3. +
+
++
++= sdqs
sdq
sdqssdq j
dt
d
IRV ψω
ψ
(9)
Idr
+
= Idr
+
+ + Idr
+
- = Idr
+
+ + Idr
-
- e-j2Ȧst
. [6;7;8] (10)
Iqr
+
= Iqr
+
+ + Iqr
+
- = Iqr
+
+ + Iqr
-
- e-j2Ȧst
. [6;7;8] (11)
Active and reactive power of stator:
Ps +
+
= (3/2).(Vds
+
+ids+
+
- Vqs+
+
iqs+
+
) (12)
Qs +
+
= (3/2).(Vds
+
+iqs+
+
- Vqs+
+
ids+
+
) (13)
Figure 5. Relationships between (Į,ȕ)s, (Į,ȕ)r and dq+ and dqí reference
frames [6].
PI-Fuzzy controllers as shown in figure 6 are used to
control the errors between the required and actual values of
both the active power and reactive power delivered to the grid
by the generator. The parameters of the PI-Fuzzy are adjusted
by the fuzzy rules to obtain the best output to drive the errors
to zero. The variable parameters of the controllers, which are
fixed in traditional PI controllers, will help to achieve the best
performance of the system. The outputs of these controllers
are commanded values of d-q components of rotor current in
the stator flux oriented reference frame. These commanded
values of currents are used to regulate the RSC for provision
of the rotor phase voltage to DFIG.
Figure 6: PI-Fuzzy controller.
The fuzzy rules for parameters of PI-FUZZY
controllers are presented in table 1 and table 2. The rules are
developed by trial and error method. LN, SN, ZE, SP, and LP
represents large negative, small negative, zero, small positive,
large positive. S, M, H are for small, medium, high.
TABLE I: RULE BASE OF KP [5]
TABLE II: RULE BASE OF TI [5]
The triangular membership functions of inputs and
outputs of PI-Fuzzy controller are shown in figures 7 and 8:
Figure 7: Membership functions of two inputs of fuzzy block.
Figure 8: Membership functions of two outputs of fuzzy block.
157
4. 4. SIMULATION AND RESULTS
Simulation of proposed control method’s
implementation for 2.3 MW DFIG is carried out, table 3. The
grid voltage unbalance happens after 35 seconds, the
commanded values of reactive power and active power change
at 50s and 60s respectively. Comparisons of average values of
active and reactive powers in steady state with different
controllers are presented in table 4 and 5. Both actual values
and percentage of references are shown. Average
electromagnetic torque of the generator is shown in table 6.
TABLE III : PARAMETERS OF DFIG 2.3MW
The randomly variable wind speed is shown in figure
9 and figure 10 is grid unbalance at 35s.
Figure 9: Random variation of wind speed.
29.95 29.96 29.97 29.98 29.99 30 30.01 30.02 30.03 30.04 30.05
-800
-600
-400
-200
0
200
400
600
800
Time [s]
Vabcs[V]
Figure 10: The grid voltage unbalance happens after 35 seconds.
TABLE IV: AVERAGE VALUE OF PS IN STEADY STATE FOR 3
CONTROLLERS.
%)(%)(
Psref
PsrefP
Deviation
−
=
During unbalanced voltage
Lowest value of PMax: DPC with Notch Filter (5%)
Highest value of PMin: DPC with Notch Filter (-4,2%)
TABLE V: AVERAGE VALUE OF QS IN STEADY
STATE FOR 3 CONTROLLER.
%)(%)(
Qsref
QsrefQ
Deviation
−
=
During unbalanced voltage
Lowest value of QMax : DPC with Notch Filter (5.7%)
Highest value of QMin : DPC with Notch Filter (-10.9%)
TABLE VI: AVERAGE VALUE OF GENERATOR’S TORQUE IN
STEADY STATE FOR THE 3 CONTROLLERS.
During unbalanced voltage
Lowest value of TeMax: SFOC with Notch Filter (15899 N.m)
Highest value of TeMin: SFOC with Notch Filter (10195 N.m)
The simulation results with different controllers are
shown in figures 11 to 16 for active and reactive output power
respectively. These figures demonstrate the power responses
when voltage unbalance happens and when the commanded
158
5. values of powers change under voltage unbalance. Torque
response of the generator is shown in figure 17.
20 30 40
1.8
2
2.2
2.3
DPC WITHOUT NOTCH FILTER
Time [s]
20 30 40
1.8
2
2.2
2.3
SFOC WITH PI+F& NOTCH FILTER
Time [s]
20 30 40
1.8
2
2.2
2.3
Time [s]
Ps[MW]
DPC WITH NOTCH FILTER
Figure 11: Active output power of DFIG when voltage unbalances happen.
20 40 60
0.8
1.1
1.4
1.7
2
2.3
DPC WITHOUT NOTCH FILTER
Time [s]
20 40 60
0.8
1.1
1.4
1.7
2
2.3
SFOC WITH PI+F& NOTCH FILTER
Time [s]
20 40 60
0.8
1.1
1.4
1.7
2
2.3
Time [s]
Ps[MW]
DPC WITH NOTCH FILTER
Figure 12: Active output power of DFIG during the transient states.
49.5 50 50.5
0.8
1.1
1.4
1.7
2
2.3
DPC WITHOUT NOTCH FILTER
Time [s]
49.5 50 50.5
0.8
1.1
1.4
1.7
2
2.3
SFOC WITH PI+F& NOTCH FILTER
Time [s]
49.5 50 50.5
0.8
1.1
1.4
1.7
2
2.3
Time [s]
Ps[MW]
DPC WITH NOTCH FILTER
Figure 13: Dynamic responses of DFIG’s active output power during the
change of commanded value.
20 30 40
0.8
0.9
1
1.1
1.2
Time [s]
Qs[MVAR]
DPC WITH NOTCH FILTER
20 30 40
0.8
0.9
1
1.1
1.2
DPC WITHOUT NOTCH FILTER
Time [s]
20 30 40
0.8
0.9
1
1.1
1.2
SFOC WITH PI+F&NOTCH FILTER
Time [s]
Figure 14: Reactive output power of DFIG when voltage unbalances happen.
20 40 60
.7
1
1.3
1.6
1.9
2.2
Time [s]
Qs[MVAR]
DPC WITH NOTCH FILTER
20 40 60
0.7
1
1.3
1.6
1.9
2.2
DPC WITHOUT NOTCH FILTER
Time [s]
20 40 60
.07
1
1.2
1.6
1.9
2.2
SFOC WITH PI+F&NOTCH FILTER
Time [s]
Figure 15: Reactive output power of DFIG during transient states.
49.5 50 50.5
.7
1
1.3
1.6
1.9
2.2
Time [s]
Qs[MVAR]
DPC WITH NOTCH FILTER
49.5 50 50.5
0.7
1
1.3
1.6
1.9
2.2
DPC WITHOUT NOTCH FILTER
Time [s]
49.5 50 50.5
.07
1
1.2
1.6
1.9
2.2
SFOC WITH PI+F&NOTCH FILTER
Time [s]
Figure 16: Dynamic responses of DFIG’s reactive power during the change of
commanded value.
20 40 60 80
0
3
6
9
12
15
18
20
Time [s]
Te[KN.m]
DPC WITH NOTCH FILTER
20 40 60 80
0
3
6
9
12
15
18
20
DPC WITHOUT NOTCH FILTER
Time [s]
20 40 60 80
0
3
6
9
12
15
18
20
FOC WITH PI+F& NOTCH FILTER
Time [s]
Figure 17: Torque of DFIG
5. DISCUSSION
DPC has shown good steady state active power responses
during the voltage balance and unbalance as shown in table 4. The
deviation of the mean value of active power from the reference value
is almost zero percent with the inclusion of Notch filter. SFOC is also
giving good performance with small deviation (about 1%). The
fluctuation of active power is smallest for DPC with Notch filter
during the unbalance.
Steady state responses of reactive power are also very good
when Notch filters are included. The deviations are 0% and 0.3%
respectively for DPC and SFOC. The deviation is much higher
without Notch filter during the voltage unbalance as shown in table 5.
159
6. There is no significant difference observed between the responses
during the voltage balance, with or without Notch filters. The
fluctuation is observed to be smallest for DPC with Notch filter.
SFOC however gives smallest torque variation during voltage
unbalance as shown in table 6.
The results obtained in table 4 are further demonstrated in
figure 11. SFOC’s active power response when voltage unbalance
happens has higher ripples while the responses obtained with the two
DPC schemes are not significantly distorted. The responses to change
in the commanded values during the unbalance are good for the three
control scheme as shown in figure 12. DPC schemes give faster
responses as shown in figure 13.
Higher ripples are also observed in reactive power
responses of SFOC when voltage unbalance occurs as shown in
figure 14. The observation is consistent with statistics presented in
table 5. Reactive powers in the three control scheme follow the
commanded values under the condition of voltage unbalance as
shown in figure 15. Time responses of reactive power in DPC control
schemes are also less than SFOC’s one as shown in figure 16.
Torque responses observed in figure 17 are also consistent
with the statistics shown in table 6.
6. CONCLUSION
The proposed SFOC scheme for DFIG with the inclusion of
PI-Fuzzy controllers and Notch filters has improved the stability of
independent control of active and reactive power during grid voltage
unbalance. The responses of active and reactive power are compared
with a traditional DPC and modified DPC using Notch filters to
increase the stability. The observations are made during the
occurrence of voltage dip in one phase, transient states as well steady
states of the powers under unbalanced condition. In all the
observations, the independent control of the powers are maintained
for the proposed scheme.
However, high fluctuations in active and reactive powers
are present in the responses obtained with the proposed scheme.
Although lower ripples are observed for generator’s torque.
Experimental verification of the new control scheme should
be carried out to validate the results obtained with simulation.
7. REFERENCES
[1] Ackermann, T. (2003), Wind power in power systems, John Wiley and
Sons, USA.
[2] Leonhard, W. (2001), Control of electric drives, Springer-Verlag, 3rd
edition, USA.
[3] Muljadi, E., Yildirim, D., Batan, T., and Butterfield, C.P. (1999),
“Understand the unbalanced-voltage problem in wind turbine generation”,
Proceeding of IEEE Industry Application Conference, Phoenix, USA,
pp.1359-1365.
[4]. Baggu, M. M. (2009); “Advanced control techniques for doubly fed
induction generator – based wind turbine converters to improve low voltage
ride- throught during system imbalances”, PhD Thesis, Missouri University of
Science and Technology.
[5]. Pham-Dinh, T., Pham-Trung, H., Le-Thanh, H. (2011), “PI-Fuzzy
Controller for Doubly Fed Induction Generator Wind Turbine”, Proceedings
of ASEAN Symposium on Automatic Control ASAC 2011, Vietnam, pp.79 –
81.
[6] Phan, V. T., Lee, H. H., Chun, T. W. (2010); “An Effective rotor current
controller for unbalanced stand – alone DFIG systems in the rotor reference
frame”, Journal of Power electrionics, Vol.10, No.6, pp194-202.
[7]. L. Xu, Y. Wang, “Dynamic modeling and control of DFIG based wind
turbines under unbalanced network conditions”, IEEE Trans. Power Syst. 22
(1) (2007) 314–323.
[8]. A. Peterson, L. Harnefors, T. Thiringer, “Comparison between stator-flux
and grid flux oriented rotor current control of doubly-fed induction
generators”, in: The 35th Annual IEEE Power Electronics Specialist
Conference, vol. 1, 20–25 June,2004, pp. 482–486.
[9] Sorensen, P.; Hansen, D.A.; Christensen, P.; Mieritz, M.; Bech, J.; Bak-
Jensen, B.; Nielsen, H. (2003); “Simulation and Verification of Transient
Events in Large Wind Power Installation”, Project Report, Risø National
Laboratory, Roskilde, Norway.
[10] Masters, M. G. (2004), Renewable and Efficient Electric Power Systems,
John Wiley and Sons, Inc., Publication.
[11] Jia-bing HU, Yi-kang HE, Lie XU (2008) ; “Dynamic modeling and
direct power control of wind turbine driven DFIG under unbalanced network
voltage conditions”, Journal of Zhejiang University SCIENCE
160