4.2.1 Better Load

  1. 1. Circuit Function L1 L2 L3 Number ✔ ➜➜ 12 twin 36 W fluorescent lighting 1 Move to L3 ✔ fittings at 0.4 A per fitting Circuit 12 twin 36 W fluorescent lighting 2 ✔ fittings at 2.2 A per fitting 3 3 Highbay MV light fittings ✔ 3 3 Highbay MV light fittings ✔ 5 ✔ 7 double 10 A outlets 6 7doube10Aoutlets ✔ 7 6 double 10 A outlets ✔ 8 2 x 15 A single-phase outlet ✔ 9 2 x 15 A single-phase outlet ✔ 10 15 A three-phase outlet ✔ ✔ ✔ 11 15 A three-phase outlet ✔ ✔ ✔ 12 Single-phase range ✔ 13 Instantaneous water heater ✔ 14 -16 4 kW, three-phase motors ✔ ✔ ✔ 16 - 19 5.5 kW, three-phase motors ✔ ✔ ✔
  2. 2. Circuit Function L1 L2 L3 Number ✔ ➜➜ 12 twin 36 W fluorescent lighting 1 Move to L3 ✔ fittings at 0.4 A per fitting Circuit 12 twin 36 W fluorescent lighting 2 ✔ fittings at 2.2 A per fitting 3 3 Highbay MV light fittings ✔ 3 3 Highbay MV light fittings ✔ 5 ✔ 7 double 10 A outlets 6 7doube10Aoutlets ✔ 7 6 double 10 A outlets ✔ 8 2 x 15 A single-phase outlet ✔ 9 2 x 15 A single-phase outlet ✔ 10 15 A three-phase outlet ✔ ✔ ✔ 11 15 A three-phase outlet ✔ ✔ ✔ 12 Single-phase range ✔ 13 Instantaneous water heater ✔ 14 -16 4 kW, three-phase motors ✔ ✔ ✔ 16 - 19 5.5 kW, three-phase motors ✔ ✔ ✔
  3. 3. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 ➜➜ 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 139.0 153.25 149.85
  4. 4. Using the highest loaded phase (L2 at 153.25 A) 10% for future additions = 1.1 x 153.25 = 168.575 A.

×