1. NGG/NGB 125A MCCB
Siemens Energy &
Automation
Siemens
Molded Case Circuit Breakers for the OEM Market
2. NGG 125A MCCB
Siemens Energy &
Automation
Molded Case Circuit
Breakers for the
Global OEM Market
• 15 – 125A
• 1-, 2- and 3-pole versions
• 65kA @ 240 Vac
• 25 kA @ 480 Vac
• 14 kA @ 600Y/347 Vac
• 14 kA @ 125/250 Vdc
• Full line of accessories
SIEMENS
2
3. NGB 125A MCCB
Siemens Energy &
Automation
Molded Case Circuit
Breakers for the
Global OEM Market
• 15 – 125A
• 1-, 2- and 3-pole versions
• 100kA @ 240 Vac
• 25 kA @ 480Y/277 Vac
• 14 kA @ 600Y/347 Vac
• 14 kA @ 125/250 Vdc
• Fits P1-P5 Panelboards
SIEMENS
3
4. NGG 125A MCCB
Siemens Energy &
Automation
Compared to previous SIEMENS lines:
Smaller than Sentron E-Frame
Only 5.4”H, 3”W, 2.8”D
Higher interrupting ratings than CQD
65 KAIC @ 240 Vac
25 KAIC @ 480 Vac
High Performance/Current Limitation
Enhances product offering for the most popular
current ratings
Accepts ring terminals
DIN Rail mounting
Global ratings:
SIEMENS
UL489
CSA 22.1
NOM (pending)
IEC 60947-2 (pending)
4
5. Where does the NGG 125 fit in the Siemens product
range?
Siemens Energy &
Automation
Frame
Amp Range (A)
AIC @ 480 Vac
(kA)
Global Ratings
Internally Mounted
Accessories
SIEMENS
N
H
L
C
CQ
NGG EG 125
ED
DG
D
15-100 15-125 15-125 15-125 30-150
14
25
35
25
35
65
42
65
65
100
200
Yes
Yes
Yes
No
Yes
(up to
30A)
No
No
Yes
No
5
Yes
6. Interrupting Capacity Ratings
Siemens Energy &
Automation
Interrupting Capacity Ratings
UL 489 / IEC 60947-2 Interrupting Capacity Ratings
Ratings
NGG
Ratings
NGB
SIEMENS
Volts AC
Poles
120
240
1
2, 3
65
-
65
Volts AC
Poles
120
240
1
2, 3
100
-
100
277
347
480
25
-
14
-
25
277
347
25
-
14
-
Volts DC
Volts AC
600Y/347
125
125/250
240
14
14
-
14
25
65
Volts DC
Volts AC
480Y/277 600Y/347
125
125/250
240
25
14
14
-
14
6
25
65
415
25
415
25
Volts DC
125/250
14
Volts DC
125/250
14
9. Common Accessories CQD, NGG & NGB
Siemens Energy &
Automation
Handle Mechanisms
Through the door
Features
Door mount
Door interlock & padlock provision standard
NEMA 1 & 12 for both configurations
NEMA 3R & 4X for door mount handle operator
(CQDOP34 – uses Sentron handles)
SIEMENS
9
10. Space Savings Over Sentron ED
Siemens Energy &
Automation
0.98” Height Difference
ED
SIEMENS
NGG
10
15% Decreased Panel Space
11. Space Savings Over Sentron ED
Siemens Energy &
Automation
ED
NGG
1.05” Depth Difference
SIEMENS
11
38% Decreased Volume
12. Customer Benefits – General OEM
Siemens Energy &
Automation
Space savings over Sentron ED
15% decrease in panel space
38% decrease in volume
Less confusion with terminal connectors
Ring terminal compatible
Two options satisfy #14-2/0 wire range
Sentron
ED has 8 options for same wire range
Global Ratings
High performance / current limitation
Integral DIN Rail mounting
SIEMENS
12
Editor's Notes
Future MCCB product offering - completion 2004
E125 15 - 125 A UL/CSA/IEC 1,2,3,4-pole
Four interrupting ratings
Complete line of internal & external accessories
External accessories
Interphase barriers
Endcap kit
Terminal cover & shields
Din rail adapter
IEC earth leakage
Pad lock device
Handle mech. close couple, flex shaft, vari-depth
Internal accessories
Field installable - remove secondary - does not void UL
Breaker trip when secondary cover removed
Will not reset w/o secondary cover installed
No internal breaker components exposed
Wide range of voltage ratings
Common w/ J250 - inventory savings
Trip accessory - left pole
Indication - breaker status - right pole