SlideShare a Scribd company logo
1 of 73
Download to read offline
REACTIVE POWER COMPENSATION AND
MANAGEMENT(BPEBO7)
I M. Tech I semester (Autonomous IARE R-18)
BY
Mr. P. Shivakumar
Assistant Professor, EEE
DEPARTMENT OF ELECTRICAL AND ELECTRONICS
ENGINEERING
INSTITUTE OF AERONAUTICAL ENGINEERING
(Autonomous)
DUNDIGAL, HYDERABAD - 500 043
UNIT - I
LOAD COMPENSATION
1
Introduction:
It is necessary to manage the reactive power to improve the
power factor and the quality of supply Load compensation is the
major player in it.
Load Compensation
3
 Power factor improvement
 Balanced load
 It is important to maintain the voltage profile within +-5% of
the rated value.
The main objectives in load compensation are:
Improved voltage profile
4
DEFINATIONS OF VARIOUS POWERS
 POWER : POWER can be defined as the rate of flow of
energy at a given point of circuit
 REAL POWER :The portion of power that
,averaged over a complete cycle of the ac waveform
,results in net transfer of energy in one direction is
known as real power
 Reactive power : The portion of power due to stored
energy , which returns to the source in each cycle is
known as reactive power
Basic concepts of power
5
Different types of power
6
 Voltage control in an electrical power system is very
important for proper operation for electrical power
equipment to prevent damage
 Decreasing reactive power causing voltage to fall while
increasing it causing voltage to rise
 When reactive power supply lower voltage,
as voltage drops current must increase to maintain
power supplied , causing system to consume more
reactive power which causes cascading failures
IMPORTANCE OF REACTIVE POWER
7
8
 If the voltage drops too low ,some generators
will disconnect automatically to protect
themselves ,these will cause additional elements
of trip , leading further reduction In voltage and
loss of the load
 Reactive power is essential to move active
power through the transmission and
distribution system to the consumer
 Three reasons :
 It must maintain adequate voltages throughout the
transmission and distribution system for both current
and contingency conditions
 It seeks to maintain congestion of real power flows
 It seeks to minimize real power losses
NCESSITY TO CONTROL VOLTAGE AND
REACTIVE POWER
9
 Voltages are controlled by providing sufficient
reactive power control margin to supply needs
through
 1.shunt capacitor and reactor compensations
 2.dynamic compensation
 3. proper voltage schedule of generation
NCESSITY TO CONTROL VOLTAGE AND
REACTIVE POWER
10
 Reactive power does not travel very far
 Usually necessary to produce it close to the location
where it is needed
 A supplier/source close to the location of the need is In
a much better position to provide reactive power versus
one that is located far from the location of the need
 Reactive power supplies are closely tied to the
availability to deliver real or active power
LIMITATIONS OF REACTIVEPOWER
11
 1.Generation
 2.synchronous condensors
 3. capacitors & inductors
 4.static var compensators ( svcs )
 5.distributed generation
 6.transmission side
EFFECTS OF REACTIVE POWER ON POWER SYSTEM
12
TYPES OF FACTS DEVICES
13
 Static VAR compensator
 Static compensator(STATCOM)
 Series compensation
 Thyristor controlled series CAPACITORS
 SSSC
INTRODUCTION OF POWER FACTOR
14
 What is power factor
 What causes low power factor
 Why should I improve my power factor
 How should I correct (Improve) my power factor
15
KW is Working Power (also called Actual Power or Active Power or Real
Power). It is the power that actually powers the equipment and performs
useful work.
KVA is Apparent Power. It is the “vectorial summation” of KVAR and
KW.
KVAR is Reactive Power. It is the power that magnetic equipment
(transformer, motor and relay) needs to produce the magnetizing flux.
What causes Low Power Factor?
16
What causes Low Power Factor?
Low power factor results when KW is small in relation to KVA.
Remembering our beer mug analogy, this would occur when KVAR (foam, or Mac’s
shoulder height) is large.
What causes a large KVAR in a system? The answer is…inductive loads.
Transformers
 Induction motors
 Induction generators (wind mill generators)
 High intensity discharge (HID) lighting
Why should I Improve my Power Factor?
17
• Lower the Utility bill
Why should I Improve my Power Factor?
inductive loads require reactive power, caused your low power factor. This
increase in required reactive power (KVAR) causes an increase in required
apparent power (KVA), which is what the utility is supplying.
So, a facility’s low power factor causes the utility to have to increase its
generation and transmission capacity in order to handle this extra demand.
By raising your power factor, you use less KVAR. This results in less KW,
which equates to savings from the utility.
• Increased system capacity and reduced system losses
By adding capacitors (KVAR generators) to the system, the power factor is
improved and the KW capacity of the system is increased.
Reduces I2R losses in conductors
UNIT II
STEADYSTATE REACTIVE POWER
COMPENSATION IN TRANSMISSION
SYSTEM
32
 The demand of the reactive power is mainly originated from
inductive load connected to the system .
 These inductive loads generally electromagnetic circuit of electric
motors, electrical transformers, distribution networks and
induction furnaces etc.
 Reactive power compensation is the defined as the management
of reactive power to improve the
 performance of AC system . There are two aspects : -
1. Load compensation
2. Voltage support
Introduction
34
Power traingle
35
 Active Power ( P ) : - It is the power that actuallypowers the
equipment and performs useful work . Unitof it W .
 Reactive Power ( Q ) : - It is the power that
magneticequipment{ transformer , motor etc. } needs to
produce the magnetizing flux . Unit of it VAr .
 Apparent Power ( S ) : - It is the “ vectorial summation ”
ofactive power ( P ) and reactive power ( Q ) . Unit of it VA .
36
Reactive Power
37
•The portion of power flow that is temporarily stored in the form of magnetic
or electric fields , due to inductive or capacitive network element and then
returned to source is known as reactive power .
•Reactive power can best be described as thequantity of “unused” power
that is stored in reactive components , such as inductors or capacitors . In
other words , the reactive circuit returns as muchpower to the supply as it
consumes .
 In resistive loads the current produces the heat energy which
produces the desired output but incase of inductive loads the
current creates the magnetic field which further produces the
desired work.
 Therefore reactive power is the non working power caused by
the magnetic current to operate and sustain magnetism in the
device .
 Reactive power (vars) is required to maintain the voltage to
deliver active power (watts) through transmission lines.
 When there is not enough reactive power the voltage sags
down and it is not possible to deliver the required power to
load through the lines.
Why do we need reactive
power
38
1
40
: -
Reactive power generated by the ac power source is stored in a reactor during a
quarter of a cycle and in the next quarter of the cycle it is sent back to the power
source.
Therefore the reactive power oscillates between the ac source and the reactor at
a frequency equals to two times the rated value (50 or 60 Hz). So to avoid the
circulation between the load and source it needs to be compensate t o improve
system power factor .
Need for reactive power
compensation
 Reduce losses associated with the system .
 Improves the voltage regulation in the network .
 Increased system stability .
 Reactive power levels have an effect on voltage
 collapse .
41
compensation
Fig 5: Thyristor voltage waveforms (with delay α)
42
.
Compensation Techniques
43
•Synchronous Condenser
•Shunt Compensation
•Series Compensation
Synchronous Condenser
44
 Synchronous condensers are the active shunt compensators and
have been used to improve the voltage profile and system
stability . It is installed at the receiving end of the line .
 When machine is overexcited , it acts as shunt capacitor as it
supplies VAr to the system and when under excited it acts as a
shunt coil as it absorbs reactive power to maintain terminal
voltage.
 The device that is connected in parallel with the transmission
line for reactive power compensation is called the shunt
compensator
 It can be provided by either a current source, voltage source
or a capacitor.If XC = 1/ωC be the reactance of the shunt
capacitorthen the reactive power generated of leading VAr
Shunt Compensation
45
Transmission line with shunt
compensation
46
 Capacitor are connected in series in the lines and are used
mainly for boosting the receiving end voltage, increase in
transmission capacity and reduction in losses in the lines .
 The capacitive reactance of series capacitor neutralizes the
inductive reactance of the line hence ,reduces effective
reactance of the line. Thereby , voltage regulation of the
system is improved .
Series Compensation
47
Transmission line with series
compensation
48
VOLTAGE WAVEFORM
Fig 9: Thyristor voltage waveforms
49
UNIT III
REACTIVE POWER COORDINATION
54
Control objectives contributing to efficient and
reliable operation of power system:
56
•Voltage at terminals of all equipment are within
acceptable limits
•both utility and customer equipment designed to
operate at certain voltage rating
•prolonged operation outside allowable range
could cause them damage
•System stability is satisfactory
•voltage levels and reactive power control have
significant impact on stability
•The reactive power flow is minimized so as to reduce
I 2R and I 2X losses to a practical minimum
• ensures transmission system operates efficiently
Production and Absorption of
Reactive Power (Q)
57
•Synchronous Generators
•can generate or absorb Q depending on excitation
•capability limited by field current, armature current, and end-region
heating limits
•automatic voltage regulator continuously adjusts excitation to control
armature voltage
•primary source of voltage support!
•Overhead lines
•at loads below natural or surge impedance load (SIL), produce Q
•at loads above SIL, absorb Q
 Transformers
 absorb Q due to shunt magnetizing reactance and series
leakage inductance
 Loads
 a typical "load bus" is composed of a large number of
devices
 composite characteristics are normally such that a load bus
absorbs Q
 industrial loads usually have shunt capacitors to improve
power factor
Production and Absorption of Q
58
Methods of Voltage Control
59
 Control of voltage levels is accomplished by controlling the
production, absorption, and flow of reactive power at all levels
in the system
 Generating units provide the basic means of voltage control
 Shunt capacitors and reactors, and series capacitors provide
passive compensation
 are either permanently connected to the transmission and
distribution system, or switched
 contribute to voltage control by modifying the network
characteristics
 Synchronous condensers and SVCs provide active
compensation; the reactive power absorbed/ supplied by
them are automatically adjusted so as to maintain voltages of
the buses to which they are connected
Methods of Voltage Control
60
Objectives of Reactive Power
Compensation
61
To control voltage and/or improve maximum
power transfer capability
 Used to compensate the undesirable voltage effects associated
with line capacitance
 limit voltage rise on open circuit or light load
 Shunt compensation with reactors:
Shunt Reactors
62
 Used in transmission systems to compensate for I 2X losses
 Connected either directly to H.V. bus or to tertiary winding of
transformers
 Normally distributed throughout the system so as to minimize
losses and voltage drops
 Usually switched: a convenient means of controlling voltage
 Shunt capacitor compensation of transmission lines in effect
 decreases ZC
 increases θ, i.e., electrical length
 Advantages: low cost and flexibility of installation and
operating
Shunt Capacitors
63
 Connected in series with the line
 Used to reduce effective inductive reactance of line
 increases maximum power
 reduces I2X loss
 Series capacitive compensation in effect reduces both:
 characteristic impedance ZC, and
 electrical length θ
 Reactive power produced increases with increasing power transfer
 Self regulating !
Series Capacitors
64
 A synchronous machine running without a prime mover or a
mechanical load
 Depending on field excitation, it can either absorb or
generate vars
 With a voltage regulator, it can automatically adjust vars to
maintain constant voltage
 Started as an induction motor and then synchronized
 Normally connected to tertiary windings of transformers
 Unlike a SVC, a synchronous condenser has an internal
voltage
Synchronous Condenser
65
 Shunt connected static var generators and/or absorbers
whose outputs are varied so as to control specific power
system quantities
 The term static is used to denote that there are no moving or
rotating components
 Basic types of SVCs:
 thyristor-controlled reactor
 thyristor-switched capacitor
 saturated reactor
Static VAR Compensators (SVC)
66
UNIT IV
DEMAND SIDE MANAGEMENT
78
 Supply-side management (SSM) refers to actions taken to
ensure the generation, transmission and distribution of
energy are conducted efficiently.
 This has become especially important with the deregulation
of the electricity industry in many countries, where the
efficient use of available energy sources becomes essential to
remain competitive.
 Utility companies may look at means of modifying their load
profile to allow their least efficient generating equipment to
be used as little as possible.
Supply side management:
80
Why it is necessary?
81
 To Ensure sustained availability of reliable energy
 To Meet increasing electricity demand
 To reduce environmental impact of energy production and
supply
Supply side measures
82
1.Clean coal technology
2.Fuel substitution
Resources and resource preparation
83
1.Proper maintenance
2.Data and performance monitoring
3. Combustion control
4.Upgradation of generation unit
Power generation and energy conversion
84
1.Transmission lines
2.Data monitoring and control
3. Load aggregation
4. Facts
Transmission and distribution
85
 SVC (Static Var Compensators),
 Thyristor-Controlled Series Capacitors (TCSC) and Statcom.
 PST (Phase-shifting Transformers),
 IPC (Interphase Power Controllers),
 UPFC (Universal Power Flow Controllers),
 and DVR (Dynamic Voltage Restorers).
Important devices power transmission
involving FACTS and Power Quality devices:
86
 It is also called as Energy Demand Management.
 The modification of consumer demand for energy through various
methods such as financial incentives and education is termed as
Demand Side Management.
 The main goal of demand side management is to encourage the
consumer to use less energy during peak hours, or to move the
time of energy use to off-peak times such as night time and
weekends.
Demand Side management
87
 Definition - DSM (Demand Side Management) is the
'Scientific control of usage and demand of Electricity, for
achieving better load factor and economy, by the
Licensee/Supplier'.
88
Benefits of Demand Side Management
89
i) Monopoly power market structure.
•ii) No competition which leads to traditional and inefficient
tariff structure.
•iii) Lack of creating awareness among consumers about the
efficient use of energy.
•iv) Lack of energy efficient environment.
•v) Huge gap between supply and demand of energy.
•vi) Lack of proper incentive schemes to consumer on using
energy efficient appliances and utility to implement DSM
solutions.
•vii) Power system reliability, quality and stability is not able to
keep itself in standard position.
The barriers for DSM
90
 Initiative from the consumer side is very important for
successful DSM
•The scope of DSM includes
1. Load shifting/ Load management
2. Energy conservation
3. Increased electrification
Implementation of DSM
91
1.Develop end-use Demand forecasting
•Forecasting by end-use is an essential pre-requisite for
effective DSM planning and implementation.
•Mid- and long-term forecasts of power demand variations play
a very important role in the development of a DSM
programme.
•Demand forecasting is an exercise that every electricity-
generating company should carry out regularly in order to
assess its future equipment requirements.
Planning & Implementation of DSM
92
2. Undertake Load/ Market Research to identify end-use
patterns and market barriers
•To design effective DSM programmes it is important to know
how electricity is used and what barriers are preventing
customers from using efficient technologies.
•Load research should be undertaken to estimate load curves for
each sector or region, using local sub-metering, customer bill
analysis and customer surveys.
•Major areas of interest to DSM programmes include the
residential, commercial, industrial, and public utility sectors.
•Market research is needed to understand the target market,
identify barriers and evaluate possible solutions.
Planning & Implementation of DSM
93
Planning & Implementation of DSM
94
4. Identify target sectors, end-uses, and measures
•The collected information is normally useful in determining a
typical load curve for each end-use.
•Find out load-curve management objectives
•Choose sectors and end-uses that account for the largest
power consumption and peak loads, or will do so in the
future.
•Select DSM measures which will have the largest impact on
peak demand and electricity use.
Planning & Implementation of DSM
95
5. Identify sources of financing
•In any DSM programme, financing is needed for individual
projects undertaken by participants.
•Utilities may also require financing to cover administrative costs
and cost sharing investments.
•Government/public fund is required.
Planning & Implementation of DSM
96
6. Review Cost Sharing and Viability Options
•Cost sharing in a DSM programme should try to maximize
viability for each partner (participant, utility, and
government).
•The wider the differences between tariffs, the higher the
utility investment can be, which in turn leads to a higher
participation rate.
97
7. Programme Selection and Design
•Identifying a list of programmes for each customer class.
•Formation of brief report corresponding to that program
•Uniform reporting format is required.
98
8. DSM Cost/Benefit Analysis
•Based on the case study /measurement
•Calculation of financial interest
9. Identify Local Socio-Economic and Environmental Impacts
•Most DSM programmes provide indirect economic and
environmental benefits as well as reducing emissions and
other impacts from power supply facilities.
•Eg. employment is created in the energy services industry
99
UNIT V
USER SIDE REACTIVE POWER
MANAGEMENT
100
Control of voltage and reactive power should satisfy the
followingobjectives:
1. Voltages at the terminals of all equipment in the system
arewithin acceptable limits.
2. System stability is enhanced to maximize
utilization of thetransmission system. Voltage
and reactive power control havea significant impact on
system stability.
Methods of voltage control:
102
 A. Sources or sinks of reactive power, such as shunt
capacitors, shunt reactors, synchronous condensers, and
static var
compensators (SVCs).B. Line reactance compensators, such as
series capacitors. C. Regulating transformers, such as tap-
changing transformers and boosters.
 Shunt capacitors and reactors, and series capacitors provide
passive compensation. They are either permanently
connected to the transmission and distribution system, or
switched. They contribute to voltage control by modifying the
networkcharacteristics.
 Synchronous condensers and SVCs provide activecompensati
on; the reactive power absorbed/supplied bythem is
automatically adjusted so as to maintain voltagesof the buses
to which they are connected.
103
•Shunt capacitors supply reactive power and boost local voltages.
•They are used throughout the system and are applied in a wide
range of sizes
•The principal advantages of shunt capacitors are their low
costand their flexibility of installation and operation.
• The principal disadvantage of shunt capacitors is that their
•reactive power output is proportional to the square of
the voltage.
•The reactive power output is reduced at low voltages when it is
likelyto be needed most.
Shunt capacitor
104
 Transformers with tap-changing
facilities constitute an importantmeans of controlling voltage
throughout the system at all voltagelevels.
 The taps on transformers provide a
convenient means of controlling reactive power flow between
subsystems.
 Coordinated control of the tap changers of all the transforme
rs interconnecting the subsystems is required if the general
level of voltage is to be changed.
 During high
system load conditions, the network voltages are kept at the
highest practical level to minimize reactive power
requirements and increasethe effectiveness of shunt
capacitors and line charging.
Application of Tap-
Changing Transformers to Transmission Systems
105
 During light load conditions, it is usually required to lower
the networkvoltages to reduce line charging and avoid under
excited operation of generators.
 Transformers with off-load tap-changing facilities can also
help maintainsatisfactory voltage profiles.
 While transformers with ULTC can be used to take care of
daily, hourly,and minute-by-minute variations in system
conditions, settings of off-loadtap-changing transformers
have to be carefully chosen depending on long-term
variations due to system expansion, load growth, or seasonal
changes.
106
THANK YOU
125

More Related Content

Similar to REACTIVE POWER COMPENSATION AND MANAGEMENT

Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur AreaReactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Areaijceronline
 
Reactivepowercompensation 140401183847-phpapp01 (6)
Reactivepowercompensation 140401183847-phpapp01 (6)Reactivepowercompensation 140401183847-phpapp01 (6)
Reactivepowercompensation 140401183847-phpapp01 (6)REVANTH CHINTU
 
An Overview of Facts Devices used for Reactive Power Compensation Techniques
An Overview of Facts Devices used for Reactive Power Compensation TechniquesAn Overview of Facts Devices used for Reactive Power Compensation Techniques
An Overview of Facts Devices used for Reactive Power Compensation TechniquesDr. Sudhir Kumar Srivastava
 
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdfpowerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdfBOOPATHIMADHAIYAN
 
Power factor introduction and its correction final
Power factor introduction and its correction final Power factor introduction and its correction final
Power factor introduction and its correction final manpreetsingh1076
 
power factor correction using smart relay
power factor correction using smart relaypower factor correction using smart relay
power factor correction using smart relayHatem Seoudy
 
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...IRJET Journal
 
Reactive Power Compensation and Control via Shunt Reactors and Under Ground P...
Reactive Power Compensation and Control via Shunt Reactors and Under Ground P...Reactive Power Compensation and Control via Shunt Reactors and Under Ground P...
Reactive Power Compensation and Control via Shunt Reactors and Under Ground P...IJERA Editor
 
Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportTheory to Practical
 
Importance of reactive power in determining the cost of power system in futur...
Importance of reactive power in determining the cost of power system in futur...Importance of reactive power in determining the cost of power system in futur...
Importance of reactive power in determining the cost of power system in futur...Shubham Sachan
 

Similar to REACTIVE POWER COMPENSATION AND MANAGEMENT (20)

Reactive power
Reactive powerReactive power
Reactive power
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
 
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur AreaReactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
 
Reactivepowercompensation 140401183847-phpapp01 (6)
Reactivepowercompensation 140401183847-phpapp01 (6)Reactivepowercompensation 140401183847-phpapp01 (6)
Reactivepowercompensation 140401183847-phpapp01 (6)
 
Mohsin rana
Mohsin ranaMohsin rana
Mohsin rana
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
An Overview of Facts Devices used for Reactive Power Compensation Techniques
An Overview of Facts Devices used for Reactive Power Compensation TechniquesAn Overview of Facts Devices used for Reactive Power Compensation Techniques
An Overview of Facts Devices used for Reactive Power Compensation Techniques
 
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdfpowerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
 
Power factor introduction and its correction final
Power factor introduction and its correction final Power factor introduction and its correction final
Power factor introduction and its correction final
 
Thyristor switched capacitor
Thyristor switched capacitorThyristor switched capacitor
Thyristor switched capacitor
 
power factor correction using smart relay
power factor correction using smart relaypower factor correction using smart relay
power factor correction using smart relay
 
Power factor
Power factorPower factor
Power factor
 
Power factor
Power factorPower factor
Power factor
 
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
 
Reactive Power Compensation and Control via Shunt Reactors and Under Ground P...
Reactive Power Compensation and Control via Shunt Reactors and Under Ground P...Reactive Power Compensation and Control via Shunt Reactors and Under Ground P...
Reactive Power Compensation and Control via Shunt Reactors and Under Ground P...
 
Reactive power management in india
Reactive power  management in indiaReactive power  management in india
Reactive power management in india
 
POWER FACTOR IMPROVE
POWER FACTOR IMPROVEPOWER FACTOR IMPROVE
POWER FACTOR IMPROVE
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System Report
 
Importance of reactive power in determining the cost of power system in futur...
Importance of reactive power in determining the cost of power system in futur...Importance of reactive power in determining the cost of power system in futur...
Importance of reactive power in determining the cost of power system in futur...
 

Recently uploaded

(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAbhinavSharma374939
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxhumanexperienceaaa
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 

Recently uploaded (20)

(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog Converter
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 

REACTIVE POWER COMPENSATION AND MANAGEMENT

  • 1. REACTIVE POWER COMPENSATION AND MANAGEMENT(BPEBO7) I M. Tech I semester (Autonomous IARE R-18) BY Mr. P. Shivakumar Assistant Professor, EEE DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) DUNDIGAL, HYDERABAD - 500 043
  • 2. UNIT - I LOAD COMPENSATION 1
  • 3. Introduction: It is necessary to manage the reactive power to improve the power factor and the quality of supply Load compensation is the major player in it. Load Compensation 3
  • 4.  Power factor improvement  Balanced load  It is important to maintain the voltage profile within +-5% of the rated value. The main objectives in load compensation are: Improved voltage profile 4
  • 5. DEFINATIONS OF VARIOUS POWERS  POWER : POWER can be defined as the rate of flow of energy at a given point of circuit  REAL POWER :The portion of power that ,averaged over a complete cycle of the ac waveform ,results in net transfer of energy in one direction is known as real power  Reactive power : The portion of power due to stored energy , which returns to the source in each cycle is known as reactive power Basic concepts of power 5
  • 7.  Voltage control in an electrical power system is very important for proper operation for electrical power equipment to prevent damage  Decreasing reactive power causing voltage to fall while increasing it causing voltage to rise  When reactive power supply lower voltage, as voltage drops current must increase to maintain power supplied , causing system to consume more reactive power which causes cascading failures IMPORTANCE OF REACTIVE POWER 7
  • 8. 8  If the voltage drops too low ,some generators will disconnect automatically to protect themselves ,these will cause additional elements of trip , leading further reduction In voltage and loss of the load  Reactive power is essential to move active power through the transmission and distribution system to the consumer
  • 9.  Three reasons :  It must maintain adequate voltages throughout the transmission and distribution system for both current and contingency conditions  It seeks to maintain congestion of real power flows  It seeks to minimize real power losses NCESSITY TO CONTROL VOLTAGE AND REACTIVE POWER 9
  • 10.  Voltages are controlled by providing sufficient reactive power control margin to supply needs through  1.shunt capacitor and reactor compensations  2.dynamic compensation  3. proper voltage schedule of generation NCESSITY TO CONTROL VOLTAGE AND REACTIVE POWER 10
  • 11.  Reactive power does not travel very far  Usually necessary to produce it close to the location where it is needed  A supplier/source close to the location of the need is In a much better position to provide reactive power versus one that is located far from the location of the need  Reactive power supplies are closely tied to the availability to deliver real or active power LIMITATIONS OF REACTIVEPOWER 11
  • 12.  1.Generation  2.synchronous condensors  3. capacitors & inductors  4.static var compensators ( svcs )  5.distributed generation  6.transmission side EFFECTS OF REACTIVE POWER ON POWER SYSTEM 12
  • 13. TYPES OF FACTS DEVICES 13  Static VAR compensator  Static compensator(STATCOM)  Series compensation  Thyristor controlled series CAPACITORS  SSSC
  • 14. INTRODUCTION OF POWER FACTOR 14  What is power factor  What causes low power factor  Why should I improve my power factor  How should I correct (Improve) my power factor
  • 15. 15 KW is Working Power (also called Actual Power or Active Power or Real Power). It is the power that actually powers the equipment and performs useful work. KVA is Apparent Power. It is the “vectorial summation” of KVAR and KW. KVAR is Reactive Power. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux.
  • 16. What causes Low Power Factor? 16 What causes Low Power Factor? Low power factor results when KW is small in relation to KVA. Remembering our beer mug analogy, this would occur when KVAR (foam, or Mac’s shoulder height) is large. What causes a large KVAR in a system? The answer is…inductive loads. Transformers  Induction motors  Induction generators (wind mill generators)  High intensity discharge (HID) lighting
  • 17. Why should I Improve my Power Factor? 17 • Lower the Utility bill Why should I Improve my Power Factor? inductive loads require reactive power, caused your low power factor. This increase in required reactive power (KVAR) causes an increase in required apparent power (KVA), which is what the utility is supplying. So, a facility’s low power factor causes the utility to have to increase its generation and transmission capacity in order to handle this extra demand. By raising your power factor, you use less KVAR. This results in less KW, which equates to savings from the utility. • Increased system capacity and reduced system losses By adding capacitors (KVAR generators) to the system, the power factor is improved and the KW capacity of the system is increased. Reduces I2R losses in conductors
  • 18. UNIT II STEADYSTATE REACTIVE POWER COMPENSATION IN TRANSMISSION SYSTEM 32
  • 19.  The demand of the reactive power is mainly originated from inductive load connected to the system .  These inductive loads generally electromagnetic circuit of electric motors, electrical transformers, distribution networks and induction furnaces etc.  Reactive power compensation is the defined as the management of reactive power to improve the  performance of AC system . There are two aspects : - 1. Load compensation 2. Voltage support Introduction 34
  • 21.  Active Power ( P ) : - It is the power that actuallypowers the equipment and performs useful work . Unitof it W .  Reactive Power ( Q ) : - It is the power that magneticequipment{ transformer , motor etc. } needs to produce the magnetizing flux . Unit of it VAr .  Apparent Power ( S ) : - It is the “ vectorial summation ” ofactive power ( P ) and reactive power ( Q ) . Unit of it VA . 36
  • 22. Reactive Power 37 •The portion of power flow that is temporarily stored in the form of magnetic or electric fields , due to inductive or capacitive network element and then returned to source is known as reactive power . •Reactive power can best be described as thequantity of “unused” power that is stored in reactive components , such as inductors or capacitors . In other words , the reactive circuit returns as muchpower to the supply as it consumes .
  • 23.  In resistive loads the current produces the heat energy which produces the desired output but incase of inductive loads the current creates the magnetic field which further produces the desired work.  Therefore reactive power is the non working power caused by the magnetic current to operate and sustain magnetism in the device .  Reactive power (vars) is required to maintain the voltage to deliver active power (watts) through transmission lines.  When there is not enough reactive power the voltage sags down and it is not possible to deliver the required power to load through the lines. Why do we need reactive power 38
  • 24. 1 40 : - Reactive power generated by the ac power source is stored in a reactor during a quarter of a cycle and in the next quarter of the cycle it is sent back to the power source. Therefore the reactive power oscillates between the ac source and the reactor at a frequency equals to two times the rated value (50 or 60 Hz). So to avoid the circulation between the load and source it needs to be compensate t o improve system power factor . Need for reactive power compensation
  • 25.  Reduce losses associated with the system .  Improves the voltage regulation in the network .  Increased system stability .  Reactive power levels have an effect on voltage  collapse . 41
  • 26. compensation Fig 5: Thyristor voltage waveforms (with delay α) 42
  • 28. Synchronous Condenser 44  Synchronous condensers are the active shunt compensators and have been used to improve the voltage profile and system stability . It is installed at the receiving end of the line .  When machine is overexcited , it acts as shunt capacitor as it supplies VAr to the system and when under excited it acts as a shunt coil as it absorbs reactive power to maintain terminal voltage.
  • 29.  The device that is connected in parallel with the transmission line for reactive power compensation is called the shunt compensator  It can be provided by either a current source, voltage source or a capacitor.If XC = 1/ωC be the reactance of the shunt capacitorthen the reactive power generated of leading VAr Shunt Compensation 45
  • 30. Transmission line with shunt compensation 46
  • 31.  Capacitor are connected in series in the lines and are used mainly for boosting the receiving end voltage, increase in transmission capacity and reduction in losses in the lines .  The capacitive reactance of series capacitor neutralizes the inductive reactance of the line hence ,reduces effective reactance of the line. Thereby , voltage regulation of the system is improved . Series Compensation 47
  • 32. Transmission line with series compensation 48
  • 33. VOLTAGE WAVEFORM Fig 9: Thyristor voltage waveforms 49
  • 34. UNIT III REACTIVE POWER COORDINATION 54
  • 35. Control objectives contributing to efficient and reliable operation of power system: 56 •Voltage at terminals of all equipment are within acceptable limits •both utility and customer equipment designed to operate at certain voltage rating •prolonged operation outside allowable range could cause them damage •System stability is satisfactory •voltage levels and reactive power control have significant impact on stability •The reactive power flow is minimized so as to reduce I 2R and I 2X losses to a practical minimum • ensures transmission system operates efficiently
  • 36. Production and Absorption of Reactive Power (Q) 57 •Synchronous Generators •can generate or absorb Q depending on excitation •capability limited by field current, armature current, and end-region heating limits •automatic voltage regulator continuously adjusts excitation to control armature voltage •primary source of voltage support! •Overhead lines •at loads below natural or surge impedance load (SIL), produce Q •at loads above SIL, absorb Q
  • 37.  Transformers  absorb Q due to shunt magnetizing reactance and series leakage inductance  Loads  a typical "load bus" is composed of a large number of devices  composite characteristics are normally such that a load bus absorbs Q  industrial loads usually have shunt capacitors to improve power factor Production and Absorption of Q 58
  • 38. Methods of Voltage Control 59  Control of voltage levels is accomplished by controlling the production, absorption, and flow of reactive power at all levels in the system  Generating units provide the basic means of voltage control
  • 39.  Shunt capacitors and reactors, and series capacitors provide passive compensation  are either permanently connected to the transmission and distribution system, or switched  contribute to voltage control by modifying the network characteristics  Synchronous condensers and SVCs provide active compensation; the reactive power absorbed/ supplied by them are automatically adjusted so as to maintain voltages of the buses to which they are connected Methods of Voltage Control 60
  • 40. Objectives of Reactive Power Compensation 61 To control voltage and/or improve maximum power transfer capability
  • 41.  Used to compensate the undesirable voltage effects associated with line capacitance  limit voltage rise on open circuit or light load  Shunt compensation with reactors: Shunt Reactors 62
  • 42.  Used in transmission systems to compensate for I 2X losses  Connected either directly to H.V. bus or to tertiary winding of transformers  Normally distributed throughout the system so as to minimize losses and voltage drops  Usually switched: a convenient means of controlling voltage  Shunt capacitor compensation of transmission lines in effect  decreases ZC  increases θ, i.e., electrical length  Advantages: low cost and flexibility of installation and operating Shunt Capacitors 63
  • 43.  Connected in series with the line  Used to reduce effective inductive reactance of line  increases maximum power  reduces I2X loss  Series capacitive compensation in effect reduces both:  characteristic impedance ZC, and  electrical length θ  Reactive power produced increases with increasing power transfer  Self regulating ! Series Capacitors 64
  • 44.  A synchronous machine running without a prime mover or a mechanical load  Depending on field excitation, it can either absorb or generate vars  With a voltage regulator, it can automatically adjust vars to maintain constant voltage  Started as an induction motor and then synchronized  Normally connected to tertiary windings of transformers  Unlike a SVC, a synchronous condenser has an internal voltage Synchronous Condenser 65
  • 45.  Shunt connected static var generators and/or absorbers whose outputs are varied so as to control specific power system quantities  The term static is used to denote that there are no moving or rotating components  Basic types of SVCs:  thyristor-controlled reactor  thyristor-switched capacitor  saturated reactor Static VAR Compensators (SVC) 66
  • 46. UNIT IV DEMAND SIDE MANAGEMENT 78
  • 47.  Supply-side management (SSM) refers to actions taken to ensure the generation, transmission and distribution of energy are conducted efficiently.  This has become especially important with the deregulation of the electricity industry in many countries, where the efficient use of available energy sources becomes essential to remain competitive.  Utility companies may look at means of modifying their load profile to allow their least efficient generating equipment to be used as little as possible. Supply side management: 80
  • 48. Why it is necessary? 81  To Ensure sustained availability of reliable energy  To Meet increasing electricity demand  To reduce environmental impact of energy production and supply
  • 50. 1.Clean coal technology 2.Fuel substitution Resources and resource preparation 83
  • 51. 1.Proper maintenance 2.Data and performance monitoring 3. Combustion control 4.Upgradation of generation unit Power generation and energy conversion 84
  • 52. 1.Transmission lines 2.Data monitoring and control 3. Load aggregation 4. Facts Transmission and distribution 85
  • 53.  SVC (Static Var Compensators),  Thyristor-Controlled Series Capacitors (TCSC) and Statcom.  PST (Phase-shifting Transformers),  IPC (Interphase Power Controllers),  UPFC (Universal Power Flow Controllers),  and DVR (Dynamic Voltage Restorers). Important devices power transmission involving FACTS and Power Quality devices: 86
  • 54.  It is also called as Energy Demand Management.  The modification of consumer demand for energy through various methods such as financial incentives and education is termed as Demand Side Management.  The main goal of demand side management is to encourage the consumer to use less energy during peak hours, or to move the time of energy use to off-peak times such as night time and weekends. Demand Side management 87
  • 55.  Definition - DSM (Demand Side Management) is the 'Scientific control of usage and demand of Electricity, for achieving better load factor and economy, by the Licensee/Supplier'. 88
  • 56. Benefits of Demand Side Management 89
  • 57. i) Monopoly power market structure. •ii) No competition which leads to traditional and inefficient tariff structure. •iii) Lack of creating awareness among consumers about the efficient use of energy. •iv) Lack of energy efficient environment. •v) Huge gap between supply and demand of energy. •vi) Lack of proper incentive schemes to consumer on using energy efficient appliances and utility to implement DSM solutions. •vii) Power system reliability, quality and stability is not able to keep itself in standard position. The barriers for DSM 90
  • 58.  Initiative from the consumer side is very important for successful DSM •The scope of DSM includes 1. Load shifting/ Load management 2. Energy conservation 3. Increased electrification Implementation of DSM 91
  • 59. 1.Develop end-use Demand forecasting •Forecasting by end-use is an essential pre-requisite for effective DSM planning and implementation. •Mid- and long-term forecasts of power demand variations play a very important role in the development of a DSM programme. •Demand forecasting is an exercise that every electricity- generating company should carry out regularly in order to assess its future equipment requirements. Planning & Implementation of DSM 92
  • 60. 2. Undertake Load/ Market Research to identify end-use patterns and market barriers •To design effective DSM programmes it is important to know how electricity is used and what barriers are preventing customers from using efficient technologies. •Load research should be undertaken to estimate load curves for each sector or region, using local sub-metering, customer bill analysis and customer surveys. •Major areas of interest to DSM programmes include the residential, commercial, industrial, and public utility sectors. •Market research is needed to understand the target market, identify barriers and evaluate possible solutions. Planning & Implementation of DSM 93
  • 62. 4. Identify target sectors, end-uses, and measures •The collected information is normally useful in determining a typical load curve for each end-use. •Find out load-curve management objectives •Choose sectors and end-uses that account for the largest power consumption and peak loads, or will do so in the future. •Select DSM measures which will have the largest impact on peak demand and electricity use. Planning & Implementation of DSM 95
  • 63. 5. Identify sources of financing •In any DSM programme, financing is needed for individual projects undertaken by participants. •Utilities may also require financing to cover administrative costs and cost sharing investments. •Government/public fund is required. Planning & Implementation of DSM 96
  • 64. 6. Review Cost Sharing and Viability Options •Cost sharing in a DSM programme should try to maximize viability for each partner (participant, utility, and government). •The wider the differences between tariffs, the higher the utility investment can be, which in turn leads to a higher participation rate. 97
  • 65. 7. Programme Selection and Design •Identifying a list of programmes for each customer class. •Formation of brief report corresponding to that program •Uniform reporting format is required. 98
  • 66. 8. DSM Cost/Benefit Analysis •Based on the case study /measurement •Calculation of financial interest 9. Identify Local Socio-Economic and Environmental Impacts •Most DSM programmes provide indirect economic and environmental benefits as well as reducing emissions and other impacts from power supply facilities. •Eg. employment is created in the energy services industry 99
  • 67. UNIT V USER SIDE REACTIVE POWER MANAGEMENT 100
  • 68. Control of voltage and reactive power should satisfy the followingobjectives: 1. Voltages at the terminals of all equipment in the system arewithin acceptable limits. 2. System stability is enhanced to maximize utilization of thetransmission system. Voltage and reactive power control havea significant impact on system stability. Methods of voltage control: 102
  • 69.  A. Sources or sinks of reactive power, such as shunt capacitors, shunt reactors, synchronous condensers, and static var compensators (SVCs).B. Line reactance compensators, such as series capacitors. C. Regulating transformers, such as tap- changing transformers and boosters.  Shunt capacitors and reactors, and series capacitors provide passive compensation. They are either permanently connected to the transmission and distribution system, or switched. They contribute to voltage control by modifying the networkcharacteristics.  Synchronous condensers and SVCs provide activecompensati on; the reactive power absorbed/supplied bythem is automatically adjusted so as to maintain voltagesof the buses to which they are connected. 103
  • 70. •Shunt capacitors supply reactive power and boost local voltages. •They are used throughout the system and are applied in a wide range of sizes •The principal advantages of shunt capacitors are their low costand their flexibility of installation and operation. • The principal disadvantage of shunt capacitors is that their •reactive power output is proportional to the square of the voltage. •The reactive power output is reduced at low voltages when it is likelyto be needed most. Shunt capacitor 104
  • 71.  Transformers with tap-changing facilities constitute an importantmeans of controlling voltage throughout the system at all voltagelevels.  The taps on transformers provide a convenient means of controlling reactive power flow between subsystems.  Coordinated control of the tap changers of all the transforme rs interconnecting the subsystems is required if the general level of voltage is to be changed.  During high system load conditions, the network voltages are kept at the highest practical level to minimize reactive power requirements and increasethe effectiveness of shunt capacitors and line charging. Application of Tap- Changing Transformers to Transmission Systems 105
  • 72.  During light load conditions, it is usually required to lower the networkvoltages to reduce line charging and avoid under excited operation of generators.  Transformers with off-load tap-changing facilities can also help maintainsatisfactory voltage profiles.  While transformers with ULTC can be used to take care of daily, hourly,and minute-by-minute variations in system conditions, settings of off-loadtap-changing transformers have to be carefully chosen depending on long-term variations due to system expansion, load growth, or seasonal changes. 106