International Journal of Power Electronics and Drive System (IJPEDS)
Vol.x, No.x, Month 201x, pp. xx~xx
ISSN: 2088-8694  34
Journal homepage: http://iaesjournal.com/online/index.php/IJPEDS
A Generalized Parameter Tuning Method of Proportional-
Resonant Controllers for Dynamic Voltage Restorers
Phuong Vu*, Ngoc Dinh*, Nam Hoang*, Quan Nguyen**, Dich Nguyen*, Minh Tran*
* School of Electrical Engineering, Hanoi University of Science and Technology, Hanoi, Vietnam
** Department of Electrical and Computer Engineering, The University of Texas at Austin, Texas, U.S.A
Article Info ABSTRACT
Article history:
Received Jun 12th
, 201x
Revised Aug 20th
, 201x
Accepted Aug 26th
, 201x
Temporary voltage swells and sags appear with high frequency in electric
power systems, and they significantly affect sensitive loads such as industrial
manufacturing or communication devices. This paper presents a strategy to
design proportional-resonant controllers for three full-bridge voltage-source
converters with a common DC-link in dynamic voltage restorer systems. The
proposed controllers allow the system to quickly overcome temporary
unbalanced voltage sags. Simulation results carried out in MATLAB/Simulink
and experimental results implemented in a Typhoon HIL402 device
demonstrate the ability of the proposed design method. The results show that
the system with the proposed controllers can ride-through single-phase or
double-phase voltage sags up to 55% and three-phase voltage sags up to 70%
in a duration less than one grid-voltage cycle.
Keyword:
Dynamic voltage restorer
Proportional-resonant controller
Hardware-in-the-loop
Copyright © 201x Institute of Advanced Engineering and Science.
All rights reserved.
Corresponding Author:
Phuong Vu,
School of Electrical Engineering, Hanoi University of Science and Technology,
No.1, Dai Co Viet Road, Hai Ba Trung, Hanoi, Vietnam,
Email: phuong.vuhoang@hust.edu.vn
1. INTRODUCTION
Power quality disturbances such as voltage sag and swell have been causing serious concerns for
modern distribution systems operated at low- and medium-voltage levels. The percentage of voltage sags
caused by single line-to-ground fault, double line-to-ground fault, and balanced three phase-to-ground fault in
power systems are 68%, 19%, 13%, respectively [1]. Such voltage variations in short durations (less than 60
seconds) lead to improper operation of sensitive loads, while longer voltage variations can result in sustained
interruptions or failures. Therefore, mitigating voltage sags and swells in low- and medium-voltage distribution
systems is critical.
One of the most solution to improve voltage regulation is dynamic voltage restorers (DVRs). The
operating principle of DVRs is to inject appropriate voltage in series and synchronism with the distorted AC
grid source to compensate for the amount of voltage sag or swell [2-4]. A DVR system includes an energy
storage, a three-phase voltage-source inverter, and series connected transformers between an AC grid source
and a load. Regarding the three-phase voltage-source inverters, it is necessary to control the positive-, negative-
, and zero-sequence components to compensate the voltage sag or swell of each phase [5]. Therefore, the
control scheme is complicated and insufficiently reliable. To eliminate voltage sags and swells, several
alternative topologies of DVR have been introduced such as a three-phase inverters with a neutral point created
by a DC-link capacitor, three-phase four-wire inverters, and three single-phase full-bridge inverters with a
common DC-link capacitor [6, 7]. The latter is preferred because of the simple pulse-width modulation (PWM)
method.
In DVR systems using three full-bridge inverters with a common DC-link capacitor, several control
approaches have been suggested. A coordination of both feed-back and feed-forward control in synchronously
rotating frame dq is introduced in [8, 9]. However, this topology does not have current loops to compensate for
the losses in the transformers and output filter, which leads to a slow voltage response. Another approach is to
IJPEDS ISSN: 2088-8694 
Title of manuscript is short and clear, implies research results (First Author)
35
implement proportional-resonant (PR) or Hinf control for the voltage loop and proportional (P) control for the
current loop in the stationary frame αβ [10]. However, controlling only two components of αβ frame as
presented in this approach is not effective when the voltage sag is unbalanced, which is the typical case in
practice. A P control for both voltage and current loops with independent controllers between each phase is
proposed in [11]. This approach is unable to eliminate the steady-state error in spite of its fast response. A
multi-loop with PI controllers is applied to DVR systems in [12], but steady-state error also exists.
From this literature review, the control strategy using PR controllers for both current and voltage loops
is the most effective for DVR systems to improve dynamic response and eliminate steady-state error [13]. To
the best knowledge of the authors, little research has been done to elaborate on the process of determining
parameters for PR controllers, which is highly complicated. Several studies apply trial and error procedures to
obtain the parameters of PR controllers [14]. Another approach to design PR controllers is based on the SISO
design tool in MATLAB and system dynamic response [15]. Such methods are time-consuming and not
generalized.
This paper proposes a systematic and generalized design method for PR voltage and current
controllers of three single-phase full-bridge inverters with a common DC-link capacitor in DVR systems. The
major contributions of this paper includes:
 An equivalent circuit of full-bridge inverters and series connected transformers in a DVR system.
Unlike other existing methods, the model of the series transformers is taken into account in this paper when
designing the controllers for the DVR system.
 A method to design parameters of PR controllers in the frequency domain for both current and
voltage loops to guarantees system stability with a desired cross-over frequency and phase margin. The
discretization in the z-domain of the designed PR controllers for digital implementation is also included.
 An approach to verify the proposed controller by hardware-in-the-loop (HIL) real-time
experiments using a Typhoon HIL402 device. HIL simulation has been highly recommended as an effective
design approach with the ease in modifying controller parameters and creating different operating scenarios of
grid voltage [16-18].
The remainder of this paper is organized as follows. Section 2 describes the general control topology and
the model of a DVR system including the equivalent circuit of full-bridge inverters and series transformers.
The proposed design in the frequency domain of the PR current and voltage controllers is presented based on
the developed equivalent model. The discretization of the designed PR controller is also included. Section 3
demonstrates the efficacy of the proposed method by off-line simulation and HIL real-time experiments using
Typhoon HIL402 system.
2. CONTROL SCHEME
A scalar control scheme for three full-bridge inverters with a common DC-link capacitor in a DVR
system is shown in Fig. 1. Similar controllers are applied separately for each phase corresponding to each H-
bridge inverter. In this control scheme, voltages and currents of all phases are controlled independently using
nested control loops. At each phase, the outer voltage control loop regulates the voltage at the secondary side
of the transformer while the inner current loop regulates the output current of the H-bridge inverter. The set
points of the current loop are the output of the voltage loop, while the set points of the voltage loop are
calculated based on the root-mean-square (RMS) values of the desired voltage (for example, 220 V) and the
grid voltage. In the proposed control approach, since the instantaneous voltage and current are measured, PR
controllers are chosen to eliminate the steady-state error. The resonant frequencies of the PR controllers are
equal to the grid frequency. In addition, phase-locked loop (PLL), which is required for grid synchronization,
is implemented by measuring the voltage at each phase of the grid source. In this paper, a phase-locked loop
(PLL) algorithm based on a second-order generalized integrator phase-locked loop (SOGI PLL) is used [19].
To properly design PR controllers, the model of series transformers in a DVR system should be taken
into account. The equivalent circuit of each H-bridge and the simplified model of the transformer referred to
the secondary side are shown in Fig. 2. The leakage impedance of the transformer and capacitance result in a
second-order low-pass filter. The equivalent impedance referred to the secondary side of the transformer is
given as follows:
12 2
,
p p
eqS s s
r x
Z r j x R j L
N N
(1)
where N is the turns ratio of the transformer, rp and rs are the resistances of the primary and secondary windings,
px and sx are the leakage inductances of the primary and secondary windings, and R and L are the resulting
resistance and inductance of the equivalent impedance.
 ISSN: 2088-8694
IJECE Vol. x, No. x, Month 201x : xx – xx
36
Cdc
FB Phase A
FB Phase B
FB Phase C
700 V
S1,2,3,4a
S1,2,3,4b
S1,2,3,4c
Sin
PWM
Udc
Supply
isa
isb
is uc
PR
is
* uabc
is
uc
VAVC_ref
N:1
Voltage controllers Current controllers
+
-
+
-
PR
θ
Sensitive load
PLL
vgrid
Vgrid_RMSVref_RMS
220
x
vref
S4
S1
S2
S3
Udc
+
-
-
+
Full bridge
V0_ref_RMS
RMS
isc
vinj
vinj
vinj
vsa
vsb
vsc
C
C
C
Figure 1. Control topology of the inverter in DVR.
Xm
rm
Xσp/N2
rs Xσp
vinj C
Grid
Load
S4
S1
S2
S3
Udc
+
-
-
+
vsa/N
Nisa
rp/N2
Figure 2. Equivalent circuit of per phase and series connected transformer.
A PR controller has an infinite gain at a selected resonant frequency; thus, the zero steady-state error or
the harmonic at this frequency can be eliminated. The transfer function of a PR controller is mathematically
expressed as follows [20]:
22
1
.c r
PR p
k s
G s k
s
(2)
where pk and rk are the coefficients of the PR controller while 1 is a selected frequency. The frequency
response characteristics of the PR controller are calculated as follows:
2
2 2 2 2 2
1
2 2
1
p r
PR
k k
G j (3)
2 2
0
arctan .r
PR
p
k
G j
k
(4)
From (3), it can be seen that the PR controller has an infinite gain at 1 . In [21], the transfer function of the
PR controller with the delay compensation can be written as follows:
IJPEDS ISSN: 2088-8694 
Title of manuscript is short and clear, implies research results (First Author)
37
1
22
1
cos sin
.
d dc
PR p r
s
G s k k
s
(5)
The delay can be compensated by adding a lead angle  1d skT  to the inverse Park transform angle, where
k is an integer representing the number of periods to be compensated [21]. In this paper, k is set to 1. To avoid
an algebraic loop during the discrete implementation, it is suggested that the direct integrator is discretized
using the forward method while the feedback integrator is discretized using the backward method [20, 21]. The
PR controller with the delay compensation and discrete PR controller is shown in Fig. 3.
y
kr
kp
1
s
2
1
1
s
cos(θd)
ω1sin(θd)
x vu
a. The PR controller with the delay compensation.
x
y
kr
kp
2
1
cos(θd)
ω1sin(θd)
z-1
Delay
1
1
sT
z
1
1
sT
z
vu vpre
b. The resulting discrete PR controller.
Figure 3. Block diagram of PR controllers.
3.1 Design the PR controller for the inner current loop
From Fig. 1 and Fig. 2, the plant transfer function of current control loop in series converter is determined as
follows:
 
 
  2 2
1
.
1
sa
iv
sa
i s sC
G s
v s N s L C sRC
 
 
(6)
The cross-over frequency is usually selected to be far lower than the sampling frequency fs. On the other hand,
the cross-over frequency fc is significantly higher than the grid frequency f1. From (3),
C
PR pcG j k .
The parameter pck of the PR regulator for the current loop is thus determined as follows:
1
1
.
ci ci
ci
PRc iv
pc
iv
G j G j
k
G j
(7)
Next, based on the desired phase margin cPM of whole system, the parameter rck of the PR controller for the
current loop is chosen such that:
0
+ 180 .
ci ci
c PRc ivPM G j G j (8)
Therefore, the parameter rck of the PR regulator is determined as follows:
2 2
1
arctan r ci
c
p ci
k
A
k
(8)
2 2
0tan
,
c p ci
rc
ci
A k
k (10)
where 0
- 180
C
c c ivA PM G j .
3.2 Design the PR controller for the outer voltage loop
From Fig. 2, the plant transfer function of voltage control loop in series converter is determined as follows:
 ISSN: 2088-8694
IJECE Vol. x, No. x, Month 201x : xx – xx
38
 
 
 
1
.
inj
vi
c
v s
G s
i s Cs
  (9)
The magnitude-frequency and phase-frequency response of  viG s can be written as follows:
    01
, 90vi viG j G j
C
 

    (10)
1
.
cv cv
PRv iv
pv cv
G j G j
k C
(11)
From the desired phase margin vPM of whole system, the parameter rvk of the PR controller is chosen such
that:
0
+ 180 .
cv cv
v PRv viPM G j G j (12)
Therefore, the parameter rvk of the PR regulator is determined as follows:
2 2
1
arctan rv cv
v
pv cv
k
A
k
(13)
2 2
0tan
,
v p cv
rv
cv
A k
k (16)
where
0
-90v vA PM .
3. RESULTS AND ANALYSIS
3.1. Simulation results
The proposed control topology is validated using MATLAB/Simulink/Simpower Systems. The DC
voltage is 700VDC while the transformer turns ratio N is 2. The total of leakage inductance L in (1) is
0.2975mH, the filter capacitance C is 30µF, and the switching frequency fs is 5kHz. Unipolar PWM technique
is implemented to control the switching of the IGBT switches of the H-bridge inverters [19]. The phase margin
and cross-over frequency of current loop are chosen to be 450
and 500Hz, respectively. The phase margin and
cross-over frequency of voltage loop are chosen to be 450
, and 200Hz, respectively.
This paper investigates the following transient scenarios of the grid voltage: single-phase 55% voltage
sag (0.1-0.2s), double-phase 55% voltage sag (0.25-0.35s), and three-phase 70% voltage sag (0.4-0.5s). The
RMS value of the phase-to-phase grid voltage is 380 VAC, i.e. the phase-to-neutral voltage is 220VAC. The
three-phase voltage sags are created by a programmable voltage source in Matlab/Simpowwer Systems.
0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
-400
-200
0
200
400
0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
-200
-100
0
100
200
0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
-400
-200
0
200
400
Supply
voltage(V)
Injected
voltage(V)
Load
voltage(V)
Time(s)
Figure 4. Measured response of DVR (grid voltages,
voltages injected by the DVR, load voltages).
0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
-150
-100
-50
0
50
100
150
0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
-200
-100
0
100
200
Injected
voltage_phasea(V)
Inverter
current_phasea(A)
Ref
Act
Ref-Act
Ref-Act
Time (s)
Figure 5. The reference and actual voltage and current of
phase a.
IJPEDS ISSN: 2088-8694 
Title of manuscript is short and clear, implies research results (First Author)
39
Fig. 4 and Fig.5 show the response of the DVR system with the proposed control during the supply
voltage sags. It is clear that the DVR is able to restore correctly to the nominal value within just one cycle of
grid voltage (20 ms). The overshoots of the load voltage are negligible, and the steady-state error of injected
voltage and inverter current is eliminated in the three cases in Fig.5. A dramatic part of the delay is due to the
calculation of the root mean square (RMS) of supply voltage.
3.2. Hardware-in-the-loop experimental results
The proposed control is also verified in HIL environment using a Typhoon device. This device
consists of an HIL402 card that simulates grid source, load, and three full-bridge with a common DC-link
capacitor using IGBTs. The hardware system is simulated in real time on the HIL platform with a time step of
1 μs, which is close to the physical model. The carrier frequency of the PWM is 5 kHz. The voltage and current
controllers as well as PLL are implemented in the DSP TMS320F2808 card.
All data of HIL is recorded by the Typhoon HIL Control Center Software and shown in Fig.6. The
load voltage and the injected voltage from the DVR system are measured using the oscilloscope HAMEG –
200MHz at test points in the HIL DSP interface of Typhoon. These voltages are shown in Fig.7. It is clear that
the responses of the HIL experimental results are similar to those in the simulation results in MATLAB. The
DVR system is able to regulate the load voltage with an ignorable overshoot within an acceptable period (less
than 20 ms) in the injection mode. When supply voltage stable at the nominal value, the DVR system is
operated in the standby mode, which means no voltage is injected.
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
-400
-200
0
200
400
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
-200
-100
0
100
200
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
-500
0
500
Supply
voltage(V)
Injected
Voltage(V)
Load
Voltage(V)
Time (s)
Fig. 6. HIL experimental results: supply voltage, injected voltage, and load voltage.
Load voltages Load voltages Load voltages
 ISSN: 2088-8694
IJECE Vol. x, No. x, Month 201x : xx – xx
40
Voltages injected by the DVR. Voltages injected by the DVR. Voltages injected by the DVR.
a. Single-phase 55% voltage sag b. Double-phase 55% voltage sag c. Three-phase 70% voltage sag.
Figure 7. HIL experimental results in different operating conditions.
4. CONCLUSION
This paper proposes a systematic and generalized design method for PR controllers of three single-phase
full-bridge inverters with a common DC-link capacitor in DVR systems. The proposed control is designed for
each single-phase inverter, taken into account the model of the series transformers. MATLAB and the HIL
experimental results validate the performance of voltage in scenarios: single-phase and double phase voltage
sags up to 55%, and three-phase voltage sag up to 70% within acceptable periods. The results prove that the
DVR system is able to protect the load from voltage sags due to these various types of faults. Such promising
results create a crucial foundation for the application of DVR systems in industry.
ACKNOWLEDGEMENTS
This research was funded by the Ministry of Science and Technology (Vietnam) under project number
KC.05.03/16-20.
REFERENCES
[1] ABB, PCS100 AVC-40 - Active Voltage conditioner.
[2] J. G. Nielsen and F. Blaabjerg, "A detailed comparison of system topologies for dynamic voltage restorers," in IEEE
Transactions on Industry Applications, vol. 41, no. 5, pp. 1272-1280, Sept.-Oct. 2005.
[3] Syed Suraya, P. Sujatha, P. Bharat Kumar, “A Novel Control Strategy for Compensation of Voltage Quality Problem
in AC Drives”, International Journal of Power Electronics and Drive System (IJPEDS), Vol. 9, No. 1, March 2018,
pp. 8~16 ISSN: 2088-8694, DOI: 10.11591/ijpeds.v9n1.pp8-16.
[4] Brahim Ferdi, Samira Dib, Brahim Berbaoui, Rachid Dehini, “Design and Simulation of Dynamic Voltage Restorer
Based on Fuzzy Controller Optimized by ANFIS,” International journal of power electronics and drive systems
(IJPEDS), Vol 4, No 2: June 2014, pp 212-222.
[5] H. Awad, J. Svensson and M. Bollen, "Mitigation of unbalanced voltage dips using static series compensator,"
in IEEE Transactions on Power Electronics, vol. 19, no. 3, pp. 837-846, May 2004.
[6] S. R. Naidu and D. A. Fernandes, "Dynamic voltage restorer based on a four-leg voltage source converter," in IET
Generation, Transmission & Distribution, vol. 3, no. 5, pp. 437-447, May 2009.
[7] Seon-Yeong Jeong, Thanh Hai Nguyen, Quoc Anh Le, and Dong-Choon Lee, “High-Performance Control of Three-
Phase Four- Wire DVR Systems using Feedback Linearization”, Journal of Power Electronics, Vol. 16, No. 1, pp.
351-361, January 2016.
[8] J. G. Nielsen, M. Newman, H. Nielsen and F. Blaabjerg, "Control and testing of a dynamic voltage restorer (DVR)
at medium voltage level," in IEEE Transactions on Power Electronics, vol. 19, no. 3, pp. 806-813, May 2004.
[9] Hyosung Kim and Seung-Ki Sul, "Compensation voltage control in dynamic voltage restorers by use of feed forward
and state feedback scheme," in IEEE Transactions on Power Electronics, vol. 20, no. 5, pp. 1169-1177, Sept. 2005.
[10] Y. W. Li, F. Blaabjerg, D. M. Vilathgamuwa and P. C. Loh, "Design and Comparison of High Performance
Stationary-Frame Controllers for DVR Implementation," in IEEE Transactions on Power Electronics, vol. 22, no. 2,
pp. 602-612, March 2007.
[11] F. B. Ajaei, S. Afsharnia, A. Kahrobaeian and S. Farhangi, "A Fast and Effective Control Scheme for the Dynamic
Voltage Restorer," in IEEE Transactions on Power Delivery, vol. 26, no. 4, pp. 2398-2406, Oct. 2011.
[12] Amit Meena, Shirazul Islam, Sandeep Anand, Yogesh Sonawane, Sanjay Tungare, “Design and control of single-
phase dynamic voltage restorer”, Springer India, August 2017, Volume 42, Issue 8, pp 1363–1375.
[13] 1. S. Andrews and S. Joshi, "Performance Improvement of Dynamic Voltage Restorer using Proportional - Resonant
Controller," Proceedings of PCIM Europe 2015; International Exhibition and Conference for Power Electronics,
Intelligent Motion, Renewable Energy and Energy Management, Nuremberg, Germany, 2015, pp. 1-8.
IJPEDS ISSN: 2088-8694 
Title of manuscript is short and clear, implies research results (First Author)
41
[14] hen, K.C., Salimin, S, Zulkifli, S.A., and Aziz, R. Single phase inverter system using proportional resonant current
control. International Journal of Power Electronics and Drive Systems. 8. 1913-1918. 10.11591/ijpeds.v8i4.pp1913-
1918.
[15] Daniel Zammit, Cyril Spiteri Staines, Maurice Apap, John Licari, Design of PR current control with selective
harmonic compensators using Matlab, Journal of Electrical Systems and Information Technology, Volume 4, Issue
3, 2017, Pages 347-358, ISSN 2314-7172, https://doi.org/10.1016/j.jesit.2017.01.003.
[16] Typhoon HIL, “Inverter Testing & Pre-certification with HIL Testing”. Available: https://www.typhoon-
hil.com/applications/converter-testing.
[17] Z. R. Ivanović, E. M. Adžić, M. S. Vekić, S. U. Grabić, N. L. Čelanović and V. A. Katić, "HIL Evaluation of Power
Flow Control Strategies for Energy Storage Connected to Smart Grid Under Unbalanced Conditions," in IEEE
Transactions on Power Electronics, vol. 27, no. 11, pp. 4699-4710, Nov. 2012.
[18] M. S. Vekić, S. U. Grabić, D. P. Majstorović, I. L. Čelanović, N. L. Čelanović and V. A. Katić, "Ultralow Latency
HIL Platform for Rapid Development of Complex Power Electronics Systems," in IEEE Transactions on Power
Electronics, vol. 27, no. 11, pp. 4436-4444, Nov. 2012.
[19] R. Teodorescu, M. Liserre, and P. Rodrguez, Grid converters for photovoltaic and wind power systems. John Wiley,
Ltd, 2011.
[20] R. Teodorescu, F. Blaabjerg, U. Borup and M. Liserre, "A new control structure for grid-connected LCL PV inverters
with zero steady-state error and selective harmonic compensation," Applied Power Electronics Conference and
Exposition, 2004. APEC '04. Nineteenth Annual IEEE, 2004, pp. 580-586 Vol.1.
[21] M. S. Lima, L. A. d. S. Ribeiro and J. G. de Matos, "Comparison analysis of resonant controllers in discrete domain
taking into account the computational delay," 2015 IEEE 13th Brazilian Power Electronics Conference and 1st
Southern Power Electronics Conference (COBEP/SPEC), Fortaleza, 2015, pp. 1-6.
BIBLIOGRAPHY OF AUTHORS
Phuong Vu received his B.S., M.S., and Ph.D. degrees from Hanoi University of Science and
Technology, Vietnam, in 2006, 2008, and 2014, respectively, all in Control Engineering and
Automation. Since 2006 he has been employed at Hanoi University of Science and Technology,
where he is a lecturer and researcher at school of electrical engineering. His research interests
include modeling and controlling of power electronics converters for applications such as
photovoltaic, wind system, electrical machine drive.
Ngoc Dinh was born 1994. He received his Engineer’s degree from Hanoi University of Science
and Technology, Vietnam in 2017, in Electrical Engineering. He is currently pursuing M.Sc at
Hanoi University of Science and Technology and working Institute for Control Engineering and
Automation - ICEA. He research interests are power electronics on the DSP and FPGA platform.
Nam Hoang was born 1994. He received his Engineer’s degree from Hanoi University of Science
and Technology, Vietnam in 2017, in Electrical Engineering. He is currently pursuing M.Sc at
Hanoi University of Science and Technology. He research interests are multilevel converter and
power electronics.
Quan Nguyen received his Bachelor’s degree from Hanoi University of Science and Technology,
Vietnam in 2012 and the M.S degree from The University of Texas at Austin, USA in 2016, both
in Electrical Engineering. He is currently pursuing a PhD at The University of Texas at Austin.
His research interests are power system control and optimization, renewable energy integration,
power quality, and power electronics.
Minh Tran received his B.S. degree Technical university in Bacu, in 1983. He received his M.S.
degree from Asian Institute of Technology, Thailand and Ph.D from Hanoi University of Science
and Technology, Vietnam, in 2007 and 2014, respectively. Since1983, he has been with Hanoi
University of Science and Technology, Vietnam, where he is currently an Associate Professor and
Executive Dean of the Department of Industrial Automation. His research interests include
modelling and controlling of power converters, multilevel converter, HVDC transmission
technology.

More Related Content

What's hot

A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...IAES-IJPEDS
 
Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Maximise Efficiency & Reliability - Maintain ‘healthy’ electrical network wit...
Maximise Efficiency & Reliability - Maintain ‘healthy’ electrical network wit...Maximise Efficiency & Reliability - Maintain ‘healthy’ electrical network wit...
Maximise Efficiency & Reliability - Maintain ‘healthy’ electrical network wit...Eng Yong CH'NG, CEng MEI, CEM, CMVP, PEM
 
A Predictive Control Strategy for Power Factor Correction
A Predictive Control Strategy for Power Factor CorrectionA Predictive Control Strategy for Power Factor Correction
A Predictive Control Strategy for Power Factor CorrectionIOSR Journals
 
Basic Configurations of Thyristor Controlled Phase Shifting Transformer or Ph...
Basic Configurations of Thyristor Controlled Phase Shifting Transformer or Ph...Basic Configurations of Thyristor Controlled Phase Shifting Transformer or Ph...
Basic Configurations of Thyristor Controlled Phase Shifting Transformer or Ph...SushovanRoy12
 
Modified three phase Unified Power Quality Conditioner with capacitor midpoin...
Modified three phase Unified Power Quality Conditioner with capacitor midpoin...Modified three phase Unified Power Quality Conditioner with capacitor midpoin...
Modified three phase Unified Power Quality Conditioner with capacitor midpoin...IOSR Journals
 
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...INFOGAIN PUBLICATION
 
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...IRJET Journal
 
Advanced techniques of PULSE WIDTH MODULATION.
Advanced techniques of PULSE WIDTH MODULATION.Advanced techniques of PULSE WIDTH MODULATION.
Advanced techniques of PULSE WIDTH MODULATION.Subashini Puchalapalli
 
Sine Pulse Width Modulation Inverter
Sine Pulse Width Modulation InverterSine Pulse Width Modulation Inverter
Sine Pulse Width Modulation InverterAditya Parmar
 
Space Vector Pulse Width Modulation Technique Applied to Two Level Voltage So...
Space Vector Pulse Width Modulation Technique Applied to Two Level Voltage So...Space Vector Pulse Width Modulation Technique Applied to Two Level Voltage So...
Space Vector Pulse Width Modulation Technique Applied to Two Level Voltage So...Qusai Abdelrahman
 
Unified Power Flow Controller(upfc) 2
Unified Power Flow Controller(upfc) 2Unified Power Flow Controller(upfc) 2
Unified Power Flow Controller(upfc) 2JayakalyanReddy
 
A Novel Control Strategy of Indirect Matrix Converter Using Space Vector Modu...
A Novel Control Strategy of Indirect Matrix Converter Using Space Vector Modu...A Novel Control Strategy of Indirect Matrix Converter Using Space Vector Modu...
A Novel Control Strategy of Indirect Matrix Converter Using Space Vector Modu...IJPEDS-IAES
 
A Simple Strategy of Controlling a Balanced Voltage Capacitor in Single Phase...
A Simple Strategy of Controlling a Balanced Voltage Capacitor in Single Phase...A Simple Strategy of Controlling a Balanced Voltage Capacitor in Single Phase...
A Simple Strategy of Controlling a Balanced Voltage Capacitor in Single Phase...IAES-IJPEDS
 

What's hot (19)

A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
 
Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)
 
Maximise Efficiency & Reliability - Maintain ‘healthy’ electrical network wit...
Maximise Efficiency & Reliability - Maintain ‘healthy’ electrical network wit...Maximise Efficiency & Reliability - Maintain ‘healthy’ electrical network wit...
Maximise Efficiency & Reliability - Maintain ‘healthy’ electrical network wit...
 
Km3518071813
Km3518071813Km3518071813
Km3518071813
 
B360614
B360614B360614
B360614
 
A Predictive Control Strategy for Power Factor Correction
A Predictive Control Strategy for Power Factor CorrectionA Predictive Control Strategy for Power Factor Correction
A Predictive Control Strategy for Power Factor Correction
 
Basic Configurations of Thyristor Controlled Phase Shifting Transformer or Ph...
Basic Configurations of Thyristor Controlled Phase Shifting Transformer or Ph...Basic Configurations of Thyristor Controlled Phase Shifting Transformer or Ph...
Basic Configurations of Thyristor Controlled Phase Shifting Transformer or Ph...
 
Modified three phase Unified Power Quality Conditioner with capacitor midpoin...
Modified three phase Unified Power Quality Conditioner with capacitor midpoin...Modified three phase Unified Power Quality Conditioner with capacitor midpoin...
Modified three phase Unified Power Quality Conditioner with capacitor midpoin...
 
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
 
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...
 
L43067578
L43067578L43067578
L43067578
 
digital
digitaldigital
digital
 
Advanced techniques of PULSE WIDTH MODULATION.
Advanced techniques of PULSE WIDTH MODULATION.Advanced techniques of PULSE WIDTH MODULATION.
Advanced techniques of PULSE WIDTH MODULATION.
 
Sine Pulse Width Modulation Inverter
Sine Pulse Width Modulation InverterSine Pulse Width Modulation Inverter
Sine Pulse Width Modulation Inverter
 
Space Vector Pulse Width Modulation Technique Applied to Two Level Voltage So...
Space Vector Pulse Width Modulation Technique Applied to Two Level Voltage So...Space Vector Pulse Width Modulation Technique Applied to Two Level Voltage So...
Space Vector Pulse Width Modulation Technique Applied to Two Level Voltage So...
 
Unified Power Flow Controller(upfc) 2
Unified Power Flow Controller(upfc) 2Unified Power Flow Controller(upfc) 2
Unified Power Flow Controller(upfc) 2
 
A Novel Control Strategy of Indirect Matrix Converter Using Space Vector Modu...
A Novel Control Strategy of Indirect Matrix Converter Using Space Vector Modu...A Novel Control Strategy of Indirect Matrix Converter Using Space Vector Modu...
A Novel Control Strategy of Indirect Matrix Converter Using Space Vector Modu...
 
Ijaret 06 08_006
Ijaret 06 08_006Ijaret 06 08_006
Ijaret 06 08_006
 
A Simple Strategy of Controlling a Balanced Voltage Capacitor in Single Phase...
A Simple Strategy of Controlling a Balanced Voltage Capacitor in Single Phase...A Simple Strategy of Controlling a Balanced Voltage Capacitor in Single Phase...
A Simple Strategy of Controlling a Balanced Voltage Capacitor in Single Phase...
 

Similar to [7] a generalized parameter tuning method of proportional resonant controllers for dynamic voltage restorers

Control of grid connected inverter system for sinusoidal current injection wi...
Control of grid connected inverter system for sinusoidal current injection wi...Control of grid connected inverter system for sinusoidal current injection wi...
Control of grid connected inverter system for sinusoidal current injection wi...ijiert bestjournal
 
[9] a systematic parameter tuning of pi current controller for lcl type activ...
[9] a systematic parameter tuning of pi current controller for lcl type activ...[9] a systematic parameter tuning of pi current controller for lcl type activ...
[9] a systematic parameter tuning of pi current controller for lcl type activ...Ngoc Dinh
 
The Need for Enhanced Power System Modelling Techniques and Simulation Tools
The Need for Enhanced Power System Modelling Techniques and Simulation ToolsThe Need for Enhanced Power System Modelling Techniques and Simulation Tools
The Need for Enhanced Power System Modelling Techniques and Simulation ToolsPower System Operation
 
Power Factor Improvement in Distribution System using DSTATCOM Based on Unit ...
Power Factor Improvement in Distribution System using DSTATCOM Based on Unit ...Power Factor Improvement in Distribution System using DSTATCOM Based on Unit ...
Power Factor Improvement in Distribution System using DSTATCOM Based on Unit ...RSIS International
 
Small Signal Modeling Of Controller For Statcom Used In Distribution System F...
Small Signal Modeling Of Controller For Statcom Used In Distribution System F...Small Signal Modeling Of Controller For Statcom Used In Distribution System F...
Small Signal Modeling Of Controller For Statcom Used In Distribution System F...IJERA Editor
 
Enhancement of Power System Dynamics Using a Novel Series Compensation Scheme
Enhancement of Power System Dynamics Using a Novel Series Compensation SchemeEnhancement of Power System Dynamics Using a Novel Series Compensation Scheme
Enhancement of Power System Dynamics Using a Novel Series Compensation SchemeIJMER
 
ijre paper
ijre paperijre paper
ijre paperNithin S
 
A New Multilevel Active Power Filter Using Switches Meticulously Controlled
A New Multilevel Active Power Filter Using Switches Meticulously ControlledA New Multilevel Active Power Filter Using Switches Meticulously Controlled
A New Multilevel Active Power Filter Using Switches Meticulously ControlledIAES-IJPEDS
 
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...paperpublications3
 
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...Venkata Gowtam Nallamothu
 

Similar to [7] a generalized parameter tuning method of proportional resonant controllers for dynamic voltage restorers (20)

www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 
Control of grid connected inverter system for sinusoidal current injection wi...
Control of grid connected inverter system for sinusoidal current injection wi...Control of grid connected inverter system for sinusoidal current injection wi...
Control of grid connected inverter system for sinusoidal current injection wi...
 
Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...
Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...
Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...
 
Reduction in Current THD of Grid Parallel Inverters Using Randomized PR Control
Reduction in Current THD of Grid Parallel Inverters Using Randomized PR ControlReduction in Current THD of Grid Parallel Inverters Using Randomized PR Control
Reduction in Current THD of Grid Parallel Inverters Using Randomized PR Control
 
[9] a systematic parameter tuning of pi current controller for lcl type activ...
[9] a systematic parameter tuning of pi current controller for lcl type activ...[9] a systematic parameter tuning of pi current controller for lcl type activ...
[9] a systematic parameter tuning of pi current controller for lcl type activ...
 
Y04408126132
Y04408126132Y04408126132
Y04408126132
 
The Need for Enhanced Power System Modelling Techniques and Simulation Tools
The Need for Enhanced Power System Modelling Techniques and Simulation ToolsThe Need for Enhanced Power System Modelling Techniques and Simulation Tools
The Need for Enhanced Power System Modelling Techniques and Simulation Tools
 
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
 
Power Factor Improvement in Distribution System using DSTATCOM Based on Unit ...
Power Factor Improvement in Distribution System using DSTATCOM Based on Unit ...Power Factor Improvement in Distribution System using DSTATCOM Based on Unit ...
Power Factor Improvement in Distribution System using DSTATCOM Based on Unit ...
 
Small Signal Modeling Of Controller For Statcom Used In Distribution System F...
Small Signal Modeling Of Controller For Statcom Used In Distribution System F...Small Signal Modeling Of Controller For Statcom Used In Distribution System F...
Small Signal Modeling Of Controller For Statcom Used In Distribution System F...
 
Kf3517721775
Kf3517721775Kf3517721775
Kf3517721775
 
Enhancement of Power System Dynamics Using a Novel Series Compensation Scheme
Enhancement of Power System Dynamics Using a Novel Series Compensation SchemeEnhancement of Power System Dynamics Using a Novel Series Compensation Scheme
Enhancement of Power System Dynamics Using a Novel Series Compensation Scheme
 
E04724148
E04724148E04724148
E04724148
 
Ib3313831387
Ib3313831387Ib3313831387
Ib3313831387
 
Ib3313831387
Ib3313831387Ib3313831387
Ib3313831387
 
An Analysis of Virtual Flux Direct Power Control of Three-Phase AC-DC Converter
An Analysis of Virtual Flux Direct Power Control of Three-Phase AC-DC ConverterAn Analysis of Virtual Flux Direct Power Control of Three-Phase AC-DC Converter
An Analysis of Virtual Flux Direct Power Control of Three-Phase AC-DC Converter
 
ijre paper
ijre paperijre paper
ijre paper
 
A New Multilevel Active Power Filter Using Switches Meticulously Controlled
A New Multilevel Active Power Filter Using Switches Meticulously ControlledA New Multilevel Active Power Filter Using Switches Meticulously Controlled
A New Multilevel Active Power Filter Using Switches Meticulously Controlled
 
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
 
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
 

More from Ngoc Dinh

[10] test bench setup for active voltage conditioner in low voltage
[10] test bench setup for active voltage conditioner in low voltage[10] test bench setup for active voltage conditioner in low voltage
[10] test bench setup for active voltage conditioner in low voltageNgoc Dinh
 
[8] implementation of pmsm servo drive using digital signal processing
[8] implementation of pmsm servo drive using digital signal processing[8] implementation of pmsm servo drive using digital signal processing
[8] implementation of pmsm servo drive using digital signal processingNgoc Dinh
 
[6] pr controllers for series converter in active voltage conditioner
[6] pr controllers for series converter in active voltage conditioner[6] pr controllers for series converter in active voltage conditioner
[6] pr controllers for series converter in active voltage conditionerNgoc Dinh
 
[5] the simulated series converter in active voltage conditioner
[5] the simulated series converter in active voltage conditioner[5] the simulated series converter in active voltage conditioner
[5] the simulated series converter in active voltage conditionerNgoc Dinh
 
[4] a control of active rectifier in unbalanced grid condition
[4] a control of active rectifier in unbalanced grid condition[4] a control of active rectifier in unbalanced grid condition
[4] a control of active rectifier in unbalanced grid conditionNgoc Dinh
 
[3] simulation active voltage conditioner converter for load three phase
[3] simulation active voltage conditioner converter for load three phase[3] simulation active voltage conditioner converter for load three phase
[3] simulation active voltage conditioner converter for load three phaseNgoc Dinh
 
[1] a control of stand alone photovoltaic water
[1] a control of stand alone photovoltaic water[1] a control of stand alone photovoltaic water
[1] a control of stand alone photovoltaic waterNgoc Dinh
 
[2] the control of active rectifier base on hil402 platform
[2] the control of active rectifier base on hil402 platform[2] the control of active rectifier base on hil402 platform
[2] the control of active rectifier base on hil402 platformNgoc Dinh
 

More from Ngoc Dinh (8)

[10] test bench setup for active voltage conditioner in low voltage
[10] test bench setup for active voltage conditioner in low voltage[10] test bench setup for active voltage conditioner in low voltage
[10] test bench setup for active voltage conditioner in low voltage
 
[8] implementation of pmsm servo drive using digital signal processing
[8] implementation of pmsm servo drive using digital signal processing[8] implementation of pmsm servo drive using digital signal processing
[8] implementation of pmsm servo drive using digital signal processing
 
[6] pr controllers for series converter in active voltage conditioner
[6] pr controllers for series converter in active voltage conditioner[6] pr controllers for series converter in active voltage conditioner
[6] pr controllers for series converter in active voltage conditioner
 
[5] the simulated series converter in active voltage conditioner
[5] the simulated series converter in active voltage conditioner[5] the simulated series converter in active voltage conditioner
[5] the simulated series converter in active voltage conditioner
 
[4] a control of active rectifier in unbalanced grid condition
[4] a control of active rectifier in unbalanced grid condition[4] a control of active rectifier in unbalanced grid condition
[4] a control of active rectifier in unbalanced grid condition
 
[3] simulation active voltage conditioner converter for load three phase
[3] simulation active voltage conditioner converter for load three phase[3] simulation active voltage conditioner converter for load three phase
[3] simulation active voltage conditioner converter for load three phase
 
[1] a control of stand alone photovoltaic water
[1] a control of stand alone photovoltaic water[1] a control of stand alone photovoltaic water
[1] a control of stand alone photovoltaic water
 
[2] the control of active rectifier base on hil402 platform
[2] the control of active rectifier base on hil402 platform[2] the control of active rectifier base on hil402 platform
[2] the control of active rectifier base on hil402 platform
 

Recently uploaded

Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxhumanexperienceaaa
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 

Recently uploaded (20)

Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 

[7] a generalized parameter tuning method of proportional resonant controllers for dynamic voltage restorers

  • 1. International Journal of Power Electronics and Drive System (IJPEDS) Vol.x, No.x, Month 201x, pp. xx~xx ISSN: 2088-8694  34 Journal homepage: http://iaesjournal.com/online/index.php/IJPEDS A Generalized Parameter Tuning Method of Proportional- Resonant Controllers for Dynamic Voltage Restorers Phuong Vu*, Ngoc Dinh*, Nam Hoang*, Quan Nguyen**, Dich Nguyen*, Minh Tran* * School of Electrical Engineering, Hanoi University of Science and Technology, Hanoi, Vietnam ** Department of Electrical and Computer Engineering, The University of Texas at Austin, Texas, U.S.A Article Info ABSTRACT Article history: Received Jun 12th , 201x Revised Aug 20th , 201x Accepted Aug 26th , 201x Temporary voltage swells and sags appear with high frequency in electric power systems, and they significantly affect sensitive loads such as industrial manufacturing or communication devices. This paper presents a strategy to design proportional-resonant controllers for three full-bridge voltage-source converters with a common DC-link in dynamic voltage restorer systems. The proposed controllers allow the system to quickly overcome temporary unbalanced voltage sags. Simulation results carried out in MATLAB/Simulink and experimental results implemented in a Typhoon HIL402 device demonstrate the ability of the proposed design method. The results show that the system with the proposed controllers can ride-through single-phase or double-phase voltage sags up to 55% and three-phase voltage sags up to 70% in a duration less than one grid-voltage cycle. Keyword: Dynamic voltage restorer Proportional-resonant controller Hardware-in-the-loop Copyright © 201x Institute of Advanced Engineering and Science. All rights reserved. Corresponding Author: Phuong Vu, School of Electrical Engineering, Hanoi University of Science and Technology, No.1, Dai Co Viet Road, Hai Ba Trung, Hanoi, Vietnam, Email: phuong.vuhoang@hust.edu.vn 1. INTRODUCTION Power quality disturbances such as voltage sag and swell have been causing serious concerns for modern distribution systems operated at low- and medium-voltage levels. The percentage of voltage sags caused by single line-to-ground fault, double line-to-ground fault, and balanced three phase-to-ground fault in power systems are 68%, 19%, 13%, respectively [1]. Such voltage variations in short durations (less than 60 seconds) lead to improper operation of sensitive loads, while longer voltage variations can result in sustained interruptions or failures. Therefore, mitigating voltage sags and swells in low- and medium-voltage distribution systems is critical. One of the most solution to improve voltage regulation is dynamic voltage restorers (DVRs). The operating principle of DVRs is to inject appropriate voltage in series and synchronism with the distorted AC grid source to compensate for the amount of voltage sag or swell [2-4]. A DVR system includes an energy storage, a three-phase voltage-source inverter, and series connected transformers between an AC grid source and a load. Regarding the three-phase voltage-source inverters, it is necessary to control the positive-, negative- , and zero-sequence components to compensate the voltage sag or swell of each phase [5]. Therefore, the control scheme is complicated and insufficiently reliable. To eliminate voltage sags and swells, several alternative topologies of DVR have been introduced such as a three-phase inverters with a neutral point created by a DC-link capacitor, three-phase four-wire inverters, and three single-phase full-bridge inverters with a common DC-link capacitor [6, 7]. The latter is preferred because of the simple pulse-width modulation (PWM) method. In DVR systems using three full-bridge inverters with a common DC-link capacitor, several control approaches have been suggested. A coordination of both feed-back and feed-forward control in synchronously rotating frame dq is introduced in [8, 9]. However, this topology does not have current loops to compensate for the losses in the transformers and output filter, which leads to a slow voltage response. Another approach is to
  • 2. IJPEDS ISSN: 2088-8694  Title of manuscript is short and clear, implies research results (First Author) 35 implement proportional-resonant (PR) or Hinf control for the voltage loop and proportional (P) control for the current loop in the stationary frame αβ [10]. However, controlling only two components of αβ frame as presented in this approach is not effective when the voltage sag is unbalanced, which is the typical case in practice. A P control for both voltage and current loops with independent controllers between each phase is proposed in [11]. This approach is unable to eliminate the steady-state error in spite of its fast response. A multi-loop with PI controllers is applied to DVR systems in [12], but steady-state error also exists. From this literature review, the control strategy using PR controllers for both current and voltage loops is the most effective for DVR systems to improve dynamic response and eliminate steady-state error [13]. To the best knowledge of the authors, little research has been done to elaborate on the process of determining parameters for PR controllers, which is highly complicated. Several studies apply trial and error procedures to obtain the parameters of PR controllers [14]. Another approach to design PR controllers is based on the SISO design tool in MATLAB and system dynamic response [15]. Such methods are time-consuming and not generalized. This paper proposes a systematic and generalized design method for PR voltage and current controllers of three single-phase full-bridge inverters with a common DC-link capacitor in DVR systems. The major contributions of this paper includes:  An equivalent circuit of full-bridge inverters and series connected transformers in a DVR system. Unlike other existing methods, the model of the series transformers is taken into account in this paper when designing the controllers for the DVR system.  A method to design parameters of PR controllers in the frequency domain for both current and voltage loops to guarantees system stability with a desired cross-over frequency and phase margin. The discretization in the z-domain of the designed PR controllers for digital implementation is also included.  An approach to verify the proposed controller by hardware-in-the-loop (HIL) real-time experiments using a Typhoon HIL402 device. HIL simulation has been highly recommended as an effective design approach with the ease in modifying controller parameters and creating different operating scenarios of grid voltage [16-18]. The remainder of this paper is organized as follows. Section 2 describes the general control topology and the model of a DVR system including the equivalent circuit of full-bridge inverters and series transformers. The proposed design in the frequency domain of the PR current and voltage controllers is presented based on the developed equivalent model. The discretization of the designed PR controller is also included. Section 3 demonstrates the efficacy of the proposed method by off-line simulation and HIL real-time experiments using Typhoon HIL402 system. 2. CONTROL SCHEME A scalar control scheme for three full-bridge inverters with a common DC-link capacitor in a DVR system is shown in Fig. 1. Similar controllers are applied separately for each phase corresponding to each H- bridge inverter. In this control scheme, voltages and currents of all phases are controlled independently using nested control loops. At each phase, the outer voltage control loop regulates the voltage at the secondary side of the transformer while the inner current loop regulates the output current of the H-bridge inverter. The set points of the current loop are the output of the voltage loop, while the set points of the voltage loop are calculated based on the root-mean-square (RMS) values of the desired voltage (for example, 220 V) and the grid voltage. In the proposed control approach, since the instantaneous voltage and current are measured, PR controllers are chosen to eliminate the steady-state error. The resonant frequencies of the PR controllers are equal to the grid frequency. In addition, phase-locked loop (PLL), which is required for grid synchronization, is implemented by measuring the voltage at each phase of the grid source. In this paper, a phase-locked loop (PLL) algorithm based on a second-order generalized integrator phase-locked loop (SOGI PLL) is used [19]. To properly design PR controllers, the model of series transformers in a DVR system should be taken into account. The equivalent circuit of each H-bridge and the simplified model of the transformer referred to the secondary side are shown in Fig. 2. The leakage impedance of the transformer and capacitance result in a second-order low-pass filter. The equivalent impedance referred to the secondary side of the transformer is given as follows: 12 2 , p p eqS s s r x Z r j x R j L N N (1) where N is the turns ratio of the transformer, rp and rs are the resistances of the primary and secondary windings, px and sx are the leakage inductances of the primary and secondary windings, and R and L are the resulting resistance and inductance of the equivalent impedance.
  • 3.  ISSN: 2088-8694 IJECE Vol. x, No. x, Month 201x : xx – xx 36 Cdc FB Phase A FB Phase B FB Phase C 700 V S1,2,3,4a S1,2,3,4b S1,2,3,4c Sin PWM Udc Supply isa isb is uc PR is * uabc is uc VAVC_ref N:1 Voltage controllers Current controllers + - + - PR θ Sensitive load PLL vgrid Vgrid_RMSVref_RMS 220 x vref S4 S1 S2 S3 Udc + - - + Full bridge V0_ref_RMS RMS isc vinj vinj vinj vsa vsb vsc C C C Figure 1. Control topology of the inverter in DVR. Xm rm Xσp/N2 rs Xσp vinj C Grid Load S4 S1 S2 S3 Udc + - - + vsa/N Nisa rp/N2 Figure 2. Equivalent circuit of per phase and series connected transformer. A PR controller has an infinite gain at a selected resonant frequency; thus, the zero steady-state error or the harmonic at this frequency can be eliminated. The transfer function of a PR controller is mathematically expressed as follows [20]: 22 1 .c r PR p k s G s k s (2) where pk and rk are the coefficients of the PR controller while 1 is a selected frequency. The frequency response characteristics of the PR controller are calculated as follows: 2 2 2 2 2 2 1 2 2 1 p r PR k k G j (3) 2 2 0 arctan .r PR p k G j k (4) From (3), it can be seen that the PR controller has an infinite gain at 1 . In [21], the transfer function of the PR controller with the delay compensation can be written as follows:
  • 4. IJPEDS ISSN: 2088-8694  Title of manuscript is short and clear, implies research results (First Author) 37 1 22 1 cos sin . d dc PR p r s G s k k s (5) The delay can be compensated by adding a lead angle  1d skT  to the inverse Park transform angle, where k is an integer representing the number of periods to be compensated [21]. In this paper, k is set to 1. To avoid an algebraic loop during the discrete implementation, it is suggested that the direct integrator is discretized using the forward method while the feedback integrator is discretized using the backward method [20, 21]. The PR controller with the delay compensation and discrete PR controller is shown in Fig. 3. y kr kp 1 s 2 1 1 s cos(θd) ω1sin(θd) x vu a. The PR controller with the delay compensation. x y kr kp 2 1 cos(θd) ω1sin(θd) z-1 Delay 1 1 sT z 1 1 sT z vu vpre b. The resulting discrete PR controller. Figure 3. Block diagram of PR controllers. 3.1 Design the PR controller for the inner current loop From Fig. 1 and Fig. 2, the plant transfer function of current control loop in series converter is determined as follows:       2 2 1 . 1 sa iv sa i s sC G s v s N s L C sRC     (6) The cross-over frequency is usually selected to be far lower than the sampling frequency fs. On the other hand, the cross-over frequency fc is significantly higher than the grid frequency f1. From (3), C PR pcG j k . The parameter pck of the PR regulator for the current loop is thus determined as follows: 1 1 . ci ci ci PRc iv pc iv G j G j k G j (7) Next, based on the desired phase margin cPM of whole system, the parameter rck of the PR controller for the current loop is chosen such that: 0 + 180 . ci ci c PRc ivPM G j G j (8) Therefore, the parameter rck of the PR regulator is determined as follows: 2 2 1 arctan r ci c p ci k A k (8) 2 2 0tan , c p ci rc ci A k k (10) where 0 - 180 C c c ivA PM G j . 3.2 Design the PR controller for the outer voltage loop From Fig. 2, the plant transfer function of voltage control loop in series converter is determined as follows:
  • 5.  ISSN: 2088-8694 IJECE Vol. x, No. x, Month 201x : xx – xx 38       1 . inj vi c v s G s i s Cs   (9) The magnitude-frequency and phase-frequency response of  viG s can be written as follows:     01 , 90vi viG j G j C        (10) 1 . cv cv PRv iv pv cv G j G j k C (11) From the desired phase margin vPM of whole system, the parameter rvk of the PR controller is chosen such that: 0 + 180 . cv cv v PRv viPM G j G j (12) Therefore, the parameter rvk of the PR regulator is determined as follows: 2 2 1 arctan rv cv v pv cv k A k (13) 2 2 0tan , v p cv rv cv A k k (16) where 0 -90v vA PM . 3. RESULTS AND ANALYSIS 3.1. Simulation results The proposed control topology is validated using MATLAB/Simulink/Simpower Systems. The DC voltage is 700VDC while the transformer turns ratio N is 2. The total of leakage inductance L in (1) is 0.2975mH, the filter capacitance C is 30µF, and the switching frequency fs is 5kHz. Unipolar PWM technique is implemented to control the switching of the IGBT switches of the H-bridge inverters [19]. The phase margin and cross-over frequency of current loop are chosen to be 450 and 500Hz, respectively. The phase margin and cross-over frequency of voltage loop are chosen to be 450 , and 200Hz, respectively. This paper investigates the following transient scenarios of the grid voltage: single-phase 55% voltage sag (0.1-0.2s), double-phase 55% voltage sag (0.25-0.35s), and three-phase 70% voltage sag (0.4-0.5s). The RMS value of the phase-to-phase grid voltage is 380 VAC, i.e. the phase-to-neutral voltage is 220VAC. The three-phase voltage sags are created by a programmable voltage source in Matlab/Simpowwer Systems. 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 -400 -200 0 200 400 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 -200 -100 0 100 200 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 -400 -200 0 200 400 Supply voltage(V) Injected voltage(V) Load voltage(V) Time(s) Figure 4. Measured response of DVR (grid voltages, voltages injected by the DVR, load voltages). 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 -150 -100 -50 0 50 100 150 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 -200 -100 0 100 200 Injected voltage_phasea(V) Inverter current_phasea(A) Ref Act Ref-Act Ref-Act Time (s) Figure 5. The reference and actual voltage and current of phase a.
  • 6. IJPEDS ISSN: 2088-8694  Title of manuscript is short and clear, implies research results (First Author) 39 Fig. 4 and Fig.5 show the response of the DVR system with the proposed control during the supply voltage sags. It is clear that the DVR is able to restore correctly to the nominal value within just one cycle of grid voltage (20 ms). The overshoots of the load voltage are negligible, and the steady-state error of injected voltage and inverter current is eliminated in the three cases in Fig.5. A dramatic part of the delay is due to the calculation of the root mean square (RMS) of supply voltage. 3.2. Hardware-in-the-loop experimental results The proposed control is also verified in HIL environment using a Typhoon device. This device consists of an HIL402 card that simulates grid source, load, and three full-bridge with a common DC-link capacitor using IGBTs. The hardware system is simulated in real time on the HIL platform with a time step of 1 μs, which is close to the physical model. The carrier frequency of the PWM is 5 kHz. The voltage and current controllers as well as PLL are implemented in the DSP TMS320F2808 card. All data of HIL is recorded by the Typhoon HIL Control Center Software and shown in Fig.6. The load voltage and the injected voltage from the DVR system are measured using the oscilloscope HAMEG – 200MHz at test points in the HIL DSP interface of Typhoon. These voltages are shown in Fig.7. It is clear that the responses of the HIL experimental results are similar to those in the simulation results in MATLAB. The DVR system is able to regulate the load voltage with an ignorable overshoot within an acceptable period (less than 20 ms) in the injection mode. When supply voltage stable at the nominal value, the DVR system is operated in the standby mode, which means no voltage is injected. 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 -400 -200 0 200 400 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 -200 -100 0 100 200 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 -500 0 500 Supply voltage(V) Injected Voltage(V) Load Voltage(V) Time (s) Fig. 6. HIL experimental results: supply voltage, injected voltage, and load voltage. Load voltages Load voltages Load voltages
  • 7.  ISSN: 2088-8694 IJECE Vol. x, No. x, Month 201x : xx – xx 40 Voltages injected by the DVR. Voltages injected by the DVR. Voltages injected by the DVR. a. Single-phase 55% voltage sag b. Double-phase 55% voltage sag c. Three-phase 70% voltage sag. Figure 7. HIL experimental results in different operating conditions. 4. CONCLUSION This paper proposes a systematic and generalized design method for PR controllers of three single-phase full-bridge inverters with a common DC-link capacitor in DVR systems. The proposed control is designed for each single-phase inverter, taken into account the model of the series transformers. MATLAB and the HIL experimental results validate the performance of voltage in scenarios: single-phase and double phase voltage sags up to 55%, and three-phase voltage sag up to 70% within acceptable periods. The results prove that the DVR system is able to protect the load from voltage sags due to these various types of faults. Such promising results create a crucial foundation for the application of DVR systems in industry. ACKNOWLEDGEMENTS This research was funded by the Ministry of Science and Technology (Vietnam) under project number KC.05.03/16-20. REFERENCES [1] ABB, PCS100 AVC-40 - Active Voltage conditioner. [2] J. G. Nielsen and F. Blaabjerg, "A detailed comparison of system topologies for dynamic voltage restorers," in IEEE Transactions on Industry Applications, vol. 41, no. 5, pp. 1272-1280, Sept.-Oct. 2005. [3] Syed Suraya, P. Sujatha, P. Bharat Kumar, “A Novel Control Strategy for Compensation of Voltage Quality Problem in AC Drives”, International Journal of Power Electronics and Drive System (IJPEDS), Vol. 9, No. 1, March 2018, pp. 8~16 ISSN: 2088-8694, DOI: 10.11591/ijpeds.v9n1.pp8-16. [4] Brahim Ferdi, Samira Dib, Brahim Berbaoui, Rachid Dehini, “Design and Simulation of Dynamic Voltage Restorer Based on Fuzzy Controller Optimized by ANFIS,” International journal of power electronics and drive systems (IJPEDS), Vol 4, No 2: June 2014, pp 212-222. [5] H. Awad, J. Svensson and M. Bollen, "Mitigation of unbalanced voltage dips using static series compensator," in IEEE Transactions on Power Electronics, vol. 19, no. 3, pp. 837-846, May 2004. [6] S. R. Naidu and D. A. Fernandes, "Dynamic voltage restorer based on a four-leg voltage source converter," in IET Generation, Transmission & Distribution, vol. 3, no. 5, pp. 437-447, May 2009. [7] Seon-Yeong Jeong, Thanh Hai Nguyen, Quoc Anh Le, and Dong-Choon Lee, “High-Performance Control of Three- Phase Four- Wire DVR Systems using Feedback Linearization”, Journal of Power Electronics, Vol. 16, No. 1, pp. 351-361, January 2016. [8] J. G. Nielsen, M. Newman, H. Nielsen and F. Blaabjerg, "Control and testing of a dynamic voltage restorer (DVR) at medium voltage level," in IEEE Transactions on Power Electronics, vol. 19, no. 3, pp. 806-813, May 2004. [9] Hyosung Kim and Seung-Ki Sul, "Compensation voltage control in dynamic voltage restorers by use of feed forward and state feedback scheme," in IEEE Transactions on Power Electronics, vol. 20, no. 5, pp. 1169-1177, Sept. 2005. [10] Y. W. Li, F. Blaabjerg, D. M. Vilathgamuwa and P. C. Loh, "Design and Comparison of High Performance Stationary-Frame Controllers for DVR Implementation," in IEEE Transactions on Power Electronics, vol. 22, no. 2, pp. 602-612, March 2007. [11] F. B. Ajaei, S. Afsharnia, A. Kahrobaeian and S. Farhangi, "A Fast and Effective Control Scheme for the Dynamic Voltage Restorer," in IEEE Transactions on Power Delivery, vol. 26, no. 4, pp. 2398-2406, Oct. 2011. [12] Amit Meena, Shirazul Islam, Sandeep Anand, Yogesh Sonawane, Sanjay Tungare, “Design and control of single- phase dynamic voltage restorer”, Springer India, August 2017, Volume 42, Issue 8, pp 1363–1375. [13] 1. S. Andrews and S. Joshi, "Performance Improvement of Dynamic Voltage Restorer using Proportional - Resonant Controller," Proceedings of PCIM Europe 2015; International Exhibition and Conference for Power Electronics, Intelligent Motion, Renewable Energy and Energy Management, Nuremberg, Germany, 2015, pp. 1-8.
  • 8. IJPEDS ISSN: 2088-8694  Title of manuscript is short and clear, implies research results (First Author) 41 [14] hen, K.C., Salimin, S, Zulkifli, S.A., and Aziz, R. Single phase inverter system using proportional resonant current control. International Journal of Power Electronics and Drive Systems. 8. 1913-1918. 10.11591/ijpeds.v8i4.pp1913- 1918. [15] Daniel Zammit, Cyril Spiteri Staines, Maurice Apap, John Licari, Design of PR current control with selective harmonic compensators using Matlab, Journal of Electrical Systems and Information Technology, Volume 4, Issue 3, 2017, Pages 347-358, ISSN 2314-7172, https://doi.org/10.1016/j.jesit.2017.01.003. [16] Typhoon HIL, “Inverter Testing & Pre-certification with HIL Testing”. Available: https://www.typhoon- hil.com/applications/converter-testing. [17] Z. R. Ivanović, E. M. Adžić, M. S. Vekić, S. U. Grabić, N. L. Čelanović and V. A. Katić, "HIL Evaluation of Power Flow Control Strategies for Energy Storage Connected to Smart Grid Under Unbalanced Conditions," in IEEE Transactions on Power Electronics, vol. 27, no. 11, pp. 4699-4710, Nov. 2012. [18] M. S. Vekić, S. U. Grabić, D. P. Majstorović, I. L. Čelanović, N. L. Čelanović and V. A. Katić, "Ultralow Latency HIL Platform for Rapid Development of Complex Power Electronics Systems," in IEEE Transactions on Power Electronics, vol. 27, no. 11, pp. 4436-4444, Nov. 2012. [19] R. Teodorescu, M. Liserre, and P. Rodrguez, Grid converters for photovoltaic and wind power systems. John Wiley, Ltd, 2011. [20] R. Teodorescu, F. Blaabjerg, U. Borup and M. Liserre, "A new control structure for grid-connected LCL PV inverters with zero steady-state error and selective harmonic compensation," Applied Power Electronics Conference and Exposition, 2004. APEC '04. Nineteenth Annual IEEE, 2004, pp. 580-586 Vol.1. [21] M. S. Lima, L. A. d. S. Ribeiro and J. G. de Matos, "Comparison analysis of resonant controllers in discrete domain taking into account the computational delay," 2015 IEEE 13th Brazilian Power Electronics Conference and 1st Southern Power Electronics Conference (COBEP/SPEC), Fortaleza, 2015, pp. 1-6. BIBLIOGRAPHY OF AUTHORS Phuong Vu received his B.S., M.S., and Ph.D. degrees from Hanoi University of Science and Technology, Vietnam, in 2006, 2008, and 2014, respectively, all in Control Engineering and Automation. Since 2006 he has been employed at Hanoi University of Science and Technology, where he is a lecturer and researcher at school of electrical engineering. His research interests include modeling and controlling of power electronics converters for applications such as photovoltaic, wind system, electrical machine drive. Ngoc Dinh was born 1994. He received his Engineer’s degree from Hanoi University of Science and Technology, Vietnam in 2017, in Electrical Engineering. He is currently pursuing M.Sc at Hanoi University of Science and Technology and working Institute for Control Engineering and Automation - ICEA. He research interests are power electronics on the DSP and FPGA platform. Nam Hoang was born 1994. He received his Engineer’s degree from Hanoi University of Science and Technology, Vietnam in 2017, in Electrical Engineering. He is currently pursuing M.Sc at Hanoi University of Science and Technology. He research interests are multilevel converter and power electronics. Quan Nguyen received his Bachelor’s degree from Hanoi University of Science and Technology, Vietnam in 2012 and the M.S degree from The University of Texas at Austin, USA in 2016, both in Electrical Engineering. He is currently pursuing a PhD at The University of Texas at Austin. His research interests are power system control and optimization, renewable energy integration, power quality, and power electronics. Minh Tran received his B.S. degree Technical university in Bacu, in 1983. He received his M.S. degree from Asian Institute of Technology, Thailand and Ph.D from Hanoi University of Science and Technology, Vietnam, in 2007 and 2014, respectively. Since1983, he has been with Hanoi University of Science and Technology, Vietnam, where he is currently an Associate Professor and Executive Dean of the Department of Industrial Automation. His research interests include modelling and controlling of power converters, multilevel converter, HVDC transmission technology.