ABSTRACT: With the advancement of science in all fields, particularly the discovery of electricity and gas, that created urban installations, plumbing and power plants with urban life of the people, along with all the advantages and comfort to the human race, had also associated risks. Among these are fire hazards. That this incident alone caused losses of life and property also and it can be imagined that in accompany of earthquakes and fires what kinds of the tragedy occurs. In this article, it can be attempted that first, to introduce Plasco Building and its history to speak briefly to explain the reasons for the collapse of this old and massive structures.
2. Shot firing the Plasco Building and Reasons for the collapse
*Corresponding Author: Mohsen Gerami2*
22 | Page
Based on the third paragraph of Section 18-1-3 National Building Regulations any building which its
height (vertical distance between the floor levels of the highest disposable floor to the lowest level of access for
fire engines) is more than 23 meters is High-rise building.
Based on this Regulations, buildings Higher than the 7-story are considered high-rise buildings.
II. METHODS AND MATERIALS
To collect the data, library studies was used and documents was identified the various aspects of the subject.
Instruments for data collection in the library method was books, articles, dissertations, Internet and in the field
study was the documents.
III. DISCUSSION AND DATA COLLECTION:
3.1 Plasco Building history
This building is the second high-rise building and with elevator in Iran and it is the first high-rise building with a
steel structure. This 17-story building was built in the years 1960 to 1962 by Israeli engineers and its structure
architect was a German engineer. This structure ousted Iranian market from the traditional mode [2]. This building
has a basement and a ground floor and 15 floors on it. The total area of the building is 29,000 square meters and
the first and fourth floors of the building has more surface area than other classes. Total height of the structure is
over 42 meters. This building was intended for distribution and garment manufacturing and have been business
users with 560 commercial units. This structure was designed in accordance with Regulation 519 and due to old
design Regulations did not consider the impact of fire on the structure.
The roof of this structure was formed concrete slab with simple reinforcement. The function of this
building change over time and from place of business had become to the workshop production of clothing so that
70% units change to production units. So, heavy equipment placed on the higher floors of building. So, it causes
abnormal heavy of floors. Only 160 units from 560 units of this building were insured. Columns was formed 4
metal cans filled with concrete, so these structures were not protected against fire. All of the Armatures was
simple.
3.2 Description of Plasco building fire:
The main cause of this incident was reported Electrical connection in 19 January 2017. It started from
one of the production units and caused the fire started from 9th floor to the top. Classes 8 and 9 of the building
caught fire in the morning and 4 hours after the fire, the whole of building collapsed at 11:20 minutes. In total its
damage is estimated 1700 billion.
Destruction of structures has been started since a vibration in structures and within 15 seconds of progressive
collapse, the whole structure was destructed.
It should be noted that the strength of steel at a temperature of 600 ° C is half of its initial strength. If
temperature reaches to 1000 ° Strength of steel will tend to zero. In this event, fire temperature under the rubble
has been reported 1000 to 1500 ° C because of the presence of flammable materials inside the structure.
3.3 Study on collapse factors of Plasco
3.3.1 The general trend "progressive collapse"
There is a phenomenon called "Progressive Collapse" or "progressive destruction". In this phenomenon,
main elements of the building destroyed [3].Progressive destruction starts by removing Structural load capacity
of a small portion of the structure and more damage occurs in other structural elements. Now everything is ready
to broker a column out of the cycle. As soon as one column was loosed, other columns must be bearing that
column load. Now the next column loses on the outskirts of the columns and so the progressive collapse process
continues until the whole structure collapses.
Yet all of the above we add that steel crisis caused by heat at temperatures of up to 80 percent of normal
fire loses his resistance and therefore its duration is much reduced. If the structure was concrete, after the fire
began, firefighters had the opportunity to fire off a lot more and not poured down rate structures with this speed.
Progressive destruction may be spread in part or extend range of structures. This phenomenon is due to factors
such as explosions, fires and etc. in structures. In other words, after the fire and reducing the bearing capacity of
steel elements, structures have to be progressive destruction and part or all structures will be destroyed. In this
process at first the fire and heat (650 ° C) weaken the steel structure and steel strength were reduced where the
trusses bend progressively.
As a result, in addition to the load tolerance horizontally and downwards, also an aggravated extra load
enters into the building. This load causes the outer pillars and the inner pillars bend and eventually led to the
destruction of structures.
For this reason, according to international standards for fire extinguish on buildings with steel structure,
if fire not controlled after 30 minutes, firefighters must leave the building and extinguish fire from out of building.
3. Shot firing the Plasco Building and Reasons for the collapse
*Corresponding Author: Mohsen Gerami2*
23 | Page
While firefighters were busy fighting Plasco about 3 hours and 30 minutes. Of course, 30 minutes is for buildings
that its structure is fire-proof insulation.
Also pressure from Collapsing upper floors will cause Collapsing lower classes and according to interior design
Plasco in the form of U, Collapsing buildings were completely internal and surrounding buildings were not
seriously hurt.
3.3.2. Scientific phenomenon in the fire called Backdraft
When the fire is deficient in oxygen and choking incomplete and then for whatever reason it was accessed
to oxygen and air, flashover was happened (i.e. the height of the fire) and smoke and hot gases violently hurled.
This is same of explosion phenomenon and of course the far less sound. Pressure caused by this phenomenon
enters additional stress on the structure under stress, and thus destroy the structures.
3.3.3 Water and fire, thermal shock
This fire is placed in the groups that the fire skyscrapers or high rise fire is said. These fires usually affect
the structure of high-rise buildings and off and overcoming it requires much training and use of appropriate
equipment [4]. Contrary to rumors that were launched after the September 11 attacks, the Twin Towers were not
the only structures that collapsed due to fire. There is a long list of high-rise buildings have taken down due to a
fire. Inhibition of fires such buildings, important points must be met. According to a spokesman for the fire
department and safety services of Tehran Municipality Seyyed Jalal Maleki A total of 200 firefighters with 15
water tankers and three lifts aided fire Suppression Operations in Plasco's building (Fig 2).
Fig. 2- Plasco incident pictures [4]
Use of water for Extensive firefighting in buildings with steel structure is a strategic mistake. Water in
addition to adding the building weight, also, causing thermal shock too. In particular, this shock is high in the
clothing distribution center. Because of textiles, fire quickly spread and the temperature rises quickly. This will
affect the steel structure of building and if the temperature will not collapse the building alone, pouring cold water
on the molten metal to cause shock and thermal stress on them. In this way, may be some key components of
structures bend, twist or cut under shock and weight gain caused by water. In this way a chain reaction that
"progressive collapse" is known to occur. What makes the key components of the structure is disrupted and the
shock of the collapse of the upper classes will disrupt components of the lower classes. So, the event is determined
that the classic example is the Twin Towers and here in Tehran Plasco building. In the design, structures must be
designed with not progressive destruction. Better designing of steel structure connections is one of the strategies
to prevent progressive destruction.
3.3.4 The lack of fire proof cover
Old structures of Plasco building was lack of fire proof cover. Materials researchers showed that the
metal parts of these structures in the heat and splashing water was collapsed. It does not require steel used in metal
structures melt because in high heat metal behavior changes against the force. This seems a combination of
temperature, thermal shock, lack of safety (causing a second explosion), the increase in weight because of water;
fatigue steel structure and the absence of anti-heating cover caused to collapse buildings due to fire (Fig 3).
4. Shot firing the Plasco Building and Reasons for the collapse
*Corresponding Author: Mohsen Gerami2*
24 | Page
Fig 3. Plasco Building demolition [4]
IV. CONCLUSIONS AND THE WAY THINGS:
The useful life of this building was estimated 200 years but it was collapsed 54-year-old due to fire. It collapsed
after 4 hours the fire at 11:20 minutes in total damage is estimated 1700 billion.
With all things said, it can be concluded that:
If in an incident did not disrupt the path of car fire and the streets were open
If people listen to municipal warnings and organizations in charge
If authorities reconstruct this kind of buildings before the event
If owners did not change users from commercial to production and workshop
If firefighters had needed equipment to turn off this kind of events, they were replaced the water with
extinguisher
If at the time of the accident crisis management was done and the evacuation was took placed instead of
firefighters were gone inside the unsafe building
If all the shops were insured
If the owners of the stalls were followed safety issues
Maybe none of these events would have happened and firefighters returned safely to their homes
However, these bitter events were for a while, the subject of hot virtual world and then less than a month was
forgotten and we forget that dozens of buildings with the same attributes throughout Tehran is waiting for a spark
to create a new scenario.
REFERENCES
[1]. ABAQUS / standard analysis user's manual v. 6.10. SIMULIA; 2010 1
[2]. Khairuddin, A. and Fallahzadeh, S. (2015).The behavior of steel moment frames in the phenomenon of progressive
collapse, the first national conference on development-oriented of civil, architecture, electrical and mechanical
engineering, Iran. (In Persian).
[3]. Khairuddin, A. (2016). The reasons for Plasco collapse; internal conference of Semnan University, Iran, (in Persian).
[4]. Ranjbar, A. (2016). Science journalist; 11 My 2015. Accessible at: http://bigbangpage.com/science-content/