150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
eSTS Automatically Transfers Between Two or Three* Power Sources
LayerZero Power Systems designs and manufactures the world’s most reliable static transfer switch. The Series 70 eSTS is
a solid-state transfer switch that automatically or manually provides solid state transfers between two in-phase AC sources
in a quarter cycle. The eSTS performs open-transition transfer in such a manner that the connected load disruption is
minimized without ever cross-connecting the power sources. One power source is selected to be the preferred source.
If the preferred source fails the load is automatically and seamlessly connected to the alternate source by means
of an open-transition static transfer. For emergency transfers between asynchronous sources, dynamically phase
compensated transfers minimize saturation of downstream transformers in 3-phase, 3-wire eSTS.
The LayerZero eSTS Static Transfer Switch
Maximizes Power Reliability
*Optional
One Line Diagram
2 Š Copyright 2016 LayerZero Power Systems, Inc.
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
;; Optional Triple Modular Redundancy: TMR Contains Fully-Independent Control Paths With No Single Point-Of-Failure
;; Safe Bypass Procedure: Mechanical Bypass Interlock Eliminates Human Error When Performing Bypass Procedures
;; Voice Guided Bypass: Step-By-Step Instructions With Audio and Video Guidance To Assist Operators Through Bypass
;; Convection Cooling: Natural Convection-Cooled Heat Dissipation System is Maintenance-Free
;; Epoxy Coated Buswork: Maximizes Reliability By Eliminating The Possibility of Bus-To-Bus Faults
;; Silver Plated Terminals: Silver Has Excellent Conductivity To Provide Superior Electrical Performance and Reliability
;; Maintenance-Free Joints: Brazed Joints Are Permanent And Maintenance-Free, Maximizing Product Life
;; Machined Hardware: Machined Cap Screws and Engineered Disc Springs Maintain Constant Torque Throughout Product Life
;; Screw Thread Inserts: Prevents Screws From Loosening Under Vibration For Long-Term Reliability
;; Optical Fiber Based Controls: Eliminates Noise and Interference While Isolating Components from High Voltage
;; Serialized Critical Board Tracking: Critical Boards Are Serialized And Cataloged in an Active Database For Traceability
Reliability
Standard Features
LayerZero’s eSTS Is Equipped Fully-Loaded
Safety
;; InSight™ IR Portholes: Bolted Connections & Critical Boards Can Be IR Scanned With the Dead-Front Doors Closed
;; Sectionalized Components: Isolated Sections That Can Be Safely De-Energized For Performing Maintenance
;; Polycarbonate Windows: Allows Critical Board LEDs To Be Viewed With The Dead-Front Door Closed
;; Front-Only Access: Installation and Maintenance Can Be Safely Performed Without Side or Rear Access
;; Dead Front Hinged Doors: Barrier To Provide A Safe Working Area With No Exposed Live Parts
Connectivity
;; Ethernet Connectivity: Secure VPN Router Connects To Network For Advanced Remote Monitoring Capabilities
;; Modbus/TCP: Open Connectivity to Existing Monitoring Systems Without Proprietary Limitations
;; NTP Time Clock Synchronization: Facilitates Timeline-Based Logging For Post-Event Reconstruction
;; SNMP Connectivity: Permits Remote Management Via Simple Network Management Protocol
;; Real-Time Waveform Capture: Automatically Captures A Picture Of The Power Three-Cycles Before and After Every Event
;; Local Touch-Screen Interface: Password-Protected Color Touch-Screen GUI For Local STS Setup/Operation/Administration
;; Black-Box Forensics: Captures and Records All Events To Provide Vital Information In Root-Cause Analysis
;; Waveforms Automatically Emailed: Capability to Send Waveform Captures To Designated Individuals For Every Transfer
3 Š Copyright 2016 LayerZero Power Systems, Inc.
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
1200 A eSTS Section Overview
Controls Section
Power Electronics Section
Input/Output Bypass Isolation Section
Source & Load Terminal Section
Controls Section
Circuit Breaker Section
150 A - 800 A eSTS Section Overview
4 Š Copyright 2016 LayerZero Power Systems, Inc.
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
CB Section Contains:
Input isolation switches
Bypass isolation Switches
Output isolation switches
Source connection terminals
Load connection terminals
Controls Section Contains:
Power electronics
• SCRs (Silicon Control Rectifier) in
Convection Cooled Heat Sinks
Control Electronics
• System Control & Data Acquisition 	
Boards
• SCR Gate Drives
• Redundant Power Supply System
• I/O system; VPN Router
Equipment Layout (400 A Shown)
CB101 Source 1 Isolate
Source 1 Phase A SCRs
CB102 Source 2 Isolate
CB201 Bypass Isolate,
Source 1
CB202 Bypass Isolate,
Source 2
CB301 Output Isolate 1
CB302 Output Isolate 2,
(Redundant, Optional)
Source 2 Phase A SCRs
Source 2 Phase B SCRs
Source 1 Phase B SCRs
Source 1 Phase C SCRs
Source 2 Phase C SCRs
5 Š Copyright 2016 LayerZero Power Systems, Inc.
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
1. Alarmed Doors
2. Hinged Dead Front Doors
3. 15” Color Touch Screen GUI
4. Printed Bypass Instructions
5. InSight™ IR Portholes
6. Convection Cooled Heat Sinks
7. Staggered Gate Drive Arrangement
8. Epoxy Coated Buswork
9. Circuit Breakers
10. Redundant Power Supplies
11. Convection Cooled Intake
1
2
3
4
5
67
8
9
10
11
Equipment Construction Detail (800 A Shown)
1. Alarmed Doors
2. Hinged Dead Front Doors
3. Silver Plated Terminals
4. 15” Color Touch Screen GUI
5. Printed Bypass Instructions
6. Polycarbonate Window
7. InSight™ IR Portholes
8. Convection Cooled Heat Sinks
9. Staggered Gate Drive Arrangement
10. Epoxy Coated Buswork
11. Circuit Breakers
12. Redundant Power Supplies
13. Convection Cooled Intake
1
2
3
4
5
6
7 8
9
10
11
12 13
1200 A Shown
6 Š Copyright 2016 LayerZero Power Systems, Inc.
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
LayerZero eSTS Reliability Overview
The LayerZero eSTS Provides Many Dimensions of Reliability:
•	 Control System Reliability
•	 SMR (Single Module Redundancy, Standard)
•	 TMR (Triple Modular Redundancy, Optional)
•	 Control Power Supply Reliability
•	 Signal Reliability
•	 Operator Procedural Reliability
Gate Drive 1
Source 1 A
Gate Drive 2
Source 1 B
Gate Drive 3
Source 1 C
Gate Drive 4
Source 2 A
Gate Drive 5
Source 2 B
Gate Drive 6
Source 2 C
Source 1
Control
Source 2
Control
WAN Port
Fiber Optics
SCB 1
Single Module Redundancy (SMR) Reliability (Standard)
Single Module Redundancy is a cost-effective topology that provides
redundant power paths to mission-critical equipment. In SMR
systems, sources each have built-in triple redundancy of processors.
In addition, every phase is controlled with a separate gate drive
board.
LayerZero Single Modular Redundant topology is unique that it the
system is fail-safe, maintaining full switching functionality even if a
critical board were to fail.
Reliability Overview
7 Š Copyright 2016 LayerZero Power Systems, Inc.
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
Reliability Features: Triple Modular Redundancy (TMR) *Optional
Triple Modular Redundancy (TMR) Reliability (Optional)
LayerZero TMR has all the redundancy of SMR, plus each STS has three
independent sets of analog and digital data acquisition and control systems. There
is no direct communication between the three systems. The three systems do not
even share a common system clock.
•	 Each control system acquires voltage and current data independently
•	 Each control system determines whether a source is good/bad independently
•	 Upon loss of a source, each control system makes decisions to transfer
independently
Even if an entire control path or its subcomponent were to fail; and then if
the active power source were to fail, the STS is able to complete its mission of
transferring to the alternate source.
Triple Modular Redundancy, a proper noun, is a based on proven statistics and
stringent mathematics. There are similar sounding terms like, tri- or triple-
redundant, used in industry to describe other STS products – but they simply do
not yield the same, high level of reliability.
Gate Drive 1
Source 1 A
Gate Drive 2
Source 1 B
Gate Drive 3
Source 1 C
Gate Drive 4
Source 2 A
Gate Drive 5
Source 2 B
Gate Drive 6
Source 2 C
Source 1
Control
Source 2
Control
Source 1
Control
Source 2
Control
Source 1
Control
Source 2
Control
WAN Port
Fiber Optics
SCB 1
SCB 2
(TMR)
SCB 3
(TMR)
8 Š Copyright 2016 LayerZero Power Systems, Inc.
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
eSTS SMR Triple Redundant Power Supply Architecture
Divided into four (4) logical failure groups:
•	 System controls
•	 Source 1 gate drives
•	 Source 2 gate drives
•	 Peripherals.
The three (3) available source of power from which to supply control
power to each failure group are:
•	 Source 1
•	 Source 2
•	 STS Output.
LayerZero’s STS design incorporates twelve (12) power supplies (3
power sources x 4 failure groups.) The resultant control power topology
utilizes all possible power paths to the four logical STS failure groups;
and is the most comprehensive and redundant power supply system in
existence.
Reliability Features: Single Module Redundant (SMR) Redundancy
Peripherals
PS 1
S1 A-B
Source 1
A B C
Source 2
A B C
PS 4
S1 B-C
PS 7
S1 A-C
PS 10
S1 A-B
PS 3
S2 B-C
PS 6
S2 A-C
PS 9
S2 A-B
PS 12
S2 B-C
System Controls
Gate Drives,
Source 1
Gate Drives,
Source 2
GD 1 GD 3 GD 5
SCB 1 SCB 2
TMR Only
SCB 3
TMR Only
GD 2 GD 4 GD 6
PS 5
Out A-B
System Controls
PS 8
Out B-C
Gate Drives S1
PS 11
Out A-C
Gate Drives S2
PS 2
Out A-C
Peripherals
Output
Bus
A
B
C
eSTS SMR Triple Redundant Processors
•	 Separate/independent processors for Source 1, Source 2 and
Output power quality analysis
•	 If Source 1 processor malfunctions then system is able to be
commanded to transfer to Source 2; & vice versa.
•	 If main control system fails then STS continues to conduct power to
the load from the existing source of power. (However STS is unable
to transfer to the other source)
•	 Each phase of each source is controlled with a separate gate drive
circuit board.
9 Š Copyright 2016 LayerZero Power Systems, Inc.
S1 S2 Output
Gate
Drive 1
Gate
Drive 2
Gate
Drive 3
Gate
Drive 4
Gate
Drive 5
Gate
Drive 6
A B C A B C
Source 1 Transfer Control Source 2 Transfer Control
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
Mechanical Bypass Interlock
In order to minimize the possibility of operator error during equipment
bypass operations, LayerZero provides:
1.	 Interlocked breakers
2.	 Mechanisms to ensure that a source cannot be bypassed without
the STS on the correct source.
3.	 Safeguards to make certain that sources cannot be connected to
each other inadvertently.
4.	 A voice-prompted bypass procedure that guides the operator
through the sequence.
5.	 A step-wise pictorial & video presentation is provided on the
touch-screen display during bypass.
Voice Guided Bypass
Operator error during maintenance bypass has been known to be
a reliability hazard. To help prevent operators from completing the
bypass procedure out-of-sequence, our product features a voice
prompted bypass procedure. This instructs the operator in a step-
by-step course of action of the process, with only one operation
per screen. Visual and audio cues provide clear instructions on the
bypassing sequence, reducing the probability of operator error.
Reliability Features
10 Š Copyright 2016 LayerZero Power Systems, Inc.
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
No Fans, Dust Filters, or Fan Fuses
The Series 70: eSTS Static Transfer Switch utilizes a natural convection-
cooled heat dissipation system.
Fans and fan sensors are some of the most common components to
fail. For maximum uptime, LayerZero’s eSTS systems do not contain
any fans, dust filters to change, or fan fuses to replace.
The heat sink arrangement is staggered between sources and phases
to minimize the creation of extreme thermal gradients between heat
sink columns when conducting on one source or the other.
Epoxy Coated Buswork/Maintenance Free Joints
Our usage of epoxy coated buswork helps ensure safety, and makes
the system inherently more reliable by eliminating the possibility
of bus-to-bus faults. Bus joints are permanently brazed and
maintenance-free.
Silver Plating
LayerZero utilizes silver plating on all bus joints and terminals to be
able to provide the highest performance. Silver has high conductivity
and low resistance - which makes for a great contact.
Reliability Features
11 Š Copyright 2016 LayerZero Power Systems, Inc.
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
Fiber Optic Controls Increase System Reliability
Fiber optic based controls eliminate noise and interference, while
isolating components from high voltage.
Optical fiber allows service to be reliably connected, while protecting
the equipment.
In LayerZero’s eSTS design, the gate drives (at Power Circuit Voltage)
receive control signals via optical fibers.
Serialized Critical Board Tracking
We serialize and track all critical boards and maintain this information
in an active, dynamic database.
12 Š Copyright 2016 LayerZero Power Systems, Inc.
Reliability Features
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
InSight™ IR Portholes Permit Scanning of Bolted
Connections with Dead-Front Doors Closed
Strategically positioned IR-scan portholes to enable safe thermal
scanning of all bolted connections with the deadfront closed, without
exposing the operator to power circuit voltage. Thermal scans can be
done from the front – without ever having to open the dead-front door.
The IR window swivels upward and unlocks with key-hole access to
reveal a mesh, allowing the operator to point-and-shoot thermal
cameras to obtain readings.
CB101 CB102
CB201 CB202
CB302
Source 1 Source 2
CB301
Load
1
2
1
2 2
IR Portholes in eSTS
(Door and side panel hidden for visibility)
Ease of Maintenance
13 Š Copyright 2016 LayerZero Power Systems, Inc.
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
Modbus/TCP http:// through a
standard web browser
Network Time Protocol
(NTP) Compliant
For Clock Synchronization
Simple Network
Management Protocol
(SNMP)
Waveforms
Automatically Emailed
Series 70: eSTS
Standard
Ethernet
Dry Contacts
• Meters
• Alarms
• Meters
• Alarms
• Waveforms
• History/Event Log
• Diagnostics
• Summary Alarm
• On Source 1
• On Source 2
• Source 1 Available
• Source 2 Available
eSTS Connectivity Options
• Non-Proprietary Protocols
Ease of Maintenance/Connectivity Options
Front Only Access Saves Space
The Series 70: A eSTS is designed to be installed, operated, diagnosed
and maintained only from the front. The dead-front panels are hinged,
and side or rear covers never have to be removed.
Unhinged covers can be bulky and unwieldy, and operator error during
removal and replacement of covers has been known to cause mishaps
and compromise load reliability. A safe, non-invasive operation and
maintenance regime results in a higher reliability of the critical load.
The Series 70: eSTS utilizes dead-front hinged doors. An alarm notifies
when an outer door has been opened.
14 Š Copyright 2016 LayerZero Power Systems, Inc.
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
A
V
PQ
Current Metering Point
Voltage Metering Point
Power Quality Metering Point
BM Branch Current Monitoring
Features/Power Quality Monitoring
15” Color Touch Screen (Standard)
1. Stereo Speakers for Guided Bypass Prompts
2. Output On Light (Remains Lit in Bypass Isolate Mode)
3. Alarm & Bypass Indicator
4. SCB Status Indicator
5. Logged In User
6. Navigation Menu
7. Customer & Project Information
8. Date & Time
1 2
3
4 5
6
207 8
Zen is being aware of all all activity in your critical power distribution
systems, it is an all encompassing monitoring system with local and
remote communications options. From basic monitoring, alarms, to
advanced power quality monitoring functionality, Zen SSQM provides
a wide-range of options to help you maintain the highest level of
reliability.
Zen gives you a vendor-neutral “Birds Eye” view of your entire
critical power distribution infrastructure. Zen maximizes reliability,
letting you know if a source has quality issues, if a UPS output is
bad, or if there are any alarms. In addition, Zen empowers users
with the capability to go back in time to retrace the exact sequence
of historical events. No other tool in the mission-critical industry
empowers users with this robust capability.
15 Š Copyright 2016 LayerZero Power Systems, Inc.
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
The Series 70: eSTS is equipped with Zen SSQM (Static Switch
Quality Monitoring), an all encompassing monitoring system with
local and remote communications options.
From basic monitoring & alarm reporting, to advanced power
quality monitoring functionality, Zen SSQM provides a wide-range
of options to help you be aware, be vigilant, be proactive in your
quest to create a safe, stable and reliable operation.
Zen SSQM Provides Answers
Zen SSQM provides timestamped pictures of waveforms before and after events, providing information that enables facilities to go
back in time to methodically identify and correct the root causes of events. Zen actively captures power quality information at the
STS, PDU, and RPP - permitting thorough post-event analysis.
Product Name: Series 70 ePODs: Type-P
Unit Name: 500 + 1000 turn CTs
Serial #: 10028-34
Capture Reason: SQ Xfer 0-1
Captured By: scb122
Capture Time: 01-04-2016 6:53:08 PM
Microticks: 1449941
Phase A
Phase B
Phase C
Phase N
Phase G
Source 1 Volts L-L
Milliseconds
V
o
l
t
s
0
-200
200
-400
400
-600
600
-800
800
-1000
1000
Source 2 Volts L-L
Milliseconds
V
o
l
t
s
0
-200
200
-400
400
-600
600
-800
800
-1000
1000
Load Volts L-L
V
o
200
400
600
800
1000
Trigger Event
3 Electrical Cycles 3 Electrical Cycles
Waveform Capture of Current in a Source TransferPhase A
Phase B
Phase C
Power Quality Monitoring
16 Š Copyright 2016 LayerZero Power Systems, Inc.
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
Zen SSQM Parameters Mains
Voltage Inputs and Output
Voltage (Volts) Ăź
Voltage Average of Phases (Volts) Ăź
Frequency (Hertz) Ăź
Total Harmonic Distortion (Percent VTHD) Ăź
Phase Rotation Ăź
Current Inputs
Current (Amps) Ăź
Current Average of Phases (Amps) Ăź
Current Imbalance (Percent) Ăź
Real Power (kilowatts) Ăź
Apparent Power (kilovolt-amperes) Ăź
Reactive Power (kilovolt-amperes reactive) Ăź
Power Factor Ăź
Crest Factor Ăź
Crest Factor Average of Phases Ăź
Phase Difference Between Sources Ăź
Phase Difference Between Sources and Output Ăź
Alarms
Summary Alarm Ăź
On Source (1/2/3) Ăź
Source Fail (1/2/3) Ăź
Source Preferred (1/2/3) Ăź
Source 1st Alternate (1/2/3) Ăź
Source Over/Under Voltage (1/2/3) Ăź
Source Over/Under Frequency (1/2/3) Ăź
Source Not Available (1/2/3) Ăź
Output Failure Ăź
Source Overcurrent (1/2/3) Ăź
Source Exceeds Manual Limit (1/2/3) Ăź
Source Exceeds Automatic Limit (1/2/3) Ăź
Bypassed to Source (1/2/3) Ăź
Zen SSQM Technical Specifications
17 Š Copyright 2016 LayerZero Power Systems, Inc.
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
eSTS Models with Withstand Ratings
eSTS Rating (100%)
120/208 V
480 V; 480/277 V; 415/240 V;
400/230 V; 220/380 V
600 V; 600/347 V; 575 V
150 A
150kA; 100kA; 65kA 150kA; 100kA; 65kA; 35kA 100kA; 65kA; 35kA; 25kA
250 A
400 A
600 A
800 A
100kA; 65kA
100kA; 65kA; 50kA; 35kA 42kA; 35kA; 25kA
1200 A 100kA*; 65kA; 50kA 65kA*; 50kA; 25kA
* Upgrade to Automatic Circuit Breakers
Mechanical Characteristics *
150 A - 250 A 400 A 600 A 800 A 1200 A
Heat Dissipation 4,750 BTU/Hr 7,000 BTU/Hr 9,500 BTU/Hr 12,500 BTU/Hr 24,000 BTU/Hr
Weight 1,350 lbs
(612 kg)
1,400 lbs
(635 kg)
1,500 lbs
(680 kg)
1,950 lbs
(885 kg)
5,500 lbs
(2495 kg)
Dimensions 48”W x 36”D x 80”H
(1219 mm x 914 mm x 2032 mm)
58”W x 36”D x 80”H
(1473 mm x 914 mm x 2032 mm)
96”W x 48”D x 90”H
(2438 mm x 1219 mm x 2286 mm)
Frame Construction Welded Frame
Electrical Connections Silver-Plated Solid Busbar
Color Textured Powder Coat White (RAL 7035), Blue (RAL 5017), Black, Custom
Floor Stands Optional
Seismic floor stands Optional
Junction Boxes Optional
Sectionalization Engineered Composite Insulation, Dead Front Doors
Electrical Characteristics
Number of Inputs 2, 3 (3 optional)
Number of Output CBs 1, 2
Frequency 50 Hz, 60 Hz
Poles 3-pole
Phases 3 Phase, 3 Wire, 4 Wire + Ground
Neutral Rating 100%, 150%, 200%
Transfer Time Nominal 1/4- cycle for in-phase sources
Redundancy Single Module Redundancy, Triple Modular Redundancy (Optional)
Circuit Breaker Type Molded Case Switch (Standard), Electronic Trip (Optional)
Circuit Breaker Mounting Type Plug-In up through 600 A; Draw-out 800 A, 1200 A
TVSS Standard
Power Quality Monitoring
Power Quality Monitoring Technology Zen SSQM™ (Static Switch Quality Monitoring)
Waveform Capture Local Display, Remote Display via Web Browser, Waveforms Automatically Emailed
Voltmeter Input sources and Output, for each phase
Ammeter Input sources and Output, for each phase
Frequency Meter Both Sources
Synchroscope Phase Angle Meter Between Sources
Metering Apparent Power, Real Power, Power Factor, Output Total Harmonic Distortion
Time Stamped Transfer Count From First Day Use, From Last Reset
CB Status Indicator Open/Closed/Tripped Circuit Breaker
Source Indicator Preferred Source
Power Path Indicator On Live Mimic
*Dimensional & weight data is only valid for 2-source.
Technical Specifications: 3-Pole Static Transfer Switch
All product specifications are subject to change without notice.
18 Š Copyright 2016 LayerZero Power Systems, Inc.
150 A - 1200 A Static Transfer SwitchSeries 70: eSTS
Operational Characteristics
Transfer Modes Automatic; Manual (via Preferred Source Selection)
Inrush Mitigation Technology Patented Dynamic Phase Compensation Algorithm (U.S. Patent 7,589,438 B2)
Cooling Convection Cooling
Cable Access Top/Bottom
Service Access Front Only
Bypass Interlock Mechanism Mechanical
Noise & Interference Isolation Optical Fiber in Critical Control Paths
IR Scan Port Type InSight™ IR Portholes
SCR Type Puck
Display Type 15” Color Touch Screen
Display Resolution 1024x768
Bypass Assistance Voice-Guided Bypass
Audio Bezel-Mounted Stereo Speakers
Languages English, French
Mimic Panel Digital
Setpoints Control Digital
Power Supplies Redundant (4 Failure Groups. Triple Redundant Supplies. 12 Power Supplies Provided.)
Connectivity
Meters Local Display, Ethernet, Modbus/TCP, http via Web Browser (Non-Proprietary)
Alarms Local Display, Ethernet, Modbus/TCP, http via Web Browser (Non-Proprietary)
Summary Alarm Dry Contacts; Local Display; Modbus/TCP; Web Browser
Waveforms Local Display, Ethernet, http via Web Browser (Non-Proprietary)
History/Event Log Local Display, Ethernet, http via Web Browser (Non-Proprietary)
Diagnostics Local Display, Ethernet, http via Web Browser (Non-Proprietary)
Time Synchronization Network Time Protocol (NTP)
Standards Conformance
CSA ETL Listed to C22.22 No 107.
UL ETL Listed to UL 1008S
All data tables above are for 3-pole only. Contact LayerZero for custom sizes and designs.
Technical Specifications
All product specifications are subject to change without notice.
19 Š Copyright 2016 LayerZero Power Systems, Inc.
LayerZero Power Systems, Inc.
1500 Danner Drive
Aurora, OH 44202 U.S.A.
Š 2016 LayerZero Power Systems, Inc.
LayerZero Power Systems, LayerZero.com and the LayerZero logo are registered trademark of LayerZero.
All product specifications are subject to change without notice.
Learn more at www.LayerZero.com
Rev. 7/16 #16

More Related Content

What's hot

Advanced motion controls 20a20
Advanced motion controls 20a20Advanced motion controls 20a20
Advanced motion controls 20a20
Electromate
 
Advanced motion controls az6a8
Advanced motion controls az6a8Advanced motion controls az6a8
Advanced motion controls az6a8
Electromate
 
Advanced motion controls sx30a8
Advanced motion controls sx30a8Advanced motion controls sx30a8
Advanced motion controls sx30a8
Electromate
 
Advanced motion controls az12a8
Advanced motion controls az12a8Advanced motion controls az12a8
Advanced motion controls az12a8
Electromate
 
Advanced motion controls azxb8a8
Advanced motion controls azxb8a8Advanced motion controls azxb8a8
Advanced motion controls azxb8a8
Electromate
 
Advanced motion controls az25a20ddc
Advanced motion controls az25a20ddcAdvanced motion controls az25a20ddc
Advanced motion controls az25a20ddc
Electromate
 
Advanced motion controls s60a8
Advanced motion controls s60a8Advanced motion controls s60a8
Advanced motion controls s60a8
Electromate
 
Max485ds
Max485dsMax485ds
Max485ds
____
 
Advanced motion controls az20a8
Advanced motion controls az20a8Advanced motion controls az20a8
Advanced motion controls az20a8
Electromate
 
Advanced motion controls 10a8dd
Advanced motion controls 10a8ddAdvanced motion controls 10a8dd
Advanced motion controls 10a8dd
Electromate
 
Advanced motion controls s100a8
Advanced motion controls s100a8Advanced motion controls s100a8
Advanced motion controls s100a8
Electromate
 
Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"
michaeljmack
 
Advanced motion controls az60a8ddc
Advanced motion controls az60a8ddcAdvanced motion controls az60a8ddc
Advanced motion controls az60a8ddc
Electromate
 
Advanced motion controls az20a8i final
Advanced motion controls az20a8i finalAdvanced motion controls az20a8i final
Advanced motion controls az20a8i final
Electromate
 
Advanced motion controls az20a8i
Advanced motion controls az20a8iAdvanced motion controls az20a8i
Advanced motion controls az20a8i
Electromate
 
Switchgear Installation Precomissioning Inspection.PPT
Switchgear Installation  Precomissioning Inspection.PPTSwitchgear Installation  Precomissioning Inspection.PPT
Switchgear Installation Precomissioning Inspection.PPT
Abdullah Al Dushaishi
 

What's hot (20)

Advanced motion controls 20a20
Advanced motion controls 20a20Advanced motion controls 20a20
Advanced motion controls 20a20
 
Advanced motion controls az6a8
Advanced motion controls az6a8Advanced motion controls az6a8
Advanced motion controls az6a8
 
Cptg011 en (web)
Cptg011 en (web)Cptg011 en (web)
Cptg011 en (web)
 
Advanced motion controls sx30a8
Advanced motion controls sx30a8Advanced motion controls sx30a8
Advanced motion controls sx30a8
 
Advanced motion controls az12a8
Advanced motion controls az12a8Advanced motion controls az12a8
Advanced motion controls az12a8
 
VR-8 step voltage regulator
VR-8 step voltage regulatorVR-8 step voltage regulator
VR-8 step voltage regulator
 
Overview Study on Single-Channel I2C to 1-Wire Master DS2482
Overview Study on Single-Channel I2C to 1-Wire Master DS2482Overview Study on Single-Channel I2C to 1-Wire Master DS2482
Overview Study on Single-Channel I2C to 1-Wire Master DS2482
 
Advanced motion controls azxb8a8
Advanced motion controls azxb8a8Advanced motion controls azxb8a8
Advanced motion controls azxb8a8
 
Advanced motion controls az25a20ddc
Advanced motion controls az25a20ddcAdvanced motion controls az25a20ddc
Advanced motion controls az25a20ddc
 
Max 232
Max 232Max 232
Max 232
 
Advanced motion controls s60a8
Advanced motion controls s60a8Advanced motion controls s60a8
Advanced motion controls s60a8
 
Max485ds
Max485dsMax485ds
Max485ds
 
Advanced motion controls az20a8
Advanced motion controls az20a8Advanced motion controls az20a8
Advanced motion controls az20a8
 
Advanced motion controls 10a8dd
Advanced motion controls 10a8ddAdvanced motion controls 10a8dd
Advanced motion controls 10a8dd
 
Advanced motion controls s100a8
Advanced motion controls s100a8Advanced motion controls s100a8
Advanced motion controls s100a8
 
Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"
 
Advanced motion controls az60a8ddc
Advanced motion controls az60a8ddcAdvanced motion controls az60a8ddc
Advanced motion controls az60a8ddc
 
Advanced motion controls az20a8i final
Advanced motion controls az20a8i finalAdvanced motion controls az20a8i final
Advanced motion controls az20a8i final
 
Advanced motion controls az20a8i
Advanced motion controls az20a8iAdvanced motion controls az20a8i
Advanced motion controls az20a8i
 
Switchgear Installation Precomissioning Inspection.PPT
Switchgear Installation  Precomissioning Inspection.PPTSwitchgear Installation  Precomissioning Inspection.PPT
Switchgear Installation Precomissioning Inspection.PPT
 

Similar to LayerZero Series 70: eSTS Static Transfer Switch 150 A - 1200 A

Similar to LayerZero Series 70: eSTS Static Transfer Switch 150 A - 1200 A (20)

LayerZero Series 70 ePODs: Type-S (Power Distribution Unit)
LayerZero Series 70 ePODs: Type-S (Power Distribution Unit)LayerZero Series 70 ePODs: Type-S (Power Distribution Unit)
LayerZero Series 70 ePODs: Type-S (Power Distribution Unit)
 
LayerZero Series 70 ePODs: Dual Type-P
LayerZero Series 70 ePODs: Dual Type-PLayerZero Series 70 ePODs: Dual Type-P
LayerZero Series 70 ePODs: Dual Type-P
 
LayerZero Series 70 ePODs: Type-N Static Transfer Switch with Distribution
LayerZero Series 70 ePODs: Type-N Static Transfer Switch with DistributionLayerZero Series 70 ePODs: Type-N Static Transfer Switch with Distribution
LayerZero Series 70 ePODs: Type-N Static Transfer Switch with Distribution
 
LayerZero Series 70: eRPP Remote Power Panel
LayerZero Series 70: eRPP Remote Power PanelLayerZero Series 70: eRPP Remote Power Panel
LayerZero Series 70: eRPP Remote Power Panel
 
Ats brochure
Ats brochureAts brochure
Ats brochure
 
LayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
LayerZero Series 70: eRPP-SL2 Slim Remote Power PanelLayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
LayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
 
Chapter 10 Introduction to Air Insulation Substation .pptx
Chapter 10 Introduction to Air Insulation Substation .pptxChapter 10 Introduction to Air Insulation Substation .pptx
Chapter 10 Introduction to Air Insulation Substation .pptx
 
Power Distribution Report of THE NEOTIA UNIVERSITY CAMPUS
Power Distribution Report of  THE NEOTIA UNIVERSITY CAMPUSPower Distribution Report of  THE NEOTIA UNIVERSITY CAMPUS
Power Distribution Report of THE NEOTIA UNIVERSITY CAMPUS
 
LayerZero Series 70: ePanel-2 Wall-Mounted Power Panel
LayerZero Series 70: ePanel-2 Wall-Mounted Power PanelLayerZero Series 70: ePanel-2 Wall-Mounted Power Panel
LayerZero Series 70: ePanel-2 Wall-Mounted Power Panel
 
LayerZero Series 70 ePODs: Type-X Power Distribution Unit with Transformer an...
LayerZero Series 70 ePODs: Type-X Power Distribution Unit with Transformer an...LayerZero Series 70 ePODs: Type-X Power Distribution Unit with Transformer an...
LayerZero Series 70 ePODs: Type-X Power Distribution Unit with Transformer an...
 
LayerZero Series 70: ePanel-1 Wall-Mounted Power Panel
LayerZero Series 70: ePanel-1 Wall-Mounted Power PanelLayerZero Series 70: ePanel-1 Wall-Mounted Power Panel
LayerZero Series 70: ePanel-1 Wall-Mounted Power Panel
 
LayerZero Series 70: ePanel-HD2 High Density Power Panel
LayerZero Series 70: ePanel-HD2 High Density Power PanelLayerZero Series 70: ePanel-HD2 High Density Power Panel
LayerZero Series 70: ePanel-HD2 High Density Power Panel
 
Riello master-switch-sts-3p
Riello master-switch-sts-3pRiello master-switch-sts-3p
Riello master-switch-sts-3p
 
LayerZero Series 70: eRPP-FS Front/Side Access Remote Power Panel
LayerZero Series 70: eRPP-FS Front/Side Access Remote Power PanelLayerZero Series 70: eRPP-FS Front/Side Access Remote Power Panel
LayerZero Series 70: eRPP-FS Front/Side Access Remote Power Panel
 
ABB Relay
ABB RelayABB Relay
ABB Relay
 
Abb pvs 100-tl
Abb pvs 100-tlAbb pvs 100-tl
Abb pvs 100-tl
 
DSE335-Data-Sheet (1).pdf
DSE335-Data-Sheet (1).pdfDSE335-Data-Sheet (1).pdf
DSE335-Data-Sheet (1).pdf
 
Axpert hivert series mv drive
Axpert hivert series mv driveAxpert hivert series mv drive
Axpert hivert series mv drive
 
7SR12 Directional Over Current Relay
7SR12 Directional Over Current Relay7SR12 Directional Over Current Relay
7SR12 Directional Over Current Relay
 
Gemini_3__3008_web
Gemini_3__3008_webGemini_3__3008_web
Gemini_3__3008_web
 

Recently uploaded

Recently uploaded (20)

🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘
 
Deploy with confidence: VMware Cloud Foundation 5.1 on next gen Dell PowerEdg...
Deploy with confidence: VMware Cloud Foundation 5.1 on next gen Dell PowerEdg...Deploy with confidence: VMware Cloud Foundation 5.1 on next gen Dell PowerEdg...
Deploy with confidence: VMware Cloud Foundation 5.1 on next gen Dell PowerEdg...
 
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot TakeoffStrategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
 
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...
 
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
 
presentation ICT roal in 21st century education
presentation ICT roal in 21st century educationpresentation ICT roal in 21st century education
presentation ICT roal in 21st century education
 
Partners Life - Insurer Innovation Award 2024
Partners Life - Insurer Innovation Award 2024Partners Life - Insurer Innovation Award 2024
Partners Life - Insurer Innovation Award 2024
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024
 
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivity
 
Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)
 
Top 5 Benefits OF Using Muvi Live Paywall For Live Streams
Top 5 Benefits OF Using Muvi Live Paywall For Live StreamsTop 5 Benefits OF Using Muvi Live Paywall For Live Streams
Top 5 Benefits OF Using Muvi Live Paywall For Live Streams
 
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
 
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
 
Manulife - Insurer Innovation Award 2024
Manulife - Insurer Innovation Award 2024Manulife - Insurer Innovation Award 2024
Manulife - Insurer Innovation Award 2024
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processors
 
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, AdobeApidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
 
Tata AIG General Insurance Company - Insurer Innovation Award 2024
Tata AIG General Insurance Company - Insurer Innovation Award 2024Tata AIG General Insurance Company - Insurer Innovation Award 2024
Tata AIG General Insurance Company - Insurer Innovation Award 2024
 

LayerZero Series 70: eSTS Static Transfer Switch 150 A - 1200 A

  • 1. Series 70: eSTS 150 A - 1200 A Static Transfer Switch The Foundation Layer Product Brochure
  • 2. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS eSTS Automatically Transfers Between Two or Three* Power Sources LayerZero Power Systems designs and manufactures the world’s most reliable static transfer switch. The Series 70 eSTS is a solid-state transfer switch that automatically or manually provides solid state transfers between two in-phase AC sources in a quarter cycle. The eSTS performs open-transition transfer in such a manner that the connected load disruption is minimized without ever cross-connecting the power sources. One power source is selected to be the preferred source. If the preferred source fails the load is automatically and seamlessly connected to the alternate source by means of an open-transition static transfer. For emergency transfers between asynchronous sources, dynamically phase compensated transfers minimize saturation of downstream transformers in 3-phase, 3-wire eSTS. The LayerZero eSTS Static Transfer Switch Maximizes Power Reliability *Optional One Line Diagram 2 Š Copyright 2016 LayerZero Power Systems, Inc.
  • 3. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS ;; Optional Triple Modular Redundancy: TMR Contains Fully-Independent Control Paths With No Single Point-Of-Failure ;; Safe Bypass Procedure: Mechanical Bypass Interlock Eliminates Human Error When Performing Bypass Procedures ;; Voice Guided Bypass: Step-By-Step Instructions With Audio and Video Guidance To Assist Operators Through Bypass ;; Convection Cooling: Natural Convection-Cooled Heat Dissipation System is Maintenance-Free ;; Epoxy Coated Buswork: Maximizes Reliability By Eliminating The Possibility of Bus-To-Bus Faults ;; Silver Plated Terminals: Silver Has Excellent Conductivity To Provide Superior Electrical Performance and Reliability ;; Maintenance-Free Joints: Brazed Joints Are Permanent And Maintenance-Free, Maximizing Product Life ;; Machined Hardware: Machined Cap Screws and Engineered Disc Springs Maintain Constant Torque Throughout Product Life ;; Screw Thread Inserts: Prevents Screws From Loosening Under Vibration For Long-Term Reliability ;; Optical Fiber Based Controls: Eliminates Noise and Interference While Isolating Components from High Voltage ;; Serialized Critical Board Tracking: Critical Boards Are Serialized And Cataloged in an Active Database For Traceability Reliability Standard Features LayerZero’s eSTS Is Equipped Fully-Loaded Safety ;; InSight™ IR Portholes: Bolted Connections & Critical Boards Can Be IR Scanned With the Dead-Front Doors Closed ;; Sectionalized Components: Isolated Sections That Can Be Safely De-Energized For Performing Maintenance ;; Polycarbonate Windows: Allows Critical Board LEDs To Be Viewed With The Dead-Front Door Closed ;; Front-Only Access: Installation and Maintenance Can Be Safely Performed Without Side or Rear Access ;; Dead Front Hinged Doors: Barrier To Provide A Safe Working Area With No Exposed Live Parts Connectivity ;; Ethernet Connectivity: Secure VPN Router Connects To Network For Advanced Remote Monitoring Capabilities ;; Modbus/TCP: Open Connectivity to Existing Monitoring Systems Without Proprietary Limitations ;; NTP Time Clock Synchronization: Facilitates Timeline-Based Logging For Post-Event Reconstruction ;; SNMP Connectivity: Permits Remote Management Via Simple Network Management Protocol ;; Real-Time Waveform Capture: Automatically Captures A Picture Of The Power Three-Cycles Before and After Every Event ;; Local Touch-Screen Interface: Password-Protected Color Touch-Screen GUI For Local STS Setup/Operation/Administration ;; Black-Box Forensics: Captures and Records All Events To Provide Vital Information In Root-Cause Analysis ;; Waveforms Automatically Emailed: Capability to Send Waveform Captures To Designated Individuals For Every Transfer 3 Š Copyright 2016 LayerZero Power Systems, Inc.
  • 4. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS 1200 A eSTS Section Overview Controls Section Power Electronics Section Input/Output Bypass Isolation Section Source & Load Terminal Section Controls Section Circuit Breaker Section 150 A - 800 A eSTS Section Overview 4 Š Copyright 2016 LayerZero Power Systems, Inc.
  • 5. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS CB Section Contains: Input isolation switches Bypass isolation Switches Output isolation switches Source connection terminals Load connection terminals Controls Section Contains: Power electronics • SCRs (Silicon Control Rectifier) in Convection Cooled Heat Sinks Control Electronics • System Control & Data Acquisition Boards • SCR Gate Drives • Redundant Power Supply System • I/O system; VPN Router Equipment Layout (400 A Shown) CB101 Source 1 Isolate Source 1 Phase A SCRs CB102 Source 2 Isolate CB201 Bypass Isolate, Source 1 CB202 Bypass Isolate, Source 2 CB301 Output Isolate 1 CB302 Output Isolate 2, (Redundant, Optional) Source 2 Phase A SCRs Source 2 Phase B SCRs Source 1 Phase B SCRs Source 1 Phase C SCRs Source 2 Phase C SCRs 5 Š Copyright 2016 LayerZero Power Systems, Inc.
  • 6. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS 1. Alarmed Doors 2. Hinged Dead Front Doors 3. 15” Color Touch Screen GUI 4. Printed Bypass Instructions 5. InSight™ IR Portholes 6. Convection Cooled Heat Sinks 7. Staggered Gate Drive Arrangement 8. Epoxy Coated Buswork 9. Circuit Breakers 10. Redundant Power Supplies 11. Convection Cooled Intake 1 2 3 4 5 67 8 9 10 11 Equipment Construction Detail (800 A Shown) 1. Alarmed Doors 2. Hinged Dead Front Doors 3. Silver Plated Terminals 4. 15” Color Touch Screen GUI 5. Printed Bypass Instructions 6. Polycarbonate Window 7. InSight™ IR Portholes 8. Convection Cooled Heat Sinks 9. Staggered Gate Drive Arrangement 10. Epoxy Coated Buswork 11. Circuit Breakers 12. Redundant Power Supplies 13. Convection Cooled Intake 1 2 3 4 5 6 7 8 9 10 11 12 13 1200 A Shown 6 Š Copyright 2016 LayerZero Power Systems, Inc.
  • 7. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS LayerZero eSTS Reliability Overview The LayerZero eSTS Provides Many Dimensions of Reliability: • Control System Reliability • SMR (Single Module Redundancy, Standard) • TMR (Triple Modular Redundancy, Optional) • Control Power Supply Reliability • Signal Reliability • Operator Procedural Reliability Gate Drive 1 Source 1 A Gate Drive 2 Source 1 B Gate Drive 3 Source 1 C Gate Drive 4 Source 2 A Gate Drive 5 Source 2 B Gate Drive 6 Source 2 C Source 1 Control Source 2 Control WAN Port Fiber Optics SCB 1 Single Module Redundancy (SMR) Reliability (Standard) Single Module Redundancy is a cost-effective topology that provides redundant power paths to mission-critical equipment. In SMR systems, sources each have built-in triple redundancy of processors. In addition, every phase is controlled with a separate gate drive board. LayerZero Single Modular Redundant topology is unique that it the system is fail-safe, maintaining full switching functionality even if a critical board were to fail. Reliability Overview 7 Š Copyright 2016 LayerZero Power Systems, Inc.
  • 8. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS Reliability Features: Triple Modular Redundancy (TMR) *Optional Triple Modular Redundancy (TMR) Reliability (Optional) LayerZero TMR has all the redundancy of SMR, plus each STS has three independent sets of analog and digital data acquisition and control systems. There is no direct communication between the three systems. The three systems do not even share a common system clock. • Each control system acquires voltage and current data independently • Each control system determines whether a source is good/bad independently • Upon loss of a source, each control system makes decisions to transfer independently Even if an entire control path or its subcomponent were to fail; and then if the active power source were to fail, the STS is able to complete its mission of transferring to the alternate source. Triple Modular Redundancy, a proper noun, is a based on proven statistics and stringent mathematics. There are similar sounding terms like, tri- or triple- redundant, used in industry to describe other STS products – but they simply do not yield the same, high level of reliability. Gate Drive 1 Source 1 A Gate Drive 2 Source 1 B Gate Drive 3 Source 1 C Gate Drive 4 Source 2 A Gate Drive 5 Source 2 B Gate Drive 6 Source 2 C Source 1 Control Source 2 Control Source 1 Control Source 2 Control Source 1 Control Source 2 Control WAN Port Fiber Optics SCB 1 SCB 2 (TMR) SCB 3 (TMR) 8 Š Copyright 2016 LayerZero Power Systems, Inc.
  • 9. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS eSTS SMR Triple Redundant Power Supply Architecture Divided into four (4) logical failure groups: • System controls • Source 1 gate drives • Source 2 gate drives • Peripherals. The three (3) available source of power from which to supply control power to each failure group are: • Source 1 • Source 2 • STS Output. LayerZero’s STS design incorporates twelve (12) power supplies (3 power sources x 4 failure groups.) The resultant control power topology utilizes all possible power paths to the four logical STS failure groups; and is the most comprehensive and redundant power supply system in existence. Reliability Features: Single Module Redundant (SMR) Redundancy Peripherals PS 1 S1 A-B Source 1 A B C Source 2 A B C PS 4 S1 B-C PS 7 S1 A-C PS 10 S1 A-B PS 3 S2 B-C PS 6 S2 A-C PS 9 S2 A-B PS 12 S2 B-C System Controls Gate Drives, Source 1 Gate Drives, Source 2 GD 1 GD 3 GD 5 SCB 1 SCB 2 TMR Only SCB 3 TMR Only GD 2 GD 4 GD 6 PS 5 Out A-B System Controls PS 8 Out B-C Gate Drives S1 PS 11 Out A-C Gate Drives S2 PS 2 Out A-C Peripherals Output Bus A B C eSTS SMR Triple Redundant Processors • Separate/independent processors for Source 1, Source 2 and Output power quality analysis • If Source 1 processor malfunctions then system is able to be commanded to transfer to Source 2; & vice versa. • If main control system fails then STS continues to conduct power to the load from the existing source of power. (However STS is unable to transfer to the other source) • Each phase of each source is controlled with a separate gate drive circuit board. 9 Š Copyright 2016 LayerZero Power Systems, Inc. S1 S2 Output Gate Drive 1 Gate Drive 2 Gate Drive 3 Gate Drive 4 Gate Drive 5 Gate Drive 6 A B C A B C Source 1 Transfer Control Source 2 Transfer Control
  • 10. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS Mechanical Bypass Interlock In order to minimize the possibility of operator error during equipment bypass operations, LayerZero provides: 1. Interlocked breakers 2. Mechanisms to ensure that a source cannot be bypassed without the STS on the correct source. 3. Safeguards to make certain that sources cannot be connected to each other inadvertently. 4. A voice-prompted bypass procedure that guides the operator through the sequence. 5. A step-wise pictorial & video presentation is provided on the touch-screen display during bypass. Voice Guided Bypass Operator error during maintenance bypass has been known to be a reliability hazard. To help prevent operators from completing the bypass procedure out-of-sequence, our product features a voice prompted bypass procedure. This instructs the operator in a step- by-step course of action of the process, with only one operation per screen. Visual and audio cues provide clear instructions on the bypassing sequence, reducing the probability of operator error. Reliability Features 10 Š Copyright 2016 LayerZero Power Systems, Inc.
  • 11. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS No Fans, Dust Filters, or Fan Fuses The Series 70: eSTS Static Transfer Switch utilizes a natural convection- cooled heat dissipation system. Fans and fan sensors are some of the most common components to fail. For maximum uptime, LayerZero’s eSTS systems do not contain any fans, dust filters to change, or fan fuses to replace. The heat sink arrangement is staggered between sources and phases to minimize the creation of extreme thermal gradients between heat sink columns when conducting on one source or the other. Epoxy Coated Buswork/Maintenance Free Joints Our usage of epoxy coated buswork helps ensure safety, and makes the system inherently more reliable by eliminating the possibility of bus-to-bus faults. Bus joints are permanently brazed and maintenance-free. Silver Plating LayerZero utilizes silver plating on all bus joints and terminals to be able to provide the highest performance. Silver has high conductivity and low resistance - which makes for a great contact. Reliability Features 11 Š Copyright 2016 LayerZero Power Systems, Inc.
  • 12. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS Fiber Optic Controls Increase System Reliability Fiber optic based controls eliminate noise and interference, while isolating components from high voltage. Optical fiber allows service to be reliably connected, while protecting the equipment. In LayerZero’s eSTS design, the gate drives (at Power Circuit Voltage) receive control signals via optical fibers. Serialized Critical Board Tracking We serialize and track all critical boards and maintain this information in an active, dynamic database. 12 Š Copyright 2016 LayerZero Power Systems, Inc. Reliability Features
  • 13. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS InSight™ IR Portholes Permit Scanning of Bolted Connections with Dead-Front Doors Closed Strategically positioned IR-scan portholes to enable safe thermal scanning of all bolted connections with the deadfront closed, without exposing the operator to power circuit voltage. Thermal scans can be done from the front – without ever having to open the dead-front door. The IR window swivels upward and unlocks with key-hole access to reveal a mesh, allowing the operator to point-and-shoot thermal cameras to obtain readings. CB101 CB102 CB201 CB202 CB302 Source 1 Source 2 CB301 Load 1 2 1 2 2 IR Portholes in eSTS (Door and side panel hidden for visibility) Ease of Maintenance 13 Š Copyright 2016 LayerZero Power Systems, Inc.
  • 14. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS Modbus/TCP http:// through a standard web browser Network Time Protocol (NTP) Compliant For Clock Synchronization Simple Network Management Protocol (SNMP) Waveforms Automatically Emailed Series 70: eSTS Standard Ethernet Dry Contacts • Meters • Alarms • Meters • Alarms • Waveforms • History/Event Log • Diagnostics • Summary Alarm • On Source 1 • On Source 2 • Source 1 Available • Source 2 Available eSTS Connectivity Options • Non-Proprietary Protocols Ease of Maintenance/Connectivity Options Front Only Access Saves Space The Series 70: A eSTS is designed to be installed, operated, diagnosed and maintained only from the front. The dead-front panels are hinged, and side or rear covers never have to be removed. Unhinged covers can be bulky and unwieldy, and operator error during removal and replacement of covers has been known to cause mishaps and compromise load reliability. A safe, non-invasive operation and maintenance regime results in a higher reliability of the critical load. The Series 70: eSTS utilizes dead-front hinged doors. An alarm notifies when an outer door has been opened. 14 Š Copyright 2016 LayerZero Power Systems, Inc.
  • 15. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS A V PQ Current Metering Point Voltage Metering Point Power Quality Metering Point BM Branch Current Monitoring Features/Power Quality Monitoring 15” Color Touch Screen (Standard) 1. Stereo Speakers for Guided Bypass Prompts 2. Output On Light (Remains Lit in Bypass Isolate Mode) 3. Alarm & Bypass Indicator 4. SCB Status Indicator 5. Logged In User 6. Navigation Menu 7. Customer & Project Information 8. Date & Time 1 2 3 4 5 6 207 8 Zen is being aware of all all activity in your critical power distribution systems, it is an all encompassing monitoring system with local and remote communications options. From basic monitoring, alarms, to advanced power quality monitoring functionality, Zen SSQM provides a wide-range of options to help you maintain the highest level of reliability. Zen gives you a vendor-neutral “Birds Eye” view of your entire critical power distribution infrastructure. Zen maximizes reliability, letting you know if a source has quality issues, if a UPS output is bad, or if there are any alarms. In addition, Zen empowers users with the capability to go back in time to retrace the exact sequence of historical events. No other tool in the mission-critical industry empowers users with this robust capability. 15 Š Copyright 2016 LayerZero Power Systems, Inc.
  • 16. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS The Series 70: eSTS is equipped with Zen SSQM (Static Switch Quality Monitoring), an all encompassing monitoring system with local and remote communications options. From basic monitoring & alarm reporting, to advanced power quality monitoring functionality, Zen SSQM provides a wide-range of options to help you be aware, be vigilant, be proactive in your quest to create a safe, stable and reliable operation. Zen SSQM Provides Answers Zen SSQM provides timestamped pictures of waveforms before and after events, providing information that enables facilities to go back in time to methodically identify and correct the root causes of events. Zen actively captures power quality information at the STS, PDU, and RPP - permitting thorough post-event analysis. Product Name: Series 70 ePODs: Type-P Unit Name: 500 + 1000 turn CTs Serial #: 10028-34 Capture Reason: SQ Xfer 0-1 Captured By: scb122 Capture Time: 01-04-2016 6:53:08 PM Microticks: 1449941 Phase A Phase B Phase C Phase N Phase G Source 1 Volts L-L Milliseconds V o l t s 0 -200 200 -400 400 -600 600 -800 800 -1000 1000 Source 2 Volts L-L Milliseconds V o l t s 0 -200 200 -400 400 -600 600 -800 800 -1000 1000 Load Volts L-L V o 200 400 600 800 1000 Trigger Event 3 Electrical Cycles 3 Electrical Cycles Waveform Capture of Current in a Source TransferPhase A Phase B Phase C Power Quality Monitoring 16 Š Copyright 2016 LayerZero Power Systems, Inc.
  • 17. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS Zen SSQM Parameters Mains Voltage Inputs and Output Voltage (Volts) Ăź Voltage Average of Phases (Volts) Ăź Frequency (Hertz) Ăź Total Harmonic Distortion (Percent VTHD) Ăź Phase Rotation Ăź Current Inputs Current (Amps) Ăź Current Average of Phases (Amps) Ăź Current Imbalance (Percent) Ăź Real Power (kilowatts) Ăź Apparent Power (kilovolt-amperes) Ăź Reactive Power (kilovolt-amperes reactive) Ăź Power Factor Ăź Crest Factor Ăź Crest Factor Average of Phases Ăź Phase Difference Between Sources Ăź Phase Difference Between Sources and Output Ăź Alarms Summary Alarm Ăź On Source (1/2/3) Ăź Source Fail (1/2/3) Ăź Source Preferred (1/2/3) Ăź Source 1st Alternate (1/2/3) Ăź Source Over/Under Voltage (1/2/3) Ăź Source Over/Under Frequency (1/2/3) Ăź Source Not Available (1/2/3) Ăź Output Failure Ăź Source Overcurrent (1/2/3) Ăź Source Exceeds Manual Limit (1/2/3) Ăź Source Exceeds Automatic Limit (1/2/3) Ăź Bypassed to Source (1/2/3) Ăź Zen SSQM Technical Specifications 17 Š Copyright 2016 LayerZero Power Systems, Inc.
  • 18. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS eSTS Models with Withstand Ratings eSTS Rating (100%) 120/208 V 480 V; 480/277 V; 415/240 V; 400/230 V; 220/380 V 600 V; 600/347 V; 575 V 150 A 150kA; 100kA; 65kA 150kA; 100kA; 65kA; 35kA 100kA; 65kA; 35kA; 25kA 250 A 400 A 600 A 800 A 100kA; 65kA 100kA; 65kA; 50kA; 35kA 42kA; 35kA; 25kA 1200 A 100kA*; 65kA; 50kA 65kA*; 50kA; 25kA * Upgrade to Automatic Circuit Breakers Mechanical Characteristics * 150 A - 250 A 400 A 600 A 800 A 1200 A Heat Dissipation 4,750 BTU/Hr 7,000 BTU/Hr 9,500 BTU/Hr 12,500 BTU/Hr 24,000 BTU/Hr Weight 1,350 lbs (612 kg) 1,400 lbs (635 kg) 1,500 lbs (680 kg) 1,950 lbs (885 kg) 5,500 lbs (2495 kg) Dimensions 48”W x 36”D x 80”H (1219 mm x 914 mm x 2032 mm) 58”W x 36”D x 80”H (1473 mm x 914 mm x 2032 mm) 96”W x 48”D x 90”H (2438 mm x 1219 mm x 2286 mm) Frame Construction Welded Frame Electrical Connections Silver-Plated Solid Busbar Color Textured Powder Coat White (RAL 7035), Blue (RAL 5017), Black, Custom Floor Stands Optional Seismic floor stands Optional Junction Boxes Optional Sectionalization Engineered Composite Insulation, Dead Front Doors Electrical Characteristics Number of Inputs 2, 3 (3 optional) Number of Output CBs 1, 2 Frequency 50 Hz, 60 Hz Poles 3-pole Phases 3 Phase, 3 Wire, 4 Wire + Ground Neutral Rating 100%, 150%, 200% Transfer Time Nominal 1/4- cycle for in-phase sources Redundancy Single Module Redundancy, Triple Modular Redundancy (Optional) Circuit Breaker Type Molded Case Switch (Standard), Electronic Trip (Optional) Circuit Breaker Mounting Type Plug-In up through 600 A; Draw-out 800 A, 1200 A TVSS Standard Power Quality Monitoring Power Quality Monitoring Technology Zen SSQM™ (Static Switch Quality Monitoring) Waveform Capture Local Display, Remote Display via Web Browser, Waveforms Automatically Emailed Voltmeter Input sources and Output, for each phase Ammeter Input sources and Output, for each phase Frequency Meter Both Sources Synchroscope Phase Angle Meter Between Sources Metering Apparent Power, Real Power, Power Factor, Output Total Harmonic Distortion Time Stamped Transfer Count From First Day Use, From Last Reset CB Status Indicator Open/Closed/Tripped Circuit Breaker Source Indicator Preferred Source Power Path Indicator On Live Mimic *Dimensional & weight data is only valid for 2-source. Technical Specifications: 3-Pole Static Transfer Switch All product specifications are subject to change without notice. 18 Š Copyright 2016 LayerZero Power Systems, Inc.
  • 19. 150 A - 1200 A Static Transfer SwitchSeries 70: eSTS Operational Characteristics Transfer Modes Automatic; Manual (via Preferred Source Selection) Inrush Mitigation Technology Patented Dynamic Phase Compensation Algorithm (U.S. Patent 7,589,438 B2) Cooling Convection Cooling Cable Access Top/Bottom Service Access Front Only Bypass Interlock Mechanism Mechanical Noise & Interference Isolation Optical Fiber in Critical Control Paths IR Scan Port Type InSight™ IR Portholes SCR Type Puck Display Type 15” Color Touch Screen Display Resolution 1024x768 Bypass Assistance Voice-Guided Bypass Audio Bezel-Mounted Stereo Speakers Languages English, French Mimic Panel Digital Setpoints Control Digital Power Supplies Redundant (4 Failure Groups. Triple Redundant Supplies. 12 Power Supplies Provided.) Connectivity Meters Local Display, Ethernet, Modbus/TCP, http via Web Browser (Non-Proprietary) Alarms Local Display, Ethernet, Modbus/TCP, http via Web Browser (Non-Proprietary) Summary Alarm Dry Contacts; Local Display; Modbus/TCP; Web Browser Waveforms Local Display, Ethernet, http via Web Browser (Non-Proprietary) History/Event Log Local Display, Ethernet, http via Web Browser (Non-Proprietary) Diagnostics Local Display, Ethernet, http via Web Browser (Non-Proprietary) Time Synchronization Network Time Protocol (NTP) Standards Conformance CSA ETL Listed to C22.22 No 107. UL ETL Listed to UL 1008S All data tables above are for 3-pole only. Contact LayerZero for custom sizes and designs. Technical Specifications All product specifications are subject to change without notice. 19 Š Copyright 2016 LayerZero Power Systems, Inc.
  • 20. LayerZero Power Systems, Inc. 1500 Danner Drive Aurora, OH 44202 U.S.A. Š 2016 LayerZero Power Systems, Inc. LayerZero Power Systems, LayerZero.com and the LayerZero logo are registered trademark of LayerZero. All product specifications are subject to change without notice. Learn more at www.LayerZero.com Rev. 7/16 #16