching
Source Fault Level 
Transformer Thru Fault
1200, 1600, 2000
1200, 1600, 2000
To 40,000 
4,000 
Line or Cable
Switching (LSH/LSH-B)
Alternate: Southern States LLS Products
Loop Splitting
Load Breaking
Line, Cable Dropping
1200, 1600, 2000
1200, 1600, 2000
600
Capacitor Switching
Shunt Capacitor Bank
Switching and Protection
Southern States
CapSwitcher®
Recommended
Reactor Switching
Series Reactor Bypass 1200, 1600, 2000
Shunt Reactor Switching
Southern States
RLSwitcher®
Recommended
 Southern States circuit switchers
can close, carry, and interrupt
the magnetizing current of the
protected transformer.
 The rating shown is applicable for
the following duty cycles: O or CO.
 Tripping of Southern States circuit
switchers must be coordinated with
source-side protective equipment
for short-circuit currents in excess of
this value.
 Rating is based on transient
recovery voltage parameters
defined in Table 2 of ANSI standard
C37.06-2000 for Southern States
circuit switchers rated 38 kV
through 72.5 kV and Table 3 for 123
kV through 170 kV.
 Southern States circuit switchers
are suitable for transformer primary
applications where the inherent
secondary fault current as reflected
on the primary side of the
transformer, assuming an infinite
zero impedance source, does not
exceed 4,000 amperes. The
inherent secondary fault current
may be calculated as follows:
Z
*
E
*
3
100
*
KVA
I =
where
I = Inherent Secondary Fault
Current
KVA = Transformer Self-cooled
3-Phase Rating
E = System Voltage (kV)Z =
Impedance Primary-to-Secondary
in Percent
(Inherent is defined as
secondary-side fault current
as reflected through the
primary side of the
transformer.)
For applications where the
inherent secondary fault
current exceeds the above
limits but where the
maximum expected fault
current, based on
transformer impedance plus
source impedance, is within
these limits, contact Southern
States.
 Southern States circuit switchers are
suitable for line impedance to source
of 3 ohms or greater.
Technical Data Accessories
Operating Current
Ratings
Standard Optional
Device
Description
48
VDC
(Amps)
125
VDC
(Amps)
Motor Inrush
Current
75 33
Motor
Running
Current
15 7.5
Trip Coil
Current
25 25
Reversing
Contactor
Coil
1 0.5
Anti-Pump
Relay Coil
0.2 0.1
Time Delay
Relay Coil
0.2 0.1
Motor Fuses
Heater
Fuses
30
30
15
15
Shunt Trip Unit
Description Ohms
125 VDC Trip Coil
Resistance
15.5
48 VDC Trip Coil
Resistance
5.7
Heater Resistance 500
Structures
Southern States circuit
switchers are designed for
standard support structures
provided by Southern States or
others. For information on
installation on existing support
structures, information on other
pre-designed structures, or for
mobile applications contact
Southern States.
Motor Operator
Southern States type CM-4AE
motor operator is a torsional
output, high torque unit capable
of remote and supervisory
control.
Shunt Trip
The shunt trip provides high
speed tripping for fault
protection of power
transformers. Each phase has
a shunt trip unit consisting of a
spring, a latch, and a solenoid
within a heated housing. When
the system relay senses a fault
the solenoid is energized and
the spring is unlatched. This
gives the insulator a high speed
rotational kick, sufficient to
break ¾ inch ice. The trip coil
can be supplied at 48 VDC or
125 VDC, with either voltage
coil drawing only 8.33 amperes.
The three coils in parallel draw
a total of 25 amperes from the
time the solenoid is energized
until the interrupter clears the
fault, minimizing power
requirements.
Bypass Switch
The bypass switch allows
the interrupter (and integral
disconnect switch blades on
type CSH-B model) to be
opened and closed for
inspection and trip checking
of the circuit switcher
without opening the high
voltage circuit.
External Auxiliary Switch
The external auxiliary switch,
used in control circuits and
interlocking schemes, is
supplied in a separate
weatherproof housing and is
actuated by the vertical
operating pipe.
Ground Switch
The ground switch is a three
phase, group operated device
furnished with the required
momentary rating. Ground
switches can be mounted
in-line with the circuit switcher
bases or perpendicular to the
circuit switcher bases.
Interlock
Mechanical, electrical, and
key interlocks are available if
required for a specific
application.
Type CM-AE Motor Operator
General Application
The CM-4AE is a precision built, torsional output,
high torque motor operator for use with circuit
switchers. It can also be used with disconnect
switches and with load and line switchers such
as the Southern States types LSH-B, LSH,
LLS-II-2000, and LLS-II-3000.
Motor
A permanent magnet motor is available at 48 VDC
and 125 VDC. All motors are NEMA rated and are
supplied with permanently greased ball bearings.
Overload protection is provided by standard dual
element fuses which are easily removed.
Brake
Dynamic braking is standard for all CM-4AE motor
operators.
Cabinet
The CM-4AE has an all-aluminum, maintenance-
free, weatherproof cabinet. Two removable doors
allow easy access to the controls, limit switches,
motor, wiring, and other internal parts. To secure
the motor operator from unauthorized entrance or
operation the side door is latched internally and the
front door has provisions for padlocking.
Conduit Entrance
The bottom of the cabinet is removable for field
drilling to accommodate customer-furnished
conduit.
Reduction Gear
The reduction gear is totally enclosed in a cast
aluminum housing. It is a spur gear design with a
worm gear shaft for manual hand crank operation.
Gears and bearings are lifetime lubricated at the
factory and require no maintenance.
Manual Operation
All type CM-4AE motor operators are designed to
permit manual operation to facilitate installation,
maintenance, and inspection. Operation of the
circuit switcher manually is possible in the event of
a source voltage failure to the motor circuit.
Heater
A 100-watt, thermostatically controlled heater is
provided to prevent condensation inside the
cabinet.
Auxiliary Switch
The auxiliary switch used in control circuits and
interlocking schemes is installed within the motor
operator housing. Contacts are field adjustable via
an Allen wrench without disassembly of the
auxiliary switch.
Standard Features
 Position Indicating Lights
 Dead Front Panel
 Open-Close Pushbuttons
 Decoupler for Vertical Operating Pipe
 12-Stage Auxiliary Switch (8 stages of
which are for customer use)
 120 VAC or 240 VAC, Thermostatically
Controlled, 100-Watt Heater
 Operations Counter
 Fused Pullouts for Motor and Heater
Circuits (provides visible open circuit)
 NEMA 56 Frame Size Motor (48 VDC
or 125 VDC)
 2 Hinged, Removable Doors
 Manual Crank Handle (insertion
automatically disconnects motor circuit)
 Internal Cabinet Light with Toggle
Switch
 Local-Remote Selector Switch
Optional Features
 Extra Auxiliary Switch Stages (up to 4
additional, for a total of 16, 12 of which
are for customer use)
 View Window in Front Cabinet Door
 Screened cabinet vents
 Fused Knife Switches (in lieu of fused
pullouts) for Motor and Heater Circuits
 Molded Case Circuit Breakers (in lieu of
fused pullouts) for Motor and Heater
Circuits
 Terminal Lug for Cabinet Grounding
 Door Actuated Light Switch (in lieu of
toggle switch)
 Trip Circuit Monitoring Relay
 Loss of Voltage Relays
 Duplex Receptacle with GFCI
 Bridge Rectifier (allows 120 VAC input
to be converted into 125 VDC for use in
operating DC internal components of
the motor operator)
 Contact Southern States for Availability
of Optional Features Not Listed.
Feature Location
A Manual Crank Handle
B Decoupler (pistol grip type shown; pin type also available [and
swing handle type is available for disconnect switch
applications])
C Indicating Lights
D Open & Close Pushbuttons
E Operations Counter
F Local-Remote Selector Switch
G Hand Crank Interlock Switch
H Motor, 48 VDC or 125 VDC
I Auxiliary Switches
J Anti-Pump Relay, Time Delay Relay, and Reversing Contactor
K Hinged Removable Doors (2)
L Terminal Blocks (4)
M Fused Pullouts
N Aluminum Cabinet
The Quality Name In High Voltage Switching
30 Georgia Avenue
Hampton, Georgia 30228
Phone (770) 946-4562
Fax (770) 946-8106
e-mail: sales@southernstatesLLC.com
http://www.southernstatesLLC.com
© 2015 Southern States, LLC
PB 803-40 CSH CSH-B-R2 04092015
Printed in the U.S.A.

More Related Content

What's hot

Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsSumeet Ratnawat
 
Iai rcp2 w_sa16c_specsheet
Iai rcp2 w_sa16c_specsheetIai rcp2 w_sa16c_specsheet
Iai rcp2 w_sa16c_specsheetElectromate
 
Iai 08 rc general_cj0203-2_a_p493-522_dust-proof
Iai 08 rc general_cj0203-2_a_p493-522_dust-proofIai 08 rc general_cj0203-2_a_p493-522_dust-proof
Iai 08 rc general_cj0203-2_a_p493-522_dust-proofElectromate
 
ABB KON-17 Medium Voltage MV Outdoor Current Transformers CT's - ABB KON-17
ABB KON-17 Medium Voltage MV Outdoor Current Transformers CT's - ABB KON-17ABB KON-17 Medium Voltage MV Outdoor Current Transformers CT's - ABB KON-17
ABB KON-17 Medium Voltage MV Outdoor Current Transformers CT's - ABB KON-17Thorne & Derrick International
 
Best Medium Voltage Drives for Process Control
Best Medium Voltage Drives for Process ControlBest Medium Voltage Drives for Process Control
Best Medium Voltage Drives for Process ControlSwan May
 
Iai rcp2 w_ra6c_specsheet
Iai rcp2 w_ra6c_specsheetIai rcp2 w_ra6c_specsheet
Iai rcp2 w_ra6c_specsheetElectromate
 
Power transformer manufacturing process and testing
Power transformer manufacturing process and testingPower transformer manufacturing process and testing
Power transformer manufacturing process and testingSai Kumar
 
Iai rcp2 rgs6_c_specsheet
Iai rcp2 rgs6_c_specsheetIai rcp2 rgs6_c_specsheet
Iai rcp2 rgs6_c_specsheetElectromate
 
Pre commissioning checks & periodic inspection on power transformers
Pre commissioning checks & periodic inspection  on power transformersPre commissioning checks & periodic inspection  on power transformers
Pre commissioning checks & periodic inspection on power transformersayyadurai SHANMUGAM
 
Catalog cs contactor d range-dienhathe.vn
Catalog cs contactor d range-dienhathe.vnCatalog cs contactor d range-dienhathe.vn
Catalog cs contactor d range-dienhathe.vnDien Ha The
 
AC-DC Single Output Power Module: PFE Series
AC-DC Single Output Power Module:  PFE SeriesAC-DC Single Output Power Module:  PFE Series
AC-DC Single Output Power Module: PFE SeriesPremier Farnell
 
Iai rcp2 rgd6_c_specsheet
Iai rcp2 rgd6_c_specsheetIai rcp2 rgd6_c_specsheet
Iai rcp2 rgd6_c_specsheetElectromate
 
Iai rcs2 f5_d_specsheet
Iai rcs2 f5_d_specsheetIai rcs2 f5_d_specsheet
Iai rcs2 f5_d_specsheetElectromate
 
1000W Medical AC-DC Power Supply
1000W Medical AC-DC Power Supply1000W Medical AC-DC Power Supply
1000W Medical AC-DC Power SupplyPremier Farnell
 
어태치먼트 적용 벨브
어태치먼트 적용 벨브어태치먼트 적용 벨브
어태치먼트 적용 벨브Sean Kim
 
Ct2000 es manual_english_version_1[1].0
Ct2000 es manual_english_version_1[1].0Ct2000 es manual_english_version_1[1].0
Ct2000 es manual_english_version_1[1].0Toàn Huỳnh
 

What's hot (18)

Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation Equipments
 
Wft053728
Wft053728Wft053728
Wft053728
 
Iai rcp2 w_sa16c_specsheet
Iai rcp2 w_sa16c_specsheetIai rcp2 w_sa16c_specsheet
Iai rcp2 w_sa16c_specsheet
 
Iai 08 rc general_cj0203-2_a_p493-522_dust-proof
Iai 08 rc general_cj0203-2_a_p493-522_dust-proofIai 08 rc general_cj0203-2_a_p493-522_dust-proof
Iai 08 rc general_cj0203-2_a_p493-522_dust-proof
 
ABB KON-17 Medium Voltage MV Outdoor Current Transformers CT's - ABB KON-17
ABB KON-17 Medium Voltage MV Outdoor Current Transformers CT's - ABB KON-17ABB KON-17 Medium Voltage MV Outdoor Current Transformers CT's - ABB KON-17
ABB KON-17 Medium Voltage MV Outdoor Current Transformers CT's - ABB KON-17
 
Electronic relays
Electronic relaysElectronic relays
Electronic relays
 
Best Medium Voltage Drives for Process Control
Best Medium Voltage Drives for Process ControlBest Medium Voltage Drives for Process Control
Best Medium Voltage Drives for Process Control
 
Iai rcp2 w_ra6c_specsheet
Iai rcp2 w_ra6c_specsheetIai rcp2 w_ra6c_specsheet
Iai rcp2 w_ra6c_specsheet
 
Power transformer manufacturing process and testing
Power transformer manufacturing process and testingPower transformer manufacturing process and testing
Power transformer manufacturing process and testing
 
Iai rcp2 rgs6_c_specsheet
Iai rcp2 rgs6_c_specsheetIai rcp2 rgs6_c_specsheet
Iai rcp2 rgs6_c_specsheet
 
Pre commissioning checks & periodic inspection on power transformers
Pre commissioning checks & periodic inspection  on power transformersPre commissioning checks & periodic inspection  on power transformers
Pre commissioning checks & periodic inspection on power transformers
 
Catalog cs contactor d range-dienhathe.vn
Catalog cs contactor d range-dienhathe.vnCatalog cs contactor d range-dienhathe.vn
Catalog cs contactor d range-dienhathe.vn
 
AC-DC Single Output Power Module: PFE Series
AC-DC Single Output Power Module:  PFE SeriesAC-DC Single Output Power Module:  PFE Series
AC-DC Single Output Power Module: PFE Series
 
Iai rcp2 rgd6_c_specsheet
Iai rcp2 rgd6_c_specsheetIai rcp2 rgd6_c_specsheet
Iai rcp2 rgd6_c_specsheet
 
Iai rcs2 f5_d_specsheet
Iai rcs2 f5_d_specsheetIai rcs2 f5_d_specsheet
Iai rcs2 f5_d_specsheet
 
1000W Medical AC-DC Power Supply
1000W Medical AC-DC Power Supply1000W Medical AC-DC Power Supply
1000W Medical AC-DC Power Supply
 
어태치먼트 적용 벨브
어태치먼트 적용 벨브어태치먼트 적용 벨브
어태치먼트 적용 벨브
 
Ct2000 es manual_english_version_1[1].0
Ct2000 es manual_english_version_1[1].0Ct2000 es manual_english_version_1[1].0
Ct2000 es manual_english_version_1[1].0
 

Similar to 18824156

Abb trip ckt supervision relay
Abb trip ckt supervision relayAbb trip ckt supervision relay
Abb trip ckt supervision relaySaurabh Singh
 
Inertia dynamics wrap_spring_specsheet
Inertia dynamics wrap_spring_specsheetInertia dynamics wrap_spring_specsheet
Inertia dynamics wrap_spring_specsheetElectromate
 
Kyn28 metal clad switchgear
Kyn28 metal clad switchgearKyn28 metal clad switchgear
Kyn28 metal clad switchgearJoeChueng
 
Air insulated sf6 ring main unit 36kv
Air insulated sf6 ring main unit 36kvAir insulated sf6 ring main unit 36kv
Air insulated sf6 ring main unit 36kvAUTO RECLOSER
 
Advanced motion controls s60a40ac
Advanced motion controls s60a40acAdvanced motion controls s60a40ac
Advanced motion controls s60a40acElectromate
 
Catalog Contactor Fuji Electric - Beeteco.com
Catalog Contactor Fuji Electric - Beeteco.comCatalog Contactor Fuji Electric - Beeteco.com
Catalog Contactor Fuji Electric - Beeteco.comBeeteco
 
Catalog contactor fuji-electric Mới Nhất - Hạo Phương
Catalog contactor fuji-electric Mới Nhất - Hạo PhươngCatalog contactor fuji-electric Mới Nhất - Hạo Phương
Catalog contactor fuji-electric Mới Nhất - Hạo PhươngCTY TNHH HẠO PHƯƠNG
 
Principles Control & Protection of HVDC Schemes
Principles Control & Protection of HVDC SchemesPrinciples Control & Protection of HVDC Schemes
Principles Control & Protection of HVDC SchemesPower System Operation
 
2017 2 tutorial-ac_hv_circuit_breakers_dufournet
2017 2 tutorial-ac_hv_circuit_breakers_dufournet2017 2 tutorial-ac_hv_circuit_breakers_dufournet
2017 2 tutorial-ac_hv_circuit_breakers_dufournetZİYA MURAT KIRGIZ
 
Advanced motion controls s30a40ac
Advanced motion controls s30a40acAdvanced motion controls s30a40ac
Advanced motion controls s30a40acElectromate
 
Advanced motion controls se30a40ac
Advanced motion controls se30a40acAdvanced motion controls se30a40ac
Advanced motion controls se30a40acElectromate
 
LV SWITCHGEAR -Final PPT.pptx
LV SWITCHGEAR -Final PPT.pptxLV SWITCHGEAR -Final PPT.pptx
LV SWITCHGEAR -Final PPT.pptxshivendra68
 
Advanced motion controls s60a40
Advanced motion controls s60a40Advanced motion controls s60a40
Advanced motion controls s60a40Electromate
 
Brochure_BMS..08_SG202168BEN_B06-0914
Brochure_BMS..08_SG202168BEN_B06-0914Brochure_BMS..08_SG202168BEN_B06-0914
Brochure_BMS..08_SG202168BEN_B06-0914Patrick Volluz
 
Advanced motion controls s100a40ac
Advanced motion controls s100a40acAdvanced motion controls s100a40ac
Advanced motion controls s100a40acElectromate
 
Air insulated sf6 ring main unit
Air insulated sf6 ring main unitAir insulated sf6 ring main unit
Air insulated sf6 ring main unitAUTO RECLOSER
 
Air insulated sf6 ring main unit
Air insulated sf6 ring main unitAir insulated sf6 ring main unit
Air insulated sf6 ring main unitJoeChueng
 

Similar to 18824156 (20)

KYN28 12kV Medium voltage metal clad switchgear
KYN28 12kV Medium voltage metal clad switchgearKYN28 12kV Medium voltage metal clad switchgear
KYN28 12kV Medium voltage metal clad switchgear
 
Wp series manual
Wp series manualWp series manual
Wp series manual
 
Abb trip ckt supervision relay
Abb trip ckt supervision relayAbb trip ckt supervision relay
Abb trip ckt supervision relay
 
Inertia dynamics wrap_spring_specsheet
Inertia dynamics wrap_spring_specsheetInertia dynamics wrap_spring_specsheet
Inertia dynamics wrap_spring_specsheet
 
Kyn28 metal clad switchgear
Kyn28 metal clad switchgearKyn28 metal clad switchgear
Kyn28 metal clad switchgear
 
Air insulated sf6 ring main unit 36kv
Air insulated sf6 ring main unit 36kvAir insulated sf6 ring main unit 36kv
Air insulated sf6 ring main unit 36kv
 
Advanced motion controls s60a40ac
Advanced motion controls s60a40acAdvanced motion controls s60a40ac
Advanced motion controls s60a40ac
 
Catalog Contactor Fuji Electric - Beeteco.com
Catalog Contactor Fuji Electric - Beeteco.comCatalog Contactor Fuji Electric - Beeteco.com
Catalog Contactor Fuji Electric - Beeteco.com
 
Catalog contactor fuji-electric Mới Nhất - Hạo Phương
Catalog contactor fuji-electric Mới Nhất - Hạo PhươngCatalog contactor fuji-electric Mới Nhất - Hạo Phương
Catalog contactor fuji-electric Mới Nhất - Hạo Phương
 
Principles Control & Protection of HVDC Schemes
Principles Control & Protection of HVDC SchemesPrinciples Control & Protection of HVDC Schemes
Principles Control & Protection of HVDC Schemes
 
2017 2 tutorial-ac_hv_circuit_breakers_dufournet
2017 2 tutorial-ac_hv_circuit_breakers_dufournet2017 2 tutorial-ac_hv_circuit_breakers_dufournet
2017 2 tutorial-ac_hv_circuit_breakers_dufournet
 
Advanced motion controls s30a40ac
Advanced motion controls s30a40acAdvanced motion controls s30a40ac
Advanced motion controls s30a40ac
 
Advanced motion controls se30a40ac
Advanced motion controls se30a40acAdvanced motion controls se30a40ac
Advanced motion controls se30a40ac
 
LV SWITCHGEAR -Final PPT.pptx
LV SWITCHGEAR -Final PPT.pptxLV SWITCHGEAR -Final PPT.pptx
LV SWITCHGEAR -Final PPT.pptx
 
Advanced motion controls s60a40
Advanced motion controls s60a40Advanced motion controls s60a40
Advanced motion controls s60a40
 
Brochure_BMS..08_SG202168BEN_B06-0914
Brochure_BMS..08_SG202168BEN_B06-0914Brochure_BMS..08_SG202168BEN_B06-0914
Brochure_BMS..08_SG202168BEN_B06-0914
 
Advanced motion controls s100a40ac
Advanced motion controls s100a40acAdvanced motion controls s100a40ac
Advanced motion controls s100a40ac
 
Air insulated sf6 ring main unit
Air insulated sf6 ring main unitAir insulated sf6 ring main unit
Air insulated sf6 ring main unit
 
Air insulated sf6 ring main unit
Air insulated sf6 ring main unitAir insulated sf6 ring main unit
Air insulated sf6 ring main unit
 
Axpert hivert series mv drive
Axpert hivert series mv driveAxpert hivert series mv drive
Axpert hivert series mv drive
 

Recently uploaded

the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxhumanexperienceaaa
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...RajaP95
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 

Recently uploaded (20)

the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 

18824156

  • 1. General Application • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving solution for transformer switching and protection. The Southern States’ circuit switcher design combines SF6 puffer interruption and optional air break isolation functions into a single compact unit for application on systems with fault currents to 40 kA rms. The three phase, group operated, interrupting device is typically mounted on a galvanized steel structure provided by Southern States or by others. Pole simultaneity is achieved through the use of shunt trips on opening and through mechanical interphase linkages on closing. A motor mechanism supplies the power to rotate the insulators and to reset both the tripping and the closing springs. Two versions of the Southern States horizontal circuit switcher are available:  The Type CSH non-blade model is an end rotating insulator circuit switcher that mounts independent of an air disconnect switch.  The Type CSH-B blade model is a center rotating insulator circuit switcher that mounts in series with an integral vertical break air disconnect switch. Both models are offered at voltage ratings of 38 kV through 170 kV and continuous current ratings of 1200, 1600, and 2000 amperes. > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N Horizontal Circuit Switchers Types CSH & CSH-B 38 kV – 170 kV 1200, 1600, 2000 Amperes
  • 2. Types CSH and CSH-B Horizontal Circuit Switchers Key Features  Interrupter design combines the use of SF6 gas and the most advanced puffer technology.  Full strength interrupter insulation: • Maintains full BIL insulation across the open interrupter. • Permits use of the CSH non-blade model. • Increases system reliability.  Single gap interruption occurs without the use of voltage grading resistors or capacitors.  Fast interrupting speeds significantly reduce system disturbance, minimizing damage to key system components: • 5 cycles at 170 kV and below  Fault closing and circuit making are fully contained within the interrupter unit: • Provides superior equipment protection. • Minimizes system disturbances.
  • 3. Ratings  Maximum Voltages 38, 48.3, 72.5, 123, 145, and 170 kV.  SF6 Interrupter - BIL 550, and 750 kV  CSH-B Disconnect Blade - BIL 200, 250, 350, 550, 650, and 750 kV  Continuous Current - Amperes 1200, 1600, and 2000  Maximum Source Fault Level 25, 31.5, and 40 kA rms  Transformer Thru Fault 4 kA rms  Interrupting Times (60 Hz) 5 cycles  Close and Latch (fault closing, multiple duty) 108 kA peak  3-Second Short Time Current 40 kA rms Typical Assembly and Testing  Each three-phase circuit switcher is factory pre-assembled, adjusted, tested, and timed with its own motor operator.  After testing, the unit is match- marked and disassembled in preparation for shipment or is shipped assembled on its common subframe.  Individual phases are shipped assembled on insulators at all kV ratings. Warranty  The CSH and CSH-B circuit switchers are covered by Southern States’ standard five year warranty. Typical Southern States CSH-B Circuit Switcher – Side View
  • 4. Interrupter Design Features  System Fault Current Rated for systems up to 40 kA. Switching of magnetizing current occurs without restrikes.  SF6 Interrupting Medium Units are typically shipped with 5- 10 PSIG and are topped off to their rated pressure in the field. It is possible to ship fully pressurized when using composite interrupters.  Operating Temperature Range -40º C to +40º C for 38 kV through 170 kV. (For applications at colder or warmer temperatures contact Southern States.)  Interrupter Position Indicator The position of the interrupter is displayed in the driver window. A colored indicator, directly connected to the moving contact, visually indicates the interrupter’s true position.  Pressure Gauge Each phase is equipped with a fill valve, pressure gauge, and over- pressure relief device. The pressure gauge is color-coded and visible from the ground.  Full kV BIL Full BIL across the interrupter permits the switch blade to remain in the closed position indefinitely. The single gap design requires no dividing resistors.  Contained Closing Closing takes place within the interrupter, not on the blade. Erosion of the switch blade contacts and jaw contacts is eliminated, minimizing the need for maintenance. There is no prestrike arcing on the switch jaws to cause system disturbance. No arc products are released into the atmosphere. The low noise level permits installations in residential areas.
  • 5. Sequence of Operation Opening Sequence Steps 1 through 4 provide a brief illustration of the opening sequence, starting from the fully closed position. Rotation of the center insulator 12 degrees (by a shunt trip, motor operator, or manual crank) releases the opening springs in the driver mechanism, resulting in high speed opening of the interrupter contacts. An additional 114 degrees of rotation fully opens the switch blades as shown in Step 4. Upon reaching the full open blade position, the driver mechanism is reset for a closing sequence. Charging of the shunt trip equipped units occurs during the last 12 degrees of opening rotation. Closing Sequence Rotation of the center insulator to close results in blade travel and charging of the interrupter closing springs in the driver mechanism. The closing springs are released with the last few degrees of insulator rotation, closing the interrupter and charging the opening springs. With the CSH-B blade model, the switch blade is closed first, followed by closing of the interrupter, making the circuit in SF6 gas. 1. Interrupter trips with contacts “A” and “B” in the closed position. “A” and “B” remain in contact as “B” travels over “A” and compresses the gas. Gas is ready to flow when the contacts part. 2. Contacts part – arcing begins – gas flows to extinguish the arc. 3. Gas divides the arc – interruption complete. Full BIL established. Blade signaled to open. 4. Switch blade now in full open position.
  • 6. Type CSH Table 1 – Dimensions and Ratings Maximum kV Rating 72.5 123 145 170 Interrupter BIL (kV) 550 550 750 750 Standard Insulator TR No. 276 286 288 291 Standard Phase Spacings (Inches) 60 84 -- 84 96 102 84 96 102 102 120 -- Operator & Shunt Trip Voltage (VDC) 48 125 48 125 48 125 48 125 Standard Structure Heights 8’-0” 10’-0” 12’-0” 8’-0” 10’-0” 12’-0” 8’-0” 10’-0” 12’-0” 8’-0” 10’-0” 12’-0” Dimension “A” (Inches) 76.0 76.0 90.3 90.3 Dimension “B” (Inches) 68.9 83.9 92.9 100.9 Table 2 – Net Weight (Pounds) Maximum kV Rating 72.5 123 145 170 Structure Height 8’-0” 5612 6174 6624 6976 Structure Height 10’-0” 5751 6313 6787 7115 Structure Height 12’-0” 5887 6449 6899 7251 For dimensions, ratings, and weights of 38 kV and 48.3 kV units contact Southern States. NOTE: All information contained herein is general in nature and is not intended for specific construction, installation, or application purposes. Other structure heights, phase spacings, column spacings, mounting positions, and anchor bolt spacings are available to meet specific installation requirements. Contact Southern States for details. Typical Anchor Bolt Detail Dimensions Typical Anchor Bolt Setting Plan * Contact Southern States for detail. 2 anchor bolt setting positions for 72.5 kV, 123 kV, 145 kV & 170 kV (72.5 kV and below ratings can also be furnished on single column structures.)
  • 7. Type CSH-B Table 1 – Dimensions and Ratings Maximum kV Rating 72.5 123 145 170 Interrupter/Blade BIL (kV) 550/350 550/550 750/650 750/750 Standard Insulator TR No. 276 286 288 291 Standard Phase Spacings (Inches) 60 84 -- 84 96 102 84 96 102 102 120 -- Operator & Shunt Trip Voltage (VDC) 48 125 48 125 48 125 48 125 Standard Structure Heights 8’-0” 10’-0” 12’-0” 8’-0” 10’-0” 12’-0” 8’-0” 10’-0” 12’-0” 8’-0” 10’-0” 12’-0” Dimension “A” (Inches) 112.0 127.0 154.5 166.5 Dimension “B” (Inches) 57.4 57.4 72.5 72.5 Dimension “C” (Inches) 45.0 60.0 72.0 84.0 Dimension “D” (Inches) 68.9 83.9 92.9 100.9 Dimension “E” (Inches) 126.5 156.5 177.5 196.5 Table 2 – Net Weight (Pounds) Maximum kV Rating 72.5 123 145 170 Structure Height 8’-0” 6839 7821 8391 9994 Structure Height 10’-0” 6978 7960 8530 10234 Structure Height 12’-0” 7114 8096 8666 10474 For dimensions, ratings, and weights of 38 kV and 48.3 kV units contact Southern States. NOTE: All information contained herein is general in nature and is not intended for specific construction, installation, or application purposes. Other structure heights, phase spacings, column spacings, mounting positions, and anchor bolt spacings are available to meet specific installation requirements. Contact Southern States for details. Typical Anchor Bolt Detail Dimensions Typical Anchor Bolt Setting Plan * Contact Southern States for detail. 2 Anchor Bolt Setting Positions for 72.5 kV, 123 kV,145 KV & 170 kV (72.5 kV and below ratings can also be furnished on single column structures.) 3 Anchor Bolt Setting Positions for 170 kV. 3 Column Structure
  • 8. Circuit Switcher Application Guide Types CSH and CSH-B Ratings Application Duty Maximum Amperes Transformer Switching and Protection Load Breaking  Parallel Switching Source Fault Level  Transformer Thru Fault 1200, 1600, 2000 1200, 1600, 2000 To 40,000  4,000  Line or Cable Switching (LSH/LSH-B) Alternate: Southern States LLS Products Loop Splitting Load Breaking Line, Cable Dropping 1200, 1600, 2000 1200, 1600, 2000 600 Capacitor Switching Shunt Capacitor Bank Switching and Protection Southern States CapSwitcher® Recommended Reactor Switching Series Reactor Bypass 1200, 1600, 2000 Shunt Reactor Switching Southern States RLSwitcher® Recommended  Southern States circuit switchers can close, carry, and interrupt the magnetizing current of the protected transformer.  The rating shown is applicable for the following duty cycles: O or CO.  Tripping of Southern States circuit switchers must be coordinated with source-side protective equipment for short-circuit currents in excess of this value.  Rating is based on transient recovery voltage parameters defined in Table 2 of ANSI standard C37.06-2000 for Southern States circuit switchers rated 38 kV through 72.5 kV and Table 3 for 123 kV through 170 kV.  Southern States circuit switchers are suitable for transformer primary applications where the inherent secondary fault current as reflected on the primary side of the transformer, assuming an infinite zero impedance source, does not exceed 4,000 amperes. The inherent secondary fault current may be calculated as follows: Z * E * 3 100 * KVA I = where I = Inherent Secondary Fault Current KVA = Transformer Self-cooled 3-Phase Rating E = System Voltage (kV)Z = Impedance Primary-to-Secondary in Percent (Inherent is defined as secondary-side fault current as reflected through the primary side of the transformer.) For applications where the inherent secondary fault current exceeds the above limits but where the maximum expected fault current, based on transformer impedance plus source impedance, is within these limits, contact Southern States.  Southern States circuit switchers are suitable for line impedance to source of 3 ohms or greater.
  • 9. Technical Data Accessories Operating Current Ratings Standard Optional Device Description 48 VDC (Amps) 125 VDC (Amps) Motor Inrush Current 75 33 Motor Running Current 15 7.5 Trip Coil Current 25 25 Reversing Contactor Coil 1 0.5 Anti-Pump Relay Coil 0.2 0.1 Time Delay Relay Coil 0.2 0.1 Motor Fuses Heater Fuses 30 30 15 15 Shunt Trip Unit Description Ohms 125 VDC Trip Coil Resistance 15.5 48 VDC Trip Coil Resistance 5.7 Heater Resistance 500 Structures Southern States circuit switchers are designed for standard support structures provided by Southern States or others. For information on installation on existing support structures, information on other pre-designed structures, or for mobile applications contact Southern States. Motor Operator Southern States type CM-4AE motor operator is a torsional output, high torque unit capable of remote and supervisory control. Shunt Trip The shunt trip provides high speed tripping for fault protection of power transformers. Each phase has a shunt trip unit consisting of a spring, a latch, and a solenoid within a heated housing. When the system relay senses a fault the solenoid is energized and the spring is unlatched. This gives the insulator a high speed rotational kick, sufficient to break ¾ inch ice. The trip coil can be supplied at 48 VDC or 125 VDC, with either voltage coil drawing only 8.33 amperes. The three coils in parallel draw a total of 25 amperes from the time the solenoid is energized until the interrupter clears the fault, minimizing power requirements. Bypass Switch The bypass switch allows the interrupter (and integral disconnect switch blades on type CSH-B model) to be opened and closed for inspection and trip checking of the circuit switcher without opening the high voltage circuit. External Auxiliary Switch The external auxiliary switch, used in control circuits and interlocking schemes, is supplied in a separate weatherproof housing and is actuated by the vertical operating pipe. Ground Switch The ground switch is a three phase, group operated device furnished with the required momentary rating. Ground switches can be mounted in-line with the circuit switcher bases or perpendicular to the circuit switcher bases. Interlock Mechanical, electrical, and key interlocks are available if required for a specific application.
  • 10. Type CM-AE Motor Operator General Application The CM-4AE is a precision built, torsional output, high torque motor operator for use with circuit switchers. It can also be used with disconnect switches and with load and line switchers such as the Southern States types LSH-B, LSH, LLS-II-2000, and LLS-II-3000. Motor A permanent magnet motor is available at 48 VDC and 125 VDC. All motors are NEMA rated and are supplied with permanently greased ball bearings. Overload protection is provided by standard dual element fuses which are easily removed. Brake Dynamic braking is standard for all CM-4AE motor operators. Cabinet The CM-4AE has an all-aluminum, maintenance- free, weatherproof cabinet. Two removable doors allow easy access to the controls, limit switches, motor, wiring, and other internal parts. To secure the motor operator from unauthorized entrance or operation the side door is latched internally and the front door has provisions for padlocking. Conduit Entrance The bottom of the cabinet is removable for field drilling to accommodate customer-furnished conduit. Reduction Gear The reduction gear is totally enclosed in a cast aluminum housing. It is a spur gear design with a worm gear shaft for manual hand crank operation. Gears and bearings are lifetime lubricated at the factory and require no maintenance. Manual Operation All type CM-4AE motor operators are designed to permit manual operation to facilitate installation, maintenance, and inspection. Operation of the circuit switcher manually is possible in the event of a source voltage failure to the motor circuit. Heater A 100-watt, thermostatically controlled heater is provided to prevent condensation inside the cabinet. Auxiliary Switch The auxiliary switch used in control circuits and interlocking schemes is installed within the motor operator housing. Contacts are field adjustable via an Allen wrench without disassembly of the auxiliary switch. Standard Features  Position Indicating Lights  Dead Front Panel  Open-Close Pushbuttons  Decoupler for Vertical Operating Pipe  12-Stage Auxiliary Switch (8 stages of which are for customer use)  120 VAC or 240 VAC, Thermostatically Controlled, 100-Watt Heater  Operations Counter  Fused Pullouts for Motor and Heater Circuits (provides visible open circuit)  NEMA 56 Frame Size Motor (48 VDC or 125 VDC)  2 Hinged, Removable Doors  Manual Crank Handle (insertion automatically disconnects motor circuit)  Internal Cabinet Light with Toggle Switch  Local-Remote Selector Switch Optional Features  Extra Auxiliary Switch Stages (up to 4 additional, for a total of 16, 12 of which are for customer use)  View Window in Front Cabinet Door  Screened cabinet vents  Fused Knife Switches (in lieu of fused pullouts) for Motor and Heater Circuits  Molded Case Circuit Breakers (in lieu of fused pullouts) for Motor and Heater Circuits  Terminal Lug for Cabinet Grounding  Door Actuated Light Switch (in lieu of toggle switch)  Trip Circuit Monitoring Relay  Loss of Voltage Relays  Duplex Receptacle with GFCI  Bridge Rectifier (allows 120 VAC input to be converted into 125 VDC for use in operating DC internal components of the motor operator)  Contact Southern States for Availability of Optional Features Not Listed.
  • 11. Feature Location A Manual Crank Handle B Decoupler (pistol grip type shown; pin type also available [and swing handle type is available for disconnect switch applications]) C Indicating Lights D Open & Close Pushbuttons E Operations Counter F Local-Remote Selector Switch G Hand Crank Interlock Switch H Motor, 48 VDC or 125 VDC I Auxiliary Switches J Anti-Pump Relay, Time Delay Relay, and Reversing Contactor K Hinged Removable Doors (2) L Terminal Blocks (4) M Fused Pullouts N Aluminum Cabinet
  • 12. The Quality Name In High Voltage Switching 30 Georgia Avenue Hampton, Georgia 30228 Phone (770) 946-4562 Fax (770) 946-8106 e-mail: sales@southernstatesLLC.com http://www.southernstatesLLC.com © 2015 Southern States, LLC PB 803-40 CSH CSH-B-R2 04092015 Printed in the U.S.A.