Minimize the load reduction considering the activities control of
the generators and phase distance
Le Trong Nghia1
, Quyen Huy Anh2
, Phan Thi Thanh Binh3
, Phung Trieu Tan4
1,2
HCMC University of Technology and Education, Vietnam
3
HCMC University of Technology, Vietnam
4
CaoThang Technical College, Vietnam
Article Info ABSTRACT
Article history:
Received Feb 28, 2020
Revised Jun 14, 2020
Accepted Jun 29, 2020
This study shows how to calculate the minimum load that needs to be
reduced to restore the frequency to the specified threshold. To implement this
problem, the actual operation of the electricity system in the event of a
generator outage is considered. The main idea of this method is to use the
power balance equation between the generation and the load with different
frequency levels. In all cases of operating the electrical system before and
after the generator outage, the reserve capacity of other generators is
considered in each generator outage situation. The reduced load capacity is
calculated based on the reciprocal phase angle sensitivity or phase distance.
This makes the voltage phase angle and voltage value quality of recovery
nodes better. The standard IEEE 9-generator 37-bus test scheme was
simulated to show the result of the proposed technique.
Keywords:
Frequency control
Generator control
Load shedding
Phase electrical distance
This is an open access article under the CC BY-SA license.
Corresponding Author:
Trong Nghia Le
HCMC University of Technology and Education
Hochiminh city, Vietnam
Email: trongnghia@hcmute.edu.vn
1. INTRODUCTION
Generator outage is reason for the inequality of real power and frequency reduction in the electrical
system. In some cases, this may blackout the system. In [1] presented a summary of the load shedding
solutions implemented over the years. In [2-4] presented intelligent solutions to maintain electricity system
stability. Besides the implementation of all control solutions, including the solutions using FACT equipment
[5, 6] to maintain electrical system constraints, the load shedding is an undesirable action of electricity
suppliers and also for electricity consumers because it has impacts on socio-economic impacts. However, this
is an unavoidable case when other possible solutions are used to restore the frequency. What is needed here is
to cut the load to reduce the consequences for electricity consumers and socio-economic. The design and
calculation the amount of load shedding is a complex process, requiring large amounts of input data on
incident situations that cause serious frequency attenuation. Conventional load-shedding methods typically
use load shedding relays [7-11] with step-by-step load shedding that correspond to levels of frequency
attenuation or df/dt [12]. Most of these methods, the power of load that need to be cut in the form of load
shedding tables is built by the electrical system specialist. This may cause inadequate or excessive load
shedding compared to the value required. Some of the current load shedding methods used the swing rotor
equation and voltage electrical distance application [13-15] to estimate the load to be cut. They combined
with knowledge technology algorithms to calculate the minimum economic losses. However, these methods
have not considered the technical and operational factors of electricity system after power inequality.
 ISSN: 2088-8708
Int J Elec & Comp Eng, Vol. 11, No. 2, April 2021 : 993 - 1001
994
In this article, a technique of calculating the load curtailment that takes into account generator
control problems is appropriate for the actual operation of the electrical system such as: primary control
issues, secondary control issues of generators. Furthermore, load reduction based on phase distance ensures
that phase angle and frequency recover faster than traditional load shedding methods.
2. METHODOLOGY FOR RESEARCH
2.1. The frequency responds
The ability to vary power according to frequency or the frequency stability ability of a turbine is
determined by the drop of the speed control characteristic [16, 17]. Characteristics present the ability to
adjust the turbine's power when the rotation speed changes are presented in Figure 1. The correlation is
determined by equation:
p
f
R
PG



(1)
where R is the speed or droop adjustment factor; p
f
 is the frequency change; PG
 is the change in generator
power. Variation of both power and frequency is determined by equation:
.
G p
n
G
i n
P f
P
R f
 
 
(2)
where: is the rated power of the generators.
The load in the electricity system is a diverse collection of different electrical equipment. The power
can be either relied on the frequency (for instance the case of a motor load like fan or pump, the change in
power and frequency leading to the change of motor speed) or not relied on the frequency (for instance resistive
loads like lighting or heating). The power of the combined load can be expressed by the (3) [18, 19]:
(3)
where PL is the combined load component, PID is the frequency-independent load component, e.g. heat load,
lighting… PD is the frequency-relied load component. The change correlation between the load power
characteristics and frequency is shown in Figure 2.
Figure 1. Correlation between generator power
change and frequency change
Figure 2. The change correlation between the load
power characteristics and frequency
The variation of load according to the frequency variation is shown in the following equation [18]:
P P P
L ID D
  
(4)
P
Gn
P P P
L ID D
 
Int J Elec & Comp Eng ISSN: 2088-8708 
Minimize the load reduction considering the activities control of ... (Le Trong Nghia)
995
When the frequency is equal to the rated frequency fn, the required power of the load is the same as
the actual consumed power PL0, when the frequency decreases from fn to f1, the actual power used decreases
from PL0 to PL1. The correlation between the load variations and frequency variation is determined by
equation:
. .
combined load
f
P P D
D fn

  
(5)
where ∆PD is the variation of load power according to frequency variation; D is the percentage variation of
load according to the percentage frequency variation [16]; D value ranges from 1% to 2% and is determined
by experimental methods on electricity systems.
2.2. Regulator activities the generators in accordance with the actual operation
When the generator is failed, the frequency adjustment will start and include the following
operations: primary regulating effects and secondary regulating effects. In case, at the end of this impact
activity and the frequency is still below the permissible constrains, the next step will implement the load
reduction. The objective is to restore the frequency to the required threshold value. These impact activities
are indicated in Figure 3.
In this figure, line (A) is the normal operating characteristic of the system; line (B) and (D) are the
feature of generators without the governor; line (C) is the feature at the time the generator is disconnected;
line (E) is the operating characteristic after the secondary regulating effects of the generator; line (F) and (G)
are the load characteristics before and after implement the load reduction; the fpermit value is the frequency
parameter achieved after the load reduction.
Figure 3. Regulator activities the generators and load reduction
2.3. The minimum load reduction capacity
Calculating minimum load reduction PLS min ensures restoration of electricity system frequency to
the allowable value, minimizing damage to electricity consumers. The calculation includes the activity
control of the generators in accordance with the actual operation. In a power system with n generators, when a
generator outage, the primary regulating effects of the others (n-1) generators is made with the adjustment of the
power with the below equation:
1 1
,
Pr
1 1
.
n n
p
Gn i
i
i i i
f
P
P
f
R n
 
 

  
  (6)
The amount of power of the frequency-dependent load reduces the amount of ∆PD is shown in (5).
Power balance status is presented in the following equation:
(7)
1 1
Primary control
1 1
n n
P P P P
L D Gi
i i
 
   
 
 
 ISSN: 2088-8708
Int J Elec & Comp Eng, Vol. 11, No. 2, April 2021 : 993 - 1001
996
1 1
,
1 1
.
n n
p
Gn i
G
L D
i
i i i
f
P
P P P
f
R n
 
 

   
  (8)
1 1
,
1 1
. .
n n
p p
Gn i
G
L L
i
i i i
f f
P
P P P D
f f
R
n n
 
 
 
   
  (9)
(10)
Set and
From (10) infer:
(11)
In the case of the considering secondary control power, the new power balance equation with the new
frequency value f2, the (7) becomes:
(12)
Secondary control max , Primary control, j
1
( )
k
Gm j
j
P P P

   
 (13)
If frequency value after implement the secondary regulating effects is lower than tolerable rate, load
reduction is required to restore frequency. The minimum load reduction PLSmin is considered by:
(14)
(15)
1 1
,
secondary control max
1 1
. P . .
min
n n
permit permit
Gn i
G
L L
i
i i i
f f
P
P P P D P
LS f f
R
n n
 
 
 
     
  (16)
Equation (15) is abbreviated according to the following equation:
secondary max
.
min
permit
L
f
P P P
LS fn


      (17)
2.4. The phase angle sensitivity or phase distance (PD)
The reciprocal phase angle sensitivity or phase distance (PD) from the load reduction to disconnected
generator is considered using the methods in [20-24], that is applied as procedure:
- Calculate the Jacobian matrix from the power flow distribution according to Newton Raphson, and from
there obtain the sub matrix J1 with 1 .
P
P
J J 


 
   

 
- Inverse matrix, 1
P
J 

- Calculate the PD between two bus i and j according to the formula [20, 21]:
1 1 ,
( )( . )
1 1
PG
n n
f n i
P P P D
L G L
f R
i
i i
n i
 

  
 
 
-1
-
1
n
P P P
L L Gi
i
  

1 ,
.
1
PG
n n i
P D
L R
i i


  

.
f
PL fn


 
1 1
Primary control Secondary control max
1 1
n n
P P P P P
L D Gi
i i
 
    
 
 
1 1
Primary control Secondary control max min
1 1
i
n n
L D G LS
i i
P P P P P P
 
 
       
 
1 1
min Primary control Secondary control max
1 1
n n
P P P P P P
LS L D Gi
i i
 
      
 
 
Int J Elec & Comp Eng ISSN: 2088-8708 
Minimize the load reduction considering the activities control of ... (Le Trong Nghia)
997
( , )
j j
i i
PD
i j j i
D i j
P P P P
 
 
 
 
   
   
(18)
The purpose of the delivery the load reduction at each buses is to restore the rotor angle deviation
faster. The load near the generator outage will have a much reduced load. The formula for this delivery is
given in the following:
,
min
,
.
i
PD eq
LSi LS
PD m
D
P P
D
 (19)
,
,
1
1
i
PD eq
i m
PD m
D
D



(20)
where , i
PD m
D is the phase space or distance from load reduction to i
m disconnected generator; DPD,eq is the
equivalent phase distance
3. SIMULATION AND RESULTS
The PowerWorld simulator version 19 is used to set up the simulation background. The standard
IEEE 9-generator 37-bus test system [25] is used to support simulation and calculation. This diagram is
shown in Figure 4. The accepted frequency values are between 59.7 Hz and 60 Hz.
Figure 4. The standard 9-generator 37-bus test system
 ISSN: 2088-8708
Int J Elec & Comp Eng, Vol. 11, No. 2, April 2021 : 993 - 1001
998
In this study, the generator JO345#1 is disconnected from the grid. From (11), the frequency obtains
59.6 Hz. Therefore, it is necessary to implement the frequency adjustment action to restore frequency. This
adjustment activity is done automatically. The reaction of the turbine governor is performed immediately
after the generator JO345#1 is disconnected. The spinning standby power values of the others generators are
presented in Table 1.
Table 1. Parameter values and standby power of generators
No Gen PG (MW) PG (pu) R Pri
P
 ,
G n
P
R
1 WEBER69 31.5 0.315 0.05 0.035 7
2 JO345#1 0 0 0.05 0 0
3 JO345#2 135 1.35 0.05 0.15 30
4 SLACK345 187.28 1.8728 0.05 0.22 44
5 LAUF69 135 1.35 0.05 0.15 30
6 BOB69 46 0.46 0.05 0.052 10.4
7 ROGER69 72 0.72 0.05 0.08 16
8 BLT138 126 1.26 0.05 0.14 28
9 BLT69 99 0.99 0.05 0.11 22
Total 831.78 8.3178 0.937 187.4
The standard IEEE 9-generator 37-bus test system, the SLACK 345 (SLACK Bus) is selected as the
secondary frequency control generator. In this case, application (13) calculates the ability of secondary
regulating effects of 10.72 MW. This frequency response following the others generators implement
frequency adjustment is displayed at Figure 5.
Figure 5. The frequency response after remaining generators implements frequency adjustment
The frequency reaction displays that frequency value has not been reestablished to the permissible
operating series. Applying (17) calculates the load to be cut or reduced to reestablish the frequency value to
the required operating range.
min Secondary control max
0
.
cp
LS L
f
P P P
f


     
1
1
9,5394 8,31780 1,2216
i
n
L L G
i
P P P


     

Int J Elec & Comp Eng ISSN: 2088-8708 
Minimize the load reduction considering the activities control of ... (Le Trong Nghia)
999
1
1
. 9,5394.0,02 187,4 187,59
n
Gi
L
i i
P
P D
R



    

min
( 0.3)
1,2216 .187,59 0,1072 0,1764
60
LS
P pu

    
So, the minimum load shedding capacity of P Load shedding min is 17.64 MW. This value is distributed
for each load according to the (19). The comparison of frequency response and rotor angle is shown in
Figure 6 and Figure.
It is marked that the suggested method is produced a lesser load reduction than the traditional load
reduction method [4], in particular the load shedding number is reduced from 82.93 MW to 17.64 MW. The
frequency response of the traditional load reduction method is better than the proposed method. Due to the
traditional method, the load is reduced more than the proposed method of reducing the load. However, this
value is acceptable because it is inside the suitable range of 59.7 Hz. The rotor deviation angle of both
solutions is approximately equivalent. This has many positive implications in maintaining system stability.
Figure 6. Frequency response of the offered load reduction and old load reduction method
Figure 7. Rotor angle when applying the traditional and the proposed load reduction method
 ISSN: 2088-8708
Int J Elec & Comp Eng, Vol. 11, No. 2, April 2021 : 993 - 1001
1000
4. CONCLUSION
The consideration of the standby power of the generators has supported to calculate the load to be
reduced in accordance with reality. This calculation makes the recovery frequency to an acceptable value.
The calculation method takes into account the standby ability the generators, and the process of adjusting
frequency of generator in the event of a power outage. Calculating the amount of load to disconnect causes
damage to the lowest level for customers, important services when cutting load. The distribution of load
shedding capacity based on Phase Electrical Distance makes the rotor deviation angle equivalent to UFLS
method. This increases the stability of the system when a power outage occurs.
ACKNOWLEDGEMENTS
This work belongs to the project in 2020 funded by Ho Chi Minh City University of Technology
and Education, Vietnam.
REFERENCES
[1] Raghu C. N. and A. Manjunatha, “Assessing Effectiveness of Research for Load Shedding in Power System,”
International Journal of Electrical and Computer Engineering (IJECE), vol. 7, no. 6, pp. 3235-3245, 2017.
[2] S. F. A. Shukor, et al., “Intelligent based technique for under voltage load shedding in power transmission
systems,” Indonesian Journal of Electrical Engineering and Computer Science (IJEECS), vol. 17, no. 1,
pp. 110-117, 2020.
[3] S. M. Hossain and M. M. Hasan, “Energy Management through Bio-gas Based Electricity Generation System
during Load Shedding in Rural Areas,” TELKOMNIKA Telecommunication Computing Electronics and Control,
vol. 16, no. 2, pp. 525-532, 2018.
[4] R. M. Larik, et al., “A statistical jacobian application for power system optimization of voltage stability,”
Indonesian Journal of Electrical Engineering and Computer Science (IJEECS), vol. 13, no. 1, pp. 331-338, 2019.
[5] G. A. M. H. Hajivar and S. S. Mortazavi, “Impact of Shunt FACTS Devices on Security Constrained Unit
Commitment,” International Journal of Applied Power Engineering (IJAPE), vol. 5, no. 1, pp. 22-39, 2016.
[6] M. Joorabian and M. Saniei, “Optimal locating and sizing of TCPST for Congestion management in Deregulated
Electricity markets,” 46th International Universities’ Power Engineering Conference (UPEC), pp. 1-6, 2011.
[7] Florida Reliability Coordinating Council, “FRCC Regional under Frequency Load Shedding (UFLS)
Implementation Schedule,” FRCC handbook, 2011.
[8] Tang J., et al., “Adaptive load shedding based on combined frequency and voltage stability assessment using
synchrophasor measurements,” IEEE Transactions on Power Systems, vol. 28, no. 2, pp. 2035-2047, 2013.
[9] L. Sigrist, “A UFLS Scheme for Small Isolated Power Systems Using Rate-of-Change of Frequency,” IEEE
Transactions on Power Systems, vol. 30, no. 4, pp. 2192-2193, 2015.
[10] G. Kabashi and S. Kabashi, “Review of under Frequency Load Shedding Program of Kosovo Power System based
on ENTSO-E Requirements,” International Journal of Electrical and Computer Engineering (IJECE), vol. 8, no. 2,
pp. 741-748, 2018.
[11] El-Sadek M. Z., “Preventive measures for voltage collapses and voltage failures in the Egyptian power system,”
Electric Power Systems Reserach, vol. 44, no. 3, pp. 203-211, 1998.
[12] T. Amraee, et al., “Probabilistic Under Frequency Load Shedding Considering RoCoF Relays of Distributed
Generators,” IEEE Transactions on Power Systems, vol. 33, pp. 3587-3598, 2018.
[13] V. V. Terzija, “Adaptive Under Frequency Load Shedding Based on the Magnitude of the Disturbance Estimation,”
IEEE Transactions on Power Systems, vol. 21, no. 3, pp. 1260-1266, 2006.
[14] T. Amraee, et al., “An Improved Model for Optimal Under Voltage Load Shedding, Particle Swarm Approach,”
IEEE Power India Conference, 2006.
[15] L. T. Nghia, et al., “A voltage electrical distance application for power system load shedding considering the
primary and secondary generator controls,” International Journal of Electrical and Computer Engineering
(IJECE), vol. 9, no. 5, pp. 3993-4002, 2019.
[16] P. Kundur, “Power stem Stability and Control,” McGraw-Hill, 1994.
[17] S. Weckx, et al., “Primary and Secondary Frequency Support by a Multi-Agent Demand Control System,” IEEE
Transactions on Power Systems, vol. 30, no. 3, pp. 1394-1404, 2015.
[18] C. R. Balamurugan, “Three Area Power System Load Frequency Control Using Fuzzy Logic Controller,”
International Journal of Applied Power Engineering (IJAPE), vol. 7, no. 1, pp. 18-26, 2018.
[19] A. J. Wood, et al., “Power Generation, Operation and Control,” Third Edition, John Wiley & Sons, Inc,
pp. 473-481, 2014.
[20] L. Patrick, “The different electrical distance,” in Proceedings of the Tenth Power Systems Computation Conference,
Graz, 1990.
[21] P. Cuffe and A. Keane, “Visualizing the Electrical Structure of Power Systems,” IEEE Systems Journal, vol. 11,
no. 3, pp. 1810-1821, 2017.
[22] T. Greville, “Some applications of the pseudoinverse of a matrix,” SIAM Review, vol. 2, no. 1, pp. 15-22, 1960.
[23] E. Cotilla-Sanchez, et al., “Multi-attribute partitioning of power networks based on electrical distance,” IEEE
Transactions on Power Systems, vol. 28, no. 4, pp. 4979-4987, 2013.
Int J Elec & Comp Eng ISSN: 2088-8708 
Minimize the load reduction considering the activities control of ... (Le Trong Nghia)
1001
[24] D. J. Klein and M. Randi´c, “Resistance distance,” Journal of Mathematical Chemistry, vol. 12, no. 1, pp. 81-95,
1993.
[25] J. D. Glover, et al., “Power System Analysis and Design,” Sixth Edition, Cengage Learning, 2017, pp. 1-718.
BIOGRAPHIES OF AUTHORS
Trong Nghia Le achieved M.Sc degree from HCMUTE, Vietnam, 2012. Currently, Mr. Nghia
is a lecturer at the HCMUTE. His interested fields are load shedding, system identification, and
low voltage system.
Quyen Huy Anh achieved PhD degree in power system from MPIE, Russia, 1993. Currently,
professor Anh is lecturer at the Electrical and Electronic Engineering Department, HCMUTE.
His interested fields are modeling and simulation electrical system, dynamic stability, load
reduction, electrical system in building, lightning system, and AI.
Phan Thi Thanh Binh achieved Ph.D. degree from Kiev Polytechnique University, Ukraine in
1995. Currently, professor Binh is a lecturer at the Electrical and Electronic Engineering
Department, HCMUT. Her interested fields are Microgrid, Optimal generator dispatch, data
mining, and load forecasting.
Phung Trieu Tan achieved his M.Sc. from HCMUTE, Vietnam, 2018. Currently, Mr. Tan is
lecturer at CaoThang colleges. His main areas of research interests are artificial neural network,
load shedding in power systems, Microgrid, and load forecasting and power supply system.

More Related Content

What's hot

Optimized coordinated economic dispatch and automatic generation control for ...
Optimized coordinated economic dispatch and automatic generation control for ...Optimized coordinated economic dispatch and automatic generation control for ...
Optimized coordinated economic dispatch and automatic generation control for ...
SANJAY SHARMA
 

What's hot (20)

0178__Waseda__HCMUT
0178__Waseda__HCMUT0178__Waseda__HCMUT
0178__Waseda__HCMUT
 
Ib2615731577
Ib2615731577Ib2615731577
Ib2615731577
 
IRJET- An Investigative Study of Generator-Load Tie-Line Model of Speed Gover...
IRJET- An Investigative Study of Generator-Load Tie-Line Model of Speed Gover...IRJET- An Investigative Study of Generator-Load Tie-Line Model of Speed Gover...
IRJET- An Investigative Study of Generator-Load Tie-Line Model of Speed Gover...
 
Performance analysis and simulation of solar pv wind hybrid energy system wit...
Performance analysis and simulation of solar pv wind hybrid energy system wit...Performance analysis and simulation of solar pv wind hybrid energy system wit...
Performance analysis and simulation of solar pv wind hybrid energy system wit...
 
Neural Network Based Voltage and Frequency Controller for standalone Wind Pow...
Neural Network Based Voltage and Frequency Controller for standalone Wind Pow...Neural Network Based Voltage and Frequency Controller for standalone Wind Pow...
Neural Network Based Voltage and Frequency Controller for standalone Wind Pow...
 
Optimized coordinated economic dispatch and automatic generation control for ...
Optimized coordinated economic dispatch and automatic generation control for ...Optimized coordinated economic dispatch and automatic generation control for ...
Optimized coordinated economic dispatch and automatic generation control for ...
 
Chapter 2 automatic_load_frequency_contr
Chapter 2 automatic_load_frequency_contrChapter 2 automatic_load_frequency_contr
Chapter 2 automatic_load_frequency_contr
 
Load Frequency Control of DFIG-isolated and Grid Connected Mode
Load Frequency Control of DFIG-isolated and Grid Connected ModeLoad Frequency Control of DFIG-isolated and Grid Connected Mode
Load Frequency Control of DFIG-isolated and Grid Connected Mode
 
Maximum Power Point Tracker Using Fuzzy Logic Controller with Reduced Rules
Maximum Power Point Tracker Using Fuzzy Logic Controller with Reduced RulesMaximum Power Point Tracker Using Fuzzy Logic Controller with Reduced Rules
Maximum Power Point Tracker Using Fuzzy Logic Controller with Reduced Rules
 
Nonlinear control for an optimized grid connection system of renewable energy...
Nonlinear control for an optimized grid connection system of renewable energy...Nonlinear control for an optimized grid connection system of renewable energy...
Nonlinear control for an optimized grid connection system of renewable energy...
 
Automatic Generation Control
Automatic Generation ControlAutomatic Generation Control
Automatic Generation Control
 
D027026030
D027026030D027026030
D027026030
 
Dynamic responses improvement of grid connected wpgs using flc in high wind s...
Dynamic responses improvement of grid connected wpgs using flc in high wind s...Dynamic responses improvement of grid connected wpgs using flc in high wind s...
Dynamic responses improvement of grid connected wpgs using flc in high wind s...
 
Australia 1
Australia 1Australia 1
Australia 1
 
Fuzzy and predictive control of a photovoltaic pumping system based on three-...
Fuzzy and predictive control of a photovoltaic pumping system based on three-...Fuzzy and predictive control of a photovoltaic pumping system based on three-...
Fuzzy and predictive control of a photovoltaic pumping system based on three-...
 
Wind Energy Conversion Based On Matrix Converter
Wind Energy Conversion Based On Matrix ConverterWind Energy Conversion Based On Matrix Converter
Wind Energy Conversion Based On Matrix Converter
 
Bc35306309
Bc35306309Bc35306309
Bc35306309
 
A Lyapunov Based Approach to Enchance Wind Turbine Stability
A Lyapunov Based Approach to Enchance Wind Turbine StabilityA Lyapunov Based Approach to Enchance Wind Turbine Stability
A Lyapunov Based Approach to Enchance Wind Turbine Stability
 
R04601113118
R04601113118R04601113118
R04601113118
 
A Simplified Design and Modeling of Boost Converter for Photovoltaic Sytem
A Simplified Design and Modeling of Boost Converter for Photovoltaic Sytem A Simplified Design and Modeling of Boost Converter for Photovoltaic Sytem
A Simplified Design and Modeling of Boost Converter for Photovoltaic Sytem
 

Similar to Minimize the load reduction considering the activities control of the generators and phase distance

11.modeling and performance analysis of a small scale direct driven pmsg base...
11.modeling and performance analysis of a small scale direct driven pmsg base...11.modeling and performance analysis of a small scale direct driven pmsg base...
11.modeling and performance analysis of a small scale direct driven pmsg base...
Alexander Decker
 

Similar to Minimize the load reduction considering the activities control of the generators and phase distance (20)

Combinational load shedding using load frequency control and voltage stabili...
Combinational load shedding using load frequency control and  voltage stabili...Combinational load shedding using load frequency control and  voltage stabili...
Combinational load shedding using load frequency control and voltage stabili...
 
A017150107
A017150107A017150107
A017150107
 
DYNAMIC RESPONSES IMPROVEMENT OF GRID CONNECTED WPGS USING FLC IN HIGH WIND S...
DYNAMIC RESPONSES IMPROVEMENT OF GRID CONNECTED WPGS USING FLC IN HIGH WIND S...DYNAMIC RESPONSES IMPROVEMENT OF GRID CONNECTED WPGS USING FLC IN HIGH WIND S...
DYNAMIC RESPONSES IMPROVEMENT OF GRID CONNECTED WPGS USING FLC IN HIGH WIND S...
 
Grid-Connected Pv-Fc Hybrid System Power Control Using Mppt And Boost Converter
Grid-Connected Pv-Fc Hybrid System Power Control Using Mppt And Boost ConverterGrid-Connected Pv-Fc Hybrid System Power Control Using Mppt And Boost Converter
Grid-Connected Pv-Fc Hybrid System Power Control Using Mppt And Boost Converter
 
4.power quality improvement in dg system using shunt active filter
4.power quality improvement in dg system using shunt active filter4.power quality improvement in dg system using shunt active filter
4.power quality improvement in dg system using shunt active filter
 
Solar energy based impedance-source inverter for grid system
Solar energy based impedance-source inverter for grid systemSolar energy based impedance-source inverter for grid system
Solar energy based impedance-source inverter for grid system
 
New PQ Controller for Interconnected Microgrids
New PQ Controller for Interconnected MicrogridsNew PQ Controller for Interconnected Microgrids
New PQ Controller for Interconnected Microgrids
 
11.modeling and performance analysis of a small scale direct driven pmsg base...
11.modeling and performance analysis of a small scale direct driven pmsg base...11.modeling and performance analysis of a small scale direct driven pmsg base...
11.modeling and performance analysis of a small scale direct driven pmsg base...
 
Modeling and performance analysis of a small scale direct driven pmsg based w...
Modeling and performance analysis of a small scale direct driven pmsg based w...Modeling and performance analysis of a small scale direct driven pmsg based w...
Modeling and performance analysis of a small scale direct driven pmsg based w...
 
Control of PMSG based variable speed wind energy conversion system connected ...
Control of PMSG based variable speed wind energy conversion system connected ...Control of PMSG based variable speed wind energy conversion system connected ...
Control of PMSG based variable speed wind energy conversion system connected ...
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
 
Self-Regulation of the Project Great Inga for an Interconnected Electrical Ne...
Self-Regulation of the Project Great Inga for an Interconnected Electrical Ne...Self-Regulation of the Project Great Inga for an Interconnected Electrical Ne...
Self-Regulation of the Project Great Inga for an Interconnected Electrical Ne...
 
Enhanced decoupled current control with voltage compensation for modular mult...
Enhanced decoupled current control with voltage compensation for modular mult...Enhanced decoupled current control with voltage compensation for modular mult...
Enhanced decoupled current control with voltage compensation for modular mult...
 
Performance analysis and enhancement of direct power control of DFIG based wi...
Performance analysis and enhancement of direct power control of DFIG based wi...Performance analysis and enhancement of direct power control of DFIG based wi...
Performance analysis and enhancement of direct power control of DFIG based wi...
 
LOAD FREQUENCY CONTROL USING ELECTRIC VEICHLE SYSTEM IN INTERCONNECTED POWER ...
LOAD FREQUENCY CONTROL USING ELECTRIC VEICHLE SYSTEM IN INTERCONNECTED POWER ...LOAD FREQUENCY CONTROL USING ELECTRIC VEICHLE SYSTEM IN INTERCONNECTED POWER ...
LOAD FREQUENCY CONTROL USING ELECTRIC VEICHLE SYSTEM IN INTERCONNECTED POWER ...
 
ipec_hai
ipec_haiipec_hai
ipec_hai
 
Artificial neural network based unity power factor corrector for single phas...
Artificial neural network based unity power factor corrector  for single phas...Artificial neural network based unity power factor corrector  for single phas...
Artificial neural network based unity power factor corrector for single phas...
 
Indian journal 3
Indian journal 3Indian journal 3
Indian journal 3
 
Analysis of fuzzy logic controller based bi-directional DC-DC converter for b...
Analysis of fuzzy logic controller based bi-directional DC-DC converter for b...Analysis of fuzzy logic controller based bi-directional DC-DC converter for b...
Analysis of fuzzy logic controller based bi-directional DC-DC converter for b...
 
LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEMLOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
 

More from IJECEIAES

Predicting churn with filter-based techniques and deep learning
Predicting churn with filter-based techniques and deep learningPredicting churn with filter-based techniques and deep learning
Predicting churn with filter-based techniques and deep learning
IJECEIAES
 
Automatic customer review summarization using deep learningbased hybrid senti...
Automatic customer review summarization using deep learningbased hybrid senti...Automatic customer review summarization using deep learningbased hybrid senti...
Automatic customer review summarization using deep learningbased hybrid senti...
IJECEIAES
 
Situational judgment test measures administrator computational thinking with ...
Situational judgment test measures administrator computational thinking with ...Situational judgment test measures administrator computational thinking with ...
Situational judgment test measures administrator computational thinking with ...
IJECEIAES
 
Hand LightWeightNet: an optimized hand pose estimation for interactive mobile...
Hand LightWeightNet: an optimized hand pose estimation for interactive mobile...Hand LightWeightNet: an optimized hand pose estimation for interactive mobile...
Hand LightWeightNet: an optimized hand pose estimation for interactive mobile...
IJECEIAES
 
Application of deep learning methods for automated analysis of retinal struct...
Application of deep learning methods for automated analysis of retinal struct...Application of deep learning methods for automated analysis of retinal struct...
Application of deep learning methods for automated analysis of retinal struct...
IJECEIAES
 
Predictive modeling for breast cancer based on machine learning algorithms an...
Predictive modeling for breast cancer based on machine learning algorithms an...Predictive modeling for breast cancer based on machine learning algorithms an...
Predictive modeling for breast cancer based on machine learning algorithms an...
IJECEIAES
 

More from IJECEIAES (20)

Predicting churn with filter-based techniques and deep learning
Predicting churn with filter-based techniques and deep learningPredicting churn with filter-based techniques and deep learning
Predicting churn with filter-based techniques and deep learning
 
Taxi-out time prediction at Mohammed V Casablanca Airport
Taxi-out time prediction at Mohammed V Casablanca AirportTaxi-out time prediction at Mohammed V Casablanca Airport
Taxi-out time prediction at Mohammed V Casablanca Airport
 
Automatic customer review summarization using deep learningbased hybrid senti...
Automatic customer review summarization using deep learningbased hybrid senti...Automatic customer review summarization using deep learningbased hybrid senti...
Automatic customer review summarization using deep learningbased hybrid senti...
 
Ataxic person prediction using feature optimized based on machine learning model
Ataxic person prediction using feature optimized based on machine learning modelAtaxic person prediction using feature optimized based on machine learning model
Ataxic person prediction using feature optimized based on machine learning model
 
Situational judgment test measures administrator computational thinking with ...
Situational judgment test measures administrator computational thinking with ...Situational judgment test measures administrator computational thinking with ...
Situational judgment test measures administrator computational thinking with ...
 
Hand LightWeightNet: an optimized hand pose estimation for interactive mobile...
Hand LightWeightNet: an optimized hand pose estimation for interactive mobile...Hand LightWeightNet: an optimized hand pose estimation for interactive mobile...
Hand LightWeightNet: an optimized hand pose estimation for interactive mobile...
 
An overlapping conscious relief-based feature subset selection method
An overlapping conscious relief-based feature subset selection methodAn overlapping conscious relief-based feature subset selection method
An overlapping conscious relief-based feature subset selection method
 
Recognition of music symbol notation using convolutional neural network
Recognition of music symbol notation using convolutional neural networkRecognition of music symbol notation using convolutional neural network
Recognition of music symbol notation using convolutional neural network
 
A simplified classification computational model of opinion mining using deep ...
A simplified classification computational model of opinion mining using deep ...A simplified classification computational model of opinion mining using deep ...
A simplified classification computational model of opinion mining using deep ...
 
An efficient convolutional neural network-extreme gradient boosting hybrid de...
An efficient convolutional neural network-extreme gradient boosting hybrid de...An efficient convolutional neural network-extreme gradient boosting hybrid de...
An efficient convolutional neural network-extreme gradient boosting hybrid de...
 
Generating images using generative adversarial networks based on text descrip...
Generating images using generative adversarial networks based on text descrip...Generating images using generative adversarial networks based on text descrip...
Generating images using generative adversarial networks based on text descrip...
 
Collusion-resistant multiparty data sharing in social networks
Collusion-resistant multiparty data sharing in social networksCollusion-resistant multiparty data sharing in social networks
Collusion-resistant multiparty data sharing in social networks
 
Application of deep learning methods for automated analysis of retinal struct...
Application of deep learning methods for automated analysis of retinal struct...Application of deep learning methods for automated analysis of retinal struct...
Application of deep learning methods for automated analysis of retinal struct...
 
Proposal of a similarity measure for unified modeling language class diagram ...
Proposal of a similarity measure for unified modeling language class diagram ...Proposal of a similarity measure for unified modeling language class diagram ...
Proposal of a similarity measure for unified modeling language class diagram ...
 
Efficient criticality oriented service brokering policy in cloud datacenters
Efficient criticality oriented service brokering policy in cloud datacentersEfficient criticality oriented service brokering policy in cloud datacenters
Efficient criticality oriented service brokering policy in cloud datacenters
 
System call frequency analysis-based generative adversarial network model for...
System call frequency analysis-based generative adversarial network model for...System call frequency analysis-based generative adversarial network model for...
System call frequency analysis-based generative adversarial network model for...
 
Comparison of Iris dataset classification with Gaussian naïve Bayes and decis...
Comparison of Iris dataset classification with Gaussian naïve Bayes and decis...Comparison of Iris dataset classification with Gaussian naïve Bayes and decis...
Comparison of Iris dataset classification with Gaussian naïve Bayes and decis...
 
Efficient intelligent crawler for hamming distance based on prioritization of...
Efficient intelligent crawler for hamming distance based on prioritization of...Efficient intelligent crawler for hamming distance based on prioritization of...
Efficient intelligent crawler for hamming distance based on prioritization of...
 
Predictive modeling for breast cancer based on machine learning algorithms an...
Predictive modeling for breast cancer based on machine learning algorithms an...Predictive modeling for breast cancer based on machine learning algorithms an...
Predictive modeling for breast cancer based on machine learning algorithms an...
 
An algorithm for decomposing variations of 3D model
An algorithm for decomposing variations of 3D modelAn algorithm for decomposing variations of 3D model
An algorithm for decomposing variations of 3D model
 

Recently uploaded

Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
ankushspencer015
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Christo Ananth
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Dr.Costas Sachpazis
 

Recently uploaded (20)

PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
Vivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design SpainVivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design Spain
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 

Minimize the load reduction considering the activities control of the generators and phase distance

  • 1. International Journal of Electrical and Computer Engineering (IJECE) Vol. 11, No. 2, April 2021, pp. 993~1001 ISSN: 2088-8708, DOI: 10.11591/ijece.v11i2.pp993-1001  993 Journal homepage: http://ijece.iaescore.com Minimize the load reduction considering the activities control of the generators and phase distance Le Trong Nghia1 , Quyen Huy Anh2 , Phan Thi Thanh Binh3 , Phung Trieu Tan4 1,2 HCMC University of Technology and Education, Vietnam 3 HCMC University of Technology, Vietnam 4 CaoThang Technical College, Vietnam Article Info ABSTRACT Article history: Received Feb 28, 2020 Revised Jun 14, 2020 Accepted Jun 29, 2020 This study shows how to calculate the minimum load that needs to be reduced to restore the frequency to the specified threshold. To implement this problem, the actual operation of the electricity system in the event of a generator outage is considered. The main idea of this method is to use the power balance equation between the generation and the load with different frequency levels. In all cases of operating the electrical system before and after the generator outage, the reserve capacity of other generators is considered in each generator outage situation. The reduced load capacity is calculated based on the reciprocal phase angle sensitivity or phase distance. This makes the voltage phase angle and voltage value quality of recovery nodes better. The standard IEEE 9-generator 37-bus test scheme was simulated to show the result of the proposed technique. Keywords: Frequency control Generator control Load shedding Phase electrical distance This is an open access article under the CC BY-SA license. Corresponding Author: Trong Nghia Le HCMC University of Technology and Education Hochiminh city, Vietnam Email: trongnghia@hcmute.edu.vn 1. INTRODUCTION Generator outage is reason for the inequality of real power and frequency reduction in the electrical system. In some cases, this may blackout the system. In [1] presented a summary of the load shedding solutions implemented over the years. In [2-4] presented intelligent solutions to maintain electricity system stability. Besides the implementation of all control solutions, including the solutions using FACT equipment [5, 6] to maintain electrical system constraints, the load shedding is an undesirable action of electricity suppliers and also for electricity consumers because it has impacts on socio-economic impacts. However, this is an unavoidable case when other possible solutions are used to restore the frequency. What is needed here is to cut the load to reduce the consequences for electricity consumers and socio-economic. The design and calculation the amount of load shedding is a complex process, requiring large amounts of input data on incident situations that cause serious frequency attenuation. Conventional load-shedding methods typically use load shedding relays [7-11] with step-by-step load shedding that correspond to levels of frequency attenuation or df/dt [12]. Most of these methods, the power of load that need to be cut in the form of load shedding tables is built by the electrical system specialist. This may cause inadequate or excessive load shedding compared to the value required. Some of the current load shedding methods used the swing rotor equation and voltage electrical distance application [13-15] to estimate the load to be cut. They combined with knowledge technology algorithms to calculate the minimum economic losses. However, these methods have not considered the technical and operational factors of electricity system after power inequality.
  • 2.  ISSN: 2088-8708 Int J Elec & Comp Eng, Vol. 11, No. 2, April 2021 : 993 - 1001 994 In this article, a technique of calculating the load curtailment that takes into account generator control problems is appropriate for the actual operation of the electrical system such as: primary control issues, secondary control issues of generators. Furthermore, load reduction based on phase distance ensures that phase angle and frequency recover faster than traditional load shedding methods. 2. METHODOLOGY FOR RESEARCH 2.1. The frequency responds The ability to vary power according to frequency or the frequency stability ability of a turbine is determined by the drop of the speed control characteristic [16, 17]. Characteristics present the ability to adjust the turbine's power when the rotation speed changes are presented in Figure 1. The correlation is determined by equation: p f R PG    (1) where R is the speed or droop adjustment factor; p f  is the frequency change; PG  is the change in generator power. Variation of both power and frequency is determined by equation: . G p n G i n P f P R f     (2) where: is the rated power of the generators. The load in the electricity system is a diverse collection of different electrical equipment. The power can be either relied on the frequency (for instance the case of a motor load like fan or pump, the change in power and frequency leading to the change of motor speed) or not relied on the frequency (for instance resistive loads like lighting or heating). The power of the combined load can be expressed by the (3) [18, 19]: (3) where PL is the combined load component, PID is the frequency-independent load component, e.g. heat load, lighting… PD is the frequency-relied load component. The change correlation between the load power characteristics and frequency is shown in Figure 2. Figure 1. Correlation between generator power change and frequency change Figure 2. The change correlation between the load power characteristics and frequency The variation of load according to the frequency variation is shown in the following equation [18]: P P P L ID D    (4) P Gn P P P L ID D  
  • 3. Int J Elec & Comp Eng ISSN: 2088-8708  Minimize the load reduction considering the activities control of ... (Le Trong Nghia) 995 When the frequency is equal to the rated frequency fn, the required power of the load is the same as the actual consumed power PL0, when the frequency decreases from fn to f1, the actual power used decreases from PL0 to PL1. The correlation between the load variations and frequency variation is determined by equation: . . combined load f P P D D fn     (5) where ∆PD is the variation of load power according to frequency variation; D is the percentage variation of load according to the percentage frequency variation [16]; D value ranges from 1% to 2% and is determined by experimental methods on electricity systems. 2.2. Regulator activities the generators in accordance with the actual operation When the generator is failed, the frequency adjustment will start and include the following operations: primary regulating effects and secondary regulating effects. In case, at the end of this impact activity and the frequency is still below the permissible constrains, the next step will implement the load reduction. The objective is to restore the frequency to the required threshold value. These impact activities are indicated in Figure 3. In this figure, line (A) is the normal operating characteristic of the system; line (B) and (D) are the feature of generators without the governor; line (C) is the feature at the time the generator is disconnected; line (E) is the operating characteristic after the secondary regulating effects of the generator; line (F) and (G) are the load characteristics before and after implement the load reduction; the fpermit value is the frequency parameter achieved after the load reduction. Figure 3. Regulator activities the generators and load reduction 2.3. The minimum load reduction capacity Calculating minimum load reduction PLS min ensures restoration of electricity system frequency to the allowable value, minimizing damage to electricity consumers. The calculation includes the activity control of the generators in accordance with the actual operation. In a power system with n generators, when a generator outage, the primary regulating effects of the others (n-1) generators is made with the adjustment of the power with the below equation: 1 1 , Pr 1 1 . n n p Gn i i i i i f P P f R n           (6) The amount of power of the frequency-dependent load reduces the amount of ∆PD is shown in (5). Power balance status is presented in the following equation: (7) 1 1 Primary control 1 1 n n P P P P L D Gi i i          
  • 4.  ISSN: 2088-8708 Int J Elec & Comp Eng, Vol. 11, No. 2, April 2021 : 993 - 1001 996 1 1 , 1 1 . n n p Gn i G L D i i i i f P P P P f R n            (8) 1 1 , 1 1 . . n n p p Gn i G L L i i i i f f P P P P D f f R n n             (9) (10) Set and From (10) infer: (11) In the case of the considering secondary control power, the new power balance equation with the new frequency value f2, the (7) becomes: (12) Secondary control max , Primary control, j 1 ( ) k Gm j j P P P       (13) If frequency value after implement the secondary regulating effects is lower than tolerable rate, load reduction is required to restore frequency. The minimum load reduction PLSmin is considered by: (14) (15) 1 1 , secondary control max 1 1 . P . . min n n permit permit Gn i G L L i i i i f f P P P P D P LS f f R n n               (16) Equation (15) is abbreviated according to the following equation: secondary max . min permit L f P P P LS fn         (17) 2.4. The phase angle sensitivity or phase distance (PD) The reciprocal phase angle sensitivity or phase distance (PD) from the load reduction to disconnected generator is considered using the methods in [20-24], that is applied as procedure: - Calculate the Jacobian matrix from the power flow distribution according to Newton Raphson, and from there obtain the sub matrix J1 with 1 . P P J J             - Inverse matrix, 1 P J   - Calculate the PD between two bus i and j according to the formula [20, 21]: 1 1 , ( )( . ) 1 1 PG n n f n i P P P D L G L f R i i i n i           -1 - 1 n P P P L L Gi i     1 , . 1 PG n n i P D L R i i       . f PL fn     1 1 Primary control Secondary control max 1 1 n n P P P P P L D Gi i i            1 1 Primary control Secondary control max min 1 1 i n n L D G LS i i P P P P P P               1 1 min Primary control Secondary control max 1 1 n n P P P P P P LS L D Gi i i             
  • 5. Int J Elec & Comp Eng ISSN: 2088-8708  Minimize the load reduction considering the activities control of ... (Le Trong Nghia) 997 ( , ) j j i i PD i j j i D i j P P P P                 (18) The purpose of the delivery the load reduction at each buses is to restore the rotor angle deviation faster. The load near the generator outage will have a much reduced load. The formula for this delivery is given in the following: , min , . i PD eq LSi LS PD m D P P D  (19) , , 1 1 i PD eq i m PD m D D    (20) where , i PD m D is the phase space or distance from load reduction to i m disconnected generator; DPD,eq is the equivalent phase distance 3. SIMULATION AND RESULTS The PowerWorld simulator version 19 is used to set up the simulation background. The standard IEEE 9-generator 37-bus test system [25] is used to support simulation and calculation. This diagram is shown in Figure 4. The accepted frequency values are between 59.7 Hz and 60 Hz. Figure 4. The standard 9-generator 37-bus test system
  • 6.  ISSN: 2088-8708 Int J Elec & Comp Eng, Vol. 11, No. 2, April 2021 : 993 - 1001 998 In this study, the generator JO345#1 is disconnected from the grid. From (11), the frequency obtains 59.6 Hz. Therefore, it is necessary to implement the frequency adjustment action to restore frequency. This adjustment activity is done automatically. The reaction of the turbine governor is performed immediately after the generator JO345#1 is disconnected. The spinning standby power values of the others generators are presented in Table 1. Table 1. Parameter values and standby power of generators No Gen PG (MW) PG (pu) R Pri P  , G n P R 1 WEBER69 31.5 0.315 0.05 0.035 7 2 JO345#1 0 0 0.05 0 0 3 JO345#2 135 1.35 0.05 0.15 30 4 SLACK345 187.28 1.8728 0.05 0.22 44 5 LAUF69 135 1.35 0.05 0.15 30 6 BOB69 46 0.46 0.05 0.052 10.4 7 ROGER69 72 0.72 0.05 0.08 16 8 BLT138 126 1.26 0.05 0.14 28 9 BLT69 99 0.99 0.05 0.11 22 Total 831.78 8.3178 0.937 187.4 The standard IEEE 9-generator 37-bus test system, the SLACK 345 (SLACK Bus) is selected as the secondary frequency control generator. In this case, application (13) calculates the ability of secondary regulating effects of 10.72 MW. This frequency response following the others generators implement frequency adjustment is displayed at Figure 5. Figure 5. The frequency response after remaining generators implements frequency adjustment The frequency reaction displays that frequency value has not been reestablished to the permissible operating series. Applying (17) calculates the load to be cut or reduced to reestablish the frequency value to the required operating range. min Secondary control max 0 . cp LS L f P P P f         1 1 9,5394 8,31780 1,2216 i n L L G i P P P         
  • 7. Int J Elec & Comp Eng ISSN: 2088-8708  Minimize the load reduction considering the activities control of ... (Le Trong Nghia) 999 1 1 . 9,5394.0,02 187,4 187,59 n Gi L i i P P D R          min ( 0.3) 1,2216 .187,59 0,1072 0,1764 60 LS P pu       So, the minimum load shedding capacity of P Load shedding min is 17.64 MW. This value is distributed for each load according to the (19). The comparison of frequency response and rotor angle is shown in Figure 6 and Figure. It is marked that the suggested method is produced a lesser load reduction than the traditional load reduction method [4], in particular the load shedding number is reduced from 82.93 MW to 17.64 MW. The frequency response of the traditional load reduction method is better than the proposed method. Due to the traditional method, the load is reduced more than the proposed method of reducing the load. However, this value is acceptable because it is inside the suitable range of 59.7 Hz. The rotor deviation angle of both solutions is approximately equivalent. This has many positive implications in maintaining system stability. Figure 6. Frequency response of the offered load reduction and old load reduction method Figure 7. Rotor angle when applying the traditional and the proposed load reduction method
  • 8.  ISSN: 2088-8708 Int J Elec & Comp Eng, Vol. 11, No. 2, April 2021 : 993 - 1001 1000 4. CONCLUSION The consideration of the standby power of the generators has supported to calculate the load to be reduced in accordance with reality. This calculation makes the recovery frequency to an acceptable value. The calculation method takes into account the standby ability the generators, and the process of adjusting frequency of generator in the event of a power outage. Calculating the amount of load to disconnect causes damage to the lowest level for customers, important services when cutting load. The distribution of load shedding capacity based on Phase Electrical Distance makes the rotor deviation angle equivalent to UFLS method. This increases the stability of the system when a power outage occurs. ACKNOWLEDGEMENTS This work belongs to the project in 2020 funded by Ho Chi Minh City University of Technology and Education, Vietnam. REFERENCES [1] Raghu C. N. and A. Manjunatha, “Assessing Effectiveness of Research for Load Shedding in Power System,” International Journal of Electrical and Computer Engineering (IJECE), vol. 7, no. 6, pp. 3235-3245, 2017. [2] S. F. A. Shukor, et al., “Intelligent based technique for under voltage load shedding in power transmission systems,” Indonesian Journal of Electrical Engineering and Computer Science (IJEECS), vol. 17, no. 1, pp. 110-117, 2020. [3] S. M. Hossain and M. M. Hasan, “Energy Management through Bio-gas Based Electricity Generation System during Load Shedding in Rural Areas,” TELKOMNIKA Telecommunication Computing Electronics and Control, vol. 16, no. 2, pp. 525-532, 2018. [4] R. M. Larik, et al., “A statistical jacobian application for power system optimization of voltage stability,” Indonesian Journal of Electrical Engineering and Computer Science (IJEECS), vol. 13, no. 1, pp. 331-338, 2019. [5] G. A. M. H. Hajivar and S. S. Mortazavi, “Impact of Shunt FACTS Devices on Security Constrained Unit Commitment,” International Journal of Applied Power Engineering (IJAPE), vol. 5, no. 1, pp. 22-39, 2016. [6] M. Joorabian and M. Saniei, “Optimal locating and sizing of TCPST for Congestion management in Deregulated Electricity markets,” 46th International Universities’ Power Engineering Conference (UPEC), pp. 1-6, 2011. [7] Florida Reliability Coordinating Council, “FRCC Regional under Frequency Load Shedding (UFLS) Implementation Schedule,” FRCC handbook, 2011. [8] Tang J., et al., “Adaptive load shedding based on combined frequency and voltage stability assessment using synchrophasor measurements,” IEEE Transactions on Power Systems, vol. 28, no. 2, pp. 2035-2047, 2013. [9] L. Sigrist, “A UFLS Scheme for Small Isolated Power Systems Using Rate-of-Change of Frequency,” IEEE Transactions on Power Systems, vol. 30, no. 4, pp. 2192-2193, 2015. [10] G. Kabashi and S. Kabashi, “Review of under Frequency Load Shedding Program of Kosovo Power System based on ENTSO-E Requirements,” International Journal of Electrical and Computer Engineering (IJECE), vol. 8, no. 2, pp. 741-748, 2018. [11] El-Sadek M. Z., “Preventive measures for voltage collapses and voltage failures in the Egyptian power system,” Electric Power Systems Reserach, vol. 44, no. 3, pp. 203-211, 1998. [12] T. Amraee, et al., “Probabilistic Under Frequency Load Shedding Considering RoCoF Relays of Distributed Generators,” IEEE Transactions on Power Systems, vol. 33, pp. 3587-3598, 2018. [13] V. V. Terzija, “Adaptive Under Frequency Load Shedding Based on the Magnitude of the Disturbance Estimation,” IEEE Transactions on Power Systems, vol. 21, no. 3, pp. 1260-1266, 2006. [14] T. Amraee, et al., “An Improved Model for Optimal Under Voltage Load Shedding, Particle Swarm Approach,” IEEE Power India Conference, 2006. [15] L. T. Nghia, et al., “A voltage electrical distance application for power system load shedding considering the primary and secondary generator controls,” International Journal of Electrical and Computer Engineering (IJECE), vol. 9, no. 5, pp. 3993-4002, 2019. [16] P. Kundur, “Power stem Stability and Control,” McGraw-Hill, 1994. [17] S. Weckx, et al., “Primary and Secondary Frequency Support by a Multi-Agent Demand Control System,” IEEE Transactions on Power Systems, vol. 30, no. 3, pp. 1394-1404, 2015. [18] C. R. Balamurugan, “Three Area Power System Load Frequency Control Using Fuzzy Logic Controller,” International Journal of Applied Power Engineering (IJAPE), vol. 7, no. 1, pp. 18-26, 2018. [19] A. J. Wood, et al., “Power Generation, Operation and Control,” Third Edition, John Wiley & Sons, Inc, pp. 473-481, 2014. [20] L. Patrick, “The different electrical distance,” in Proceedings of the Tenth Power Systems Computation Conference, Graz, 1990. [21] P. Cuffe and A. Keane, “Visualizing the Electrical Structure of Power Systems,” IEEE Systems Journal, vol. 11, no. 3, pp. 1810-1821, 2017. [22] T. Greville, “Some applications of the pseudoinverse of a matrix,” SIAM Review, vol. 2, no. 1, pp. 15-22, 1960. [23] E. Cotilla-Sanchez, et al., “Multi-attribute partitioning of power networks based on electrical distance,” IEEE Transactions on Power Systems, vol. 28, no. 4, pp. 4979-4987, 2013.
  • 9. Int J Elec & Comp Eng ISSN: 2088-8708  Minimize the load reduction considering the activities control of ... (Le Trong Nghia) 1001 [24] D. J. Klein and M. Randi´c, “Resistance distance,” Journal of Mathematical Chemistry, vol. 12, no. 1, pp. 81-95, 1993. [25] J. D. Glover, et al., “Power System Analysis and Design,” Sixth Edition, Cengage Learning, 2017, pp. 1-718. BIOGRAPHIES OF AUTHORS Trong Nghia Le achieved M.Sc degree from HCMUTE, Vietnam, 2012. Currently, Mr. Nghia is a lecturer at the HCMUTE. His interested fields are load shedding, system identification, and low voltage system. Quyen Huy Anh achieved PhD degree in power system from MPIE, Russia, 1993. Currently, professor Anh is lecturer at the Electrical and Electronic Engineering Department, HCMUTE. His interested fields are modeling and simulation electrical system, dynamic stability, load reduction, electrical system in building, lightning system, and AI. Phan Thi Thanh Binh achieved Ph.D. degree from Kiev Polytechnique University, Ukraine in 1995. Currently, professor Binh is a lecturer at the Electrical and Electronic Engineering Department, HCMUT. Her interested fields are Microgrid, Optimal generator dispatch, data mining, and load forecasting. Phung Trieu Tan achieved his M.Sc. from HCMUTE, Vietnam, 2018. Currently, Mr. Tan is lecturer at CaoThang colleges. His main areas of research interests are artificial neural network, load shedding in power systems, Microgrid, and load forecasting and power supply system.