CONTROLLER
                                           ATyS C20 / C30
       Notice d’utilisation - Operating instructions
                                F     GB   MAKE YOUR BUSINESS SAFE




SOCOMEC GROUP SWITCHING PROTECTION & UPS
F
         Sommaire


                    LA GAMME ATyS _________________________________3
                    PRÉSENTATION GÉNÉRALE _______________________4
                      Présentation des produits ________________________4
                    INSTALLATION ___________________________________5
                      Montage _______________________________________5
                      Dimensions_____________________________________5
                      Caractéristiques_________________________________5
                    RACCORDEMENTS _______________________________6
                      Circuits de commande ___________________________6
                      Commande électrique __________________________11
                    FONCTIONNEMENT _____________________________12
                      Présentation___________________________________12
                      Modes d’utilisation _____________________________13
                      Programmation ________________________________14
                      Exploitation____________________________________24
                      Visualisation ___________________________________26
                      Séquences automatiques _______________________28
                    AIDE AU DÉPANNAGE ___________________________31
                    ANNEXES ______________________________________32
                      Typologie des réseaux __________________________32
                      Programmation et câblage ATyS __________________33




    GB
         Summary




                    THE ATyS RANGE _______________________________35
                    GENERAL PRESENTATION _______________________36
                      Product introduction ____________________________36
                    INSTALLATION __________________________________37
                      Mounting _____________________________________37
                      Dimensions ___________________________________37
                      Characteristics_________________________________37
                    CONNECTIONS _________________________________38
                      Control circuits_________________________________38
                      Electrical operation _____________________________43
                    OPERATION ____________________________________44
                      Presentation ___________________________________44
                      Operational modes _____________________________45
                      Programming __________________________________46
                      Operation _____________________________________56
                      Visualisation ___________________________________58
                      Automatic sequences ___________________________60
                    TROUBLESHOOTING GUIDE _____________________63
                    ANNEXES ______________________________________64
                      Network analysis _______________________________64
                      Programming and connections ATyS C30 __________65




                                                                             SOCOMEC - Réf. : 532 214 C
2
Controller ATyS

THE ATyS RANGE



The ATyS family proposes a complete motorised                       • Automatic control: AtyS 6 products integrate all
changeover range including electrical and mechanical                  controls, timers and relays required to realise a
interlocking. Manual operation is always possible on all              Normal / Emergency application.
the products in case of emergency.                                  ATyS 6e and 6m versions also integrate the remote
The electric command is realised via a motorised                    controlled feature.
module, electronically driven by 2 types of logic:                  The motorised and control modules can easily be
• Remote controlled: ATyS 3 products are controlled by              replaced without disconnecting the power cables.
  volt free contacts allowing the switch to be driven in 1,
  0 or 2 position. These contacts can come from an
  external control logic.


   ATyS 3s       ATyS 3e         ATyS 6s        ATyS 6e         ATyS 6m        ATyS C30        ATyS C20   ATyS C40

                        MOTORISED CHANGEOVER


                                   Dual power supply


                                                                                        Changeover
                                         Integrated control relay                                          Dual genset
                                                                                         controller


                                                                    Metering


                 Com option                      Communication option


                2 I/2 O option                  2 inputs / 2 outputs option


                                                     Remote interfaces ATyS D10 & D20




> This instruction manual applies to following                      > Following products are delivered with their own
  products:                                                           instruction manual:
• Controller ATyS C20 / C30                                         • ATyS 3s
                                                                    • ATyS 3e, 6s, 6e
                                                                    • ATyS 6m
                                                                    • Remote interfaces ATyS D10 & D20
                                                                    • Centroller ATyS C40.



      For personnel and product safety, please
      read the contents of these operating
      instructions carefully before connecting.




SOCOMEC - Réf. : 532 214 C
                                                                                                                         35
Controller ATyS
                                                               Product introduction
GENERAL PRESENTATION
ATyS C20/C30


Product introduction
ATYS C20
LCD                                   Control terminals                      Modular frame
                         ATYS 453 A




Voltage sensing and
power supply terminals                                                       Keypad




ATYS C30
LCD                                   Control terminals                      Modular frame
                         ATYS 448 A




                                      Voltage sensing and
RJ45 terminal                         power supply terminals                 Keypad

                                                                        SOCOMEC - Réf. : 532 214 C
36
Controller ATyS
                                                                            Mounting
                INSTALLATION                                                Dimensions
                                                                            Characteristics
                ATyS C20/C30


                Mounting
                > DIN rail mounting
ATYS 449 A NB




                Dimensions
                                                             58
                                        106               48
                                                        26,5
                                                                  45
                    90




                                                                       62
                                                   93
ATYS 437 A




                Characteristics
                > IP
                IP2 and class II on front face
                > Operation
                • Temperature : -20 °C to +60 °C
                • Humidity : 80 % at 55 °C
                             95 % at 40 °C
                > Consumption
                7.5 VA max
                > Measurement category
                Cat III

                SOCOMEC - Réf. : 532 214 C
                                                                                              37
Controller ATyS
                                                                                                                                    Control circuits
CONNECTIONS                                                                                                                         Electrical operation

ATyS C20/C30


Control circuits
400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR
SWITCHING TYPE TECHNOLOGY
• Configure the type of control logic in impulse mode                                            • Automatic Power supply 203-205 or 104-106
  (see Programming chapter).                                                                       (see power supply chapter).

                                                                                          LOAD

                                 L1                                                                                                                    L1
                                 L2                                                                                                                    L2
                 1               L3                                                                                                                    L3                        2
                                 N                                                                                                                     N



                                      F1                                                                                                                               F2

                                                                                                                                                                       F1, F2
                                                                                                                                                                       Fuse protection
                                                                                                                                                                             230 Vac 5 A

                                                                     Ph Power
                                              DPS
                                                                     N 230 Vac



                                              Double Power
                                              Supply option                          Control                     CA1 CA0      CA2
                                                                           I         II    0     C



                                                                                                                              I1 I2

                                                                                                     O2

                                                  GE

                                                                    13 14 23 24 33 34 43 44 53              54 301 302 303 304 305 306 DC-* DC+*




                                 ONLY ON ATyS C30




                                                         Cable
                                                         RJ45 8/8
                                                                    N          L3          L2         L1                        L1           L3
                                      ATyS D10 or D20               103        104         105        106                      203          205
                                      remote interface
 ATYS 426 A GB




* Only on DC versions.


                 Maximum control cables lenght = 10 m.                                                    Remote interfaces maximum connection
                 In case of longer distance, insert control                                               cable (RJ45) = 3 m.
                 relays.

                                                                                                                                                   SOCOMEC - Réf. : 532 214 C
38
Controller ATyS
                                                                                                                                              CONNECTIONS




Control circuits
400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR
CONTACTOR TYPE TECHNOLOGY
• Configure the type of control logic in contactor (see                                        • Automatic Power supply 203-205 or 104-106
  Programming chapter).                                                                          (see power supply chapter).
                                                                                              LOAD

                                                                               K1                               K2
                                L1                                                                                                                 L1
                                L2                                                                                                                 L2
                1               L3                                                                                                                 L3                     2
                                N                                                                                                                  N



                                     F1                                                                                                                         F2




                                                                                                                                                                F1, F2
                                                                               K1                               K2                                              Fuse protection
                                                                                                                                                                      230 Vac 5 A
                                                                          K2                                         K1




                                                                                                                               I1 I2
                                                                                           O1        O2
                                                                           I        II



                                                GE
                                                                   13 14 23 24 33 34 43 44 53               54 301 302 303 304 305 306 DC-* DC+*




                                ONLY ON ATyS C30




                                                        Cable
                                                        RJ45 8/8
                                                                   N           L3        L2           L1                        L1           L3
                                     ATyS D10 or D20               103     104           105          106                      203          205
                                     remote interface
ATYS 438 A GB




* Only on DC versions.


                Maximum control cables lenght = 10 m.                                                     Remote interfaces maximum connection
                In case of longer distance, insert control                                                cable (RJ45) = 3 m.
                relays.

SOCOMEC - Réf. : 532 214 C
                                                                                                                                                                              39
Controller              ATyS
                                                                                                                                                 Control circuits
CONNECTIONS                                                                                                                                      Electrical operation

ATyS C20/C30


Control circuits
400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR
CIRCUIT BREAKER TYPE TECHNOLOGY

> Electrical interlocking via external control relays
• Configure the type of control logic in contactor (see                                                          • Automatic Power supply 203-205 or 104-106
  Programming chapter).                                                                                            (see power supply chapter).
                                                                         LOAD


                                 L1                                                                                                                                   L1
                                 L2                                                                                                                                   L2
                 1               L3                                                                                                                                   L3                 2
                                 N                                                                                                                                    N




                                      F1                                                                                                                                            F2



                                                               POS 1     POS 2                          POS 2        POS 1                    AUXILIARY CONTACT                     F1, F2
                                                              closing    opening                       closing       opening                BRE. 1            BRE. 2                Fuse protection
                                                                                                                                                                                          230 Vac 5 A

                                                          K1                                K2


                                                         K2                                           K1




                                                                                   I             II          O1      O2                       I1 I2


                                                  GE

                                                                        13 14 23 24 33 34 43 44 53                         54 301 302 303 304 305 306 DC-* DC+*




                                 ONLY ON ATyS C30




                                                         Cable
                                                         RJ45 8/8
                                                                        N              L3                  L2         L1                       L1           L3
                                      ATyS D10 or D20                   103        104                     105       106                      203          205
                                      remote interface
 ATYS 439 A GB




* Only on DC versions.


                 Maximum control cables lenght = 10 m.                                                                 Remote interfaces maximum connection
                 In case of longer distance, insert control                                                            cable (RJ45) = 3 m.
                 relays.

                                                                                                                                                                  SOCOMEC - Réf. : 532 214 C
40
Controller ATyS
                                                                                                                                        CONNECTIONS




Control circuits
400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR
CIRCUIT BREAKER TYPE TECHNOLOGY

> Electrical interlocking not integrated
• Configure the type of control logic in breaker                                           • Automatic Power supply 203-205 or 104-106
  (see Programming chapter)                                                                  (see power supply chapter).
                                                                                LOAD


                              L1                                                                                                             L1
                              L2                                                                                                             L2
                1             L3                                                                                                             L3               2
                              N                                                                                                              N




                                   F1                                                                                                                  F2
                                                                                        OPENING

                                                                                                                                                     F1, F2
                                                                                  Breaker 1   Breaker 2
                                                                                                                                                     Fuse protection
                                                                                                                                                          230 Vac 5 A




                                                                        CLOSING

                                                                   Breaker 1   Breaker 2                                 I1 I2




                                              GE

                                                             13 14 23 24 33 34 43 44 53                54 301 302 303 304 305 306 DC-*DC+*




                               ONLY ON ATyS C30




                                                  Cable
                                                  RJ45 8/8
                                                             N            L3           L2         L1                      L1          L3
                                   ATyS D10 or D20           103         104         105        106                       203         205
                                   remote interface
ATYS 440 B GB




* Only on DC versions.

                Maximum control cables lenght = 10 m.                                             This drawing is not including the electrical
                In case of longer distance, insert control                                        interlock.
                relays.
                                                                                                  It might be necessary for some breakers not
                Remote interfaces maximum connection                                              to set up OMR and OMF timers to 0.
                cable (RJ45) = 3 m.                                                               (refer to programming)

SOCOMEC - Réf. : 532 214 C
                                                                                                                                                                        41
Controller ATyS
                                                                                             Control circuits
CONNECTIONS                                                                                  Electrical operation

ATyS C20/C30


Control circuits
 Denomination Terminals Description                                                        Characteristics           Recommended
                                                                                                                     section
 Power supply N (103)          Neutral                                                     440 V ac (phase-phase)    1.5 mm2
 Source 1           L3 (104)   Phase 3                                                     maximum, 50 / 60 Hz
                    L2 (105)   Phase 2                                                     254 V ac (phase neutre)
                    L1 (106)   Phase 1                                                     maximum, 50 / 60 Hz
 Power supply L1 (203)         Phase 1                                                     440 V ac (phase-phase)    1.5 mm2
 Source 2           L3 (205)   Phase 3                                                     maximum
 Power supply DC(1) DC-        Power supply 0 V                                            From 9 V dc to 30 V dc    1.5 mm2
 12Vdc, 24Vdc       DC+        Power supply +V dc
 Genset(2)          13         Genset start / stop relay - 2 stable positions              Dry contact               1.5 mm2
 start signal       14         Programmable state - factory setting = NO, close to start   5A AC1 / 250 V
 Control            23         Impulse mode: order to close source 1                       5 A AC1 / 250 V           1.5 mm2
 (impulse,          24         Contactor mode: order to close contactor source 1
 contactor                     Breaker mode: order to close breaker source 1
 and breaker        33         Impulse mode: order to close source 2                       5 A AC1 / 250 V           1.5 mm2
 mode to            34         Contactor mode: order to close contactor source 2
 programm)                     Breaker mode: order to close breaker source 2
                    43         Impulse mode: order to reach position 0                     5 A AC1 / 250 V           1.5 mm2
                    44         Contactor mode: programmable relay O1
                               Breaker mode: order to open breaker source 1
                    53         Impulse mode: programmable relay O2                         5 A AC1 / 250 V           1.5 mm2
                    54         Contactor mode: programmable relay O2
                               Breaker mode: order to open breaker source 2
 Information        301        Auxiliary contact information position 1 AC1                Do not connect to         1.5 mm2
 auxiliary          302        Auxiliary contact information position 0 AC0                any power supply
 contacts           303        Auxiliary contact information position 2 AC2
 Programmable       304        Programmable input In1                                      Do not connect to         1.5 mm2
 Inputs             305        Programmable input In2                                      any power supply
 Common             306        Specific voltage supply                                     Do not connect to         1.5 mm2
 input                         Common terminals 301 to 306                                 any power supply
 Remote interface   RJ         Remote interface ATyS D10 or D20                            Maximum connection        RJ45 8/8
 connection                                                                                cable 3 m
(1) Only on DC version
(2) Refer to programming, Setup, to modify relay state.




                                                                                                        SOCOMEC - Réf. : 532 214 C
42
Controller ATyS
                                                                                                       CONNECTIONS




Electrical operation
POWER SUPPLY
ATyS C20/C30 integrates 2 power inputs (104-106, 203-                      AUT position
205), and consider the available source to keep the
                                                                           priority power source   1
product operational. Product supplied when voltage on




                                                           ATYS 444 A GB
terminals ≥ 100 Vac                                                        backup power source     2

For the DC version, these is only one power supply input                   product ON
(DC-, DC+).                                                                1 : terminals 104-106       2 : terminals 203-205




SOCOMEC - Réf. : 532 214 C
                                                                                                                               43
Controller ATyS
                                                                                                               Presentation
                OPERATION                                                                                      Operational modes
                                                                                                               Programming
                ATyS C20/C30                                                                                   Operation
                                                                                                               Visualisation
                                                                                                               Automatic sequences




                Presentation
                The product allows:
                • sources control,                                                   • voltage and frequency metering,
                • automatic transfer control in AUT mode,                            • system state display,
                • parameters configuration,                                          • alarm or fault indication,

                  FAULT led                                                            LCD
                  Led is on when product is faulty.                                   7 digits + 14 pointers
                  Disconnect power supplies to reset



                  POWER led
                  Green led is on when product is
                  powered




                  RJ45 connection*
                  RJ45 terminal for
                  ATyS D10 or D20.
                  If connected, the
                  LCD is off




                                                               Keypad

                   Sources state
                                                                 Escape                                                          Navigation
                  - Led is on: source = OK
                  - Led is off: source is not available
                                                                 LCD & leds test


                                                                 Operations                                                      Validation



                  Switch state                                  Operational modes
                  2 green leds:                                - Automatic sequence simulator (test on load)
ATYS 427 A GB




                  - switch I state                             - Genset remote start (test off load)
                  - switch II state                            - Changeover switch position control (local or remote)


                * only on ATyS C30.




                SOFTWARE VERSION
                Displayed after reset.
                                                                     ATYS 428 A GB




                (3 minutes power off action to allow reset).
                                                                                             Version
                                                                                             number




                                                                                                                       SOCOMEC - Réf. : 532 214 C
   44
Controller ATyS
                                                                                                                          OPERATION




Operational modes
VISUALISATION                                                                     OPERATION
Measured values & parametered timers display. Always                              Test sequences. Password access (code 4000).
accessible without code.

PROGRAMMING
Parameters configuration. Password access (code 1000
from factory).
The manual mode must be programmed on an input if
required.

                                                             Available functions in          mode
                  Programming                                                                                    Operation
                  Code                                                                                           Code

        Programming                                 Visualisation                                          Operation




                                                                                                          Test off load




                                                          Available functions in “ AUT ” mode
                  Programming                                                    Operation
                  Code                                                           Code

        Programming        Visualisation                                    Operation




                                                          Test off load                    Test on load          Loss of main      Main’s
                                                                                                                   source           return
                                                                                                                  sequence        sequence




PHASES ROTATION CONTROL
Function available only on source 1 in case of 3NBL,
4NBL and 41NBL network.
If a fault is detected, the source 1 is not indicated as
available.
                      V1                                     V1


                                OK                                        NOK
ATYS 219 A




                                       ATYS 441 A




                                                                                   1   2
                                                                                                displayed according to faulty source.
             V3                 V2                   V2               V3




SOCOMEC - Réf. : 532 214 C
                                                                                                                                             45
Controller ATyS
                                                                                   Presentation
OPERATION                                                                          Operational modes
                                                                                   Programming
ATyS C20/C30                                                                       Operation
                                                                                   Visualisation
                                                                                   Automatic sequences




Programming
• This mode allows product parameters configuration
• Always accessible in mode (when programmed on
  an input)
• Always accessible in AUT mode, changeover switch on
  priority source, priority source being available
• Not accessible when “test off load”, “test on load”
  functions are active or during automatic sequence.

          Parameters requiring programming before
          use:
          • type of network
          • nominal voltage
          • nominal frequency
          • control logic
          • number of auxiliary contact.


 > Navigation in the menus


     or   • Parameters access: Press “up”, “down”, “left” & “right” push buttons




           • Parametermodification: press “left” & “right” push button to access the parameter to modify
     +
             Press “up’’ and “down” push buttons to modify the parameter
             and “validate”
     +


          • Return to main menu: press “ESC” push button
            Value is only modified after validation


 > Programming access                                        > Programming exit

          • Step 1: press and hold for 5 s                         • Press and hold for 5 s
            “validation” push button                                 “validation” push button


          • Step 2: enter code (factory code = 1000)
            using navigation push buttons


           • Step 3: press validation
             push button




                                                                                           SOCOMEC - Réf. : 532 214 C
46
47
                                                                                        Setup                          Voltage                      Frequency                     Timer                          2I / 2O
Controller ATyS
                  OPERATION




                                                                             1   2                          1   2                        1   2                         1   2                       1   2
                                                                                     ESC                             ESC                         ESC                           ESC                             ESC
                                                                                        Type of network                Network 1 over               Network 1 over                Main Failure                   Option 1
                                                                             1   2                          1   2      voltage           1   2      frequency          1   2      Timer            1   2         Input 1 (variable
                                                                                                                       threshold                    threshold                                                    selection)
                                                                                        Phase-Phase                                                                                                              Option 1
                                                                             1   2      nominal voltage                Network 1 over               Network 1 over                Delay on         1   2         Input 1 (contact
                                                                                                            1   2      voltage           1   2      frequency          1   2      Transfer                       state selection)
                                                                                                                       threshold                    threshold                     Timer
                                                                                        Nominal                        hysteresis                   hysteresis
                                                                             1   2
                                                                                        frequency                                                                                                                Option 2
                                                                                                                                                                                  O main failure   1   2         Input 2 (variable
                                                                                                                       Network 1                    Network 1                     Timer                          selection)
                                                                                        Genset start                                                                   1   2
                                                                             1   2      signal state        1   2      under voltage     1   2      under frequency                                              Option 2
                                                                                                                       threshold                    threshold                                      1   2         Input 2 (contact
                                                                                        Network priority                                                                          Main Return                    state selection)
                                                                             1   2      selection:                     Network 1                    Network 1          1   2      Timer
                                                                                         1 or 2             1   2      under voltage     1   2      under frequency                                              Output 1*
                                                                                                                       threshold                    threshold                                      1   2
                                                                                        Manuel                         hysteresis                   hysteresis                    O main Return
                                                                             1   2      retransfer                                                                                Timer
                                                                                                                                                                       1   2
                                                                                                                                                                                                                 Output 2*
                                                                                                                       Network 2 over               Network 2 over                                 1   2
                                                                                        Impulse,
                                                                                                            1   2      voltage           1   2      frequency
                                                                             1   2      breaker or
                                                                                                                       threshold                    threshold                     Cool Down                      Load shedding
                                                                                        contactor logic
                                                                                                                                                                       1   2      Timer                          timer**
                                            PROGRAMMING MENU ARCHITECTURE




                                                                                                                                                                                                   1   2
                                                                                        Number of                      Network 2 over               Network 2 over
                                                                             1   2      auxiliary contact   1   2      voltage           1   2      frequency
                                                                                                                       threshold                    threshold
                                                                                        Return on                      hysteresis                   hysteresis
                                                                             1   2      position 0
                                                                                         1 -> 2
                                                                                                                       Network 2                    Network 2
                                                                                                            1   2      under voltage     1   2      under frequency
                                                                                        Return on
                                                                                                                       threshold                    threshold
                                                                             1   2      position 0
                                                                                         2 -> 1




                                                                                                                                                                                                                                     SOCOMEC - Réf. : 532 214 C
                                                                                                                       Network 2                    Network 2
                              Programming
                                                                                        Number of           1   2      under voltage     1   2      under frequency
                                                                             1   2      permutation                    threshold                    threshold
                                                                                        counter Reset                  hysteresis                   hysteresis
                                                                                        Programming
                                                                             1   2      code modification
                                                                                     See page 49                    See page 50                  See page 51                   See page 52                 See pages 53 to 55
                                                                            * Availability of output functions depending on control logic selection (impulse, breaker or contactor logic)
                                                                            ** Displayed if LS variable has been selected.
Controller ATyS
                                                                      Presentation
OPERATION                                                             Operational modes
                                                                      Programming
ATyS C20/C30                                                          Operation
                                                                      Visualisation
                                                                      Automatic sequences




Programming
PARAMETER MODIFICATION
> Example:
Modify network 1 nominal voltage from 400 to 230 V.




             Press                to access first digit (blinking)




             Press 2X             to display 2 (blinking)




             Press                to access second digit (blinking)




             Press 3X             to display 3 (blinking)




             Press                to validate
 ATI 074 A




                                                                              SOCOMEC - Réf. : 532 214 C
48
Controller ATyS
                                                                                                    OPERATION




Programming
PARAMETERS CHARACTERISTICS
> Menu Setup        1   2




LCD        Denomination      Definition                                                   Setting             Default
                                                                                          range               values
           Type of           Number of active conductors of controlled network            1BL, 2BL,           4NBL
1   2
           network*          (refer to annexes)                                           2NBL, 3NBL,
                                                                                          4NBL, 41 NBL
           Network         Phase-Neutral voltage for 1BL & 41NBL                          from 100 V          400 V
1   2
           nominal voltage Phase-Phase voltage for others                                 to 400 V

           Network           Network nominal frequency                                    50 Hz or 60 Hz      50 Hz
1   2
           nominal
           frequency
           Genset start      Normally opened or closed                                    NO or NC            NO
1   2
           signal state

           Network priority Keypad selection (1 or 2)                                     1 or 2              1(1)
1   2      selection        Also possible via external contact using option               ( 1 or 2 )

           Manual            Activation of the feature                                    Yes or No           No
1   2
           Retransfer

           Type of control   Impulse, contactor or breaker.                               Imp, con, brE       Imp
1   2
           logic selection          It might be necessary for some breakers not to set up
                                    OMR and OMF timers to 0 (2 sec. for exemple).
           Number of         Depending on the number if available auxiliary contacts      0, 2, 3             2
1   2
           auxiliary contact (switch, contactor, breaker)

           Parameter 1,      Allows to go to position 0 in case of voltage or frequency   Yes or No           No
1   2
           return in         outage (out if the defined U, f range)
           position 0
           Parameter 2       Allows to go to position 0 in case of voltage or frequency   Yes or No           No
1   2
           return in         outage (out if the defined U, f range)
           position 0
           Number of         Allows source 1 -> source 2 automatic sequences              Yes or No           No
1   2
           permutation       counter reset
           counter Reset
           Programming       Possible to change the programming code                      from 0000 to        1000
1   2
           code                                                                           9999
           modification

* Refer to annexes.
(1) It might be necessary for some breakers not to set up OMR and OMF timers to 0. (2 sec.)




SOCOMEC - Réf. : 532 214 C
                                                                                                                         49
Controller ATyS
                                                                                                 Presentation
OPERATION                                                                                        Operational modes
                                                                                                 Programming
ATyS C20/C30                                                                                     Operation
                                                                                                 Visualisation
                                                                                                 Automatic sequences




Programming
> Volt Menu                            1   2



Threshold detection starts from the loss of source
or source return sequence.


     %               Controlled value (voltage)

                                                                                 Over voltage threshold (oU)

                                                                                 Over voltage hysteresys
                                                                                 threshold (oUh)
                                                                                  Available source
 100                                                                                 t

                                                                                 Under voltage hysteresys
                                                                                 threshold (uUh)
     ATYS 243 A GB




                                                                                 Under voltage threshold (uU)




 LCD                       Denomination / Definition                                                   Setting             Default
                                                                                                       range               values
                           Network 1 over voltage threshold                                            From 102            115 %
 1   2
                                                                                                       to 120 %
                           Network 1 over voltage threshold hysteresis                                 From 101            110 %
 1   2
                                                                                                       to 119 % (< oU)
                           Network 1 under voltage threshold                                           From 80             85 %
 1   2
                                                                                                       to 98 %
                           Network 1 under voltage threshold hysteresis                                From 81             95 %
 1   2
                                                                                                       to 99 % (> uO)
                           Network 2 over voltage threshold                                            From 102            115 %
 1   2
                                                                                                       to 120 %
                           Network 2 over voltage threshold hysteresis                                 From 101            110 %
 1   2
                                                                                                       to 119 % (< oU)
                           Network 2 under voltage threshold                                           From 80             85 %
 1   2
                                                                                                       to 98 %
                           Network 2 under voltage threshold hysteresis                                From 81             95 %
 1   2
                                                                                                       to 99 % (> uU)



                      Values definition: % of nominal values
                      Hysteresis values range is limited by thresholds values.




                                                                                                                SOCOMEC - Réf. : 532 214 C
50
Controller ATyS
                                                                                                                     OPERATION




Programming
> Frequency Menu                                1   2



Threshold detection starts from the loss of source
or source return sequence.

    %                   Controlled value (frequency)

                                                                                    Over frequency threshold (oU)

                                                                                    Over frequency hysteresys
                                                                                    threshold (oUh)
                                                                                     Available source
100                                                                                     t

                                                                                    Under frequency hysteresys
                                                                                    threshold (uUh)
        ATYS 286 A GB




                                                                                    Under frequency threshold (uU)




LCD                           Denomination / Definition                                                  Setting            Default
                                                                                                         range              values
                              Network 1 over frequency threshold                                         From 101           105 %
1   2                                                                                                    to 120 %
                              Network 1 over frequency threshold hysteresis                              From 100.5       103 %
1   2                                                                                                    to 119.5% (< oF)
                              Network 1 under frequency threshold                                        From 80            95 %
1   2                                                                                                    to 99 %
                              Network 1 under frequency threshold hysteresis                             From 80.5        97 %
1   2                                                                                                    to 99.5 % (> uF)
                              Network 2 over frequency threshold                                         From 101           105 %
1   2                                                                                                    to 120 %
                              Network 2 over frequency threshold hysteresis                              From 100.5       103 %
1   2                                                                                                    to 119.5% (< oF)
                              Network 2 under frequency threshold                                        From 80            95 %
1   2                                                                                                    to 99 %
                              Network 2 under frequency threshold hysteresis                             From 80.5        97 %
1   2                                                                                                    to 99.5 % (> uF)


                         Values definition: % of nominal values
                         Hysteresis values range is limited by thresholds values.




SOCOMEC - Réf. : 532 214 C
                                                                                                                                       51
Controller ATyS
                                                                                  Presentation
OPERATION                                                                         Operational modes
                                                                                  Programming
ATyS C20/C30                                                                      Operation
                                                                                  Visualisation
                                                                                  Automatic sequences




Programming
> Menu Timer    1   2




 LCD     Denomination     Definition                                                  Setting          Default
                                                                                      range            values
         Main Failure     Delays priority network failure detection                   from 0 to 60 s   5s
 1   2
         Timer
         Delay on         Standby network stability validation before transfer        from 0 to 60 s   5s
 1   2
         transfer Timer
         O Main failure   Rest in O position when transferring                        from 0 to 20 s   0s
 1   2
         Timer            from main network to secondary network
         Main return      Main network stability validation before re-transfer        from 0 to 30 min 2 min
 1   2
         Timer
         O main return    Rest in O position when re-transferring from standby        from 0 to 20 s   0s
 1   2
         Timer            network to main network
         Cool down        Allows generator cooling down period after load’s           from 0 to 30 min 4 min
 1   2
         Timer            retransfer from standby source (generator) to Main source




                                                                                           SOCOMEC - Réf. : 532 214 C
52
Controller ATyS
                                                                                              OPERATION




Programming
> Inputs/Outputs Menu            1   2




         Output relays are NO type (construction) and
         can not be configured as NC.

Input state can be configured: NC or NO.
LCD                          Denomination / Definition   Setting range                   Default values
                             Input 1                     Ft1, Ft2, Ft3, Ft4, Pri, Mtf, / /
 1   2
                                                         S2A, MAN, CtS, tol, tfl, EJP
                             Input 1state                NO, NC, /                       NO
 1   2




                             Input 2                     Ft1, Ft2, Ft3, Ft4, Pri, Mtf, / /
 1   2
                                                         S2A, MAN, CtS, tol, tfl, EJP
                             Input 2 state               NO, NC, /                       NO
 1   2




                             Output 1                    S1A, S2A, LS, /                 /
 1   2




                             Output 2                    S1A, S2A, LS, /                 /
 1   2




SOCOMEC - Réf. : 532 214 C
                                                                                                                53
Controller ATyS
                                                                                                                Presentation
                OPERATION                                                                                       Operational modes
                                                                                                                Programming
                ATyS C20/C30                                                                                    Operation
                                                                                                                Visualisation
                                                                                                                Automatic sequences




                Programming
                > Inputs/Outputs Menu                1   2



                      Inputs
                Variable                 Description
                Ft1                      Fault input 1. The fault led is blinking as soon as the input is active and
                                         Ft1 is displayed on LCD. Reset when the input is de-activated
                Ft2                      Fault input 2. The fault led is blinking as soon as the input is active and Ft2 is displayed on LCD.
                                         Reset when the input is de-activated
                Ft3                      Fault input 3. The fault led is blinking as soon as the input is active and Ft3 is displayed on LCD.
                                         The transfer switch is immediately driven in 0 position (only in contactor mode).
                                         Keypad action (Validation) necessary to Reset the fault
                Ft4                      Fault input 4. The fault led is blinking as soon as the input is active and Ft4 is displayed on LCD.
                                         The transfer switch is immediately driven in 0 position (only in contactor mode).
                                         Keypad action (Validation) necessary to Reset the fault
                Pri(1)                   Priority network selection.
                                         Network 1 has priority when input is not activated. Network 2 has priority if input is active
                Mtf                      Remote manuel re-transfer. Feature identical to manual retransfer on keypad.
                                         Re-transfer from priority network to backup network is allowed from input activation (1 s front).
                                         The Mtf variable in the setup menu must be selected (Yes) to allow input recognition
                S2A                      Information source 2 available (Genset) used instead of voltage / frequency measurement
                                         (inhibited when S2A is selected)
                Man                      Information transfer system in manual mode
                                         All automatic commands (+ test on load) are inhibited as soon as the input is activated
                CtS                      Remote transfer control. Possible to initiate transfer from priority source to backup source
                                         before DTT ends. If DTT is set to its maximum value (60s), the transfer is initiated as soon as
                                         the input is activated (1 s front)
                tol                      Remote test on load. Started from input activation.
                                         Re-transfer is blocked until input de-activation
                tfl                      Remote test off load
                                         Started from input activation (remote genset start / stop)
                EJP                      2 inputs are automatically affected to EJP
                                         • input 1 for EJP advice, to start generator
                                         • input 2 to transfer on emergency source
                                         Retransfer is activated when input 2 dissapears

                         (1) This information is the only considered in case of option configuration. Programming variable Pri
                         is then inhibited.

                • EJP cycle

                 EJP advice (input 1)

                EJP transfer (input 2)

                       Start generator                                     CDT


                                 DTT
ATYS 442 B GB




                            Source 1
                                                             OMF        OMR
                            Source 2


                                                                                                                            SOCOMEC - Réf. : 532 214 C
 54
Controller ATyS
                                                                                                                                        OPERATION




                Programming
                > Inputs/Outputs Menu                1   2



                     Outputs
                Variable                Description
                S1A                     Source 1 available.
                                        Output activated as soon as source 1 is considered available (similar to front led source 1)
                S2A                     Source 2 available.
                                        Output activated as soon as source 2 is considered available (similar to front led source 2)
                LS                      Load shedding relay. LS timer corresponds to time available to disconnect the shed loads.
                                        The relay is activated before permutation on standby network according to LS timer.
                                        The relay is de-activated after retransfer on mains network and LS timer countdown

                In case of LS function selection, it is required to configure associated LS timer.
                Output                          Function                                                 Default Value             Setting range

                 1   2
                                                                                                         For LS:                   For LS:
                                                S1A, S2A, LS, /                                          0 to 60 s (≤ DTT)*        3s
                 1   2




                * In case of DTT variable configuration below LS, LS will be automatically set to DTT value.

                • Example: LS configuration (output relay Ou1, 3 seconds):
                The load shedding can’t be used with the priority
                network (priority source = source 2 ). In this case, LS                              1   2


                output is not valid.
                                                                                       ATYS 269 A




                                                                                                     1   2




                • Load shedding cycle

                                 DTT timer
                                                                    Priority source -                              Emergency source -
                                                                   emergency source                                  priority source           LS timer
                                                                        transfer                                         transfer
                                       LS timer

                                                                          Position II (emergency) AC activation

                                                                                   LS relay Activation




                                                                                                          The output is de-activated in case of loss of
                LS           AC II          Load shedding output                                          power. It may then be required to put in
ATYS 334 A GB




                                                                                                    parrallel with the load shedding ouptut relay,
                                                                                                    position 2 auxiliary contact. This would avoid taking
                                                                                                    back the load in case of loss of emergency source in
                                                                                                    emergency position.


                SOCOMEC - Réf. : 532 214 C
                                                                                                                                                            55
Controller ATyS
                                                                                                                 Presentation
                OPERATION                                                                                        Operational modes
                                                                                                                 Programming
                ATyS C20/C30                                                                                     Operation
                                                                                                                 Visualisation
                                                                                                                 Automatic sequences




                Operation
                PRESENTATION
                This mode allows in manual mode (not padlocked) to start
                a test off load. In automatic mode, it allows to start a test,
                on or off load.


                Enter operation mode:                                                     Exit operation mode:


                        • Step 1: press and hold                                                   Press and hold the “TEST” push button for 5 s
                          the “TEST” push button for 5 s                                           or automatic exit without action during around
                                                                                                   2 min
                        • Step 2: enter the operation code (CE) using
                          navigation push buttons (code 4000)
                                                                                          Navigate in operation mode:

                        • Step 3: press “validation”
                          push button                                                              • Press “TEST” push button to access
                                                                                                     different features


                                                                                                   • Press “validation” push button to activate
                                                                                                     required function




                OPERATION MODE ARCHITECTURE
                                                               Enter: press 5 seconds



                                                           Yes, press
                    Led “test on load”                     “validation”      Led “TEST ON LOAD”                  TEST ON LOAD
                       is blinking         1   2                                    is fixed                     Loss of priority
                                                                                                                source sequence

                                                   No, press
                                                   “TEST”




                                                           Yes, press
                                                           “validation”                                         TEST OFF LOAD
                    Led “test off load”                                      Led “TEST OFF LOAD”
                        is blinking        1   2                                    is fixed                      Genset start
                                                                                                                   sequence

                                                   No, press
                                                   “TEST”
ATYS 432 A GB




                                                               Exit: press 5 seconds




                                                                                                                                 SOCOMEC - Réf. : 532 214 C
         56
Controller ATyS
                                                                                                                          OPERATION




Operation
TEST OFF LOAD (ACCESSIBLE IN AUT /                      MODES)                         1   2




It can be activated from:
• operation mode
• ATyS D20 interface                                                                           1   2



                                                                                                       start Gen
• programming input (TFL) if selected.
This test is made for applications where emergency
source 2 is typically a genset (priority source must be
source 1 ). This test can be activated, in automatic                                                       Gen ?     No
mode, changeover switch in position 1 , source 1                                                   1   2



available.
                                                                                                               Yes
> Description                                                                                                                 Validate

• This mode will start and stop remotely genset operation
                                                                                                Stop Gen ?
  without load transfer
• The test is not possible during an automatic sequence                                            1   2




> Keypad activation
After operation mode access, press mode push button
to make the test off load led blinking and validate to
                                                                ATI 087 B GB




start the sequence.                                                                            1   2




                                                                                               Gen stopped




TEST ON LOAD (ACCESSIBLE IN AUT MODE)                                          1   2




It is activated from:
• operation mode
• ATyS D20 interface
• programming input (TOL) if selected.                                                 Automatic cycle keeps priority.


> Description:                                                  > Remote activation via specific input
• This test simulates a loss of priority source situation.      It is also possible to start a test on load remotely with
  The sequence generates load transfer from priority            the programming input TOL if selected.
  source to emergency source after backup source start          The cycle is started from contacts closure.
  up operation (in case of genset). The return sequence         The re-transfer is initiated from contacts opening.
  always keeps manual re transfer feature activated (from
  priority source availability). All timers are counted down.
                                                                                       The re-transfer from emergency source to
> Keypad activation                                                                    priority source is blocked and only authorized
After operation mode access, press mode push button                                    after manuel retransfer validation (keypad
to make test on load led blinking and validate to start a                              activation) or terminals opening.
cycle.
The test is only possible in automatic mode, the chan-
geover switch in priority source position, priority source                             Start gen relay is closed if source 2 has
being available.                                                                       priority.
> Keypad or remote operation
       Manual retransfer to validate on keypad.
       In retransfer sequence from emergency
       source to priority source, the MRT count
       down is set to 10 seconds (maximum),
       unless a lower value has been programmed.

SOCOMEC - Réf. : 532 214 C
                                                                                                                                            57
Controller ATyS
                                                                                Presentation
OPERATION                                                                       Operational modes
                                                                                Programming
ATyS C20/C30                                                                    Operation
                                                                                Visualisation
                                                                                Automatic sequences




Visualisation
PRESENTATION
• This mode allows parameters to be displayed
  independently from mode        / AUT switch position
  (if  programmed on input)
• No code required to access parameters visualisation
• Without any action during 5 seconds on the keypad,
  the LCD displays voltage available on active network.
  In case of changeover switch on 0 position, priority
  network voltage is displayed.


 Navigation in visualisation mode:



       • Press “up” and “bottom” push buttons to access required parameter


       • Press “left” and “right” push buttons to navigate in the different menus




                                                                                        SOCOMEC - Réf. : 532 214 C
58
Controller ATyS
                                                                                               OPERATION




Visualisation
VISUALISATION ARCHITECTURE MODE

MENUS
Metering                                    Timers                             Counter
                 Phase-neutral voltage V1            Main Failure Timer                  Priority source ->
1   2                                       1   2

                 network 1                                                               Emergency source
                                                                                         transfer counter
                 Phase-neutral voltage V2            Delay on Transfer Timer
1   2
                 network 1                  1   2




                 Phase-neutral voltage V3            O Main Failure Timer
1   2
                 network 1                  1   2




                 Network 1 frequency                 Main Return Timer
1   2                                       1   2




                 Phase-phase U12                     O Main Return Timer
1   2
                 network 1                  1   2




                 Phase-phase U23                     Cool Down Timer
1   2
                 network 1                  1   2




                 Phase-phase U31                     Load shedding*
1   2
                 network 1                  1   2




                 Phase-neutral voltage V1
1   2
                 network 2


                 Phase-phase U31
1   2
                 network 2


                 Network 2 frequency
1   2




* If selected.


        All values indicated might not be available according to programmed network. Refer to annexes.




SOCOMEC - Réf. : 532 214 C
                                                                                                                  59
Controller ATyS
                                                                                       Presentation
OPERATION                                                                              Operational modes
                                                                                       Programming
ATyS C20/C30                                                                           Operation
                                                                                       Visualisation
                                                                                       Automatic sequences




Automatic sequences
MANUAL MODE / AUTOMATIC MODE
> Manual mode - Automatic mode
     permutation/power supply reappearance
• As soon as man input desapears (if selected), the
  automatic mode is active
• Voltages and frequencies are verified to define new stable
  position of the changeover switch
• The same table can be taken into account after
  complete power supply loss (the product must be                Refer to timer menus for MFT, MRT or DTT timers
  completely discharged to reset = 3 minutes.)                   definition.

> New stable position of the changeover switch

 Changeover switch Sources availability                                 New position
 initial position
 Priority source     Priority source available,                         Priority source
                     emergency source available or unavailable
 Priority source     Priority source unavailable for MFT time period,   Emergency source. If emergency source
                     emergency source available or unavailable          unavailable start emergency source first and wait
                                                                        for DTT timer period before transfer
 Emergency source    Emergency source available,                        Emergency source
                     priority source unavailable
 Emergency source    Emergency source available,                        Priority source
                     priority source available for MRT time period
 Emergency source    Emergency source not available,                    Priority source
                     priority source available
 Position 0          Priority source available,                         Available source to count down MRT before
                     emergency source unavailable                       transfer to priority source
 Position 0          Priority source available,                         Priority source
                     emergency source unavailable
 Position 0          Priority source unavailable,                       Emergency source
                     emergency source available
 Position 0          Priority source unavailable,                       No action (because no supply).
                     emergency source unavailable                       When supply becomes available change to priority
                                                                        source or emergency source

        The switch transfers to new stable position as soon as Automatic mode is active.



LOSS OF PRIORITY SOURCE AUTOMATIC SEQUENCE
This sequence is started as soon as the switch is in           > Specific feature: remote transfer control
automatic mode and in priority position (position I -
                                                               It is possible to transfer from main source to emergency
source 1 ).
                                                               source before DTT finishes up and to allow transfer with
• source 1 is available
                                                               CTS option if selected on an unput. DTT is automatically
• transfer switch is in position I
                                                               set up to its maximum value as soon as CTS is selected.
• source 2 is available or unavailable
> Available source
Source being within programmed voltage and frequency
settings, phases rotation being correct.
                                                                                                SOCOMEC - Réf. : 532 214 C
60
Controller ATyS
                                                                                                                                               OPERATION




Automatic sequences
> Sequence description
Example:
position I = priority source ( 1 )
position II = emergency source type Genset ( 2 )
                                   Automatic mode




                     Loss of
                     mains?
                                                    No
                                    Loss of main?



                                            Yes



                                                    MFT = 0
                                  Count down MFT                                                        Genset
                                                                                                        start up
                                              Main comes back
                                              before MFT ends?                           Start Genset


                                   Reset MFT


                                                                                         Emergency            Yes
                                                                                          source
                                                                                         available?

                                                                       No                       No

                                                    Yes
                             Stop gen                         Priority
                                                              source?




                                                            Reset DTT


                                                                                                                                         No


                                                                       Gen fails                              No
                                                                                          Count down                             CTS = 1 ?
                                                                                           DTT = 0


                                                                                                                                         Yes




                                                                                   Yes                   No
                                                                                          OMF    0?




                                                          Transfer I        > 0




                                                           Count down OMF


                                                                       OMF = 0



                                                          Transfer 0        > II                                   Transfer I     > II




                                                                                                         Transfer I             > II
ATYS 443 A GB




                                                                                     Go to priority source
                                                                                      return automatic
                                                                                          sequence




SOCOMEC - Réf. : 532 214 C
                                                                                                                                                                 61
Controller ATyS
                                                                                                                                        Presentation
OPERATION                                                                                                                               Operational modes
                                                                                                                                        Programming
ATyS C20/C30                                                                                                                            Operation
                                                                                                                                        Visualisation
                                                                                                                                        Automatic sequences




Automatic sequences
RETURN TO PRIORITY SOURCE
This sequence is activated as soon as the changeover                                              • the changeover switch is in emergency position (ex:
switch is in automatic mode and in emergency position                                               genset)
(position II):                                                                                    • the emergency source 2 is available.
• the priority source 1 is not available

> Specific feature: manual re-transfer
• When priority source comes back, it can be required                                                                                                                         Manual retransfer
   not to automatically retransfer and wait for a more                                                                                                                        = validation press
   adequate moment.                                                                                                                                                                           Or
• It is possible, validating manual retransfer feature (refer                                                                                                                optional input acti-
   to programming), to block the re-transfer.                                                                                                                                vation, Mtf feature
It is initiated from:
                                                                                     ATYS 143 B




• validation push button localy or on ATyS D20
• via a programming input if MTF option is selected.


> Sequence description
                                                   Priority source unavailable
                                             Generator running (emergency source) &
                                                       Switch in position II




                                          Main’s
                                          return            Priority       No
                                                            source
                                                            return?                                                                                                                Yes
                                                                                                        Manual re-transfer
                                                                                                                                                                           Loss of
                                                                  Yes                                                                                                 priority source ?



                                                                           MRT = 0                                                                                                 No
                                                          Count down
                                                             MRT


                                                                   Priority source
                                                                      lost again
                                                                    before MRT                                                            Mode         Yes
                                                                     times out?                                                         semi-auto
                                                                                                                                        activated ?
                                                                                                                                           (Mtf)
                                                           Reset MRT

                                                                                                                                        No       Yes
                                                                                                                                                             Validation




                                                                                                                                        OMR ≠ 0?
                                                                                                           Yes
                                                                                                                                                                             No


                                                                                                       Transfer II    >0




                                                                                                       Count Down OMR

                                                                                                                     OMR = 0



                                                                                                       Transfer 0      >I                                      Transfer II        >I




                                  To loss of priority
                                  source sequence
                                                                       Reset CDT                                                  Count Down CDT             Transfer II               >I
                                                                                                              Loss of priority source
                                                                                                                                                CDT = 0
                                                                                                                                                                                               ATYS 155 A GB




                                                                                                                                   Stop generator
                                                                                                                                      position 1
                                                                                                                            Back to priority source control



                                                                                                                                                             SOCOMEC - Réf. : 532 214 C
62
09. operating instruction c20 c30
09. operating instruction c20 c30
09. operating instruction c20 c30
09. operating instruction c20 c30
09. operating instruction c20 c30
09. operating instruction c20 c30

More Related Content

What's hot

Catalogue tunisie cable
Catalogue  tunisie cableCatalogue  tunisie cable
Catalogue tunisie cableBen Hichem
 
03_20R300_1_C300 Controller Architecture.ppt
03_20R300_1_C300 Controller Architecture.ppt03_20R300_1_C300 Controller Architecture.ppt
03_20R300_1_C300 Controller Architecture.pptHaTa33
 
S10 tr-tank rupturetutorial
S10 tr-tank rupturetutorialS10 tr-tank rupturetutorial
S10 tr-tank rupturetutorialazerty82
 
PLC data types and addressing
PLC data types and addressingPLC data types and addressing
PLC data types and addressingAmeen San
 
Weg cfw300-manual-de-programacao-10003424521-1.1x-manual-portugues-br
Weg cfw300-manual-de-programacao-10003424521-1.1x-manual-portugues-brWeg cfw300-manual-de-programacao-10003424521-1.1x-manual-portugues-br
Weg cfw300-manual-de-programacao-10003424521-1.1x-manual-portugues-brdoidohugo
 
Rt acceptance criteria by zas
Rt acceptance  criteria by zasRt acceptance  criteria by zas
Rt acceptance criteria by zaszaheer sajid
 
Pneumatics festo eng
Pneumatics festo engPneumatics festo eng
Pneumatics festo engDavid Trần
 
Low voltage circuit breakers & contactors general leaflet ls
Low voltage circuit breakers & contactors general leaflet   lsLow voltage circuit breakers & contactors general leaflet   ls
Low voltage circuit breakers & contactors general leaflet lsmaianhbao_6519
 
Modelling and Stress Analysis of the Pig Loop Module of a Piping System.
Modelling and Stress Analysis of the Pig Loop Module of a Piping System.Modelling and Stress Analysis of the Pig Loop Module of a Piping System.
Modelling and Stress Analysis of the Pig Loop Module of a Piping System.IJRES Journal
 
ABB Transformer Bushing Molykote Recommendations - Project Sales Corp
ABB Transformer Bushing Molykote Recommendations - Project Sales CorpABB Transformer Bushing Molykote Recommendations - Project Sales Corp
ABB Transformer Bushing Molykote Recommendations - Project Sales CorpProject Sales Corp
 
Tolerance chart
Tolerance chartTolerance chart
Tolerance chartenagaraj
 
Breaking the rules! bicsi
Breaking the rules! bicsi  Breaking the rules! bicsi
Breaking the rules! bicsi Jeffrey Lam
 
ITS_Repair & Refurbishment of GE SPEEDTRONIC Mark V and ABB INFI 90 Power Mod...
ITS_Repair & Refurbishment of GE SPEEDTRONIC Mark V and ABB INFI 90 Power Mod...ITS_Repair & Refurbishment of GE SPEEDTRONIC Mark V and ABB INFI 90 Power Mod...
ITS_Repair & Refurbishment of GE SPEEDTRONIC Mark V and ABB INFI 90 Power Mod...Winson Tan
 
Volvo EC210B LC EC210BLC Excavator Service Repair Manual
Volvo EC210B LC EC210BLC Excavator Service Repair ManualVolvo EC210B LC EC210BLC Excavator Service Repair Manual
Volvo EC210B LC EC210BLC Excavator Service Repair Manualjfkksefmmsem
 
AIS Torque Cal, Torque Chart and Bolting Pattern.pdf
AIS Torque Cal, Torque Chart and Bolting Pattern.pdfAIS Torque Cal, Torque Chart and Bolting Pattern.pdf
AIS Torque Cal, Torque Chart and Bolting Pattern.pdfWorawitBoonnaeb
 
Welding consumable control
Welding consumable controlWelding consumable control
Welding consumable controlNguyen Tung
 

What's hot (20)

Catalogue tunisie cable
Catalogue  tunisie cableCatalogue  tunisie cable
Catalogue tunisie cable
 
03_20R300_1_C300 Controller Architecture.ppt
03_20R300_1_C300 Controller Architecture.ppt03_20R300_1_C300 Controller Architecture.ppt
03_20R300_1_C300 Controller Architecture.ppt
 
S10 tr-tank rupturetutorial
S10 tr-tank rupturetutorialS10 tr-tank rupturetutorial
S10 tr-tank rupturetutorial
 
Dcs
DcsDcs
Dcs
 
PLC data types and addressing
PLC data types and addressingPLC data types and addressing
PLC data types and addressing
 
Weg cfw300-manual-de-programacao-10003424521-1.1x-manual-portugues-br
Weg cfw300-manual-de-programacao-10003424521-1.1x-manual-portugues-brWeg cfw300-manual-de-programacao-10003424521-1.1x-manual-portugues-br
Weg cfw300-manual-de-programacao-10003424521-1.1x-manual-portugues-br
 
Rt acceptance criteria by zas
Rt acceptance  criteria by zasRt acceptance  criteria by zas
Rt acceptance criteria by zas
 
Pneumatics festo eng
Pneumatics festo engPneumatics festo eng
Pneumatics festo eng
 
Sinamics g120 treinamento (en)
Sinamics g120 treinamento (en)Sinamics g120 treinamento (en)
Sinamics g120 treinamento (en)
 
Low voltage circuit breakers & contactors general leaflet ls
Low voltage circuit breakers & contactors general leaflet   lsLow voltage circuit breakers & contactors general leaflet   ls
Low voltage circuit breakers & contactors general leaflet ls
 
Modelling and Stress Analysis of the Pig Loop Module of a Piping System.
Modelling and Stress Analysis of the Pig Loop Module of a Piping System.Modelling and Stress Analysis of the Pig Loop Module of a Piping System.
Modelling and Stress Analysis of the Pig Loop Module of a Piping System.
 
ABB Transformer Bushing Molykote Recommendations - Project Sales Corp
ABB Transformer Bushing Molykote Recommendations - Project Sales CorpABB Transformer Bushing Molykote Recommendations - Project Sales Corp
ABB Transformer Bushing Molykote Recommendations - Project Sales Corp
 
S81-HS Panel Presentation
S81-HS Panel PresentationS81-HS Panel Presentation
S81-HS Panel Presentation
 
Self Regulating Heat Trace Guide
Self Regulating Heat Trace GuideSelf Regulating Heat Trace Guide
Self Regulating Heat Trace Guide
 
Tolerance chart
Tolerance chartTolerance chart
Tolerance chart
 
Breaking the rules! bicsi
Breaking the rules! bicsi  Breaking the rules! bicsi
Breaking the rules! bicsi
 
ITS_Repair & Refurbishment of GE SPEEDTRONIC Mark V and ABB INFI 90 Power Mod...
ITS_Repair & Refurbishment of GE SPEEDTRONIC Mark V and ABB INFI 90 Power Mod...ITS_Repair & Refurbishment of GE SPEEDTRONIC Mark V and ABB INFI 90 Power Mod...
ITS_Repair & Refurbishment of GE SPEEDTRONIC Mark V and ABB INFI 90 Power Mod...
 
Volvo EC210B LC EC210BLC Excavator Service Repair Manual
Volvo EC210B LC EC210BLC Excavator Service Repair ManualVolvo EC210B LC EC210BLC Excavator Service Repair Manual
Volvo EC210B LC EC210BLC Excavator Service Repair Manual
 
AIS Torque Cal, Torque Chart and Bolting Pattern.pdf
AIS Torque Cal, Torque Chart and Bolting Pattern.pdfAIS Torque Cal, Torque Chart and Bolting Pattern.pdf
AIS Torque Cal, Torque Chart and Bolting Pattern.pdf
 
Welding consumable control
Welding consumable controlWelding consumable control
Welding consumable control
 

Similar to 09. operating instruction c20 c30

cts320_manual.pdf
cts320_manual.pdfcts320_manual.pdf
cts320_manual.pdfTrung855324
 
Mark VI ST Control Product Overview GEH 6127
Mark VI ST Control Product Overview GEH 6127Mark VI ST Control Product Overview GEH 6127
Mark VI ST Control Product Overview GEH 6127Mircea Tomescu
 
Operations and Maintaince Manual Sample
Operations and Maintaince Manual SampleOperations and Maintaince Manual Sample
Operations and Maintaince Manual SamplePeter Coffey
 
Siemens catalog tong hop 3 uf simocode
Siemens catalog tong hop 3 uf simocodeSiemens catalog tong hop 3 uf simocode
Siemens catalog tong hop 3 uf simocodeDien Ha The
 
BEP Marine Catalog
BEP Marine CatalogBEP Marine Catalog
BEP Marine CatalogRimsky Cheng
 
2005 MITSUBISHI AIRTREK Service Repair Manual
2005 MITSUBISHI AIRTREK Service Repair Manual2005 MITSUBISHI AIRTREK Service Repair Manual
2005 MITSUBISHI AIRTREK Service Repair Manualtygrtd iolpo
 
Vlt fc 300 operating instructions
Vlt fc 300 operating instructionsVlt fc 300 operating instructions
Vlt fc 300 operating instructionsToàn Huỳnh
 
Yamaha 60 fehto, p60th outboard service repair manual l 551924
Yamaha 60 fehto, p60th outboard service repair manual l 551924  Yamaha 60 fehto, p60th outboard service repair manual l 551924
Yamaha 60 fehto, p60th outboard service repair manual l 551924 fjsekdmmme
 
YAMAHA 60FETO OUTBOARD Service Repair Manual L: 472180 -
YAMAHA 60FETO OUTBOARD Service Repair Manual L: 472180 -YAMAHA 60FETO OUTBOARD Service Repair Manual L: 472180 -
YAMAHA 60FETO OUTBOARD Service Repair Manual L: 472180 -kjndksme89
 
Yamaha 60 fedo outboard service repair manual s 100850
Yamaha 60 fedo outboard service repair manual s 100850  Yamaha 60 fedo outboard service repair manual s 100850
Yamaha 60 fedo outboard service repair manual s 100850 fhjsekdmme
 
YAMAHA 75CET, C75TR OUTBOARD Service Repair Manual L: 001251 -
YAMAHA 75CET, C75TR OUTBOARD Service Repair Manual L: 001251 -YAMAHA 75CET, C75TR OUTBOARD Service Repair Manual L: 001251 -
YAMAHA 75CET, C75TR OUTBOARD Service Repair Manual L: 001251 -jknksemmd
 
YAMAHA 75CETO, 75TR OUTBOARD Service Repair Manual L: 951540 -
YAMAHA 75CETO, 75TR OUTBOARD Service Repair Manual L: 951540 -YAMAHA 75CETO, 75TR OUTBOARD Service Repair Manual L: 951540 -
YAMAHA 75CETO, 75TR OUTBOARD Service Repair Manual L: 951540 -jemmmd rfdvfv
 
YAMAHA 60FET, C60TR OUTBOARD Service Repair Manual L: 357665
YAMAHA 60FET, C60TR OUTBOARD Service Repair Manual L: 357665YAMAHA 60FET, C60TR OUTBOARD Service Repair Manual L: 357665
YAMAHA 60FET, C60TR OUTBOARD Service Repair Manual L: 357665kjksemjdmkdm
 
YAMAHA 60FEDO OUTBOARD Service Repair Manual L: 407212 -
YAMAHA 60FEDO OUTBOARD Service Repair Manual L: 407212 -YAMAHA 60FEDO OUTBOARD Service Repair Manual L: 407212 -
YAMAHA 60FEDO OUTBOARD Service Repair Manual L: 407212 -jhsefnn kjsfem
 
YAMAHA 70BETO, 70TR OUTBOARD Service Repair Manual X: 731262 -
YAMAHA 70BETO, 70TR OUTBOARD Service Repair Manual X: 731262 -YAMAHA 70BETO, 70TR OUTBOARD Service Repair Manual X: 731262 -
YAMAHA 70BETO, 70TR OUTBOARD Service Repair Manual X: 731262 -kleijdkmsm
 
Yamaha 60 fet, c60tr outboard service repair manual s 050474
Yamaha 60 fet, c60tr outboard service repair manual s 050474  Yamaha 60 fet, c60tr outboard service repair manual s 050474
Yamaha 60 fet, c60tr outboard service repair manual s 050474 fjkskemdmm
 
YAMAHA 90AETO, 90TR, B90TR OUTBOARD Service Repair Manual L: 498690 -
YAMAHA 90AETO, 90TR, B90TR OUTBOARD Service Repair Manual L: 498690 -YAMAHA 90AETO, 90TR, B90TR OUTBOARD Service Repair Manual L: 498690 -
YAMAHA 90AETO, 90TR, B90TR OUTBOARD Service Repair Manual L: 498690 -uekjmd kmwsed
 

Similar to 09. operating instruction c20 c30 (20)

cts320_manual.pdf
cts320_manual.pdfcts320_manual.pdf
cts320_manual.pdf
 
Mark VI ST Control Product Overview GEH 6127
Mark VI ST Control Product Overview GEH 6127Mark VI ST Control Product Overview GEH 6127
Mark VI ST Control Product Overview GEH 6127
 
Amb x 24_3_t_s
Amb x 24_3_t_sAmb x 24_3_t_s
Amb x 24_3_t_s
 
Operations and Maintaince Manual Sample
Operations and Maintaince Manual SampleOperations and Maintaince Manual Sample
Operations and Maintaince Manual Sample
 
Siemens catalog tong hop 3 uf simocode
Siemens catalog tong hop 3 uf simocodeSiemens catalog tong hop 3 uf simocode
Siemens catalog tong hop 3 uf simocode
 
MVE brochure US
MVE brochure USMVE brochure US
MVE brochure US
 
BEP Marine Catalog
BEP Marine CatalogBEP Marine Catalog
BEP Marine Catalog
 
2005 MITSUBISHI AIRTREK Service Repair Manual
2005 MITSUBISHI AIRTREK Service Repair Manual2005 MITSUBISHI AIRTREK Service Repair Manual
2005 MITSUBISHI AIRTREK Service Repair Manual
 
Vlt fc 300 operating instructions
Vlt fc 300 operating instructionsVlt fc 300 operating instructions
Vlt fc 300 operating instructions
 
Hướng dẫn vận hành Danfoss VLT FC 300
Hướng dẫn vận hành Danfoss VLT FC 300Hướng dẫn vận hành Danfoss VLT FC 300
Hướng dẫn vận hành Danfoss VLT FC 300
 
Yamaha 60 fehto, p60th outboard service repair manual l 551924
Yamaha 60 fehto, p60th outboard service repair manual l 551924  Yamaha 60 fehto, p60th outboard service repair manual l 551924
Yamaha 60 fehto, p60th outboard service repair manual l 551924
 
YAMAHA 60FETO OUTBOARD Service Repair Manual L: 472180 -
YAMAHA 60FETO OUTBOARD Service Repair Manual L: 472180 -YAMAHA 60FETO OUTBOARD Service Repair Manual L: 472180 -
YAMAHA 60FETO OUTBOARD Service Repair Manual L: 472180 -
 
Yamaha 60 fedo outboard service repair manual s 100850
Yamaha 60 fedo outboard service repair manual s 100850  Yamaha 60 fedo outboard service repair manual s 100850
Yamaha 60 fedo outboard service repair manual s 100850
 
YAMAHA 75CET, C75TR OUTBOARD Service Repair Manual L: 001251 -
YAMAHA 75CET, C75TR OUTBOARD Service Repair Manual L: 001251 -YAMAHA 75CET, C75TR OUTBOARD Service Repair Manual L: 001251 -
YAMAHA 75CET, C75TR OUTBOARD Service Repair Manual L: 001251 -
 
YAMAHA 75CETO, 75TR OUTBOARD Service Repair Manual L: 951540 -
YAMAHA 75CETO, 75TR OUTBOARD Service Repair Manual L: 951540 -YAMAHA 75CETO, 75TR OUTBOARD Service Repair Manual L: 951540 -
YAMAHA 75CETO, 75TR OUTBOARD Service Repair Manual L: 951540 -
 
YAMAHA 60FET, C60TR OUTBOARD Service Repair Manual L: 357665
YAMAHA 60FET, C60TR OUTBOARD Service Repair Manual L: 357665YAMAHA 60FET, C60TR OUTBOARD Service Repair Manual L: 357665
YAMAHA 60FET, C60TR OUTBOARD Service Repair Manual L: 357665
 
YAMAHA 60FEDO OUTBOARD Service Repair Manual L: 407212 -
YAMAHA 60FEDO OUTBOARD Service Repair Manual L: 407212 -YAMAHA 60FEDO OUTBOARD Service Repair Manual L: 407212 -
YAMAHA 60FEDO OUTBOARD Service Repair Manual L: 407212 -
 
YAMAHA 70BETO, 70TR OUTBOARD Service Repair Manual X: 731262 -
YAMAHA 70BETO, 70TR OUTBOARD Service Repair Manual X: 731262 -YAMAHA 70BETO, 70TR OUTBOARD Service Repair Manual X: 731262 -
YAMAHA 70BETO, 70TR OUTBOARD Service Repair Manual X: 731262 -
 
Yamaha 60 fet, c60tr outboard service repair manual s 050474
Yamaha 60 fet, c60tr outboard service repair manual s 050474  Yamaha 60 fet, c60tr outboard service repair manual s 050474
Yamaha 60 fet, c60tr outboard service repair manual s 050474
 
YAMAHA 90AETO, 90TR, B90TR OUTBOARD Service Repair Manual L: 498690 -
YAMAHA 90AETO, 90TR, B90TR OUTBOARD Service Repair Manual L: 498690 -YAMAHA 90AETO, 90TR, B90TR OUTBOARD Service Repair Manual L: 498690 -
YAMAHA 90AETO, 90TR, B90TR OUTBOARD Service Repair Manual L: 498690 -
 

09. operating instruction c20 c30

  • 1. CONTROLLER ATyS C20 / C30 Notice d’utilisation - Operating instructions F GB MAKE YOUR BUSINESS SAFE SOCOMEC GROUP SWITCHING PROTECTION & UPS
  • 2. F Sommaire LA GAMME ATyS _________________________________3 PRÉSENTATION GÉNÉRALE _______________________4 Présentation des produits ________________________4 INSTALLATION ___________________________________5 Montage _______________________________________5 Dimensions_____________________________________5 Caractéristiques_________________________________5 RACCORDEMENTS _______________________________6 Circuits de commande ___________________________6 Commande électrique __________________________11 FONCTIONNEMENT _____________________________12 Présentation___________________________________12 Modes d’utilisation _____________________________13 Programmation ________________________________14 Exploitation____________________________________24 Visualisation ___________________________________26 Séquences automatiques _______________________28 AIDE AU DÉPANNAGE ___________________________31 ANNEXES ______________________________________32 Typologie des réseaux __________________________32 Programmation et câblage ATyS __________________33 GB Summary THE ATyS RANGE _______________________________35 GENERAL PRESENTATION _______________________36 Product introduction ____________________________36 INSTALLATION __________________________________37 Mounting _____________________________________37 Dimensions ___________________________________37 Characteristics_________________________________37 CONNECTIONS _________________________________38 Control circuits_________________________________38 Electrical operation _____________________________43 OPERATION ____________________________________44 Presentation ___________________________________44 Operational modes _____________________________45 Programming __________________________________46 Operation _____________________________________56 Visualisation ___________________________________58 Automatic sequences ___________________________60 TROUBLESHOOTING GUIDE _____________________63 ANNEXES ______________________________________64 Network analysis _______________________________64 Programming and connections ATyS C30 __________65 SOCOMEC - Réf. : 532 214 C 2
  • 3. Controller ATyS THE ATyS RANGE The ATyS family proposes a complete motorised • Automatic control: AtyS 6 products integrate all changeover range including electrical and mechanical controls, timers and relays required to realise a interlocking. Manual operation is always possible on all Normal / Emergency application. the products in case of emergency. ATyS 6e and 6m versions also integrate the remote The electric command is realised via a motorised controlled feature. module, electronically driven by 2 types of logic: The motorised and control modules can easily be • Remote controlled: ATyS 3 products are controlled by replaced without disconnecting the power cables. volt free contacts allowing the switch to be driven in 1, 0 or 2 position. These contacts can come from an external control logic. ATyS 3s ATyS 3e ATyS 6s ATyS 6e ATyS 6m ATyS C30 ATyS C20 ATyS C40 MOTORISED CHANGEOVER Dual power supply Changeover Integrated control relay Dual genset controller Metering Com option Communication option 2 I/2 O option 2 inputs / 2 outputs option Remote interfaces ATyS D10 & D20 > This instruction manual applies to following > Following products are delivered with their own products: instruction manual: • Controller ATyS C20 / C30 • ATyS 3s • ATyS 3e, 6s, 6e • ATyS 6m • Remote interfaces ATyS D10 & D20 • Centroller ATyS C40. For personnel and product safety, please read the contents of these operating instructions carefully before connecting. SOCOMEC - Réf. : 532 214 C 35
  • 4. Controller ATyS Product introduction GENERAL PRESENTATION ATyS C20/C30 Product introduction ATYS C20 LCD Control terminals Modular frame ATYS 453 A Voltage sensing and power supply terminals Keypad ATYS C30 LCD Control terminals Modular frame ATYS 448 A Voltage sensing and RJ45 terminal power supply terminals Keypad SOCOMEC - Réf. : 532 214 C 36
  • 5. Controller ATyS Mounting INSTALLATION Dimensions Characteristics ATyS C20/C30 Mounting > DIN rail mounting ATYS 449 A NB Dimensions 58 106 48 26,5 45 90 62 93 ATYS 437 A Characteristics > IP IP2 and class II on front face > Operation • Temperature : -20 °C to +60 °C • Humidity : 80 % at 55 °C 95 % at 40 °C > Consumption 7.5 VA max > Measurement category Cat III SOCOMEC - Réf. : 532 214 C 37
  • 6. Controller ATyS Control circuits CONNECTIONS Electrical operation ATyS C20/C30 Control circuits 400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR SWITCHING TYPE TECHNOLOGY • Configure the type of control logic in impulse mode • Automatic Power supply 203-205 or 104-106 (see Programming chapter). (see power supply chapter). LOAD L1 L1 L2 L2 1 L3 L3 2 N N F1 F2 F1, F2 Fuse protection 230 Vac 5 A Ph Power DPS N 230 Vac Double Power Supply option Control CA1 CA0 CA2 I II 0 C I1 I2 O2 GE 13 14 23 24 33 34 43 44 53 54 301 302 303 304 305 306 DC-* DC+* ONLY ON ATyS C30 Cable RJ45 8/8 N L3 L2 L1 L1 L3 ATyS D10 or D20 103 104 105 106 203 205 remote interface ATYS 426 A GB * Only on DC versions. Maximum control cables lenght = 10 m. Remote interfaces maximum connection In case of longer distance, insert control cable (RJ45) = 3 m. relays. SOCOMEC - Réf. : 532 214 C 38
  • 7. Controller ATyS CONNECTIONS Control circuits 400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR CONTACTOR TYPE TECHNOLOGY • Configure the type of control logic in contactor (see • Automatic Power supply 203-205 or 104-106 Programming chapter). (see power supply chapter). LOAD K1 K2 L1 L1 L2 L2 1 L3 L3 2 N N F1 F2 F1, F2 K1 K2 Fuse protection 230 Vac 5 A K2 K1 I1 I2 O1 O2 I II GE 13 14 23 24 33 34 43 44 53 54 301 302 303 304 305 306 DC-* DC+* ONLY ON ATyS C30 Cable RJ45 8/8 N L3 L2 L1 L1 L3 ATyS D10 or D20 103 104 105 106 203 205 remote interface ATYS 438 A GB * Only on DC versions. Maximum control cables lenght = 10 m. Remote interfaces maximum connection In case of longer distance, insert control cable (RJ45) = 3 m. relays. SOCOMEC - Réf. : 532 214 C 39
  • 8. Controller ATyS Control circuits CONNECTIONS Electrical operation ATyS C20/C30 Control circuits 400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR CIRCUIT BREAKER TYPE TECHNOLOGY > Electrical interlocking via external control relays • Configure the type of control logic in contactor (see • Automatic Power supply 203-205 or 104-106 Programming chapter). (see power supply chapter). LOAD L1 L1 L2 L2 1 L3 L3 2 N N F1 F2 POS 1 POS 2 POS 2 POS 1 AUXILIARY CONTACT F1, F2 closing opening closing opening BRE. 1 BRE. 2 Fuse protection 230 Vac 5 A K1 K2 K2 K1 I II O1 O2 I1 I2 GE 13 14 23 24 33 34 43 44 53 54 301 302 303 304 305 306 DC-* DC+* ONLY ON ATyS C30 Cable RJ45 8/8 N L3 L2 L1 L1 L3 ATyS D10 or D20 103 104 105 106 203 205 remote interface ATYS 439 A GB * Only on DC versions. Maximum control cables lenght = 10 m. Remote interfaces maximum connection In case of longer distance, insert control cable (RJ45) = 3 m. relays. SOCOMEC - Réf. : 532 214 C 40
  • 9. Controller ATyS CONNECTIONS Control circuits 400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR CIRCUIT BREAKER TYPE TECHNOLOGY > Electrical interlocking not integrated • Configure the type of control logic in breaker • Automatic Power supply 203-205 or 104-106 (see Programming chapter) (see power supply chapter). LOAD L1 L1 L2 L2 1 L3 L3 2 N N F1 F2 OPENING F1, F2 Breaker 1 Breaker 2 Fuse protection 230 Vac 5 A CLOSING Breaker 1 Breaker 2 I1 I2 GE 13 14 23 24 33 34 43 44 53 54 301 302 303 304 305 306 DC-*DC+* ONLY ON ATyS C30 Cable RJ45 8/8 N L3 L2 L1 L1 L3 ATyS D10 or D20 103 104 105 106 203 205 remote interface ATYS 440 B GB * Only on DC versions. Maximum control cables lenght = 10 m. This drawing is not including the electrical In case of longer distance, insert control interlock. relays. It might be necessary for some breakers not Remote interfaces maximum connection to set up OMR and OMF timers to 0. cable (RJ45) = 3 m. (refer to programming) SOCOMEC - Réf. : 532 214 C 41
  • 10. Controller ATyS Control circuits CONNECTIONS Electrical operation ATyS C20/C30 Control circuits Denomination Terminals Description Characteristics Recommended section Power supply N (103) Neutral 440 V ac (phase-phase) 1.5 mm2 Source 1 L3 (104) Phase 3 maximum, 50 / 60 Hz L2 (105) Phase 2 254 V ac (phase neutre) L1 (106) Phase 1 maximum, 50 / 60 Hz Power supply L1 (203) Phase 1 440 V ac (phase-phase) 1.5 mm2 Source 2 L3 (205) Phase 3 maximum Power supply DC(1) DC- Power supply 0 V From 9 V dc to 30 V dc 1.5 mm2 12Vdc, 24Vdc DC+ Power supply +V dc Genset(2) 13 Genset start / stop relay - 2 stable positions Dry contact 1.5 mm2 start signal 14 Programmable state - factory setting = NO, close to start 5A AC1 / 250 V Control 23 Impulse mode: order to close source 1 5 A AC1 / 250 V 1.5 mm2 (impulse, 24 Contactor mode: order to close contactor source 1 contactor Breaker mode: order to close breaker source 1 and breaker 33 Impulse mode: order to close source 2 5 A AC1 / 250 V 1.5 mm2 mode to 34 Contactor mode: order to close contactor source 2 programm) Breaker mode: order to close breaker source 2 43 Impulse mode: order to reach position 0 5 A AC1 / 250 V 1.5 mm2 44 Contactor mode: programmable relay O1 Breaker mode: order to open breaker source 1 53 Impulse mode: programmable relay O2 5 A AC1 / 250 V 1.5 mm2 54 Contactor mode: programmable relay O2 Breaker mode: order to open breaker source 2 Information 301 Auxiliary contact information position 1 AC1 Do not connect to 1.5 mm2 auxiliary 302 Auxiliary contact information position 0 AC0 any power supply contacts 303 Auxiliary contact information position 2 AC2 Programmable 304 Programmable input In1 Do not connect to 1.5 mm2 Inputs 305 Programmable input In2 any power supply Common 306 Specific voltage supply Do not connect to 1.5 mm2 input Common terminals 301 to 306 any power supply Remote interface RJ Remote interface ATyS D10 or D20 Maximum connection RJ45 8/8 connection cable 3 m (1) Only on DC version (2) Refer to programming, Setup, to modify relay state. SOCOMEC - Réf. : 532 214 C 42
  • 11. Controller ATyS CONNECTIONS Electrical operation POWER SUPPLY ATyS C20/C30 integrates 2 power inputs (104-106, 203- AUT position 205), and consider the available source to keep the priority power source 1 product operational. Product supplied when voltage on ATYS 444 A GB terminals ≥ 100 Vac backup power source 2 For the DC version, these is only one power supply input product ON (DC-, DC+). 1 : terminals 104-106 2 : terminals 203-205 SOCOMEC - Réf. : 532 214 C 43
  • 12. Controller ATyS Presentation OPERATION Operational modes Programming ATyS C20/C30 Operation Visualisation Automatic sequences Presentation The product allows: • sources control, • voltage and frequency metering, • automatic transfer control in AUT mode, • system state display, • parameters configuration, • alarm or fault indication, FAULT led LCD Led is on when product is faulty. 7 digits + 14 pointers Disconnect power supplies to reset POWER led Green led is on when product is powered RJ45 connection* RJ45 terminal for ATyS D10 or D20. If connected, the LCD is off Keypad Sources state Escape Navigation - Led is on: source = OK - Led is off: source is not available LCD & leds test Operations Validation Switch state Operational modes 2 green leds: - Automatic sequence simulator (test on load) ATYS 427 A GB - switch I state - Genset remote start (test off load) - switch II state - Changeover switch position control (local or remote) * only on ATyS C30. SOFTWARE VERSION Displayed after reset. ATYS 428 A GB (3 minutes power off action to allow reset). Version number SOCOMEC - Réf. : 532 214 C 44
  • 13. Controller ATyS OPERATION Operational modes VISUALISATION OPERATION Measured values & parametered timers display. Always Test sequences. Password access (code 4000). accessible without code. PROGRAMMING Parameters configuration. Password access (code 1000 from factory). The manual mode must be programmed on an input if required. Available functions in mode Programming Operation Code Code Programming Visualisation Operation Test off load Available functions in “ AUT ” mode Programming Operation Code Code Programming Visualisation Operation Test off load Test on load Loss of main Main’s source return sequence sequence PHASES ROTATION CONTROL Function available only on source 1 in case of 3NBL, 4NBL and 41NBL network. If a fault is detected, the source 1 is not indicated as available. V1 V1 OK NOK ATYS 219 A ATYS 441 A 1 2 displayed according to faulty source. V3 V2 V2 V3 SOCOMEC - Réf. : 532 214 C 45
  • 14. Controller ATyS Presentation OPERATION Operational modes Programming ATyS C20/C30 Operation Visualisation Automatic sequences Programming • This mode allows product parameters configuration • Always accessible in mode (when programmed on an input) • Always accessible in AUT mode, changeover switch on priority source, priority source being available • Not accessible when “test off load”, “test on load” functions are active or during automatic sequence. Parameters requiring programming before use: • type of network • nominal voltage • nominal frequency • control logic • number of auxiliary contact. > Navigation in the menus or • Parameters access: Press “up”, “down”, “left” & “right” push buttons • Parametermodification: press “left” & “right” push button to access the parameter to modify + Press “up’’ and “down” push buttons to modify the parameter and “validate” + • Return to main menu: press “ESC” push button Value is only modified after validation > Programming access > Programming exit • Step 1: press and hold for 5 s • Press and hold for 5 s “validation” push button “validation” push button • Step 2: enter code (factory code = 1000) using navigation push buttons • Step 3: press validation push button SOCOMEC - Réf. : 532 214 C 46
  • 15. 47 Setup Voltage Frequency Timer 2I / 2O Controller ATyS OPERATION 1 2 1 2 1 2 1 2 1 2 ESC ESC ESC ESC ESC Type of network Network 1 over Network 1 over Main Failure Option 1 1 2 1 2 voltage 1 2 frequency 1 2 Timer 1 2 Input 1 (variable threshold threshold selection) Phase-Phase Option 1 1 2 nominal voltage Network 1 over Network 1 over Delay on 1 2 Input 1 (contact 1 2 voltage 1 2 frequency 1 2 Transfer state selection) threshold threshold Timer Nominal hysteresis hysteresis 1 2 frequency Option 2 O main failure 1 2 Input 2 (variable Network 1 Network 1 Timer selection) Genset start 1 2 1 2 signal state 1 2 under voltage 1 2 under frequency Option 2 threshold threshold 1 2 Input 2 (contact Network priority Main Return state selection) 1 2 selection: Network 1 Network 1 1 2 Timer 1 or 2 1 2 under voltage 1 2 under frequency Output 1* threshold threshold 1 2 Manuel hysteresis hysteresis O main Return 1 2 retransfer Timer 1 2 Output 2* Network 2 over Network 2 over 1 2 Impulse, 1 2 voltage 1 2 frequency 1 2 breaker or threshold threshold Cool Down Load shedding contactor logic 1 2 Timer timer** PROGRAMMING MENU ARCHITECTURE 1 2 Number of Network 2 over Network 2 over 1 2 auxiliary contact 1 2 voltage 1 2 frequency threshold threshold Return on hysteresis hysteresis 1 2 position 0 1 -> 2 Network 2 Network 2 1 2 under voltage 1 2 under frequency Return on threshold threshold 1 2 position 0 2 -> 1 SOCOMEC - Réf. : 532 214 C Network 2 Network 2 Programming Number of 1 2 under voltage 1 2 under frequency 1 2 permutation threshold threshold counter Reset hysteresis hysteresis Programming 1 2 code modification See page 49 See page 50 See page 51 See page 52 See pages 53 to 55 * Availability of output functions depending on control logic selection (impulse, breaker or contactor logic) ** Displayed if LS variable has been selected.
  • 16. Controller ATyS Presentation OPERATION Operational modes Programming ATyS C20/C30 Operation Visualisation Automatic sequences Programming PARAMETER MODIFICATION > Example: Modify network 1 nominal voltage from 400 to 230 V. Press to access first digit (blinking) Press 2X to display 2 (blinking) Press to access second digit (blinking) Press 3X to display 3 (blinking) Press to validate ATI 074 A SOCOMEC - Réf. : 532 214 C 48
  • 17. Controller ATyS OPERATION Programming PARAMETERS CHARACTERISTICS > Menu Setup 1 2 LCD Denomination Definition Setting Default range values Type of Number of active conductors of controlled network 1BL, 2BL, 4NBL 1 2 network* (refer to annexes) 2NBL, 3NBL, 4NBL, 41 NBL Network Phase-Neutral voltage for 1BL & 41NBL from 100 V 400 V 1 2 nominal voltage Phase-Phase voltage for others to 400 V Network Network nominal frequency 50 Hz or 60 Hz 50 Hz 1 2 nominal frequency Genset start Normally opened or closed NO or NC NO 1 2 signal state Network priority Keypad selection (1 or 2) 1 or 2 1(1) 1 2 selection Also possible via external contact using option ( 1 or 2 ) Manual Activation of the feature Yes or No No 1 2 Retransfer Type of control Impulse, contactor or breaker. Imp, con, brE Imp 1 2 logic selection It might be necessary for some breakers not to set up OMR and OMF timers to 0 (2 sec. for exemple). Number of Depending on the number if available auxiliary contacts 0, 2, 3 2 1 2 auxiliary contact (switch, contactor, breaker) Parameter 1, Allows to go to position 0 in case of voltage or frequency Yes or No No 1 2 return in outage (out if the defined U, f range) position 0 Parameter 2 Allows to go to position 0 in case of voltage or frequency Yes or No No 1 2 return in outage (out if the defined U, f range) position 0 Number of Allows source 1 -> source 2 automatic sequences Yes or No No 1 2 permutation counter reset counter Reset Programming Possible to change the programming code from 0000 to 1000 1 2 code 9999 modification * Refer to annexes. (1) It might be necessary for some breakers not to set up OMR and OMF timers to 0. (2 sec.) SOCOMEC - Réf. : 532 214 C 49
  • 18. Controller ATyS Presentation OPERATION Operational modes Programming ATyS C20/C30 Operation Visualisation Automatic sequences Programming > Volt Menu 1 2 Threshold detection starts from the loss of source or source return sequence. % Controlled value (voltage) Over voltage threshold (oU) Over voltage hysteresys threshold (oUh) Available source 100 t Under voltage hysteresys threshold (uUh) ATYS 243 A GB Under voltage threshold (uU) LCD Denomination / Definition Setting Default range values Network 1 over voltage threshold From 102 115 % 1 2 to 120 % Network 1 over voltage threshold hysteresis From 101 110 % 1 2 to 119 % (< oU) Network 1 under voltage threshold From 80 85 % 1 2 to 98 % Network 1 under voltage threshold hysteresis From 81 95 % 1 2 to 99 % (> uO) Network 2 over voltage threshold From 102 115 % 1 2 to 120 % Network 2 over voltage threshold hysteresis From 101 110 % 1 2 to 119 % (< oU) Network 2 under voltage threshold From 80 85 % 1 2 to 98 % Network 2 under voltage threshold hysteresis From 81 95 % 1 2 to 99 % (> uU) Values definition: % of nominal values Hysteresis values range is limited by thresholds values. SOCOMEC - Réf. : 532 214 C 50
  • 19. Controller ATyS OPERATION Programming > Frequency Menu 1 2 Threshold detection starts from the loss of source or source return sequence. % Controlled value (frequency) Over frequency threshold (oU) Over frequency hysteresys threshold (oUh) Available source 100 t Under frequency hysteresys threshold (uUh) ATYS 286 A GB Under frequency threshold (uU) LCD Denomination / Definition Setting Default range values Network 1 over frequency threshold From 101 105 % 1 2 to 120 % Network 1 over frequency threshold hysteresis From 100.5 103 % 1 2 to 119.5% (< oF) Network 1 under frequency threshold From 80 95 % 1 2 to 99 % Network 1 under frequency threshold hysteresis From 80.5 97 % 1 2 to 99.5 % (> uF) Network 2 over frequency threshold From 101 105 % 1 2 to 120 % Network 2 over frequency threshold hysteresis From 100.5 103 % 1 2 to 119.5% (< oF) Network 2 under frequency threshold From 80 95 % 1 2 to 99 % Network 2 under frequency threshold hysteresis From 80.5 97 % 1 2 to 99.5 % (> uF) Values definition: % of nominal values Hysteresis values range is limited by thresholds values. SOCOMEC - Réf. : 532 214 C 51
  • 20. Controller ATyS Presentation OPERATION Operational modes Programming ATyS C20/C30 Operation Visualisation Automatic sequences Programming > Menu Timer 1 2 LCD Denomination Definition Setting Default range values Main Failure Delays priority network failure detection from 0 to 60 s 5s 1 2 Timer Delay on Standby network stability validation before transfer from 0 to 60 s 5s 1 2 transfer Timer O Main failure Rest in O position when transferring from 0 to 20 s 0s 1 2 Timer from main network to secondary network Main return Main network stability validation before re-transfer from 0 to 30 min 2 min 1 2 Timer O main return Rest in O position when re-transferring from standby from 0 to 20 s 0s 1 2 Timer network to main network Cool down Allows generator cooling down period after load’s from 0 to 30 min 4 min 1 2 Timer retransfer from standby source (generator) to Main source SOCOMEC - Réf. : 532 214 C 52
  • 21. Controller ATyS OPERATION Programming > Inputs/Outputs Menu 1 2 Output relays are NO type (construction) and can not be configured as NC. Input state can be configured: NC or NO. LCD Denomination / Definition Setting range Default values Input 1 Ft1, Ft2, Ft3, Ft4, Pri, Mtf, / / 1 2 S2A, MAN, CtS, tol, tfl, EJP Input 1state NO, NC, / NO 1 2 Input 2 Ft1, Ft2, Ft3, Ft4, Pri, Mtf, / / 1 2 S2A, MAN, CtS, tol, tfl, EJP Input 2 state NO, NC, / NO 1 2 Output 1 S1A, S2A, LS, / / 1 2 Output 2 S1A, S2A, LS, / / 1 2 SOCOMEC - Réf. : 532 214 C 53
  • 22. Controller ATyS Presentation OPERATION Operational modes Programming ATyS C20/C30 Operation Visualisation Automatic sequences Programming > Inputs/Outputs Menu 1 2 Inputs Variable Description Ft1 Fault input 1. The fault led is blinking as soon as the input is active and Ft1 is displayed on LCD. Reset when the input is de-activated Ft2 Fault input 2. The fault led is blinking as soon as the input is active and Ft2 is displayed on LCD. Reset when the input is de-activated Ft3 Fault input 3. The fault led is blinking as soon as the input is active and Ft3 is displayed on LCD. The transfer switch is immediately driven in 0 position (only in contactor mode). Keypad action (Validation) necessary to Reset the fault Ft4 Fault input 4. The fault led is blinking as soon as the input is active and Ft4 is displayed on LCD. The transfer switch is immediately driven in 0 position (only in contactor mode). Keypad action (Validation) necessary to Reset the fault Pri(1) Priority network selection. Network 1 has priority when input is not activated. Network 2 has priority if input is active Mtf Remote manuel re-transfer. Feature identical to manual retransfer on keypad. Re-transfer from priority network to backup network is allowed from input activation (1 s front). The Mtf variable in the setup menu must be selected (Yes) to allow input recognition S2A Information source 2 available (Genset) used instead of voltage / frequency measurement (inhibited when S2A is selected) Man Information transfer system in manual mode All automatic commands (+ test on load) are inhibited as soon as the input is activated CtS Remote transfer control. Possible to initiate transfer from priority source to backup source before DTT ends. If DTT is set to its maximum value (60s), the transfer is initiated as soon as the input is activated (1 s front) tol Remote test on load. Started from input activation. Re-transfer is blocked until input de-activation tfl Remote test off load Started from input activation (remote genset start / stop) EJP 2 inputs are automatically affected to EJP • input 1 for EJP advice, to start generator • input 2 to transfer on emergency source Retransfer is activated when input 2 dissapears (1) This information is the only considered in case of option configuration. Programming variable Pri is then inhibited. • EJP cycle EJP advice (input 1) EJP transfer (input 2) Start generator CDT DTT ATYS 442 B GB Source 1 OMF OMR Source 2 SOCOMEC - Réf. : 532 214 C 54
  • 23. Controller ATyS OPERATION Programming > Inputs/Outputs Menu 1 2 Outputs Variable Description S1A Source 1 available. Output activated as soon as source 1 is considered available (similar to front led source 1) S2A Source 2 available. Output activated as soon as source 2 is considered available (similar to front led source 2) LS Load shedding relay. LS timer corresponds to time available to disconnect the shed loads. The relay is activated before permutation on standby network according to LS timer. The relay is de-activated after retransfer on mains network and LS timer countdown In case of LS function selection, it is required to configure associated LS timer. Output Function Default Value Setting range 1 2 For LS: For LS: S1A, S2A, LS, / 0 to 60 s (≤ DTT)* 3s 1 2 * In case of DTT variable configuration below LS, LS will be automatically set to DTT value. • Example: LS configuration (output relay Ou1, 3 seconds): The load shedding can’t be used with the priority network (priority source = source 2 ). In this case, LS 1 2 output is not valid. ATYS 269 A 1 2 • Load shedding cycle DTT timer Priority source - Emergency source - emergency source priority source LS timer transfer transfer LS timer Position II (emergency) AC activation LS relay Activation The output is de-activated in case of loss of LS AC II Load shedding output power. It may then be required to put in ATYS 334 A GB parrallel with the load shedding ouptut relay, position 2 auxiliary contact. This would avoid taking back the load in case of loss of emergency source in emergency position. SOCOMEC - Réf. : 532 214 C 55
  • 24. Controller ATyS Presentation OPERATION Operational modes Programming ATyS C20/C30 Operation Visualisation Automatic sequences Operation PRESENTATION This mode allows in manual mode (not padlocked) to start a test off load. In automatic mode, it allows to start a test, on or off load. Enter operation mode: Exit operation mode: • Step 1: press and hold Press and hold the “TEST” push button for 5 s the “TEST” push button for 5 s or automatic exit without action during around 2 min • Step 2: enter the operation code (CE) using navigation push buttons (code 4000) Navigate in operation mode: • Step 3: press “validation” push button • Press “TEST” push button to access different features • Press “validation” push button to activate required function OPERATION MODE ARCHITECTURE Enter: press 5 seconds Yes, press Led “test on load” “validation” Led “TEST ON LOAD” TEST ON LOAD is blinking 1 2 is fixed Loss of priority source sequence No, press “TEST” Yes, press “validation” TEST OFF LOAD Led “test off load” Led “TEST OFF LOAD” is blinking 1 2 is fixed Genset start sequence No, press “TEST” ATYS 432 A GB Exit: press 5 seconds SOCOMEC - Réf. : 532 214 C 56
  • 25. Controller ATyS OPERATION Operation TEST OFF LOAD (ACCESSIBLE IN AUT / MODES) 1 2 It can be activated from: • operation mode • ATyS D20 interface 1 2 start Gen • programming input (TFL) if selected. This test is made for applications where emergency source 2 is typically a genset (priority source must be source 1 ). This test can be activated, in automatic Gen ? No mode, changeover switch in position 1 , source 1 1 2 available. Yes > Description Validate • This mode will start and stop remotely genset operation Stop Gen ? without load transfer • The test is not possible during an automatic sequence 1 2 > Keypad activation After operation mode access, press mode push button to make the test off load led blinking and validate to ATI 087 B GB start the sequence. 1 2 Gen stopped TEST ON LOAD (ACCESSIBLE IN AUT MODE) 1 2 It is activated from: • operation mode • ATyS D20 interface • programming input (TOL) if selected. Automatic cycle keeps priority. > Description: > Remote activation via specific input • This test simulates a loss of priority source situation. It is also possible to start a test on load remotely with The sequence generates load transfer from priority the programming input TOL if selected. source to emergency source after backup source start The cycle is started from contacts closure. up operation (in case of genset). The return sequence The re-transfer is initiated from contacts opening. always keeps manual re transfer feature activated (from priority source availability). All timers are counted down. The re-transfer from emergency source to > Keypad activation priority source is blocked and only authorized After operation mode access, press mode push button after manuel retransfer validation (keypad to make test on load led blinking and validate to start a activation) or terminals opening. cycle. The test is only possible in automatic mode, the chan- geover switch in priority source position, priority source Start gen relay is closed if source 2 has being available. priority. > Keypad or remote operation Manual retransfer to validate on keypad. In retransfer sequence from emergency source to priority source, the MRT count down is set to 10 seconds (maximum), unless a lower value has been programmed. SOCOMEC - Réf. : 532 214 C 57
  • 26. Controller ATyS Presentation OPERATION Operational modes Programming ATyS C20/C30 Operation Visualisation Automatic sequences Visualisation PRESENTATION • This mode allows parameters to be displayed independently from mode / AUT switch position (if programmed on input) • No code required to access parameters visualisation • Without any action during 5 seconds on the keypad, the LCD displays voltage available on active network. In case of changeover switch on 0 position, priority network voltage is displayed. Navigation in visualisation mode: • Press “up” and “bottom” push buttons to access required parameter • Press “left” and “right” push buttons to navigate in the different menus SOCOMEC - Réf. : 532 214 C 58
  • 27. Controller ATyS OPERATION Visualisation VISUALISATION ARCHITECTURE MODE MENUS Metering Timers Counter Phase-neutral voltage V1 Main Failure Timer Priority source -> 1 2 1 2 network 1 Emergency source transfer counter Phase-neutral voltage V2 Delay on Transfer Timer 1 2 network 1 1 2 Phase-neutral voltage V3 O Main Failure Timer 1 2 network 1 1 2 Network 1 frequency Main Return Timer 1 2 1 2 Phase-phase U12 O Main Return Timer 1 2 network 1 1 2 Phase-phase U23 Cool Down Timer 1 2 network 1 1 2 Phase-phase U31 Load shedding* 1 2 network 1 1 2 Phase-neutral voltage V1 1 2 network 2 Phase-phase U31 1 2 network 2 Network 2 frequency 1 2 * If selected. All values indicated might not be available according to programmed network. Refer to annexes. SOCOMEC - Réf. : 532 214 C 59
  • 28. Controller ATyS Presentation OPERATION Operational modes Programming ATyS C20/C30 Operation Visualisation Automatic sequences Automatic sequences MANUAL MODE / AUTOMATIC MODE > Manual mode - Automatic mode permutation/power supply reappearance • As soon as man input desapears (if selected), the automatic mode is active • Voltages and frequencies are verified to define new stable position of the changeover switch • The same table can be taken into account after complete power supply loss (the product must be Refer to timer menus for MFT, MRT or DTT timers completely discharged to reset = 3 minutes.) definition. > New stable position of the changeover switch Changeover switch Sources availability New position initial position Priority source Priority source available, Priority source emergency source available or unavailable Priority source Priority source unavailable for MFT time period, Emergency source. If emergency source emergency source available or unavailable unavailable start emergency source first and wait for DTT timer period before transfer Emergency source Emergency source available, Emergency source priority source unavailable Emergency source Emergency source available, Priority source priority source available for MRT time period Emergency source Emergency source not available, Priority source priority source available Position 0 Priority source available, Available source to count down MRT before emergency source unavailable transfer to priority source Position 0 Priority source available, Priority source emergency source unavailable Position 0 Priority source unavailable, Emergency source emergency source available Position 0 Priority source unavailable, No action (because no supply). emergency source unavailable When supply becomes available change to priority source or emergency source The switch transfers to new stable position as soon as Automatic mode is active. LOSS OF PRIORITY SOURCE AUTOMATIC SEQUENCE This sequence is started as soon as the switch is in > Specific feature: remote transfer control automatic mode and in priority position (position I - It is possible to transfer from main source to emergency source 1 ). source before DTT finishes up and to allow transfer with • source 1 is available CTS option if selected on an unput. DTT is automatically • transfer switch is in position I set up to its maximum value as soon as CTS is selected. • source 2 is available or unavailable > Available source Source being within programmed voltage and frequency settings, phases rotation being correct. SOCOMEC - Réf. : 532 214 C 60
  • 29. Controller ATyS OPERATION Automatic sequences > Sequence description Example: position I = priority source ( 1 ) position II = emergency source type Genset ( 2 ) Automatic mode Loss of mains? No Loss of main? Yes MFT = 0 Count down MFT Genset start up Main comes back before MFT ends? Start Genset Reset MFT Emergency Yes source available? No No Yes Stop gen Priority source? Reset DTT No Gen fails No Count down CTS = 1 ? DTT = 0 Yes Yes No OMF 0? Transfer I > 0 Count down OMF OMF = 0 Transfer 0 > II Transfer I > II Transfer I > II ATYS 443 A GB Go to priority source return automatic sequence SOCOMEC - Réf. : 532 214 C 61
  • 30. Controller ATyS Presentation OPERATION Operational modes Programming ATyS C20/C30 Operation Visualisation Automatic sequences Automatic sequences RETURN TO PRIORITY SOURCE This sequence is activated as soon as the changeover • the changeover switch is in emergency position (ex: switch is in automatic mode and in emergency position genset) (position II): • the emergency source 2 is available. • the priority source 1 is not available > Specific feature: manual re-transfer • When priority source comes back, it can be required Manual retransfer not to automatically retransfer and wait for a more = validation press adequate moment. Or • It is possible, validating manual retransfer feature (refer optional input acti- to programming), to block the re-transfer. vation, Mtf feature It is initiated from: ATYS 143 B • validation push button localy or on ATyS D20 • via a programming input if MTF option is selected. > Sequence description Priority source unavailable Generator running (emergency source) & Switch in position II Main’s return Priority No source return? Yes Manual re-transfer Loss of Yes priority source ? MRT = 0 No Count down MRT Priority source lost again before MRT Mode Yes times out? semi-auto activated ? (Mtf) Reset MRT No Yes Validation OMR ≠ 0? Yes No Transfer II >0 Count Down OMR OMR = 0 Transfer 0 >I Transfer II >I To loss of priority source sequence Reset CDT Count Down CDT Transfer II >I Loss of priority source CDT = 0 ATYS 155 A GB Stop generator position 1 Back to priority source control SOCOMEC - Réf. : 532 214 C 62