L.V Technical Data
Outline
 Introduction about LV SWG.
 Alfanar LV products.
 Alfanar Terasaki.
 Alfanar’s Approvals.
Introduction for LV electrical characteristics
Circuit-breakers:
Disconnect and connect the power and provide protection for
cable, load and human against overload and overcurrent.
The following are the type of the CB:
MCB, RCCB, RCBO, MCCB, ICCB, ELCP, MCP, Power circuit and ACB.
Rated operational current (In, Ie):
Continuous current Without overheating
Rated operational voltage (Ue):
This is the voltage at which the equipment has been designed to
operate, in normal (undisturbed) conditions
Rated insulation voltage (Ui) for Circuit-breakers:
This is the value of voltage to which the dielectric tests voltage
and Creepage distances are referred too. The Ue ≤ Ui
Rated impulse-withstand voltage (Uimp) for Circuit-breakers:
This characteristic expresses, in kV peak, the value of voltage
which the equipment is capable of withstanding without failure,
under test conditions. Generally, for industrial circuit-breakers,
Uimp=8kV and for domestic types, Uimp=6kV, and in special cases
could be 12KV
Rated ultimate short-circuit breaking capacity (Icu):
The maximum current, that can be broken across the contacts,
twice times without being damage.
Introduction for LV electrical characteristics
Rated service short-circuit breaking capacity (Ics):
The maximum current, that can be broken across the contacts, without being
damage.
Rated short-time withstand current rating (Icw):
Is the maximum current, that the B category CB can withstand, thermally and
electro dynamically, without sustaining damage, for a period of time given by the
manufacturer.
Category A:
For which there is no calibrate delay in the operation of the “instantaneous” short-
circuit magnetic tripping device.
Category B:
For which, in order to discriminate with other circuit-breakers on a time basis, it is
possible to delay the tripping of the CB, where the fault-current level is lower than,
that of the short-time withstand current rating (Icw) of the CB.
Introduction for LV electrical characteristics
Co-ordination study:
 Discrimination/Selectivity:
Is the Co-ordination of protective device such that a fault is
cleared by the protective device installed immediately
upstream of the fault, and by that device alone.
 Total Discrimination:
Discrimination is said to be total if the downstream circuit
breaker opens and the upstream circuit breaker remains
closed. This ensure maximum availability of the system.
 Partial Discrimination:
Discrimination is partial if the above condition is not fulfilled
up to the prospective short-circuit current, but to lesser
value, above this value both circuit breakers could open,
resulting in loss selectivity.
 Cascading/Backup:
Is a technique where the current limiting capability of
upstream circuit breakers is used to permit the installation
of lower circuit breakers downstream.
Introduction for LV electrical characteristics
Introduction for LV electrical characteristics
 Discrimination/Selectivity:
 Cascading/Backup:
Introduction for LV Mechanical characteristics
Ingrees of Protection (IP X X):
Standard IEC 60529 (February 2001) indicates the degree of protection
provided by electrical equipment enclosures against accidental direct contact
with live parts and against the ingress of solid foreign objects or water.
IK Code “Mechanical Impact test:
The European standard EN 50102 dated March 1995 defines a coding system
(IK code) for indicating the degree of protection provided by electrical equipment
enclosures against external mechanical impact.
Introduction for LV Mechanical characteristics
Separation Forms:
Introduction for LV Mechanical characteristics
Form IEC standard definition Specific recommendations
1 No Internal separation Protection over busbar for customer
safety
2a Separation of busbars from the functional units Terminals not separated from busbars
2b Separation of busbars from the functional units Terminals separated from busbars
3a Separation of busbars from the functional units
and of all functional units from each other.
Terminals not separated from busbars
3b Separation of busbars from the functional units
and of all functional units from each other.
Terminals separated from busbars
4a Separation of busbars from the functional units
and of all functional units from each other, also
separation of terminals from any functional unit
Terminals in the same compartment
as associated functional units.
4b Separation of busbars from the functional units
and of all functional units from each other, also
separation of terminals from any functional unit
Terminals are not in the same
compartment as the associated
functional units
Introduction for LV Mechanical characteristics
IEC 61439:
Is a series of standard IEC 60439
 Fundamental change:
• The categories of TTA (Type Tested Assemblies) and PTTA (Partially
Type Tested Assemblies) have been discarded in favor of a design.
• The performance of assemblies is now determined by a “Design
Verification”.
IEC 61439 Vs IEC 60439:
Arc Flash protection:
International standards (IEC / ANSI) guidelines are
different but the objectives are the same,
i.e. defining minimum safety level for operators
 Assessment criteria for the internal arc test:
• Correctly secured doors, covers, etc. do not open.
• Parts of the assembly (which may cause a hazard) do
not fly off.
• Arcing does not cause holes in the external parts of
the enclosure.
• Indicators do not ignite (made from black cretonne).
• The protective circuit is still operational.
• The arc is to be confined in the same area where it
was ignited.
If these criteria are achieved by the panel, then the
test is a success.
Arc Flash protection:
Seismic :
Proper mounting of the equipment is the
single most important factor in
withstanding a seismic event.
The foundation must be level and
continuous under the entire assembly. The
foundation must be designed to withstand
the reaction loads imposed on it by the
equipment during a seismic event.
Earth quake protection (Seismic):
Product Portfolio :
 Main Distribution Switchboards
 ATS, Synch, 2 out of 3
 Motor Control Center (MCC)
 Control Panels & Panel Boards
 Power Factor Correction Capacitors (PFC)
 Switch rack
 ICP
alfanar L.V Factory:
• Applicable standards IEC 61439-2
• Ie Up to 6300A (No derating up to 6100A, tested at 40° C)
• ICW 100kA/1 sec or 50kA/3 sec
• Ue 690Vac/600Vdc
• Ui 1000Vac
• Uimp 12KV
• Form Form 1 to Form 4B
• Internal Arc Withstand 65kA/300 mSec (Upon Request)
• Seismic Withstand 8 on Richter Scale (Standard Feature)
Alfanar-Terasaki
alfanar L.V SWG:
Who is TERASAKI ?
Alfanar Low Voltage equipment:
ALFANAR TERASAKI Breakers:
 Tem Power-2 is ACB made in Japan up to 6300A/135kA.
 TemBreak2 is MCCB made in Japan up to 1600A/200kA.
 TemDin2 is MCB made in France up to 125A/15KA.
 All ACBs & MCCBs tested under 50°C w/o derating.
Alfanar Low Voltage equipment:
Air Circuit Breakers (World Class Circuit Breakers):
 Ie=800A to 6300A
 Icu=Ics=Icw/1sec
 Ue=690Vac/600Vdc
 Ui=1000Vac
 Uimp=12KV
 Three frame size (800-2000A, 2500-4000A and 5000-6300A)
 Fixed or Withdrawable (Front, vertical or horizontal connection)
 Manual or Motor charging
 Comply with IEC 60947-2
 Comply with ANSI C37.13 and NEMA PUB NO.SG3
 3P or 4P
 Category B
 Trip Unit is AGR (L, R for general feeder or Transformer and S for
generator protection)
Alfanar Low Voltage equipment:
Protection Relays:
The Tem Power-2 series is equipped with an RMS sensing over-current
release AGRB AR Protection Relay samples& calculates the load current
every
(500 micro seconds).
Alfanar Low Voltage equipment:
Harmonic Monitoring:
TemPower 2 AGRs can detect & protect up to the 31th Harmonic.
Protection Relays:
The Phase Rotation Protection function detects the negative phase
current occurring due to reverse phase or phase loss and prevents
burnout of a
Moto or damage to equipment.
Alfanar Low Voltage equipment:
Tempreture control:
CONTACT TEMPERATURE MONITORING, This AGR protection function
monitors the temperature of the ACBs main contacts.
An alarm when the temperature exceeds 155°C.
Continuous monitoring of the contact temperature provides valuable
information for BMS, preventative and predictive maintenance programs.
Alfanar Low Voltage equipment:
Double break:
The Tem Power-2 Air Circuit Breaker is the smallest depth Air Circuit
Breaker in the world with a one second Short Circuit Withstand.
The unique “Double Break” main contact system ensures extremely
fast interruption of short circuit currents.
Conventional break time is 70msec, TemPower 2 breaking time is
25~30msec.
Alfanar Low Voltage equipment:
Eeasy maintenance:
The unique design of Tem Power-2 incorporates its
isolating clusters and main contacts on the ACB body. Allowing for
quick easy maintenance of the main electrical contact points and for
maintenance to be completed without having to isolate the board.
Alfanar Low Voltage equipment:
Replacement of main contacts:
The fixed and moving main contacts can easily
be replaced in the field, thus prolonging the life
on the circuit breaker. Changing each pole takes
around 15 minutes.
Alfanar Low Voltage equipment:
Double opening and closing coils:
Double Opening and Closing Coils provides extended control
system redundancy to an ACB. Double coils allow designers to
implement back-up tripping and closing systems. It provides the
end user with ultimate reliability on critical UPS circuits connected
to critical loads.
Alfanar Low Voltage equipment:
ACB accessories:
Alfanar Low Voltage equipment:
Moulded Case Circuit Breakers Circuit Breakers:
 Ie=125A to 1600A
 Ue=690Vac/600Vdc
 Ui=800Vac
 Uimp=8KV
 Fixed or Withdrawable (Front, vertical or horizontal connection)
 Manual or Motor charging
 Comply with IEC 60947-2
 Comply with NEMA AB-1
 1P, 3P or 4P
 Category A/B
Alfanar Low Voltage equipment:
Moulded Case Circuit Breakers (Thermal Magnetic):
6
8
12
10
0.8
0.63
1
Ir (x ln) Ii (x ln)
125A
Alfanar Low Voltage equipment:
Moulded Case Circuit Breakers
(Electronic):
Electronic version with integrated
monitoring and communication, data
can be sent to integrated display
local display and Modbus network
simultaneously.
Alfanar Low Voltage equipment:
Direct opening “Yellow and red symbol “:
This symbol located on the MCCB rating label,
indicates that the MCCB has direct opening
action.
According to IEC 60204 provides a positive
off.
Alfanar Low Voltage equipment:
Plug-in safety lock:
MCCB can only be
withdrawn when MCCB is
switched off.
Alfanar Low Voltage equipment:
MCCB accessories:
Alfanar Low Voltage equipment:
Circuit breaker with integral Residual Current
Protection “CBR”:
Alfanar Low Voltage equipment:
Al Imam Muhammed
ibn Saud Islamic
University
King Abdullah
Financial District -
KAFD
King Abdullah Sport
City –Jeddah (KASC)
Haramain High Speed Railway
King Abdullah Port
Alfanar Low Voltage equipment:
Reference projects in KSA:
Alfanar Low Voltage equipment:
Reference projects in overseas:
Alfanar Low Voltage equipment:
Reference projects in overseas:
Alfanar Low Voltage equipment:
Reference projects in overseas:
Alfanar Low Voltage equipment:
Reference projects in overseas:
L.v tech presentation 2

More Related Content

What's hot

switchgear and protection by vala kamlesh
switchgear and protection by vala kamleshswitchgear and protection by vala kamlesh
switchgear and protection by vala kamleshKamlesh Vala
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentationNageswar Rao
 
LV SWITCHGEAR -Final PPT.pptx
LV SWITCHGEAR -Final PPT.pptxLV SWITCHGEAR -Final PPT.pptx
LV SWITCHGEAR -Final PPT.pptxshivendra68
 
Short Circuit, Protective Device Coordination
Short Circuit, Protective Device CoordinationShort Circuit, Protective Device Coordination
Short Circuit, Protective Device Coordinationmichaeljmack
 
Switchgear and protection lecture 2 type of circuit breakers and applications
Switchgear and protection lecture 2 type of circuit breakers and applicationsSwitchgear and protection lecture 2 type of circuit breakers and applications
Switchgear and protection lecture 2 type of circuit breakers and applicationsanuphowlader1
 
Low Voltage Circuit Breaker
Low Voltage Circuit BreakerLow Voltage Circuit Breaker
Low Voltage Circuit BreakerAbdul Haseeb
 
ETAP - Arc flash introduction
ETAP - Arc flash introductionETAP - Arc flash introduction
ETAP - Arc flash introductionHimmelstern
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentationNadir Baloch
 
ETAP - Transformer mva sizing
ETAP - Transformer mva sizingETAP - Transformer mva sizing
ETAP - Transformer mva sizingHimmelstern
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersSARAVANAN A
 
Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB
Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB
Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB System Protection
 
TESTING AND COMMISSIONING OF ELECTRICAL EQUIPMENTS. TESTING OF CURRENT TRANSF...
TESTING AND COMMISSIONING OF ELECTRICAL EQUIPMENTS. TESTING OF CURRENT TRANSF...TESTING AND COMMISSIONING OF ELECTRICAL EQUIPMENTS. TESTING OF CURRENT TRANSF...
TESTING AND COMMISSIONING OF ELECTRICAL EQUIPMENTS. TESTING OF CURRENT TRANSF...Jobin Abraham
 
Substation Maintenance
Substation MaintenanceSubstation Maintenance
Substation Maintenancekarikalan123
 

What's hot (20)

switchgear and protection by vala kamlesh
switchgear and protection by vala kamleshswitchgear and protection by vala kamlesh
switchgear and protection by vala kamlesh
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 
LV SWITCHGEAR -Final PPT.pptx
LV SWITCHGEAR -Final PPT.pptxLV SWITCHGEAR -Final PPT.pptx
LV SWITCHGEAR -Final PPT.pptx
 
Short Circuit, Protective Device Coordination
Short Circuit, Protective Device CoordinationShort Circuit, Protective Device Coordination
Short Circuit, Protective Device Coordination
 
Switchgear and protection lecture 2 type of circuit breakers and applications
Switchgear and protection lecture 2 type of circuit breakers and applicationsSwitchgear and protection lecture 2 type of circuit breakers and applications
Switchgear and protection lecture 2 type of circuit breakers and applications
 
Low Voltage Circuit Breaker
Low Voltage Circuit BreakerLow Voltage Circuit Breaker
Low Voltage Circuit Breaker
 
ETAP - Arc flash introduction
ETAP - Arc flash introductionETAP - Arc flash introduction
ETAP - Arc flash introduction
 
IEEE substation design
IEEE substation designIEEE substation design
IEEE substation design
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
MV Switchgear from IEEE
MV Switchgear from IEEEMV Switchgear from IEEE
MV Switchgear from IEEE
 
ETAP - Transformer mva sizing
ETAP - Transformer mva sizingETAP - Transformer mva sizing
ETAP - Transformer mva sizing
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineers
 
Switchgear
Switchgear Switchgear
Switchgear
 
RTCC & AVR
RTCC & AVRRTCC & AVR
RTCC & AVR
 
Load list calculation
Load list calculationLoad list calculation
Load list calculation
 
Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB
Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB
Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB
 
Low voltage circuit breakers
Low voltage circuit breakersLow voltage circuit breakers
Low voltage circuit breakers
 
TESTING AND COMMISSIONING OF ELECTRICAL EQUIPMENTS. TESTING OF CURRENT TRANSF...
TESTING AND COMMISSIONING OF ELECTRICAL EQUIPMENTS. TESTING OF CURRENT TRANSF...TESTING AND COMMISSIONING OF ELECTRICAL EQUIPMENTS. TESTING OF CURRENT TRANSF...
TESTING AND COMMISSIONING OF ELECTRICAL EQUIPMENTS. TESTING OF CURRENT TRANSF...
 
Substation Maintenance
Substation MaintenanceSubstation Maintenance
Substation Maintenance
 

Similar to L.v tech presentation 2

244109578 estandar-iec-60947-2-pdf
244109578 estandar-iec-60947-2-pdf244109578 estandar-iec-60947-2-pdf
244109578 estandar-iec-60947-2-pdfBarlomax
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERRitesh Kumawat
 
Electrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCBElectrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCBMANOJ964697
 
changwon MVP, EMDB, SMDB & DB
changwon MVP, EMDB, SMDB & DBchangwon MVP, EMDB, SMDB & DB
changwon MVP, EMDB, SMDB & DBSheikh Imran
 
Substation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSubstation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSatish Pydimarla
 
1 residual current circuit breaker (rccb) ( elcb)
1 residual current circuit breaker (rccb) ( elcb)1 residual current circuit breaker (rccb) ( elcb)
1 residual current circuit breaker (rccb) ( elcb)nikeshdubey
 
Numerical analysis of short circuit testing & verification of a MCCB.
Numerical analysis of short circuit testing & verification of a MCCB.Numerical analysis of short circuit testing & verification of a MCCB.
Numerical analysis of short circuit testing & verification of a MCCB.Rajeev Kumar Raj
 
Tongou electrical catalogue
Tongou electrical catalogue Tongou electrical catalogue
Tongou electrical catalogue Johnson lim
 
Adjustable/Regulated DC Power Supply
Adjustable/Regulated DC Power SupplyAdjustable/Regulated DC Power Supply
Adjustable/Regulated DC Power SupplyMuhsin Fahim
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersThorne & Derrick International
 
DPL Transmission And Distribution
DPL Transmission And DistributionDPL Transmission And Distribution
DPL Transmission And DistributionSubhojeet Sinha ☁
 
Crouzet Aerospace - Electrical Protection & Distribution
Crouzet Aerospace - Electrical Protection & DistributionCrouzet Aerospace - Electrical Protection & Distribution
Crouzet Aerospace - Electrical Protection & DistributionCrouzet
 
Selective Coodination
Selective CoodinationSelective Coodination
Selective Coodinationmichaeljmack
 
Residual current-circuit-breaker www.meba.net
Residual current-circuit-breaker www.meba.netResidual current-circuit-breaker www.meba.net
Residual current-circuit-breaker www.meba.netMeba Electric Co.,Ltd
 
2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear StandardsBryan Johnson
 

Similar to L.v tech presentation 2 (20)

244109578 estandar-iec-60947-2-pdf
244109578 estandar-iec-60947-2-pdf244109578 estandar-iec-60947-2-pdf
244109578 estandar-iec-60947-2-pdf
 
Thông số kĩ thuật MCCB LS
Thông số kĩ thuật MCCB LSThông số kĩ thuật MCCB LS
Thông số kĩ thuật MCCB LS
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
 
Electrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCBElectrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCB
 
changwon MVP, EMDB, SMDB & DB
changwon MVP, EMDB, SMDB & DBchangwon MVP, EMDB, SMDB & DB
changwon MVP, EMDB, SMDB & DB
 
Substation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSubstation_equipment_ (1).pptx
Substation_equipment_ (1).pptx
 
1 residual current circuit breaker (rccb) ( elcb)
1 residual current circuit breaker (rccb) ( elcb)1 residual current circuit breaker (rccb) ( elcb)
1 residual current circuit breaker (rccb) ( elcb)
 
Numerical analysis of short circuit testing & verification of a MCCB.
Numerical analysis of short circuit testing & verification of a MCCB.Numerical analysis of short circuit testing & verification of a MCCB.
Numerical analysis of short circuit testing & verification of a MCCB.
 
Mcb catalogue
Mcb catalogueMcb catalogue
Mcb catalogue
 
Tongou electrical catalogue
Tongou electrical catalogue Tongou electrical catalogue
Tongou electrical catalogue
 
Dc mini-breaker
Dc mini-breakerDc mini-breaker
Dc mini-breaker
 
Adjustable/Regulated DC Power Supply
Adjustable/Regulated DC Power SupplyAdjustable/Regulated DC Power Supply
Adjustable/Regulated DC Power Supply
 
havells ppt
havells ppthavells ppt
havells ppt
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment Designers
 
DPL Transmission And Distribution
DPL Transmission And DistributionDPL Transmission And Distribution
DPL Transmission And Distribution
 
Crouzet Aerospace - Electrical Protection & Distribution
Crouzet Aerospace - Electrical Protection & DistributionCrouzet Aerospace - Electrical Protection & Distribution
Crouzet Aerospace - Electrical Protection & Distribution
 
4.RCCB -Meba
4.RCCB -Meba 4.RCCB -Meba
4.RCCB -Meba
 
Selective Coodination
Selective CoodinationSelective Coodination
Selective Coodination
 
Residual current-circuit-breaker www.meba.net
Residual current-circuit-breaker www.meba.netResidual current-circuit-breaker www.meba.net
Residual current-circuit-breaker www.meba.net
 
2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards
 

Recently uploaded

Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringmulugeta48
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756dollysharma2066
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfJiananWang21
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 

Recently uploaded (20)

Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 

L.v tech presentation 2

  • 2. Outline  Introduction about LV SWG.  Alfanar LV products.  Alfanar Terasaki.  Alfanar’s Approvals.
  • 3.
  • 4. Introduction for LV electrical characteristics Circuit-breakers: Disconnect and connect the power and provide protection for cable, load and human against overload and overcurrent. The following are the type of the CB: MCB, RCCB, RCBO, MCCB, ICCB, ELCP, MCP, Power circuit and ACB. Rated operational current (In, Ie): Continuous current Without overheating Rated operational voltage (Ue): This is the voltage at which the equipment has been designed to operate, in normal (undisturbed) conditions
  • 5. Rated insulation voltage (Ui) for Circuit-breakers: This is the value of voltage to which the dielectric tests voltage and Creepage distances are referred too. The Ue ≤ Ui Rated impulse-withstand voltage (Uimp) for Circuit-breakers: This characteristic expresses, in kV peak, the value of voltage which the equipment is capable of withstanding without failure, under test conditions. Generally, for industrial circuit-breakers, Uimp=8kV and for domestic types, Uimp=6kV, and in special cases could be 12KV Rated ultimate short-circuit breaking capacity (Icu): The maximum current, that can be broken across the contacts, twice times without being damage. Introduction for LV electrical characteristics
  • 6. Rated service short-circuit breaking capacity (Ics): The maximum current, that can be broken across the contacts, without being damage. Rated short-time withstand current rating (Icw): Is the maximum current, that the B category CB can withstand, thermally and electro dynamically, without sustaining damage, for a period of time given by the manufacturer. Category A: For which there is no calibrate delay in the operation of the “instantaneous” short- circuit magnetic tripping device. Category B: For which, in order to discriminate with other circuit-breakers on a time basis, it is possible to delay the tripping of the CB, where the fault-current level is lower than, that of the short-time withstand current rating (Icw) of the CB. Introduction for LV electrical characteristics
  • 7. Co-ordination study:  Discrimination/Selectivity: Is the Co-ordination of protective device such that a fault is cleared by the protective device installed immediately upstream of the fault, and by that device alone.  Total Discrimination: Discrimination is said to be total if the downstream circuit breaker opens and the upstream circuit breaker remains closed. This ensure maximum availability of the system.  Partial Discrimination: Discrimination is partial if the above condition is not fulfilled up to the prospective short-circuit current, but to lesser value, above this value both circuit breakers could open, resulting in loss selectivity.  Cascading/Backup: Is a technique where the current limiting capability of upstream circuit breakers is used to permit the installation of lower circuit breakers downstream. Introduction for LV electrical characteristics
  • 8. Introduction for LV electrical characteristics  Discrimination/Selectivity:  Cascading/Backup:
  • 9. Introduction for LV Mechanical characteristics Ingrees of Protection (IP X X): Standard IEC 60529 (February 2001) indicates the degree of protection provided by electrical equipment enclosures against accidental direct contact with live parts and against the ingress of solid foreign objects or water.
  • 10. IK Code “Mechanical Impact test: The European standard EN 50102 dated March 1995 defines a coding system (IK code) for indicating the degree of protection provided by electrical equipment enclosures against external mechanical impact. Introduction for LV Mechanical characteristics
  • 11. Separation Forms: Introduction for LV Mechanical characteristics
  • 12. Form IEC standard definition Specific recommendations 1 No Internal separation Protection over busbar for customer safety 2a Separation of busbars from the functional units Terminals not separated from busbars 2b Separation of busbars from the functional units Terminals separated from busbars 3a Separation of busbars from the functional units and of all functional units from each other. Terminals not separated from busbars 3b Separation of busbars from the functional units and of all functional units from each other. Terminals separated from busbars 4a Separation of busbars from the functional units and of all functional units from each other, also separation of terminals from any functional unit Terminals in the same compartment as associated functional units. 4b Separation of busbars from the functional units and of all functional units from each other, also separation of terminals from any functional unit Terminals are not in the same compartment as the associated functional units Introduction for LV Mechanical characteristics
  • 13. IEC 61439: Is a series of standard IEC 60439  Fundamental change: • The categories of TTA (Type Tested Assemblies) and PTTA (Partially Type Tested Assemblies) have been discarded in favor of a design. • The performance of assemblies is now determined by a “Design Verification”. IEC 61439 Vs IEC 60439:
  • 14. Arc Flash protection: International standards (IEC / ANSI) guidelines are different but the objectives are the same, i.e. defining minimum safety level for operators  Assessment criteria for the internal arc test: • Correctly secured doors, covers, etc. do not open. • Parts of the assembly (which may cause a hazard) do not fly off. • Arcing does not cause holes in the external parts of the enclosure. • Indicators do not ignite (made from black cretonne). • The protective circuit is still operational. • The arc is to be confined in the same area where it was ignited. If these criteria are achieved by the panel, then the test is a success. Arc Flash protection:
  • 15. Seismic : Proper mounting of the equipment is the single most important factor in withstanding a seismic event. The foundation must be level and continuous under the entire assembly. The foundation must be designed to withstand the reaction loads imposed on it by the equipment during a seismic event. Earth quake protection (Seismic):
  • 16. Product Portfolio :  Main Distribution Switchboards  ATS, Synch, 2 out of 3  Motor Control Center (MCC)  Control Panels & Panel Boards  Power Factor Correction Capacitors (PFC)  Switch rack  ICP alfanar L.V Factory:
  • 17. • Applicable standards IEC 61439-2 • Ie Up to 6300A (No derating up to 6100A, tested at 40° C) • ICW 100kA/1 sec or 50kA/3 sec • Ue 690Vac/600Vdc • Ui 1000Vac • Uimp 12KV • Form Form 1 to Form 4B • Internal Arc Withstand 65kA/300 mSec (Upon Request) • Seismic Withstand 8 on Richter Scale (Standard Feature) Alfanar-Terasaki alfanar L.V SWG:
  • 18. Who is TERASAKI ? Alfanar Low Voltage equipment:
  • 19. ALFANAR TERASAKI Breakers:  Tem Power-2 is ACB made in Japan up to 6300A/135kA.  TemBreak2 is MCCB made in Japan up to 1600A/200kA.  TemDin2 is MCB made in France up to 125A/15KA.  All ACBs & MCCBs tested under 50°C w/o derating. Alfanar Low Voltage equipment:
  • 20. Air Circuit Breakers (World Class Circuit Breakers):  Ie=800A to 6300A  Icu=Ics=Icw/1sec  Ue=690Vac/600Vdc  Ui=1000Vac  Uimp=12KV  Three frame size (800-2000A, 2500-4000A and 5000-6300A)  Fixed or Withdrawable (Front, vertical or horizontal connection)  Manual or Motor charging  Comply with IEC 60947-2  Comply with ANSI C37.13 and NEMA PUB NO.SG3  3P or 4P  Category B  Trip Unit is AGR (L, R for general feeder or Transformer and S for generator protection) Alfanar Low Voltage equipment:
  • 21. Protection Relays: The Tem Power-2 series is equipped with an RMS sensing over-current release AGRB AR Protection Relay samples& calculates the load current every (500 micro seconds). Alfanar Low Voltage equipment:
  • 22. Harmonic Monitoring: TemPower 2 AGRs can detect & protect up to the 31th Harmonic. Protection Relays: The Phase Rotation Protection function detects the negative phase current occurring due to reverse phase or phase loss and prevents burnout of a Moto or damage to equipment. Alfanar Low Voltage equipment:
  • 23. Tempreture control: CONTACT TEMPERATURE MONITORING, This AGR protection function monitors the temperature of the ACBs main contacts. An alarm when the temperature exceeds 155°C. Continuous monitoring of the contact temperature provides valuable information for BMS, preventative and predictive maintenance programs. Alfanar Low Voltage equipment:
  • 24. Double break: The Tem Power-2 Air Circuit Breaker is the smallest depth Air Circuit Breaker in the world with a one second Short Circuit Withstand. The unique “Double Break” main contact system ensures extremely fast interruption of short circuit currents. Conventional break time is 70msec, TemPower 2 breaking time is 25~30msec. Alfanar Low Voltage equipment:
  • 25. Eeasy maintenance: The unique design of Tem Power-2 incorporates its isolating clusters and main contacts on the ACB body. Allowing for quick easy maintenance of the main electrical contact points and for maintenance to be completed without having to isolate the board. Alfanar Low Voltage equipment:
  • 26. Replacement of main contacts: The fixed and moving main contacts can easily be replaced in the field, thus prolonging the life on the circuit breaker. Changing each pole takes around 15 minutes. Alfanar Low Voltage equipment:
  • 27. Double opening and closing coils: Double Opening and Closing Coils provides extended control system redundancy to an ACB. Double coils allow designers to implement back-up tripping and closing systems. It provides the end user with ultimate reliability on critical UPS circuits connected to critical loads. Alfanar Low Voltage equipment:
  • 28. ACB accessories: Alfanar Low Voltage equipment:
  • 29. Moulded Case Circuit Breakers Circuit Breakers:  Ie=125A to 1600A  Ue=690Vac/600Vdc  Ui=800Vac  Uimp=8KV  Fixed or Withdrawable (Front, vertical or horizontal connection)  Manual or Motor charging  Comply with IEC 60947-2  Comply with NEMA AB-1  1P, 3P or 4P  Category A/B Alfanar Low Voltage equipment:
  • 30. Moulded Case Circuit Breakers (Thermal Magnetic): 6 8 12 10 0.8 0.63 1 Ir (x ln) Ii (x ln) 125A Alfanar Low Voltage equipment:
  • 31. Moulded Case Circuit Breakers (Electronic): Electronic version with integrated monitoring and communication, data can be sent to integrated display local display and Modbus network simultaneously. Alfanar Low Voltage equipment:
  • 32. Direct opening “Yellow and red symbol “: This symbol located on the MCCB rating label, indicates that the MCCB has direct opening action. According to IEC 60204 provides a positive off. Alfanar Low Voltage equipment:
  • 33. Plug-in safety lock: MCCB can only be withdrawn when MCCB is switched off. Alfanar Low Voltage equipment:
  • 34. MCCB accessories: Alfanar Low Voltage equipment:
  • 35. Circuit breaker with integral Residual Current Protection “CBR”: Alfanar Low Voltage equipment:
  • 36. Al Imam Muhammed ibn Saud Islamic University King Abdullah Financial District - KAFD King Abdullah Sport City –Jeddah (KASC) Haramain High Speed Railway King Abdullah Port Alfanar Low Voltage equipment: Reference projects in KSA:
  • 37. Alfanar Low Voltage equipment: Reference projects in overseas:
  • 38. Alfanar Low Voltage equipment: Reference projects in overseas:
  • 39. Alfanar Low Voltage equipment: Reference projects in overseas:
  • 40. Alfanar Low Voltage equipment: Reference projects in overseas: