1. CONTROLLER
ATyS C20 / C30
Notice d’utilisation - Operating instructions
F GB MAKE YOUR BUSINESS SAFE
SOCOMEC GROUP SWITCHING PROTECTION & UPS
2. F
Sommaire
LA GAMME ATyS _________________________________3
PRÉSENTATION GÉNÉRALE _______________________4
Présentation des produits ________________________4
INSTALLATION ___________________________________5
Montage _______________________________________5
Dimensions_____________________________________5
Caractéristiques_________________________________5
RACCORDEMENTS _______________________________6
Circuits de commande ___________________________6
Commande électrique __________________________11
FONCTIONNEMENT _____________________________12
Présentation___________________________________12
Modes d’utilisation _____________________________13
Programmation ________________________________14
Exploitation____________________________________24
Visualisation ___________________________________26
Séquences automatiques _______________________28
AIDE AU DÉPANNAGE ___________________________31
ANNEXES ______________________________________32
Typologie des réseaux __________________________32
Programmation et câblage ATyS __________________33
GB
Summary
THE ATyS RANGE _______________________________35
GENERAL PRESENTATION _______________________36
Product introduction ____________________________36
INSTALLATION __________________________________37
Mounting _____________________________________37
Dimensions ___________________________________37
Characteristics_________________________________37
CONNECTIONS _________________________________38
Control circuits_________________________________38
Electrical operation _____________________________43
OPERATION ____________________________________44
Presentation ___________________________________44
Operational modes _____________________________45
Programming __________________________________46
Operation _____________________________________56
Visualisation ___________________________________58
Automatic sequences ___________________________60
TROUBLESHOOTING GUIDE _____________________63
ANNEXES ______________________________________64
Network analysis _______________________________64
Programming and connections ATyS C30 __________65
SOCOMEC - Réf. : 532 214 C
2
3. Controller ATyS
THE ATyS RANGE
The ATyS family proposes a complete motorised • Automatic control: AtyS 6 products integrate all
changeover range including electrical and mechanical controls, timers and relays required to realise a
interlocking. Manual operation is always possible on all Normal / Emergency application.
the products in case of emergency. ATyS 6e and 6m versions also integrate the remote
The electric command is realised via a motorised controlled feature.
module, electronically driven by 2 types of logic: The motorised and control modules can easily be
• Remote controlled: ATyS 3 products are controlled by replaced without disconnecting the power cables.
volt free contacts allowing the switch to be driven in 1,
0 or 2 position. These contacts can come from an
external control logic.
ATyS 3s ATyS 3e ATyS 6s ATyS 6e ATyS 6m ATyS C30 ATyS C20 ATyS C40
MOTORISED CHANGEOVER
Dual power supply
Changeover
Integrated control relay Dual genset
controller
Metering
Com option Communication option
2 I/2 O option 2 inputs / 2 outputs option
Remote interfaces ATyS D10 & D20
> This instruction manual applies to following > Following products are delivered with their own
products: instruction manual:
• Controller ATyS C20 / C30 • ATyS 3s
• ATyS 3e, 6s, 6e
• ATyS 6m
• Remote interfaces ATyS D10 & D20
• Centroller ATyS C40.
For personnel and product safety, please
read the contents of these operating
instructions carefully before connecting.
SOCOMEC - Réf. : 532 214 C
35
4. Controller ATyS
Product introduction
GENERAL PRESENTATION
ATyS C20/C30
Product introduction
ATYS C20
LCD Control terminals Modular frame
ATYS 453 A
Voltage sensing and
power supply terminals Keypad
ATYS C30
LCD Control terminals Modular frame
ATYS 448 A
Voltage sensing and
RJ45 terminal power supply terminals Keypad
SOCOMEC - Réf. : 532 214 C
36
5. Controller ATyS
Mounting
INSTALLATION Dimensions
Characteristics
ATyS C20/C30
Mounting
> DIN rail mounting
ATYS 449 A NB
Dimensions
58
106 48
26,5
45
90
62
93
ATYS 437 A
Characteristics
> IP
IP2 and class II on front face
> Operation
• Temperature : -20 °C to +60 °C
• Humidity : 80 % at 55 °C
95 % at 40 °C
> Consumption
7.5 VA max
> Measurement category
Cat III
SOCOMEC - Réf. : 532 214 C
37
6. Controller ATyS
Control circuits
CONNECTIONS Electrical operation
ATyS C20/C30
Control circuits
400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR
SWITCHING TYPE TECHNOLOGY
• Configure the type of control logic in impulse mode • Automatic Power supply 203-205 or 104-106
(see Programming chapter). (see power supply chapter).
LOAD
L1 L1
L2 L2
1 L3 L3 2
N N
F1 F2
F1, F2
Fuse protection
230 Vac 5 A
Ph Power
DPS
N 230 Vac
Double Power
Supply option Control CA1 CA0 CA2
I II 0 C
I1 I2
O2
GE
13 14 23 24 33 34 43 44 53 54 301 302 303 304 305 306 DC-* DC+*
ONLY ON ATyS C30
Cable
RJ45 8/8
N L3 L2 L1 L1 L3
ATyS D10 or D20 103 104 105 106 203 205
remote interface
ATYS 426 A GB
* Only on DC versions.
Maximum control cables lenght = 10 m. Remote interfaces maximum connection
In case of longer distance, insert control cable (RJ45) = 3 m.
relays.
SOCOMEC - Réf. : 532 214 C
38
7. Controller ATyS
CONNECTIONS
Control circuits
400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR
CONTACTOR TYPE TECHNOLOGY
• Configure the type of control logic in contactor (see • Automatic Power supply 203-205 or 104-106
Programming chapter). (see power supply chapter).
LOAD
K1 K2
L1 L1
L2 L2
1 L3 L3 2
N N
F1 F2
F1, F2
K1 K2 Fuse protection
230 Vac 5 A
K2 K1
I1 I2
O1 O2
I II
GE
13 14 23 24 33 34 43 44 53 54 301 302 303 304 305 306 DC-* DC+*
ONLY ON ATyS C30
Cable
RJ45 8/8
N L3 L2 L1 L1 L3
ATyS D10 or D20 103 104 105 106 203 205
remote interface
ATYS 438 A GB
* Only on DC versions.
Maximum control cables lenght = 10 m. Remote interfaces maximum connection
In case of longer distance, insert control cable (RJ45) = 3 m.
relays.
SOCOMEC - Réf. : 532 214 C
39
8. Controller ATyS
Control circuits
CONNECTIONS Electrical operation
ATyS C20/C30
Control circuits
400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR
CIRCUIT BREAKER TYPE TECHNOLOGY
> Electrical interlocking via external control relays
• Configure the type of control logic in contactor (see • Automatic Power supply 203-205 or 104-106
Programming chapter). (see power supply chapter).
LOAD
L1 L1
L2 L2
1 L3 L3 2
N N
F1 F2
POS 1 POS 2 POS 2 POS 1 AUXILIARY CONTACT F1, F2
closing opening closing opening BRE. 1 BRE. 2 Fuse protection
230 Vac 5 A
K1 K2
K2 K1
I II O1 O2 I1 I2
GE
13 14 23 24 33 34 43 44 53 54 301 302 303 304 305 306 DC-* DC+*
ONLY ON ATyS C30
Cable
RJ45 8/8
N L3 L2 L1 L1 L3
ATyS D10 or D20 103 104 105 106 203 205
remote interface
ATYS 439 A GB
* Only on DC versions.
Maximum control cables lenght = 10 m. Remote interfaces maximum connection
In case of longer distance, insert control cable (RJ45) = 3 m.
relays.
SOCOMEC - Réf. : 532 214 C
40
9. Controller ATyS
CONNECTIONS
Control circuits
400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR
CIRCUIT BREAKER TYPE TECHNOLOGY
> Electrical interlocking not integrated
• Configure the type of control logic in breaker • Automatic Power supply 203-205 or 104-106
(see Programming chapter) (see power supply chapter).
LOAD
L1 L1
L2 L2
1 L3 L3 2
N N
F1 F2
OPENING
F1, F2
Breaker 1 Breaker 2
Fuse protection
230 Vac 5 A
CLOSING
Breaker 1 Breaker 2 I1 I2
GE
13 14 23 24 33 34 43 44 53 54 301 302 303 304 305 306 DC-*DC+*
ONLY ON ATyS C30
Cable
RJ45 8/8
N L3 L2 L1 L1 L3
ATyS D10 or D20 103 104 105 106 203 205
remote interface
ATYS 440 B GB
* Only on DC versions.
Maximum control cables lenght = 10 m. This drawing is not including the electrical
In case of longer distance, insert control interlock.
relays.
It might be necessary for some breakers not
Remote interfaces maximum connection to set up OMR and OMF timers to 0.
cable (RJ45) = 3 m. (refer to programming)
SOCOMEC - Réf. : 532 214 C
41
10. Controller ATyS
Control circuits
CONNECTIONS Electrical operation
ATyS C20/C30
Control circuits
Denomination Terminals Description Characteristics Recommended
section
Power supply N (103) Neutral 440 V ac (phase-phase) 1.5 mm2
Source 1 L3 (104) Phase 3 maximum, 50 / 60 Hz
L2 (105) Phase 2 254 V ac (phase neutre)
L1 (106) Phase 1 maximum, 50 / 60 Hz
Power supply L1 (203) Phase 1 440 V ac (phase-phase) 1.5 mm2
Source 2 L3 (205) Phase 3 maximum
Power supply DC(1) DC- Power supply 0 V From 9 V dc to 30 V dc 1.5 mm2
12Vdc, 24Vdc DC+ Power supply +V dc
Genset(2) 13 Genset start / stop relay - 2 stable positions Dry contact 1.5 mm2
start signal 14 Programmable state - factory setting = NO, close to start 5A AC1 / 250 V
Control 23 Impulse mode: order to close source 1 5 A AC1 / 250 V 1.5 mm2
(impulse, 24 Contactor mode: order to close contactor source 1
contactor Breaker mode: order to close breaker source 1
and breaker 33 Impulse mode: order to close source 2 5 A AC1 / 250 V 1.5 mm2
mode to 34 Contactor mode: order to close contactor source 2
programm) Breaker mode: order to close breaker source 2
43 Impulse mode: order to reach position 0 5 A AC1 / 250 V 1.5 mm2
44 Contactor mode: programmable relay O1
Breaker mode: order to open breaker source 1
53 Impulse mode: programmable relay O2 5 A AC1 / 250 V 1.5 mm2
54 Contactor mode: programmable relay O2
Breaker mode: order to open breaker source 2
Information 301 Auxiliary contact information position 1 AC1 Do not connect to 1.5 mm2
auxiliary 302 Auxiliary contact information position 0 AC0 any power supply
contacts 303 Auxiliary contact information position 2 AC2
Programmable 304 Programmable input In1 Do not connect to 1.5 mm2
Inputs 305 Programmable input In2 any power supply
Common 306 Specific voltage supply Do not connect to 1.5 mm2
input Common terminals 301 to 306 any power supply
Remote interface RJ Remote interface ATyS D10 or D20 Maximum connection RJ45 8/8
connection cable 3 m
(1) Only on DC version
(2) Refer to programming, Setup, to modify relay state.
SOCOMEC - Réf. : 532 214 C
42
11. Controller ATyS
CONNECTIONS
Electrical operation
POWER SUPPLY
ATyS C20/C30 integrates 2 power inputs (104-106, 203- AUT position
205), and consider the available source to keep the
priority power source 1
product operational. Product supplied when voltage on
ATYS 444 A GB
terminals ≥ 100 Vac backup power source 2
For the DC version, these is only one power supply input product ON
(DC-, DC+). 1 : terminals 104-106 2 : terminals 203-205
SOCOMEC - Réf. : 532 214 C
43
12. Controller ATyS
Presentation
OPERATION Operational modes
Programming
ATyS C20/C30 Operation
Visualisation
Automatic sequences
Presentation
The product allows:
• sources control, • voltage and frequency metering,
• automatic transfer control in AUT mode, • system state display,
• parameters configuration, • alarm or fault indication,
FAULT led LCD
Led is on when product is faulty. 7 digits + 14 pointers
Disconnect power supplies to reset
POWER led
Green led is on when product is
powered
RJ45 connection*
RJ45 terminal for
ATyS D10 or D20.
If connected, the
LCD is off
Keypad
Sources state
Escape Navigation
- Led is on: source = OK
- Led is off: source is not available
LCD & leds test
Operations Validation
Switch state Operational modes
2 green leds: - Automatic sequence simulator (test on load)
ATYS 427 A GB
- switch I state - Genset remote start (test off load)
- switch II state - Changeover switch position control (local or remote)
* only on ATyS C30.
SOFTWARE VERSION
Displayed after reset.
ATYS 428 A GB
(3 minutes power off action to allow reset).
Version
number
SOCOMEC - Réf. : 532 214 C
44
13. Controller ATyS
OPERATION
Operational modes
VISUALISATION OPERATION
Measured values & parametered timers display. Always Test sequences. Password access (code 4000).
accessible without code.
PROGRAMMING
Parameters configuration. Password access (code 1000
from factory).
The manual mode must be programmed on an input if
required.
Available functions in mode
Programming Operation
Code Code
Programming Visualisation Operation
Test off load
Available functions in “ AUT ” mode
Programming Operation
Code Code
Programming Visualisation Operation
Test off load Test on load Loss of main Main’s
source return
sequence sequence
PHASES ROTATION CONTROL
Function available only on source 1 in case of 3NBL,
4NBL and 41NBL network.
If a fault is detected, the source 1 is not indicated as
available.
V1 V1
OK NOK
ATYS 219 A
ATYS 441 A
1 2
displayed according to faulty source.
V3 V2 V2 V3
SOCOMEC - Réf. : 532 214 C
45
14. Controller ATyS
Presentation
OPERATION Operational modes
Programming
ATyS C20/C30 Operation
Visualisation
Automatic sequences
Programming
• This mode allows product parameters configuration
• Always accessible in mode (when programmed on
an input)
• Always accessible in AUT mode, changeover switch on
priority source, priority source being available
• Not accessible when “test off load”, “test on load”
functions are active or during automatic sequence.
Parameters requiring programming before
use:
• type of network
• nominal voltage
• nominal frequency
• control logic
• number of auxiliary contact.
> Navigation in the menus
or • Parameters access: Press “up”, “down”, “left” & “right” push buttons
• Parametermodification: press “left” & “right” push button to access the parameter to modify
+
Press “up’’ and “down” push buttons to modify the parameter
and “validate”
+
• Return to main menu: press “ESC” push button
Value is only modified after validation
> Programming access > Programming exit
• Step 1: press and hold for 5 s • Press and hold for 5 s
“validation” push button “validation” push button
• Step 2: enter code (factory code = 1000)
using navigation push buttons
• Step 3: press validation
push button
SOCOMEC - Réf. : 532 214 C
46
15. 47
Setup Voltage Frequency Timer 2I / 2O
Controller ATyS
OPERATION
1 2 1 2 1 2 1 2 1 2
ESC ESC ESC ESC ESC
Type of network Network 1 over Network 1 over Main Failure Option 1
1 2 1 2 voltage 1 2 frequency 1 2 Timer 1 2 Input 1 (variable
threshold threshold selection)
Phase-Phase Option 1
1 2 nominal voltage Network 1 over Network 1 over Delay on 1 2 Input 1 (contact
1 2 voltage 1 2 frequency 1 2 Transfer state selection)
threshold threshold Timer
Nominal hysteresis hysteresis
1 2
frequency Option 2
O main failure 1 2 Input 2 (variable
Network 1 Network 1 Timer selection)
Genset start 1 2
1 2 signal state 1 2 under voltage 1 2 under frequency Option 2
threshold threshold 1 2 Input 2 (contact
Network priority Main Return state selection)
1 2 selection: Network 1 Network 1 1 2 Timer
1 or 2 1 2 under voltage 1 2 under frequency Output 1*
threshold threshold 1 2
Manuel hysteresis hysteresis O main Return
1 2 retransfer Timer
1 2
Output 2*
Network 2 over Network 2 over 1 2
Impulse,
1 2 voltage 1 2 frequency
1 2 breaker or
threshold threshold Cool Down Load shedding
contactor logic
1 2 Timer timer**
PROGRAMMING MENU ARCHITECTURE
1 2
Number of Network 2 over Network 2 over
1 2 auxiliary contact 1 2 voltage 1 2 frequency
threshold threshold
Return on hysteresis hysteresis
1 2 position 0
1 -> 2
Network 2 Network 2
1 2 under voltage 1 2 under frequency
Return on
threshold threshold
1 2 position 0
2 -> 1
SOCOMEC - Réf. : 532 214 C
Network 2 Network 2
Programming
Number of 1 2 under voltage 1 2 under frequency
1 2 permutation threshold threshold
counter Reset hysteresis hysteresis
Programming
1 2 code modification
See page 49 See page 50 See page 51 See page 52 See pages 53 to 55
* Availability of output functions depending on control logic selection (impulse, breaker or contactor logic)
** Displayed if LS variable has been selected.
16. Controller ATyS
Presentation
OPERATION Operational modes
Programming
ATyS C20/C30 Operation
Visualisation
Automatic sequences
Programming
PARAMETER MODIFICATION
> Example:
Modify network 1 nominal voltage from 400 to 230 V.
Press to access first digit (blinking)
Press 2X to display 2 (blinking)
Press to access second digit (blinking)
Press 3X to display 3 (blinking)
Press to validate
ATI 074 A
SOCOMEC - Réf. : 532 214 C
48
17. Controller ATyS
OPERATION
Programming
PARAMETERS CHARACTERISTICS
> Menu Setup 1 2
LCD Denomination Definition Setting Default
range values
Type of Number of active conductors of controlled network 1BL, 2BL, 4NBL
1 2
network* (refer to annexes) 2NBL, 3NBL,
4NBL, 41 NBL
Network Phase-Neutral voltage for 1BL & 41NBL from 100 V 400 V
1 2
nominal voltage Phase-Phase voltage for others to 400 V
Network Network nominal frequency 50 Hz or 60 Hz 50 Hz
1 2
nominal
frequency
Genset start Normally opened or closed NO or NC NO
1 2
signal state
Network priority Keypad selection (1 or 2) 1 or 2 1(1)
1 2 selection Also possible via external contact using option ( 1 or 2 )
Manual Activation of the feature Yes or No No
1 2
Retransfer
Type of control Impulse, contactor or breaker. Imp, con, brE Imp
1 2
logic selection It might be necessary for some breakers not to set up
OMR and OMF timers to 0 (2 sec. for exemple).
Number of Depending on the number if available auxiliary contacts 0, 2, 3 2
1 2
auxiliary contact (switch, contactor, breaker)
Parameter 1, Allows to go to position 0 in case of voltage or frequency Yes or No No
1 2
return in outage (out if the defined U, f range)
position 0
Parameter 2 Allows to go to position 0 in case of voltage or frequency Yes or No No
1 2
return in outage (out if the defined U, f range)
position 0
Number of Allows source 1 -> source 2 automatic sequences Yes or No No
1 2
permutation counter reset
counter Reset
Programming Possible to change the programming code from 0000 to 1000
1 2
code 9999
modification
* Refer to annexes.
(1) It might be necessary for some breakers not to set up OMR and OMF timers to 0. (2 sec.)
SOCOMEC - Réf. : 532 214 C
49
18. Controller ATyS
Presentation
OPERATION Operational modes
Programming
ATyS C20/C30 Operation
Visualisation
Automatic sequences
Programming
> Volt Menu 1 2
Threshold detection starts from the loss of source
or source return sequence.
% Controlled value (voltage)
Over voltage threshold (oU)
Over voltage hysteresys
threshold (oUh)
Available source
100 t
Under voltage hysteresys
threshold (uUh)
ATYS 243 A GB
Under voltage threshold (uU)
LCD Denomination / Definition Setting Default
range values
Network 1 over voltage threshold From 102 115 %
1 2
to 120 %
Network 1 over voltage threshold hysteresis From 101 110 %
1 2
to 119 % (< oU)
Network 1 under voltage threshold From 80 85 %
1 2
to 98 %
Network 1 under voltage threshold hysteresis From 81 95 %
1 2
to 99 % (> uO)
Network 2 over voltage threshold From 102 115 %
1 2
to 120 %
Network 2 over voltage threshold hysteresis From 101 110 %
1 2
to 119 % (< oU)
Network 2 under voltage threshold From 80 85 %
1 2
to 98 %
Network 2 under voltage threshold hysteresis From 81 95 %
1 2
to 99 % (> uU)
Values definition: % of nominal values
Hysteresis values range is limited by thresholds values.
SOCOMEC - Réf. : 532 214 C
50
19. Controller ATyS
OPERATION
Programming
> Frequency Menu 1 2
Threshold detection starts from the loss of source
or source return sequence.
% Controlled value (frequency)
Over frequency threshold (oU)
Over frequency hysteresys
threshold (oUh)
Available source
100 t
Under frequency hysteresys
threshold (uUh)
ATYS 286 A GB
Under frequency threshold (uU)
LCD Denomination / Definition Setting Default
range values
Network 1 over frequency threshold From 101 105 %
1 2 to 120 %
Network 1 over frequency threshold hysteresis From 100.5 103 %
1 2 to 119.5% (< oF)
Network 1 under frequency threshold From 80 95 %
1 2 to 99 %
Network 1 under frequency threshold hysteresis From 80.5 97 %
1 2 to 99.5 % (> uF)
Network 2 over frequency threshold From 101 105 %
1 2 to 120 %
Network 2 over frequency threshold hysteresis From 100.5 103 %
1 2 to 119.5% (< oF)
Network 2 under frequency threshold From 80 95 %
1 2 to 99 %
Network 2 under frequency threshold hysteresis From 80.5 97 %
1 2 to 99.5 % (> uF)
Values definition: % of nominal values
Hysteresis values range is limited by thresholds values.
SOCOMEC - Réf. : 532 214 C
51
20. Controller ATyS
Presentation
OPERATION Operational modes
Programming
ATyS C20/C30 Operation
Visualisation
Automatic sequences
Programming
> Menu Timer 1 2
LCD Denomination Definition Setting Default
range values
Main Failure Delays priority network failure detection from 0 to 60 s 5s
1 2
Timer
Delay on Standby network stability validation before transfer from 0 to 60 s 5s
1 2
transfer Timer
O Main failure Rest in O position when transferring from 0 to 20 s 0s
1 2
Timer from main network to secondary network
Main return Main network stability validation before re-transfer from 0 to 30 min 2 min
1 2
Timer
O main return Rest in O position when re-transferring from standby from 0 to 20 s 0s
1 2
Timer network to main network
Cool down Allows generator cooling down period after load’s from 0 to 30 min 4 min
1 2
Timer retransfer from standby source (generator) to Main source
SOCOMEC - Réf. : 532 214 C
52
21. Controller ATyS
OPERATION
Programming
> Inputs/Outputs Menu 1 2
Output relays are NO type (construction) and
can not be configured as NC.
Input state can be configured: NC or NO.
LCD Denomination / Definition Setting range Default values
Input 1 Ft1, Ft2, Ft3, Ft4, Pri, Mtf, / /
1 2
S2A, MAN, CtS, tol, tfl, EJP
Input 1state NO, NC, / NO
1 2
Input 2 Ft1, Ft2, Ft3, Ft4, Pri, Mtf, / /
1 2
S2A, MAN, CtS, tol, tfl, EJP
Input 2 state NO, NC, / NO
1 2
Output 1 S1A, S2A, LS, / /
1 2
Output 2 S1A, S2A, LS, / /
1 2
SOCOMEC - Réf. : 532 214 C
53
22. Controller ATyS
Presentation
OPERATION Operational modes
Programming
ATyS C20/C30 Operation
Visualisation
Automatic sequences
Programming
> Inputs/Outputs Menu 1 2
Inputs
Variable Description
Ft1 Fault input 1. The fault led is blinking as soon as the input is active and
Ft1 is displayed on LCD. Reset when the input is de-activated
Ft2 Fault input 2. The fault led is blinking as soon as the input is active and Ft2 is displayed on LCD.
Reset when the input is de-activated
Ft3 Fault input 3. The fault led is blinking as soon as the input is active and Ft3 is displayed on LCD.
The transfer switch is immediately driven in 0 position (only in contactor mode).
Keypad action (Validation) necessary to Reset the fault
Ft4 Fault input 4. The fault led is blinking as soon as the input is active and Ft4 is displayed on LCD.
The transfer switch is immediately driven in 0 position (only in contactor mode).
Keypad action (Validation) necessary to Reset the fault
Pri(1) Priority network selection.
Network 1 has priority when input is not activated. Network 2 has priority if input is active
Mtf Remote manuel re-transfer. Feature identical to manual retransfer on keypad.
Re-transfer from priority network to backup network is allowed from input activation (1 s front).
The Mtf variable in the setup menu must be selected (Yes) to allow input recognition
S2A Information source 2 available (Genset) used instead of voltage / frequency measurement
(inhibited when S2A is selected)
Man Information transfer system in manual mode
All automatic commands (+ test on load) are inhibited as soon as the input is activated
CtS Remote transfer control. Possible to initiate transfer from priority source to backup source
before DTT ends. If DTT is set to its maximum value (60s), the transfer is initiated as soon as
the input is activated (1 s front)
tol Remote test on load. Started from input activation.
Re-transfer is blocked until input de-activation
tfl Remote test off load
Started from input activation (remote genset start / stop)
EJP 2 inputs are automatically affected to EJP
• input 1 for EJP advice, to start generator
• input 2 to transfer on emergency source
Retransfer is activated when input 2 dissapears
(1) This information is the only considered in case of option configuration. Programming variable Pri
is then inhibited.
• EJP cycle
EJP advice (input 1)
EJP transfer (input 2)
Start generator CDT
DTT
ATYS 442 B GB
Source 1
OMF OMR
Source 2
SOCOMEC - Réf. : 532 214 C
54
23. Controller ATyS
OPERATION
Programming
> Inputs/Outputs Menu 1 2
Outputs
Variable Description
S1A Source 1 available.
Output activated as soon as source 1 is considered available (similar to front led source 1)
S2A Source 2 available.
Output activated as soon as source 2 is considered available (similar to front led source 2)
LS Load shedding relay. LS timer corresponds to time available to disconnect the shed loads.
The relay is activated before permutation on standby network according to LS timer.
The relay is de-activated after retransfer on mains network and LS timer countdown
In case of LS function selection, it is required to configure associated LS timer.
Output Function Default Value Setting range
1 2
For LS: For LS:
S1A, S2A, LS, / 0 to 60 s (≤ DTT)* 3s
1 2
* In case of DTT variable configuration below LS, LS will be automatically set to DTT value.
• Example: LS configuration (output relay Ou1, 3 seconds):
The load shedding can’t be used with the priority
network (priority source = source 2 ). In this case, LS 1 2
output is not valid.
ATYS 269 A
1 2
• Load shedding cycle
DTT timer
Priority source - Emergency source -
emergency source priority source LS timer
transfer transfer
LS timer
Position II (emergency) AC activation
LS relay Activation
The output is de-activated in case of loss of
LS AC II Load shedding output power. It may then be required to put in
ATYS 334 A GB
parrallel with the load shedding ouptut relay,
position 2 auxiliary contact. This would avoid taking
back the load in case of loss of emergency source in
emergency position.
SOCOMEC - Réf. : 532 214 C
55
24. Controller ATyS
Presentation
OPERATION Operational modes
Programming
ATyS C20/C30 Operation
Visualisation
Automatic sequences
Operation
PRESENTATION
This mode allows in manual mode (not padlocked) to start
a test off load. In automatic mode, it allows to start a test,
on or off load.
Enter operation mode: Exit operation mode:
• Step 1: press and hold Press and hold the “TEST” push button for 5 s
the “TEST” push button for 5 s or automatic exit without action during around
2 min
• Step 2: enter the operation code (CE) using
navigation push buttons (code 4000)
Navigate in operation mode:
• Step 3: press “validation”
push button • Press “TEST” push button to access
different features
• Press “validation” push button to activate
required function
OPERATION MODE ARCHITECTURE
Enter: press 5 seconds
Yes, press
Led “test on load” “validation” Led “TEST ON LOAD” TEST ON LOAD
is blinking 1 2 is fixed Loss of priority
source sequence
No, press
“TEST”
Yes, press
“validation” TEST OFF LOAD
Led “test off load” Led “TEST OFF LOAD”
is blinking 1 2 is fixed Genset start
sequence
No, press
“TEST”
ATYS 432 A GB
Exit: press 5 seconds
SOCOMEC - Réf. : 532 214 C
56
25. Controller ATyS
OPERATION
Operation
TEST OFF LOAD (ACCESSIBLE IN AUT / MODES) 1 2
It can be activated from:
• operation mode
• ATyS D20 interface 1 2
start Gen
• programming input (TFL) if selected.
This test is made for applications where emergency
source 2 is typically a genset (priority source must be
source 1 ). This test can be activated, in automatic Gen ? No
mode, changeover switch in position 1 , source 1 1 2
available.
Yes
> Description Validate
• This mode will start and stop remotely genset operation
Stop Gen ?
without load transfer
• The test is not possible during an automatic sequence 1 2
> Keypad activation
After operation mode access, press mode push button
to make the test off load led blinking and validate to
ATI 087 B GB
start the sequence. 1 2
Gen stopped
TEST ON LOAD (ACCESSIBLE IN AUT MODE) 1 2
It is activated from:
• operation mode
• ATyS D20 interface
• programming input (TOL) if selected. Automatic cycle keeps priority.
> Description: > Remote activation via specific input
• This test simulates a loss of priority source situation. It is also possible to start a test on load remotely with
The sequence generates load transfer from priority the programming input TOL if selected.
source to emergency source after backup source start The cycle is started from contacts closure.
up operation (in case of genset). The return sequence The re-transfer is initiated from contacts opening.
always keeps manual re transfer feature activated (from
priority source availability). All timers are counted down.
The re-transfer from emergency source to
> Keypad activation priority source is blocked and only authorized
After operation mode access, press mode push button after manuel retransfer validation (keypad
to make test on load led blinking and validate to start a activation) or terminals opening.
cycle.
The test is only possible in automatic mode, the chan-
geover switch in priority source position, priority source Start gen relay is closed if source 2 has
being available. priority.
> Keypad or remote operation
Manual retransfer to validate on keypad.
In retransfer sequence from emergency
source to priority source, the MRT count
down is set to 10 seconds (maximum),
unless a lower value has been programmed.
SOCOMEC - Réf. : 532 214 C
57
26. Controller ATyS
Presentation
OPERATION Operational modes
Programming
ATyS C20/C30 Operation
Visualisation
Automatic sequences
Visualisation
PRESENTATION
• This mode allows parameters to be displayed
independently from mode / AUT switch position
(if programmed on input)
• No code required to access parameters visualisation
• Without any action during 5 seconds on the keypad,
the LCD displays voltage available on active network.
In case of changeover switch on 0 position, priority
network voltage is displayed.
Navigation in visualisation mode:
• Press “up” and “bottom” push buttons to access required parameter
• Press “left” and “right” push buttons to navigate in the different menus
SOCOMEC - Réf. : 532 214 C
58
27. Controller ATyS
OPERATION
Visualisation
VISUALISATION ARCHITECTURE MODE
MENUS
Metering Timers Counter
Phase-neutral voltage V1 Main Failure Timer Priority source ->
1 2 1 2
network 1 Emergency source
transfer counter
Phase-neutral voltage V2 Delay on Transfer Timer
1 2
network 1 1 2
Phase-neutral voltage V3 O Main Failure Timer
1 2
network 1 1 2
Network 1 frequency Main Return Timer
1 2 1 2
Phase-phase U12 O Main Return Timer
1 2
network 1 1 2
Phase-phase U23 Cool Down Timer
1 2
network 1 1 2
Phase-phase U31 Load shedding*
1 2
network 1 1 2
Phase-neutral voltage V1
1 2
network 2
Phase-phase U31
1 2
network 2
Network 2 frequency
1 2
* If selected.
All values indicated might not be available according to programmed network. Refer to annexes.
SOCOMEC - Réf. : 532 214 C
59
28. Controller ATyS
Presentation
OPERATION Operational modes
Programming
ATyS C20/C30 Operation
Visualisation
Automatic sequences
Automatic sequences
MANUAL MODE / AUTOMATIC MODE
> Manual mode - Automatic mode
permutation/power supply reappearance
• As soon as man input desapears (if selected), the
automatic mode is active
• Voltages and frequencies are verified to define new stable
position of the changeover switch
• The same table can be taken into account after
complete power supply loss (the product must be Refer to timer menus for MFT, MRT or DTT timers
completely discharged to reset = 3 minutes.) definition.
> New stable position of the changeover switch
Changeover switch Sources availability New position
initial position
Priority source Priority source available, Priority source
emergency source available or unavailable
Priority source Priority source unavailable for MFT time period, Emergency source. If emergency source
emergency source available or unavailable unavailable start emergency source first and wait
for DTT timer period before transfer
Emergency source Emergency source available, Emergency source
priority source unavailable
Emergency source Emergency source available, Priority source
priority source available for MRT time period
Emergency source Emergency source not available, Priority source
priority source available
Position 0 Priority source available, Available source to count down MRT before
emergency source unavailable transfer to priority source
Position 0 Priority source available, Priority source
emergency source unavailable
Position 0 Priority source unavailable, Emergency source
emergency source available
Position 0 Priority source unavailable, No action (because no supply).
emergency source unavailable When supply becomes available change to priority
source or emergency source
The switch transfers to new stable position as soon as Automatic mode is active.
LOSS OF PRIORITY SOURCE AUTOMATIC SEQUENCE
This sequence is started as soon as the switch is in > Specific feature: remote transfer control
automatic mode and in priority position (position I -
It is possible to transfer from main source to emergency
source 1 ).
source before DTT finishes up and to allow transfer with
• source 1 is available
CTS option if selected on an unput. DTT is automatically
• transfer switch is in position I
set up to its maximum value as soon as CTS is selected.
• source 2 is available or unavailable
> Available source
Source being within programmed voltage and frequency
settings, phases rotation being correct.
SOCOMEC - Réf. : 532 214 C
60
29. Controller ATyS
OPERATION
Automatic sequences
> Sequence description
Example:
position I = priority source ( 1 )
position II = emergency source type Genset ( 2 )
Automatic mode
Loss of
mains?
No
Loss of main?
Yes
MFT = 0
Count down MFT Genset
start up
Main comes back
before MFT ends? Start Genset
Reset MFT
Emergency Yes
source
available?
No No
Yes
Stop gen Priority
source?
Reset DTT
No
Gen fails No
Count down CTS = 1 ?
DTT = 0
Yes
Yes No
OMF 0?
Transfer I > 0
Count down OMF
OMF = 0
Transfer 0 > II Transfer I > II
Transfer I > II
ATYS 443 A GB
Go to priority source
return automatic
sequence
SOCOMEC - Réf. : 532 214 C
61
30. Controller ATyS
Presentation
OPERATION Operational modes
Programming
ATyS C20/C30 Operation
Visualisation
Automatic sequences
Automatic sequences
RETURN TO PRIORITY SOURCE
This sequence is activated as soon as the changeover • the changeover switch is in emergency position (ex:
switch is in automatic mode and in emergency position genset)
(position II): • the emergency source 2 is available.
• the priority source 1 is not available
> Specific feature: manual re-transfer
• When priority source comes back, it can be required Manual retransfer
not to automatically retransfer and wait for a more = validation press
adequate moment. Or
• It is possible, validating manual retransfer feature (refer optional input acti-
to programming), to block the re-transfer. vation, Mtf feature
It is initiated from:
ATYS 143 B
• validation push button localy or on ATyS D20
• via a programming input if MTF option is selected.
> Sequence description
Priority source unavailable
Generator running (emergency source) &
Switch in position II
Main’s
return Priority No
source
return? Yes
Manual re-transfer
Loss of
Yes priority source ?
MRT = 0 No
Count down
MRT
Priority source
lost again
before MRT Mode Yes
times out? semi-auto
activated ?
(Mtf)
Reset MRT
No Yes
Validation
OMR ≠ 0?
Yes
No
Transfer II >0
Count Down OMR
OMR = 0
Transfer 0 >I Transfer II >I
To loss of priority
source sequence
Reset CDT Count Down CDT Transfer II >I
Loss of priority source
CDT = 0
ATYS 155 A GB
Stop generator
position 1
Back to priority source control
SOCOMEC - Réf. : 532 214 C
62