International Journal of Advanced Engineering, Management and Science (IJAEMS) [Vol-3, Issue-5, May- 2017]
https://dx.doi.org/10.24001/ijaems.3.5.9 ISSN: 2454-1311
www.ijaems.com Page | 458
Real Time Power System and Sub Synchronous
Inter Harmonics
Milan Sasmal, Biswamoy Pal, Sudip Das, Partha Das
Asst. Professor, JIS College of Engineering, W.B., India
Abstract— Real time Power system is associated with
different types of abnormalities which percolate into the
system thus generating various spurious signals, which
ultimately results in massive breakdown of the same. In this
scope of work, we have intended to design a real time power
system using MATLAB (Version7.8.0.347) (R2009a) and
incorporating Continuous Wavelet Transform and also we
have developed a program for effective identification of sub-
harmonics, generated or carried into the system due to the
power system behavioral nature.
Keyword— Sub synchronous Inter harmonics, fault,
continuous wavelet (CWT), power system, single phasing,
ground fault.
I. INTRODUCTION
Power Quality [1,5]
has regained consciousness due to certain
visual effects occurring in the day to day household
applications. Some of the inevitable visual effects due to
sub-harmonics[2.4]
being present in a system are listed as
Television Receivers, Fluorescent and mercury arc lighting,
Computers, Lamp Flicker, Washing Machines. These sub-
harmonic components of frequency are expected to be
generated from high frequency supplies been fed to arc or
blast furnaces which back feeds into the system thus
generating other spurious signals, which are detrimental for
our household appliances and results in ageing of the same
in due time.
Power Quality is of utmost concern now-a-days to endure
system reliability and to cater customer needs of decreased
tariff rate. In this regard identification of specialized
harmonic content is of utter importance. In this work, we
have developed a program using Continuous Wavelet
Transform to find out sub-synchronous inter-harmonic[2,4,5]
content of a real time signal obtained from industry. The
program is also able to find out sub-synchronous inter
harmonics of a particular signal in the different ranges of
frequency which has various detrimental effects on the
household appliances.
II. CIRCUIT DIAGRAM
In our scope of work we have developed a real time power
system (dual feeding), using MATLAB (Version 7.8.0.347)
(R2009a) for our reliability analysis [3]
purpose. The Block
Diagram of the developed circuit is given below:-
MODEL 1. BLOCK DIAGRAM OF THE DEVELOPED CIRCUIT
The circuit specifications are listed below:
 Alternator:- Frequency 50Hz, 6*350MVA,
13.8kv, 1500MW
 Load1:- 100MW
 Transformer1:- 6*350MVA, 13.8/735KV
 Circuit Breakers:-Transition time 5/50
Breaker resistance 0.001ohms,
Snubber resistance and snubber
capacitances infinity
 Line: - 300 Km
 3ph series RLC load:-330MVAR
 Transformer 2:- 300MVA, 735/230/25KV
 3ph RL load: - 30000MVA, 735KV
 3 phase series compensator:- Line reactance in
positive sequence 105.6ohms, series capacitance
62.8 micro Farad, the nominal capacitor voltage is
taken at 2 kA r.m.s. line current, MOV protection
level required to protect the capacitors at 2.5 times
the nominal capacitor voltage.
III. THE DETAILED ALGORITHM OF THE
DEVELOPED PROGRAM IS GIVEN BELOW
1) x(t) is the signal to be analyzed
2) A mother wavelet like Daubechies 10 is chosen to
serve as a prototype of windows in the process
3) Other windows are dilated/compressed and shifted
versions of the mother wavelet
4) To begin with, a scale s=1, is chosen (most
compressed wavelet)
International Journal of Advanced Engineering, Management and Science (IJAEMS) [Vol-3, Issue-5, May- 2017]
https://dx.doi.org/10.24001/ijaems.3.5.9 ISSN: 2454-1311
www.ijaems.com Page | 459
5) Wavelet placed at the beginning of the signal, i.e. at
t=0
6) CWT is computed using the required expression for
s=1 & t=0
7) Wavelet shifted to t=60 and CWT calculated for s=1 &
t= 60
8) Process repeated till the end of signal is reached
9) Thus 1 row of points on the time scale for s=1 is
obtained
10) The above steps are repeated now, for different values
of ‘s’
11) The value of ‘s’ is incremented up to 10.
12) This corresponds to the sampling of the time-scale
plane
13) When the above process is completed for all values of
‘s’, the CWT of the signal is said to be calculated.
IV. CASE STUDY
The various case studies are listed below:
Case Study 1: Single phasing & ground fault
simultaneously
Case Study 1.1: 3 phase circuit with single phasing in phase
A & line to ground fault in phase A
Fig. 1: Voltage and current spectrums of Bus 1 after single
phasing of Phase A and Ground fault of the same
The above spectrums of Bus B1 Vabc shows that each phase
has sag, swell, notches which are visible in each phase
spectrum.
The current spectrum also shows initial transient state. It
seems that some sub-harmonics are present in the current
spectrum. Also the current spectrum for phase A becomes
zero after 5 cycles which was set by the circuit breaker to
obtain single phasing of the 3 phase circuit under operating
condition.
[A phase-Blue colour, B phase-Green colour, C phase-Red
colour]
Fig. 2: Voltage, current and fault current spectrums of Bus
2after single phasing of Phase A and Ground fault of the
same
Figure 9 shows that Harmonic distortion in the voltage
spectrum is much clear in the bus 2 voltage spectrum. The
current spectrum also shows some notches at the tips. Due
to single phasing, the magnitude of current in the phase A
has become twice of the regular magnitude under balanced
condition which will cause burning of the phase of the 3
phase circuit resulting in active single phase condition while
running. The voltage spectrum[2]
of phase A becomes zero
between time instants of 0.09-0.11 sec and then again a
steep rise in abnormal voltage of twice the magnitude under
healthy condition is seen. But again the system goes into
steady state with the aid of MOV (Metal Oxide Varister)
and series compensators connected to the load end.
Thereafter the current spectrum of Bus 1 and Bus 2 was
analyzed using Continuous Wavelet Transform to check
whether any sub-harmonic content is present or not.
Case Study 1.2: Continuous wavelet[2,4]
Transform analysis
of the current spectrum of phase A, B, C of Bus 1 under
single phasing of phase A and line to ground fault condition
Fig. 3: CWT analysis of current- spectrum of Bus 1 (Phase
A)
International Journal of Advanced Engineering, Management and Science (IJAEMS) [Vol-3, Issue-5, May- 2017]
https://dx.doi.org/10.24001/ijaems.3.5.9 ISSN: 2454-1311
www.ijaems.com Page | 460
Fig. 4: CWT analysis of current- spectrum of Bus 1 (Phase
B)
Fig. 5: CWT analysis of current- spectrum of Bus 1 (Phase
C)
It is very clear from the fig. 3 that sub-harmonics of 0.1Hz
is clearly visible in the output spectrum whose amplitude is
0.4 occurring at a time instant between 1400-1510 seconds.
The above figure 4 shows no such visible distortion except
between time instants of 1900-2500 sec. But their
magnitudes are not so significant which can be neglected in
comparison to the phase A harmonic spectrum.
The figure 5 also shows no such visible distortion except
between time instants of 1900-2500 sec. But their
magnitudes are not so significant which can be neglected in
comparison to the phase A harmonic spectrum.
Case Study 1.3: Continuous wavelet Transform analysis[2]
of the current spectrum of phase A, B, C of Bus 2 under
single phasing of phase A and line to ground fault condition
FIG. 6. CWT ANALYSIS OF CURRENT- SPECTRUM OF BUS 2
(PHASE A)
Fig. 7: CWT analysis of current- spectrum of Bus 2
(Phase B)
Fig.8: CWT analysis of current- spectrum of Bus 2 (Phase
C)
It is very clear from the above fig.6 that here at the load end
the distortion in current spectrum is much more severe
which will percolate into the household appliances in no
time, thus damaging the same. Here the 0.1Hz frequency is
predominant twice, one between time instant between 500-
1400 seconds, having amplitude 0.5Hz and the other
between 1750-2100 seconds, having amplitude of 1.9 which
is significant.
Figure 7 is seen to have harmonics of 0.1Hz frequency of
amplitude value 0.5, occurring in the time instant between
1800-2300 seconds.
Figure 8 is seen to have harmonics of 0.1Hz frequency of
amplitude value 0.5, occurring in the time instant between
1800-2500 seconds.
Case Study 2: Ground fault without single phasing
Case Study 2.1: 3 phase circuit with only ground fault
without any single phasing in phase A
Fig. 9: Voltage and current spectrums of Bus 1 under
ground fault condition of phase A
International Journal of Advanced Engineering, Management and Science (IJAEMS) [Vol-3, Issue-5, May- 2017]
https://dx.doi.org/10.24001/ijaems.3.5.9 ISSN: 2454-1311
www.ijaems.com Page | 461
Figure 9 shows only sag swell and notches in the output
current and voltage spectrums. Distortion in voltage is
much effectively visible between time instants 0.09-
0.15seconds. On the other hand, massive distortion in
current spectrum is only much predominant between time
intervals of 0.13-0.155 seconds.
Fig. 10: Voltage and current spectrums of Bus 2 under
ground fault condition of phase A
Figure 10 voltage spectrum shows the presence of DC
offset, which is visible between time intervals of 0.02-
0.09seconds. In addition to it overvoltage and under
voltages are also visible in the output frame. Current
spectrum is seen to have some harmonics in the output
frame but fractional harmonics is assumed to be not
appearing in the output frame which will be clear after
CWT[2,4]
analysis of phase current. Also the use of series
compensators and MOV clears the fault after a certain
interval of time and renders reliable behavior of the
developed power system with zero fault current under
running condition.
Case Study 2.2: Continuous wavelet Transform analysis of
the current spectrum of phase A, B, C of Bus 1 under line to
ground fault condition of phase A
Fig. 11: CWT analysis of current- spectrum of Bus 1 (Phase
A)
Fig. 12: CWT analysis of current- spectrum of Bus 1 (Phase
B)
Fig. 13: CWT analysis of current- spectrum of Bus 1 (Phase
C)
Figure11 shows sub-harmonics of very minute amount of
amplitude between time 1700sec & 3000sec
Fig.12 shows in distortion at phase B of bus 1 except sub-
harmonics of amplitude nearly 0.4 between time 1900-
2400sec.
No such spurious injection in the current spectrums of
A,B,C phases is seen except in Figure 13, where 0.1Hz is
visible with amplitude of 0.3 occurring in the time instant of
1900-2200 seconds.
Case Study 2.3: Continuous wavelet Transform analysis of
the current spectrum of phase A, B, C of Bus 2 under line to
ground fault condition of phase A
Fig. 14: CWT analysis of current- spectrum of Bus 2 (Phase
A)
International Journal of Advanced Engineering, Management and Science (IJAEMS) [Vol-3, Issue-5, May- 2017]
https://dx.doi.org/10.24001/ijaems.3.5.9 ISSN: 2454-1311
www.ijaems.com Page | 462
Fig. 15: CWT analysis of current- spectrum of Bus 2 (Phase
B)
Fig. 16: CWT analysis of current- spectrum of Bus 2 (Phase
C)
The above fig. 14 shows that phase A has huge amount of
sub-harmonics embedded into it whose lumped nature
shows its peak amplitude between 1.65-2 occurring in the
time instant of 1500-2000seconds. Also o.1Hz is peaking
out at time interval of 2000-2500 seconds with amplitude
ranging between 0.5-1.
Figure 15 shows no such infiltration of fractional harmonics
in the phase current spectrum.
The response in figure 16 shows that here the sub harmonics
are embedded with adjacent frequencies, yet between time
instants of 1800-2200 seconds the lumped parameter repose
peaks out with amplitude 0.5.
Case Study 3: Single phasing without ground fault
Case study 3.1: 3 phase circuit with single phasing at phase
A without any ground fault.
Fig. 17: Voltage and current spectrums of Bus 1 when
single phasing at phase A
Bus B1 Vabc spectrum shows a very small distortion in
magnitude of phases B & C after time 0.1secs.Swell is
visible in phase B and sag in phase C after time 0.1sec.
The current spectrums of each phase shows swell till
0.1secs. The current spectrum for phase A becomes zero
after 5 cycles which was set by the circuit breaker to obtain
single phasing of the 3 phase circuit. After phase A becomes
zero, the swell only can be seen in phase B and sag in phase
C.
Fig. 18:Voltage, Current & Fault Current Spectrum of bus 2
when single phasing at phase A
The current waveform distortion and swell in the Iabc
spectrum can be seen. Due to single phasing, the magnitude
of current in the phase A has become zero after 5 cycles.
Before single phasing swell can be seen in each phase and
after single phasing swell in phase B and sag in phase C
happen.
The voltage spectrum of phase A shows swell after single
phasing. But again the system goes into steady state with the
aid of MOV and series compensators connected to the load
end.
International Journal of Advanced Engineering, Management and Science (IJAEMS) [Vol-3, Issue-5, May- 2017]
https://dx.doi.org/10.24001/ijaems.3.5.9 ISSN: 2454-1311
www.ijaems.com Page | 463
Case Study 3.2: Continuous wavelet Transform analysis of
the current spectrum of phase A, B, C of Bus 1 when single
phasing at phase A.
Fig. 19: CWT analysis of current- spectrum of Bus 1 (Phase
A)
Fig. 20: CWT analysis of current- spectrum of Bus 1 (Phase
B)
Fig. 20: CWT analysis of current- spectrum of Bus 1 (Phase
B)
Fig. 21: CWT analysis of current- spectrum of Bus 1 (Phase
C)
In fig.19 shows the phase A of bus 1 consists sub-harmonics
of amplitude 0.4 in time 2200secs.Here no such heavy
amount of sub-harmonics are present.
In fig. 20 No such sub-harmonics of considerable magnitude
are present. Though single phasing of phase A is made but
still there is no such sub-harmonics present at the bus1 of
source end.
In fig. 21 No such sub-harmonics of considerable magnitude
are present. Though single phasing of phase A is made but
still there is no such sub-harmonics present at the bus1 of
source end.
Case Study 8.3: Continuous wavelet Transform analysis of
the current spectrum of phase A of Bus 2 when single
phasing at phase A.
Fig. 22: CWT analysis of current- spectrum of Bus 2 (Phase
A)
International Journal of Advanced Engineering, Management and Science (IJAEMS) [Vol-3, Issue-5, May- 2017]
https://dx.doi.org/10.24001/ijaems.3.5.9 ISSN: 2454-1311
www.ijaems.com Page | 464
Fig. 23. CWT analysis of current- spectrum of Bus 2 (Phase
B)
Fig. 24. CWT analysis of current- spectrum of Bus 2 (Phase
C)
In fig.22 shows the phase A of bus2 consists sub-harmonics
of amplitude 0.4 in time 2200secs.Here no other sub-
harmonics are present.
In fig.23 no such sub-harmonics of considerable magnitude
are present. In between time instant 2200-2600secs some
very small magnitude of sub-harmonics can be seen.
In fig.24 No such sub-harmonics of considerable magnitude
are present. In between time instant 2200-2600secs some
very small magnitude of sub-harmonics can be seen.
Table.1: Consolidated conclusion of CWT
Fi
g
No
Topic Name Remarks and
Harmonics
description
Single phasing and
line to ground fault
3 phase A current
spectrum bus1
1400-1510 sec
amplitude 0.4
4 phase B current
spectrum bus1
No such sub-
harmonics
5 phase C current
spectrum bus1
No such sub-
harmonics
6 phase A current
spectrum bus2
500-1400sec
amplitude 0.5
1750-2100sec
amplitude 1.9
7 phase B current
spectrum bus2
1800-2300sec
amplitude 0.5
8 phase C current
spectrum bus2
1800-2500sec
amplitude 0.5
Only line to ground
fault
11 Current spectrum
phase A bus1
No such sub
harmonics
12 Current spectrum
phase B bus1
No such sub
harmonics
13 current spectrum phase
C bus1
1900-2200sec
amplitude 0.3
14 Current spectrum
phase A bus2
1500-2000sec
amplitude 1.5-2.0
2000-2500sec
amplitude 0.5-1.0
15 Current spectrum
phase B bus2
No such sub
harmonics
16 Current spectrum
phase C bus2
1800-2200sec
amplitude 0.5
With single phasing
& without ground
fault
19 phase A current
spectrum bus1
2200 sec amplitude
0.4
20 phase B current
spectrum bus1
No such sub
Harmonics
21 phase C current
spectrum bus1
No such sub
Harmonics
22 phase A current
spectrum bus2
2200 sec amplitude
0.4
23 phase B current
spectrum bus2
No such sub
Harmonics
24 phase C current
spectrum bus2
No such sub
Harmonics
V. CONCLUSION
The developed power system reveals that different
abnormalities appear in the output voltage and current
spectrum of a bus for same type of fault in each phase. Also
Dc offset much predominant only when there is only line to
ground fault. Sub harmonics is not much predominant in
ground fault condition, but it is of much more concern under
single phasing and ground fault condition. Even during only
single phasing condition sub harmonics is present.
International Journal of Advanced Engineering, Management and Science (IJAEMS) [Vol-3, Issue-5, May- 2017]
https://dx.doi.org/10.24001/ijaems.3.5.9 ISSN: 2454-1311
www.ijaems.com Page | 465
REFERENCES
[1] Chattopadhyay.S, Mitra.M, Sengupta.S, “Electric
Power Quality”, ISBN 978-94-007-0634-7, e-ISBN
978-94-007-0635-4, DOI 10.1007/978-94-007-0635-4,
Springer Dordrecht Heidelberg London New York.P. J.
Tavner and J. Penman, Condition Monitoring of
Electrical Machines. Research Studies Press, Ltd.,
1987.
[2] D.Kar Ray, S.Deb, T.Kumar, S.Sengupta, “Diagnosis
of Sub-synchronous Inter-harmonics in Power System
Signals under non-sinusoidal environment”, LCIT,
National Journal of Engineering & Technology, Vol I,
2012,Special issue on proceedings of “National
Conference on Advances and Challenges in
Engineering & Science”.
[3] Tse.F.C.Norman & Lai.L.L, “Research Article-
Wavelet Based Algorithm for Signal
Analysis”,Hindawi Publishing Corporation, EURASIP
Journal on Advances in Signal Processing, Volume
2007, Article ID 38916, 10 pages, doi:
10.115/2007/38916.
[4] Barros.J, Apraiz de.M & Diego.T.R, “Measurement of
Sub harmonics in Power Voltages”, Paper ID: 31.
[5] Arrilaga.J, Watson.N.R,”Power System Harmonics”,
2nd Edition, 2003, John Wiley & Sons, Ltd, ISBN: 0-
470-85129-5.

More Related Content

What's hot

EE456_NWPUD Transmission Reinforcement Planning
EE456_NWPUD Transmission Reinforcement PlanningEE456_NWPUD Transmission Reinforcement Planning
EE456_NWPUD Transmission Reinforcement Planning
ki hei chan
 
Rlc circuits and differential equations1
Rlc circuits and differential equations1Rlc circuits and differential equations1
Rlc circuits and differential equations1
Ghanima Eyleeuhs
 
EE454_Power Flow Programming
EE454_Power Flow ProgrammingEE454_Power Flow Programming
EE454_Power Flow Programming
ki hei chan
 
modeling of three phase rectifier
modeling of three phase rectifiermodeling of three phase rectifier
modeling of three phase rectifier
usic123
 

What's hot (20)

O044057984
O044057984O044057984
O044057984
 
B010221018
B010221018B010221018
B010221018
 
[IJET V2I5P10] Authors: Vinith Das, Dr. Babu Paul, Prof. Elizabeth Seba stian
[IJET V2I5P10] Authors: Vinith Das, Dr. Babu Paul, Prof. Elizabeth Seba stian [IJET V2I5P10] Authors: Vinith Das, Dr. Babu Paul, Prof. Elizabeth Seba stian
[IJET V2I5P10] Authors: Vinith Das, Dr. Babu Paul, Prof. Elizabeth Seba stian
 
B010221018
B010221018B010221018
B010221018
 
149305853 practical-transmission-line-calculation
149305853 practical-transmission-line-calculation149305853 practical-transmission-line-calculation
149305853 practical-transmission-line-calculation
 
EE456_NWPUD Transmission Reinforcement Planning
EE456_NWPUD Transmission Reinforcement PlanningEE456_NWPUD Transmission Reinforcement Planning
EE456_NWPUD Transmission Reinforcement Planning
 
Solar Panel Using Active Stacked Npc Multi Level Converter
Solar Panel Using Active Stacked Npc Multi Level ConverterSolar Panel Using Active Stacked Npc Multi Level Converter
Solar Panel Using Active Stacked Npc Multi Level Converter
 
IJETT-V3I2P216
IJETT-V3I2P216IJETT-V3I2P216
IJETT-V3I2P216
 
COBEP_2007
COBEP_2007COBEP_2007
COBEP_2007
 
Rlc circuits and differential equations1
Rlc circuits and differential equations1Rlc circuits and differential equations1
Rlc circuits and differential equations1
 
Cd35455460
Cd35455460Cd35455460
Cd35455460
 
Rc and rl differentiator and integrator circuit
Rc and rl differentiator and integrator circuitRc and rl differentiator and integrator circuit
Rc and rl differentiator and integrator circuit
 
EE454_Power Flow Programming
EE454_Power Flow ProgrammingEE454_Power Flow Programming
EE454_Power Flow Programming
 
Ripple theorem
Ripple theoremRipple theorem
Ripple theorem
 
modeling of three phase rectifier
modeling of three phase rectifiermodeling of three phase rectifier
modeling of three phase rectifier
 
Three phase System
Three phase SystemThree phase System
Three phase System
 
Power system calculations
Power system calculationsPower system calculations
Power system calculations
 
Three phase balanced load circuits and synchronous generators
Three phase balanced load circuits and synchronous generatorsThree phase balanced load circuits and synchronous generators
Three phase balanced load circuits and synchronous generators
 
L 3,t-1,eee, 2018-2019
L 3,t-1,eee, 2018-2019L 3,t-1,eee, 2018-2019
L 3,t-1,eee, 2018-2019
 
High Speed, Low Power Current Comparators with Hysteresis
High Speed, Low Power Current Comparators with HysteresisHigh Speed, Low Power Current Comparators with Hysteresis
High Speed, Low Power Current Comparators with Hysteresis
 

Similar to Real Time Power System and Sub Synchronous Inter Harmonics

Moshtagh new-approach-ieee-2006
Moshtagh new-approach-ieee-2006Moshtagh new-approach-ieee-2006
Moshtagh new-approach-ieee-2006
imeneii
 
Space vector pwm_inverter
Space vector pwm_inverterSpace vector pwm_inverter
Space vector pwm_inverter
ZunAib Ali
 
Electric Circuits Lab Series RC Circuits Phase Angle, Phase Lag.docx
Electric Circuits Lab Series RC Circuits Phase Angle, Phase Lag.docxElectric Circuits Lab Series RC Circuits Phase Angle, Phase Lag.docx
Electric Circuits Lab Series RC Circuits Phase Angle, Phase Lag.docx
pauline234567
 

Similar to Real Time Power System and Sub Synchronous Inter Harmonics (20)

Errors analysis in distance relay readings with presence of facts devices
Errors analysis in distance relay readings with presence of facts devicesErrors analysis in distance relay readings with presence of facts devices
Errors analysis in distance relay readings with presence of facts devices
 
Space Vector Pulse Width Modulation Technique Applied to Two Level Voltage So...
Space Vector Pulse Width Modulation Technique Applied to Two Level Voltage So...Space Vector Pulse Width Modulation Technique Applied to Two Level Voltage So...
Space Vector Pulse Width Modulation Technique Applied to Two Level Voltage So...
 
Moshtagh new-approach-ieee-2006
Moshtagh new-approach-ieee-2006Moshtagh new-approach-ieee-2006
Moshtagh new-approach-ieee-2006
 
I41045662
I41045662I41045662
I41045662
 
A New Proposal for OFCC-based Instrumentation Amplifier
A New Proposal for OFCC-based Instrumentation AmplifierA New Proposal for OFCC-based Instrumentation Amplifier
A New Proposal for OFCC-based Instrumentation Amplifier
 
A New Proposal for OFCC-based Instrumentation Amplifier
A New Proposal for OFCC-based Instrumentation AmplifierA New Proposal for OFCC-based Instrumentation Amplifier
A New Proposal for OFCC-based Instrumentation Amplifier
 
IRJET- Fault Location using Discrete Wavelet Transform for Smart Grid Distrib...
IRJET- Fault Location using Discrete Wavelet Transform for Smart Grid Distrib...IRJET- Fault Location using Discrete Wavelet Transform for Smart Grid Distrib...
IRJET- Fault Location using Discrete Wavelet Transform for Smart Grid Distrib...
 
Two-level inverter and three-level neutral point diode clamped inverter for t...
Two-level inverter and three-level neutral point diode clamped inverter for t...Two-level inverter and three-level neutral point diode clamped inverter for t...
Two-level inverter and three-level neutral point diode clamped inverter for t...
 
Space vector pwm_inverter
Space vector pwm_inverterSpace vector pwm_inverter
Space vector pwm_inverter
 
Analysis and Characterization of Different Comparator Topologies
Analysis and Characterization of Different Comparator TopologiesAnalysis and Characterization of Different Comparator Topologies
Analysis and Characterization of Different Comparator Topologies
 
Implementation for Controller to Unified Single Phase Power Flow Using Digita...
Implementation for Controller to Unified Single Phase Power Flow Using Digita...Implementation for Controller to Unified Single Phase Power Flow Using Digita...
Implementation for Controller to Unified Single Phase Power Flow Using Digita...
 
Electric Circuits Lab Series RC Circuits Phase Angle, Phase Lag.docx
Electric Circuits Lab Series RC Circuits Phase Angle, Phase Lag.docxElectric Circuits Lab Series RC Circuits Phase Angle, Phase Lag.docx
Electric Circuits Lab Series RC Circuits Phase Angle, Phase Lag.docx
 
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOM
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOMDistance Algorithm for Transmission Line with Mid-Point Connected STATCOM
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOM
 
Application of SVM Technique for Three Phase Three Leg Ac/Ac Converter Topology
Application of SVM Technique for Three Phase Three Leg Ac/Ac Converter TopologyApplication of SVM Technique for Three Phase Three Leg Ac/Ac Converter Topology
Application of SVM Technique for Three Phase Three Leg Ac/Ac Converter Topology
 
A0430107
A0430107A0430107
A0430107
 
Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...
Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...
Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...
 
Circuit-based method for extracting the resistive leakage current of metal ox...
Circuit-based method for extracting the resistive leakage current of metal ox...Circuit-based method for extracting the resistive leakage current of metal ox...
Circuit-based method for extracting the resistive leakage current of metal ox...
 
A High-Swing OTA with wide Linearity for design of self-tunable linear resistor
A High-Swing OTA with wide Linearity for design of self-tunable linear resistorA High-Swing OTA with wide Linearity for design of self-tunable linear resistor
A High-Swing OTA with wide Linearity for design of self-tunable linear resistor
 
Sensoring Leakage Current to Predict Pollution Levels to Improve Transmission...
Sensoring Leakage Current to Predict Pollution Levels to Improve Transmission...Sensoring Leakage Current to Predict Pollution Levels to Improve Transmission...
Sensoring Leakage Current to Predict Pollution Levels to Improve Transmission...
 
Sensoring Leakage Current to Predict Pollution Levels to Improve Transmission...
Sensoring Leakage Current to Predict Pollution Levels to Improve Transmission...Sensoring Leakage Current to Predict Pollution Levels to Improve Transmission...
Sensoring Leakage Current to Predict Pollution Levels to Improve Transmission...
 

Recently uploaded

FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Christo Ananth
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
rknatarajan
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Dr.Costas Sachpazis
 

Recently uploaded (20)

CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
Vivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design SpainVivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design Spain
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 

Real Time Power System and Sub Synchronous Inter Harmonics

  • 1. International Journal of Advanced Engineering, Management and Science (IJAEMS) [Vol-3, Issue-5, May- 2017] https://dx.doi.org/10.24001/ijaems.3.5.9 ISSN: 2454-1311 www.ijaems.com Page | 458 Real Time Power System and Sub Synchronous Inter Harmonics Milan Sasmal, Biswamoy Pal, Sudip Das, Partha Das Asst. Professor, JIS College of Engineering, W.B., India Abstract— Real time Power system is associated with different types of abnormalities which percolate into the system thus generating various spurious signals, which ultimately results in massive breakdown of the same. In this scope of work, we have intended to design a real time power system using MATLAB (Version7.8.0.347) (R2009a) and incorporating Continuous Wavelet Transform and also we have developed a program for effective identification of sub- harmonics, generated or carried into the system due to the power system behavioral nature. Keyword— Sub synchronous Inter harmonics, fault, continuous wavelet (CWT), power system, single phasing, ground fault. I. INTRODUCTION Power Quality [1,5] has regained consciousness due to certain visual effects occurring in the day to day household applications. Some of the inevitable visual effects due to sub-harmonics[2.4] being present in a system are listed as Television Receivers, Fluorescent and mercury arc lighting, Computers, Lamp Flicker, Washing Machines. These sub- harmonic components of frequency are expected to be generated from high frequency supplies been fed to arc or blast furnaces which back feeds into the system thus generating other spurious signals, which are detrimental for our household appliances and results in ageing of the same in due time. Power Quality is of utmost concern now-a-days to endure system reliability and to cater customer needs of decreased tariff rate. In this regard identification of specialized harmonic content is of utter importance. In this work, we have developed a program using Continuous Wavelet Transform to find out sub-synchronous inter-harmonic[2,4,5] content of a real time signal obtained from industry. The program is also able to find out sub-synchronous inter harmonics of a particular signal in the different ranges of frequency which has various detrimental effects on the household appliances. II. CIRCUIT DIAGRAM In our scope of work we have developed a real time power system (dual feeding), using MATLAB (Version 7.8.0.347) (R2009a) for our reliability analysis [3] purpose. The Block Diagram of the developed circuit is given below:- MODEL 1. BLOCK DIAGRAM OF THE DEVELOPED CIRCUIT The circuit specifications are listed below:  Alternator:- Frequency 50Hz, 6*350MVA, 13.8kv, 1500MW  Load1:- 100MW  Transformer1:- 6*350MVA, 13.8/735KV  Circuit Breakers:-Transition time 5/50 Breaker resistance 0.001ohms, Snubber resistance and snubber capacitances infinity  Line: - 300 Km  3ph series RLC load:-330MVAR  Transformer 2:- 300MVA, 735/230/25KV  3ph RL load: - 30000MVA, 735KV  3 phase series compensator:- Line reactance in positive sequence 105.6ohms, series capacitance 62.8 micro Farad, the nominal capacitor voltage is taken at 2 kA r.m.s. line current, MOV protection level required to protect the capacitors at 2.5 times the nominal capacitor voltage. III. THE DETAILED ALGORITHM OF THE DEVELOPED PROGRAM IS GIVEN BELOW 1) x(t) is the signal to be analyzed 2) A mother wavelet like Daubechies 10 is chosen to serve as a prototype of windows in the process 3) Other windows are dilated/compressed and shifted versions of the mother wavelet 4) To begin with, a scale s=1, is chosen (most compressed wavelet)
  • 2. International Journal of Advanced Engineering, Management and Science (IJAEMS) [Vol-3, Issue-5, May- 2017] https://dx.doi.org/10.24001/ijaems.3.5.9 ISSN: 2454-1311 www.ijaems.com Page | 459 5) Wavelet placed at the beginning of the signal, i.e. at t=0 6) CWT is computed using the required expression for s=1 & t=0 7) Wavelet shifted to t=60 and CWT calculated for s=1 & t= 60 8) Process repeated till the end of signal is reached 9) Thus 1 row of points on the time scale for s=1 is obtained 10) The above steps are repeated now, for different values of ‘s’ 11) The value of ‘s’ is incremented up to 10. 12) This corresponds to the sampling of the time-scale plane 13) When the above process is completed for all values of ‘s’, the CWT of the signal is said to be calculated. IV. CASE STUDY The various case studies are listed below: Case Study 1: Single phasing & ground fault simultaneously Case Study 1.1: 3 phase circuit with single phasing in phase A & line to ground fault in phase A Fig. 1: Voltage and current spectrums of Bus 1 after single phasing of Phase A and Ground fault of the same The above spectrums of Bus B1 Vabc shows that each phase has sag, swell, notches which are visible in each phase spectrum. The current spectrum also shows initial transient state. It seems that some sub-harmonics are present in the current spectrum. Also the current spectrum for phase A becomes zero after 5 cycles which was set by the circuit breaker to obtain single phasing of the 3 phase circuit under operating condition. [A phase-Blue colour, B phase-Green colour, C phase-Red colour] Fig. 2: Voltage, current and fault current spectrums of Bus 2after single phasing of Phase A and Ground fault of the same Figure 9 shows that Harmonic distortion in the voltage spectrum is much clear in the bus 2 voltage spectrum. The current spectrum also shows some notches at the tips. Due to single phasing, the magnitude of current in the phase A has become twice of the regular magnitude under balanced condition which will cause burning of the phase of the 3 phase circuit resulting in active single phase condition while running. The voltage spectrum[2] of phase A becomes zero between time instants of 0.09-0.11 sec and then again a steep rise in abnormal voltage of twice the magnitude under healthy condition is seen. But again the system goes into steady state with the aid of MOV (Metal Oxide Varister) and series compensators connected to the load end. Thereafter the current spectrum of Bus 1 and Bus 2 was analyzed using Continuous Wavelet Transform to check whether any sub-harmonic content is present or not. Case Study 1.2: Continuous wavelet[2,4] Transform analysis of the current spectrum of phase A, B, C of Bus 1 under single phasing of phase A and line to ground fault condition Fig. 3: CWT analysis of current- spectrum of Bus 1 (Phase A)
  • 3. International Journal of Advanced Engineering, Management and Science (IJAEMS) [Vol-3, Issue-5, May- 2017] https://dx.doi.org/10.24001/ijaems.3.5.9 ISSN: 2454-1311 www.ijaems.com Page | 460 Fig. 4: CWT analysis of current- spectrum of Bus 1 (Phase B) Fig. 5: CWT analysis of current- spectrum of Bus 1 (Phase C) It is very clear from the fig. 3 that sub-harmonics of 0.1Hz is clearly visible in the output spectrum whose amplitude is 0.4 occurring at a time instant between 1400-1510 seconds. The above figure 4 shows no such visible distortion except between time instants of 1900-2500 sec. But their magnitudes are not so significant which can be neglected in comparison to the phase A harmonic spectrum. The figure 5 also shows no such visible distortion except between time instants of 1900-2500 sec. But their magnitudes are not so significant which can be neglected in comparison to the phase A harmonic spectrum. Case Study 1.3: Continuous wavelet Transform analysis[2] of the current spectrum of phase A, B, C of Bus 2 under single phasing of phase A and line to ground fault condition FIG. 6. CWT ANALYSIS OF CURRENT- SPECTRUM OF BUS 2 (PHASE A) Fig. 7: CWT analysis of current- spectrum of Bus 2 (Phase B) Fig.8: CWT analysis of current- spectrum of Bus 2 (Phase C) It is very clear from the above fig.6 that here at the load end the distortion in current spectrum is much more severe which will percolate into the household appliances in no time, thus damaging the same. Here the 0.1Hz frequency is predominant twice, one between time instant between 500- 1400 seconds, having amplitude 0.5Hz and the other between 1750-2100 seconds, having amplitude of 1.9 which is significant. Figure 7 is seen to have harmonics of 0.1Hz frequency of amplitude value 0.5, occurring in the time instant between 1800-2300 seconds. Figure 8 is seen to have harmonics of 0.1Hz frequency of amplitude value 0.5, occurring in the time instant between 1800-2500 seconds. Case Study 2: Ground fault without single phasing Case Study 2.1: 3 phase circuit with only ground fault without any single phasing in phase A Fig. 9: Voltage and current spectrums of Bus 1 under ground fault condition of phase A
  • 4. International Journal of Advanced Engineering, Management and Science (IJAEMS) [Vol-3, Issue-5, May- 2017] https://dx.doi.org/10.24001/ijaems.3.5.9 ISSN: 2454-1311 www.ijaems.com Page | 461 Figure 9 shows only sag swell and notches in the output current and voltage spectrums. Distortion in voltage is much effectively visible between time instants 0.09- 0.15seconds. On the other hand, massive distortion in current spectrum is only much predominant between time intervals of 0.13-0.155 seconds. Fig. 10: Voltage and current spectrums of Bus 2 under ground fault condition of phase A Figure 10 voltage spectrum shows the presence of DC offset, which is visible between time intervals of 0.02- 0.09seconds. In addition to it overvoltage and under voltages are also visible in the output frame. Current spectrum is seen to have some harmonics in the output frame but fractional harmonics is assumed to be not appearing in the output frame which will be clear after CWT[2,4] analysis of phase current. Also the use of series compensators and MOV clears the fault after a certain interval of time and renders reliable behavior of the developed power system with zero fault current under running condition. Case Study 2.2: Continuous wavelet Transform analysis of the current spectrum of phase A, B, C of Bus 1 under line to ground fault condition of phase A Fig. 11: CWT analysis of current- spectrum of Bus 1 (Phase A) Fig. 12: CWT analysis of current- spectrum of Bus 1 (Phase B) Fig. 13: CWT analysis of current- spectrum of Bus 1 (Phase C) Figure11 shows sub-harmonics of very minute amount of amplitude between time 1700sec & 3000sec Fig.12 shows in distortion at phase B of bus 1 except sub- harmonics of amplitude nearly 0.4 between time 1900- 2400sec. No such spurious injection in the current spectrums of A,B,C phases is seen except in Figure 13, where 0.1Hz is visible with amplitude of 0.3 occurring in the time instant of 1900-2200 seconds. Case Study 2.3: Continuous wavelet Transform analysis of the current spectrum of phase A, B, C of Bus 2 under line to ground fault condition of phase A Fig. 14: CWT analysis of current- spectrum of Bus 2 (Phase A)
  • 5. International Journal of Advanced Engineering, Management and Science (IJAEMS) [Vol-3, Issue-5, May- 2017] https://dx.doi.org/10.24001/ijaems.3.5.9 ISSN: 2454-1311 www.ijaems.com Page | 462 Fig. 15: CWT analysis of current- spectrum of Bus 2 (Phase B) Fig. 16: CWT analysis of current- spectrum of Bus 2 (Phase C) The above fig. 14 shows that phase A has huge amount of sub-harmonics embedded into it whose lumped nature shows its peak amplitude between 1.65-2 occurring in the time instant of 1500-2000seconds. Also o.1Hz is peaking out at time interval of 2000-2500 seconds with amplitude ranging between 0.5-1. Figure 15 shows no such infiltration of fractional harmonics in the phase current spectrum. The response in figure 16 shows that here the sub harmonics are embedded with adjacent frequencies, yet between time instants of 1800-2200 seconds the lumped parameter repose peaks out with amplitude 0.5. Case Study 3: Single phasing without ground fault Case study 3.1: 3 phase circuit with single phasing at phase A without any ground fault. Fig. 17: Voltage and current spectrums of Bus 1 when single phasing at phase A Bus B1 Vabc spectrum shows a very small distortion in magnitude of phases B & C after time 0.1secs.Swell is visible in phase B and sag in phase C after time 0.1sec. The current spectrums of each phase shows swell till 0.1secs. The current spectrum for phase A becomes zero after 5 cycles which was set by the circuit breaker to obtain single phasing of the 3 phase circuit. After phase A becomes zero, the swell only can be seen in phase B and sag in phase C. Fig. 18:Voltage, Current & Fault Current Spectrum of bus 2 when single phasing at phase A The current waveform distortion and swell in the Iabc spectrum can be seen. Due to single phasing, the magnitude of current in the phase A has become zero after 5 cycles. Before single phasing swell can be seen in each phase and after single phasing swell in phase B and sag in phase C happen. The voltage spectrum of phase A shows swell after single phasing. But again the system goes into steady state with the aid of MOV and series compensators connected to the load end.
  • 6. International Journal of Advanced Engineering, Management and Science (IJAEMS) [Vol-3, Issue-5, May- 2017] https://dx.doi.org/10.24001/ijaems.3.5.9 ISSN: 2454-1311 www.ijaems.com Page | 463 Case Study 3.2: Continuous wavelet Transform analysis of the current spectrum of phase A, B, C of Bus 1 when single phasing at phase A. Fig. 19: CWT analysis of current- spectrum of Bus 1 (Phase A) Fig. 20: CWT analysis of current- spectrum of Bus 1 (Phase B) Fig. 20: CWT analysis of current- spectrum of Bus 1 (Phase B) Fig. 21: CWT analysis of current- spectrum of Bus 1 (Phase C) In fig.19 shows the phase A of bus 1 consists sub-harmonics of amplitude 0.4 in time 2200secs.Here no such heavy amount of sub-harmonics are present. In fig. 20 No such sub-harmonics of considerable magnitude are present. Though single phasing of phase A is made but still there is no such sub-harmonics present at the bus1 of source end. In fig. 21 No such sub-harmonics of considerable magnitude are present. Though single phasing of phase A is made but still there is no such sub-harmonics present at the bus1 of source end. Case Study 8.3: Continuous wavelet Transform analysis of the current spectrum of phase A of Bus 2 when single phasing at phase A. Fig. 22: CWT analysis of current- spectrum of Bus 2 (Phase A)
  • 7. International Journal of Advanced Engineering, Management and Science (IJAEMS) [Vol-3, Issue-5, May- 2017] https://dx.doi.org/10.24001/ijaems.3.5.9 ISSN: 2454-1311 www.ijaems.com Page | 464 Fig. 23. CWT analysis of current- spectrum of Bus 2 (Phase B) Fig. 24. CWT analysis of current- spectrum of Bus 2 (Phase C) In fig.22 shows the phase A of bus2 consists sub-harmonics of amplitude 0.4 in time 2200secs.Here no other sub- harmonics are present. In fig.23 no such sub-harmonics of considerable magnitude are present. In between time instant 2200-2600secs some very small magnitude of sub-harmonics can be seen. In fig.24 No such sub-harmonics of considerable magnitude are present. In between time instant 2200-2600secs some very small magnitude of sub-harmonics can be seen. Table.1: Consolidated conclusion of CWT Fi g No Topic Name Remarks and Harmonics description Single phasing and line to ground fault 3 phase A current spectrum bus1 1400-1510 sec amplitude 0.4 4 phase B current spectrum bus1 No such sub- harmonics 5 phase C current spectrum bus1 No such sub- harmonics 6 phase A current spectrum bus2 500-1400sec amplitude 0.5 1750-2100sec amplitude 1.9 7 phase B current spectrum bus2 1800-2300sec amplitude 0.5 8 phase C current spectrum bus2 1800-2500sec amplitude 0.5 Only line to ground fault 11 Current spectrum phase A bus1 No such sub harmonics 12 Current spectrum phase B bus1 No such sub harmonics 13 current spectrum phase C bus1 1900-2200sec amplitude 0.3 14 Current spectrum phase A bus2 1500-2000sec amplitude 1.5-2.0 2000-2500sec amplitude 0.5-1.0 15 Current spectrum phase B bus2 No such sub harmonics 16 Current spectrum phase C bus2 1800-2200sec amplitude 0.5 With single phasing & without ground fault 19 phase A current spectrum bus1 2200 sec amplitude 0.4 20 phase B current spectrum bus1 No such sub Harmonics 21 phase C current spectrum bus1 No such sub Harmonics 22 phase A current spectrum bus2 2200 sec amplitude 0.4 23 phase B current spectrum bus2 No such sub Harmonics 24 phase C current spectrum bus2 No such sub Harmonics V. CONCLUSION The developed power system reveals that different abnormalities appear in the output voltage and current spectrum of a bus for same type of fault in each phase. Also Dc offset much predominant only when there is only line to ground fault. Sub harmonics is not much predominant in ground fault condition, but it is of much more concern under single phasing and ground fault condition. Even during only single phasing condition sub harmonics is present.
  • 8. International Journal of Advanced Engineering, Management and Science (IJAEMS) [Vol-3, Issue-5, May- 2017] https://dx.doi.org/10.24001/ijaems.3.5.9 ISSN: 2454-1311 www.ijaems.com Page | 465 REFERENCES [1] Chattopadhyay.S, Mitra.M, Sengupta.S, “Electric Power Quality”, ISBN 978-94-007-0634-7, e-ISBN 978-94-007-0635-4, DOI 10.1007/978-94-007-0635-4, Springer Dordrecht Heidelberg London New York.P. J. Tavner and J. Penman, Condition Monitoring of Electrical Machines. Research Studies Press, Ltd., 1987. [2] D.Kar Ray, S.Deb, T.Kumar, S.Sengupta, “Diagnosis of Sub-synchronous Inter-harmonics in Power System Signals under non-sinusoidal environment”, LCIT, National Journal of Engineering & Technology, Vol I, 2012,Special issue on proceedings of “National Conference on Advances and Challenges in Engineering & Science”. [3] Tse.F.C.Norman & Lai.L.L, “Research Article- Wavelet Based Algorithm for Signal Analysis”,Hindawi Publishing Corporation, EURASIP Journal on Advances in Signal Processing, Volume 2007, Article ID 38916, 10 pages, doi: 10.115/2007/38916. [4] Barros.J, Apraiz de.M & Diego.T.R, “Measurement of Sub harmonics in Power Voltages”, Paper ID: 31. [5] Arrilaga.J, Watson.N.R,”Power System Harmonics”, 2nd Edition, 2003, John Wiley & Sons, Ltd, ISBN: 0- 470-85129-5.