1. A New Test Method to Measure
the Freeze Thaw Durability of
Fresh Concrete
Braden Tabb, Robert Felice, John Michael
Freeman, Robert Frazier, David Welchel
Tyler Ley, P.E., Ph. D
6. Why Do We Add Air to Concrete?
• Air-entrained bubbles are the key to
the freeze-thaw resistance of concrete
Air volume = Freeze Thaw Performance
• Smaller bubbles are more effective in
providing freeze-thaw resistance than
larger bubbles
7. • Volume of air provided is the same for both circumstances.
• Case B has a lower spacing factor and a higher specific surface.
A B
What Do You Want in an Air-Void System?
8. A B
• Volume of air provided is the same for both circumstances.
• Case B has a lower spacing factor and a higher specific surface.
What Do You Want in an Air-Void System?
16. Summary
• It is common to require a certain
volume of air in concrete in order to
obtain freeze thaw durability
• The volume of air does not equal air
void system quality
• Although, a hardened air void analysis
(ASTM C 457) can measure the air-
void quality it is not practical to run
regularly
17. What do we need?
• We need a test that can quantify air-
void systems quickly in fresh concrete
• Investigate a sample of significant size
• Economical
• Field ready
18. Super Air Meter (SAM)
• We have modified a typical ASTM C
231 pressure meter so that it can hold
larger pressures
• We have replaced the typical gage
with a digital one
• The test takes 8 minutes
28. How does it work?
• We use an algorithm to find a SAM
number.
• The SAM number correlates to air
void distribution
• The meter also measures air volume
29. How can we prove it?
• We made 95 concrete mixtures
• Different AEAs
• Combinations of AEAs and PCs
• Different w/cm (0.39 - 0.53)
• Slumps from 0.25” to 10”
• Air contents from 1.25% to 10%
• Hardened air void analysis (ASTM C
457) was completed on each mixture
• Values were compared to the SAM
number
32. Observations
• When the SAM number is below 0.2
then the spacing factor is below
0.008” for 90% of the samples and
98% of the samples had a spacing
factor below 0.010”
• The SAM number seems to correlate
with the amount of small bubbles in
the sample
33. How Consistent Is It?
• We ran the following on each of the 95
mixtures with two separate SAMs:
– Air contents
– SAM numbers
– ASTM C 457 hardened air void analysis
– Unit Weight
34. y = 1.015x - 0.0227
R² = 0.9932
0
1
2
3
4
5
6
7
8
9
0 1 2 3 4 5 6 7 8 9
SAM2AirContent(%)
SAM 1 Air Content (%)
Mean Difference -0.005%
Standard dev. 0.064%
38. Conclusions
• The SAM test can be completed in
about 10 minutes with fresh concrete
• A SAM number of 0.20 seems to
correlate with the ASTM C 457
spacing factor of 0.008” and freeze
thaw durability as per ASTM C 666
• Two SAMs have been shown to
provide consistent results.