SlideShare a Scribd company logo
1 of 99
UNIT-02
FUSE AND CIRCUIT BREAKERS
CO-02- Understand the construction and working of
Fuse and circuit breakers
Meaning of Switchgear
The apparatus used for switching, controlling
and protecting the electrical circuits and
equipment is known as switchgear
Essential features of Switchgear
(i) Complete reliability : When fault occurs on
any part of the power system, the switchgear
must operate to isolate the faulty section
from the remainder circuit.
(ii)Absolutely certain discrimination : When
fault occurs on any section of the power
system, the switchgear must be able to
discriminate between the faulty section and
the healthy section. It should isolate the
faulty section from the system without
affecting the healthy section. This will ensure
continuity of supply.
(iii) Quick operation: When fault occurs on any part
of the power system, the switchgear must operate
quickly so that power system equipment .
(iv) Provision for manual control : A switchgear must
have provision for manual control. In case the
electrical (or electronics) control fails, the
necessary operation can be carried out through
manual control.
(v) Provision for instruments : There must be
provision for instruments which may be required.
These may be in the form of ammeter or voltmeter
on the unit itself or the necessary current and
voltage transformers for connecting to the main
switchboard or a separate instrument panel.
Switchgear Equipment
Switchgear covers a wide range of equipment concerned with
switching and interrupting currents under both normal and
abnormal conditions. It includes switches, fuses, circuit breakers,
relays and other equipment.
• Some devices is given below.
1. Switches
(i) Air switches
(ii) Isolator or disconnecting switch.
(iii) Oil switches
2. Fuses.
3. Circuit breakers.
4. Relays.
I. Air-break switch : It is an air switch and is
designed to open a circuit under load. In
order to quench the arc that occurs on
opening such a switch, special arcing horns
are provided.
II. Isolator or disconnecting switch : It is
essentially a knife switch and is designed to
open a circuit under no load.
III. Oil switches : The contacts of such switches
are opened under oil, usually transformer oil.
2. Fuses
A fuse is a short piece of wire or thin strip
which melts when excessive current flows
through it for sufficient time. It is inserted in
series with the circuit to be protected.
When a short circuit or overload occurs, the
current through the fuse element increases
beyond its rated capacity. This raises the
temperature and the fuse element melts (or
blows out), disconnecting the circuit protected
by it.
3. Circuit Breakers
A circuit breaker is an equipment which can open or
close a circuit under all conditions viz. no load, full
load and fault conditions. It is so designed that it
can be operated manually (or by remote control)
under normal conditions and automatically under
fault conditions. For the latter operation, a relay
circuit is used with a circuit breaker.
4. Relays
A relay is a device which detects the fault and
supplies information to the breaker for circuit
interruption.
When a fault occurs the relay contacts are closed
and the trip coil of the circuit breaker is energised to
open the contacts of the circuit breaker.
Differences between Indoor type and Outdoor
type Switchgear
(i) Indoor type.
• For voltages below 66 kV, switchgear is
generally installed indoor because of
economic considerations.
• The indoor switchgear is generally of metal-
clad type. In this type of construction, all
live parts are completely enclosed in an
earthed metal casing.
• The primary object of this practice is the
definite localization and restriction of any
fault to its place of origin.
(ii) Outdoor type.
• For voltages beyond 66 kV, switchgear
equipment is installed outdoor.
• It is because for such voltages, the clearances
between conductors and the space required
for switches, circuit breakers, transformers
and others equipment become so great that it
is not economical to install all such equipment
indoor.
• The circuit breakers , isolators, transformers
and bus-bars occupy considerable space on
account of large electrical clearance
associated with high voltages.
Fuses
A fuse is a short piece of metal,
inserted in the circuit, which melts
when excessive current flows through
it and thus breaks the circuit.
Desirable Characteristics of Fuse elements
The function of a fuse is to carry the
normal current without overheating but
when the current exceeds its normal
value, it rapidly heats up to melting point
and disconnects the circuit protected by
it. In order that it may perform this
function satisfactorily.
Desirable characteristics
(i) low melting point e.g., tin, lead.
(ii) high conductivity e.g., silver, copper.
(iii) free from deterioration due to oxidation e.g., silver.
(iv) low cost e.g., lead, tin, copper.
Types of Fuses
(1) Low voltages fuses
(i) Semi-enclosed rewireable fuse
(ii) High rupturing capacity (H.R.C.) cartridge fuse.
(iii) H.R.C. fuse with tripping device.
(2) High voltage fuses
(i) Cartridge type
(ii) Liquid type.
(iii) Metal clad fuses.
Semi-enclosed rewireable fuse
or Kit-Kat Fuses High rupturing capacity (H.R.C.)
H.R.C. fuse with tripping device.
Cartridge type fuse for LV Cartridge type fuse for HV
Liquid type.
Metal clad fuses
Fuse Element Materials
• The most commonly used materials for fuse
element are lead, tin, copper, zinc and silver.
• For small currents up to 10 A, tin or an alloy of
lead and tin (lead 37%, tin 63%) is used for
making the fuse element.
• For larger currents, copper or silver is employed.
It is a usual practice to tin the copper to protect it
from oxidation.
• Zinc (in strip form only) is good if a fuse with
considerable time-lag is required i.e., one which
does not melt very quickly with a small overload.
The present trend is to use silver despite its high cost due to the following
reasons :
(i) It is comparatively free from oxidation.
(ii) It does not deteriorate when used in dry air.
(iii) The coefficient of expansion of silver is so small that no critical fatigue
occurs. Therefore, the fuse element can carry the rated current continuously
for a long time.
(iv) The conductivity of silver is very high. Therefore, for a given rating of fuse
element, the mass of silver metal required is smaller than that of other
materials. This minimizes the problem of clearing the mass of vapourised
material set free on fusion and thus permits fast operating speed.
(v) Due to comparatively low specific heat, silver fusible elements can be raised
from normal temperature to vapourisation quicker than other fusible
elements. Moreover, the resistance of silver increases abruptly as the melting
temperature is reached, thus making the transition from melting to
vapourisation almost instantaneous. Consequently, operation becomes very
much faster at higher currents.
(vi) Silver vapourises at a temperature much lower than the one at which its
vapour will readily ionize. Therefore, when an arc is formed through the
vapourised portion of the element, the arc path has high resistance. As a
result, short-circuit current is quickly interrupted.
Important Terms of Fuse
(i) Current rating of fuse element.
It is the current which the fuse element can normally
carry without overheating or melting.
It depends upon the temperature rise of the contacts
of the fuse holder, fuse material and the surroundings
of the fuse.
(ii) Fusing current.
It is the minimum current at which the fuse element
melts and thus disconnects the circuit protected by it.
Obviously, its value will be more than the current
rating of the fuse element.
iii) Fusing factor.
It is the ratio of minimum fusing current to the
current rating of the fuse element i.e.
(iv) Prospective Current
The r.m.s.value of the first loop of fault current
is known as prospective current.
Therefore, prospective current can be
defined as under: It is the r.m.s. value of the
first loop of the fault current obtained if the
fuse is replaced by an ordinary conductor of
negligible resistance.
(v) Cut-off current.
It is the maximum value of fault current actually
reached before the fuse melts.
(vi) Pre-arcing time.
It is the time between the commencement of fault
and the instant when cut off occurs.
When a fault occurs, the fault current rises rapidly
and generates heat in the fuse element. As the fault
current reaches the cut off value, the fuse element
melts and an arc in initiated. The time from the start
of the fault to the instant the arc is initiated is
known as pre-arcing time. The pre-arcing time is
generally small : a typical value being 0·001second
(vii) Arcing time.
This is the time between the end of pre-arcing time and
the instant when the arc is extinguished.
(viii) Total operating time.
It is the sum of pre-arcing and arcing times.
It may be noted that operating time of a fuse is generally quite low (say 0·002
sec.) as compared to a circuit breaker (say 0·2 sec or so). This is an added
advantage of a fuse over a circuit breaker. A fuse in series with a circuit breaker
of low-breaking capacity is a useful and economical arrangement to provide
adequate short-circuit protection. It is because the fuse will blow under fault
conditions before the circuit breaker has the time to operate.
(ix) Breaking capacity.
It is the r.m.s. value of a.c. component of maximum
prospective current that a fuse can deal with at rated
service voltage.
HRC fuse
Construction of HRC fuse:
HRC fuse mainly consists of heat resisting
ceramic body. The current carrying element is
compactly surrounded by the filling powder.
Filling material acts as an arc quenching and
cooling medium when the fuse element blows off
due to excessive heat generated under abnormal
conditions.
Working:
Under normal conditions, the fuse element is at
a temperature below its melting point.
Therefore, it carries the normal current without
overheating.
When a fault occurs, the current increases and
the heat produced is sufficient to melt these
elements. Fuse element melts before the fault
current reaches its first peak value. Vaporized
metal /fuse element chemically reacts with
filling powder and results in the formation of
high resistance substance that helps in
quenching the arc.
Advantages / Merits
1. When compared to other circuit interrupters of same capacity
HRC fuses are the cheaper one.
2. Simple and easy to install.
3. No maintenance required.
4. High breaking capacity.
5. They are consistent in performance.
6. Their inverse time characteristic makes them much suited for
overload protection.
7. They are capable of clearing high as well as low currents.
8. Quick operation.
Disadvantages / Demerits
1. These fuses once blown out cannot be reused.
2. Heat produced by the arc may affect the associated switches.
3. Causes over heating of adjacent contacts.
4. The current-time characteristic of a fuse cannot always be
correlated with that of the protective device.
Application of HRC Fuses:
1. Protection of radial lines.
2. Transformer protection.
3. It is also used of capacitor protection.
4. It is also provide protection of underground
distribution system.
5. It is used in meter board in residential
application.
Arc formation process
• When a short-circuit occurs, a heavy current flows through the contacts of the
circuit breaker before they are opened by the protective system.
• At the instant when the contacts begin to separate the contact area decreases
rapidly and large fault current causes increased current density and hence rise in
temperature.
• The heat produced in the medium between contacts (usually the medium is oil
or air) is sufficient to ionise the air or vapourise and ionise the oil. The ionised air
or vapour ,acts as conductor and an arc is struck between the contacts.
• The potential difference between the contacts is quite small and is just sufficient
to maintain the arc. The arc provides a low resistance path and consequently the
current in the circuit remains uninterrupted so long as the arc persists.
During the arcing period, the current flowing
between the contacts depends upon the arc
resistance. The greater the arc resistance, the smaller
the current that flows between the contacts.
The arc resistance depends upon the following factors:
Degree of ionization - the arc resistance increases with
the decrease in the number of ionised particles
between the contacts.
Length of the arc - the arc resistance increases with the
length of the arc i.e. separation of contacts.
Cross section of arc - the arc resistance increase with
the decrease in the area of cross section of the arc.
Methods of arc extinction (HT & LT method)
There are two methods of extinguishing the arc
in circuit breakers.
1. High resistance method
2. Low resistance or current zero method.
1. High Resistance Method
In this method, arc resistance is made to
increase with time so that current is reduced to
a value insufficient to maintain the arc.
Consequently, the current is interrupted or the
arc is extinguished.
The principal disadvantage of this method is
that enormous energy is dissipated in the arc.
Therefore, it is employed only in d.c. circuit
breakers Land low-capacity a.c. circuit breakers.
The resistance of the arc may be increased by
Lengthening the arc - The resistance of the arc is
directly proportional to its length. The length of the arc can be
increased by increasing the gap between contacts.
Cooling the arc - Cooling helps in medium between the contacts.
This increases the arc may be obtained by a gas resistance.
Efficient cooling blast directed along the arc.
Reducing X-section of the arc - If the area of X-section of the arc
is reduced, the voltage necessary to maintain the arc is
increased. In other words, the resistance of the arc path is
increased. The cross-section of the arc can be reduced by
letting the arc pass through a narrow opening or by having
smaller area of contacts.
Splitting the arc - The resistance of the arc can be increased by
splitting the arc into a number of smaller arcs in series. Each
one of these arcs experiences the effect of lengthening and
cooling. The arc may be split by introducing some conducting
plates between the contacts.
2. Low Resistance or Current zero Method
• This method is employed for arc extinction in AC Circuits only. In
this method, arc resistance is kept low until current zero where
the arc extinguishes naturally and is prevented from restriking
inspite of the rising voltage across the contacts.
• All modern high power AC Circuit Breakers employ this method
for arc extinction. In an a.c. system, current drops to zero after
every half-cycle. At every current zero, the arc extinguishes for a
brief moment.
• Now the medium between the contacts contains ions and
electrons so that it has small dielectric strength and can be easily
broken down by the rising contact voltage known as restriking
voltage. If such a break-down does occur, the arc will persist for
another half-cycle. If immediately after current zero, the
dielectric strength of the medium between contacts is built up
more rapidly than the voltage across the contacts, the arc fails to
restrike and the current will be interrupted.
The rapid increase of dielectric strength of the
medium near current zero can be achieved by-
• causing the ionised particles in the space
between contacts to recombine into neutral
molecules.
• sweeping the ionised particles away and
replacing them by unionised
particles. Therefore, the real problem in AC arc
interruption is to rapidly deionise the medium
between contacts as soon as
the current becomes zero so that the rising
contact voltage or restriking voltage cannot
breakdown the space between contacts.
The deionisation of the medium can be achieved by :
(i)Lengthening of the gap : The dielectric strength of the medium is
proportional to the length of the gap between contacts. Therefore, by
opening the contacts rapidly, higher dielectric strength of the medium can
be achieved.
(ii)High pressure: If the pressure in the vicinity of the arc, is increased,
the density of the particles constituting the' discharge also increases. The
increased density of particles causes higher rate of deionisation and
consequently the dielectric strength of the medium between contacts is
increased.
(iii)Cooling : Natural combination of ionised particles takes place more
rapidly if they are allowed to cool. Therefore, dielectric strength of the
medium between the contacts can be increased by cooling the arc.
(iv)Blast effect : If the ionised particles between the contacts are swept
away and replaced by un-ionised particles, the dielectric strength of the
medium can be increased consider-ably. This may be achieved by a gas
blast directed along the discharge or by forcing oil into the contact space.
Circuit Breaker Ratings
A circuit breaker may be called upon to operate under all
conditions. However, major duties are imposed on the circuit
breaker when there is a fault on the system in which it is
connected.
Under fault conditions, a circuit breaker is required to perform
the following three duties :
1. It must be capable of opening the faulty circuit and breaking
the fault current.
2. It must be capable of being closed on to a fault.
3. It must be capable of carrying fault current for a short time
while another circuit breaker (in series) is clearing the fault.
The rating of a circuit breaker includes
I. Breaking capacity or Rated short circuit breaking current.
II. Making capacity or Rated short circuit making current.
III. Short-time capacity or Rated short time current.
• Breaking capacity :
This is the maximum short circuit current which
a circuit breaker can withstand before it, finally
cleared by opening its contacts.
• It is a common practice to express the breaking
capacity in MVA by taking into account the
rated breaking current and rated service
voltage. Thus, if I is the rated breaking current
in amperes and V is the rated service line
voltage in volts, then for a 3-phase circuit.
• Making capacity
The peak value of current during the first cycle
of current wave after the closure of circuit
breaker is known as making capacity.
• Short-time capacity
It is the period for which the circuit breaker is able
to carry fault current while remaining closed.
• The short-time rating of a circuit breaker depends
upon its ability to withstand-
(a) the electromagnetic force effects and
(b) the temperature rise.
The oil circuit breakers have a specified limit of 3
seconds when the ratio of symmetrical breaking
current to the rated normal current does not
exceed 40. However, if this ratio is more than 40,
then the specified limit is 1 second.
• Circuit Breaker Terminology.
• Arc Voltage. It is the voltage that appears
across the contacts of the circuit breaker during
the arcing period.
• Pre-arcing time. It is the time between the
commencement of fault and the instant when cut off
occurs.
• Arcing time. This is the time between the end of pre-
arcing time and the instant when the arc is
extinguished.
• Prospective Current. It is the r.m.s. value of the first
loop of the fault current obtained if the use is
replaced by an ordinary conductor of eligible
resistance.
• Cut-off current. It is the maximum value of fault
current actually reached before the CB opens its
contacts.
• Total operating time.
It is the sum of pre-arcing and arcing times.
• Breaking capacity.
It is the r.m.s. value of a.c. component
of maximum prospective current that a CB can
deal with at rated service voltage
• Restriking voltage
It is the transient voltage that appears across
the contacts at or near current zero during arcing
period.
• Recovery voltage.
It is the normal frequency (50 Hz) r.m.s.
voltage that appears across the contacts of the
circuit breaker after final arc extinction. It is
approximately equal to the system voltage.
• RRRV (Rate Of Rise Of The Restriking Voltage):
The RRRV (rate of rise of the restriking voltage)
is defined as the slope of the steepest tangent
to the restriking voltage curve. It is expressed in
volts per micro-second.
• TRV (Transient Recovery Voltage) :TRV is the
voltage difference observed between the
breaker terminals immediately after the current
interruption of the breaker.
• Total Break Time Fault clearing time is the sum
of "relay time" and "circuit breaker time".
Circuit breaker time is also called "total break
time“
• Classification of Circuit Breakers
There are several ways of classifying the circuit breakers.
However, the most general way of classification is on the
basis of medium used for arc extinction.
(i) Oil circuit breakers:
which employ some insulating oil (e.g., transformer oil) for arc extinction.
(ii) Air-blast circuit breakers:
In which high pressure air-blast is used for extinguishing the arc.
(iii) Sulphur hexafluoride circuit breakers :
In which sulphur hexafluoride (SF6) gas is used for arc extinction.
(iv)Vacuum circuit breakers :
In which vacuum is used for arc extinction.
Each type of circuit breaker has its own advantages and disadvantages. In
the following sections, we shall discuss the construction and working of
these circuit breakers with special emphasis on the way the arc extinction is
facilitated.
Working of Circuit Breaker by Trip Circuit Mechanism
When a short circuit occurs at point F on the transmission line, the current
flowing in the line increases to an enormous value. This results in a heavy
current flow through the relay coil, causing the relay to operate by closing
its contacts. This in turn closes the trip circuit of the breaker, making the
circuit breaker open and isolating the faulty section from the rest of the
system. In this way, the relay ensures the safety of the circuit equipment
from damage and normal working of the healthy portion of the system.
Plain Break Oil CB
Principle of Working
A plain-break oil circuit breaker involves the
simple process of separating the contacts
under the whole of the oil in the tank. There is
no special system for arc control other than the
increase in length caused by the separation of
contacts. The arc extinction occurs when a
certain critical gap between the contacts is
reached.
Construction
It consists of fixed and moving
contacts enclosed in a strong weather-tight
earthed tank containing oil up to a certain level
and an air cushion above the oil level. The
air cushion provides sufficient room to allow for
the reception of the arc gases without the
generation of unsafe pressure in the dome of
the circuit breaker. It also absorbs the
mechanical shock of the upward oil movement.
Working
under normal operating conditions, the fixed and moving contacts
remain closed and the breaker carries the normal circuit current.
When a fault occurs, the moving contacts are pulled down by the
protective system and an arc is struck which vaporizes the oil
mainly into hydrogen gas.
• The arc extinction is facilitated by the following processes :
1. The hydrogen gas bubble generated around the arc cools the arc
column and aids the deionization of the medium between the
contacts.
2. The gas sets up turbulence in the oil and helps in eliminating the
arcing products from the arc path.
3. As the arc lengthens due to the separating contacts, the dielectric
strength of the medium is increased. The result of these actions is
that at some critical gap length, the arc is extinguished and
the circuit current is interrupted.
Advantages of plain break oil circuit breakers
1. Oil produces hydrogen during arcing. The hydrogen helps
extinguish the arc.
2. The oil provides insulation for the live exposed contacts
from the earthed portions of the container.
3. Oil provides insulation between the contacts after the arc
has been extinguished.
Disadvantages of plain break oil circuit breakers
1. There is no special control over the arc other than the
increase in length by separating the moving contacts.
Therefore, for successful interruption, long arc length is
necessary.
2. These breakers have long and inconsistent arcing times.
3. These breakers do not permit high speed interruption.
Applications Plain Break Oil CB
1. Plain-break oil circuit breakers are used only
for low-voltage applications.
2. It is a usual practice to use such breakers for
low capacity installations for voltages not
exceeding 11 kV.
ACB- Air Circuit Breaker (Axial blast)
Construction :
• Fig .shows the essential components of a typical axial blast air circuit
breaker. The fixed and moving contacts are held in the closed position
by spring pressure under normal conditions. The air reservoir is
connected to the arcing chamber through an air valve.
• This valve remains closed under normal conditions but opens
automatically by the tripping impulse when a fault occurs on the
system . When a fault occurs, the tripping impulse causes opening of
the air valve which connects the circuit breaker reservoir to the arcing
chamber.
• The high pressure air entering the arcing chamber pushes away the
moving contact against spring pressure. The moving contact is
separated and an arc is struck. At the same time, high pressure air
blast flows along the arc and takes away the ionised gases along with
it. Consequently, the arc is extinguished and current flow is
interrupted.
• In such circuit breakers, the contact separation required for
interruption is generally small (1·75 cm or so). Such a small gap may
constitute inadequate clearance for the normal service voltage.
Therefore, an isolating switch is incorporated as a part of this type of
circuit breaker. This switch opens immediately after fault interruption
to provide the necessary clearance for insulation
Working :
The fixed and moving contacts are held in closed
position by spring pressure under normal
condition. When a fault occurs, the tripping
impulse causes opening of the air valve, which
connects the C.B. reservoir to the arcing chamber
pushes away the moving contacts against spring
pressure. The moving contact is separated and
arc is struck. At the same time, high pressure air
blast flows along the arc and arc gets extinguish.
ACB- Air Circuit Breaker (cross blast)
Construction:
In this type of circuit breaker, an air-blast is directed at
right angles to the arc. The cross-blast lengthens and forces
the arc into a suitable chute for arc extinction. Fig. shows
the essential parts of a typical cross-blast air circuit breaker.
working :
When the moving contact is withdrawn, an arc is struck
between the fixed and moving contacts. The high pressure
cross-blast forces the arc into a chute consisting of arc
splitters and baffles. The splitters serve to increase the
length of the arc and baffles give improved cooling. The
result is that arc is extinguished and flow of current is
interrupted. Since blast pressure is same for all currents,
the inefficiency at low currents is eliminated. The final gap
for interruption is great enough to give normal insulation
clearance so that a series isolating switch is not necessary.
Advantages air-blast circuit breakers
(i) The risk of fire is eliminated.
(ii) The arcing products are completely removed by the blast
whereas the oil deteriorates with successive operations; the
expense of regular oil replacement is avoided.
(iii) The growth of dielectric strength is so rapid that final contact
gap needed for arc extinction is very small. This reduces the
size of the device.
(iv) The arcing time is very small due to the rapid build up of
dielectric strength between contacts. Therefore, the arc
energy is only a fraction of that in oil circuit breakers, thus
resulting in less burning of contacts.
(v) Due to lesser arc energy, air-blast circuit breakers are very
suitable for conditions where frequent operation is required.
(vi) The energy supplied for arc extinction is obtained from high
pressure air and is independent of the current to be
interrupted.
Disadvantages air-blast circuit breaker
(i) The air has relatively inferior arc extinguishing
properties.
(ii)The air-blast circuit breakers are very sensitive to
the variations in the rate of rise of restriking
voltage.
(iii) Considerable maintenance is required for the
compressor plant which supplies the air-blast.
Applications air-blast circuit breaker
The air blast circuit breakers are finding wide
applications in high voltage installations.
Majority of the circuit breakers for voltages
beyond 110 kV are of this type.
Puffer Type SF6 CB
• Construction :
• The moving cylinder is coupled with the movable
conductor against the fixed piston, and there is a relative
movement between the moving cylinder and the fixed
piston.
• The gas is compressed in the cavity.
• This trapped gas is released through the nozzle, during arc
extinction process.
• During the travel, of the moving contact and the movable
cylinder, the gas puffs over the arc and reduces the arc
diameter by axial convection and radial dissipation.
• At current zero, the arc diameter becomes too small and
the arc gets extinguished
• The puffing action continues for some time, even after
the arc extinction, and the contact space is filled with
cool, fresh gas.
• Working :
• SF6 is a Gas type circuit breaker since SF6 gas is used in
it for extinguishing the arc. The quenching of arc in SF6
circuit breaker takes place due to the puffer
phenomenon taking place inside this circuit breaker
Puffer means quick & short blast of gas on the arc. In
SF6 C.B blast the SF6 gas is made on the arc through
puffer action & the arc gets quenched
• As shown in fig above, the fixed & moving contacts are
kept in insulating nozzle section. The whole assembly
i.e insulating nozzle, puffer action cylinder with moving
contact ,a fixed piston is provided to it through the
other end of moving contact. The chamber is filled with
SF6gas. Under normal working condition, the contacts
are closed but on the fault , the contacts open so
moving contacts move right & SF6 gas move left side.
• An arc is struck between the moving contact &
fixed contact. The travel of movable cylinder
causes increase in pressure on SF6 gas & this
high pressure SF6 gas travels towards arc i.e it
puffs over the arc or in simple we can say it
blast over the arc
• so when this puffer action is completed the arc
gets extinguished. This type of C.B is called
simple SF6 C.B. but it has limitation of refilling
the SF6 which is has by disconnecting from its
circuit for this we introduced Double pressure
dead type SF6.
Non Puffer Type SF6 CB
Construction.
Fig. shows the parts of a typical SF6 circuit breaker.
It consists of fixed and moving contacts enclosed
in a chamber (called arc interruption chamber)
containing SF6 gas. This chamber is connected to
SF6 gas reservoir. When the contacts of breaker
are opened, the valve mechanism permits a high
pressure SF6 gas from the reservoir to flow
towards the arc interruption chamber.
• The fixed contact is a hollow cylindrical current
carrying contact fitted with an arc horn. The
moving contact is also a hollow cylinder with
rectangular holes in the sides to permit the
SF6 gas to let out through these holes after
flowing along and across the arc.
• The tips of fixed contact, moving contact and
arcing horn are coated with copper-tungsten
arc resistant material.
Working.
• When the breaker operates, the moving contact is
pulled apart and an arc is struck between the
contacts.
• The movement of the moving contact is
synchronised with the opening of a valve which
permits SF6 gas at 14 kg/cm2 pressure from the
reservoir to the arc interruption chamber. The
high pressure flow of SF6 rapidly absorbs the free
electrons in the arc path.
• The result is that the medium between the
contacts quickly builds up high dielectric strength
and causes the extinction of the arc . After the
breaker operation (i.e., after arc extinction), the
valve is closed by the action of a set of springs.
Advantages:
(i) Due to the superior arc quenching property of SF6,
such circuit breakers have very short arcing time.
(ii) Since the dielectric strength of SF6 gas is 2 to 3
times that of air, such breakers can interrupt much
larger currents.
(iii) The SF6 circuit breaker gives noiseless operation
due to its closed gas circuit and no exhaust to
atmosphere unlike the air blast circuit breaker.
iv) The closed gas enclosure keeps the interior dry so
that there is no moisture problem.
(v) There is no risk of fire in such breakers
because SF6 gas is non-inflammable.
(vi) There are no carbon deposits so that tracking
and insulation problems are eliminated.
(vii) The SF6 breakers have low maintenance cost,
light foundation requirements and minimum
auxiliary equipment.
(viii) Since SF6 breakers are totally enclosed and
sealed from atmosphere, they are particularly
suitable where explosion hazard exists e.g.,
coal mines.
Disadvantages
(i) SF6 breakers are costly due to the high cost of SF6.
(ii)Since SF6 gas has to be reconditioned after every
operation of the breaker, additional equipment is
required for this purpose.
Applications.
A typical SF6 circuit breaker is uses for the
voltage range 50kV to 230kV.
Power Ratings 10MVA to 20MVA and
interrupting time less than 3 cycles.
Vacuum Circuit Breakers (VCB)
Vacuum Circuit Breakers (VCB)
In such breakers, vacuum (degree of vacuum
being in the range from 10−7 to 10−5 torr) is used
as the arc quenching medium. Since vacuum
offers the highest insulating strength, it has far
superior arc quenching properties than any other
medium. For example, when contacts of a breaker
are opened in vacuum, the interruption occurs at
first current zero with dielectric strength between
the contacts building up at a rate thousands of
times higher than that obtained with other circuit
breakers.
Working Principle.
• When the contacts of the breaker are opened in
vacuum (10−7 to 10−5 torr), an arc is produced
between the contacts by the ionisation of metal
vapours of contacts.
• However, the arc is quickly extinguished because
the metallic vapours, electrons and ions produced
during arc rapidly condense on the surfaces of the
circuit breaker contacts, resulting in quick recovery
of dielectric strength.
• As soon as the arc is produced in vacuum, it is
quickly extinguished due to the fast rate of recovery
of dielectric strength in vacuum. the arc extinction in
a vacuum breaker occurs with a short contact
separation (say 0·625 cm).
Construction :
Fig. shows the parts of a typical vacuum circuit
breaker. It consists of fixed contact, moving contact
and arc shield mounted inside a vacuum chamber.
The movable member is connected to the control
mechanism by stainless steel bellows. This enables
the permanent sealing of the vacuum chamber so
as to eliminate the possibility of leak. A glass vessel
or ceramic vessel is used as the outer insulating
body. The arc shield prevents the deterioration of
the internal dielectric strength by preventing
metallic vapours falling on the inside surface of the
outer insulating cover.
Working.
When the breaker operates, the moving contact
separates from the fixed contact and an arc is
struck between the contacts. The production of
arc is due to the ionisation of metal ions and
depends very much upon the material of contacts.
The arc is quickly extinguished because the
metallic vapours, electrons and ions produced
during arc are diffused in a short time and seized
by the surfaces of moving and fixed members and
shields. Since vacuum has very fast rate of
recovery of dielectric strength,
Advantages.
1. They are compact, reliable and have longer life.
2. There are no fire hazards.
3. There is no generation of gas during and after
operation.
4. They can interrupt heavy fault current perfectly
just before the contacts reach the definite open
position.
5. They require little maintenance and are quiet in
operation.
6. They can successfully withstand lightning surges.
7. They have low arc energy.
8. They have low inertia and hence require smaller
power for control mechanism.
Applications.
Vacuum circuit breakers are being employed for
outdoor applications ranging from 22 kV to 66 kV.
• Features of Intelligent Circuit Breaker
1. It has Easy User setting facility.
2. Over load alarm function.
3. Display function.
4. Self diagnosis function.
5. Fault memory storage.
6. LED indication of Trip condition.
Maintenance Schedule of OCB,ACB, SF6 and VCB Circuit Breakers
• For maintenance of circuit breaker , it must be
first switched off and then isolated from both
sides by opening concerned electrical isolator.
• Daily Maintenance Schedule for all CB’s-
Physical appearance Doors and covers to be
bolted. Check for noise, smell or damage.
Oil Circuit Breaker Maintenance
• For oil circuit breaker, we should check contact
burning. If burning is very light, remove the burn
beads and polish the surface.
• check & Clean the extinguishing chamber.
• Half yearly-The proper adjustment of auxiliary
switch by ensuring correct NO NC contacts at
breaker OFF and ON condition must be checked
• The spring charging motor and mechanism should
also be cleaned and associated bearing should
also be lubricated half yearly.
Maintenance of Air Blast Circuit Breaker
Yearly & half Yearly
• In air circuit breaker, the air leakage should be
checked monthly.
• Yearly, dew point of the operating air at the
outlet of the air dryer should be measured with
the help of Dew Point Meter or Hygro Meters.
SF6 Circuit Breaker Maintenance
Yearly & half Yearly
• SF6 circuit breaker must be checked for SF6 gas
leakage.
• Dew point of SF6 should be checked with the help
of dew point meter or hygro meters in every 3 to
4 years interval.
• Maintenance of Vacuum Circuit Breaker
Yearly & half Yearly
• Using a clean, dry cloth, remove all dirt and moisture
from insulating parts.
• Inspect the entire circuit breaker and operating
mechanism for loose hardware and worn or broken
parts. Check all wiring for loose connections and
damaged insulation. Inspect all bearings and contact
surfaces for damage or excessive wear.
• All ball and roller bearings used in these circuit
breakers are sealed; they do not require lubrication.
Comparisons between fuse and circuit breaker.
Particular FUSE CIRCUIT BREAKER
Working Principle Fuse works on the electrical and
thermal properties of the
conducting materials.
Circuit breaker works on the
Electromagnetism and switching
principle.
Reusability Fuses can be used only once. Circuit breakers can be used a
number of times.
Status indication It does not give any indication. It gives an indication of the
status
Auxiliary contact No auxiliary contact is required. They are available with
auxiliary contact.
Switching Action Fuse cannot be used as an ON/OFF
switch.
The Circuit breaker is used e as
ON/OFF switches.
Breaking capacity Breaking capacity of the fuse is low
as compared to the circuit breaker.
Breaking capacity is high.
Operating time Operating time of fuse is very less
(0.002 seconds)
Operating time is comparatively
more than that of the fuse.
(0.02 – 0.05 seconds)
MODEL QUESTION BANK
Cognitive Level: Remember
1. List different Switchgear equipment
2. List Differences between Indoor type and Outdoor type
Switchgear
3. List Desirable Characteristics of Fuse elements
4. List Fuse Element Materials
5. State Merits and Demerits of HRC fuse
6. List any 3 Application of HRC fuse
7. List the different methods of arc extinction
8. List different circuit breakers
9. List the Features of Intelligent Circuit Breaker
10. State Merits and Demerits of Plain oil OCB
11. State Merits and Demerits of Air circuit breaker
12. State Merits and Demerits of SF6 CB
13.State Merits and Demerits of Vacuum Circuit breaker
14. List the Applications of OCB
15. List the Applications of ACB
16. List the Applications of SF6 CB
17. List the Applications of VCB
18. Lists the steps in maintenance of OCB
19. Lists the steps in maintenance of SF6 CB
20. Lists the steps in maintenance of ACB
21. Define breaking capacity, making capacity and Sort
time rating
22. Lists the steps in maintenance of VCB
Cognitive Level: Understanding
23. Explain Essential features of Switchgear
24. Explain Switchgear equipment
25. Explain terms: Terms: Current Rating of Fuse
element, Fusing current, Fusing factor, Prospective
current, cut off current , Pre Arcing Time, Arcing
Time, Breaking Capacity, Total Operating Time.
26. Explain construction and working of HRC fuse
27. Explain the different methods of arc extinction
28. Explain Arc Extinction phenomena in CB by high
resistance method
29. Illustrate the working of Circuit Breaker by Trip
Circuit Mechanism
30. Explain circuit breaker rating
31. Explain the terminologies – Arc-Voltage, arching Time,
Pre –Arching Time, Prospective
Current, T R V, Recovery Voltage, R RR V, Total Break Time
32. Explain Working principle of Circuit Breakers
33. Explain construction and working of Plain oil OCB ACB
34. Explain construction and working of Axial blast ACB
35. Explain construction and working of cross blast ACB
36. Explain construction and working of Puffer Type SF6 CB
37. Explain construction and working of Non Puffer Type
SF6 CB
38. Explain construction and working of VACUUM CB
39. Differentiate between fuse and circuit breaker
Cognitive Level: Application/Analyze
1. Compare fuse and circuit breaker.
2. Explain Working principle of Circuit Breakers
3. Explain Essential features of Switchgear
4. Explain Switchgear equipment
5. Explain terms: Terms: Current Rating of Fuse
element, Fusing current, Fusing factor, Prospective
current, cut off current , Pre Arcing Time, Arcing
Time, Breaking Capacity, Total Operating Time.
6. Explain construction and working of HRC fuse
7. Explain the different methods of arc extinction
8. Explain breaking capacity of CB
9. Explain making capacity of CB
10. Explain Short time rating of CB
Fuse and circuit breakers explained

More Related Content

What's hot

Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1Md Irshad Ahmad
 
Types Of Substations
Types Of SubstationsTypes Of Substations
Types Of Substationssapna186
 
Classification of transmission lines
Classification of transmission linesClassification of transmission lines
Classification of transmission linesHamzaAbbas43
 
Transmission & distribution of electrical power
Transmission & distribution of electrical powerTransmission & distribution of electrical power
Transmission & distribution of electrical powerpriyanka1432
 
Presentation topic is transmission line
Presentation topic is transmission linePresentation topic is transmission line
Presentation topic is transmission linemd muzahidul haque
 
Air circuit breakers
Air circuit breakersAir circuit breakers
Air circuit breakersPrasant Kumar
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION moiz89
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devicesRahul Aman
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformerssiddharam kantoli
 
Presentation on substations
Presentation on substationsPresentation on substations
Presentation on substationsvishalgohel12195
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear johny renoald
 
Power System Protection course - Part I
Power System Protection course - Part IPower System Protection course - Part I
Power System Protection course - Part ISlides Hub
 

What's hot (20)

Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1
 
Vacuum circuit breaker
Vacuum circuit breakerVacuum circuit breaker
Vacuum circuit breaker
 
Types Of Substations
Types Of SubstationsTypes Of Substations
Types Of Substations
 
Classification of transmission lines
Classification of transmission linesClassification of transmission lines
Classification of transmission lines
 
Transmission & distribution of electrical power
Transmission & distribution of electrical powerTransmission & distribution of electrical power
Transmission & distribution of electrical power
 
Presentation topic is transmission line
Presentation topic is transmission linePresentation topic is transmission line
Presentation topic is transmission line
 
Air circuit breakers
Air circuit breakersAir circuit breakers
Air circuit breakers
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devices
 
Types of relay
Types of relayTypes of relay
Types of relay
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Presentation on substations
Presentation on substationsPresentation on substations
Presentation on substations
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
 
Earthing
EarthingEarthing
Earthing
 
Power System Protection course - Part I
Power System Protection course - Part IPower System Protection course - Part I
Power System Protection course - Part I
 
Introduction to Power Quality Problems
Introduction to Power Quality ProblemsIntroduction to Power Quality Problems
Introduction to Power Quality Problems
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
33kv substation
33kv substation33kv substation
33kv substation
 
Supports of overhead line
Supports of overhead lineSupports of overhead line
Supports of overhead line
 

Similar to Fuse and circuit breakers explained

Similar to Fuse and circuit breakers explained (20)

Fuse- Power system Protection
Fuse- Power system Protection  Fuse- Power system Protection
Fuse- Power system Protection
 
An introduction to FUSES
An introduction to FUSESAn introduction to FUSES
An introduction to FUSES
 
Fuse and its types
Fuse and its typesFuse and its types
Fuse and its types
 
Module 5 FUSES.pptx
Module 5 FUSES.pptxModule 5 FUSES.pptx
Module 5 FUSES.pptx
 
Fuses
FusesFuses
Fuses
 
4 fuses
4 fuses4 fuses
4 fuses
 
Lecture_14_Circuit_Breakers.pptx
Lecture_14_Circuit_Breakers.pptxLecture_14_Circuit_Breakers.pptx
Lecture_14_Circuit_Breakers.pptx
 
Components of LT Switchgear.pptx
Components of LT Switchgear.pptxComponents of LT Switchgear.pptx
Components of LT Switchgear.pptx
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Fuse.pdf
Fuse.pdfFuse.pdf
Fuse.pdf
 
Switchgear and Protection of HV Systems
Switchgear and Protection of HV SystemsSwitchgear and Protection of HV Systems
Switchgear and Protection of HV Systems
 
Electrical Installation.pptx
Electrical Installation.pptxElectrical Installation.pptx
Electrical Installation.pptx
 
Power system
Power systemPower system
Power system
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakers
 
Experiments manual
Experiments manual Experiments manual
Experiments manual
 
Fuses_Lec_1.pptx
Fuses_Lec_1.pptxFuses_Lec_1.pptx
Fuses_Lec_1.pptx
 
Fuses and mcb
Fuses and mcbFuses and mcb
Fuses and mcb
 
Fuses and its type in power system
Fuses and its type in power systemFuses and its type in power system
Fuses and its type in power system
 
ABB Medium Voltage Fuses
ABB Medium Voltage FusesABB Medium Voltage Fuses
ABB Medium Voltage Fuses
 

More from PremanandDesai

Week-11 - Assembly drawing - Synchronous Motor
Week-11 - Assembly drawing -  Synchronous Motor Week-11 - Assembly drawing -  Synchronous Motor
Week-11 - Assembly drawing - Synchronous Motor PremanandDesai
 
Week-10 - Assembly drawing - Alternators
Week-10 - Assembly drawing - AlternatorsWeek-10 - Assembly drawing - Alternators
Week-10 - Assembly drawing - AlternatorsPremanandDesai
 
Week-09 - Assembly drawing-Induction Motor
Week-09 - Assembly drawing-Induction Motor Week-09 - Assembly drawing-Induction Motor
Week-09 - Assembly drawing-Induction Motor PremanandDesai
 
Week-08 - Transformer Assembly-Threephase
Week-08 - Transformer Assembly-ThreephaseWeek-08 - Transformer Assembly-Threephase
Week-08 - Transformer Assembly-ThreephasePremanandDesai
 
Week-07- Developed Winding Diagrams - 1 phase--.pptx
Week-07- Developed Winding Diagrams - 1 phase--.pptxWeek-07- Developed Winding Diagrams - 1 phase--.pptx
Week-07- Developed Winding Diagrams - 1 phase--.pptxPremanandDesai
 
Week-06 - Developed Winding Diagrams - 3 phase--.pptx
Week-06 - Developed Winding Diagrams - 3 phase--.pptxWeek-06 - Developed Winding Diagrams - 3 phase--.pptx
Week-06 - Developed Winding Diagrams - 3 phase--.pptxPremanandDesai
 
Week-05 -Design a GA LT panel wiring--.pptx
Week-05 -Design a GA LT panel wiring--.pptxWeek-05 -Design a GA LT panel wiring--.pptx
Week-05 -Design a GA LT panel wiring--.pptxPremanandDesai
 
Week-04 -Motor control Panel board
Week-04 -Motor control Panel boardWeek-04 -Motor control Panel board
Week-04 -Motor control Panel boardPremanandDesai
 
Week-03 - Electrical wiring of Residential, Hospital , small workshop
Week-03 - Electrical wiring of  Residential, Hospital , small workshopWeek-03 - Electrical wiring of  Residential, Hospital , small workshop
Week-03 - Electrical wiring of Residential, Hospital , small workshopPremanandDesai
 
Week-02 - Single line diagram of Substations
Week-02 - Single line diagram of SubstationsWeek-02 - Single line diagram of Substations
Week-02 - Single line diagram of SubstationsPremanandDesai
 
Week-01 - INTRODUCTION to CAD
Week-01  - INTRODUCTION to CADWeek-01  - INTRODUCTION to CAD
Week-01 - INTRODUCTION to CADPremanandDesai
 
Week- 13 - APFC , AMF & STP
Week- 13 - APFC , AMF & STP Week- 13 - APFC , AMF & STP
Week- 13 - APFC , AMF & STP PremanandDesai
 
Week - 12 - Motor control centre (MCC)
Week - 12 - Motor control centre (MCC) Week - 12 - Motor control centre (MCC)
Week - 12 - Motor control centre (MCC) PremanandDesai
 
Week - 11 - Metering section and Auxiliary Relays
Week  - 11 - Metering section  and Auxiliary RelaysWeek  - 11 - Metering section  and Auxiliary Relays
Week - 11 - Metering section and Auxiliary RelaysPremanandDesai
 
Week 10 - Control Panel & Power gears
Week  10 - Control Panel &  Power gearsWeek  10 - Control Panel &  Power gears
Week 10 - Control Panel & Power gearsPremanandDesai
 
Switchgear and protection - lab
Switchgear and protection - labSwitchgear and protection - lab
Switchgear and protection - labPremanandDesai
 
Week - 09 - Testing of CB & Substation Earthing
Week - 09 - Testing of CB & Substation Earthing Week - 09 - Testing of CB & Substation Earthing
Week - 09 - Testing of CB & Substation Earthing PremanandDesai
 
Week- 08 - Feeder protection and Bus–Bar Protection.
Week- 08 - Feeder protection and  Bus–Bar Protection.Week- 08 - Feeder protection and  Bus–Bar Protection.
Week- 08 - Feeder protection and Bus–Bar Protection.PremanandDesai
 
Week 07 - Alternator Protection
Week   07 - Alternator Protection Week   07 - Alternator Protection
Week 07 - Alternator Protection PremanandDesai
 
WEEK- 06/ UNIT – 06 Transformer Protection
WEEK- 06/ UNIT – 06 Transformer Protection WEEK- 06/ UNIT – 06 Transformer Protection
WEEK- 06/ UNIT – 06 Transformer Protection PremanandDesai
 

More from PremanandDesai (20)

Week-11 - Assembly drawing - Synchronous Motor
Week-11 - Assembly drawing -  Synchronous Motor Week-11 - Assembly drawing -  Synchronous Motor
Week-11 - Assembly drawing - Synchronous Motor
 
Week-10 - Assembly drawing - Alternators
Week-10 - Assembly drawing - AlternatorsWeek-10 - Assembly drawing - Alternators
Week-10 - Assembly drawing - Alternators
 
Week-09 - Assembly drawing-Induction Motor
Week-09 - Assembly drawing-Induction Motor Week-09 - Assembly drawing-Induction Motor
Week-09 - Assembly drawing-Induction Motor
 
Week-08 - Transformer Assembly-Threephase
Week-08 - Transformer Assembly-ThreephaseWeek-08 - Transformer Assembly-Threephase
Week-08 - Transformer Assembly-Threephase
 
Week-07- Developed Winding Diagrams - 1 phase--.pptx
Week-07- Developed Winding Diagrams - 1 phase--.pptxWeek-07- Developed Winding Diagrams - 1 phase--.pptx
Week-07- Developed Winding Diagrams - 1 phase--.pptx
 
Week-06 - Developed Winding Diagrams - 3 phase--.pptx
Week-06 - Developed Winding Diagrams - 3 phase--.pptxWeek-06 - Developed Winding Diagrams - 3 phase--.pptx
Week-06 - Developed Winding Diagrams - 3 phase--.pptx
 
Week-05 -Design a GA LT panel wiring--.pptx
Week-05 -Design a GA LT panel wiring--.pptxWeek-05 -Design a GA LT panel wiring--.pptx
Week-05 -Design a GA LT panel wiring--.pptx
 
Week-04 -Motor control Panel board
Week-04 -Motor control Panel boardWeek-04 -Motor control Panel board
Week-04 -Motor control Panel board
 
Week-03 - Electrical wiring of Residential, Hospital , small workshop
Week-03 - Electrical wiring of  Residential, Hospital , small workshopWeek-03 - Electrical wiring of  Residential, Hospital , small workshop
Week-03 - Electrical wiring of Residential, Hospital , small workshop
 
Week-02 - Single line diagram of Substations
Week-02 - Single line diagram of SubstationsWeek-02 - Single line diagram of Substations
Week-02 - Single line diagram of Substations
 
Week-01 - INTRODUCTION to CAD
Week-01  - INTRODUCTION to CADWeek-01  - INTRODUCTION to CAD
Week-01 - INTRODUCTION to CAD
 
Week- 13 - APFC , AMF & STP
Week- 13 - APFC , AMF & STP Week- 13 - APFC , AMF & STP
Week- 13 - APFC , AMF & STP
 
Week - 12 - Motor control centre (MCC)
Week - 12 - Motor control centre (MCC) Week - 12 - Motor control centre (MCC)
Week - 12 - Motor control centre (MCC)
 
Week - 11 - Metering section and Auxiliary Relays
Week  - 11 - Metering section  and Auxiliary RelaysWeek  - 11 - Metering section  and Auxiliary Relays
Week - 11 - Metering section and Auxiliary Relays
 
Week 10 - Control Panel & Power gears
Week  10 - Control Panel &  Power gearsWeek  10 - Control Panel &  Power gears
Week 10 - Control Panel & Power gears
 
Switchgear and protection - lab
Switchgear and protection - labSwitchgear and protection - lab
Switchgear and protection - lab
 
Week - 09 - Testing of CB & Substation Earthing
Week - 09 - Testing of CB & Substation Earthing Week - 09 - Testing of CB & Substation Earthing
Week - 09 - Testing of CB & Substation Earthing
 
Week- 08 - Feeder protection and Bus–Bar Protection.
Week- 08 - Feeder protection and  Bus–Bar Protection.Week- 08 - Feeder protection and  Bus–Bar Protection.
Week- 08 - Feeder protection and Bus–Bar Protection.
 
Week 07 - Alternator Protection
Week   07 - Alternator Protection Week   07 - Alternator Protection
Week 07 - Alternator Protection
 
WEEK- 06/ UNIT – 06 Transformer Protection
WEEK- 06/ UNIT – 06 Transformer Protection WEEK- 06/ UNIT – 06 Transformer Protection
WEEK- 06/ UNIT – 06 Transformer Protection
 

Recently uploaded

Enzyme, Pharmaceutical Aids, Miscellaneous Last Part of Chapter no 5th.pdf
Enzyme, Pharmaceutical Aids, Miscellaneous Last Part of Chapter no 5th.pdfEnzyme, Pharmaceutical Aids, Miscellaneous Last Part of Chapter no 5th.pdf
Enzyme, Pharmaceutical Aids, Miscellaneous Last Part of Chapter no 5th.pdfSumit Tiwari
 
Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)eniolaolutunde
 
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPT
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPTECONOMIC CONTEXT - LONG FORM TV DRAMA - PPT
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPTiammrhaywood
 
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxSOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxiammrhaywood
 
Presiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha electionsPresiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha electionsanshu789521
 
MENTAL STATUS EXAMINATION format.docx
MENTAL     STATUS EXAMINATION format.docxMENTAL     STATUS EXAMINATION format.docx
MENTAL STATUS EXAMINATION format.docxPoojaSen20
 
Separation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesSeparation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesFatimaKhan178732
 
_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting Data_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting DataJhengPantaleon
 
Introduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher EducationIntroduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher Educationpboyjonauth
 
Accessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactAccessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactdawncurless
 
How to Configure Email Server in Odoo 17
How to Configure Email Server in Odoo 17How to Configure Email Server in Odoo 17
How to Configure Email Server in Odoo 17Celine George
 
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17Celine George
 
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptx
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptxPOINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptx
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptxSayali Powar
 
Concept of Vouching. B.Com(Hons) /B.Compdf
Concept of Vouching. B.Com(Hons) /B.CompdfConcept of Vouching. B.Com(Hons) /B.Compdf
Concept of Vouching. B.Com(Hons) /B.CompdfUmakantAnnand
 
KSHARA STURA .pptx---KSHARA KARMA THERAPY (CAUSTIC THERAPY)————IMP.OF KSHARA ...
KSHARA STURA .pptx---KSHARA KARMA THERAPY (CAUSTIC THERAPY)————IMP.OF KSHARA ...KSHARA STURA .pptx---KSHARA KARMA THERAPY (CAUSTIC THERAPY)————IMP.OF KSHARA ...
KSHARA STURA .pptx---KSHARA KARMA THERAPY (CAUSTIC THERAPY)————IMP.OF KSHARA ...M56BOOKSTORE PRODUCT/SERVICE
 
A Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformA Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformChameera Dedduwage
 
Mastering the Unannounced Regulatory Inspection
Mastering the Unannounced Regulatory InspectionMastering the Unannounced Regulatory Inspection
Mastering the Unannounced Regulatory InspectionSafetyChain Software
 
Science 7 - LAND and SEA BREEZE and its Characteristics
Science 7 - LAND and SEA BREEZE and its CharacteristicsScience 7 - LAND and SEA BREEZE and its Characteristics
Science 7 - LAND and SEA BREEZE and its CharacteristicsKarinaGenton
 

Recently uploaded (20)

Enzyme, Pharmaceutical Aids, Miscellaneous Last Part of Chapter no 5th.pdf
Enzyme, Pharmaceutical Aids, Miscellaneous Last Part of Chapter no 5th.pdfEnzyme, Pharmaceutical Aids, Miscellaneous Last Part of Chapter no 5th.pdf
Enzyme, Pharmaceutical Aids, Miscellaneous Last Part of Chapter no 5th.pdf
 
Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)
 
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPT
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPTECONOMIC CONTEXT - LONG FORM TV DRAMA - PPT
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPT
 
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxSOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
 
Presiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha electionsPresiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha elections
 
Model Call Girl in Bikash Puri Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Bikash Puri  Delhi reach out to us at 🔝9953056974🔝Model Call Girl in Bikash Puri  Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Bikash Puri Delhi reach out to us at 🔝9953056974🔝
 
MENTAL STATUS EXAMINATION format.docx
MENTAL     STATUS EXAMINATION format.docxMENTAL     STATUS EXAMINATION format.docx
MENTAL STATUS EXAMINATION format.docx
 
Separation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesSeparation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and Actinides
 
_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting Data_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting Data
 
9953330565 Low Rate Call Girls In Rohini Delhi NCR
9953330565 Low Rate Call Girls In Rohini  Delhi NCR9953330565 Low Rate Call Girls In Rohini  Delhi NCR
9953330565 Low Rate Call Girls In Rohini Delhi NCR
 
Introduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher EducationIntroduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher Education
 
Accessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactAccessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impact
 
How to Configure Email Server in Odoo 17
How to Configure Email Server in Odoo 17How to Configure Email Server in Odoo 17
How to Configure Email Server in Odoo 17
 
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
 
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptx
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptxPOINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptx
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptx
 
Concept of Vouching. B.Com(Hons) /B.Compdf
Concept of Vouching. B.Com(Hons) /B.CompdfConcept of Vouching. B.Com(Hons) /B.Compdf
Concept of Vouching. B.Com(Hons) /B.Compdf
 
KSHARA STURA .pptx---KSHARA KARMA THERAPY (CAUSTIC THERAPY)————IMP.OF KSHARA ...
KSHARA STURA .pptx---KSHARA KARMA THERAPY (CAUSTIC THERAPY)————IMP.OF KSHARA ...KSHARA STURA .pptx---KSHARA KARMA THERAPY (CAUSTIC THERAPY)————IMP.OF KSHARA ...
KSHARA STURA .pptx---KSHARA KARMA THERAPY (CAUSTIC THERAPY)————IMP.OF KSHARA ...
 
A Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformA Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy Reform
 
Mastering the Unannounced Regulatory Inspection
Mastering the Unannounced Regulatory InspectionMastering the Unannounced Regulatory Inspection
Mastering the Unannounced Regulatory Inspection
 
Science 7 - LAND and SEA BREEZE and its Characteristics
Science 7 - LAND and SEA BREEZE and its CharacteristicsScience 7 - LAND and SEA BREEZE and its Characteristics
Science 7 - LAND and SEA BREEZE and its Characteristics
 

Fuse and circuit breakers explained

  • 1.
  • 2. UNIT-02 FUSE AND CIRCUIT BREAKERS CO-02- Understand the construction and working of Fuse and circuit breakers
  • 3. Meaning of Switchgear The apparatus used for switching, controlling and protecting the electrical circuits and equipment is known as switchgear
  • 4. Essential features of Switchgear (i) Complete reliability : When fault occurs on any part of the power system, the switchgear must operate to isolate the faulty section from the remainder circuit. (ii)Absolutely certain discrimination : When fault occurs on any section of the power system, the switchgear must be able to discriminate between the faulty section and the healthy section. It should isolate the faulty section from the system without affecting the healthy section. This will ensure continuity of supply.
  • 5. (iii) Quick operation: When fault occurs on any part of the power system, the switchgear must operate quickly so that power system equipment . (iv) Provision for manual control : A switchgear must have provision for manual control. In case the electrical (or electronics) control fails, the necessary operation can be carried out through manual control. (v) Provision for instruments : There must be provision for instruments which may be required. These may be in the form of ammeter or voltmeter on the unit itself or the necessary current and voltage transformers for connecting to the main switchboard or a separate instrument panel.
  • 6. Switchgear Equipment Switchgear covers a wide range of equipment concerned with switching and interrupting currents under both normal and abnormal conditions. It includes switches, fuses, circuit breakers, relays and other equipment. • Some devices is given below. 1. Switches (i) Air switches (ii) Isolator or disconnecting switch. (iii) Oil switches 2. Fuses. 3. Circuit breakers. 4. Relays.
  • 7. I. Air-break switch : It is an air switch and is designed to open a circuit under load. In order to quench the arc that occurs on opening such a switch, special arcing horns are provided. II. Isolator or disconnecting switch : It is essentially a knife switch and is designed to open a circuit under no load. III. Oil switches : The contacts of such switches are opened under oil, usually transformer oil.
  • 8. 2. Fuses A fuse is a short piece of wire or thin strip which melts when excessive current flows through it for sufficient time. It is inserted in series with the circuit to be protected. When a short circuit or overload occurs, the current through the fuse element increases beyond its rated capacity. This raises the temperature and the fuse element melts (or blows out), disconnecting the circuit protected by it.
  • 9. 3. Circuit Breakers A circuit breaker is an equipment which can open or close a circuit under all conditions viz. no load, full load and fault conditions. It is so designed that it can be operated manually (or by remote control) under normal conditions and automatically under fault conditions. For the latter operation, a relay circuit is used with a circuit breaker. 4. Relays A relay is a device which detects the fault and supplies information to the breaker for circuit interruption. When a fault occurs the relay contacts are closed and the trip coil of the circuit breaker is energised to open the contacts of the circuit breaker.
  • 10. Differences between Indoor type and Outdoor type Switchgear (i) Indoor type. • For voltages below 66 kV, switchgear is generally installed indoor because of economic considerations. • The indoor switchgear is generally of metal- clad type. In this type of construction, all live parts are completely enclosed in an earthed metal casing. • The primary object of this practice is the definite localization and restriction of any fault to its place of origin.
  • 11. (ii) Outdoor type. • For voltages beyond 66 kV, switchgear equipment is installed outdoor. • It is because for such voltages, the clearances between conductors and the space required for switches, circuit breakers, transformers and others equipment become so great that it is not economical to install all such equipment indoor. • The circuit breakers , isolators, transformers and bus-bars occupy considerable space on account of large electrical clearance associated with high voltages.
  • 12. Fuses A fuse is a short piece of metal, inserted in the circuit, which melts when excessive current flows through it and thus breaks the circuit.
  • 13. Desirable Characteristics of Fuse elements The function of a fuse is to carry the normal current without overheating but when the current exceeds its normal value, it rapidly heats up to melting point and disconnects the circuit protected by it. In order that it may perform this function satisfactorily.
  • 14. Desirable characteristics (i) low melting point e.g., tin, lead. (ii) high conductivity e.g., silver, copper. (iii) free from deterioration due to oxidation e.g., silver. (iv) low cost e.g., lead, tin, copper.
  • 15. Types of Fuses (1) Low voltages fuses (i) Semi-enclosed rewireable fuse (ii) High rupturing capacity (H.R.C.) cartridge fuse. (iii) H.R.C. fuse with tripping device. (2) High voltage fuses (i) Cartridge type (ii) Liquid type. (iii) Metal clad fuses.
  • 16. Semi-enclosed rewireable fuse or Kit-Kat Fuses High rupturing capacity (H.R.C.) H.R.C. fuse with tripping device.
  • 17. Cartridge type fuse for LV Cartridge type fuse for HV Liquid type. Metal clad fuses
  • 18. Fuse Element Materials • The most commonly used materials for fuse element are lead, tin, copper, zinc and silver. • For small currents up to 10 A, tin or an alloy of lead and tin (lead 37%, tin 63%) is used for making the fuse element. • For larger currents, copper or silver is employed. It is a usual practice to tin the copper to protect it from oxidation. • Zinc (in strip form only) is good if a fuse with considerable time-lag is required i.e., one which does not melt very quickly with a small overload.
  • 19. The present trend is to use silver despite its high cost due to the following reasons : (i) It is comparatively free from oxidation. (ii) It does not deteriorate when used in dry air. (iii) The coefficient of expansion of silver is so small that no critical fatigue occurs. Therefore, the fuse element can carry the rated current continuously for a long time. (iv) The conductivity of silver is very high. Therefore, for a given rating of fuse element, the mass of silver metal required is smaller than that of other materials. This minimizes the problem of clearing the mass of vapourised material set free on fusion and thus permits fast operating speed. (v) Due to comparatively low specific heat, silver fusible elements can be raised from normal temperature to vapourisation quicker than other fusible elements. Moreover, the resistance of silver increases abruptly as the melting temperature is reached, thus making the transition from melting to vapourisation almost instantaneous. Consequently, operation becomes very much faster at higher currents. (vi) Silver vapourises at a temperature much lower than the one at which its vapour will readily ionize. Therefore, when an arc is formed through the vapourised portion of the element, the arc path has high resistance. As a result, short-circuit current is quickly interrupted.
  • 20. Important Terms of Fuse (i) Current rating of fuse element. It is the current which the fuse element can normally carry without overheating or melting. It depends upon the temperature rise of the contacts of the fuse holder, fuse material and the surroundings of the fuse. (ii) Fusing current. It is the minimum current at which the fuse element melts and thus disconnects the circuit protected by it. Obviously, its value will be more than the current rating of the fuse element.
  • 21.
  • 22. iii) Fusing factor. It is the ratio of minimum fusing current to the current rating of the fuse element i.e.
  • 23. (iv) Prospective Current The r.m.s.value of the first loop of fault current is known as prospective current. Therefore, prospective current can be defined as under: It is the r.m.s. value of the first loop of the fault current obtained if the fuse is replaced by an ordinary conductor of negligible resistance.
  • 24. (v) Cut-off current. It is the maximum value of fault current actually reached before the fuse melts. (vi) Pre-arcing time. It is the time between the commencement of fault and the instant when cut off occurs. When a fault occurs, the fault current rises rapidly and generates heat in the fuse element. As the fault current reaches the cut off value, the fuse element melts and an arc in initiated. The time from the start of the fault to the instant the arc is initiated is known as pre-arcing time. The pre-arcing time is generally small : a typical value being 0·001second
  • 25. (vii) Arcing time. This is the time between the end of pre-arcing time and the instant when the arc is extinguished. (viii) Total operating time. It is the sum of pre-arcing and arcing times. It may be noted that operating time of a fuse is generally quite low (say 0·002 sec.) as compared to a circuit breaker (say 0·2 sec or so). This is an added advantage of a fuse over a circuit breaker. A fuse in series with a circuit breaker of low-breaking capacity is a useful and economical arrangement to provide adequate short-circuit protection. It is because the fuse will blow under fault conditions before the circuit breaker has the time to operate.
  • 26. (ix) Breaking capacity. It is the r.m.s. value of a.c. component of maximum prospective current that a fuse can deal with at rated service voltage.
  • 27. HRC fuse Construction of HRC fuse: HRC fuse mainly consists of heat resisting ceramic body. The current carrying element is compactly surrounded by the filling powder. Filling material acts as an arc quenching and cooling medium when the fuse element blows off due to excessive heat generated under abnormal conditions.
  • 28. Working: Under normal conditions, the fuse element is at a temperature below its melting point. Therefore, it carries the normal current without overheating. When a fault occurs, the current increases and the heat produced is sufficient to melt these elements. Fuse element melts before the fault current reaches its first peak value. Vaporized metal /fuse element chemically reacts with filling powder and results in the formation of high resistance substance that helps in quenching the arc.
  • 29. Advantages / Merits 1. When compared to other circuit interrupters of same capacity HRC fuses are the cheaper one. 2. Simple and easy to install. 3. No maintenance required. 4. High breaking capacity. 5. They are consistent in performance. 6. Their inverse time characteristic makes them much suited for overload protection. 7. They are capable of clearing high as well as low currents. 8. Quick operation. Disadvantages / Demerits 1. These fuses once blown out cannot be reused. 2. Heat produced by the arc may affect the associated switches. 3. Causes over heating of adjacent contacts. 4. The current-time characteristic of a fuse cannot always be correlated with that of the protective device.
  • 30. Application of HRC Fuses: 1. Protection of radial lines. 2. Transformer protection. 3. It is also used of capacitor protection. 4. It is also provide protection of underground distribution system. 5. It is used in meter board in residential application.
  • 31. Arc formation process • When a short-circuit occurs, a heavy current flows through the contacts of the circuit breaker before they are opened by the protective system. • At the instant when the contacts begin to separate the contact area decreases rapidly and large fault current causes increased current density and hence rise in temperature. • The heat produced in the medium between contacts (usually the medium is oil or air) is sufficient to ionise the air or vapourise and ionise the oil. The ionised air or vapour ,acts as conductor and an arc is struck between the contacts. • The potential difference between the contacts is quite small and is just sufficient to maintain the arc. The arc provides a low resistance path and consequently the current in the circuit remains uninterrupted so long as the arc persists.
  • 32. During the arcing period, the current flowing between the contacts depends upon the arc resistance. The greater the arc resistance, the smaller the current that flows between the contacts. The arc resistance depends upon the following factors: Degree of ionization - the arc resistance increases with the decrease in the number of ionised particles between the contacts. Length of the arc - the arc resistance increases with the length of the arc i.e. separation of contacts. Cross section of arc - the arc resistance increase with the decrease in the area of cross section of the arc.
  • 33. Methods of arc extinction (HT & LT method) There are two methods of extinguishing the arc in circuit breakers. 1. High resistance method 2. Low resistance or current zero method.
  • 34. 1. High Resistance Method In this method, arc resistance is made to increase with time so that current is reduced to a value insufficient to maintain the arc. Consequently, the current is interrupted or the arc is extinguished. The principal disadvantage of this method is that enormous energy is dissipated in the arc. Therefore, it is employed only in d.c. circuit breakers Land low-capacity a.c. circuit breakers.
  • 35. The resistance of the arc may be increased by Lengthening the arc - The resistance of the arc is directly proportional to its length. The length of the arc can be increased by increasing the gap between contacts. Cooling the arc - Cooling helps in medium between the contacts. This increases the arc may be obtained by a gas resistance. Efficient cooling blast directed along the arc. Reducing X-section of the arc - If the area of X-section of the arc is reduced, the voltage necessary to maintain the arc is increased. In other words, the resistance of the arc path is increased. The cross-section of the arc can be reduced by letting the arc pass through a narrow opening or by having smaller area of contacts. Splitting the arc - The resistance of the arc can be increased by splitting the arc into a number of smaller arcs in series. Each one of these arcs experiences the effect of lengthening and cooling. The arc may be split by introducing some conducting plates between the contacts.
  • 36. 2. Low Resistance or Current zero Method • This method is employed for arc extinction in AC Circuits only. In this method, arc resistance is kept low until current zero where the arc extinguishes naturally and is prevented from restriking inspite of the rising voltage across the contacts. • All modern high power AC Circuit Breakers employ this method for arc extinction. In an a.c. system, current drops to zero after every half-cycle. At every current zero, the arc extinguishes for a brief moment. • Now the medium between the contacts contains ions and electrons so that it has small dielectric strength and can be easily broken down by the rising contact voltage known as restriking voltage. If such a break-down does occur, the arc will persist for another half-cycle. If immediately after current zero, the dielectric strength of the medium between contacts is built up more rapidly than the voltage across the contacts, the arc fails to restrike and the current will be interrupted.
  • 37. The rapid increase of dielectric strength of the medium near current zero can be achieved by- • causing the ionised particles in the space between contacts to recombine into neutral molecules. • sweeping the ionised particles away and replacing them by unionised particles. Therefore, the real problem in AC arc interruption is to rapidly deionise the medium between contacts as soon as the current becomes zero so that the rising contact voltage or restriking voltage cannot breakdown the space between contacts.
  • 38. The deionisation of the medium can be achieved by : (i)Lengthening of the gap : The dielectric strength of the medium is proportional to the length of the gap between contacts. Therefore, by opening the contacts rapidly, higher dielectric strength of the medium can be achieved. (ii)High pressure: If the pressure in the vicinity of the arc, is increased, the density of the particles constituting the' discharge also increases. The increased density of particles causes higher rate of deionisation and consequently the dielectric strength of the medium between contacts is increased. (iii)Cooling : Natural combination of ionised particles takes place more rapidly if they are allowed to cool. Therefore, dielectric strength of the medium between the contacts can be increased by cooling the arc. (iv)Blast effect : If the ionised particles between the contacts are swept away and replaced by un-ionised particles, the dielectric strength of the medium can be increased consider-ably. This may be achieved by a gas blast directed along the discharge or by forcing oil into the contact space.
  • 39. Circuit Breaker Ratings A circuit breaker may be called upon to operate under all conditions. However, major duties are imposed on the circuit breaker when there is a fault on the system in which it is connected. Under fault conditions, a circuit breaker is required to perform the following three duties : 1. It must be capable of opening the faulty circuit and breaking the fault current. 2. It must be capable of being closed on to a fault. 3. It must be capable of carrying fault current for a short time while another circuit breaker (in series) is clearing the fault. The rating of a circuit breaker includes I. Breaking capacity or Rated short circuit breaking current. II. Making capacity or Rated short circuit making current. III. Short-time capacity or Rated short time current.
  • 40. • Breaking capacity : This is the maximum short circuit current which a circuit breaker can withstand before it, finally cleared by opening its contacts. • It is a common practice to express the breaking capacity in MVA by taking into account the rated breaking current and rated service voltage. Thus, if I is the rated breaking current in amperes and V is the rated service line voltage in volts, then for a 3-phase circuit.
  • 41. • Making capacity The peak value of current during the first cycle of current wave after the closure of circuit breaker is known as making capacity.
  • 42. • Short-time capacity It is the period for which the circuit breaker is able to carry fault current while remaining closed. • The short-time rating of a circuit breaker depends upon its ability to withstand- (a) the electromagnetic force effects and (b) the temperature rise. The oil circuit breakers have a specified limit of 3 seconds when the ratio of symmetrical breaking current to the rated normal current does not exceed 40. However, if this ratio is more than 40, then the specified limit is 1 second.
  • 43. • Circuit Breaker Terminology. • Arc Voltage. It is the voltage that appears across the contacts of the circuit breaker during the arcing period.
  • 44. • Pre-arcing time. It is the time between the commencement of fault and the instant when cut off occurs. • Arcing time. This is the time between the end of pre- arcing time and the instant when the arc is extinguished. • Prospective Current. It is the r.m.s. value of the first loop of the fault current obtained if the use is replaced by an ordinary conductor of eligible resistance. • Cut-off current. It is the maximum value of fault current actually reached before the CB opens its contacts.
  • 45. • Total operating time. It is the sum of pre-arcing and arcing times. • Breaking capacity. It is the r.m.s. value of a.c. component of maximum prospective current that a CB can deal with at rated service voltage
  • 46. • Restriking voltage It is the transient voltage that appears across the contacts at or near current zero during arcing period. • Recovery voltage. It is the normal frequency (50 Hz) r.m.s. voltage that appears across the contacts of the circuit breaker after final arc extinction. It is approximately equal to the system voltage.
  • 47. • RRRV (Rate Of Rise Of The Restriking Voltage): The RRRV (rate of rise of the restriking voltage) is defined as the slope of the steepest tangent to the restriking voltage curve. It is expressed in volts per micro-second. • TRV (Transient Recovery Voltage) :TRV is the voltage difference observed between the breaker terminals immediately after the current interruption of the breaker. • Total Break Time Fault clearing time is the sum of "relay time" and "circuit breaker time". Circuit breaker time is also called "total break time“
  • 48. • Classification of Circuit Breakers There are several ways of classifying the circuit breakers. However, the most general way of classification is on the basis of medium used for arc extinction. (i) Oil circuit breakers: which employ some insulating oil (e.g., transformer oil) for arc extinction. (ii) Air-blast circuit breakers: In which high pressure air-blast is used for extinguishing the arc. (iii) Sulphur hexafluoride circuit breakers : In which sulphur hexafluoride (SF6) gas is used for arc extinction. (iv)Vacuum circuit breakers : In which vacuum is used for arc extinction. Each type of circuit breaker has its own advantages and disadvantages. In the following sections, we shall discuss the construction and working of these circuit breakers with special emphasis on the way the arc extinction is facilitated.
  • 49. Working of Circuit Breaker by Trip Circuit Mechanism When a short circuit occurs at point F on the transmission line, the current flowing in the line increases to an enormous value. This results in a heavy current flow through the relay coil, causing the relay to operate by closing its contacts. This in turn closes the trip circuit of the breaker, making the circuit breaker open and isolating the faulty section from the rest of the system. In this way, the relay ensures the safety of the circuit equipment from damage and normal working of the healthy portion of the system.
  • 51.
  • 52. Principle of Working A plain-break oil circuit breaker involves the simple process of separating the contacts under the whole of the oil in the tank. There is no special system for arc control other than the increase in length caused by the separation of contacts. The arc extinction occurs when a certain critical gap between the contacts is reached.
  • 53. Construction It consists of fixed and moving contacts enclosed in a strong weather-tight earthed tank containing oil up to a certain level and an air cushion above the oil level. The air cushion provides sufficient room to allow for the reception of the arc gases without the generation of unsafe pressure in the dome of the circuit breaker. It also absorbs the mechanical shock of the upward oil movement.
  • 54. Working under normal operating conditions, the fixed and moving contacts remain closed and the breaker carries the normal circuit current. When a fault occurs, the moving contacts are pulled down by the protective system and an arc is struck which vaporizes the oil mainly into hydrogen gas. • The arc extinction is facilitated by the following processes : 1. The hydrogen gas bubble generated around the arc cools the arc column and aids the deionization of the medium between the contacts. 2. The gas sets up turbulence in the oil and helps in eliminating the arcing products from the arc path. 3. As the arc lengthens due to the separating contacts, the dielectric strength of the medium is increased. The result of these actions is that at some critical gap length, the arc is extinguished and the circuit current is interrupted.
  • 55. Advantages of plain break oil circuit breakers 1. Oil produces hydrogen during arcing. The hydrogen helps extinguish the arc. 2. The oil provides insulation for the live exposed contacts from the earthed portions of the container. 3. Oil provides insulation between the contacts after the arc has been extinguished. Disadvantages of plain break oil circuit breakers 1. There is no special control over the arc other than the increase in length by separating the moving contacts. Therefore, for successful interruption, long arc length is necessary. 2. These breakers have long and inconsistent arcing times. 3. These breakers do not permit high speed interruption.
  • 56. Applications Plain Break Oil CB 1. Plain-break oil circuit breakers are used only for low-voltage applications. 2. It is a usual practice to use such breakers for low capacity installations for voltages not exceeding 11 kV.
  • 57. ACB- Air Circuit Breaker (Axial blast)
  • 58.
  • 59. Construction : • Fig .shows the essential components of a typical axial blast air circuit breaker. The fixed and moving contacts are held in the closed position by spring pressure under normal conditions. The air reservoir is connected to the arcing chamber through an air valve. • This valve remains closed under normal conditions but opens automatically by the tripping impulse when a fault occurs on the system . When a fault occurs, the tripping impulse causes opening of the air valve which connects the circuit breaker reservoir to the arcing chamber. • The high pressure air entering the arcing chamber pushes away the moving contact against spring pressure. The moving contact is separated and an arc is struck. At the same time, high pressure air blast flows along the arc and takes away the ionised gases along with it. Consequently, the arc is extinguished and current flow is interrupted. • In such circuit breakers, the contact separation required for interruption is generally small (1·75 cm or so). Such a small gap may constitute inadequate clearance for the normal service voltage. Therefore, an isolating switch is incorporated as a part of this type of circuit breaker. This switch opens immediately after fault interruption to provide the necessary clearance for insulation
  • 60. Working : The fixed and moving contacts are held in closed position by spring pressure under normal condition. When a fault occurs, the tripping impulse causes opening of the air valve, which connects the C.B. reservoir to the arcing chamber pushes away the moving contacts against spring pressure. The moving contact is separated and arc is struck. At the same time, high pressure air blast flows along the arc and arc gets extinguish.
  • 61. ACB- Air Circuit Breaker (cross blast)
  • 62. Construction: In this type of circuit breaker, an air-blast is directed at right angles to the arc. The cross-blast lengthens and forces the arc into a suitable chute for arc extinction. Fig. shows the essential parts of a typical cross-blast air circuit breaker. working : When the moving contact is withdrawn, an arc is struck between the fixed and moving contacts. The high pressure cross-blast forces the arc into a chute consisting of arc splitters and baffles. The splitters serve to increase the length of the arc and baffles give improved cooling. The result is that arc is extinguished and flow of current is interrupted. Since blast pressure is same for all currents, the inefficiency at low currents is eliminated. The final gap for interruption is great enough to give normal insulation clearance so that a series isolating switch is not necessary.
  • 63. Advantages air-blast circuit breakers (i) The risk of fire is eliminated. (ii) The arcing products are completely removed by the blast whereas the oil deteriorates with successive operations; the expense of regular oil replacement is avoided. (iii) The growth of dielectric strength is so rapid that final contact gap needed for arc extinction is very small. This reduces the size of the device. (iv) The arcing time is very small due to the rapid build up of dielectric strength between contacts. Therefore, the arc energy is only a fraction of that in oil circuit breakers, thus resulting in less burning of contacts. (v) Due to lesser arc energy, air-blast circuit breakers are very suitable for conditions where frequent operation is required. (vi) The energy supplied for arc extinction is obtained from high pressure air and is independent of the current to be interrupted.
  • 64. Disadvantages air-blast circuit breaker (i) The air has relatively inferior arc extinguishing properties. (ii)The air-blast circuit breakers are very sensitive to the variations in the rate of rise of restriking voltage. (iii) Considerable maintenance is required for the compressor plant which supplies the air-blast.
  • 65. Applications air-blast circuit breaker The air blast circuit breakers are finding wide applications in high voltage installations. Majority of the circuit breakers for voltages beyond 110 kV are of this type.
  • 67. • Construction : • The moving cylinder is coupled with the movable conductor against the fixed piston, and there is a relative movement between the moving cylinder and the fixed piston. • The gas is compressed in the cavity. • This trapped gas is released through the nozzle, during arc extinction process. • During the travel, of the moving contact and the movable cylinder, the gas puffs over the arc and reduces the arc diameter by axial convection and radial dissipation. • At current zero, the arc diameter becomes too small and the arc gets extinguished • The puffing action continues for some time, even after the arc extinction, and the contact space is filled with cool, fresh gas.
  • 68. • Working : • SF6 is a Gas type circuit breaker since SF6 gas is used in it for extinguishing the arc. The quenching of arc in SF6 circuit breaker takes place due to the puffer phenomenon taking place inside this circuit breaker Puffer means quick & short blast of gas on the arc. In SF6 C.B blast the SF6 gas is made on the arc through puffer action & the arc gets quenched • As shown in fig above, the fixed & moving contacts are kept in insulating nozzle section. The whole assembly i.e insulating nozzle, puffer action cylinder with moving contact ,a fixed piston is provided to it through the other end of moving contact. The chamber is filled with SF6gas. Under normal working condition, the contacts are closed but on the fault , the contacts open so moving contacts move right & SF6 gas move left side.
  • 69. • An arc is struck between the moving contact & fixed contact. The travel of movable cylinder causes increase in pressure on SF6 gas & this high pressure SF6 gas travels towards arc i.e it puffs over the arc or in simple we can say it blast over the arc • so when this puffer action is completed the arc gets extinguished. This type of C.B is called simple SF6 C.B. but it has limitation of refilling the SF6 which is has by disconnecting from its circuit for this we introduced Double pressure dead type SF6.
  • 70. Non Puffer Type SF6 CB
  • 71.
  • 72. Construction. Fig. shows the parts of a typical SF6 circuit breaker. It consists of fixed and moving contacts enclosed in a chamber (called arc interruption chamber) containing SF6 gas. This chamber is connected to SF6 gas reservoir. When the contacts of breaker are opened, the valve mechanism permits a high pressure SF6 gas from the reservoir to flow towards the arc interruption chamber.
  • 73. • The fixed contact is a hollow cylindrical current carrying contact fitted with an arc horn. The moving contact is also a hollow cylinder with rectangular holes in the sides to permit the SF6 gas to let out through these holes after flowing along and across the arc. • The tips of fixed contact, moving contact and arcing horn are coated with copper-tungsten arc resistant material.
  • 74. Working. • When the breaker operates, the moving contact is pulled apart and an arc is struck between the contacts. • The movement of the moving contact is synchronised with the opening of a valve which permits SF6 gas at 14 kg/cm2 pressure from the reservoir to the arc interruption chamber. The high pressure flow of SF6 rapidly absorbs the free electrons in the arc path. • The result is that the medium between the contacts quickly builds up high dielectric strength and causes the extinction of the arc . After the breaker operation (i.e., after arc extinction), the valve is closed by the action of a set of springs.
  • 75. Advantages: (i) Due to the superior arc quenching property of SF6, such circuit breakers have very short arcing time. (ii) Since the dielectric strength of SF6 gas is 2 to 3 times that of air, such breakers can interrupt much larger currents. (iii) The SF6 circuit breaker gives noiseless operation due to its closed gas circuit and no exhaust to atmosphere unlike the air blast circuit breaker. iv) The closed gas enclosure keeps the interior dry so that there is no moisture problem.
  • 76. (v) There is no risk of fire in such breakers because SF6 gas is non-inflammable. (vi) There are no carbon deposits so that tracking and insulation problems are eliminated. (vii) The SF6 breakers have low maintenance cost, light foundation requirements and minimum auxiliary equipment. (viii) Since SF6 breakers are totally enclosed and sealed from atmosphere, they are particularly suitable where explosion hazard exists e.g., coal mines.
  • 77. Disadvantages (i) SF6 breakers are costly due to the high cost of SF6. (ii)Since SF6 gas has to be reconditioned after every operation of the breaker, additional equipment is required for this purpose.
  • 78. Applications. A typical SF6 circuit breaker is uses for the voltage range 50kV to 230kV. Power Ratings 10MVA to 20MVA and interrupting time less than 3 cycles.
  • 80.
  • 81. Vacuum Circuit Breakers (VCB) In such breakers, vacuum (degree of vacuum being in the range from 10−7 to 10−5 torr) is used as the arc quenching medium. Since vacuum offers the highest insulating strength, it has far superior arc quenching properties than any other medium. For example, when contacts of a breaker are opened in vacuum, the interruption occurs at first current zero with dielectric strength between the contacts building up at a rate thousands of times higher than that obtained with other circuit breakers.
  • 82. Working Principle. • When the contacts of the breaker are opened in vacuum (10−7 to 10−5 torr), an arc is produced between the contacts by the ionisation of metal vapours of contacts. • However, the arc is quickly extinguished because the metallic vapours, electrons and ions produced during arc rapidly condense on the surfaces of the circuit breaker contacts, resulting in quick recovery of dielectric strength. • As soon as the arc is produced in vacuum, it is quickly extinguished due to the fast rate of recovery of dielectric strength in vacuum. the arc extinction in a vacuum breaker occurs with a short contact separation (say 0·625 cm).
  • 83. Construction : Fig. shows the parts of a typical vacuum circuit breaker. It consists of fixed contact, moving contact and arc shield mounted inside a vacuum chamber. The movable member is connected to the control mechanism by stainless steel bellows. This enables the permanent sealing of the vacuum chamber so as to eliminate the possibility of leak. A glass vessel or ceramic vessel is used as the outer insulating body. The arc shield prevents the deterioration of the internal dielectric strength by preventing metallic vapours falling on the inside surface of the outer insulating cover.
  • 84. Working. When the breaker operates, the moving contact separates from the fixed contact and an arc is struck between the contacts. The production of arc is due to the ionisation of metal ions and depends very much upon the material of contacts. The arc is quickly extinguished because the metallic vapours, electrons and ions produced during arc are diffused in a short time and seized by the surfaces of moving and fixed members and shields. Since vacuum has very fast rate of recovery of dielectric strength,
  • 85. Advantages. 1. They are compact, reliable and have longer life. 2. There are no fire hazards. 3. There is no generation of gas during and after operation. 4. They can interrupt heavy fault current perfectly just before the contacts reach the definite open position. 5. They require little maintenance and are quiet in operation. 6. They can successfully withstand lightning surges. 7. They have low arc energy. 8. They have low inertia and hence require smaller power for control mechanism.
  • 86. Applications. Vacuum circuit breakers are being employed for outdoor applications ranging from 22 kV to 66 kV.
  • 87. • Features of Intelligent Circuit Breaker 1. It has Easy User setting facility. 2. Over load alarm function. 3. Display function. 4. Self diagnosis function. 5. Fault memory storage. 6. LED indication of Trip condition.
  • 88. Maintenance Schedule of OCB,ACB, SF6 and VCB Circuit Breakers • For maintenance of circuit breaker , it must be first switched off and then isolated from both sides by opening concerned electrical isolator. • Daily Maintenance Schedule for all CB’s- Physical appearance Doors and covers to be bolted. Check for noise, smell or damage.
  • 89. Oil Circuit Breaker Maintenance • For oil circuit breaker, we should check contact burning. If burning is very light, remove the burn beads and polish the surface. • check & Clean the extinguishing chamber. • Half yearly-The proper adjustment of auxiliary switch by ensuring correct NO NC contacts at breaker OFF and ON condition must be checked • The spring charging motor and mechanism should also be cleaned and associated bearing should also be lubricated half yearly.
  • 90. Maintenance of Air Blast Circuit Breaker Yearly & half Yearly • In air circuit breaker, the air leakage should be checked monthly. • Yearly, dew point of the operating air at the outlet of the air dryer should be measured with the help of Dew Point Meter or Hygro Meters.
  • 91. SF6 Circuit Breaker Maintenance Yearly & half Yearly • SF6 circuit breaker must be checked for SF6 gas leakage. • Dew point of SF6 should be checked with the help of dew point meter or hygro meters in every 3 to 4 years interval.
  • 92. • Maintenance of Vacuum Circuit Breaker Yearly & half Yearly • Using a clean, dry cloth, remove all dirt and moisture from insulating parts. • Inspect the entire circuit breaker and operating mechanism for loose hardware and worn or broken parts. Check all wiring for loose connections and damaged insulation. Inspect all bearings and contact surfaces for damage or excessive wear. • All ball and roller bearings used in these circuit breakers are sealed; they do not require lubrication.
  • 93. Comparisons between fuse and circuit breaker. Particular FUSE CIRCUIT BREAKER Working Principle Fuse works on the electrical and thermal properties of the conducting materials. Circuit breaker works on the Electromagnetism and switching principle. Reusability Fuses can be used only once. Circuit breakers can be used a number of times. Status indication It does not give any indication. It gives an indication of the status Auxiliary contact No auxiliary contact is required. They are available with auxiliary contact. Switching Action Fuse cannot be used as an ON/OFF switch. The Circuit breaker is used e as ON/OFF switches. Breaking capacity Breaking capacity of the fuse is low as compared to the circuit breaker. Breaking capacity is high. Operating time Operating time of fuse is very less (0.002 seconds) Operating time is comparatively more than that of the fuse. (0.02 – 0.05 seconds)
  • 94. MODEL QUESTION BANK Cognitive Level: Remember 1. List different Switchgear equipment 2. List Differences between Indoor type and Outdoor type Switchgear 3. List Desirable Characteristics of Fuse elements 4. List Fuse Element Materials 5. State Merits and Demerits of HRC fuse 6. List any 3 Application of HRC fuse 7. List the different methods of arc extinction 8. List different circuit breakers 9. List the Features of Intelligent Circuit Breaker 10. State Merits and Demerits of Plain oil OCB
  • 95. 11. State Merits and Demerits of Air circuit breaker 12. State Merits and Demerits of SF6 CB 13.State Merits and Demerits of Vacuum Circuit breaker 14. List the Applications of OCB 15. List the Applications of ACB 16. List the Applications of SF6 CB 17. List the Applications of VCB 18. Lists the steps in maintenance of OCB 19. Lists the steps in maintenance of SF6 CB 20. Lists the steps in maintenance of ACB 21. Define breaking capacity, making capacity and Sort time rating 22. Lists the steps in maintenance of VCB
  • 96. Cognitive Level: Understanding 23. Explain Essential features of Switchgear 24. Explain Switchgear equipment 25. Explain terms: Terms: Current Rating of Fuse element, Fusing current, Fusing factor, Prospective current, cut off current , Pre Arcing Time, Arcing Time, Breaking Capacity, Total Operating Time. 26. Explain construction and working of HRC fuse 27. Explain the different methods of arc extinction 28. Explain Arc Extinction phenomena in CB by high resistance method 29. Illustrate the working of Circuit Breaker by Trip Circuit Mechanism 30. Explain circuit breaker rating
  • 97. 31. Explain the terminologies – Arc-Voltage, arching Time, Pre –Arching Time, Prospective Current, T R V, Recovery Voltage, R RR V, Total Break Time 32. Explain Working principle of Circuit Breakers 33. Explain construction and working of Plain oil OCB ACB 34. Explain construction and working of Axial blast ACB 35. Explain construction and working of cross blast ACB 36. Explain construction and working of Puffer Type SF6 CB 37. Explain construction and working of Non Puffer Type SF6 CB 38. Explain construction and working of VACUUM CB 39. Differentiate between fuse and circuit breaker
  • 98. Cognitive Level: Application/Analyze 1. Compare fuse and circuit breaker. 2. Explain Working principle of Circuit Breakers 3. Explain Essential features of Switchgear 4. Explain Switchgear equipment 5. Explain terms: Terms: Current Rating of Fuse element, Fusing current, Fusing factor, Prospective current, cut off current , Pre Arcing Time, Arcing Time, Breaking Capacity, Total Operating Time. 6. Explain construction and working of HRC fuse 7. Explain the different methods of arc extinction 8. Explain breaking capacity of CB 9. Explain making capacity of CB 10. Explain Short time rating of CB