Fundamentals of
Substation Arrangement
ELECTRICAL SUB-STATION
Purpose:
1.1 The substations are very much essential to
• Evacuate power from generating stations.
• Transmit to the load centers.
• Distribute to the utilities & ultimate consumers.
The Electrical power generation from Hydel, Thermal, Nuclear and
other generating stations has to be evacuated to load centers.
The generation voltage is limited to 15/18 KV due to the limitation
of the rotating machinery. This bulk power has to be stepped up to
higher voltages depending on quantum of power generated and
distance to the load centers.
Again the power has to be stepped down to different lower
voltages for transmission and distribution.
In between the power houses and ultimate consumers a number of
Transformation and switching stations have to be created. These
are generally known as sub-stations
CLASSIFICATIONS
Accordingly the substations are classified as
Generating substations called as step up substations
Grid Substations called as Step-Down Stations
Switching Stations
Secondary Sub-stations/ Distribution substations
Converting Substation
The generating substations
 Receives electric power from a nearby generating facility and uses a
large power transformer to stepped up the voltage to primary
transmission voltage, for long distance bulk power A.C
Transmission to load Centers.
The grid substations
 Created at suitable load centers along the primary transmission
lines & connect different parts of a grid and are a source for sub
transmission lines or distribution lines. The step-down substation
can change the transmission voltage to a sub transmission voltage.
 The sub transmission voltage lines can then serve as a source to
distribution substations. Sometimes, power is tapped from the sub
transmission line for use in an industrial facility along the way.
Other wise, the power goes to a distribution substation.
Switching Stations
 Provided in between lengthy primary transmission lines:
 To avoid switching surges.
 For easy segregation of faulty zones.
 For providing effective protection to the system in the A.C. network.
 The switching stations also required wherever the EHT line are to be tapped and line to
be extended to different load centers without any step down facility at the switching
stations.
 The number of outgoing lines will be more than the incoming lines, depending on the
load points.
Secondary Sub-Stations
 Located at actual load points along the secondary transmission lines where the voltage is
further stepped down to:
 Sub transmission voltages
 Primary distribution voltage.
 Distribution substations are created where the sub-transmission voltage and primary
distribution voltage are stepped down to supply voltage and feed the actual consumers
through a network of distribution and service line.
Converting Substation
 Converting substations are the ones that change alternating current to direct current in
power transmission. Alternating current is used inside the country while direct current is
sent overseas along with subsea cables.
Classification of Sub-Station based on voltage level
• Generally the following voltage class substations prevailing in India
Designation Description Range
LV or LT Low Voltage or Low Tension Below 1000V AC
HV or HT High Voltage or High Tension All AC Voltages Above 1000V AC
MHV Medium High Voltage Between 1KV to 33KV
HV High Voltage Between 33KV to 132KV
EHV Extra High Voltage 220KV, 400KV
UHV Ultra High Voltage 765KV, 1100KV
HVDC High Voltage Direct Current 400KV, 500KV DC
Types of Sub-Stations:
• Out door- Conventional Air insulated substations (AIS)
• SF6 Gas insulated substations (GIS )
• Hybrid Sub-stations
• Converting substations
The Types of Sub-Stations depends upon:
• The availability of the land in the required place.
• Environmental conditions.
Out door- Conventional Air insulated substations (AIS)
• In Such Substations Busbars & Connectors can be seen by naked
eye.
• All equipment's like LA, Circuit Breakers, Isolators, Transformers,
CTs, VTs etc are installed in outdoor.
• The Busbars are supported on post or strain insulators
• It has Galvanised Steel Structures for supporting the Equipment,
Insulators & Incoming & Outgoing Lines
A. Primary power lines' side
B. Secondary power lines' side
1. Primary power lines
2. Ground wire
3. Overhead lines
4. Voltage Transformer/ CVT
5. Disconnect switch
6. Circuit breaker
7. Current transformer
8. Lightning arrester
9. Main transformer
10.Control building
11.Security fence
12.Secondary power lines
Out door- Conventional Air insulated substations (AIS)
Advantages of Outdoor Substation (AIS):
 Cost of Switchgear installation is low
 In future the extension of the substation installation is easier
 The time required for the erection of air insulated substation is less compared to indoor
substation
 All the equipment in AIS switch yard is within view and therefore the fault location is easier and
related repairing work is also easy
 There is practically no danger of the fault which appears at one point being propagated to
another point for the substation installation because the equipment of the adjoining connections
can be spaced liberally without any appreciable increase in the cost
Disadvantages of Air Insulated Substation (AIS):
 More space is required for outdoor substation when compared to indoor gas insulated substation
(GIS)
 Outdoor switch yards are more vulnerable to faults as it is located in outside atmosphere which
has some influence from pollution, saline environment and other environmental factors.
 Deposition of saline particles on insulators can cause insulator failures. They are also vulnerable
to direct lightning strikes and other external events such as heavy winds, rains and cyclones.
Therefore reliability wise air insulated substation or outdoor substations are relatively low
compared to indoor substation
 Regular maintenance is required compared to indoor substations (Maintenance for Gas Insulated
Substation is very minimal and reliability is very high) as they are exposed to outside environment
SF6 Gas insulated substations (GIS )
• These have been developed during 1970,s and are extremely popular in USA,
Europe, Japan, Middle east Countries etc,
• In 1989 three GIS installations have been executed in India
• They are Compact & requires Very Modest maintenance.
• In GIS various Equipment's like Circuit Breakers, Isolators, CTs, VT, Busbars &
earthing Switches are in the form of metal enclosed- SF6 gas filled Modules.
• The Modules are assembled in accordance with the required Configuration. The
various live parts are enclosed inside the enclosures and are supported on epoxy
post insulators internally.
• The hole installation is filled with SF6 gas at Pressure of about 3Kg/ Cm2
depends up on Manufactures Design.
• Such modules are dispatched in the form of major subassemblies ready to
assembly at Site
• Its only consume the 20% of floor area Conventional AIS
SF6 Gas insulated substations (GIS )
SLD for SF6 Gas insulated substations (GIS )
SF6 Gas insulated substations (GIS )
Locations where Gas Insulated Substation is preferred
• Gas Insulated Substations are preferred in the places where the land requirement for
the substation is difficult such as in populated areas and highly polluted areas where
outdoor switchyard is not preferred.
• In Gas Insulated Substations all the switching electrical equipment such as circuit
breakers, isolators, earth switches, and busbars are completely enclosed inside
modules which are filled with SF6 gas. These modules are factory made and site
assembled. Hence takes very little time for commissioning compared to air-insulated
substations.
• The main advantage of this Gas Insulated Substation is because of its compact size
due to a high dielectric strength of the SF6 gas. And the availability and reliability of
the GIS substations are more compared to air-insulated substations.
• Faults occurring chances of Air insulated substation or conventional substations are
more. Hence GIS substations are provided where the high reliability of electric
power is required such as nuclear plants and other important facilities where un-
interruption of power is more required.
Advantages of GIS Substation
 It occupies very less space (1/10th) compared to ordinary substations. Hence these Gas
Insulated Substations (GIS) are most preferred where area for substation is small (eg:
Cities)
 Most reliable compared to Air Insulated Substations, number of outages due to the
fault is less
 Maintenance Free
 Can be assembled at the shop and modules can be commissioned in the plant easily
Disadvantages of GIS Substation
 Cost is higher compared to Ordinary Conventional Substations
 Care should be taken that no dust particles enter into the live compartments which
result in flashovers
 When fault occurs internally, diagnosis of the fault and rectifying this takes very long
time (outage time is high)
 SF6 gas pressure must be monitored in each compartment, reduction in the pressure of
the SF6 gas in any module results in flashovers and faults.
Converting Substations –
 In such types of substations, AC power converting into DC power or
vice versa or it can convert high frequency to lower frequency or vice
versa.
Switching Schemes
The selection of switching scheme depend upon:
Reliability factor
Availability of the space
Economics (project cost)
There can be several combinations in which the equipment's,
bus-bars, structures etc. can be arranged to achieve a particular
switching scheme.
Importance of Busbar
There are several types of busbar arrangements used in power
systems. There are many factors to consider when selecting a
busbar, such as reliability, flexibility, and cost. In selecting a
particular busbar arrangement, the following factors should be
considered.
The busbar layout is simple and easy to maintain.
System maintenance did not affect its continuity.
Busbar installation is economical.
A single busbar is used in the case of small substations, where
continuity of supply is not critical. But in the large substations,
an additional bus bar is used in the system to avoid
interruption in the supply.
1 2 3 n-1 n
ZONE 1
- - - -
• Distribution and lower transmission voltage levels
• No operating flexibility
• Fault on the bus trips all circuit breakers
Advantages
Initial costs are low.
Less maintenance is required.
The operation is simple.
Disadvantages
The entire supply is disturbed when the fault occurs.
As the arrangement provides the least flexibility, it is used in small substations where continuity of
supply is not crucial.
Single bus - single breaker
ZONE 1
ZONE 2
• Distribution and lower transmission voltage levels
• Limited operating flexibility
Multiple bus sections - single breaker with
bus tie
ZONE 1
ZONE 2
• Transmission and distribution voltage levels
• Breaker maintenance without circuit removal
• Fault on a bus disconnects only the circuits being connected to
that bus
Double bus - single breaker with bus tie
ZONE 1
MAIN BUS
TRANFER BUS
• Increased operating flexibility
• A bus fault requires tripping all breakers
• Transfer bus for breaker maintenance
Main and transfer buses
ZONE 1
ZONE 2
• Very high operating flexibility
• Transfer bus for breaker maintenance
Double bus – single breaker w/ transfer bus
ZONE 1
ZONE 2
• High operating flexibility
• Line protection covers bus section between two CTs
• Fault on a bus does not disturb the power to circuits
Double bus - double breaker
ZONE 1
ZONE 2
• Used on higher voltage levels
• More operating flexibility
• Requires more breakers
• Middle bus sections covered by line or other equipment
protection
Breaker-and-a-half bus
• Higher voltage levels
• High operating flexibility with minimum breakers
• Separate bus protection not required at line positions
B1 B2
TB1
L1 L2
L3 L4
TB1
Ring bus
Bus components breakers
SF6, EHV & HV - Synchropuff
Low Voltage circuit breakers
BUS 2
CB 1
BUS 1
ISO 1 ISO 2
ISO 3
BYPASS
-
+
F1a
F1c
Contact Input F1a On
Contact Input F1c On
F1b
ISOLATOR
1
ISOLATOR 1 OPEN
7B 7A
BUS 1
-
+
F1a
F1c
Contact Input F1a On
Contact Input F1c On
F1b
ISOLATOR
1
ISOLATOR 1 CLOSED
7B 7A
BUS 1
Disconnect switches & auxiliary contacts
BUS 2
CB 1
BUS 1
ISO 1 ISO 2
ISO 3
BYPASS
BUS 2
CB 1
BUS 1
ISO 1 ISO 2
ISO 3
BYPASS
Current Transformers
Oil insulated current transformer
(35kV up to 800kV)
Gas (SF6) insulated current
transformer
Bushing type (medium
voltage switchgear)
Substation_fundamental.pptx
Substation_fundamental.pptx
Substation_fundamental.pptx

More Related Content

Similar to Substation_fundamental.pptx

substation 101
substation 101substation 101
substation 101
danica11
 
Electric power substation
Electric power substationElectric power substation
Electric power substation
qwerty25ty
 
Deepak kumar
Deepak kumarDeepak kumar
Deepak kumar
Deepak Kumar
 

Similar to Substation_fundamental.pptx (20)

FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWARFACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
 
Design of substation (with Transformer Design)
Design of substation (with Transformer Design) Design of substation (with Transformer Design)
Design of substation (with Transformer Design)
 
Gas insulated substation 1
Gas insulated substation 1Gas insulated substation 1
Gas insulated substation 1
 
substation 101
substation 101substation 101
substation 101
 
SUBSTATION OVERVIEW - A presentation on substation
SUBSTATION OVERVIEW - A presentation on substationSUBSTATION OVERVIEW - A presentation on substation
SUBSTATION OVERVIEW - A presentation on substation
 
Gas insulated substation.
Gas insulated substation.Gas insulated substation.
Gas insulated substation.
 
27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations
 
Seminar Report on 220 KV Grid Sub Station on Bundi
Seminar Report on 220 KV  Grid Sub Station on Bundi Seminar Report on 220 KV  Grid Sub Station on Bundi
Seminar Report on 220 KV Grid Sub Station on Bundi
 
GIS (Gas-Insulated Substation) by Bharat & Shanni
GIS (Gas-Insulated Substation) by Bharat & ShanniGIS (Gas-Insulated Substation) by Bharat & Shanni
GIS (Gas-Insulated Substation) by Bharat & Shanni
 
Design of substation
Design of substationDesign of substation
Design of substation
 
Report on 220kv substation at Jassure
Report on 220kv substation at JassureReport on 220kv substation at Jassure
Report on 220kv substation at Jassure
 
Substation and It's Equipment
Substation and It's Equipment Substation and It's Equipment
Substation and It's Equipment
 
Electric power substation
Electric power substationElectric power substation
Electric power substation
 
Seminar on Gas Insulated Substation
Seminar on Gas Insulated SubstationSeminar on Gas Insulated Substation
Seminar on Gas Insulated Substation
 
TYPES OF SUBSTATION.pptx
TYPES OF SUBSTATION.pptxTYPES OF SUBSTATION.pptx
TYPES OF SUBSTATION.pptx
 
Busduct___Busbar.pptx
Busduct___Busbar.pptxBusduct___Busbar.pptx
Busduct___Busbar.pptx
 
Tuhas chapter 6,distribution substitution
Tuhas chapter 6,distribution substitutionTuhas chapter 6,distribution substitution
Tuhas chapter 6,distribution substitution
 
Indoor & outdoor substations, an overview
Indoor & outdoor substations, an overviewIndoor & outdoor substations, an overview
Indoor & outdoor substations, an overview
 
Deepak kumar
Deepak kumarDeepak kumar
Deepak kumar
 
Gis ppt (gas insulated sub station) deepak kumar kannaujiya,
Gis ppt (gas insulated sub station)  deepak kumar kannaujiya,Gis ppt (gas insulated sub station)  deepak kumar kannaujiya,
Gis ppt (gas insulated sub station) deepak kumar kannaujiya,
 

More from Satish Pydimarla

Testing_of_transformers_adjusted.ppt
Testing_of_transformers_adjusted.pptTesting_of_transformers_adjusted.ppt
Testing_of_transformers_adjusted.ppt
Satish Pydimarla
 
Zaragoza Factory_Our product_ EN.ppt
Zaragoza Factory_Our product_ EN.pptZaragoza Factory_Our product_ EN.ppt
Zaragoza Factory_Our product_ EN.ppt
Satish Pydimarla
 
Presentation-Kalinga Stadium.pptx
Presentation-Kalinga Stadium.pptxPresentation-Kalinga Stadium.pptx
Presentation-Kalinga Stadium.pptx
Satish Pydimarla
 
transformeronno-load-200825063948.pptx
transformeronno-load-200825063948.pptxtransformeronno-load-200825063948.pptx
transformeronno-load-200825063948.pptx
Satish Pydimarla
 
Understanding_lightning_protection.pptx
Understanding_lightning_protection.pptxUnderstanding_lightning_protection.pptx
Understanding_lightning_protection.pptx
Satish Pydimarla
 

More from Satish Pydimarla (20)

9310091.ppt
9310091.ppt9310091.ppt
9310091.ppt
 
control room.pptx
control room.pptxcontrol room.pptx
control room.pptx
 
Thermovision Test.ppt
Thermovision Test.pptThermovision Test.ppt
Thermovision Test.ppt
 
4143813.ppt
4143813.ppt4143813.ppt
4143813.ppt
 
Transformer_theory.pptx
Transformer_theory.pptxTransformer_theory.pptx
Transformer_theory.pptx
 
Testing_of_transformers_adjusted.ppt
Testing_of_transformers_adjusted.pptTesting_of_transformers_adjusted.ppt
Testing_of_transformers_adjusted.ppt
 
Zaragoza Factory_Our product_ EN.ppt
Zaragoza Factory_Our product_ EN.pptZaragoza Factory_Our product_ EN.ppt
Zaragoza Factory_Our product_ EN.ppt
 
transformerprotection-180102061059.pdf
transformerprotection-180102061059.pdftransformerprotection-180102061059.pdf
transformerprotection-180102061059.pdf
 
3-Phase-Transformer (1).pptx
3-Phase-Transformer (1).pptx3-Phase-Transformer (1).pptx
3-Phase-Transformer (1).pptx
 
Electrical_Engg_Basic.PPT
Electrical_Engg_Basic.PPTElectrical_Engg_Basic.PPT
Electrical_Engg_Basic.PPT
 
Presentation-Kalinga Stadium.pptx
Presentation-Kalinga Stadium.pptxPresentation-Kalinga Stadium.pptx
Presentation-Kalinga Stadium.pptx
 
understandingtransformervectorgroup-180629014651.pptx
understandingtransformervectorgroup-180629014651.pptxunderstandingtransformervectorgroup-180629014651.pptx
understandingtransformervectorgroup-180629014651.pptx
 
transformeronno-load-200825063948.pptx
transformeronno-load-200825063948.pptxtransformeronno-load-200825063948.pptx
transformeronno-load-200825063948.pptx
 
332038674-Vector-Group-of-Transformers.ppt
332038674-Vector-Group-of-Transformers.ppt332038674-Vector-Group-of-Transformers.ppt
332038674-Vector-Group-of-Transformers.ppt
 
tcee-161003100321.pptx
tcee-161003100321.pptxtcee-161003100321.pptx
tcee-161003100321.pptx
 
Parall Operation Transformers
Parall Operation TransformersParall Operation Transformers
Parall Operation Transformers
 
Understanding_lightning_protection.pptx
Understanding_lightning_protection.pptxUnderstanding_lightning_protection.pptx
Understanding_lightning_protection.pptx
 
Understanding VCB.pptx
Understanding VCB.pptxUnderstanding VCB.pptx
Understanding VCB.pptx
 
CT & PT.pptx
CT & PT.pptxCT & PT.pptx
CT & PT.pptx
 
Construction of HV Transmission Lines etc.pptx
Construction of HV Transmission Lines etc.pptxConstruction of HV Transmission Lines etc.pptx
Construction of HV Transmission Lines etc.pptx
 

Recently uploaded

Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
Kamal Acharya
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 

Recently uploaded (20)

Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
 
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
 
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
 
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
 
Computer Graphics Introduction To Curves
Computer Graphics Introduction To CurvesComputer Graphics Introduction To Curves
Computer Graphics Introduction To Curves
 
Linux Systems Programming: Inter Process Communication (IPC) using Pipes
Linux Systems Programming: Inter Process Communication (IPC) using PipesLinux Systems Programming: Inter Process Communication (IPC) using Pipes
Linux Systems Programming: Inter Process Communication (IPC) using Pipes
 
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
 

Substation_fundamental.pptx

  • 2. ELECTRICAL SUB-STATION Purpose: 1.1 The substations are very much essential to • Evacuate power from generating stations. • Transmit to the load centers. • Distribute to the utilities & ultimate consumers.
  • 3. The Electrical power generation from Hydel, Thermal, Nuclear and other generating stations has to be evacuated to load centers. The generation voltage is limited to 15/18 KV due to the limitation of the rotating machinery. This bulk power has to be stepped up to higher voltages depending on quantum of power generated and distance to the load centers. Again the power has to be stepped down to different lower voltages for transmission and distribution. In between the power houses and ultimate consumers a number of Transformation and switching stations have to be created. These are generally known as sub-stations
  • 4. CLASSIFICATIONS Accordingly the substations are classified as Generating substations called as step up substations Grid Substations called as Step-Down Stations Switching Stations Secondary Sub-stations/ Distribution substations Converting Substation
  • 5. The generating substations  Receives electric power from a nearby generating facility and uses a large power transformer to stepped up the voltage to primary transmission voltage, for long distance bulk power A.C Transmission to load Centers. The grid substations  Created at suitable load centers along the primary transmission lines & connect different parts of a grid and are a source for sub transmission lines or distribution lines. The step-down substation can change the transmission voltage to a sub transmission voltage.  The sub transmission voltage lines can then serve as a source to distribution substations. Sometimes, power is tapped from the sub transmission line for use in an industrial facility along the way. Other wise, the power goes to a distribution substation.
  • 6. Switching Stations  Provided in between lengthy primary transmission lines:  To avoid switching surges.  For easy segregation of faulty zones.  For providing effective protection to the system in the A.C. network.  The switching stations also required wherever the EHT line are to be tapped and line to be extended to different load centers without any step down facility at the switching stations.  The number of outgoing lines will be more than the incoming lines, depending on the load points. Secondary Sub-Stations  Located at actual load points along the secondary transmission lines where the voltage is further stepped down to:  Sub transmission voltages  Primary distribution voltage.  Distribution substations are created where the sub-transmission voltage and primary distribution voltage are stepped down to supply voltage and feed the actual consumers through a network of distribution and service line.
  • 7. Converting Substation  Converting substations are the ones that change alternating current to direct current in power transmission. Alternating current is used inside the country while direct current is sent overseas along with subsea cables.
  • 8. Classification of Sub-Station based on voltage level • Generally the following voltage class substations prevailing in India Designation Description Range LV or LT Low Voltage or Low Tension Below 1000V AC HV or HT High Voltage or High Tension All AC Voltages Above 1000V AC MHV Medium High Voltage Between 1KV to 33KV HV High Voltage Between 33KV to 132KV EHV Extra High Voltage 220KV, 400KV UHV Ultra High Voltage 765KV, 1100KV HVDC High Voltage Direct Current 400KV, 500KV DC
  • 9. Types of Sub-Stations: • Out door- Conventional Air insulated substations (AIS) • SF6 Gas insulated substations (GIS ) • Hybrid Sub-stations • Converting substations The Types of Sub-Stations depends upon: • The availability of the land in the required place. • Environmental conditions.
  • 10. Out door- Conventional Air insulated substations (AIS) • In Such Substations Busbars & Connectors can be seen by naked eye. • All equipment's like LA, Circuit Breakers, Isolators, Transformers, CTs, VTs etc are installed in outdoor. • The Busbars are supported on post or strain insulators • It has Galvanised Steel Structures for supporting the Equipment, Insulators & Incoming & Outgoing Lines
  • 11. A. Primary power lines' side B. Secondary power lines' side 1. Primary power lines 2. Ground wire 3. Overhead lines 4. Voltage Transformer/ CVT 5. Disconnect switch 6. Circuit breaker 7. Current transformer 8. Lightning arrester 9. Main transformer 10.Control building 11.Security fence 12.Secondary power lines Out door- Conventional Air insulated substations (AIS)
  • 12. Advantages of Outdoor Substation (AIS):  Cost of Switchgear installation is low  In future the extension of the substation installation is easier  The time required for the erection of air insulated substation is less compared to indoor substation  All the equipment in AIS switch yard is within view and therefore the fault location is easier and related repairing work is also easy  There is practically no danger of the fault which appears at one point being propagated to another point for the substation installation because the equipment of the adjoining connections can be spaced liberally without any appreciable increase in the cost Disadvantages of Air Insulated Substation (AIS):  More space is required for outdoor substation when compared to indoor gas insulated substation (GIS)  Outdoor switch yards are more vulnerable to faults as it is located in outside atmosphere which has some influence from pollution, saline environment and other environmental factors.  Deposition of saline particles on insulators can cause insulator failures. They are also vulnerable to direct lightning strikes and other external events such as heavy winds, rains and cyclones. Therefore reliability wise air insulated substation or outdoor substations are relatively low compared to indoor substation  Regular maintenance is required compared to indoor substations (Maintenance for Gas Insulated Substation is very minimal and reliability is very high) as they are exposed to outside environment
  • 13. SF6 Gas insulated substations (GIS ) • These have been developed during 1970,s and are extremely popular in USA, Europe, Japan, Middle east Countries etc, • In 1989 three GIS installations have been executed in India • They are Compact & requires Very Modest maintenance. • In GIS various Equipment's like Circuit Breakers, Isolators, CTs, VT, Busbars & earthing Switches are in the form of metal enclosed- SF6 gas filled Modules. • The Modules are assembled in accordance with the required Configuration. The various live parts are enclosed inside the enclosures and are supported on epoxy post insulators internally. • The hole installation is filled with SF6 gas at Pressure of about 3Kg/ Cm2 depends up on Manufactures Design. • Such modules are dispatched in the form of major subassemblies ready to assembly at Site • Its only consume the 20% of floor area Conventional AIS
  • 14. SF6 Gas insulated substations (GIS )
  • 15. SLD for SF6 Gas insulated substations (GIS )
  • 16. SF6 Gas insulated substations (GIS )
  • 17. Locations where Gas Insulated Substation is preferred • Gas Insulated Substations are preferred in the places where the land requirement for the substation is difficult such as in populated areas and highly polluted areas where outdoor switchyard is not preferred. • In Gas Insulated Substations all the switching electrical equipment such as circuit breakers, isolators, earth switches, and busbars are completely enclosed inside modules which are filled with SF6 gas. These modules are factory made and site assembled. Hence takes very little time for commissioning compared to air-insulated substations. • The main advantage of this Gas Insulated Substation is because of its compact size due to a high dielectric strength of the SF6 gas. And the availability and reliability of the GIS substations are more compared to air-insulated substations. • Faults occurring chances of Air insulated substation or conventional substations are more. Hence GIS substations are provided where the high reliability of electric power is required such as nuclear plants and other important facilities where un- interruption of power is more required.
  • 18. Advantages of GIS Substation  It occupies very less space (1/10th) compared to ordinary substations. Hence these Gas Insulated Substations (GIS) are most preferred where area for substation is small (eg: Cities)  Most reliable compared to Air Insulated Substations, number of outages due to the fault is less  Maintenance Free  Can be assembled at the shop and modules can be commissioned in the plant easily Disadvantages of GIS Substation  Cost is higher compared to Ordinary Conventional Substations  Care should be taken that no dust particles enter into the live compartments which result in flashovers  When fault occurs internally, diagnosis of the fault and rectifying this takes very long time (outage time is high)  SF6 gas pressure must be monitored in each compartment, reduction in the pressure of the SF6 gas in any module results in flashovers and faults.
  • 19. Converting Substations –  In such types of substations, AC power converting into DC power or vice versa or it can convert high frequency to lower frequency or vice versa. Switching Schemes The selection of switching scheme depend upon: Reliability factor Availability of the space Economics (project cost) There can be several combinations in which the equipment's, bus-bars, structures etc. can be arranged to achieve a particular switching scheme.
  • 20. Importance of Busbar There are several types of busbar arrangements used in power systems. There are many factors to consider when selecting a busbar, such as reliability, flexibility, and cost. In selecting a particular busbar arrangement, the following factors should be considered. The busbar layout is simple and easy to maintain. System maintenance did not affect its continuity. Busbar installation is economical. A single busbar is used in the case of small substations, where continuity of supply is not critical. But in the large substations, an additional bus bar is used in the system to avoid interruption in the supply.
  • 21. 1 2 3 n-1 n ZONE 1 - - - - • Distribution and lower transmission voltage levels • No operating flexibility • Fault on the bus trips all circuit breakers Advantages Initial costs are low. Less maintenance is required. The operation is simple. Disadvantages The entire supply is disturbed when the fault occurs. As the arrangement provides the least flexibility, it is used in small substations where continuity of supply is not crucial. Single bus - single breaker
  • 22. ZONE 1 ZONE 2 • Distribution and lower transmission voltage levels • Limited operating flexibility Multiple bus sections - single breaker with bus tie
  • 23. ZONE 1 ZONE 2 • Transmission and distribution voltage levels • Breaker maintenance without circuit removal • Fault on a bus disconnects only the circuits being connected to that bus Double bus - single breaker with bus tie
  • 24. ZONE 1 MAIN BUS TRANFER BUS • Increased operating flexibility • A bus fault requires tripping all breakers • Transfer bus for breaker maintenance Main and transfer buses
  • 25. ZONE 1 ZONE 2 • Very high operating flexibility • Transfer bus for breaker maintenance Double bus – single breaker w/ transfer bus
  • 26. ZONE 1 ZONE 2 • High operating flexibility • Line protection covers bus section between two CTs • Fault on a bus does not disturb the power to circuits Double bus - double breaker
  • 27. ZONE 1 ZONE 2 • Used on higher voltage levels • More operating flexibility • Requires more breakers • Middle bus sections covered by line or other equipment protection Breaker-and-a-half bus
  • 28. • Higher voltage levels • High operating flexibility with minimum breakers • Separate bus protection not required at line positions B1 B2 TB1 L1 L2 L3 L4 TB1 Ring bus
  • 29. Bus components breakers SF6, EHV & HV - Synchropuff Low Voltage circuit breakers BUS 2 CB 1 BUS 1 ISO 1 ISO 2 ISO 3 BYPASS
  • 30. - + F1a F1c Contact Input F1a On Contact Input F1c On F1b ISOLATOR 1 ISOLATOR 1 OPEN 7B 7A BUS 1 - + F1a F1c Contact Input F1a On Contact Input F1c On F1b ISOLATOR 1 ISOLATOR 1 CLOSED 7B 7A BUS 1 Disconnect switches & auxiliary contacts BUS 2 CB 1 BUS 1 ISO 1 ISO 2 ISO 3 BYPASS
  • 31. BUS 2 CB 1 BUS 1 ISO 1 ISO 2 ISO 3 BYPASS Current Transformers Oil insulated current transformer (35kV up to 800kV) Gas (SF6) insulated current transformer Bushing type (medium voltage switchgear)