Type CDG 11
Overcurrent and Earthfault Relay
for AC series Tripping
Type CDG 11
Overcurrent and Earthfault Relay
for AC Series Tripping
CDG 11 relay
withdrawn from case
Features
• Identical time/current
characteristics on all taps.
• High torque, ensuring consistent
timing even under adverse
conditions.
• No overshoot.
• Simple construction, easily
accessible.
• Dust tight drawout case and
tropicalised finish.
Application
Selective phase and earthfault
protection in time graded system for
AC machines, transformers, feeders
etc. These relays are used where dc
tripping supply is not available and
trip the circuit breakers directly using
the current from the current
transformers.
General description
The CDG series trip relay is a slightly
modified version of type CDG 11
relay which incorporates a secondary
winding on the electromagnet of the
CDG relay and an instantaneous unit.
When the disc unit operates and
closes its contacts, the instantaneous
element connected across the
secondary winding on the
electromagnet operates, and opens
its normally closed heavy duty
contacts to allow the fault current to
flow through the circuit breaker trip
coil. The relay will safely control ac
trip coil currents upto 150 amps.
at 150 volts. When the trip current/
voltage exceeds these values, an
external series resistor with or
without a shunt choke is required.
In all other respects, the ac series
tripping relay is identical to the
plain inverse time current relay
type CDG 11.
Technical data
The operating coil can be supplied
suitable for operation from
5.0 amps. or 1.0 amp. CT
secondaries and the following
standard setting ranges are
available.
50 - 200% adjustable in seven
equal steps of 25%
20 - 80% adjustable in seven equal
steps of 10%
10 - 40% adjustable in seven equal
steps of 5%.
Starting current
103 - 105% of current setting at
TMS 1.0.
Closing current
Not more than 130% current setting.
Resetting current
The disc will completely reset at 90%
or more of the current setting.
Time settings
Operating time
0-3.0 seconds or 0-1.3 seconds at
10 times the current setting.
Time/current characteristics are
identical to the IDMT characteristics
or CDG 11.
Resetting time
With the time multiplier set at 1.0,
the resetting time is 4 seconds and 9
seconds approximately for relays
having an operating time of 1.3
seconds and 3.0 seconds
respectively at ten times the current
setting.
Burdens
2VA at lowest tap
3.5VA at highest tap
Thermal rating
The maximum continuous current
ratings for 60°C rise in coil
temperature are as follows:
Frequency error
A frequency variation of 2 Hz. gives
timing errors of less than 8%.
The time grading of a protective
system would be unaffected by this
small error since all relays would
be similarly affected.
Temperature error
For an overload equal to ten times
the current setting, the percentage
timing errors at ambient
temperatures of +45°C and –5°C
are respectively
3.0 seconds relay : –3% and +4%
1.3 seconds relay : –4% and +4%
Instantaneous unit and
operation indicator
The instantaneous unit of the relay is
usually fitted with two pairs of hand
reset heavy duty ‘break’ contacts for
connecting externally across the trip
coils of the circuit breaker and
2 pairs of hand reset ‘make’
contacts for alarm indication
purpose. The instantaneous unit is
fitted with an operation indicator
which is hand reset by means of a
push-rod protruding through the
relay case.
Contact ratings
The two pairs of hand reset heavy
duty contacts in parallel can break a
maximum current of 150 amps. at
150 volts ac. The two additional
pairs of hand reset standard ‘make’
contacts when provided for alarm
purposes can make and carry for
0.5 second 7500VA with maximum
of 30 amps. and 660 volts, ac or dc.
Insulation
The relay will withstand 2.5 KV ac
r.m.s. 50Hz for one second between
all circuits and the case and
between all circuits not intended to
be connected together. It will also
withstand 1.25 KV ac r.m.s. 50Hz
for one second between mating
contacts in open position.
The relay will withstand 20 times
the maximum current setting for
3 seconds on any setting.
Accuracy
The relay conforms to error class
index E 7.5 as per BS 142-1966 and
7.5 as per IS 3231-1965, at ten
times reference current setting.
External and internal
circuit connections
Typical external and internal
connections for type CDG 31 three
phase overcurrent, alternatively
combined overcurrent and earthfault
protection, are shown in Figure 1.
Case and finish
Relays are supplied in drawout
cases suitable for flush or projection
mounting and are finished eggshell
black and tropicalised. The drawout
feature considerably simplifies
maintenance and permits testing to
be carried out easily and quickly.
The case is fitted with switches which
short circuit the associated current
transformers on withdrawal of the
relay unit from the case. A filter
breather is fitted which equalises
pressure inside and outside the case
without admitting dust.
Operating
coil tap
1
2
3
4
5
6
7
4.5
3.7
3.2
2.7
2.6
2.4
2.2
Times current
setting
Dimensions and weights
Maximum overall dimensions Approximate
Relay Case size Height Width Depth* gross weight
mm mm mm Kg.
CDG 11 1D Vert. 233 170 203 6.0
series trip
3D Hor. 233 454 203 15.5
3D Vert. 524 170 203 15.0
* Add 76 mm for maximum length of terminal studs, alternatively,
29 mm for terminal screws.
The approximate gross weights given above are inclusive of cartons,
mounting appendages and terminal details.
The relays comply fully with the requirements of IS 3231-1965 and are
suitable for use in normal tropical environments.
CDG 31
series trip
Single pole relays are mounted in
size 1D vertical case and triple pole
relays are mounted in size 3D
horizontal or vertical case, as
required.
Certified dimensional drawings of
case outlines, panel cut-outs and
mounting details are available on
request.
Information required with
order
1. Type of relay (CDG 11 or 31)
and system frequency.
2. Current setting range.
3. Characteristic (0 - 3.0 sec. or
0 - 1.3 sec. at 10 times current
settings).
4. Operation indicator inscription,
if required.
5. Case size.
6. Type of mounting - flush or
projection.
7. Current transformer ratio and
secondary winding resistance.
8. The knee-point voltage and the
maximum voltage obtainable
from the CT.
9. One way secondary lead
resistance from CT to relay.
10. Nominal current rating of the
trip coils.
11. The trip coil impedance with
`plunger down’ and with
`plunger up’ at the maximum
and minimum tripping currents.
12. The operating voltage and the
fault level of the primary circuit.
Figure 1:
Typical external and internal connections for
CDG 31 ac series tripping relay
PR:011:0799:A Printed in India.
ALSTOM Limited Pallavaram Works: 19/1, GST Road, Pallavaram, Chennai-600 043. India.
Tel: 91-044-2368621 Fax: 91-044-2367276 Email: plw.applications@alstom.sprintrpg.eml.vsnl.net.in.
© 1998 ALSTOM Limited
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should
only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
ALSTOM Limited cannot be held responsible for any reliance on any decision taken on its contents without specific advice.

More Related Content

Similar to CDG_11.PDF

Implementationof Single Phasing, Over Voltage, Under Voltage, Protection of T...
Implementationof Single Phasing, Over Voltage, Under Voltage, Protection of T...Implementationof Single Phasing, Over Voltage, Under Voltage, Protection of T...
Implementationof Single Phasing, Over Voltage, Under Voltage, Protection of T...IJERA Editor
 
Implementationof Single Phasing, Over Voltage, Under Voltage, Protection of T...
Implementationof Single Phasing, Over Voltage, Under Voltage, Protection of T...Implementationof Single Phasing, Over Voltage, Under Voltage, Protection of T...
Implementationof Single Phasing, Over Voltage, Under Voltage, Protection of T...IJERA Editor
 
Vignettes in Grounding
Vignettes in GroundingVignettes in Grounding
Vignettes in Groundingmichaeljmack
 
Equipments in switchyard and its protection
Equipments in switchyard and its protectionEquipments in switchyard and its protection
Equipments in switchyard and its protectionJayashree Behera
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & MaintenanceHimansu Pradhan
 
Psentation.pdf351685461065165156156156165156
Psentation.pdf351685461065165156156156165156Psentation.pdf351685461065165156156156165156
Psentation.pdf351685461065165156156156165156vikknaguem
 
Generator grounding
Generator groundingGenerator grounding
Generator groundingmichaeljmack
 
Advanced motion controls s30a40ac
Advanced motion controls s30a40acAdvanced motion controls s30a40ac
Advanced motion controls s30a40acElectromate
 
10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
10 - Ac Power Regulators & Control Power Transformers - Fuji Electric10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
10 - Ac Power Regulators & Control Power Transformers - Fuji ElectricCTY TNHH HẠO PHƯƠNG
 
Smart under and over voltage protection system for
Smart under and over voltage protection system forSmart under and over voltage protection system for
Smart under and over voltage protection system forShuvadip das
 
ct pt testing...........................................
ct pt testing...........................................ct pt testing...........................................
ct pt testing...........................................hiiarindam
 
Transformerprotectionrelaycalculations.doc
Transformerprotectionrelaycalculations.docTransformerprotectionrelaycalculations.doc
Transformerprotectionrelaycalculations.docMdAbdullahAlMamun258178
 
Ds012846
Ds012846Ds012846
Ds012846____
 
Grid synchronisation
Grid synchronisationGrid synchronisation
Grid synchronisationmanogna gwen
 
the silicon controled rectifier with diagram.pptx
the silicon controled rectifier with diagram.pptxthe silicon controled rectifier with diagram.pptx
the silicon controled rectifier with diagram.pptxyogeshkute7
 
XLSEMI XL140 2A 380KHz 18V Buck DC to DC Converter
XLSEMI XL140 2A 380KHz 18V Buck DC to DC ConverterXLSEMI XL140 2A 380KHz 18V Buck DC to DC Converter
XLSEMI XL140 2A 380KHz 18V Buck DC to DC Converterdegarden
 

Similar to CDG_11.PDF (20)

Implementationof Single Phasing, Over Voltage, Under Voltage, Protection of T...
Implementationof Single Phasing, Over Voltage, Under Voltage, Protection of T...Implementationof Single Phasing, Over Voltage, Under Voltage, Protection of T...
Implementationof Single Phasing, Over Voltage, Under Voltage, Protection of T...
 
Implementationof Single Phasing, Over Voltage, Under Voltage, Protection of T...
Implementationof Single Phasing, Over Voltage, Under Voltage, Protection of T...Implementationof Single Phasing, Over Voltage, Under Voltage, Protection of T...
Implementationof Single Phasing, Over Voltage, Under Voltage, Protection of T...
 
Vignettes in Grounding
Vignettes in GroundingVignettes in Grounding
Vignettes in Grounding
 
Equipments in switchyard and its protection
Equipments in switchyard and its protectionEquipments in switchyard and its protection
Equipments in switchyard and its protection
 
Two Quadrant chopper
Two Quadrant chopperTwo Quadrant chopper
Two Quadrant chopper
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
PE1-SCRs.pdf
PE1-SCRs.pdfPE1-SCRs.pdf
PE1-SCRs.pdf
 
Bender rc48 c
Bender rc48 cBender rc48 c
Bender rc48 c
 
Thyristors
ThyristorsThyristors
Thyristors
 
Psentation.pdf351685461065165156156156165156
Psentation.pdf351685461065165156156156165156Psentation.pdf351685461065165156156156165156
Psentation.pdf351685461065165156156156165156
 
Generator grounding
Generator groundingGenerator grounding
Generator grounding
 
Advanced motion controls s30a40ac
Advanced motion controls s30a40acAdvanced motion controls s30a40ac
Advanced motion controls s30a40ac
 
10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
10 - Ac Power Regulators & Control Power Transformers - Fuji Electric10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
 
Smart under and over voltage protection system for
Smart under and over voltage protection system forSmart under and over voltage protection system for
Smart under and over voltage protection system for
 
ct pt testing...........................................
ct pt testing...........................................ct pt testing...........................................
ct pt testing...........................................
 
Transformerprotectionrelaycalculations.doc
Transformerprotectionrelaycalculations.docTransformerprotectionrelaycalculations.doc
Transformerprotectionrelaycalculations.doc
 
Ds012846
Ds012846Ds012846
Ds012846
 
Grid synchronisation
Grid synchronisationGrid synchronisation
Grid synchronisation
 
the silicon controled rectifier with diagram.pptx
the silicon controled rectifier with diagram.pptxthe silicon controled rectifier with diagram.pptx
the silicon controled rectifier with diagram.pptx
 
XLSEMI XL140 2A 380KHz 18V Buck DC to DC Converter
XLSEMI XL140 2A 380KHz 18V Buck DC to DC ConverterXLSEMI XL140 2A 380KHz 18V Buck DC to DC Converter
XLSEMI XL140 2A 380KHz 18V Buck DC to DC Converter
 

Recently uploaded

CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2RajaP95
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxvipinkmenon1
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 

Recently uploaded (20)

CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 

CDG_11.PDF

  • 1. Type CDG 11 Overcurrent and Earthfault Relay for AC series Tripping
  • 2. Type CDG 11 Overcurrent and Earthfault Relay for AC Series Tripping CDG 11 relay withdrawn from case Features • Identical time/current characteristics on all taps. • High torque, ensuring consistent timing even under adverse conditions. • No overshoot. • Simple construction, easily accessible. • Dust tight drawout case and tropicalised finish. Application Selective phase and earthfault protection in time graded system for AC machines, transformers, feeders etc. These relays are used where dc tripping supply is not available and trip the circuit breakers directly using the current from the current transformers. General description The CDG series trip relay is a slightly modified version of type CDG 11 relay which incorporates a secondary winding on the electromagnet of the CDG relay and an instantaneous unit. When the disc unit operates and closes its contacts, the instantaneous element connected across the secondary winding on the electromagnet operates, and opens its normally closed heavy duty contacts to allow the fault current to flow through the circuit breaker trip coil. The relay will safely control ac trip coil currents upto 150 amps. at 150 volts. When the trip current/ voltage exceeds these values, an external series resistor with or without a shunt choke is required. In all other respects, the ac series tripping relay is identical to the plain inverse time current relay type CDG 11. Technical data The operating coil can be supplied suitable for operation from 5.0 amps. or 1.0 amp. CT secondaries and the following standard setting ranges are available. 50 - 200% adjustable in seven equal steps of 25% 20 - 80% adjustable in seven equal steps of 10% 10 - 40% adjustable in seven equal steps of 5%. Starting current 103 - 105% of current setting at TMS 1.0. Closing current Not more than 130% current setting. Resetting current The disc will completely reset at 90% or more of the current setting.
  • 3. Time settings Operating time 0-3.0 seconds or 0-1.3 seconds at 10 times the current setting. Time/current characteristics are identical to the IDMT characteristics or CDG 11. Resetting time With the time multiplier set at 1.0, the resetting time is 4 seconds and 9 seconds approximately for relays having an operating time of 1.3 seconds and 3.0 seconds respectively at ten times the current setting. Burdens 2VA at lowest tap 3.5VA at highest tap Thermal rating The maximum continuous current ratings for 60°C rise in coil temperature are as follows: Frequency error A frequency variation of 2 Hz. gives timing errors of less than 8%. The time grading of a protective system would be unaffected by this small error since all relays would be similarly affected. Temperature error For an overload equal to ten times the current setting, the percentage timing errors at ambient temperatures of +45°C and –5°C are respectively 3.0 seconds relay : –3% and +4% 1.3 seconds relay : –4% and +4% Instantaneous unit and operation indicator The instantaneous unit of the relay is usually fitted with two pairs of hand reset heavy duty ‘break’ contacts for connecting externally across the trip coils of the circuit breaker and 2 pairs of hand reset ‘make’ contacts for alarm indication purpose. The instantaneous unit is fitted with an operation indicator which is hand reset by means of a push-rod protruding through the relay case. Contact ratings The two pairs of hand reset heavy duty contacts in parallel can break a maximum current of 150 amps. at 150 volts ac. The two additional pairs of hand reset standard ‘make’ contacts when provided for alarm purposes can make and carry for 0.5 second 7500VA with maximum of 30 amps. and 660 volts, ac or dc. Insulation The relay will withstand 2.5 KV ac r.m.s. 50Hz for one second between all circuits and the case and between all circuits not intended to be connected together. It will also withstand 1.25 KV ac r.m.s. 50Hz for one second between mating contacts in open position. The relay will withstand 20 times the maximum current setting for 3 seconds on any setting. Accuracy The relay conforms to error class index E 7.5 as per BS 142-1966 and 7.5 as per IS 3231-1965, at ten times reference current setting. External and internal circuit connections Typical external and internal connections for type CDG 31 three phase overcurrent, alternatively combined overcurrent and earthfault protection, are shown in Figure 1. Case and finish Relays are supplied in drawout cases suitable for flush or projection mounting and are finished eggshell black and tropicalised. The drawout feature considerably simplifies maintenance and permits testing to be carried out easily and quickly. The case is fitted with switches which short circuit the associated current transformers on withdrawal of the relay unit from the case. A filter breather is fitted which equalises pressure inside and outside the case without admitting dust. Operating coil tap 1 2 3 4 5 6 7 4.5 3.7 3.2 2.7 2.6 2.4 2.2 Times current setting
  • 4. Dimensions and weights Maximum overall dimensions Approximate Relay Case size Height Width Depth* gross weight mm mm mm Kg. CDG 11 1D Vert. 233 170 203 6.0 series trip 3D Hor. 233 454 203 15.5 3D Vert. 524 170 203 15.0 * Add 76 mm for maximum length of terminal studs, alternatively, 29 mm for terminal screws. The approximate gross weights given above are inclusive of cartons, mounting appendages and terminal details. The relays comply fully with the requirements of IS 3231-1965 and are suitable for use in normal tropical environments. CDG 31 series trip Single pole relays are mounted in size 1D vertical case and triple pole relays are mounted in size 3D horizontal or vertical case, as required. Certified dimensional drawings of case outlines, panel cut-outs and mounting details are available on request. Information required with order 1. Type of relay (CDG 11 or 31) and system frequency. 2. Current setting range. 3. Characteristic (0 - 3.0 sec. or 0 - 1.3 sec. at 10 times current settings). 4. Operation indicator inscription, if required. 5. Case size. 6. Type of mounting - flush or projection. 7. Current transformer ratio and secondary winding resistance. 8. The knee-point voltage and the maximum voltage obtainable from the CT. 9. One way secondary lead resistance from CT to relay. 10. Nominal current rating of the trip coils. 11. The trip coil impedance with `plunger down’ and with `plunger up’ at the maximum and minimum tripping currents. 12. The operating voltage and the fault level of the primary circuit.
  • 5. Figure 1: Typical external and internal connections for CDG 31 ac series tripping relay
  • 6. PR:011:0799:A Printed in India. ALSTOM Limited Pallavaram Works: 19/1, GST Road, Pallavaram, Chennai-600 043. India. Tel: 91-044-2368621 Fax: 91-044-2367276 Email: plw.applications@alstom.sprintrpg.eml.vsnl.net.in. © 1998 ALSTOM Limited Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it. ALSTOM Limited cannot be held responsible for any reliance on any decision taken on its contents without specific advice.