1325 North 108th E. Ave.
Tulsa, OK 74116
918.437.8333 ph. | 918.437.8487 fx.
Page 1 of 3
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM THIS REPORT IS
NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL PROJECT FILE REFERENCED.
THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
CLIENT: Nova Industries
8011 North 154th
East Avenue
Owasso, OK 74055
Attn: Tim Borgne
Test Report No: TJ1409 Date: July 23, 2013
SAMPLE ID: The client submitted and identified the following test material as “Duct Armor”
SAMPLING DETAIL: Test samples were submitted to the laboratory directly by the client. No special
sampling conditions or sample preparation were observed by QAI.
DATE OF RECEIPT: Samples were received at QAI on 6/20/13
TESTING PERIOD: July 1, 2013
AUTHORIZATION: Signed Proposal No. SP060713-2
TEST REQUESTED: Perform standard flame spread and smoke density developed classification tests on
the sample supplied by the Client in accordance with ASTM E2768-11 “Standard Test
Method for Extended Duration Surface Burning Characteristics of Building Materials (
30 min Tunnel Test). This method is similar to UBC No. 8-1 per Chapter 7A of the
2001 California Building Code, Ignition-Resistant Material 30 minute test
TEST RESULTS: Flame Spread Smoke Developed
10 @ 10:00 30 @ 10:00
Detailed test results are presented in the subsequent pages of this report
PREPARED BY SIGNED FOR AND ON BEHALF OF
QAI LABORATORIES, INC.
David Bauchmoyer J. Brian McDonald
Fire Test Technician Operations Manager
Nova Industries Inc.
Report No.: TJ1409
July 23, 2013
Page 2 of 3
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM THIS REPORT IS
NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL PROJECT FILE REFERENCED.
THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
E 84 TEST DATA SHEET:
CLIENT: Nova Industries DATE: July 1, 2013
SAMPLE: Duct Armor
FLAME SPREAD:
IGNITION: 3 Min. and 3 Sec.
FLAME FRONT: 4 feet maximum
TIME TO MAXIMUM FLAME SPREAD: 4 feet at 6 minutes
TEST DURATION: 10 minutes
SUMMARY: FLAME SPREAD: 10 @ 10:00 SMOKE DEVELOPED: 30 @ 10:00
SUMMARY OF ASTM E84 RESULTS: Because of the possible variations in reproducibility, the results are
adjusted to the nearest figure divisible by 5. Smoke Density values over 200 are rounded to the nearest
figure divisible by 50.
In order to obtain the Flame Spread Classification, the above results should be compared to the following
table:
NFPA CLASS IBC CLASS FLAME SPREAD SMOKE DEVELOPED
A A 0 through 25 Less than or equal to 450
B B 26 through 75 Less than or equal to 450
C C 76 through 200 Less than or equal to 450
BUILDING CODES CITED:
1. National Fire Protection Association, ANSI/NFPA No. 101, "Life Safety Code", 2006 Edition.
2. International Building Code, 2006 Edition, Chapter 8, Interior Finishes, Section 803.
Nova Industries Inc.
Report No.: TJ1409
July 23, 2013
Page 3 of 3
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM THIS REPORT IS
NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL PROJECT FILE REFERENCED.
THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
*******
END OF REPORT

More Related Content

Viewers also liked

NASA 2004 PP
NASA 2004 PPNASA 2004 PP
NASA 2004 PP
Robert Edwards
 
IAEA_report
IAEA_reportIAEA_report
IAEA_report
Robert Edwards
 
Special Olympics Summer Games 2015
Special Olympics Summer Games 2015Special Olympics Summer Games 2015
Special Olympics Summer Games 2015Robert Edwards
 
MINDSHARE Vol 2 Issue 3
MINDSHARE Vol 2 Issue 3MINDSHARE Vol 2 Issue 3
MINDSHARE Vol 2 Issue 3
Maryam Kalhor
 
Qcl 14-v3 introduction to flow charting-banasthali vidyapith_geetika gautam(1)
Qcl 14-v3 introduction to flow charting-banasthali vidyapith_geetika gautam(1)Qcl 14-v3 introduction to flow charting-banasthali vidyapith_geetika gautam(1)
Qcl 14-v3 introduction to flow charting-banasthali vidyapith_geetika gautam(1)
geetugeeti
 
Elastisitas X-MIA D
Elastisitas X-MIA DElastisitas X-MIA D
Elastisitas X-MIA D
Vherendio
 
y-HR-Loama - LinkedIn
y-HR-Loama - LinkedIny-HR-Loama - LinkedIn
y-HR-Loama - LinkedIn
Emad Qabbani
 
Be Equipped portfolio
Be Equipped portfolioBe Equipped portfolio
Be Equipped portfolio
Leah Johnson
 
iface_product catalog
iface_product catalogiface_product catalog
iface_product catalog
Yun Seo Am
 
Beukers LS2014-120 afl 2 (1)
Beukers LS2014-120 afl 2 (1)Beukers LS2014-120 afl 2 (1)
Beukers LS2014-120 afl 2 (1)Elène Beukers
 
ISRAA Presentation copy
ISRAA Presentation copyISRAA Presentation copy
ISRAA Presentation copy
Laura Lueninghoener
 
Rumus Matematika
Rumus  MatematikaRumus  Matematika
Rumus Matematika
NimahRahma
 
Act ind 2 1 hpa
Act ind 2 1 hpaAct ind 2 1 hpa
Act ind 2 1 hpa
Darwin Jose Silva Jurado
 
DIBUJOS CRTICOS
DIBUJOS CRTICOSDIBUJOS CRTICOS
DIBUJOS CRTICOS
Arian Flores
 
Oncoceutics leerink global healthcare 2015
Oncoceutics leerink global healthcare 2015Oncoceutics leerink global healthcare 2015
Oncoceutics leerink global healthcare 2015
oncoceutics
 
York Univ. final-schedule
York Univ. final-scheduleYork Univ. final-schedule
York Univ. final-schedule
Maryam Kalhor
 
IAEA Report-SMRsNP-T-2.2-June2009
IAEA Report-SMRsNP-T-2.2-June2009IAEA Report-SMRsNP-T-2.2-June2009
IAEA Report-SMRsNP-T-2.2-June2009
Robert Edwards
 
Law Journal
Law JournalLaw Journal
Law Journal
Maryam Kalhor
 
DUCT-ARMOR-MSDS-2013
DUCT-ARMOR-MSDS-2013DUCT-ARMOR-MSDS-2013
DUCT-ARMOR-MSDS-2013
Duct Doctors, LLC
 

Viewers also liked (20)

NASA 2004 PP
NASA 2004 PPNASA 2004 PP
NASA 2004 PP
 
IAEA_report
IAEA_reportIAEA_report
IAEA_report
 
Special Olympics Summer Games 2015
Special Olympics Summer Games 2015Special Olympics Summer Games 2015
Special Olympics Summer Games 2015
 
MINDSHARE Vol 2 Issue 3
MINDSHARE Vol 2 Issue 3MINDSHARE Vol 2 Issue 3
MINDSHARE Vol 2 Issue 3
 
Qcl 14-v3 introduction to flow charting-banasthali vidyapith_geetika gautam(1)
Qcl 14-v3 introduction to flow charting-banasthali vidyapith_geetika gautam(1)Qcl 14-v3 introduction to flow charting-banasthali vidyapith_geetika gautam(1)
Qcl 14-v3 introduction to flow charting-banasthali vidyapith_geetika gautam(1)
 
Elastisitas X-MIA D
Elastisitas X-MIA DElastisitas X-MIA D
Elastisitas X-MIA D
 
y-HR-Loama - LinkedIn
y-HR-Loama - LinkedIny-HR-Loama - LinkedIn
y-HR-Loama - LinkedIn
 
Be Equipped portfolio
Be Equipped portfolioBe Equipped portfolio
Be Equipped portfolio
 
iface_product catalog
iface_product catalogiface_product catalog
iface_product catalog
 
Beukers LS2014-120 afl 2 (1)
Beukers LS2014-120 afl 2 (1)Beukers LS2014-120 afl 2 (1)
Beukers LS2014-120 afl 2 (1)
 
ISRAA Presentation copy
ISRAA Presentation copyISRAA Presentation copy
ISRAA Presentation copy
 
Rumus Matematika
Rumus  MatematikaRumus  Matematika
Rumus Matematika
 
Act ind 2 1 hpa
Act ind 2 1 hpaAct ind 2 1 hpa
Act ind 2 1 hpa
 
Special Olympics 2014
Special Olympics 2014Special Olympics 2014
Special Olympics 2014
 
DIBUJOS CRTICOS
DIBUJOS CRTICOSDIBUJOS CRTICOS
DIBUJOS CRTICOS
 
Oncoceutics leerink global healthcare 2015
Oncoceutics leerink global healthcare 2015Oncoceutics leerink global healthcare 2015
Oncoceutics leerink global healthcare 2015
 
York Univ. final-schedule
York Univ. final-scheduleYork Univ. final-schedule
York Univ. final-schedule
 
IAEA Report-SMRsNP-T-2.2-June2009
IAEA Report-SMRsNP-T-2.2-June2009IAEA Report-SMRsNP-T-2.2-June2009
IAEA Report-SMRsNP-T-2.2-June2009
 
Law Journal
Law JournalLaw Journal
Law Journal
 
DUCT-ARMOR-MSDS-2013
DUCT-ARMOR-MSDS-2013DUCT-ARMOR-MSDS-2013
DUCT-ARMOR-MSDS-2013
 

Similar to TJ14091-Nova-Industries-ASTM-E-84

DUCT-ARMOR-ASBESTOS-TEST-630141
DUCT-ARMOR-ASBESTOS-TEST-630141DUCT-ARMOR-ASBESTOS-TEST-630141
DUCT-ARMOR-ASBESTOS-TEST-630141
Duct Doctors, LLC
 
Tamper Evidence Full Test Report for Red Flag LXR June 25, 2010
Tamper Evidence Full Test Report for Red Flag LXR June 25, 2010Tamper Evidence Full Test Report for Red Flag LXR June 25, 2010
Tamper Evidence Full Test Report for Red Flag LXR June 25, 2010
Redflagseals
 
iMovR ZipDesk ANSI/BIFMA X5.5 Test Report
iMovR ZipDesk ANSI/BIFMA X5.5 Test ReportiMovR ZipDesk ANSI/BIFMA X5.5 Test Report
iMovR ZipDesk ANSI/BIFMA X5.5 Test Report
iMovR
 
iMovR Lander Lite - ANSI/BIFMA X5.5-2014 Certification
iMovR Lander Lite - ANSI/BIFMA X5.5-2014 CertificationiMovR Lander Lite - ANSI/BIFMA X5.5-2014 Certification
iMovR Lander Lite - ANSI/BIFMA X5.5-2014 Certification
iMovR
 
ANSI/BIFMA Certification for iMovR Lander Desk - 83"
ANSI/BIFMA Certification for iMovR Lander Desk - 83"ANSI/BIFMA Certification for iMovR Lander Desk - 83"
ANSI/BIFMA Certification for iMovR Lander Desk - 83"
iMovR
 
Mc 4 connector from jmv lps ltd
Mc 4 connector from jmv lps ltdMc 4 connector from jmv lps ltd
Mc 4 connector from jmv lps ltd
Mahesh Chandra Manav
 
AS9100 Certificate
AS9100 CertificateAS9100 Certificate
AS9100 Certificate
Steven Liu
 
Bruperite Testing Report
Bruperite Testing ReportBruperite Testing Report
Bruperite Testing Report
strama3
 
Certif vitosol 100 f sv1 sh1
Certif vitosol 100 f sv1 sh1Certif vitosol 100 f sv1 sh1
Certif vitosol 100 f sv1 sh1
zouloumango
 
ELECTRICAL SAFETY-Fluke.pptx
ELECTRICAL SAFETY-Fluke.pptxELECTRICAL SAFETY-Fluke.pptx
ELECTRICAL SAFETY-Fluke.pptx
ssuserff418c
 
SAR Evaluation Report
SAR Evaluation ReportSAR Evaluation Report
SAR Evaluation Report
DC_Police_Union
 
Full Report ISO 17712:2010 Compliance for Red Flag LXR Cable Seal
Full Report ISO 17712:2010 Compliance for Red Flag LXR Cable SealFull Report ISO 17712:2010 Compliance for Red Flag LXR Cable Seal
Full Report ISO 17712:2010 Compliance for Red Flag LXR Cable Seal
Redflagseals
 
Sample Air Quality Report
Sample Air Quality Report Sample Air Quality Report
Sample Air Quality Report
Exluns
 
ANSI/BIFMA Certification for iMovR Lander Desk - 41"
ANSI/BIFMA Certification for iMovR Lander Desk - 41"ANSI/BIFMA Certification for iMovR Lander Desk - 41"
ANSI/BIFMA Certification for iMovR Lander Desk - 41"
iMovR
 
Custom tint-solutions-austin-san-antonio-window-film-4-mil-stainless-steel-50...
Custom tint-solutions-austin-san-antonio-window-film-4-mil-stainless-steel-50...Custom tint-solutions-austin-san-antonio-window-film-4-mil-stainless-steel-50...
Custom tint-solutions-austin-san-antonio-window-film-4-mil-stainless-steel-50...
CustomTintSolutionsSanAntonio
 
Rohs certificate gyta53 dual jacket armored fiber optic cable for aerial duct...
Rohs certificate gyta53 dual jacket armored fiber optic cable for aerial duct...Rohs certificate gyta53 dual jacket armored fiber optic cable for aerial duct...
Rohs certificate gyta53 dual jacket armored fiber optic cable for aerial duct...
桂凤 周
 
Sample report residential 1[1]
Sample report residential 1[1]Sample report residential 1[1]
Sample report residential 1[1]
SmartChoice Home & Mold Inspections
 
fabric inspection sample report.pdf
fabric inspection sample report.pdffabric inspection sample report.pdf
fabric inspection sample report.pdf
TestcooQualityContro
 
Custom tint-solutions-austin-san-antonio-window-film-4-mil-stainless-steel-35...
Custom tint-solutions-austin-san-antonio-window-film-4-mil-stainless-steel-35...Custom tint-solutions-austin-san-antonio-window-film-4-mil-stainless-steel-35...
Custom tint-solutions-austin-san-antonio-window-film-4-mil-stainless-steel-35...
CustomTintSolutionsSanAntonio
 
Custom tint-solutions-austin-san-antonio-window-tinting-10-mil-stainless-stee...
Custom tint-solutions-austin-san-antonio-window-tinting-10-mil-stainless-stee...Custom tint-solutions-austin-san-antonio-window-tinting-10-mil-stainless-stee...
Custom tint-solutions-austin-san-antonio-window-tinting-10-mil-stainless-stee...
GreenLightWindowFilmsCOSprings
 

Similar to TJ14091-Nova-Industries-ASTM-E-84 (20)

DUCT-ARMOR-ASBESTOS-TEST-630141
DUCT-ARMOR-ASBESTOS-TEST-630141DUCT-ARMOR-ASBESTOS-TEST-630141
DUCT-ARMOR-ASBESTOS-TEST-630141
 
Tamper Evidence Full Test Report for Red Flag LXR June 25, 2010
Tamper Evidence Full Test Report for Red Flag LXR June 25, 2010Tamper Evidence Full Test Report for Red Flag LXR June 25, 2010
Tamper Evidence Full Test Report for Red Flag LXR June 25, 2010
 
iMovR ZipDesk ANSI/BIFMA X5.5 Test Report
iMovR ZipDesk ANSI/BIFMA X5.5 Test ReportiMovR ZipDesk ANSI/BIFMA X5.5 Test Report
iMovR ZipDesk ANSI/BIFMA X5.5 Test Report
 
iMovR Lander Lite - ANSI/BIFMA X5.5-2014 Certification
iMovR Lander Lite - ANSI/BIFMA X5.5-2014 CertificationiMovR Lander Lite - ANSI/BIFMA X5.5-2014 Certification
iMovR Lander Lite - ANSI/BIFMA X5.5-2014 Certification
 
ANSI/BIFMA Certification for iMovR Lander Desk - 83"
ANSI/BIFMA Certification for iMovR Lander Desk - 83"ANSI/BIFMA Certification for iMovR Lander Desk - 83"
ANSI/BIFMA Certification for iMovR Lander Desk - 83"
 
Mc 4 connector from jmv lps ltd
Mc 4 connector from jmv lps ltdMc 4 connector from jmv lps ltd
Mc 4 connector from jmv lps ltd
 
AS9100 Certificate
AS9100 CertificateAS9100 Certificate
AS9100 Certificate
 
Bruperite Testing Report
Bruperite Testing ReportBruperite Testing Report
Bruperite Testing Report
 
Certif vitosol 100 f sv1 sh1
Certif vitosol 100 f sv1 sh1Certif vitosol 100 f sv1 sh1
Certif vitosol 100 f sv1 sh1
 
ELECTRICAL SAFETY-Fluke.pptx
ELECTRICAL SAFETY-Fluke.pptxELECTRICAL SAFETY-Fluke.pptx
ELECTRICAL SAFETY-Fluke.pptx
 
SAR Evaluation Report
SAR Evaluation ReportSAR Evaluation Report
SAR Evaluation Report
 
Full Report ISO 17712:2010 Compliance for Red Flag LXR Cable Seal
Full Report ISO 17712:2010 Compliance for Red Flag LXR Cable SealFull Report ISO 17712:2010 Compliance for Red Flag LXR Cable Seal
Full Report ISO 17712:2010 Compliance for Red Flag LXR Cable Seal
 
Sample Air Quality Report
Sample Air Quality Report Sample Air Quality Report
Sample Air Quality Report
 
ANSI/BIFMA Certification for iMovR Lander Desk - 41"
ANSI/BIFMA Certification for iMovR Lander Desk - 41"ANSI/BIFMA Certification for iMovR Lander Desk - 41"
ANSI/BIFMA Certification for iMovR Lander Desk - 41"
 
Custom tint-solutions-austin-san-antonio-window-film-4-mil-stainless-steel-50...
Custom tint-solutions-austin-san-antonio-window-film-4-mil-stainless-steel-50...Custom tint-solutions-austin-san-antonio-window-film-4-mil-stainless-steel-50...
Custom tint-solutions-austin-san-antonio-window-film-4-mil-stainless-steel-50...
 
Rohs certificate gyta53 dual jacket armored fiber optic cable for aerial duct...
Rohs certificate gyta53 dual jacket armored fiber optic cable for aerial duct...Rohs certificate gyta53 dual jacket armored fiber optic cable for aerial duct...
Rohs certificate gyta53 dual jacket armored fiber optic cable for aerial duct...
 
Sample report residential 1[1]
Sample report residential 1[1]Sample report residential 1[1]
Sample report residential 1[1]
 
fabric inspection sample report.pdf
fabric inspection sample report.pdffabric inspection sample report.pdf
fabric inspection sample report.pdf
 
Custom tint-solutions-austin-san-antonio-window-film-4-mil-stainless-steel-35...
Custom tint-solutions-austin-san-antonio-window-film-4-mil-stainless-steel-35...Custom tint-solutions-austin-san-antonio-window-film-4-mil-stainless-steel-35...
Custom tint-solutions-austin-san-antonio-window-film-4-mil-stainless-steel-35...
 
Custom tint-solutions-austin-san-antonio-window-tinting-10-mil-stainless-stee...
Custom tint-solutions-austin-san-antonio-window-tinting-10-mil-stainless-stee...Custom tint-solutions-austin-san-antonio-window-tinting-10-mil-stainless-stee...
Custom tint-solutions-austin-san-antonio-window-tinting-10-mil-stainless-stee...
 

TJ14091-Nova-Industries-ASTM-E-84

  • 1. 1325 North 108th E. Ave. Tulsa, OK 74116 918.437.8333 ph. | 918.437.8487 fx. Page 1 of 3 THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED. WWW.QAI.ORG info@qai.org CLIENT: Nova Industries 8011 North 154th East Avenue Owasso, OK 74055 Attn: Tim Borgne Test Report No: TJ1409 Date: July 23, 2013 SAMPLE ID: The client submitted and identified the following test material as “Duct Armor” SAMPLING DETAIL: Test samples were submitted to the laboratory directly by the client. No special sampling conditions or sample preparation were observed by QAI. DATE OF RECEIPT: Samples were received at QAI on 6/20/13 TESTING PERIOD: July 1, 2013 AUTHORIZATION: Signed Proposal No. SP060713-2 TEST REQUESTED: Perform standard flame spread and smoke density developed classification tests on the sample supplied by the Client in accordance with ASTM E2768-11 “Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials ( 30 min Tunnel Test). This method is similar to UBC No. 8-1 per Chapter 7A of the 2001 California Building Code, Ignition-Resistant Material 30 minute test TEST RESULTS: Flame Spread Smoke Developed 10 @ 10:00 30 @ 10:00 Detailed test results are presented in the subsequent pages of this report PREPARED BY SIGNED FOR AND ON BEHALF OF QAI LABORATORIES, INC. David Bauchmoyer J. Brian McDonald Fire Test Technician Operations Manager
  • 2. Nova Industries Inc. Report No.: TJ1409 July 23, 2013 Page 2 of 3 THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED. WWW.QAI.ORG info@qai.org E 84 TEST DATA SHEET: CLIENT: Nova Industries DATE: July 1, 2013 SAMPLE: Duct Armor FLAME SPREAD: IGNITION: 3 Min. and 3 Sec. FLAME FRONT: 4 feet maximum TIME TO MAXIMUM FLAME SPREAD: 4 feet at 6 minutes TEST DURATION: 10 minutes SUMMARY: FLAME SPREAD: 10 @ 10:00 SMOKE DEVELOPED: 30 @ 10:00 SUMMARY OF ASTM E84 RESULTS: Because of the possible variations in reproducibility, the results are adjusted to the nearest figure divisible by 5. Smoke Density values over 200 are rounded to the nearest figure divisible by 50. In order to obtain the Flame Spread Classification, the above results should be compared to the following table: NFPA CLASS IBC CLASS FLAME SPREAD SMOKE DEVELOPED A A 0 through 25 Less than or equal to 450 B B 26 through 75 Less than or equal to 450 C C 76 through 200 Less than or equal to 450 BUILDING CODES CITED: 1. National Fire Protection Association, ANSI/NFPA No. 101, "Life Safety Code", 2006 Edition. 2. International Building Code, 2006 Edition, Chapter 8, Interior Finishes, Section 803.
  • 3. Nova Industries Inc. Report No.: TJ1409 July 23, 2013 Page 3 of 3 THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED. WWW.QAI.ORG info@qai.org ******* END OF REPORT