Fire and Gas
- Oil & Gas
- Industrial
- Power
Marco Santucci
Scame Sistemi
15
Conventional F&G Philosophy
Point type Smoke/heat detector
Manual call point
Addressable beacon and sounder
Actuation of discharge
Control of delays
Dedicated fire detection
Gas detectors
Flame detectors
HSSD
High power beacons
Remote singalling
interface with other systems
Main HMI
IEC61508 for safety PLCs continous mode
16
Problems?
Designed for
building
Actuation onlyDesigned for
continous operation
Main interface
shall be EN54
INTERFACING
COMMUNICATION
ISSUES
1 The full function relies on all the three systems
2 Maintenance (3/4 power supplies and batteries)
3 TCO (NR Costs and Running Costs)
19
All in one
 Addressable and
conventional fire
detection
 Automatic fire
extinguishing
 Gas detection
 Security, access control,
CCTV, BMS,
Environmental.
SIL2 & SIL3
Programmable Electronic
System
for Safety-Related Applications
Follow Video demonstration on YouTube
http://www.youtube.com/user/Scamesistemi
21
Panel Composition
22
HW & SW Features
 Distributed intelligence
 High availability
 High fault tolerance
 HOT SWAP of
CPUs, I/O cards, power
supply units, display
 Easy maintenance
 SIL2 and SIL3 rated
for safety functions
23
Enclosures
Wall Mount 400x600x700h mm
 1 Expansion rack, max 13 cards
 1 or 2 CPUs
 SIL2 Max
 EN54
 EN12094
 Fire and Gas
24
Enclosures
Wall Mount 400x600x1100h mm
 2 Expansion racks, max 26 cards
 1 or 2 CPUs
 SIL2 & SIL3
 EN54
 EN12094
 Fire and Gas
25
Enclosures
Floor standing single door
800x800x2100h mm
 Max 6 Expansion racks
 1 or 2 CPUs
 SIL2 & SIL3
 EN54
 EN12094
 UL
 Fire and Gas
 Hot swap Power supply
26
Enclosures
Floor standing double door
1600x800x2100h mm
 Max 10 Expansion racks
 1 or 2 CPUs
 SIL2 & SIL3
 EN54
 EN12094
 Fire and Gas
 Hot swap Power supply (2x)
27
Enclosures
Compact Wall Mount 500x250x700h mm
 1 non-expandable rack, max 8 cards
 1 or 2 CPUs
 SIL2
 EN54
 EN12094
 Fire and Gas
28
Enclosures
Ex-nR for Zone 2 800x800x2100h mm
 All Stainless Steel
 Max 6 Expansion racks
 1 or 2 CPUs
 SIL2 & SIL3
 EN54
 EN12094
 Fire and Gas
29
Enclosures
Ex-d for Zone 1 (EJB5)
 1 non-expandable rack, max 8 cards
 1 or 2 CPUs
 SIL2
 EN54
 EN12094
 Fire and Gas
30
Enclosures
Demo unit in flight case
 Equipped with 1 rack and Sample cards
 2 CPUs
 SIL2
 2 Simulation push-buttons
 2 Simulation LEDs
 1 Smoke detector
 1 manual call point
 For demo and training
31
Multicard Racks
E2001-1 Rack
 Each S81 rack can contain up
to 13 cards
 The 14th slot of the rack is for
the E2002-1 card, which
manages the communication
bus
 The S81 panel can actually
manage up to 10 racks, for a
total of 130 cards
32
Card name F3002 F4001 F4002 F4003
Input lines 8 1 2 8
Kind of input Digital Analog 4-20 mA Analog 4-20 mA Analog 4-20 mA
Line monitoring S.C., O.C. 0-24 mA 0-24 mA 0-24 mA
Threshold levels 2 each line 2 2 each line 2 each line
Visual indication Led
Led, Bar Graph ,
display
Led , display Led
Card monitoring Self test Self test Self test Self test
SIL 2 rated Single Single Single Single
SIL 3 rated Redundant Redundant Redundant Redundant
Analog and digital input cards
33
Collective type connections
Different brand/type detectors (upgrading existing systems)
32 detectors per line (as per UNI 9795 standard)
Short and open circuit monitoring
Pre-alarm, alarm, alarm verification on each line
34
Connection of analogue sensors
4-20 mA inputs
Direct reading on
display
Connection of gas,
oxygen, vapour, heat,
level sensors
Return of input signal
towards external
systems
SIL 2 certified sensors
35
Card name F7002 F7009 F7007 F7010
Devices manufacturer HOCHIKI APOLLO SCAME
Notifier by
Honeywell
Loop protocol ESP XP95 / Discovery SSP System Sensor
Applications Fire detection Fire detection
Security, Env.,
BMS, Gas
Fire detection
Addressable each 127 126 127 99 in, 99 out.
I/O digital modules I/O multichannel I/O multichannel I/O multichannel I/O multichannel
Analogue inputs None None 4-20 mA 4-20 mA
Field wiring Loop (ring 3km) Loop (ring 3km) Loop (ring 3km) Loop
SIL rated None SIL 2 None None
Addressable cards
Can be
used
together
36
Card name F7009 F7007
Devices manufacturer APOLLO SCAME
Loop protocol XP95 / Discovery SSP
Applications Fire detection Security, Env., BMS, Gas
Number of devices per loop 126 127
I/O digital modules I/O multichannel I/O multichannel
Analogue inputs None 4-20 mA
Field wiring Loop (ring 3km) Loop (ring 3km)
SIL rated SIL 2 with Discovery SIL2 devices None
Addressable cards
How many
loops?
37
Connection of analogue addressable devices
Fire detection
Detection (input)
and control (output)
on the same loop
SIL 2 certified
addressable
detectors
38
Industrial anti-intrusion alarm
4-20mA
8 x Digital IN
4 x Supervised Digital IN
8 x Digital OUT.
Mixed I/Os
Access control, BMS,
integration with CCTV … in the
same loop.
Gathering of statuses for safety
functons
The security system is certified
to level II
39
Card name F5001 F5004 F5003 F5002
Ouput lines 8 4 8 16
Channel output current 500 mA 2 A 250 mA 500 mA (Total)
Line monitoring S.C., O.C. S.C., O.C. Reversal polarity None
Direct pulse line monit. Yes Yes None None
Relay card None None T8008 - 4 ch. Yes
Outputs can be paralleled Yes Yes None None
SIL 2 rated Single Single None None
SIL 3 rated Redundant Redundant None None
Output cards
40
Monitored actuators
Dedicated
command for each
actuator
Line monitoring for
short circuit and
open circuit
Card-line
diagnostics
Direct or reverse
polarity monitoring
SIL 2 certified
actuators
41
Cards name F7006 F7008 F6002
Field protocol Modbus RTU Modbus RS485 S81
Applications Data link Weighing bottles Special logics
Capacity 512 in, 512 out. 32 bottles 100 logic devices
Mode Master or Slave 2 alarm thresholds Flip-flop, toggle, timer.
Field wiring Rs232-Rs485 Rs 485 Internal bus
SIL rated None (redundant) None None
Special cards
42
Interaction and monitoring
Serial MODBUS
connection with PLC
and SCADA
Serial connection
with electronic
devices for cylinder
weighing
43
Extinguishing control card F6001
 Electrical automatic control and delay device
(e.c.d.) certified to EN 12094-1 standard
 Mandatory, in Europe for gas-based
extinguishing systems
 Able to manage all the virtual devices
necessary for an extinguishing application in
a zone
 Physical I/O’s are controlled by other S81
input and output cards
 S81 control panel can manage up to 64
F6001 cards
44
Extinguishing zone according to EN and
NFPA standards
one F6001 module per extinguishing
zone
Detection is made with any other
input card
Module 6001 does not have any
physical I/O’s
Directional and control valves,
manual call points, sounders and
other extinguishing devices are
connected to separate I/O modules or
Cards.
Extinguishing control system can be
SIL2 or up to SIL3.
AUTOMATIC EXTINGUISHING
45
Example of a SIL function
SIL certified detectors on addressable loop
SIL certified actuators (solenoids, deluge valves, monitors)
S81-HS panel with logic solver functions
46
EN54-4 / UL Power Supply Units
PU-A003-1
Power Unit
2.5 A
PU-A008-1
Power Unit – HOT SWAP
AC/DC Converter
2 or 4 x 20A
Battery Charger
120 Ah
PU-A005-1
AC/DC
Converter
4 A
PU-A004-1
Battery
Charger
65 Ah
ProS81 Configuration Program
47
1) Definition of inputs
2) Definition of outputs
3) Definition of rules
4) Check of data validity
 Runs on any Windows operating system
 Communication with panel via RS232 or TCP/IP
 Configuration is protected through password and USB dongle key
ProS81
Check of Data Validity
48
49
Very short repair time
 Front plug-in/out cards
 Automatic monitoring of cards
and CPU fault
 Automatic and safe disabling
of malfunctioning cards
 Cards can be hot swapped
with compatible cards
 CPU self configuring and
cheking the new card
 CPU can be duplicated for
redundant solution
Follow Hot Swap demonstration on YouTube
http://www.youtube.com/user/Scamesistemi
50
Hot swap in three key points
1 - No switching off
Switchin off an F&G system means actuate the
whole process shut down procedure with
consequent down time and loss of production
2 - All the rest keeps on working
When replacing a module all other safety
functions are fully guaranteed. If the module is
installed with redundancy its safety function is
guaranteed too.
3 - No need for re-programming
The new module configuration is automatically
updated by the main CPUs. Anyone can execute
the repair.
51
Hot swap in three steps
1 – Take the module out
Undo the screws and remove the module.
(Silence the buzzer if annoying)
2 – Put the new module in
Slide the module and screw.
3 – Wait for the update
Automatic update is a matter of a few seconds
depending on the module type and complexity of
its configuration. When update is finished the
fault(s) indication goes away.
52
Cards can be redundant
On the same control panel can coexist:
Redundant links (SIL3)
• Detectors for high risks
• Alarm buttons in hazard area
• Evacuation area horns
Non redundant links (SIL2 or non SIL)
• Smoke and fire detectors (safety) for
building
• Addressable I/O modules for building
53
Programming & Networking
 IRIDE management and supervision program
 ProS81 for local or remote programming
 OPC server for integration with third parties
systems (SCADA’s PLC’s etc.)
 TCP/IP protocol LAN and WAN connection via
Ethernet, for interconnection of up to 99
panels
 Modbus RTU protocol, no limits in number of
panels
 Other protocols upon request
Integration with other systems achieved via
 Hardwired signals (SIL2, SIL3) - safety related
 Modbus signals – important
 TCP/IP – useful
 Addressable modules - useful
54
OPC Server, Iride and FO ring
56
SIL2 Safety Functions
1. Analogue detection and actuation
 PFDavg = 1,4 10-4
 SFF = > 90%
 HFT = 0
2. Conventional detection and actuation
 PFDavg = 9,4 10-5
 SFF = > 90%
 HFT = 0
3. Automatic Fire Extinguishing
 PFDavg = 7,8 10-6
 SFF = > 90%
 HFT = 0
SIL2 Certified
PFDavg = Average Probability of Failure on Demand
SFF = Safe Failure Fraction; HFT= Hardware Fault Tolerance
57
SIL3 Safety Functions
1. Analogue detection and actuation
 PFDavg = 5,0 10-6
 SFF = > 90%
 HFT = 1
2. Conventional detection and actuation
 PFDavg = 4,0 10-6
 SFF = > 90%
 HFT=1
3. Automatic Fire Extinguishing
 PFDavg = 3,6 10-6
 SFF = > 90%
 HFT=1
PFDavg = Average Probability of Failure on Demand
SFF = Safe Failure Fraction; HFT= Hardware Fault Tolerance
SIL3 Certified
PFDavg
58
SIL Safety Functions
Addressable fire detection and actuation
Apollo Devices
Hot Swap Redundant Power Unit
61
Main Figures
S81HS control panel capacity UL EN
HW
Rack for each control panel 6 10
Cards for each rack 13
Maximum number of
devices for each control
panel
Single point 9,906 16,510
Addressable
(subaddresses) 29,700+29,700
SW
Max number of zones (*1) 300+300
Max number of devices per zone (*2) 99+99+99
Max number of S81-HS on TCP/IP a network 99
(*1) = 300 safety zone and 300 security zone
(*2) = 99 inputs, 99 outputs , 99 logic relationships/gates.
Zone: ”portion of protected area”
62
Certifications
Applicable standards Year Lab Report
EN 54-2
Fire detection and fire alarm systems - Control and
indicating equipment
2008 IMQ
0051-CPD-0233
0051-CPD-0234
0051-CPD-0235
EN 54-4
Fire detection and fire alarm systems - Power supply
equipment
2008 IMQ 44AH00060
EN 12094-1
Fixed fire fighting systems - Requirements for electrical
automatic control and delay devices
2008 IMQ
0051-CPD-0137
0051-CPD-0138
0051-CPD-0139
IEC 61508 1-7: 2.0
Functional safety of programmable electronic safety-
related Systems - Requirements for Safety Integrity Level
(SIL2 & SIL3)
2013 TÜV TÜV968/EL 884,01/13
EN 50402: 2005
Electrical apparatus for the detection and measurements
of combustible or toxic gases or vapours or of oxygen
2009 TÜV FS 28709180
CEI 79-2:1998
CEI 79:2 ab2000
Control and indicating equipment for alarm systems
(Italian standard for anti-intrusion systems)
2008 IMQ CA12.00953
GOST-K, GOST-R Fire detection and fire alarm control panel 2009 GH POCC IT.AB24.B01128
NFPA 72
UL864, Control Units and Accessories for Fire Alarm
Systems
UL2017, General-Purpose Signaling Devices and
Systems
2012 UL 20121002-S24857
63
SUMMARY
 Addressable and Conventional Fire Detection
 Automatic Fire Extinguishing
 Gas Detection
 Security, Access control, CCTV, etc.
ALL IN ONE
 Modular, sizeable to need
 Distributed intelligence
 High availability, fault tolerance
 HOT SWAP
 SIL2 and SIL3
Follow Video demonstration on YouTube
http://www.youtube.com/user/Scamesistemi

More Related Content

What's hot

Dcs functional block diagrams
Dcs functional block diagramsDcs functional block diagrams
Dcs functional block diagramsJesusLopez715693
 
Hazardous area classification and control of ignition sources
Hazardous area classification and control of ignition sourcesHazardous area classification and control of ignition sources
Hazardous area classification and control of ignition sourceseldhoev
 
Hazardous Area Classification
Hazardous Area ClassificationHazardous Area Classification
Hazardous Area Classificationdebuddit
 
Industrial Networking - Profibus
Industrial Networking - ProfibusIndustrial Networking - Profibus
Industrial Networking - ProfibusYogesh Kumar
 
Hazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson Industrial
Hazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson IndustrialHazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson Industrial
Hazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson IndustrialThorne & Derrick International
 
Hazardous area classification
Hazardous area classificationHazardous area classification
Hazardous area classificationrajkumar_sm
 
Fm 200
Fm 200Fm 200
Fm 200Gielle
 
SA08302002E Control Panel Design Guide
SA08302002E Control Panel Design GuideSA08302002E Control Panel Design Guide
SA08302002E Control Panel Design GuideErik Barnes
 
PLC, DCS and PLC vs DCS Presentation by Jitender Singh Shekhawat
PLC, DCS and PLC vs DCS Presentation by Jitender Singh ShekhawatPLC, DCS and PLC vs DCS Presentation by Jitender Singh Shekhawat
PLC, DCS and PLC vs DCS Presentation by Jitender Singh ShekhawatJitender Singh Shekhawat
 
Thermon Heat Tracing Cables - Brochure
Thermon Heat Tracing Cables - BrochureThermon Heat Tracing Cables - Brochure
Thermon Heat Tracing Cables - BrochureThorne & Derrick UK
 
P&ID Symbols | Gaurav Singh Rajput
P&ID Symbols | Gaurav Singh Rajput P&ID Symbols | Gaurav Singh Rajput
P&ID Symbols | Gaurav Singh Rajput Gaurav Singh Rajput
 
Water Leak Detection Systems
Water Leak Detection SystemsWater Leak Detection Systems
Water Leak Detection SystemsJohnny Tsai
 
Allenbradley Control Logix PLC Network Architecture
Allenbradley Control Logix PLC Network  ArchitectureAllenbradley Control Logix PLC Network  Architecture
Allenbradley Control Logix PLC Network ArchitectureDEEPAK GORAI
 

What's hot (20)

Working of DCS systems
Working of DCS systemsWorking of DCS systems
Working of DCS systems
 
Dcs functional block diagrams
Dcs functional block diagramsDcs functional block diagrams
Dcs functional block diagrams
 
Basics of atex
Basics of atexBasics of atex
Basics of atex
 
Hazardous area classification and control of ignition sources
Hazardous area classification and control of ignition sourcesHazardous area classification and control of ignition sources
Hazardous area classification and control of ignition sources
 
Honeywell Gas Detection Product Book
Honeywell Gas Detection Product BookHoneywell Gas Detection Product Book
Honeywell Gas Detection Product Book
 
Hazardous Area Classification
Hazardous Area ClassificationHazardous Area Classification
Hazardous Area Classification
 
Industrial Networking - Profibus
Industrial Networking - ProfibusIndustrial Networking - Profibus
Industrial Networking - Profibus
 
Hazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson Industrial
Hazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson IndustrialHazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson Industrial
Hazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson Industrial
 
Hazardous area classification
Hazardous area classificationHazardous area classification
Hazardous area classification
 
Fm 200
Fm 200Fm 200
Fm 200
 
SA08302002E Control Panel Design Guide
SA08302002E Control Panel Design GuideSA08302002E Control Panel Design Guide
SA08302002E Control Panel Design Guide
 
PLC, DCS and PLC vs DCS Presentation by Jitender Singh Shekhawat
PLC, DCS and PLC vs DCS Presentation by Jitender Singh ShekhawatPLC, DCS and PLC vs DCS Presentation by Jitender Singh Shekhawat
PLC, DCS and PLC vs DCS Presentation by Jitender Singh Shekhawat
 
Thermon Heat Tracing Cables - Brochure
Thermon Heat Tracing Cables - BrochureThermon Heat Tracing Cables - Brochure
Thermon Heat Tracing Cables - Brochure
 
P&ID Symbols | Gaurav Singh Rajput
P&ID Symbols | Gaurav Singh Rajput P&ID Symbols | Gaurav Singh Rajput
P&ID Symbols | Gaurav Singh Rajput
 
A te x wall chart
A te x wall chartA te x wall chart
A te x wall chart
 
Hazardous Area Classification
Hazardous Area ClassificationHazardous Area Classification
Hazardous Area Classification
 
Dcs operator training
Dcs operator trainingDcs operator training
Dcs operator training
 
Water Leak Detection Systems
Water Leak Detection SystemsWater Leak Detection Systems
Water Leak Detection Systems
 
Smpv(u) rules 2016-18
Smpv(u) rules  2016-18Smpv(u) rules  2016-18
Smpv(u) rules 2016-18
 
Allenbradley Control Logix PLC Network Architecture
Allenbradley Control Logix PLC Network  ArchitectureAllenbradley Control Logix PLC Network  Architecture
Allenbradley Control Logix PLC Network Architecture
 

Viewers also liked

Expropacion petrolera 1
Expropacion petrolera 1Expropacion petrolera 1
Expropacion petrolera 1kashdoor
 
การอนุรักษ์ปะการังด้วยวิธีการทางกฎหมาย บริเวณอุทยานแห่งชาติหาดนพรัตน์ธารา-หมู...
การอนุรักษ์ปะการังด้วยวิธีการทางกฎหมาย บริเวณอุทยานแห่งชาติหาดนพรัตน์ธารา-หมู...การอนุรักษ์ปะการังด้วยวิธีการทางกฎหมาย บริเวณอุทยานแห่งชาติหาดนพรัตน์ธารา-หมู...
การอนุรักษ์ปะการังด้วยวิธีการทางกฎหมาย บริเวณอุทยานแห่งชาติหาดนพรัตน์ธารา-หมู...Mild Warinee
 
El problema de investigación y el proceso del pensamiento reflexivo
El problema de investigación y el proceso del pensamiento reflexivoEl problema de investigación y el proceso del pensamiento reflexivo
El problema de investigación y el proceso del pensamiento reflexivoRecursos Docentes
 
Конференція. Львів
Конференція. ЛьвівКонференція. Львів
Конференція. ЛьвівCenter_Inspiration
 
Security training 2017
Security training 2017Security training 2017
Security training 2017Cindy Tillery
 
3.plant instrumentation and control theory
3.plant instrumentation and control theory3.plant instrumentation and control theory
3.plant instrumentation and control theoryNoor Azman Muhammad
 
Consecuencias de la Revolución Haitiana en Santo Domingo
Consecuencias de la Revolución Haitiana en Santo DomingoConsecuencias de la Revolución Haitiana en Santo Domingo
Consecuencias de la Revolución Haitiana en Santo DomingoVictor Manuel Pichardo
 
Collective identity intro
Collective identity introCollective identity intro
Collective identity introcigdemkalem
 
My Instrumentation Field/ Emp. Details.
My  Instrumentation Field/ Emp. Details.My  Instrumentation Field/ Emp. Details.
My Instrumentation Field/ Emp. Details.anantbhise
 
Collective identity lesson two
Collective identity lesson twoCollective identity lesson two
Collective identity lesson twocigdemkalem
 
Handbook For Process Plant Project Engineers - Peter Watermeyer
Handbook For Process Plant Project Engineers - Peter WatermeyerHandbook For Process Plant Project Engineers - Peter Watermeyer
Handbook For Process Plant Project Engineers - Peter WatermeyerVeerender Putta
 
DCS PRESENTATION
DCS PRESENTATIONDCS PRESENTATION
DCS PRESENTATIONbvent2005
 
Instrumentation and control systems
Instrumentation and control systemsInstrumentation and control systems
Instrumentation and control systemsErwin Coliyat
 
Instrumentation & Control For Thermal Power Plant
Instrumentation & Control For Thermal Power PlantInstrumentation & Control For Thermal Power Plant
Instrumentation & Control For Thermal Power PlantSHIVAJI CHOUDHURY
 
PERSPECTIVE EUROPE
PERSPECTIVE EUROPEPERSPECTIVE EUROPE
PERSPECTIVE EUROPEJony Kad
 

Viewers also liked (19)

Expropacion petrolera 1
Expropacion petrolera 1Expropacion petrolera 1
Expropacion petrolera 1
 
การอนุรักษ์ปะการังด้วยวิธีการทางกฎหมาย บริเวณอุทยานแห่งชาติหาดนพรัตน์ธารา-หมู...
การอนุรักษ์ปะการังด้วยวิธีการทางกฎหมาย บริเวณอุทยานแห่งชาติหาดนพรัตน์ธารา-หมู...การอนุรักษ์ปะการังด้วยวิธีการทางกฎหมาย บริเวณอุทยานแห่งชาติหาดนพรัตน์ธารา-หมู...
การอนุรักษ์ปะการังด้วยวิธีการทางกฎหมาย บริเวณอุทยานแห่งชาติหาดนพรัตน์ธารา-หมู...
 
Francesco Petrarca
Francesco PetrarcaFrancesco Petrarca
Francesco Petrarca
 
William shakespeare
William shakespeareWilliam shakespeare
William shakespeare
 
El problema de investigación y el proceso del pensamiento reflexivo
El problema de investigación y el proceso del pensamiento reflexivoEl problema de investigación y el proceso del pensamiento reflexivo
El problema de investigación y el proceso del pensamiento reflexivo
 
Конференція. Львів
Конференція. ЛьвівКонференція. Львів
Конференція. Львів
 
Security training 2017
Security training 2017Security training 2017
Security training 2017
 
3.plant instrumentation and control theory
3.plant instrumentation and control theory3.plant instrumentation and control theory
3.plant instrumentation and control theory
 
Consecuencias de la Revolución Haitiana en Santo Domingo
Consecuencias de la Revolución Haitiana en Santo DomingoConsecuencias de la Revolución Haitiana en Santo Domingo
Consecuencias de la Revolución Haitiana en Santo Domingo
 
Collective identity intro
Collective identity introCollective identity intro
Collective identity intro
 
My Instrumentation Field/ Emp. Details.
My  Instrumentation Field/ Emp. Details.My  Instrumentation Field/ Emp. Details.
My Instrumentation Field/ Emp. Details.
 
Collective identity lesson two
Collective identity lesson twoCollective identity lesson two
Collective identity lesson two
 
Class 2 design methodology for process control
Class 2   design methodology for process controlClass 2   design methodology for process control
Class 2 design methodology for process control
 
Lecture 10,11 Basics of FEM
Lecture 10,11   Basics of FEMLecture 10,11   Basics of FEM
Lecture 10,11 Basics of FEM
 
Handbook For Process Plant Project Engineers - Peter Watermeyer
Handbook For Process Plant Project Engineers - Peter WatermeyerHandbook For Process Plant Project Engineers - Peter Watermeyer
Handbook For Process Plant Project Engineers - Peter Watermeyer
 
DCS PRESENTATION
DCS PRESENTATIONDCS PRESENTATION
DCS PRESENTATION
 
Instrumentation and control systems
Instrumentation and control systemsInstrumentation and control systems
Instrumentation and control systems
 
Instrumentation & Control For Thermal Power Plant
Instrumentation & Control For Thermal Power PlantInstrumentation & Control For Thermal Power Plant
Instrumentation & Control For Thermal Power Plant
 
PERSPECTIVE EUROPE
PERSPECTIVE EUROPEPERSPECTIVE EUROPE
PERSPECTIVE EUROPE
 

Similar to S81-HS Panel Presentation

ASESIndia Analog Addressable Fire Alarm System
ASESIndia  Analog Addressable Fire Alarm SystemASESIndia  Analog Addressable Fire Alarm System
ASESIndia Analog Addressable Fire Alarm SystemASES Security Pvt. Ltd.
 
Masibus 85 xx+ masibus precious _daq module.pdf
Masibus 85 xx+ masibus precious _daq module.pdfMasibus 85 xx+ masibus precious _daq module.pdf
Masibus 85 xx+ masibus precious _daq module.pdfVignesh Ramachandan
 
Addressable system definition.pdf
Addressable system definition.pdfAddressable system definition.pdf
Addressable system definition.pdfRicardoHernanGomezB
 
Detectomat Fire Alarm Systems in India by Monsher
Detectomat Fire Alarm Systems in India by MonsherDetectomat Fire Alarm Systems in India by Monsher
Detectomat Fire Alarm Systems in India by Monshermonsher123
 
Protege Hardware Sales Updated October 2008
Protege Hardware Sales Updated October 2008Protege Hardware Sales Updated October 2008
Protege Hardware Sales Updated October 2008jeremyomeara
 
ES-200X Ficha técnica.pdf
ES-200X Ficha técnica.pdfES-200X Ficha técnica.pdf
ES-200X Ficha técnica.pdfeduard10
 
HST New Fire Alarm System
HST New Fire Alarm SystemHST New Fire Alarm System
HST New Fire Alarm Systemssuser7165ec
 
Smartline020 4-f user-manual
Smartline020 4-f user-manualSmartline020 4-f user-manual
Smartline020 4-f user-manualwoeur
 
Cps fire safety
Cps fire safetyCps fire safety
Cps fire safetymvks rao
 
D List 835-SEC-15-Sensor-Control-Unit-d-listcontroller-technical-data
D List 835-SEC-15-Sensor-Control-Unit-d-listcontroller-technical-dataD List 835-SEC-15-Sensor-Control-Unit-d-listcontroller-technical-data
D List 835-SEC-15-Sensor-Control-Unit-d-listcontroller-technical-dataHans Bronkhorst
 
Linear AM3Plus 4 Portal Access Controller
Linear AM3Plus 4 Portal Access ControllerLinear AM3Plus 4 Portal Access Controller
Linear AM3Plus 4 Portal Access ControllerMark Jim
 
Powerful Transmitter like Linear Dx21 Is Available at Reasonable Prices
Powerful Transmitter like Linear Dx21 Is Available at Reasonable PricesPowerful Transmitter like Linear Dx21 Is Available at Reasonable Prices
Powerful Transmitter like Linear Dx21 Is Available at Reasonable Pricesjohnmark00007
 
Universal modules TXM1.8x Siemens
Universal modules TXM1.8x SiemensUniversal modules TXM1.8x Siemens
Universal modules TXM1.8x SiemensJustin Hoang
 
Drager QuadGard Fixed Gas Detector Control System - Spec Sheet
Drager QuadGard Fixed Gas Detector Control System - Spec SheetDrager QuadGard Fixed Gas Detector Control System - Spec Sheet
Drager QuadGard Fixed Gas Detector Control System - Spec SheetThorne & Derrick UK
 
IM 42 XX Series - Intelligent Monitoring System - 4 to 20mA catalogue
IM 42 XX Series - Intelligent Monitoring System - 4 to 20mA catalogueIM 42 XX Series - Intelligent Monitoring System - 4 to 20mA catalogue
IM 42 XX Series - Intelligent Monitoring System - 4 to 20mA catalogueSuyash Lad
 
WIRELESS FIRE ALARM & MONITOR ON LCD
WIRELESS FIRE ALARM & MONITOR ON LCDWIRELESS FIRE ALARM & MONITOR ON LCD
WIRELESS FIRE ALARM & MONITOR ON LCD20285ThirupathiReddy
 

Similar to S81-HS Panel Presentation (20)

PS-MSMX_en
PS-MSMX_enPS-MSMX_en
PS-MSMX_en
 
ASESIndia Analog Addressable Fire Alarm System
ASESIndia  Analog Addressable Fire Alarm SystemASESIndia  Analog Addressable Fire Alarm System
ASESIndia Analog Addressable Fire Alarm System
 
Masibus 85 xx+ masibus precious _daq module.pdf
Masibus 85 xx+ masibus precious _daq module.pdfMasibus 85 xx+ masibus precious _daq module.pdf
Masibus 85 xx+ masibus precious _daq module.pdf
 
Addressable system definition.pdf
Addressable system definition.pdfAddressable system definition.pdf
Addressable system definition.pdf
 
Detectomat Fire Alarm Systems in India by Monsher
Detectomat Fire Alarm Systems in India by MonsherDetectomat Fire Alarm Systems in India by Monsher
Detectomat Fire Alarm Systems in India by Monsher
 
Protege Hardware Sales Updated October 2008
Protege Hardware Sales Updated October 2008Protege Hardware Sales Updated October 2008
Protege Hardware Sales Updated October 2008
 
ES-200X Ficha técnica.pdf
ES-200X Ficha técnica.pdfES-200X Ficha técnica.pdf
ES-200X Ficha técnica.pdf
 
HST New Fire Alarm System
HST New Fire Alarm SystemHST New Fire Alarm System
HST New Fire Alarm System
 
Smartline020 4-f user-manual
Smartline020 4-f user-manualSmartline020 4-f user-manual
Smartline020 4-f user-manual
 
Cps fire safety
Cps fire safetyCps fire safety
Cps fire safety
 
5808spec
5808spec5808spec
5808spec
 
D List 835-SEC-15-Sensor-Control-Unit-d-listcontroller-technical-data
D List 835-SEC-15-Sensor-Control-Unit-d-listcontroller-technical-dataD List 835-SEC-15-Sensor-Control-Unit-d-listcontroller-technical-data
D List 835-SEC-15-Sensor-Control-Unit-d-listcontroller-technical-data
 
Linear AM3Plus 4 Portal Access Controller
Linear AM3Plus 4 Portal Access ControllerLinear AM3Plus 4 Portal Access Controller
Linear AM3Plus 4 Portal Access Controller
 
Powerful Transmitter like Linear Dx21 Is Available at Reasonable Prices
Powerful Transmitter like Linear Dx21 Is Available at Reasonable PricesPowerful Transmitter like Linear Dx21 Is Available at Reasonable Prices
Powerful Transmitter like Linear Dx21 Is Available at Reasonable Prices
 
Security catalogue
Security catalogueSecurity catalogue
Security catalogue
 
Universal modules TXM1.8x Siemens
Universal modules TXM1.8x SiemensUniversal modules TXM1.8x Siemens
Universal modules TXM1.8x Siemens
 
Drager QuadGard Fixed Gas Detector Control System - Spec Sheet
Drager QuadGard Fixed Gas Detector Control System - Spec SheetDrager QuadGard Fixed Gas Detector Control System - Spec Sheet
Drager QuadGard Fixed Gas Detector Control System - Spec Sheet
 
IM 42 XX Series - Intelligent Monitoring System - 4 to 20mA catalogue
IM 42 XX Series - Intelligent Monitoring System - 4 to 20mA catalogueIM 42 XX Series - Intelligent Monitoring System - 4 to 20mA catalogue
IM 42 XX Series - Intelligent Monitoring System - 4 to 20mA catalogue
 
WIRELESS FIRE ALARM & MONITOR ON LCD
WIRELESS FIRE ALARM & MONITOR ON LCDWIRELESS FIRE ALARM & MONITOR ON LCD
WIRELESS FIRE ALARM & MONITOR ON LCD
 
Introduction to IO-Link - Russell Smith
Introduction to IO-Link - Russell SmithIntroduction to IO-Link - Russell Smith
Introduction to IO-Link - Russell Smith
 

S81-HS Panel Presentation

  • 1. Fire and Gas - Oil & Gas - Industrial - Power Marco Santucci Scame Sistemi
  • 2. 15 Conventional F&G Philosophy Point type Smoke/heat detector Manual call point Addressable beacon and sounder Actuation of discharge Control of delays Dedicated fire detection Gas detectors Flame detectors HSSD High power beacons Remote singalling interface with other systems Main HMI IEC61508 for safety PLCs continous mode
  • 3. 16 Problems? Designed for building Actuation onlyDesigned for continous operation Main interface shall be EN54 INTERFACING COMMUNICATION ISSUES 1 The full function relies on all the three systems 2 Maintenance (3/4 power supplies and batteries) 3 TCO (NR Costs and Running Costs)
  • 4. 19 All in one  Addressable and conventional fire detection  Automatic fire extinguishing  Gas detection  Security, access control, CCTV, BMS, Environmental.
  • 5. SIL2 & SIL3 Programmable Electronic System for Safety-Related Applications Follow Video demonstration on YouTube http://www.youtube.com/user/Scamesistemi
  • 7. 22 HW & SW Features  Distributed intelligence  High availability  High fault tolerance  HOT SWAP of CPUs, I/O cards, power supply units, display  Easy maintenance  SIL2 and SIL3 rated for safety functions
  • 8. 23 Enclosures Wall Mount 400x600x700h mm  1 Expansion rack, max 13 cards  1 or 2 CPUs  SIL2 Max  EN54  EN12094  Fire and Gas
  • 9. 24 Enclosures Wall Mount 400x600x1100h mm  2 Expansion racks, max 26 cards  1 or 2 CPUs  SIL2 & SIL3  EN54  EN12094  Fire and Gas
  • 10. 25 Enclosures Floor standing single door 800x800x2100h mm  Max 6 Expansion racks  1 or 2 CPUs  SIL2 & SIL3  EN54  EN12094  UL  Fire and Gas  Hot swap Power supply
  • 11. 26 Enclosures Floor standing double door 1600x800x2100h mm  Max 10 Expansion racks  1 or 2 CPUs  SIL2 & SIL3  EN54  EN12094  Fire and Gas  Hot swap Power supply (2x)
  • 12. 27 Enclosures Compact Wall Mount 500x250x700h mm  1 non-expandable rack, max 8 cards  1 or 2 CPUs  SIL2  EN54  EN12094  Fire and Gas
  • 13. 28 Enclosures Ex-nR for Zone 2 800x800x2100h mm  All Stainless Steel  Max 6 Expansion racks  1 or 2 CPUs  SIL2 & SIL3  EN54  EN12094  Fire and Gas
  • 14. 29 Enclosures Ex-d for Zone 1 (EJB5)  1 non-expandable rack, max 8 cards  1 or 2 CPUs  SIL2  EN54  EN12094  Fire and Gas
  • 15. 30 Enclosures Demo unit in flight case  Equipped with 1 rack and Sample cards  2 CPUs  SIL2  2 Simulation push-buttons  2 Simulation LEDs  1 Smoke detector  1 manual call point  For demo and training
  • 16. 31 Multicard Racks E2001-1 Rack  Each S81 rack can contain up to 13 cards  The 14th slot of the rack is for the E2002-1 card, which manages the communication bus  The S81 panel can actually manage up to 10 racks, for a total of 130 cards
  • 17. 32 Card name F3002 F4001 F4002 F4003 Input lines 8 1 2 8 Kind of input Digital Analog 4-20 mA Analog 4-20 mA Analog 4-20 mA Line monitoring S.C., O.C. 0-24 mA 0-24 mA 0-24 mA Threshold levels 2 each line 2 2 each line 2 each line Visual indication Led Led, Bar Graph , display Led , display Led Card monitoring Self test Self test Self test Self test SIL 2 rated Single Single Single Single SIL 3 rated Redundant Redundant Redundant Redundant Analog and digital input cards
  • 18. 33 Collective type connections Different brand/type detectors (upgrading existing systems) 32 detectors per line (as per UNI 9795 standard) Short and open circuit monitoring Pre-alarm, alarm, alarm verification on each line
  • 19. 34 Connection of analogue sensors 4-20 mA inputs Direct reading on display Connection of gas, oxygen, vapour, heat, level sensors Return of input signal towards external systems SIL 2 certified sensors
  • 20. 35 Card name F7002 F7009 F7007 F7010 Devices manufacturer HOCHIKI APOLLO SCAME Notifier by Honeywell Loop protocol ESP XP95 / Discovery SSP System Sensor Applications Fire detection Fire detection Security, Env., BMS, Gas Fire detection Addressable each 127 126 127 99 in, 99 out. I/O digital modules I/O multichannel I/O multichannel I/O multichannel I/O multichannel Analogue inputs None None 4-20 mA 4-20 mA Field wiring Loop (ring 3km) Loop (ring 3km) Loop (ring 3km) Loop SIL rated None SIL 2 None None Addressable cards Can be used together
  • 21. 36 Card name F7009 F7007 Devices manufacturer APOLLO SCAME Loop protocol XP95 / Discovery SSP Applications Fire detection Security, Env., BMS, Gas Number of devices per loop 126 127 I/O digital modules I/O multichannel I/O multichannel Analogue inputs None 4-20 mA Field wiring Loop (ring 3km) Loop (ring 3km) SIL rated SIL 2 with Discovery SIL2 devices None Addressable cards How many loops?
  • 22. 37 Connection of analogue addressable devices Fire detection Detection (input) and control (output) on the same loop SIL 2 certified addressable detectors
  • 23. 38 Industrial anti-intrusion alarm 4-20mA 8 x Digital IN 4 x Supervised Digital IN 8 x Digital OUT. Mixed I/Os Access control, BMS, integration with CCTV … in the same loop. Gathering of statuses for safety functons The security system is certified to level II
  • 24. 39 Card name F5001 F5004 F5003 F5002 Ouput lines 8 4 8 16 Channel output current 500 mA 2 A 250 mA 500 mA (Total) Line monitoring S.C., O.C. S.C., O.C. Reversal polarity None Direct pulse line monit. Yes Yes None None Relay card None None T8008 - 4 ch. Yes Outputs can be paralleled Yes Yes None None SIL 2 rated Single Single None None SIL 3 rated Redundant Redundant None None Output cards
  • 25. 40 Monitored actuators Dedicated command for each actuator Line monitoring for short circuit and open circuit Card-line diagnostics Direct or reverse polarity monitoring SIL 2 certified actuators
  • 26. 41 Cards name F7006 F7008 F6002 Field protocol Modbus RTU Modbus RS485 S81 Applications Data link Weighing bottles Special logics Capacity 512 in, 512 out. 32 bottles 100 logic devices Mode Master or Slave 2 alarm thresholds Flip-flop, toggle, timer. Field wiring Rs232-Rs485 Rs 485 Internal bus SIL rated None (redundant) None None Special cards
  • 27. 42 Interaction and monitoring Serial MODBUS connection with PLC and SCADA Serial connection with electronic devices for cylinder weighing
  • 28. 43 Extinguishing control card F6001  Electrical automatic control and delay device (e.c.d.) certified to EN 12094-1 standard  Mandatory, in Europe for gas-based extinguishing systems  Able to manage all the virtual devices necessary for an extinguishing application in a zone  Physical I/O’s are controlled by other S81 input and output cards  S81 control panel can manage up to 64 F6001 cards
  • 29. 44 Extinguishing zone according to EN and NFPA standards one F6001 module per extinguishing zone Detection is made with any other input card Module 6001 does not have any physical I/O’s Directional and control valves, manual call points, sounders and other extinguishing devices are connected to separate I/O modules or Cards. Extinguishing control system can be SIL2 or up to SIL3. AUTOMATIC EXTINGUISHING
  • 30. 45 Example of a SIL function SIL certified detectors on addressable loop SIL certified actuators (solenoids, deluge valves, monitors) S81-HS panel with logic solver functions
  • 31. 46 EN54-4 / UL Power Supply Units PU-A003-1 Power Unit 2.5 A PU-A008-1 Power Unit – HOT SWAP AC/DC Converter 2 or 4 x 20A Battery Charger 120 Ah PU-A005-1 AC/DC Converter 4 A PU-A004-1 Battery Charger 65 Ah
  • 32. ProS81 Configuration Program 47 1) Definition of inputs 2) Definition of outputs 3) Definition of rules 4) Check of data validity  Runs on any Windows operating system  Communication with panel via RS232 or TCP/IP  Configuration is protected through password and USB dongle key ProS81
  • 33. Check of Data Validity 48
  • 34. 49 Very short repair time  Front plug-in/out cards  Automatic monitoring of cards and CPU fault  Automatic and safe disabling of malfunctioning cards  Cards can be hot swapped with compatible cards  CPU self configuring and cheking the new card  CPU can be duplicated for redundant solution Follow Hot Swap demonstration on YouTube http://www.youtube.com/user/Scamesistemi
  • 35. 50 Hot swap in three key points 1 - No switching off Switchin off an F&G system means actuate the whole process shut down procedure with consequent down time and loss of production 2 - All the rest keeps on working When replacing a module all other safety functions are fully guaranteed. If the module is installed with redundancy its safety function is guaranteed too. 3 - No need for re-programming The new module configuration is automatically updated by the main CPUs. Anyone can execute the repair.
  • 36. 51 Hot swap in three steps 1 – Take the module out Undo the screws and remove the module. (Silence the buzzer if annoying) 2 – Put the new module in Slide the module and screw. 3 – Wait for the update Automatic update is a matter of a few seconds depending on the module type and complexity of its configuration. When update is finished the fault(s) indication goes away.
  • 37. 52 Cards can be redundant On the same control panel can coexist: Redundant links (SIL3) • Detectors for high risks • Alarm buttons in hazard area • Evacuation area horns Non redundant links (SIL2 or non SIL) • Smoke and fire detectors (safety) for building • Addressable I/O modules for building
  • 38. 53 Programming & Networking  IRIDE management and supervision program  ProS81 for local or remote programming  OPC server for integration with third parties systems (SCADA’s PLC’s etc.)  TCP/IP protocol LAN and WAN connection via Ethernet, for interconnection of up to 99 panels  Modbus RTU protocol, no limits in number of panels  Other protocols upon request Integration with other systems achieved via  Hardwired signals (SIL2, SIL3) - safety related  Modbus signals – important  TCP/IP – useful  Addressable modules - useful
  • 39. 54 OPC Server, Iride and FO ring
  • 40. 56 SIL2 Safety Functions 1. Analogue detection and actuation  PFDavg = 1,4 10-4  SFF = > 90%  HFT = 0 2. Conventional detection and actuation  PFDavg = 9,4 10-5  SFF = > 90%  HFT = 0 3. Automatic Fire Extinguishing  PFDavg = 7,8 10-6  SFF = > 90%  HFT = 0 SIL2 Certified PFDavg = Average Probability of Failure on Demand SFF = Safe Failure Fraction; HFT= Hardware Fault Tolerance
  • 41. 57 SIL3 Safety Functions 1. Analogue detection and actuation  PFDavg = 5,0 10-6  SFF = > 90%  HFT = 1 2. Conventional detection and actuation  PFDavg = 4,0 10-6  SFF = > 90%  HFT=1 3. Automatic Fire Extinguishing  PFDavg = 3,6 10-6  SFF = > 90%  HFT=1 PFDavg = Average Probability of Failure on Demand SFF = Safe Failure Fraction; HFT= Hardware Fault Tolerance SIL3 Certified PFDavg
  • 42. 58 SIL Safety Functions Addressable fire detection and actuation Apollo Devices Hot Swap Redundant Power Unit
  • 43. 61 Main Figures S81HS control panel capacity UL EN HW Rack for each control panel 6 10 Cards for each rack 13 Maximum number of devices for each control panel Single point 9,906 16,510 Addressable (subaddresses) 29,700+29,700 SW Max number of zones (*1) 300+300 Max number of devices per zone (*2) 99+99+99 Max number of S81-HS on TCP/IP a network 99 (*1) = 300 safety zone and 300 security zone (*2) = 99 inputs, 99 outputs , 99 logic relationships/gates. Zone: ”portion of protected area”
  • 44. 62 Certifications Applicable standards Year Lab Report EN 54-2 Fire detection and fire alarm systems - Control and indicating equipment 2008 IMQ 0051-CPD-0233 0051-CPD-0234 0051-CPD-0235 EN 54-4 Fire detection and fire alarm systems - Power supply equipment 2008 IMQ 44AH00060 EN 12094-1 Fixed fire fighting systems - Requirements for electrical automatic control and delay devices 2008 IMQ 0051-CPD-0137 0051-CPD-0138 0051-CPD-0139 IEC 61508 1-7: 2.0 Functional safety of programmable electronic safety- related Systems - Requirements for Safety Integrity Level (SIL2 & SIL3) 2013 TÜV TÜV968/EL 884,01/13 EN 50402: 2005 Electrical apparatus for the detection and measurements of combustible or toxic gases or vapours or of oxygen 2009 TÜV FS 28709180 CEI 79-2:1998 CEI 79:2 ab2000 Control and indicating equipment for alarm systems (Italian standard for anti-intrusion systems) 2008 IMQ CA12.00953 GOST-K, GOST-R Fire detection and fire alarm control panel 2009 GH POCC IT.AB24.B01128 NFPA 72 UL864, Control Units and Accessories for Fire Alarm Systems UL2017, General-Purpose Signaling Devices and Systems 2012 UL 20121002-S24857
  • 45. 63 SUMMARY  Addressable and Conventional Fire Detection  Automatic Fire Extinguishing  Gas Detection  Security, Access control, CCTV, etc. ALL IN ONE  Modular, sizeable to need  Distributed intelligence  High availability, fault tolerance  HOT SWAP  SIL2 and SIL3 Follow Video demonstration on YouTube http://www.youtube.com/user/Scamesistemi