SlideShare a Scribd company logo
1 of 8
Tunnel Ventilation in Livestock Barns —
With and Without Evaporative Cooling
D. Ward, P.Eng.
	 ORDER NO. 13-073	 AGDEX 717 	 OCTOBER 2013
(replaces OMAF Factsheet 00-085, Tunnel Ventilation for Livestock and Poultry Barns)
INTRODUCTION
Ontario’s hot, humid summer weather makes it
difficult for livestock and poultry to perform at their
best. It is important to provide cooling in barns
so animals do not experience heat stress, resulting
in an associated decrease in production. The two
most common methods of cooling are air-based
and water-based. This Factsheet discusses the design
factors and management of tunnel ventilation —
with and without evaporative cooling.
The main method of air-cooling livestock barns in
Ontario is tunnel ventilation. The entire air inlet is
located on one end wall of the barn (Figure 1) with
all of the exhaust fans located on the opposite end
(Figure 2). The idea is to create a high velocity wall
of air moving down the long axis of the building
like a wind tunnel. This provides a beneficial wind
chill effect that cools the animals by convection (the
removal of heat from the surface of an object by an
airstream moving over it) and exhausts this heat out
of the building.
In many parts of the world, evaporative cooling
pads are added to the air inlets of tunnel-ventilated
barns (Figure 3) because there is a critical upper
temperature for tunnel ventilation. Excessive air
movement above 40°C — a chicken’s core body
temperature — increases heat stress experienced by
the animal. At these high temperatures, some form of
evaporative cooling is incorporated into the system to
reduce the effects of the incoming air temperature.
With evaporative cooling, the incoming air is pulled
through a saturated medium (cooling pad). The
process of converting water from a liquid to a vapour
removes heat energy from the incoming air, lowering
its temperature but increasing its relative humidity.
Figure 1.	Tunnel ventilation inlet doors across the end wall
of a barn without evaporative cooling.
Figure 2.	Exhaust fans across the end wall of the barn.
Figure 3.	Tunnel ventilation inlet with evaporative cooling
pads installed.
2
Until recently, these systems were not commonly
used in Ontario. However, following several
summers with prolonged periods of temperatures
higher than 30°C, these systems are being used in
more barns.
AIR-BASED COOLING — TUNNEL VENTILATION
In a cross-flow ventilation system (air flows across
the length of the building) with a slot-type air inlet,
the air speed at the animal level ranges from 0.25 to
0.50 m/s (50–100 ft/min). With tunnel ventilation,
the goal is to achieve an air speed of 1.0–2.5 m/s
(200–500 ft/min) over the animals. The recent
trend in Ontario and elsewhere is to design systems
to operate at even higher airspeeds, with very
good results.
Research conducted by the U.S. Department
of Agriculture Poultry Research Laboratory
at Mississippi State University on 7-week-old
broiler chickens showed that air moving at 1 m/s
(200 ft/min) over the birds results in similar growth
rates to birds raised in still or slow-moving air
that is 1°C cooler. Similarly, air moving at 2 m/s
(400 ft/min) creates a wind chill effect of 3.7°C. The
birds in this trial, grown under tunnel ventilation at
2 m/s, were 0.5 kg heavier at 7 weeks of age than the
birds grown in still air.
Tunnel ventilation is not recommended when
ambient air temperature is below 15°C or for
sensitive, younger animals (baby chicks prior to
feathering), as the wind chill–cooling effect is not
necessary and could be stressful to these animals. For
this reason, when tunnel ventilation is designed for
a building, the normal cross-flow ventilation system
is usually sized to supply 40%–50% of the summer
ventilation requirements to accommodate the three
cooler seasons of the year and for the early growth
stages of sensitive animals.
FAN CAPACITY FOR TUNNEL VENTILATION
The size of the tunnel ventilation system is based
on the amount of power needed to create a wall of
air moving the length of the building at a velocity
of 1.0–2.5 m/s (200–500 ft/min or 3.6–9 km/hr)
or higher. Therefore, the required fan capacity is the
useable barn cross-sectional area multiplied by the
desired air speed. Note that floor-reared birds occupy
the lower 0.3 m (1 ft) of the barn cross-section, so it
is not useable for air movement. Similarly, cattle stalls,
swine pen partitioning, etc., will reduce the net cross-
sectional area available for airflow.
Fan Sizing Example
What is the fan capacity required for an 18-m x 91-m
(60-ft x 300-ft) broiler chicken barn with a 2.7-m
(9-ft) ceiling height and a desired tunnel air speed
of 2.5 m/s (500 ft/min)?
Metric Airflow Q
= (Velocity x Area) x 1,000
= 2.5 m/s x 18 m x (2.7 – 0.3 m) x 1,000
= 108,000 L/s
Imperial Airflow Q
= Velocity x Area
= 500 ft/min x 60 ft x (9 ft – 1 ft)
= 240,000 CFM
The most common fans used for tunnel ventilation
are belt-driven, single-speed 1,200-mm (48-in.)
fans equipped with exhaust cones. These fans have a
high-energy efficiency rating (normally >7.5 L/s/w
(16 CFM/w)).
On average, a 1,200 mm (48 in.) fan will move
approximately 9,400 L/s (20,000 CFM) of air.
Therefore, the number of fans required for this
barn is:
Metric:		 108,000/9,400 = 12 fans
Imperial:	 240,000/20,000 = 12 fans
Other fan sizes, or a combination of fan sizes, are
used and may be desired for a particular situation.
A common problem encountered when designing
a tunnel ventilation system is insufficient room on
the end wall to install all the tunnel fans required
to meet the target airflow. It is acceptable to install
some fans around the corner onto the sidewall as
shown in Figure 2.
3
AIR INTAKE FOR TUNNEL VENTILATION
Tunnel ventilation inlets contain motorized louvers,
curtains, panels or large doors. These openings are
usually sized on the basis of 2 m2
per 5,000 L/s
(2 ft2
/1,000 CFM) of fan capacity. Since air does
not easily turn corners, this type of inlet works
best when located across an end wall so that the
incoming fresh air travels straight into the barn in
the correct airflow direction. As shown in Figure 1,
a large panel door across the end wall provides the
necessary cross-sectional area for the air intake.
Some barns are equipped with a combination of
panels and a roll-up door to achieve the required
inlet opening.
Air Intake Sizing Example
What is the required air intake size for the example
broiler chicken barn already discussed?
Metric Area
= (2 m2
/5,000 L/s) x Airflow Q L/s
= (2 m2
/5,000 L/s) x 108,000 L/s
= 43.2 m2
= 2.59 m x 16.7 m
Imperial Area
= (2 ft2
/1,000 CFM) x Airflow Q CFM
= (2 ft2
/1,000 CFM ) x 240,000 CFM
= 480 ft2
= 8.5 ft x 56.5 ft
TUNNEL VENTILATION CONTROL
Tunnel ventilation is strictly a warm-weather system
and should only be used in temperatures above
21°C for animals that are not overly sensitive to
drafts, such as birds older than 3 weeks of age.
As with normal cross-flow ventilation, stage the
tunnel ventilation system to automatically turn on
when the barn temperature increases. Generally,
2 or 3 tunnel stages are used to manage the barn
conditions. For example, Stage 1 operates the first
group of 2 or 3 tunnel fans, Stage 2 operates another
group of fans and Stage 3 operates the remaining
fans. This control strategy allows a staggered wind
chill effect to match the ambient air conditions
experienced by the animals. As the temperature
increases through the day, the corresponding stages
are activated to create more air flow and as the
cooler night temperatures arrive, the stages are
deactivated in reverse order to decrease air flow.
Normally the cross-flow ventilation system is
turned off completely once the tunnel fans/inlets
are activated. The sidewall fans are turned off, and
the baffle board air inlet is closed to get the full
wind-tunnel effect down the length of the barn.
Remember, the main objective is to remove the hot
air in the barn, as quickly as possible.
4
POTENTIAL TUNNEL AIRFLOW CHALLENGES
Air Inlet Location
Locate air inlets on the end wall if at all possible.
Air will not turn 90° corners unless forced. Any
air entering from the sidewall creates airflow across
the barn rather than along the length. Airflow from
the sidewall inlet will eventually turn and move
endwise to the exhaust fans but will leave a dead
air zone (Figure 4) along the sidewall containing
the inlet panel. Use air deflectors to help turn this
incoming air.
SERVICE OR ENTRANCE ROOM LOCATION
Locate the service or entrance room outside the
main building, as shown in Figure 1, to provide full
end wall exposure for the tunnel air inlet. Besides
reducing the available end wall opening, it creates
a major wind shadow down that side of the room.
An unconfined air stream will fan out at about a
10° angle, and a 2.4-m (8-ft) wide service room will
prevent tunnel air movement along that wall for at
least 14 m (46 ft) (Figure 5). Smoke testing shows
the actual affected distance is even greater due to a
slow, backward eddy-type flow in the wind shadow
area. If an interior room is necessary, locate it near
the tunnel exhaust fans and opposite the winter air
inlet to minimize the amount of airflow blocked.
OUTSIDE WIND EFFECT
Significant summer winds, blowing at an angle into
the tunnel air inlet, can direct the airflow inside
to one side of the barn (Figure 6). This situation
drastically reduces the airflow along the other side
of the room. Compare an outside wind speed of
20 km/hr (12.5 mph) to a typical tunnel air speed of
6 km/hr (3.8 mph) to understand the potential for
the wind to overpower the airflow pattern. Opening
the side air inlet baffle board to introduce more air
to the side with less airflow can help even out the
airflow. Air-deflecting baffles located at the tunnel
inlet have also reduced this problem.
Figure 4.	Floor plan showing dead air zone (shaded area)
due to placement of sidewall tunnel ventilation air inlets.
Figure 5.	Floor plan showing dead air zone (shaded area)
due to obstruction by a service room entrance.
Figure 6.	Floor plan showing a skewed air flow pattern due
to wind effect.
5
CEILING AIR DEFLECTORS
A method of increasing the air speed at animal level,
without installing extra tunnel fans, is to install drop
curtains or other air deflectors from the ceiling every
12–25 m (40–80 ft) along the length of the barn
to reduce the barn cross-sectional area. Limit the
increased air speed to a maximum of 2.5 or 3.0 m/s
(500 or 600 ft/min) to prevent a reduction in fan
performance. This is because too much reduction
in the building cross-sectional area will increase the
static pressure the fan(s) has to work against.
EVAPORATIVE COOLING EQUIPMENT
Design
The evaporative cooling pad is made of fibrous
material woven together, similar to corrugated
cardboard, with large gaps in the grooves. The pad
is mounted vertically over the tunnel air intake. The
bottom of the pad sits in a drain trough, and a water
delivery pipe, with evenly spaced holes, runs across
the top of the pad.
A circulating pump is used to pump the water
from the trough at the bottom of the pad to the
distribution pipe at the top of the pad. When
evaporative cooling is needed, the controller
activates the pump, which delivers water to the
distribution pipe that trickles water down the face of
the pad to wet it.
Fresh water is added into the system via a float
mechanism to replenish the water that is evaporated
into the air stream during the ventilation process
(Figures 7–10).
Figure 7.	 Evaporative cooling pad, showing circulating pump,
cooling pad, fresh water feed pipe (blue pipe) and filter.
Figure 8.	Close-up of water trickling down the outside of
pad surface.
Figure 9.	Inside surface of the evaporative cooling pad
with the insulated door open.
Figure 10.	 Insulated door closed to cover the evaporative
cooling pad.
6
The cooling capability or efficiency of the pad
system is directly related to pad type, size of pad
and the air velocity allowed to pass through the pad.
The cooling efficiency ranges from 55%–75% for
most evaporative cooling pads. Air velocity and size
of the pad are directly related to the fan’s capacity. A
smaller pad area means a higher air velocity through
the pads. Most pad manufacturers recommend a
design air velocity of 1.27-1.78 m/s (250–350 fpm)
through their pads to ensure a long enough contact
time between the air and the wet surface to achieve
the best cooling efficiency.
The most common design problem seen with
evaporative cooling systems is not enough pad area.
Since the wet cooling pad presents a greater barrier
to air flow than a typical tunnel inlet, designers
usually increase the size of the inlet opening for the
evaporative cooling pad to ensure the static pressure
drop across the pad is “limited to” 7.47–22.4 Pa
(0.03-0.09 in.) water column. The recommended
inlet opening size is 2.5 m2
of opening/5,000 L/s
(2.5 ft2
of opening/1,000 CFM).
Evaporative cooling, like all water-based cooling
systems, increases the relative humidity of the air in
the barn space. Ensure the relative humidity in the
barn never exceeds 80% when using an evaporative
cooling pad during warm weather, as this may cause
the animals more distress. For example, poultry
pant to shed heat at higher temperatures (25°C+).
This method of controlling body temperature relies
on evaporative cooling within the bird’s own lungs
to get rid of excess heat from its body. However,
when the bird is placed in a barn with a relative
humidity greater than 80%, it cannot release heat.
The ability of the room air to absorb any additional
moisture above 80% is slowed or lessened. Since the
bird is unable to lose this excess heat, its core body
temperature begins to rise.
OPERATION
With a recirculating pump system, the most
important factor to monitor is the small holes
in the distribution pipe along the top of the
evaporative cooling pad. Ensure these holes are not
plugged and allow water to continually flow evenly
across the pad, as this is essential for good cooling
performance. If the pad is always streaking or there
are dry spots on the pad, the distribution system
likely needs cleaning and/or flushing.
Common reasons for a pad becoming plugged:
•	 High mineral content of feed water. This can
result in mineral deposits or scale forming on the
pad. To avoid this problem, treat the water used
for the evaporative cooling pad through a water
softener to remove the minerals.
•	 Algae growth. Since the pad is made of organic
material and kept in a warm moist state, algae
have a chance to grow on the pad and in the
water collection sump. It is highly recommended
to allow the pad to dry out at least once daily.
Add approved algaecides to the collection sump
to discourage algae growth: check with the
manufacturer for a list of approved products.
The pad materials decay over time due to the
repeated wet/dry cycles and should be replaced
every couple of years. Some corrugated plastic pad
materials have been tested to determine if they
would provide a longer-lasting term alternative
to current cardboard pads. These pads would not
promote algae growth since the plastic is non-
organic. The performance of the plastic pads, in
terms of water evaporation, was not as good as the
cardboard pads.
7
Figure 11.	Evaporative cooling pads with protective covers
(white tarp material) partially closed
WINTER MAINTENANCE
Completely drain the evaporative cooling systems
before freezing temperatures arrive to prevent
damage to the piping and pump.
To protect the pad materials from damage caused by
ultraviolet light, snow, ice, etc., during the winter
months when it is not in use, place a watertight
protective structure over the outside of the pad
(Figure 11).
To prevent moisture migration and heat loss
through the pad from inside the barn during colder
temperatures, install air-tight, insulated panels
on the inside of the tunnel inlets opening (see
Figure 10).
Tunnel ventilation and evaporative cooling systems
are effective methods for relieving heat stress and
enhancing animal performance in hot weather. Both
systems require careful design, operation and regular
maintenance in order to make them work effectively.
This Factsheet was written by Daniel Ward, P.Eng., Poultry
& Other Livestock Housing & Equipment, OMAF, Stratford,
and reviewed by Robert Chambers, P.Eng., Swine & Sheep
Housing and Equipment, OMAF, Elora; Al Dam, Poultry
Specialist, OMAF, Guelph; and Arlene Robertson, Education
Coordinator, OMAF, Guelph.
Published by the Ontario Ministry of Agriculture and Food
and the Ministry of Rural Affairs
© Queen’s Printer for Ontario, 2013, Toronto, Canada
ISSN 1198-712X
Également disponible en français
(Commande no
13-074)
Agricultural Information Contact Centre:
1-877-424-1300
E-mail: ag.info.omafra@ontario.ca
www.ontario.ca/omaf

More Related Content

What's hot

Emergency Alteration in Ventilation
Emergency Alteration in VentilationEmergency Alteration in Ventilation
Emergency Alteration in VentilationJasmeet Singh Saluja
 
Distribution and control of mine air standards of ventilation
Distribution and control of mine air standards of ventilationDistribution and control of mine air standards of ventilation
Distribution and control of mine air standards of ventilationSafdar Ali
 
S3 Duct System Design Consideration
S3 Duct System Design ConsiderationS3 Duct System Design Consideration
S3 Duct System Design Considerationno suhaila
 
Types of air conditioning for HVAC application
Types of air conditioning for HVAC applicationTypes of air conditioning for HVAC application
Types of air conditioning for HVAC applicationVirtu Institute
 
Types Of Centrifugal Fans Used In Power Plant Boilers
Types Of Centrifugal Fans Used In Power Plant BoilersTypes Of Centrifugal Fans Used In Power Plant Boilers
Types Of Centrifugal Fans Used In Power Plant BoilersNeelRao
 
Window Air Conditioners
Window Air ConditionersWindow Air Conditioners
Window Air Conditionersgreeonline
 
Performances of mechanical ventilation in dairy farms
Performances of mechanical ventilation in dairy farmsPerformances of mechanical ventilation in dairy farms
Performances of mechanical ventilation in dairy farmsInstitut de l'Elevage - Idele
 
Ventilation or cooling strategies
Ventilation or cooling strategiesVentilation or cooling strategies
Ventilation or cooling strategiesPulkit Goyal
 
Air conditioning window air conditioner
Air conditioning window air conditionerAir conditioning window air conditioner
Air conditioning window air conditionerNitin Grewal
 
Types of air preheaters and its advantages
Types of air preheaters and its advantagesTypes of air preheaters and its advantages
Types of air preheaters and its advantagesPreeti Agarwal
 
Building Services- Ventilation
Building Services- VentilationBuilding Services- Ventilation
Building Services- VentilationCiby John
 
building services
building servicesbuilding services
building servicesszelun
 
S3 Lec 6 (Air Distribution) Note
S3 Lec 6 (Air Distribution) NoteS3 Lec 6 (Air Distribution) Note
S3 Lec 6 (Air Distribution) Noteno suhaila
 
DADANCO ACTIVE CHILLED BEAMS
DADANCO ACTIVE CHILLED BEAMSDADANCO ACTIVE CHILLED BEAMS
DADANCO ACTIVE CHILLED BEAMSbostjanpeterman
 

What's hot (20)

Emergency Alteration in Ventilation
Emergency Alteration in VentilationEmergency Alteration in Ventilation
Emergency Alteration in Ventilation
 
HEATING AND VENTILATION
HEATING AND VENTILATIONHEATING AND VENTILATION
HEATING AND VENTILATION
 
Distribution and control of mine air standards of ventilation
Distribution and control of mine air standards of ventilationDistribution and control of mine air standards of ventilation
Distribution and control of mine air standards of ventilation
 
S3 Duct System Design Consideration
S3 Duct System Design ConsiderationS3 Duct System Design Consideration
S3 Duct System Design Consideration
 
HVAC
HVACHVAC
HVAC
 
Types of air conditioning for HVAC application
Types of air conditioning for HVAC applicationTypes of air conditioning for HVAC application
Types of air conditioning for HVAC application
 
Types Of Centrifugal Fans Used In Power Plant Boilers
Types Of Centrifugal Fans Used In Power Plant BoilersTypes Of Centrifugal Fans Used In Power Plant Boilers
Types Of Centrifugal Fans Used In Power Plant Boilers
 
Central ac
Central ac Central ac
Central ac
 
Ventilationcontrol
Ventilationcontrol Ventilationcontrol
Ventilationcontrol
 
Window Air Conditioners
Window Air ConditionersWindow Air Conditioners
Window Air Conditioners
 
Performances of mechanical ventilation in dairy farms
Performances of mechanical ventilation in dairy farmsPerformances of mechanical ventilation in dairy farms
Performances of mechanical ventilation in dairy farms
 
Ventilation or cooling strategies
Ventilation or cooling strategiesVentilation or cooling strategies
Ventilation or cooling strategies
 
Air conditioning window air conditioner
Air conditioning window air conditionerAir conditioning window air conditioner
Air conditioning window air conditioner
 
Types of air preheaters and its advantages
Types of air preheaters and its advantagesTypes of air preheaters and its advantages
Types of air preheaters and its advantages
 
Ventilation
VentilationVentilation
Ventilation
 
Building Services- Ventilation
Building Services- VentilationBuilding Services- Ventilation
Building Services- Ventilation
 
building services
building servicesbuilding services
building services
 
S3 Lec 6 (Air Distribution) Note
S3 Lec 6 (Air Distribution) NoteS3 Lec 6 (Air Distribution) Note
S3 Lec 6 (Air Distribution) Note
 
DADANCO ACTIVE CHILLED BEAMS
DADANCO ACTIVE CHILLED BEAMSDADANCO ACTIVE CHILLED BEAMS
DADANCO ACTIVE CHILLED BEAMS
 
Module (1.3) types of ac units-hvac-apex
Module (1.3) types of ac units-hvac-apexModule (1.3) types of ac units-hvac-apex
Module (1.3) types of ac units-hvac-apex
 

Viewers also liked

ΥΠ.ΟΙΚ.-ΥΠΕΚΑΚΑ 153734/2016/0092
ΥΠ.ΟΙΚ.-ΥΠΕΚΑΚΑ 153734/2016/0092ΥΠ.ΟΙΚ.-ΥΠΕΚΑΚΑ 153734/2016/0092
ΥΠ.ΟΙΚ.-ΥΠΕΚΑΚΑ 153734/2016/0092Panayotis Sofianopoulos
 
EMGOLDEX - BUSINESS FOR THIS WORLD
EMGOLDEX - BUSINESS FOR THIS WORLDEMGOLDEX - BUSINESS FOR THIS WORLD
EMGOLDEX - BUSINESS FOR THIS WORLDNikunj Chohan
 
SUTURE [SURGICOSE]
SUTURE [SURGICOSE]SUTURE [SURGICOSE]
SUTURE [SURGICOSE]SURGICOSE
 
Slideshow powerpoint
Slideshow powerpointSlideshow powerpoint
Slideshow powerpointEselKadir
 
Theory and App Presentation 1st May 2014
Theory and App Presentation 1st May 2014Theory and App Presentation 1st May 2014
Theory and App Presentation 1st May 2014Jemma Bateman
 
Alarm menggunakan HandPhone
Alarm menggunakan HandPhoneAlarm menggunakan HandPhone
Alarm menggunakan HandPhoneLeksono Mugi
 
Art Kleiner_resume Feb._2016
Art Kleiner_resume Feb._2016Art Kleiner_resume Feb._2016
Art Kleiner_resume Feb._2016Art Kleiner
 
CV of Jianyu Hu (contact info not included)
CV of Jianyu Hu (contact info not included)CV of Jianyu Hu (contact info not included)
CV of Jianyu Hu (contact info not included)Jianyu (Ken) Hu
 
DENTAL RESTORATIVE INSTRUMENTS
DENTAL RESTORATIVE INSTRUMENTSDENTAL RESTORATIVE INSTRUMENTS
DENTAL RESTORATIVE INSTRUMENTSSURGICOSE
 
سجنك حرية | قضية قتل الحارس - الحقيقة كاملة
سجنك حرية | قضية قتل الحارس - الحقيقة كاملةسجنك حرية | قضية قتل الحارس - الحقيقة كاملة
سجنك حرية | قضية قتل الحارس - الحقيقة كاملةseg7oryyah
 
NEEDLE HOLDERS [SURGICOSE PAKISTAN]
NEEDLE HOLDERS [SURGICOSE PAKISTAN]NEEDLE HOLDERS [SURGICOSE PAKISTAN]
NEEDLE HOLDERS [SURGICOSE PAKISTAN]SURGICOSE
 
Palmistry Art of palm reading by karan sharma
Palmistry  Art of palm reading by karan sharmaPalmistry  Art of palm reading by karan sharma
Palmistry Art of palm reading by karan sharmaKaran Sharma
 
Pickup Systems LTD.odp
Pickup Systems LTD.odpPickup Systems LTD.odp
Pickup Systems LTD.odpHeidi Smithson
 

Viewers also liked (18)

ΥΠ.ΟΙΚ.-ΥΠΕΚΑΚΑ 153734/2016/0092
ΥΠ.ΟΙΚ.-ΥΠΕΚΑΚΑ 153734/2016/0092ΥΠ.ΟΙΚ.-ΥΠΕΚΑΚΑ 153734/2016/0092
ΥΠ.ΟΙΚ.-ΥΠΕΚΑΚΑ 153734/2016/0092
 
EMGOLDEX - BUSINESS FOR THIS WORLD
EMGOLDEX - BUSINESS FOR THIS WORLDEMGOLDEX - BUSINESS FOR THIS WORLD
EMGOLDEX - BUSINESS FOR THIS WORLD
 
Kerusakan dan perusakan alam
Kerusakan dan perusakan alamKerusakan dan perusakan alam
Kerusakan dan perusakan alam
 
.الإلتهاب الكبدي ذات الأجسام الإحتوائية في دجاج اللاحم
.الإلتهاب الكبدي ذات الأجسام الإحتوائية في دجاج اللاحم.الإلتهاب الكبدي ذات الأجسام الإحتوائية في دجاج اللاحم
.الإلتهاب الكبدي ذات الأجسام الإحتوائية في دجاج اللاحم
 
展后报道
展后报道展后报道
展后报道
 
SUTURE [SURGICOSE]
SUTURE [SURGICOSE]SUTURE [SURGICOSE]
SUTURE [SURGICOSE]
 
Slideshow powerpoint
Slideshow powerpointSlideshow powerpoint
Slideshow powerpoint
 
Theory and App Presentation 1st May 2014
Theory and App Presentation 1st May 2014Theory and App Presentation 1st May 2014
Theory and App Presentation 1st May 2014
 
Alarm menggunakan HandPhone
Alarm menggunakan HandPhoneAlarm menggunakan HandPhone
Alarm menggunakan HandPhone
 
Art Kleiner_resume Feb._2016
Art Kleiner_resume Feb._2016Art Kleiner_resume Feb._2016
Art Kleiner_resume Feb._2016
 
CV of Jianyu Hu (contact info not included)
CV of Jianyu Hu (contact info not included)CV of Jianyu Hu (contact info not included)
CV of Jianyu Hu (contact info not included)
 
DENTAL RESTORATIVE INSTRUMENTS
DENTAL RESTORATIVE INSTRUMENTSDENTAL RESTORATIVE INSTRUMENTS
DENTAL RESTORATIVE INSTRUMENTS
 
سجنك حرية | قضية قتل الحارس - الحقيقة كاملة
سجنك حرية | قضية قتل الحارس - الحقيقة كاملةسجنك حرية | قضية قتل الحارس - الحقيقة كاملة
سجنك حرية | قضية قتل الحارس - الحقيقة كاملة
 
A Snapshot of Minecraft
A Snapshot of MinecraftA Snapshot of Minecraft
A Snapshot of Minecraft
 
NEEDLE HOLDERS [SURGICOSE PAKISTAN]
NEEDLE HOLDERS [SURGICOSE PAKISTAN]NEEDLE HOLDERS [SURGICOSE PAKISTAN]
NEEDLE HOLDERS [SURGICOSE PAKISTAN]
 
Palmistry Art of palm reading by karan sharma
Palmistry  Art of palm reading by karan sharmaPalmistry  Art of palm reading by karan sharma
Palmistry Art of palm reading by karan sharma
 
The Whole Truth About Success_v2
The Whole Truth About Success_v2The Whole Truth About Success_v2
The Whole Truth About Success_v2
 
Pickup Systems LTD.odp
Pickup Systems LTD.odpPickup Systems LTD.odp
Pickup Systems LTD.odp
 

Similar to التهوية النفقية وكيفية حساب قدرة سحب المراوح ؟؟؟

Management of Poultry House Ventilation by Dr.Muhammad Ashiq Toor
Management of Poultry House Ventilation  by Dr.Muhammad Ashiq ToorManagement of Poultry House Ventilation  by Dr.Muhammad Ashiq Toor
Management of Poultry House Ventilation by Dr.Muhammad Ashiq ToorAshiq Toor
 
Design of active winter cooling system
Design of active winter cooling systemDesign of active winter cooling system
Design of active winter cooling systemAjay Singh Lodhi
 
LECTURE 6 ZONING IN HVAC.ppt
LECTURE  6 ZONING IN HVAC.pptLECTURE  6 ZONING IN HVAC.ppt
LECTURE 6 ZONING IN HVAC.pptBhaskarBhatia2
 
ventilation in building
ventilation in buildingventilation in building
ventilation in buildingChitra Rana
 
Low energy consumption hvac systems for green buildings using chilled beam te...
Low energy consumption hvac systems for green buildings using chilled beam te...Low energy consumption hvac systems for green buildings using chilled beam te...
Low energy consumption hvac systems for green buildings using chilled beam te...IAEME Publication
 
Brioler management in cold weather part1
Brioler management in cold weather part1Brioler management in cold weather part1
Brioler management in cold weather part1Dr.Muhammad Awais
 
Solar Chimneys
Solar ChimneysSolar Chimneys
Solar ChimneysFayina19z
 
Felix trabajo de ingles
Felix trabajo de inglesFelix trabajo de ingles
Felix trabajo de inglespilarmgarre
 
Managing Ventilation In Modern Poultry House
Managing Ventilation In Modern Poultry HouseManaging Ventilation In Modern Poultry House
Managing Ventilation In Modern Poultry HouseDr Waseem Abbas
 
S3 Supply Devices and Room Air Distribution
S3 Supply Devices and Room Air DistributionS3 Supply Devices and Room Air Distribution
S3 Supply Devices and Room Air Distributionno suhaila
 
Air-5 final - Copy.pptx
Air-5 final - Copy.pptxAir-5 final - Copy.pptx
Air-5 final - Copy.pptxdejene1234567
 
Ventilating systems for electrical machines
Ventilating systems for electrical machinesVentilating systems for electrical machines
Ventilating systems for electrical machinesPraveen Kumar
 
key Components of Air Distribution Systems.pptx
key Components of Air Distribution Systems.pptxkey Components of Air Distribution Systems.pptx
key Components of Air Distribution Systems.pptxYosefBekele10
 
Air conditioning equipment and applications of air conditioning
Air conditioning equipment and applications of air conditioning Air conditioning equipment and applications of air conditioning
Air conditioning equipment and applications of air conditioning SHYAM KUMAR Reddy
 

Similar to التهوية النفقية وكيفية حساب قدرة سحب المراوح ؟؟؟ (20)

Management of Poultry House Ventilation by Dr.Muhammad Ashiq Toor
Management of Poultry House Ventilation  by Dr.Muhammad Ashiq ToorManagement of Poultry House Ventilation  by Dr.Muhammad Ashiq Toor
Management of Poultry House Ventilation by Dr.Muhammad Ashiq Toor
 
Green house cooling
Green house coolingGreen house cooling
Green house cooling
 
Storage
StorageStorage
Storage
 
analysis-of-uniformity-and-energy-consumption.pdf
analysis-of-uniformity-and-energy-consumption.pdfanalysis-of-uniformity-and-energy-consumption.pdf
analysis-of-uniformity-and-energy-consumption.pdf
 
Hvac & Refrigeration
Hvac & RefrigerationHvac & Refrigeration
Hvac & Refrigeration
 
Design of active winter cooling system
Design of active winter cooling systemDesign of active winter cooling system
Design of active winter cooling system
 
Cooling
CoolingCooling
Cooling
 
LECTURE 6 ZONING IN HVAC.ppt
LECTURE  6 ZONING IN HVAC.pptLECTURE  6 ZONING IN HVAC.ppt
LECTURE 6 ZONING IN HVAC.ppt
 
ventilation in building
ventilation in buildingventilation in building
ventilation in building
 
Low energy consumption hvac systems for green buildings using chilled beam te...
Low energy consumption hvac systems for green buildings using chilled beam te...Low energy consumption hvac systems for green buildings using chilled beam te...
Low energy consumption hvac systems for green buildings using chilled beam te...
 
Brioler management in cold weather part1
Brioler management in cold weather part1Brioler management in cold weather part1
Brioler management in cold weather part1
 
Solar Chimneys
Solar ChimneysSolar Chimneys
Solar Chimneys
 
Felix trabajo de ingles
Felix trabajo de inglesFelix trabajo de ingles
Felix trabajo de ingles
 
Managing Ventilation In Modern Poultry House
Managing Ventilation In Modern Poultry HouseManaging Ventilation In Modern Poultry House
Managing Ventilation In Modern Poultry House
 
S3 Supply Devices and Room Air Distribution
S3 Supply Devices and Room Air DistributionS3 Supply Devices and Room Air Distribution
S3 Supply Devices and Room Air Distribution
 
Cooling towers tech article v1r04
Cooling towers tech article v1r04Cooling towers tech article v1r04
Cooling towers tech article v1r04
 
Air-5 final - Copy.pptx
Air-5 final - Copy.pptxAir-5 final - Copy.pptx
Air-5 final - Copy.pptx
 
Ventilating systems for electrical machines
Ventilating systems for electrical machinesVentilating systems for electrical machines
Ventilating systems for electrical machines
 
key Components of Air Distribution Systems.pptx
key Components of Air Distribution Systems.pptxkey Components of Air Distribution Systems.pptx
key Components of Air Distribution Systems.pptx
 
Air conditioning equipment and applications of air conditioning
Air conditioning equipment and applications of air conditioning Air conditioning equipment and applications of air conditioning
Air conditioning equipment and applications of air conditioning
 

Recently uploaded

Understanding Partial Differential Equations: Types and Solution Methods
Understanding Partial Differential Equations: Types and Solution MethodsUnderstanding Partial Differential Equations: Types and Solution Methods
Understanding Partial Differential Equations: Types and Solution Methodsimroshankoirala
 
LUNULARIA -features, morphology, anatomy ,reproduction etc.
LUNULARIA -features, morphology, anatomy ,reproduction etc.LUNULARIA -features, morphology, anatomy ,reproduction etc.
LUNULARIA -features, morphology, anatomy ,reproduction etc.Cherry
 
Taphonomy and Quality of the Fossil Record
Taphonomy and Quality of the  Fossil RecordTaphonomy and Quality of the  Fossil Record
Taphonomy and Quality of the Fossil RecordSangram Sahoo
 
Plasmid: types, structure and functions.
Plasmid: types, structure and functions.Plasmid: types, structure and functions.
Plasmid: types, structure and functions.Cherry
 
ONLINE VOTING SYSTEM SE Project for vote
ONLINE VOTING SYSTEM SE Project for voteONLINE VOTING SYSTEM SE Project for vote
ONLINE VOTING SYSTEM SE Project for voteRaunakRastogi4
 
Lipids: types, structure and important functions.
Lipids: types, structure and important functions.Lipids: types, structure and important functions.
Lipids: types, structure and important functions.Cherry
 
Thyroid Physiology_Dr.E. Muralinath_ Associate Professor
Thyroid Physiology_Dr.E. Muralinath_ Associate ProfessorThyroid Physiology_Dr.E. Muralinath_ Associate Professor
Thyroid Physiology_Dr.E. Muralinath_ Associate Professormuralinath2
 
Reboulia: features, anatomy, morphology etc.
Reboulia: features, anatomy, morphology etc.Reboulia: features, anatomy, morphology etc.
Reboulia: features, anatomy, morphology etc.Cherry
 
development of diagnostic enzyme assay to detect leuser virus
development of diagnostic enzyme assay to detect leuser virusdevelopment of diagnostic enzyme assay to detect leuser virus
development of diagnostic enzyme assay to detect leuser virusNazaninKarimi6
 
PODOCARPUS...........................pptx
PODOCARPUS...........................pptxPODOCARPUS...........................pptx
PODOCARPUS...........................pptxCherry
 
Use of mutants in understanding seedling development.pptx
Use of mutants in understanding seedling development.pptxUse of mutants in understanding seedling development.pptx
Use of mutants in understanding seedling development.pptxRenuJangid3
 
Porella : features, morphology, anatomy, reproduction etc.
Porella : features, morphology, anatomy, reproduction etc.Porella : features, morphology, anatomy, reproduction etc.
Porella : features, morphology, anatomy, reproduction etc.Cherry
 
FS P2 COMBO MSTA LAST PUSH past exam papers.
FS P2 COMBO MSTA LAST PUSH past exam papers.FS P2 COMBO MSTA LAST PUSH past exam papers.
FS P2 COMBO MSTA LAST PUSH past exam papers.takadzanijustinmaime
 
(May 9, 2024) Enhanced Ultrafast Vector Flow Imaging (VFI) Using Multi-Angle ...
(May 9, 2024) Enhanced Ultrafast Vector Flow Imaging (VFI) Using Multi-Angle ...(May 9, 2024) Enhanced Ultrafast Vector Flow Imaging (VFI) Using Multi-Angle ...
(May 9, 2024) Enhanced Ultrafast Vector Flow Imaging (VFI) Using Multi-Angle ...Scintica Instrumentation
 
Dr. E. Muralinath_ Blood indices_clinical aspects
Dr. E. Muralinath_ Blood indices_clinical  aspectsDr. E. Muralinath_ Blood indices_clinical  aspects
Dr. E. Muralinath_ Blood indices_clinical aspectsmuralinath2
 
GBSN - Microbiology (Unit 5) Concept of isolation
GBSN - Microbiology (Unit 5) Concept of isolationGBSN - Microbiology (Unit 5) Concept of isolation
GBSN - Microbiology (Unit 5) Concept of isolationAreesha Ahmad
 
Module for Grade 9 for Asynchronous/Distance learning
Module for Grade 9 for Asynchronous/Distance learningModule for Grade 9 for Asynchronous/Distance learning
Module for Grade 9 for Asynchronous/Distance learninglevieagacer
 
Human & Veterinary Respiratory Physilogy_DR.E.Muralinath_Associate Professor....
Human & Veterinary Respiratory Physilogy_DR.E.Muralinath_Associate Professor....Human & Veterinary Respiratory Physilogy_DR.E.Muralinath_Associate Professor....
Human & Veterinary Respiratory Physilogy_DR.E.Muralinath_Associate Professor....muralinath2
 
Cyathodium bryophyte: morphology, anatomy, reproduction etc.
Cyathodium bryophyte: morphology, anatomy, reproduction etc.Cyathodium bryophyte: morphology, anatomy, reproduction etc.
Cyathodium bryophyte: morphology, anatomy, reproduction etc.Cherry
 
Efficient spin-up of Earth System Models usingsequence acceleration
Efficient spin-up of Earth System Models usingsequence accelerationEfficient spin-up of Earth System Models usingsequence acceleration
Efficient spin-up of Earth System Models usingsequence accelerationSérgio Sacani
 

Recently uploaded (20)

Understanding Partial Differential Equations: Types and Solution Methods
Understanding Partial Differential Equations: Types and Solution MethodsUnderstanding Partial Differential Equations: Types and Solution Methods
Understanding Partial Differential Equations: Types and Solution Methods
 
LUNULARIA -features, morphology, anatomy ,reproduction etc.
LUNULARIA -features, morphology, anatomy ,reproduction etc.LUNULARIA -features, morphology, anatomy ,reproduction etc.
LUNULARIA -features, morphology, anatomy ,reproduction etc.
 
Taphonomy and Quality of the Fossil Record
Taphonomy and Quality of the  Fossil RecordTaphonomy and Quality of the  Fossil Record
Taphonomy and Quality of the Fossil Record
 
Plasmid: types, structure and functions.
Plasmid: types, structure and functions.Plasmid: types, structure and functions.
Plasmid: types, structure and functions.
 
ONLINE VOTING SYSTEM SE Project for vote
ONLINE VOTING SYSTEM SE Project for voteONLINE VOTING SYSTEM SE Project for vote
ONLINE VOTING SYSTEM SE Project for vote
 
Lipids: types, structure and important functions.
Lipids: types, structure and important functions.Lipids: types, structure and important functions.
Lipids: types, structure and important functions.
 
Thyroid Physiology_Dr.E. Muralinath_ Associate Professor
Thyroid Physiology_Dr.E. Muralinath_ Associate ProfessorThyroid Physiology_Dr.E. Muralinath_ Associate Professor
Thyroid Physiology_Dr.E. Muralinath_ Associate Professor
 
Reboulia: features, anatomy, morphology etc.
Reboulia: features, anatomy, morphology etc.Reboulia: features, anatomy, morphology etc.
Reboulia: features, anatomy, morphology etc.
 
development of diagnostic enzyme assay to detect leuser virus
development of diagnostic enzyme assay to detect leuser virusdevelopment of diagnostic enzyme assay to detect leuser virus
development of diagnostic enzyme assay to detect leuser virus
 
PODOCARPUS...........................pptx
PODOCARPUS...........................pptxPODOCARPUS...........................pptx
PODOCARPUS...........................pptx
 
Use of mutants in understanding seedling development.pptx
Use of mutants in understanding seedling development.pptxUse of mutants in understanding seedling development.pptx
Use of mutants in understanding seedling development.pptx
 
Porella : features, morphology, anatomy, reproduction etc.
Porella : features, morphology, anatomy, reproduction etc.Porella : features, morphology, anatomy, reproduction etc.
Porella : features, morphology, anatomy, reproduction etc.
 
FS P2 COMBO MSTA LAST PUSH past exam papers.
FS P2 COMBO MSTA LAST PUSH past exam papers.FS P2 COMBO MSTA LAST PUSH past exam papers.
FS P2 COMBO MSTA LAST PUSH past exam papers.
 
(May 9, 2024) Enhanced Ultrafast Vector Flow Imaging (VFI) Using Multi-Angle ...
(May 9, 2024) Enhanced Ultrafast Vector Flow Imaging (VFI) Using Multi-Angle ...(May 9, 2024) Enhanced Ultrafast Vector Flow Imaging (VFI) Using Multi-Angle ...
(May 9, 2024) Enhanced Ultrafast Vector Flow Imaging (VFI) Using Multi-Angle ...
 
Dr. E. Muralinath_ Blood indices_clinical aspects
Dr. E. Muralinath_ Blood indices_clinical  aspectsDr. E. Muralinath_ Blood indices_clinical  aspects
Dr. E. Muralinath_ Blood indices_clinical aspects
 
GBSN - Microbiology (Unit 5) Concept of isolation
GBSN - Microbiology (Unit 5) Concept of isolationGBSN - Microbiology (Unit 5) Concept of isolation
GBSN - Microbiology (Unit 5) Concept of isolation
 
Module for Grade 9 for Asynchronous/Distance learning
Module for Grade 9 for Asynchronous/Distance learningModule for Grade 9 for Asynchronous/Distance learning
Module for Grade 9 for Asynchronous/Distance learning
 
Human & Veterinary Respiratory Physilogy_DR.E.Muralinath_Associate Professor....
Human & Veterinary Respiratory Physilogy_DR.E.Muralinath_Associate Professor....Human & Veterinary Respiratory Physilogy_DR.E.Muralinath_Associate Professor....
Human & Veterinary Respiratory Physilogy_DR.E.Muralinath_Associate Professor....
 
Cyathodium bryophyte: morphology, anatomy, reproduction etc.
Cyathodium bryophyte: morphology, anatomy, reproduction etc.Cyathodium bryophyte: morphology, anatomy, reproduction etc.
Cyathodium bryophyte: morphology, anatomy, reproduction etc.
 
Efficient spin-up of Earth System Models usingsequence acceleration
Efficient spin-up of Earth System Models usingsequence accelerationEfficient spin-up of Earth System Models usingsequence acceleration
Efficient spin-up of Earth System Models usingsequence acceleration
 

التهوية النفقية وكيفية حساب قدرة سحب المراوح ؟؟؟

  • 1. Tunnel Ventilation in Livestock Barns — With and Without Evaporative Cooling D. Ward, P.Eng. ORDER NO. 13-073 AGDEX 717 OCTOBER 2013 (replaces OMAF Factsheet 00-085, Tunnel Ventilation for Livestock and Poultry Barns) INTRODUCTION Ontario’s hot, humid summer weather makes it difficult for livestock and poultry to perform at their best. It is important to provide cooling in barns so animals do not experience heat stress, resulting in an associated decrease in production. The two most common methods of cooling are air-based and water-based. This Factsheet discusses the design factors and management of tunnel ventilation — with and without evaporative cooling. The main method of air-cooling livestock barns in Ontario is tunnel ventilation. The entire air inlet is located on one end wall of the barn (Figure 1) with all of the exhaust fans located on the opposite end (Figure 2). The idea is to create a high velocity wall of air moving down the long axis of the building like a wind tunnel. This provides a beneficial wind chill effect that cools the animals by convection (the removal of heat from the surface of an object by an airstream moving over it) and exhausts this heat out of the building. In many parts of the world, evaporative cooling pads are added to the air inlets of tunnel-ventilated barns (Figure 3) because there is a critical upper temperature for tunnel ventilation. Excessive air movement above 40°C — a chicken’s core body temperature — increases heat stress experienced by the animal. At these high temperatures, some form of evaporative cooling is incorporated into the system to reduce the effects of the incoming air temperature. With evaporative cooling, the incoming air is pulled through a saturated medium (cooling pad). The process of converting water from a liquid to a vapour removes heat energy from the incoming air, lowering its temperature but increasing its relative humidity. Figure 1. Tunnel ventilation inlet doors across the end wall of a barn without evaporative cooling. Figure 2. Exhaust fans across the end wall of the barn. Figure 3. Tunnel ventilation inlet with evaporative cooling pads installed.
  • 2. 2 Until recently, these systems were not commonly used in Ontario. However, following several summers with prolonged periods of temperatures higher than 30°C, these systems are being used in more barns. AIR-BASED COOLING — TUNNEL VENTILATION In a cross-flow ventilation system (air flows across the length of the building) with a slot-type air inlet, the air speed at the animal level ranges from 0.25 to 0.50 m/s (50–100 ft/min). With tunnel ventilation, the goal is to achieve an air speed of 1.0–2.5 m/s (200–500 ft/min) over the animals. The recent trend in Ontario and elsewhere is to design systems to operate at even higher airspeeds, with very good results. Research conducted by the U.S. Department of Agriculture Poultry Research Laboratory at Mississippi State University on 7-week-old broiler chickens showed that air moving at 1 m/s (200 ft/min) over the birds results in similar growth rates to birds raised in still or slow-moving air that is 1°C cooler. Similarly, air moving at 2 m/s (400 ft/min) creates a wind chill effect of 3.7°C. The birds in this trial, grown under tunnel ventilation at 2 m/s, were 0.5 kg heavier at 7 weeks of age than the birds grown in still air. Tunnel ventilation is not recommended when ambient air temperature is below 15°C or for sensitive, younger animals (baby chicks prior to feathering), as the wind chill–cooling effect is not necessary and could be stressful to these animals. For this reason, when tunnel ventilation is designed for a building, the normal cross-flow ventilation system is usually sized to supply 40%–50% of the summer ventilation requirements to accommodate the three cooler seasons of the year and for the early growth stages of sensitive animals. FAN CAPACITY FOR TUNNEL VENTILATION The size of the tunnel ventilation system is based on the amount of power needed to create a wall of air moving the length of the building at a velocity of 1.0–2.5 m/s (200–500 ft/min or 3.6–9 km/hr) or higher. Therefore, the required fan capacity is the useable barn cross-sectional area multiplied by the desired air speed. Note that floor-reared birds occupy the lower 0.3 m (1 ft) of the barn cross-section, so it is not useable for air movement. Similarly, cattle stalls, swine pen partitioning, etc., will reduce the net cross- sectional area available for airflow. Fan Sizing Example What is the fan capacity required for an 18-m x 91-m (60-ft x 300-ft) broiler chicken barn with a 2.7-m (9-ft) ceiling height and a desired tunnel air speed of 2.5 m/s (500 ft/min)? Metric Airflow Q = (Velocity x Area) x 1,000 = 2.5 m/s x 18 m x (2.7 – 0.3 m) x 1,000 = 108,000 L/s Imperial Airflow Q = Velocity x Area = 500 ft/min x 60 ft x (9 ft – 1 ft) = 240,000 CFM The most common fans used for tunnel ventilation are belt-driven, single-speed 1,200-mm (48-in.) fans equipped with exhaust cones. These fans have a high-energy efficiency rating (normally >7.5 L/s/w (16 CFM/w)). On average, a 1,200 mm (48 in.) fan will move approximately 9,400 L/s (20,000 CFM) of air. Therefore, the number of fans required for this barn is: Metric: 108,000/9,400 = 12 fans Imperial: 240,000/20,000 = 12 fans Other fan sizes, or a combination of fan sizes, are used and may be desired for a particular situation. A common problem encountered when designing a tunnel ventilation system is insufficient room on the end wall to install all the tunnel fans required to meet the target airflow. It is acceptable to install some fans around the corner onto the sidewall as shown in Figure 2.
  • 3. 3 AIR INTAKE FOR TUNNEL VENTILATION Tunnel ventilation inlets contain motorized louvers, curtains, panels or large doors. These openings are usually sized on the basis of 2 m2 per 5,000 L/s (2 ft2 /1,000 CFM) of fan capacity. Since air does not easily turn corners, this type of inlet works best when located across an end wall so that the incoming fresh air travels straight into the barn in the correct airflow direction. As shown in Figure 1, a large panel door across the end wall provides the necessary cross-sectional area for the air intake. Some barns are equipped with a combination of panels and a roll-up door to achieve the required inlet opening. Air Intake Sizing Example What is the required air intake size for the example broiler chicken barn already discussed? Metric Area = (2 m2 /5,000 L/s) x Airflow Q L/s = (2 m2 /5,000 L/s) x 108,000 L/s = 43.2 m2 = 2.59 m x 16.7 m Imperial Area = (2 ft2 /1,000 CFM) x Airflow Q CFM = (2 ft2 /1,000 CFM ) x 240,000 CFM = 480 ft2 = 8.5 ft x 56.5 ft TUNNEL VENTILATION CONTROL Tunnel ventilation is strictly a warm-weather system and should only be used in temperatures above 21°C for animals that are not overly sensitive to drafts, such as birds older than 3 weeks of age. As with normal cross-flow ventilation, stage the tunnel ventilation system to automatically turn on when the barn temperature increases. Generally, 2 or 3 tunnel stages are used to manage the barn conditions. For example, Stage 1 operates the first group of 2 or 3 tunnel fans, Stage 2 operates another group of fans and Stage 3 operates the remaining fans. This control strategy allows a staggered wind chill effect to match the ambient air conditions experienced by the animals. As the temperature increases through the day, the corresponding stages are activated to create more air flow and as the cooler night temperatures arrive, the stages are deactivated in reverse order to decrease air flow. Normally the cross-flow ventilation system is turned off completely once the tunnel fans/inlets are activated. The sidewall fans are turned off, and the baffle board air inlet is closed to get the full wind-tunnel effect down the length of the barn. Remember, the main objective is to remove the hot air in the barn, as quickly as possible.
  • 4. 4 POTENTIAL TUNNEL AIRFLOW CHALLENGES Air Inlet Location Locate air inlets on the end wall if at all possible. Air will not turn 90° corners unless forced. Any air entering from the sidewall creates airflow across the barn rather than along the length. Airflow from the sidewall inlet will eventually turn and move endwise to the exhaust fans but will leave a dead air zone (Figure 4) along the sidewall containing the inlet panel. Use air deflectors to help turn this incoming air. SERVICE OR ENTRANCE ROOM LOCATION Locate the service or entrance room outside the main building, as shown in Figure 1, to provide full end wall exposure for the tunnel air inlet. Besides reducing the available end wall opening, it creates a major wind shadow down that side of the room. An unconfined air stream will fan out at about a 10° angle, and a 2.4-m (8-ft) wide service room will prevent tunnel air movement along that wall for at least 14 m (46 ft) (Figure 5). Smoke testing shows the actual affected distance is even greater due to a slow, backward eddy-type flow in the wind shadow area. If an interior room is necessary, locate it near the tunnel exhaust fans and opposite the winter air inlet to minimize the amount of airflow blocked. OUTSIDE WIND EFFECT Significant summer winds, blowing at an angle into the tunnel air inlet, can direct the airflow inside to one side of the barn (Figure 6). This situation drastically reduces the airflow along the other side of the room. Compare an outside wind speed of 20 km/hr (12.5 mph) to a typical tunnel air speed of 6 km/hr (3.8 mph) to understand the potential for the wind to overpower the airflow pattern. Opening the side air inlet baffle board to introduce more air to the side with less airflow can help even out the airflow. Air-deflecting baffles located at the tunnel inlet have also reduced this problem. Figure 4. Floor plan showing dead air zone (shaded area) due to placement of sidewall tunnel ventilation air inlets. Figure 5. Floor plan showing dead air zone (shaded area) due to obstruction by a service room entrance. Figure 6. Floor plan showing a skewed air flow pattern due to wind effect.
  • 5. 5 CEILING AIR DEFLECTORS A method of increasing the air speed at animal level, without installing extra tunnel fans, is to install drop curtains or other air deflectors from the ceiling every 12–25 m (40–80 ft) along the length of the barn to reduce the barn cross-sectional area. Limit the increased air speed to a maximum of 2.5 or 3.0 m/s (500 or 600 ft/min) to prevent a reduction in fan performance. This is because too much reduction in the building cross-sectional area will increase the static pressure the fan(s) has to work against. EVAPORATIVE COOLING EQUIPMENT Design The evaporative cooling pad is made of fibrous material woven together, similar to corrugated cardboard, with large gaps in the grooves. The pad is mounted vertically over the tunnel air intake. The bottom of the pad sits in a drain trough, and a water delivery pipe, with evenly spaced holes, runs across the top of the pad. A circulating pump is used to pump the water from the trough at the bottom of the pad to the distribution pipe at the top of the pad. When evaporative cooling is needed, the controller activates the pump, which delivers water to the distribution pipe that trickles water down the face of the pad to wet it. Fresh water is added into the system via a float mechanism to replenish the water that is evaporated into the air stream during the ventilation process (Figures 7–10). Figure 7. Evaporative cooling pad, showing circulating pump, cooling pad, fresh water feed pipe (blue pipe) and filter. Figure 8. Close-up of water trickling down the outside of pad surface. Figure 9. Inside surface of the evaporative cooling pad with the insulated door open. Figure 10. Insulated door closed to cover the evaporative cooling pad.
  • 6. 6 The cooling capability or efficiency of the pad system is directly related to pad type, size of pad and the air velocity allowed to pass through the pad. The cooling efficiency ranges from 55%–75% for most evaporative cooling pads. Air velocity and size of the pad are directly related to the fan’s capacity. A smaller pad area means a higher air velocity through the pads. Most pad manufacturers recommend a design air velocity of 1.27-1.78 m/s (250–350 fpm) through their pads to ensure a long enough contact time between the air and the wet surface to achieve the best cooling efficiency. The most common design problem seen with evaporative cooling systems is not enough pad area. Since the wet cooling pad presents a greater barrier to air flow than a typical tunnel inlet, designers usually increase the size of the inlet opening for the evaporative cooling pad to ensure the static pressure drop across the pad is “limited to” 7.47–22.4 Pa (0.03-0.09 in.) water column. The recommended inlet opening size is 2.5 m2 of opening/5,000 L/s (2.5 ft2 of opening/1,000 CFM). Evaporative cooling, like all water-based cooling systems, increases the relative humidity of the air in the barn space. Ensure the relative humidity in the barn never exceeds 80% when using an evaporative cooling pad during warm weather, as this may cause the animals more distress. For example, poultry pant to shed heat at higher temperatures (25°C+). This method of controlling body temperature relies on evaporative cooling within the bird’s own lungs to get rid of excess heat from its body. However, when the bird is placed in a barn with a relative humidity greater than 80%, it cannot release heat. The ability of the room air to absorb any additional moisture above 80% is slowed or lessened. Since the bird is unable to lose this excess heat, its core body temperature begins to rise. OPERATION With a recirculating pump system, the most important factor to monitor is the small holes in the distribution pipe along the top of the evaporative cooling pad. Ensure these holes are not plugged and allow water to continually flow evenly across the pad, as this is essential for good cooling performance. If the pad is always streaking or there are dry spots on the pad, the distribution system likely needs cleaning and/or flushing. Common reasons for a pad becoming plugged: • High mineral content of feed water. This can result in mineral deposits or scale forming on the pad. To avoid this problem, treat the water used for the evaporative cooling pad through a water softener to remove the minerals. • Algae growth. Since the pad is made of organic material and kept in a warm moist state, algae have a chance to grow on the pad and in the water collection sump. It is highly recommended to allow the pad to dry out at least once daily. Add approved algaecides to the collection sump to discourage algae growth: check with the manufacturer for a list of approved products. The pad materials decay over time due to the repeated wet/dry cycles and should be replaced every couple of years. Some corrugated plastic pad materials have been tested to determine if they would provide a longer-lasting term alternative to current cardboard pads. These pads would not promote algae growth since the plastic is non- organic. The performance of the plastic pads, in terms of water evaporation, was not as good as the cardboard pads.
  • 7. 7 Figure 11. Evaporative cooling pads with protective covers (white tarp material) partially closed WINTER MAINTENANCE Completely drain the evaporative cooling systems before freezing temperatures arrive to prevent damage to the piping and pump. To protect the pad materials from damage caused by ultraviolet light, snow, ice, etc., during the winter months when it is not in use, place a watertight protective structure over the outside of the pad (Figure 11). To prevent moisture migration and heat loss through the pad from inside the barn during colder temperatures, install air-tight, insulated panels on the inside of the tunnel inlets opening (see Figure 10). Tunnel ventilation and evaporative cooling systems are effective methods for relieving heat stress and enhancing animal performance in hot weather. Both systems require careful design, operation and regular maintenance in order to make them work effectively. This Factsheet was written by Daniel Ward, P.Eng., Poultry & Other Livestock Housing & Equipment, OMAF, Stratford, and reviewed by Robert Chambers, P.Eng., Swine & Sheep Housing and Equipment, OMAF, Elora; Al Dam, Poultry Specialist, OMAF, Guelph; and Arlene Robertson, Education Coordinator, OMAF, Guelph.
  • 8. Published by the Ontario Ministry of Agriculture and Food and the Ministry of Rural Affairs © Queen’s Printer for Ontario, 2013, Toronto, Canada ISSN 1198-712X Également disponible en français (Commande no 13-074) Agricultural Information Contact Centre: 1-877-424-1300 E-mail: ag.info.omafra@ontario.ca www.ontario.ca/omaf