2. Introduction to
protection system of
Thermal stations
By
N.RENGARAJAN
Chief Manager/Elect.
Thermal Power Station-I Expansion
Neyveli Lignite Corporation Ltd, Neyveli
3. PROTECTION SYSTEM
Sensitive to abnormal condition
Protects equipment against major damage
Protects the personnel
Isolates the faulty equipment
Prevents cascade tripping
Improves system reliability
5. Instrument Transformers
To transform currents or voltages to a value easy to
handle for relays and instruments.
To insulate the metering & protection circuits from the
primary high voltage system.
To facilitate standardization of the instruments and
relays to a few rated currents and voltages.
14. Applications
Over current with IDMT characteristics
Instantaneous Short Circuit
Short Circuit / Earth fault with DTL
Under Voltage / Over Voltage
Differential current relays
Distance protection relays
21. Advantages
Low burden on CT and PT
No mechanical inertia
Fast operation and long life.
Low maintenance
Quick reset action.
Greater sensitivity.
Unconventional characteristics are possible.
The low power consumption.
28. GENERATOR DATA SHEET
ANSALDO ENERGIA, ITALY
283.5 MVA, PF 0.85, 15.75 KV,10392 A, 3 PHASE AC, 50 HZ
STATIC EXCITATION 2725 A, 346 V DC
STAR, IP 55,CLASS –F, DUTY S1
3000 RPM, OVER SPEED 3600 RPM- 2 MIN.
HYDROGEN COOLED
28
29. System Conditions
Short circuits
Overloads
Loss of load
Unbalanced load
Loss of synchronism
30. Mixture of mechanical and electrical problems.
Faults include :-
Insulation Failure
Stator
Rotor
Excitation system failure
Prime mover / governor failure
Bearing Failure
Excessive vibration
Low steam pressure
31. Generator Protections
Earth faults on stator and generator connections
Phase faults on stator and generator connections
Inter-turn faults on stator
Backup protection :- External Earth faults
External Phase faults
Failure of prime mover
Loss of field
Unbalanced loading
Rotor earth faults and inter-turn faults
Overload
Failure of speed governing system
Sudden loss of load
32. 32
GENERATOR PROTECTIONS
OVERLOAD
SHORT CIRCUIT
EARTH FAULT
INTER TURN FAULT
DIFFERENTIAL
LOSS OF EXCITATION
NEGATIVE SEQUENCE
BACK UP IMPEDENCE
OVER/UNDER VOLTAGE
OVER/UNDER
FREQUENCY
OVER-FLUXING
LOW FORWARD/
REVERSE POWER
OUT OF STEP
33. Most probable result of stator winding insulation failure is a phase-
earth fault
Desirable to earth neutral point of generator to prevent dangerous
transient over voltages during arcing earth faults
Easy to troubleshoot and measure the fault level
Damage resulting from a stator earth fault will depend upon the
earthing arrangement
Effects of Earthing
34. Solid Earthing :
Method of Earthing
Fault current is high
Rapid damage occurs
burning of core iron
welding of laminations
Used on LV machines only
Resistance/Reactance Earthing : Fault current is low
Damage is limited
Used on MV/HV machines
Neutral Grounding Transformer : Fool proof Stator E/F protection
95% and 100% S.E/F
Used on large machines
35. Small, inter-laminar short grew into a major melt zone that triggered two other
melt areas caused by intense over-fluxing of the magnetic circuit in the stator core
37. 37
GENERATOR PROTECTION
CLASSIFICATIONS
CLASS – A
FAULTS OF SERIOUS NATURE REQUIRING TOTAL SHUT
DOWN
CLASS- B
FAULTS OF LESS SERIOUS NATURE NOT REQUIRING
TURBINE TRIP
CLASS- C
FAULTS OF LEAST SERIOUS NATURE TO PERMIT HOUSE
LOAD OPERATION
38. 38
CLASS-A PROTECTIONS
REVERSE POWER
OVER VOLTAGE
STATOR E/F 100% & 95%
GENERTOR DIFF.
OVER ALL DIFF.
OVER-FLUXING
EXCITATION SYSTEM LOCK OUT
OVER FREQUENCY-II
RE/F OF GT & UAT
DIFFERENTIAL OF GT & UAT
O/L TRIP OF UAT
ROTOR E/F-2
PRV/BUCH.
LBB/BBP
EMERGENCY TRIP
39. 39
CLASS-B PROTECTIONS
LOSS OF EXCITATION
U/F - STAGE 2
NPS - STAGE 2
GEN. & GT O/C
OUT OF STEP-STAGE-2
STAND BY E/F-GT
TEMP. TRIP OF GT
UNDER IMP-2
O/C TEMP. TRIP OF
EXCITATION TR.
40. 40
CLASS-C PROTECTIONS
UNDER IMP. STAGE-1
NPS STAGE-1
OUT OF STEP STAGE-1
GENERATOR O/L
UNDER FREQUENCY STAGE-1
GENERATOR U/V
If the errors are calculated at two different currents and with the same burden it will appear that the errors are different for the two currents. The reason for this is the non-linear characteristic of the exciting curve. If a linear characteristic had been supposed, the errors would have remained constant. This is illustrated in Figure 1.7 and Figure 1.8. The dashed lines apply to the linear case.