Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Using the highest loaded
phase (L2 at 153.25 A)

10% for future additions
= 1.1 x 153.25 = 168.575 A.

More Related Content

What's hot

Solucionario circuitos eléctricos - dorf, svoboda - 6ed
Solucionario   circuitos eléctricos - dorf, svoboda - 6edSolucionario   circuitos eléctricos - dorf, svoboda - 6ed
Solucionario circuitos eléctricos - dorf, svoboda - 6ed
galiap22
 

What's hot (19)

Gate ee 2009 with solutions
Gate ee 2009 with solutionsGate ee 2009 with solutions
Gate ee 2009 with solutions
 
Development of Switch Mode Dc Converter Using MATLAB/ dSPACE
Development of Switch Mode Dc Converter Using MATLAB/ dSPACEDevelopment of Switch Mode Dc Converter Using MATLAB/ dSPACE
Development of Switch Mode Dc Converter Using MATLAB/ dSPACE
 
Gate ee 2005 with solutions
Gate ee 2005 with solutionsGate ee 2005 with solutions
Gate ee 2005 with solutions
 
Gate ee 2003 with solutions
Gate ee 2003 with solutionsGate ee 2003 with solutions
Gate ee 2003 with solutions
 
Ee ies'2014-objective paper i (set-a)-final
Ee ies'2014-objective paper i (set-a)-finalEe ies'2014-objective paper i (set-a)-final
Ee ies'2014-objective paper i (set-a)-final
 
Electricity Economics
Electricity EconomicsElectricity Economics
Electricity Economics
 
Gate ee 2008 with solutions
Gate ee 2008 with solutionsGate ee 2008 with solutions
Gate ee 2008 with solutions
 
Simple Model of DC Motor using LTspice
Simple Model of DC Motor using LTspiceSimple Model of DC Motor using LTspice
Simple Model of DC Motor using LTspice
 
Gate ee 2007 with solutions
Gate ee 2007 with solutionsGate ee 2007 with solutions
Gate ee 2007 with solutions
 
LOW POWER DIGITAL DESIGN
LOW POWER DIGITAL DESIGNLOW POWER DIGITAL DESIGN
LOW POWER DIGITAL DESIGN
 
Gate ee 2006 with solutions
Gate ee 2006 with solutionsGate ee 2006 with solutions
Gate ee 2006 with solutions
 
Electrical engineering objective type questions(www.allexamreview.com) أساأ...
Electrical engineering objective type questions(www.allexamreview.com)   أساأ...Electrical engineering objective type questions(www.allexamreview.com)   أساأ...
Electrical engineering objective type questions(www.allexamreview.com) أساأ...
 
SPICE MODEL of MSE-3000 in SPICE PARK
SPICE MODEL of MSE-3000 in SPICE PARKSPICE MODEL of MSE-3000 in SPICE PARK
SPICE MODEL of MSE-3000 in SPICE PARK
 
A.gate by-rk-kanodia
A.gate by-rk-kanodiaA.gate by-rk-kanodia
A.gate by-rk-kanodia
 
ニッケル水素電池のシンプルモデル(LTspice)
ニッケル水素電池のシンプルモデル(LTspice)ニッケル水素電池のシンプルモデル(LTspice)
ニッケル水素電池のシンプルモデル(LTspice)
 
Temple, San Jose Interconnection App Stamped (1)
Temple, San Jose Interconnection App Stamped (1)Temple, San Jose Interconnection App Stamped (1)
Temple, San Jose Interconnection App Stamped (1)
 
Lecture 17
Lecture 17Lecture 17
Lecture 17
 
Solucionario circuitos eléctricos - dorf, svoboda - 6ed
Solucionario   circuitos eléctricos - dorf, svoboda - 6edSolucionario   circuitos eléctricos - dorf, svoboda - 6ed
Solucionario circuitos eléctricos - dorf, svoboda - 6ed
 
Electrical circuits & fields
Electrical circuits & fieldsElectrical circuits & fields
Electrical circuits & fields
 

Similar to 4.1.12 Light Demand 2 Table Part2

4.1.1 Example Single
4.1.1 Example Single4.1.1 Example Single
4.1.1 Example Single
Talia Carbis
 
4.1.3 Example Solution Three
4.1.3 Example Solution Three4.1.3 Example Solution Three
4.1.3 Example Solution Three
Talia Carbis
 
4.1.6 Example Domestic 2
4.1.6 Example Domestic 24.1.6 Example Domestic 2
4.1.6 Example Domestic 2
Talia Carbis
 
Emec 1 question
Emec 1 questionEmec 1 question
Emec 1 question
Ravi Anand
 
Electrical Engineering - 2007 Unsolved Paper
Electrical Engineering - 2007 Unsolved PaperElectrical Engineering - 2007 Unsolved Paper
Electrical Engineering - 2007 Unsolved Paper
Vasista Vinuthan
 

Similar to 4.1.12 Light Demand 2 Table Part2 (20)

4.2.1 Better Load
4.2.1 Better Load4.2.1 Better Load
4.2.1 Better Load
 
4.1.4 Step 2
4.1.4 Step 24.1.4 Step 2
4.1.4 Step 2
 
Unit 2
Unit 2Unit 2
Unit 2
 
4.1.1 Example Single
4.1.1 Example Single4.1.1 Example Single
4.1.1 Example Single
 
4.1.1 Example Single
4.1.1 Example Single4.1.1 Example Single
4.1.1 Example Single
 
4.1.3 Example Solution Three
4.1.3 Example Solution Three4.1.3 Example Solution Three
4.1.3 Example Solution Three
 
4.1.6 Example Domestic 2
4.1.6 Example Domestic 24.1.6 Example Domestic 2
4.1.6 Example Domestic 2
 
Victron Power Backup Systems
Victron Power Backup SystemsVictron Power Backup Systems
Victron Power Backup Systems
 
Synchronous machines
Synchronous machinesSynchronous machines
Synchronous machines
 
Dc motors
Dc motorsDc motors
Dc motors
 
05 Cap 4 - chapter-4-2015.pdf
05 Cap 4 - chapter-4-2015.pdf05 Cap 4 - chapter-4-2015.pdf
05 Cap 4 - chapter-4-2015.pdf
 
Brochure product overview_english
Brochure product overview_englishBrochure product overview_english
Brochure product overview_english
 
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptx
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptxCHAPTER 3 Voltage Drop and Short Circuit Analysis.pptx
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptx
 
Questions unit4
Questions unit4Questions unit4
Questions unit4
 
PEQPAU.pdf
PEQPAU.pdfPEQPAU.pdf
PEQPAU.pdf
 
Emec 1 question
Emec 1 questionEmec 1 question
Emec 1 question
 
Lecture 5
Lecture 5Lecture 5
Lecture 5
 
Computer Science Homework Help
Computer Science Homework HelpComputer Science Homework Help
Computer Science Homework Help
 
Supplementary material for the article: “Pseudo DC-link EV Home Charger with ...
Supplementary material for the article: “Pseudo DC-link EV Home Charger with ...Supplementary material for the article: “Pseudo DC-link EV Home Charger with ...
Supplementary material for the article: “Pseudo DC-link EV Home Charger with ...
 
Electrical Engineering - 2007 Unsolved Paper
Electrical Engineering - 2007 Unsolved PaperElectrical Engineering - 2007 Unsolved Paper
Electrical Engineering - 2007 Unsolved Paper
 

More from Talia Carbis

4.1.13 Light Demand 3
4.1.13 Light Demand 34.1.13 Light Demand 3
4.1.13 Light Demand 3
Talia Carbis
 
4.1.10 Light Demand 2
4.1.10 Light Demand 24.1.10 Light Demand 2
4.1.10 Light Demand 2
Talia Carbis
 
4.1.9 Light Demand 1
4.1.9 Light Demand 14.1.9 Light Demand 1
4.1.9 Light Demand 1
Talia Carbis
 
4.1.8 Light Demand
4.1.8 Light Demand4.1.8 Light Demand
4.1.8 Light Demand
Talia Carbis
 
4.1.7 Example Domestic 3
4.1.7 Example Domestic 34.1.7 Example Domestic 3
4.1.7 Example Domestic 3
Talia Carbis
 
4.1.5 Example Domestic 1
4.1.5 Example Domestic 14.1.5 Example Domestic 1
4.1.5 Example Domestic 1
Talia Carbis
 
4.1.2 Example Three
4.1.2 Example Three4.1.2 Example Three
4.1.2 Example Three
Talia Carbis
 
14.5.4 Example 1 Part 1
14.5.4 Example 1 Part 114.5.4 Example 1 Part 1
14.5.4 Example 1 Part 1
Talia Carbis
 
14.5.8 Example 1 Part 5
14.5.8 Example 1 Part 514.5.8 Example 1 Part 5
14.5.8 Example 1 Part 5
Talia Carbis
 
14.5.7 Example 1 Part 4
14.5.7 Example 1 Part 414.5.7 Example 1 Part 4
14.5.7 Example 1 Part 4
Talia Carbis
 
14.5.6 Example 1 Part 3
14.5.6 Example 1 Part 314.5.6 Example 1 Part 3
14.5.6 Example 1 Part 3
Talia Carbis
 
14.5.5 Example 1 Part 2
14.5.5 Example 1 Part 214.5.5 Example 1 Part 2
14.5.5 Example 1 Part 2
Talia Carbis
 
14.5.1 Improvement
14.5.1 Improvement14.5.1 Improvement
14.5.1 Improvement
Talia Carbis
 

More from Talia Carbis (20)

7.4.6 slip
7.4.6 slip7.4.6 slip
7.4.6 slip
 
4.1.13 Light Demand 3
4.1.13 Light Demand 34.1.13 Light Demand 3
4.1.13 Light Demand 3
 
4.1.10 Light Demand 2
4.1.10 Light Demand 24.1.10 Light Demand 2
4.1.10 Light Demand 2
 
4.1.9 Light Demand 1
4.1.9 Light Demand 14.1.9 Light Demand 1
4.1.9 Light Demand 1
 
4.1.8 Light Demand
4.1.8 Light Demand4.1.8 Light Demand
4.1.8 Light Demand
 
4.1.7 Example Domestic 3
4.1.7 Example Domestic 34.1.7 Example Domestic 3
4.1.7 Example Domestic 3
 
4.1.5 Example Domestic 1
4.1.5 Example Domestic 14.1.5 Example Domestic 1
4.1.5 Example Domestic 1
 
4.1.2 Example Three
4.1.2 Example Three4.1.2 Example Three
4.1.2 Example Three
 
5.4.4 LR Circuits
5.4.4 LR Circuits5.4.4 LR Circuits
5.4.4 LR Circuits
 
14.5.4 Example 1 Part 1
14.5.4 Example 1 Part 114.5.4 Example 1 Part 1
14.5.4 Example 1 Part 1
 
14.5.3 Improve
14.5.3 Improve14.5.3 Improve
14.5.3 Improve
 
14.1.2 TRA Power
14.1.2 TRA Power14.1.2 TRA Power
14.1.2 TRA Power
 
14.5.8 Example 1 Part 5
14.5.8 Example 1 Part 514.5.8 Example 1 Part 5
14.5.8 Example 1 Part 5
 
14.5.7 Example 1 Part 4
14.5.7 Example 1 Part 414.5.7 Example 1 Part 4
14.5.7 Example 1 Part 4
 
14.5.6 Example 1 Part 3
14.5.6 Example 1 Part 314.5.6 Example 1 Part 3
14.5.6 Example 1 Part 3
 
14.5.5 Example 1 Part 2
14.5.5 Example 1 Part 214.5.5 Example 1 Part 2
14.5.5 Example 1 Part 2
 
14.5.2 Correction
14.5.2 Correction14.5.2 Correction
14.5.2 Correction
 
14.5.1 Improvement
14.5.1 Improvement14.5.1 Improvement
14.5.1 Improvement
 
14.4.5 Voltampere
14.4.5 Voltampere14.4.5 Voltampere
14.4.5 Voltampere
 
14.4.4 Three Watt
14.4.4 Three Watt14.4.4 Three Watt
14.4.4 Three Watt
 

Recently uploaded

Artificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsArtificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and Myths
Joaquim Jorge
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI Solutions
Enterprise Knowledge
 

Recently uploaded (20)

Artificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsArtificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and Myths
 
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot TakeoffStrategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivity
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
 
Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI Solutions
 
Data Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonData Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt Robison
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024
 
Evaluating the top large language models.pdf
Evaluating the top large language models.pdfEvaluating the top large language models.pdf
Evaluating the top large language models.pdf
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf
 
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
 
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day Presentation
 
presentation ICT roal in 21st century education
presentation ICT roal in 21st century educationpresentation ICT roal in 21st century education
presentation ICT roal in 21st century education
 
08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
 

4.1.12 Light Demand 2 Table Part2

  • 1. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 2. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 3. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 4. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 5. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 6. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 7. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 8. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 9. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 10. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 11.
  • 12. Using the highest loaded phase (L2 at 153.25 A) 10% for future additions = 1.1 x 153.25 = 168.575 A.