SlideShare a Scribd company logo
1 of 36
Download to read offline
UL61010-1 and -2-030
U.S. National Differences

UL Staff

                                                     Prepared: August 2012




UL and the UL logo are trademarks of UL LLC © 2012
Agenda
National Differences for:

•   Risk of Electric Shock
•   Risk of Fire
•   Protection Against Hazards from Fluids
•   Components and Subassemblies
•   Measuring Circuits
•   Annexes




                                                                       Slide 2
                  UL and the UL logo are trademarks of UL LLC © 2012
Permissible Limits for Accessible Parts
Normal Condition (6.3.1)
• Voltage Levels


                               US National Differences (to be in
     IEC 61010-1 3rd Edition   the North American Harmonized
                                          Standard)


            33 V rms                       30 V rms

          46.7 V peak                    42.4 V peak

            70 V dc                        60 V dc




                                                                   3
Permissible Limits for Accessible Parts
Single Fault Condition (6.3.2) Continued

     IEC 61010-1 3nd Edition   National Differences


            55 V rms                50 V rms


            78 V peak               70 V peak


            140 V dc                120 V dc



  Note: Sub-clauses 6.3.2 A


                                                      4
Figure 2DV - Maximum duration of short-term ACCESSIBLE
   voltages in SINGLE FAULT CONDITION (see 6.3.2 a))




    Key
    A a.c. voltage level in WET LOCATIONS   C d.c. voltage level in WET LOCATIONS
    B a.c. voltage level in dry locations   D d.c. voltage level in dry locations
National Difference – Protective Conductor
Impedance
6.5.2.4DV D2 Modification by replacing the text and the conformity
statement with the following:
• IEC – states 0.1 Ω, for non-detachable power cord 0.2 Ω.
• The impedance between the PROTECTIVE CONDUCTOR
   TERMINAL and each ACCESSIBLE part for which PROTECTIVE
   BONDING is specified shall not cause a potential drop of more than
   4 V.
• IEC - Conformity is checked by applying a test current for 1 min and
   then calculating impedance. The test current is the greater of
     a) 25 A a.c. r.m.s. at RATED MAINS frequency or d.c.,
     b) a current equal to twice the RATED current of the equipment
• Conformity is checked by inspection and by applying an a.c. test
   current for the duration specified in Table 6.5.2.4DV.1 and then
   measuring the voltage drop. See 4.4.4.3 for test conditions regarding
   the spread of fire.
•   .                    UL and the UL logo are trademarks of UL LLC © 2012
                                                                              6
National Difference – Protective Conductor
Impedance Continued
• The test current is twice the rating of the attachment plug cap, but
  not less than 40 A.

• If the equipment contains overcurrent protection devices for all poles
  of the MAINS supply, and if the wiring on the supply side of the
  overcurrent protection devices cannot become connected to
  ACCESSIBLE conductive parts in the case of a single fault, the test
  current need not be more than twice the RATED current of the
  internal overcurrent protection devices.

• If the test current exceeds 500 A, see CSA 0.4.




                                                                           7
National Difference – Table 6.5.2.4DV.1 -
Duration of Protective Bonding Test




    Table 6.5.2.4DV.1 – Duration of protective bonding test




                                                                          8
                     UL and the UL logo are trademarks of UL LLC © 2012
National Difference – Protective Bonding
impedance Conformity Statement
6.5.2.5DV D2 Modification:
• IEC - Conformity is checked by applying a test current of twice the
  value of the overcurrent protection means specified in the equipment
  installation instructions for the building supply MAINS CIRCUIT for 1
  min between the PROTECTIVE CONDUCTOR TERMINAL and
  each ACCESSIBLE conductive part for which PROTECTIVE
  BONDING is required. The voltage between them shall not exceed
  10 V a.c. r.m.s. or d.c.
• In the first sentence of the conformity statement, replace “1 min” with
  “the duration specified in Table 6.5.2.4DV.1”.
• In the second sentence of the conformity statement, replace “10 V”
  with “4 V”.




                                                                       9
National Difference - Connection to the MAINS supply
source and connections between parts of equipment
• IEC - 6.10.1 MAINS supply cords
The following requirements apply to non-detachable MAINS supply cords and to
detachable MAINS supply cords supplied with the equipment.
• Cords shall be RATED for the maximum current for the equipment and the cable
   used shall meet the requirements of IEC 60227 or IEC 60245.
ND - 6.10.1DV.1 Delete the reference to the requirements of IEC 60227 or IEC
60245 for MAINS supply cords in the second paragraph
• If a cord is likely to contact hot external parts of the equipment, it shall be made
    of suitably heat-resistant material.
•   If the cord is detachable, both the cord and the appliance inlet shall have
    adequate temperature RATINGS.
•  Conductors coloured green-and-yellow shall be used only for connection to
   PROTECTIVE CONDUCTOR TERMINALS.
6.10.1DV.2 Replace the fifth paragraph with the following:
ND - Green covered conductors (with or without yellow stripes) shall be used
only for connection to PROTECTIVE CONDUCTOR TERMINALS


                               UL and the UL logo are trademarks of UL LLC © 2012
National Difference - Connection to the MAINS supply
source and connections between parts of equipment
 Detachable MAINS supply cords with MAINS connectors according to IEC 60320 shall
 either meet the requirements of IEC 60799, or shall be RATED at least for the current
 RATING of the MAINS connector fitted to the cord.
 ND - 6.10.1DV.3 Delete the reference to the requirements of IEC 60799 for
 detachable MAINS supply cords in the sixth paragraph.
 ND - 6.10.1DV.4 Add the following paragraphs and new note after the sixth
 paragraph:
 ND - Requirements for MAINS cords or cord sets are contained in ANSI/UL 817 and
 CSA C22.2 No. 21.
 ND - Requirements for general use receptacles, attachment plugs, and similar
 wiring devices are contained in ANSI/UL 498 and CSA C22.2 No. 42, CSA C22.2 No.
 182.1, CSA C22.2 No. 182.2, and CSA C22.2 No. 182.3.
 ND - NOTE This subclause only applies to cords connected to the external fixed
 MAINS socket-outlet and to external interconnecting mains cords. This subclause
 does not apply to cords fully contained within the equipment enclosure

 •   Figure 9 explains the terminology for MAINS supply cords.
 •   Conformity is checked by inspection and, where necessary, by measurement.

                                                                                   11
National Difference - 6.10.4DV.1 PERMANENTLY CONNECTED
EQUIPMENT
• Addition of a new clause

• Equipment intended for permanent connection to the MAINS
  shall meet the requirements of Annex DVD.

• Conformity is checked as specified in Annex DVD.
National Difference – 6.11 Title Modification
• 6.11 Disconnection from supply source

• 6.11DV D2 Modification of the title: Add “and maintaining polarity” to
  the end of the subclause title.




                                                                          13
National Difference – 6.11.5DV D2 Polarity of
MAINS Connections
ND - 6.11.5DV D2 Addition of a new sub-clause for Polarity of
Connections to the MAINS Circuit:
• Any line-connected single-pole switch, any center contact of a lamp
  holder, and any automatic control with a marked off position shall be
  connected to a TERMINAL or lead intended for connection to the
  ungrounded conductor of the supply circuit.
  NOTE An “ungrounded” supply conductor is one that is not
  connected to protective earth at any point in the building installation.




                                                                         14
• National Difference – 9.6.1. ADV Connection
    of overcurrent protective devices
Added the following for connections of overcurrent protective devices

• 9.6.1ADV.1 A single-pole circuit breaker must be connected to the
    ungrounded supply conductor
•   9.6.1ADV.2 A multiple-pole circuit breaker must interrupt the neutral
    (grounded) and ungrounded conductors simultaneously.
•   9.6.1ADV.3 A single fuse must be in the ungrounded conductor.
•   9.6.1ADV.4 Fuses used in both the neutral (grounded) and
    ungrounded supply conductors must be adjacent with same ratings
    and characteristics.
•   9.6.1ADV.5 Screw shell of a plug fuseholder and accessible contact
    of an extractor type fuseholder when:
    • Located in the Ungrounded supply conductor: shall be connected towards
      the load.
    • Located in the Neutral conductor: the shell shall be connected towards the
      neutral supply line.
                                                                               15
• National Difference – 11.7.1. DV max.
  Pressure, referencing Annex G as normative
  for certain types
• 11.7.1DV.1 Laboratory and Testing and Measurement equipment
  having both of the following characteristics shall meet the
  requirements of 11.7.2 and G.5:
  a) a product of pressure and volume greater than 200 kPa·l,
  b) a pressure .greater than 50 kPa.

• 11.7.1DV.2 Laboratory equipment and testing and measurement
  equipment that do not have those characteristics shall meet the
  requirements of 11.7.3 and 11.7.4, as applicable.

• 11.7.1DV.3 Process Control and other equipment shall meet the
  requirements of Annex G, as applicable




                                                                    16
• National Difference – Leakage and Rupture at
  High Pressure11.7.2. DV Replacing Note as
  follows:
• Fluid-containing parts which in NORMAL USE have both of the
  following characteristics shall not cause a HAZARD through rupture
  or leakage:
    a) a product of pressure and volume greater than 200 kPa·l;
    b) a pressure greater than 50 kPa.
Conformity is checked by inspection and, if a HAZARD could arise, by the
described hydraulic test


• NOTE National authorities may allow safety to be established by
  calculation, for example according to the ASME Boiler and Pressure
  Vessel Code.




                                                                           17
National Difference – 14.1 Components and
Subassemblies North American Standards
• a) applicable safety requirements of a relevant IEC standard …
• b) the requirements of this standard and, where necessary for the
  application, any additional applicable safety requirements of the
  relevant IEC component standard, …
• c) if there is no relevant IEC standard, the requirements of this
  standard;
• d) applicable safety requirements of a non-IEC standard which are at
  least as high as those of the relevant IEC standard, provided that the
  component has been approved to the non- IEC standard by a
  recognized testing authority.
ND – In all these sub-clauses ), replace “IEC” with “ANSI, CAN, CSA,
IEC, ISO, or UL”.
ND - . Add a new note 3:
• NOTE 3: Annex DVA provides applicable safety requirements.

                                                                       18
National Difference – 14.7 Printed Wiring
Boards North American Flammability
Printed wiring boards shall be made of material with a flammability
classification of V-1 or better of IEC 60695-11-10.

ND - 14.7DV D2 Addition of the following to the end of the first
paragraph:
• A flammability RATING of ANSI/UL V-1 or CAN/CSA C22.2 No. 0.17
  is considered equivalent to the same classification of IEC 60695-11-
  10.




                                                                        19
National Difference – 14.9 Outdoor Use
ND - 14.9DV D2 Add a new sub-clause to address enclosures intended
for outdoor use:
• Nonmetallic enclosures intended for outdoor use shall meet the UV
   resistance requirements of ANSI/UL 746C or of CSA C22.2 No. 0.17,
   or both as appropriate.
NOTE ANSI/UL 746C, clause 25, requires a 1 000 hour UV/water exposure
preconditioning using a xenon-arc or
• alternatively a 720 hour UV/water exposure preconditioning using
  twin carbon arcs. CSA C22.2 No. 0.17, subclause 5.9, permits only
  the 1 000 hour UV/water exposure preconditioning.




                                                                        20
National Difference – 14.10 Conductive
Coatings
ND - 14.10DV D2 Add a new subclause to address conductive
coatings, shields, and tape:
• 14.10DV.1.1 The bond of a conductive (metallic) coating applied to a
  polymeric part shall be evaluated.
• 14.10DV.1.2.
    a) Evaluating the bond in accordance with the requirements for
    “Adhesives” in ANSI/UL 746C and/or CSA C22.2 No. 0.17, or
    b) Evaluating the product to determine that peeling or flaking of the
    coating would not reduce spacings or bridge live parts so as to introduce a
    risk of fire or electric shock.
.




                                                                             21
National Difference – 14.10 Conductive Shields,
and Tape
14.10DV.2 Conductive shield or tape
• 14.10DV.2.1 If peeling of the conductive shield or tape may introduce
  a RISK of fire or electric shock, the bond between a conductive
  shield or tape and any other surface shall be investigated.
• 14.10DV.2.2 Conformity is checked by inspection




                                                                      22
National Difference – 14.11 Direct Plug-in
Transformers North America Standards
• ND - Add a new sub-clause14.11DV D2

• 14.11DV.1 Direct plug-in transformer units:
• Direct plug-in transformer units are subject to additional
  requirements found in ANSI/UL 1310, CAN/CSA C22.2 No. 223,
  ANSI/UL 60950-1, or CSA C22.2 No. 60950-1, as applicable.




                                                               23
Measuring circuit TERMINALS
ND - Table 101DV DR Modify the values in Table 101 by replacing it with the
following:

Table 101DV - CLEARANCES and CREEPAGE DISTANCES for measuring circuit
TERMINALS with HAZARDOUS LIVE conductive parts (IEC Values in brackets)



     Voltage on conductive parts of TERMINAL                                CLEARANCE and
                                                                          CREEPAGE DISTANCE
      V a.c. r.m.s.                            V d.c.                            mm
     30 (33)  300                         60 (70)  414                         0,8
      >300  600                            >414  848                           1,0
     >600  1 000                          >848  1 414                          2,6
NOTE Values are determined by calculation for REINFORCED INSULATION. Transients are not taken into account.



            Conformity is checked by inspection and measurement.
101.3 Protection Against Mismatches of Inputs and
Ranges

ND - 101.3.3DV D2 Addition of the following test:

101.3.3DV.1 If the function or range controls have any effect on the
electrical characteristics of the input circuit, these controls shall
be changed to all possible settings while the input TERMINALS
are connected to the maximum RATED source.
Test leads for the tests of 101.3.2 and 101.3.3
101.3.4 …. If the manufacturer-supplied test leads are permanently
connected to the equipment, then the attached test leads supplied by
the manufacturer shall be used without modification.

ND - 101.3.4DV D2 Modification of 101.3.4 by deleting the following
   paragraph
    "If the manufacturer-supplied test leads are permanently
   connected to the equipment, then the attached test leads
   supplied by the manufacturer shall be used without
   modification." and replacing it with the following:

    101.3.4DV.1 The applicable tests of 101.3.2 and 101.3.3 shall be
    performed with the test leads specified above and shall be
    repeated with any test leads supplied with the equipment by
    the manufacturer.
Annex DVA (informative) CSA, UL, IEC
component standards.
ND - DVA D2 Addition of a new annex DVA as follows:
• The following is a matrix that provides a cross-reference
  between CSA, UL, and IEC standards for components.
• This cross-reference is not meant to imply that the standards
  are equivalent. The CSA, UL, and IEC standards listed are used
  for evaluation of components and features of products covered
  by this standard.
• Components need only comply with the applicable component
  standard acceptable in the country where the product is to be
  used.
• These standards are considered to refer to the latest edition and
  all revisions published to that edition.
Component Standards (Cont’d)
Component Standards (Cont’d)
Annex DVB (informative)
ND - DVB D2 Addition of a new annex DVB as follows
• A table indicating identifying all clauses that have a National
  Difference
Annex DVC - (informative) - UV radiation limits: Guidelines from
the American Conference of Governmental Industrial Hygienists
(ACGIH)
•   DVC D2 Addition of a new annex DVC for UV radiation limits
•   DVC.1.1 These threshold limit values (TLVs) refer to ultraviolet (UV)
    radiation in the spectral region between 180 and 400 nm and represent
    conditions under which it is believed that nearly all workers may be
    repeatedly exposed without adverse health effects.

•    DVC.1.2 These values for exposure of the eye or the skin apply to UV
    radiation from arc, gas, and vapor discharges, fluorescent and
    incandescent sources, and solar radiation, but they do not apply to UV
    lasers (see the TLV for lasers). These values do not apply to UV
    radiation exposure of photosensitive individuals or of individuals
    concomitantly exposed to photosensitizing agents. These exposures
    to the eye do not apply to aphakics. (See light and near-infrared TLV for
    radiation.) These values should be used as guides in the control of
    exposure to continuous sources where the duration of exposure is not
    less than 0,1 s. Likewise, these values should not be regarded as a fine
    line between safe and dangerous levels.
Annex DVC - (informative) - UV radiation limits:Guidelines from
the American Conference of Governmental Industrial Hygienists
(ACGIH
• DVC.2 Recommended values
•
    DVC.2.1 The TLVs for occupational exposure to UV radiation incident upon skin
    or eye where irradiance values are known and exposure time is controlled are
    as follows:
•   a) UV-A (315 to 400 nm) radiation to the unprotected eye:
•   1) For exposure times less than 1 000 seconds, the total energy should not
    exceed 1 J/cm2 (1 000 mJ/cm2).
•   2) For exposure times greater than 1 000 seconds, the average power level
    should not exceed 1 mW/cm2; and no 1 000 second time period should present
    a total energy that exceeds 1 J/cm2 (1 000 mJ/cm2).
•   b)     For monochromatic sources, the TLV for exposure to the unprotected skin
    or eye is shown in Table DVC.2.1.1 (also represented in Figure DVC.2.1.1) and
    should not be exceeded within an 8-hour period.
•   c) For broad-spectrum or multi-peak sources, the TLV for exposure of the
    unprotected skin or eye should be calculated based on an effective weighting
    formula:
•   Eeff = S (El • S l • Dl )
Annex DVD (normative) permanent connection
to MAINS
ND - DVD D2 Addition of a new Annex DVD as follows:
•   DVD.1 General
•   DVD.1.1 Equipment intended for permanent connection to the mains
    shall have provision for connection of a wiring system in accordance
    with ANSI/NFPA 70, NEC, with CSA C22.1, CEC, Part I, or with both as
    appropriate, and shall meet the requirements of DVD.2 to DVD.3, as
    applicable.
•    DVD.1.2 Conformity is checked by inspection, and as specified in
    DVD.2 to DVD.3.
Annex DVD (normative) permanent connection
to MAINS (Cont’d)
Topics Are:
DVD.2 Wiring TERMINALS and leads e.g.
• DVD.2.1.1 PERMANENTLY CONNECTED EQUIPMENT shall be provided
  with TERMINALS or leads for the connection of conductors having an
  ampacity that, in accordance with the National Electrical Code and/or the
  Canadian Electrical Code, Part I, is acceptable for the equipment.
DVD.3 ENCLOSURE requirements for conduit entry e.g
  • DVD.3.1 An ENCLOSURE shall not pull apart or sustain damage such as
    cracking and breaking, and knockouts shall remain in place when
    subjected to the pulling, torque, and bending that is likely to occur.
DVD.4 Conduit ENCLOSURE entry tests e.g.
  • DVD.4.1 Conduit pull-out test
  • DVD.4.2 Conduit torque test
  • DVD.4.3 Bending
  • DVD.4.4 Knockouts
Summary


National Differences for:

•   Risk of Electric Shock
•   Risk of Fire
•   Protection Against Hazards from Fluids
•   Components and Subassemblies
•   Measuring Circuits
•   Annexes



                                             Slide 35
Thank You

Visit: www.ul.com/61010blog to download
a comparison between IEC 61010 2nd and
                3rd edition.
 Contact us at: Medical.Inquiry@ul.com

More Related Content

What's hot

Full Wave Rectifier(SI diode)
Full Wave Rectifier(SI diode)Full Wave Rectifier(SI diode)
Full Wave Rectifier(SI diode)SyedFahim20
 
Basic electronics final presentation
Basic electronics final presentationBasic electronics final presentation
Basic electronics final presentationVijendrasingh Rathor
 
What are and how are PNP NPN Transistor materials are made ?
What are and how are PNP NPN  Transistor materials  are made ?What are and how are PNP NPN  Transistor materials  are made ?
What are and how are PNP NPN Transistor materials are made ?Amarnath Reddy
 
S02 simbologia 2018 vers4
S02 simbologia 2018 vers4S02 simbologia 2018 vers4
S02 simbologia 2018 vers4DemianRamos
 
Ukrainian conflict bulletin 1
Ukrainian conflict bulletin 1Ukrainian conflict bulletin 1
Ukrainian conflict bulletin 1Csaba7
 
MOSFET as a switch
MOSFET as a switchMOSFET as a switch
MOSFET as a switchssuser3cd2c9
 
What is IPC A-620 Training Program
What is IPC A-620 Training ProgramWhat is IPC A-620 Training Program
What is IPC A-620 Training ProgramBob Wettermann
 
POWER ELECTRONIC DEVICES
POWER ELECTRONIC DEVICESPOWER ELECTRONIC DEVICES
POWER ELECTRONIC DEVICESshazaliza
 
Acs880 All-compatible ABB industrial drives​
Acs880 All-compatible ABB industrial drives​Acs880 All-compatible ABB industrial drives​
Acs880 All-compatible ABB industrial drives​Jalal Benhiba
 
Electrical Lessons learned
Electrical Lessons learnedElectrical Lessons learned
Electrical Lessons learnedmichaeljmack
 
Beginners guide eplan_electric_p8_version_2.1_us
Beginners guide eplan_electric_p8_version_2.1_usBeginners guide eplan_electric_p8_version_2.1_us
Beginners guide eplan_electric_p8_version_2.1_usionut grozav
 

What's hot (20)

Full Wave Rectifier(SI diode)
Full Wave Rectifier(SI diode)Full Wave Rectifier(SI diode)
Full Wave Rectifier(SI diode)
 
Thyristor
ThyristorThyristor
Thyristor
 
Basic electronics final presentation
Basic electronics final presentationBasic electronics final presentation
Basic electronics final presentation
 
Diode
DiodeDiode
Diode
 
What are and how are PNP NPN Transistor materials are made ?
What are and how are PNP NPN  Transistor materials  are made ?What are and how are PNP NPN  Transistor materials  are made ?
What are and how are PNP NPN Transistor materials are made ?
 
Function generator
Function generatorFunction generator
Function generator
 
S02 simbologia 2018 vers4
S02 simbologia 2018 vers4S02 simbologia 2018 vers4
S02 simbologia 2018 vers4
 
Diode
DiodeDiode
Diode
 
Ukrainian conflict bulletin 1
Ukrainian conflict bulletin 1Ukrainian conflict bulletin 1
Ukrainian conflict bulletin 1
 
MOSFET as a switch
MOSFET as a switchMOSFET as a switch
MOSFET as a switch
 
Controllogix 5000 Training
Controllogix 5000 TrainingControllogix 5000 Training
Controllogix 5000 Training
 
What is IPC A-620 Training Program
What is IPC A-620 Training ProgramWhat is IPC A-620 Training Program
What is IPC A-620 Training Program
 
POWER ELECTRONIC DEVICES
POWER ELECTRONIC DEVICESPOWER ELECTRONIC DEVICES
POWER ELECTRONIC DEVICES
 
ESD protection
ESD protection ESD protection
ESD protection
 
Acs880 All-compatible ABB industrial drives​
Acs880 All-compatible ABB industrial drives​Acs880 All-compatible ABB industrial drives​
Acs880 All-compatible ABB industrial drives​
 
Chapter#2
Chapter#2Chapter#2
Chapter#2
 
Electrical Lessons learned
Electrical Lessons learnedElectrical Lessons learned
Electrical Lessons learned
 
MIL-STD-461 EMI Filters
MIL-STD-461 EMI FiltersMIL-STD-461 EMI Filters
MIL-STD-461 EMI Filters
 
Beginners guide eplan_electric_p8_version_2.1_us
Beginners guide eplan_electric_p8_version_2.1_usBeginners guide eplan_electric_p8_version_2.1_us
Beginners guide eplan_electric_p8_version_2.1_us
 
Cableado analogicas
Cableado analogicasCableado analogicas
Cableado analogicas
 

Similar to 61010 national difference for slideshare

Gabriel Ojeah - HV CONFERENCE PAPER- PERTH 2015
Gabriel Ojeah - HV CONFERENCE PAPER- PERTH 2015Gabriel Ojeah - HV CONFERENCE PAPER- PERTH 2015
Gabriel Ojeah - HV CONFERENCE PAPER- PERTH 2015Gabriel Emeka Ojeah
 
5 is 1554_2_pvc cables hd
5 is 1554_2_pvc cables hd5 is 1554_2_pvc cables hd
5 is 1554_2_pvc cables hdSamsher Singh
 
ABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum Contactors
ABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum ContactorsABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum Contactors
ABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum ContactorsThorne & Derrick International
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersThorne & Derrick International
 
Universal Four Leg v4
Universal Four Leg v4Universal Four Leg v4
Universal Four Leg v4AxelDijksman
 
A study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendmentsA study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendmentsricha diptisikha
 
Grounding pad mounted transformers
Grounding   pad mounted transformersGrounding   pad mounted transformers
Grounding pad mounted transformersJimmy Chaparro
 
Grounding pad mounted transformers
Grounding   pad mounted transformersGrounding   pad mounted transformers
Grounding pad mounted transformersJimmy Chaparro
 
Vacuum Circuit Breakers Testing Methods
Vacuum Circuit Breakers Testing MethodsVacuum Circuit Breakers Testing Methods
Vacuum Circuit Breakers Testing MethodsAli Sepehri
 
2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revisedBasudev patra
 
Results of 10 years after installation tests with partial discharge detection...
Results of 10 years after installation tests with partial discharge detection...Results of 10 years after installation tests with partial discharge detection...
Results of 10 years after installation tests with partial discharge detection...HighVoltageDUT
 
P D Measurements On H V Joints
P D  Measurements On  H V JointsP D  Measurements On  H V Joints
P D Measurements On H V JointsAol_Amil
 
Getting up close and personal with rc ds Bernard Gittins
Getting up close and personal with rc ds   Bernard GittinsGetting up close and personal with rc ds   Bernard Gittins
Getting up close and personal with rc ds Bernard GittinsNSW Environment and Planning
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERRitesh Kumawat
 
Topological Advancement in DVR; A review
Topological Advancement in DVR; A reviewTopological Advancement in DVR; A review
Topological Advancement in DVR; A reviewIRJET Journal
 
ZVS Circuit based – Cockcroft Walton High Voltage DC Generator
ZVS Circuit based – Cockcroft Walton High Voltage DC GeneratorZVS Circuit based – Cockcroft Walton High Voltage DC Generator
ZVS Circuit based – Cockcroft Walton High Voltage DC GeneratorIRJET Journal
 

Similar to 61010 national difference for slideshare (20)

Gabriel Ojeah - HV CONFERENCE PAPER- PERTH 2015
Gabriel Ojeah - HV CONFERENCE PAPER- PERTH 2015Gabriel Ojeah - HV CONFERENCE PAPER- PERTH 2015
Gabriel Ojeah - HV CONFERENCE PAPER- PERTH 2015
 
5 is 1554_2_pvc cables hd
5 is 1554_2_pvc cables hd5 is 1554_2_pvc cables hd
5 is 1554_2_pvc cables hd
 
ABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum Contactors
ABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum ContactorsABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum Contactors
ABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum Contactors
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment Designers
 
Universal Four Leg v4
Universal Four Leg v4Universal Four Leg v4
Universal Four Leg v4
 
A study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendmentsA study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendments
 
Grounding pad mounted transformers
Grounding   pad mounted transformersGrounding   pad mounted transformers
Grounding pad mounted transformers
 
Grounding pad mounted transformers
Grounding   pad mounted transformersGrounding   pad mounted transformers
Grounding pad mounted transformers
 
Inspector_Example1.pdf
Inspector_Example1.pdfInspector_Example1.pdf
Inspector_Example1.pdf
 
Vacuum Circuit Breakers Testing Methods
Vacuum Circuit Breakers Testing MethodsVacuum Circuit Breakers Testing Methods
Vacuum Circuit Breakers Testing Methods
 
2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised
 
Results of 10 years after installation tests with partial discharge detection...
Results of 10 years after installation tests with partial discharge detection...Results of 10 years after installation tests with partial discharge detection...
Results of 10 years after installation tests with partial discharge detection...
 
P D Measurements On H V Joints
P D  Measurements On  H V JointsP D  Measurements On  H V Joints
P D Measurements On H V Joints
 
Getting up close and personal with rc ds Bernard Gittins
Getting up close and personal with rc ds   Bernard GittinsGetting up close and personal with rc ds   Bernard Gittins
Getting up close and personal with rc ds Bernard Gittins
 
G-62.pdf
G-62.pdfG-62.pdf
G-62.pdf
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
 
M4100
M4100M4100
M4100
 
Dialectirc tests
Dialectirc testsDialectirc tests
Dialectirc tests
 
Topological Advancement in DVR; A review
Topological Advancement in DVR; A reviewTopological Advancement in DVR; A review
Topological Advancement in DVR; A review
 
ZVS Circuit based – Cockcroft Walton High Voltage DC Generator
ZVS Circuit based – Cockcroft Walton High Voltage DC GeneratorZVS Circuit based – Cockcroft Walton High Voltage DC Generator
ZVS Circuit based – Cockcroft Walton High Voltage DC Generator
 

More from ulmedical

Strategies for meeting FDA's UDI Rule
Strategies for meeting FDA's UDI RuleStrategies for meeting FDA's UDI Rule
Strategies for meeting FDA's UDI Ruleulmedical
 
eHealth - Medical Systems Interoperability & Mobile Health
eHealth - Medical Systems Interoperability & Mobile HealtheHealth - Medical Systems Interoperability & Mobile Health
eHealth - Medical Systems Interoperability & Mobile Healthulmedical
 
UL Webinar - Updates to the Regulatory Framework in Korea and their impact to...
UL Webinar - Updates to the Regulatory Framework in Korea and their impact to...UL Webinar - Updates to the Regulatory Framework in Korea and their impact to...
UL Webinar - Updates to the Regulatory Framework in Korea and their impact to...ulmedical
 
“CFDA Registration – Market Access Before Investment” delivered by Tim Lin, T...
“CFDA Registration – Market Access Before Investment” delivered by Tim Lin, T...“CFDA Registration – Market Access Before Investment” delivered by Tim Lin, T...
“CFDA Registration – Market Access Before Investment” delivered by Tim Lin, T...ulmedical
 
UL inmetro non active devices - 2012
UL inmetro non active devices - 2012UL inmetro non active devices - 2012
UL inmetro non active devices - 2012ulmedical
 
Ivd webcast june 2012 for slide share
Ivd webcast june 2012 for slide shareIvd webcast june 2012 for slide share
Ivd webcast june 2012 for slide shareulmedical
 

More from ulmedical (6)

Strategies for meeting FDA's UDI Rule
Strategies for meeting FDA's UDI RuleStrategies for meeting FDA's UDI Rule
Strategies for meeting FDA's UDI Rule
 
eHealth - Medical Systems Interoperability & Mobile Health
eHealth - Medical Systems Interoperability & Mobile HealtheHealth - Medical Systems Interoperability & Mobile Health
eHealth - Medical Systems Interoperability & Mobile Health
 
UL Webinar - Updates to the Regulatory Framework in Korea and their impact to...
UL Webinar - Updates to the Regulatory Framework in Korea and their impact to...UL Webinar - Updates to the Regulatory Framework in Korea and their impact to...
UL Webinar - Updates to the Regulatory Framework in Korea and their impact to...
 
“CFDA Registration – Market Access Before Investment” delivered by Tim Lin, T...
“CFDA Registration – Market Access Before Investment” delivered by Tim Lin, T...“CFDA Registration – Market Access Before Investment” delivered by Tim Lin, T...
“CFDA Registration – Market Access Before Investment” delivered by Tim Lin, T...
 
UL inmetro non active devices - 2012
UL inmetro non active devices - 2012UL inmetro non active devices - 2012
UL inmetro non active devices - 2012
 
Ivd webcast june 2012 for slide share
Ivd webcast june 2012 for slide shareIvd webcast june 2012 for slide share
Ivd webcast june 2012 for slide share
 

61010 national difference for slideshare

  • 1. UL61010-1 and -2-030 U.S. National Differences UL Staff Prepared: August 2012 UL and the UL logo are trademarks of UL LLC © 2012
  • 2. Agenda National Differences for: • Risk of Electric Shock • Risk of Fire • Protection Against Hazards from Fluids • Components and Subassemblies • Measuring Circuits • Annexes Slide 2 UL and the UL logo are trademarks of UL LLC © 2012
  • 3. Permissible Limits for Accessible Parts Normal Condition (6.3.1) • Voltage Levels US National Differences (to be in IEC 61010-1 3rd Edition the North American Harmonized Standard) 33 V rms 30 V rms 46.7 V peak 42.4 V peak 70 V dc 60 V dc 3
  • 4. Permissible Limits for Accessible Parts Single Fault Condition (6.3.2) Continued IEC 61010-1 3nd Edition National Differences 55 V rms 50 V rms 78 V peak 70 V peak 140 V dc 120 V dc Note: Sub-clauses 6.3.2 A 4
  • 5. Figure 2DV - Maximum duration of short-term ACCESSIBLE voltages in SINGLE FAULT CONDITION (see 6.3.2 a)) Key A a.c. voltage level in WET LOCATIONS C d.c. voltage level in WET LOCATIONS B a.c. voltage level in dry locations D d.c. voltage level in dry locations
  • 6. National Difference – Protective Conductor Impedance 6.5.2.4DV D2 Modification by replacing the text and the conformity statement with the following: • IEC – states 0.1 Ω, for non-detachable power cord 0.2 Ω. • The impedance between the PROTECTIVE CONDUCTOR TERMINAL and each ACCESSIBLE part for which PROTECTIVE BONDING is specified shall not cause a potential drop of more than 4 V. • IEC - Conformity is checked by applying a test current for 1 min and then calculating impedance. The test current is the greater of a) 25 A a.c. r.m.s. at RATED MAINS frequency or d.c., b) a current equal to twice the RATED current of the equipment • Conformity is checked by inspection and by applying an a.c. test current for the duration specified in Table 6.5.2.4DV.1 and then measuring the voltage drop. See 4.4.4.3 for test conditions regarding the spread of fire. • . UL and the UL logo are trademarks of UL LLC © 2012 6
  • 7. National Difference – Protective Conductor Impedance Continued • The test current is twice the rating of the attachment plug cap, but not less than 40 A. • If the equipment contains overcurrent protection devices for all poles of the MAINS supply, and if the wiring on the supply side of the overcurrent protection devices cannot become connected to ACCESSIBLE conductive parts in the case of a single fault, the test current need not be more than twice the RATED current of the internal overcurrent protection devices. • If the test current exceeds 500 A, see CSA 0.4. 7
  • 8. National Difference – Table 6.5.2.4DV.1 - Duration of Protective Bonding Test Table 6.5.2.4DV.1 – Duration of protective bonding test 8 UL and the UL logo are trademarks of UL LLC © 2012
  • 9. National Difference – Protective Bonding impedance Conformity Statement 6.5.2.5DV D2 Modification: • IEC - Conformity is checked by applying a test current of twice the value of the overcurrent protection means specified in the equipment installation instructions for the building supply MAINS CIRCUIT for 1 min between the PROTECTIVE CONDUCTOR TERMINAL and each ACCESSIBLE conductive part for which PROTECTIVE BONDING is required. The voltage between them shall not exceed 10 V a.c. r.m.s. or d.c. • In the first sentence of the conformity statement, replace “1 min” with “the duration specified in Table 6.5.2.4DV.1”. • In the second sentence of the conformity statement, replace “10 V” with “4 V”. 9
  • 10. National Difference - Connection to the MAINS supply source and connections between parts of equipment • IEC - 6.10.1 MAINS supply cords The following requirements apply to non-detachable MAINS supply cords and to detachable MAINS supply cords supplied with the equipment. • Cords shall be RATED for the maximum current for the equipment and the cable used shall meet the requirements of IEC 60227 or IEC 60245. ND - 6.10.1DV.1 Delete the reference to the requirements of IEC 60227 or IEC 60245 for MAINS supply cords in the second paragraph • If a cord is likely to contact hot external parts of the equipment, it shall be made of suitably heat-resistant material. • If the cord is detachable, both the cord and the appliance inlet shall have adequate temperature RATINGS. • Conductors coloured green-and-yellow shall be used only for connection to PROTECTIVE CONDUCTOR TERMINALS. 6.10.1DV.2 Replace the fifth paragraph with the following: ND - Green covered conductors (with or without yellow stripes) shall be used only for connection to PROTECTIVE CONDUCTOR TERMINALS UL and the UL logo are trademarks of UL LLC © 2012
  • 11. National Difference - Connection to the MAINS supply source and connections between parts of equipment Detachable MAINS supply cords with MAINS connectors according to IEC 60320 shall either meet the requirements of IEC 60799, or shall be RATED at least for the current RATING of the MAINS connector fitted to the cord. ND - 6.10.1DV.3 Delete the reference to the requirements of IEC 60799 for detachable MAINS supply cords in the sixth paragraph. ND - 6.10.1DV.4 Add the following paragraphs and new note after the sixth paragraph: ND - Requirements for MAINS cords or cord sets are contained in ANSI/UL 817 and CSA C22.2 No. 21. ND - Requirements for general use receptacles, attachment plugs, and similar wiring devices are contained in ANSI/UL 498 and CSA C22.2 No. 42, CSA C22.2 No. 182.1, CSA C22.2 No. 182.2, and CSA C22.2 No. 182.3. ND - NOTE This subclause only applies to cords connected to the external fixed MAINS socket-outlet and to external interconnecting mains cords. This subclause does not apply to cords fully contained within the equipment enclosure • Figure 9 explains the terminology for MAINS supply cords. • Conformity is checked by inspection and, where necessary, by measurement. 11
  • 12. National Difference - 6.10.4DV.1 PERMANENTLY CONNECTED EQUIPMENT • Addition of a new clause • Equipment intended for permanent connection to the MAINS shall meet the requirements of Annex DVD. • Conformity is checked as specified in Annex DVD.
  • 13. National Difference – 6.11 Title Modification • 6.11 Disconnection from supply source • 6.11DV D2 Modification of the title: Add “and maintaining polarity” to the end of the subclause title. 13
  • 14. National Difference – 6.11.5DV D2 Polarity of MAINS Connections ND - 6.11.5DV D2 Addition of a new sub-clause for Polarity of Connections to the MAINS Circuit: • Any line-connected single-pole switch, any center contact of a lamp holder, and any automatic control with a marked off position shall be connected to a TERMINAL or lead intended for connection to the ungrounded conductor of the supply circuit. NOTE An “ungrounded” supply conductor is one that is not connected to protective earth at any point in the building installation. 14
  • 15. • National Difference – 9.6.1. ADV Connection of overcurrent protective devices Added the following for connections of overcurrent protective devices • 9.6.1ADV.1 A single-pole circuit breaker must be connected to the ungrounded supply conductor • 9.6.1ADV.2 A multiple-pole circuit breaker must interrupt the neutral (grounded) and ungrounded conductors simultaneously. • 9.6.1ADV.3 A single fuse must be in the ungrounded conductor. • 9.6.1ADV.4 Fuses used in both the neutral (grounded) and ungrounded supply conductors must be adjacent with same ratings and characteristics. • 9.6.1ADV.5 Screw shell of a plug fuseholder and accessible contact of an extractor type fuseholder when: • Located in the Ungrounded supply conductor: shall be connected towards the load. • Located in the Neutral conductor: the shell shall be connected towards the neutral supply line. 15
  • 16. • National Difference – 11.7.1. DV max. Pressure, referencing Annex G as normative for certain types • 11.7.1DV.1 Laboratory and Testing and Measurement equipment having both of the following characteristics shall meet the requirements of 11.7.2 and G.5: a) a product of pressure and volume greater than 200 kPa·l, b) a pressure .greater than 50 kPa. • 11.7.1DV.2 Laboratory equipment and testing and measurement equipment that do not have those characteristics shall meet the requirements of 11.7.3 and 11.7.4, as applicable. • 11.7.1DV.3 Process Control and other equipment shall meet the requirements of Annex G, as applicable 16
  • 17. • National Difference – Leakage and Rupture at High Pressure11.7.2. DV Replacing Note as follows: • Fluid-containing parts which in NORMAL USE have both of the following characteristics shall not cause a HAZARD through rupture or leakage: a) a product of pressure and volume greater than 200 kPa·l; b) a pressure greater than 50 kPa. Conformity is checked by inspection and, if a HAZARD could arise, by the described hydraulic test • NOTE National authorities may allow safety to be established by calculation, for example according to the ASME Boiler and Pressure Vessel Code. 17
  • 18. National Difference – 14.1 Components and Subassemblies North American Standards • a) applicable safety requirements of a relevant IEC standard … • b) the requirements of this standard and, where necessary for the application, any additional applicable safety requirements of the relevant IEC component standard, … • c) if there is no relevant IEC standard, the requirements of this standard; • d) applicable safety requirements of a non-IEC standard which are at least as high as those of the relevant IEC standard, provided that the component has been approved to the non- IEC standard by a recognized testing authority. ND – In all these sub-clauses ), replace “IEC” with “ANSI, CAN, CSA, IEC, ISO, or UL”. ND - . Add a new note 3: • NOTE 3: Annex DVA provides applicable safety requirements. 18
  • 19. National Difference – 14.7 Printed Wiring Boards North American Flammability Printed wiring boards shall be made of material with a flammability classification of V-1 or better of IEC 60695-11-10. ND - 14.7DV D2 Addition of the following to the end of the first paragraph: • A flammability RATING of ANSI/UL V-1 or CAN/CSA C22.2 No. 0.17 is considered equivalent to the same classification of IEC 60695-11- 10. 19
  • 20. National Difference – 14.9 Outdoor Use ND - 14.9DV D2 Add a new sub-clause to address enclosures intended for outdoor use: • Nonmetallic enclosures intended for outdoor use shall meet the UV resistance requirements of ANSI/UL 746C or of CSA C22.2 No. 0.17, or both as appropriate. NOTE ANSI/UL 746C, clause 25, requires a 1 000 hour UV/water exposure preconditioning using a xenon-arc or • alternatively a 720 hour UV/water exposure preconditioning using twin carbon arcs. CSA C22.2 No. 0.17, subclause 5.9, permits only the 1 000 hour UV/water exposure preconditioning. 20
  • 21. National Difference – 14.10 Conductive Coatings ND - 14.10DV D2 Add a new subclause to address conductive coatings, shields, and tape: • 14.10DV.1.1 The bond of a conductive (metallic) coating applied to a polymeric part shall be evaluated. • 14.10DV.1.2. a) Evaluating the bond in accordance with the requirements for “Adhesives” in ANSI/UL 746C and/or CSA C22.2 No. 0.17, or b) Evaluating the product to determine that peeling or flaking of the coating would not reduce spacings or bridge live parts so as to introduce a risk of fire or electric shock. . 21
  • 22. National Difference – 14.10 Conductive Shields, and Tape 14.10DV.2 Conductive shield or tape • 14.10DV.2.1 If peeling of the conductive shield or tape may introduce a RISK of fire or electric shock, the bond between a conductive shield or tape and any other surface shall be investigated. • 14.10DV.2.2 Conformity is checked by inspection 22
  • 23. National Difference – 14.11 Direct Plug-in Transformers North America Standards • ND - Add a new sub-clause14.11DV D2 • 14.11DV.1 Direct plug-in transformer units: • Direct plug-in transformer units are subject to additional requirements found in ANSI/UL 1310, CAN/CSA C22.2 No. 223, ANSI/UL 60950-1, or CSA C22.2 No. 60950-1, as applicable. 23
  • 24. Measuring circuit TERMINALS ND - Table 101DV DR Modify the values in Table 101 by replacing it with the following: Table 101DV - CLEARANCES and CREEPAGE DISTANCES for measuring circuit TERMINALS with HAZARDOUS LIVE conductive parts (IEC Values in brackets) Voltage on conductive parts of TERMINAL CLEARANCE and CREEPAGE DISTANCE V a.c. r.m.s. V d.c. mm 30 (33)  300 60 (70)  414 0,8 >300  600 >414  848 1,0 >600  1 000 >848  1 414 2,6 NOTE Values are determined by calculation for REINFORCED INSULATION. Transients are not taken into account. Conformity is checked by inspection and measurement.
  • 25. 101.3 Protection Against Mismatches of Inputs and Ranges ND - 101.3.3DV D2 Addition of the following test: 101.3.3DV.1 If the function or range controls have any effect on the electrical characteristics of the input circuit, these controls shall be changed to all possible settings while the input TERMINALS are connected to the maximum RATED source.
  • 26. Test leads for the tests of 101.3.2 and 101.3.3 101.3.4 …. If the manufacturer-supplied test leads are permanently connected to the equipment, then the attached test leads supplied by the manufacturer shall be used without modification. ND - 101.3.4DV D2 Modification of 101.3.4 by deleting the following paragraph "If the manufacturer-supplied test leads are permanently connected to the equipment, then the attached test leads supplied by the manufacturer shall be used without modification." and replacing it with the following: 101.3.4DV.1 The applicable tests of 101.3.2 and 101.3.3 shall be performed with the test leads specified above and shall be repeated with any test leads supplied with the equipment by the manufacturer.
  • 27. Annex DVA (informative) CSA, UL, IEC component standards. ND - DVA D2 Addition of a new annex DVA as follows: • The following is a matrix that provides a cross-reference between CSA, UL, and IEC standards for components. • This cross-reference is not meant to imply that the standards are equivalent. The CSA, UL, and IEC standards listed are used for evaluation of components and features of products covered by this standard. • Components need only comply with the applicable component standard acceptable in the country where the product is to be used. • These standards are considered to refer to the latest edition and all revisions published to that edition.
  • 30. Annex DVB (informative) ND - DVB D2 Addition of a new annex DVB as follows • A table indicating identifying all clauses that have a National Difference
  • 31. Annex DVC - (informative) - UV radiation limits: Guidelines from the American Conference of Governmental Industrial Hygienists (ACGIH) • DVC D2 Addition of a new annex DVC for UV radiation limits • DVC.1.1 These threshold limit values (TLVs) refer to ultraviolet (UV) radiation in the spectral region between 180 and 400 nm and represent conditions under which it is believed that nearly all workers may be repeatedly exposed without adverse health effects. • DVC.1.2 These values for exposure of the eye or the skin apply to UV radiation from arc, gas, and vapor discharges, fluorescent and incandescent sources, and solar radiation, but they do not apply to UV lasers (see the TLV for lasers). These values do not apply to UV radiation exposure of photosensitive individuals or of individuals concomitantly exposed to photosensitizing agents. These exposures to the eye do not apply to aphakics. (See light and near-infrared TLV for radiation.) These values should be used as guides in the control of exposure to continuous sources where the duration of exposure is not less than 0,1 s. Likewise, these values should not be regarded as a fine line between safe and dangerous levels.
  • 32. Annex DVC - (informative) - UV radiation limits:Guidelines from the American Conference of Governmental Industrial Hygienists (ACGIH • DVC.2 Recommended values • DVC.2.1 The TLVs for occupational exposure to UV radiation incident upon skin or eye where irradiance values are known and exposure time is controlled are as follows: • a) UV-A (315 to 400 nm) radiation to the unprotected eye: • 1) For exposure times less than 1 000 seconds, the total energy should not exceed 1 J/cm2 (1 000 mJ/cm2). • 2) For exposure times greater than 1 000 seconds, the average power level should not exceed 1 mW/cm2; and no 1 000 second time period should present a total energy that exceeds 1 J/cm2 (1 000 mJ/cm2). • b) For monochromatic sources, the TLV for exposure to the unprotected skin or eye is shown in Table DVC.2.1.1 (also represented in Figure DVC.2.1.1) and should not be exceeded within an 8-hour period. • c) For broad-spectrum or multi-peak sources, the TLV for exposure of the unprotected skin or eye should be calculated based on an effective weighting formula: • Eeff = S (El • S l • Dl )
  • 33. Annex DVD (normative) permanent connection to MAINS ND - DVD D2 Addition of a new Annex DVD as follows: • DVD.1 General • DVD.1.1 Equipment intended for permanent connection to the mains shall have provision for connection of a wiring system in accordance with ANSI/NFPA 70, NEC, with CSA C22.1, CEC, Part I, or with both as appropriate, and shall meet the requirements of DVD.2 to DVD.3, as applicable. • DVD.1.2 Conformity is checked by inspection, and as specified in DVD.2 to DVD.3.
  • 34. Annex DVD (normative) permanent connection to MAINS (Cont’d) Topics Are: DVD.2 Wiring TERMINALS and leads e.g. • DVD.2.1.1 PERMANENTLY CONNECTED EQUIPMENT shall be provided with TERMINALS or leads for the connection of conductors having an ampacity that, in accordance with the National Electrical Code and/or the Canadian Electrical Code, Part I, is acceptable for the equipment. DVD.3 ENCLOSURE requirements for conduit entry e.g • DVD.3.1 An ENCLOSURE shall not pull apart or sustain damage such as cracking and breaking, and knockouts shall remain in place when subjected to the pulling, torque, and bending that is likely to occur. DVD.4 Conduit ENCLOSURE entry tests e.g. • DVD.4.1 Conduit pull-out test • DVD.4.2 Conduit torque test • DVD.4.3 Bending • DVD.4.4 Knockouts
  • 35. Summary National Differences for: • Risk of Electric Shock • Risk of Fire • Protection Against Hazards from Fluids • Components and Subassemblies • Measuring Circuits • Annexes Slide 35
  • 36. Thank You Visit: www.ul.com/61010blog to download a comparison between IEC 61010 2nd and 3rd edition. Contact us at: Medical.Inquiry@ul.com