19. The MVA loading should not exceed the generator rating.
This limit is determined by the armature of the stator
heating by the armature current.
The MW loading should not exceed the rating of the prime
mover.
The field current should not be allowed to exceed a
specified value determined by the heating of the field.
For steady state or stable operation, the load angle δ must be
less than 90 degrees. The theoretical stability limit
of the stable condition occurs when δ = 90⁰.
GENERATOR CAPABILITY DIAGRAM
19
21. GENERATOR CAPABILITY DIAGRAM
Armature current limit
Field current limit
Prime Mover Limit
End region heating limit
(1) Armature Current Limit/ Stator Copper Loss (stator heating): The maximum
allowable heating of the stator sets a maximum phase current IA for the machine. It’s
equivalent tomax apparent power for the machine. (Power factor is irrelevant).
PSCL = 3 IA.RS
(1) Field Current Limit/ Rotor Copper Loss (rotor heating): The maximum allowable heating
2
of the rotor sets a maximum field current IF for the machine. It’s equivalent to set a
maximum EA for the machine. PRCL = IF RF
(3)Prime-mover’s Power Limit: The active power output is limited by the prime mover
2
capability to a value within the MVA rating. P =|Esinδ|
The limit is related to the mechanical input and the ability of the generator to
electromagnetically create a torque equal and opposite to the driving mechanical torque.
DEFINES THE OPERATING ZONE OF
A SYNCHRONOUS GENERATOR IN
A P-Q PLANE
21
22. END REGION HEATING LIMIT
(4) The localized heating in the end region of the armature imposes
a third limit on the operation of a synchronous machine.
This limit affects
the capability of
the machine in the
under excited
condition.
22
23. • At a given excitation, if mechanical torque increases, rotor
accelerates, increasing δ and electromagnetic torque.
• This negative feedback continues until electromagnetic and
mechanical torques balance.
• However, if generator is operating with δ close to 90° when rotor
speeds up, δ increases past 90°, electromagnetic torque falls and
positive feedback occurs, causing rotor to accelerate further,
pull out of synchronism and result in zero output power and
possibly catastrophic failure. The static stability limit is set at
δ=90°.
GENERATOR CAPABILITY DIAGRAM
Power = 3 Vph I Cos φ = 3 Vph E Sin δ/ X.
The power or torque can be thought of as
cross product of two electromagnetic
fields or a function of the sine of angle
between V and E.
23
28. SYN. GENERATOR RATING
In any balanced design, the thermal limits for the
field and armature intersect at a point, which
represents the machine
power factor rating.
Capability Diagram gives
nameplate MV
A and
information about full
load rotor (excitation current) & maximum rotor
angle during steady state P
.F.
28