Common Reasons For Generator
        Start Failure
Understanding How to Properly Maintain Your Standby
                  Power System

                    Presented By:
                    Jason Blacker
                         and
                 Jeremiah Rosenthal
BASIC COMPONENTS OF AN
EMERGENCY POWER SYSTEM
GOOD HOUSEKEEPING
GOOD HOUSEKEEPING
COMMON REASONS FOR
  GENERATOR START FAILURE

          Controls Not in “Auto”
• Start switch in “Off/Reset” position
  – Assure System is in “Auto”
  – Check weekly



• “E- Stop” button pushed in
  – Reset E-stop
  – Check generator breaker
TYPICAL CONTROL PANEL
TYPICAL CONTROL PANEL
COMMON REASONS FOR
    GENERATOR START FAILURE
Generator Output Circuit Breaker “Open”
• Breaker left in “open” or “off” position
  – Check breaker position during weekly inspection



• Breaker tripped due to fault or shunt trip
  – Check breaker position during weekly inspection
  – Continues to trip indicates fault or alarm
TYPICAL CONTROL PANEL AND
     CIRCUIT BREAKER
COMMON REASONS FOR
    GENERATOR START FAILURE
             Battery Failure
• Age: 2-3 year life span
  – Failure rate increases after 3 yrs
  – Change before failure for uptime assurance
  – NFPA recommends new at 30 months

• Constant charging
  – Check weekly electrolyte levels
• Corroded terminals
  – Check weekly & clean terminals as needed
COMMON REASONS FOR
    GENERATOR START FAILURE
             Battery Failure
• Charger turned off
  – Check weekly charger operation
• Vibration
  – Check hold down bracket
BATTERY HOLD DOWN & CHARGER
COMMON REASONS FOR
    GENERATOR START FAILURE
   Low Coolant Level Alarm/ Shutdown
• Low coolant level
  – Assure system is full to manufacturers recommendation

• External or internal leak
  – Check for visible leaks/pooling of coolant

• Block heater
  – Heat causes coolant to evaporate over time
COMMON REASONS FOR
    GENERATOR START FAILURE
        Engine Block Heater Failure
• Indication is a low coolant temp alarm
  – Poor cooling system maintenance
     • Sampling
  – Circuit breaker to heater is off/tripped
  – Failed heater element
  – Heater hose leak
  – Valves in off position
  – Heater thermostat adjustment
     • If equipped (typical setting is 80 to 120)
COMMON REASONS FOR
    GENERATOR START FAILURE
         Leaks – Fuel or Coolant
• Coolant leaks
  – Hose connections and clamps
  – Radiator core
  – Water pump

• Fuel leaks
  – Nat Gas/Propane
  – Diesel: Filters, injection & supply lines
COMMON REASONS FOR
      GENERATOR START FAILURE
     Oil Leaks and “Wet stacking”
• Common oil leaks
  – Crankcase breather, filters, drain plug, gaskets, & seals
  – Check oil level weekly


• Wet stacking
  – Caused by running on light load
  – Results in unburned diesel fuel in exhaust system
  – Load bank testing solution
  – NFPA and by most engine manufacturers recommend load bank
    testing
  – Load bank test assures system performs under load
COMMON REASONS FOR
    GENERATOR START FAILURE
          Air In The Fuel System
• Infrequent use
  – Perform weekly test
• Line leak
  – Visual inspection
• Faulty system check valve
• Fuel storage tank location
• Low fuel
COMMON REASONS FOR
    GENERATOR START FAILURE
            Engine Out of Fuel
• Plugged fuel filters with water and
  contaminants
  – Change filters annually & test fuel
• Mechanical level gauges inaccurate
  – Visually verify fuel level
• Low level alarms failure
  – check level
• System component failure
  – Check pumps & valves
COMMON REASONS FOR
    GENERATOR START FAILURE
       “My Generator is Running!”
• Well-maintained emergency power
  systems operate automatically

• Once utility power is restored the
  generator continues to run for a short time
  – delay timer in the automatic transfer switch
    assures steady utility power is available
• Transfer Switch Indicators
AUTO TRANSFER SWTICH PANEL




                           Generator
                           Power
Utility Power
AUTO TRANSFER SWITCH PANEL




Utility Power           Generator
                        Power
TYPICAL REMOTE ANNUNCIATOR
           PANEL
COMMON REASONS FOR
   GENERATOR START FAILURE
     The Power Of A Preventative
           Maintenance Plan

A standby power system requires routine
   maintenance to guarantee emergency
              power reliability
      Visit and free inspection offer
COMMON REASONS FOR
    GENERATOR START FAILURE
           Weekly “Walk Around” Check List
       Month               Comments/Corrective Action


Date of Inspection
General Condition
of engine/generator
Condition of belts
and hoses


Engine Oil Level


Coolant Level


Coolant Heater


Water Pump


Radiator
Generator Circuit
Breaker Closed


Battery System


  Electrolyte Level


  Connections


  Charger


Exhaust System


Fuel System


  Fuel level

  Tank Vents
Thank You
Visit Our Booth Display
         #1234

      Control Panel
       Generator
 Automatic Transfer Switch
Thank You

Peterson Power Systems

    503.288.6411
Reason Gen Sets   V2

More Related Content

Viewers also liked

Test For You
Test For YouTest For You
Test For You
nazarin
 
Yeferson manual
Yeferson manualYeferson manual
Yeferson manual
Mauricio Martínez
 
Espa fresh
Espa freshEspa fresh
Espa fresh
Mauricio Martínez
 
Expo ingles (1) The Body Parts
Expo ingles (1) The Body PartsExpo ingles (1) The Body Parts
Expo ingles (1) The Body Parts
Mauricio Martínez
 
himalayan rivers
himalayan rivershimalayan rivers
himalayan rivers
deepak190
 
Manual
ManualManual

Viewers also liked (6)

Test For You
Test For YouTest For You
Test For You
 
Yeferson manual
Yeferson manualYeferson manual
Yeferson manual
 
Espa fresh
Espa freshEspa fresh
Espa fresh
 
Expo ingles (1) The Body Parts
Expo ingles (1) The Body PartsExpo ingles (1) The Body Parts
Expo ingles (1) The Body Parts
 
himalayan rivers
himalayan rivershimalayan rivers
himalayan rivers
 
Manual
ManualManual
Manual
 

Similar to Reason Gen Sets V2

Submersible Pumps Trouble Shooting
Submersible Pumps Trouble ShootingSubmersible Pumps Trouble Shooting
Submersible Pumps Trouble Shooting
controlspecialties1
 
ROTEX Controls USA: Valve Automation 101
ROTEX Controls USA: Valve Automation 101 ROTEX Controls USA: Valve Automation 101
ROTEX Controls USA: Valve Automation 101
ROTEX Controls USA
 
SD.pptx
SD.pptxSD.pptx
SD.pptx
hemant9402
 
Fuel gas system of gas production
Fuel gas system of gas productionFuel gas system of gas production
Fuel gas system of gas production
Phyoe Maung Maung
 
Engine_Application_and_Start_Up_Presentation.pdf
Engine_Application_and_Start_Up_Presentation.pdfEngine_Application_and_Start_Up_Presentation.pdf
Engine_Application_and_Start_Up_Presentation.pdf
Rafat47
 
Why Won't My Generator Maintain Operation After Starting
Why Won't My Generator Maintain Operation After StartingWhy Won't My Generator Maintain Operation After Starting
Why Won't My Generator Maintain Operation After Starting
Leddy Power Systems Inc
 
2008 honda pilot service repair manual
2008 honda pilot service repair manual2008 honda pilot service repair manual
2008 honda pilot service repair manual
fjjskdmnenemm
 
2005 HONDA PILOT Service Repair Manual
2005 HONDA PILOT Service Repair Manual2005 HONDA PILOT Service Repair Manual
2005 HONDA PILOT Service Repair Manual
hjskejdm
 
New Holland TV145 Repair Manual
New Holland TV145 Repair ManualNew Holland TV145 Repair Manual
New Holland TV145 Repair Manual
PeterStalker1
 
Hydraulic Basic
Hydraulic BasicHydraulic Basic
Hydraulic Basic
vipin kumar
 
EC8DE5D2-3B41-4599-8A5D-AB833F9397F5.pdf
EC8DE5D2-3B41-4599-8A5D-AB833F9397F5.pdfEC8DE5D2-3B41-4599-8A5D-AB833F9397F5.pdf
EC8DE5D2-3B41-4599-8A5D-AB833F9397F5.pdf
suryanshsingh836763
 
1 hydraulic troubleshooting
1 hydraulic troubleshooting1 hydraulic troubleshooting
1 hydraulic troubleshooting
Dr.R. SELVAM
 
MOTORISED VALVE ACTUATORS_SANTHIRAJ001.pptx
MOTORISED VALVE ACTUATORS_SANTHIRAJ001.pptxMOTORISED VALVE ACTUATORS_SANTHIRAJ001.pptx
MOTORISED VALVE ACTUATORS_SANTHIRAJ001.pptx
KBR-AMCDE
 
On Power Plant Operation cource In Urdu by Khalid ayaz Soomro.pdf
On Power Plant Operation  cource In Urdu by Khalid ayaz Soomro.pdfOn Power Plant Operation  cource In Urdu by Khalid ayaz Soomro.pdf
On Power Plant Operation cource In Urdu by Khalid ayaz Soomro.pdf
KhalidAyaz3
 
2004 6.0 l f error de arranque
2004 6.0 l f error de arranque2004 6.0 l f error de arranque
2004 6.0 l f error de arranque
Valentina Fernádez
 
Trouble shoot and replace motors.pdf
Trouble shoot and replace motors.pdfTrouble shoot and replace motors.pdf
Trouble shoot and replace motors.pdf
madivala nagaraja
 
Maximizing Generator Lifespan Key Strategies For Effective Maintenance
Maximizing Generator Lifespan Key Strategies For Effective MaintenanceMaximizing Generator Lifespan Key Strategies For Effective Maintenance
Maximizing Generator Lifespan Key Strategies For Effective Maintenance
Leddy Power Systems Inc
 
Hydraulic Maintenance and Troubleshooting
Hydraulic Maintenance and TroubleshootingHydraulic Maintenance and Troubleshooting
Hydraulic Maintenance and Troubleshooting
CMA/Flodyne/Hydradyne
 
Handling of turbine side emergencies
Handling of turbine side emergenciesHandling of turbine side emergencies
Handling of turbine side emergencies
Manohar Tatwawadi
 
Boiler Maintenance.pptx
Boiler Maintenance.pptxBoiler Maintenance.pptx
Boiler Maintenance.pptx
SahalSachu
 

Similar to Reason Gen Sets V2 (20)

Submersible Pumps Trouble Shooting
Submersible Pumps Trouble ShootingSubmersible Pumps Trouble Shooting
Submersible Pumps Trouble Shooting
 
ROTEX Controls USA: Valve Automation 101
ROTEX Controls USA: Valve Automation 101 ROTEX Controls USA: Valve Automation 101
ROTEX Controls USA: Valve Automation 101
 
SD.pptx
SD.pptxSD.pptx
SD.pptx
 
Fuel gas system of gas production
Fuel gas system of gas productionFuel gas system of gas production
Fuel gas system of gas production
 
Engine_Application_and_Start_Up_Presentation.pdf
Engine_Application_and_Start_Up_Presentation.pdfEngine_Application_and_Start_Up_Presentation.pdf
Engine_Application_and_Start_Up_Presentation.pdf
 
Why Won't My Generator Maintain Operation After Starting
Why Won't My Generator Maintain Operation After StartingWhy Won't My Generator Maintain Operation After Starting
Why Won't My Generator Maintain Operation After Starting
 
2008 honda pilot service repair manual
2008 honda pilot service repair manual2008 honda pilot service repair manual
2008 honda pilot service repair manual
 
2005 HONDA PILOT Service Repair Manual
2005 HONDA PILOT Service Repair Manual2005 HONDA PILOT Service Repair Manual
2005 HONDA PILOT Service Repair Manual
 
New Holland TV145 Repair Manual
New Holland TV145 Repair ManualNew Holland TV145 Repair Manual
New Holland TV145 Repair Manual
 
Hydraulic Basic
Hydraulic BasicHydraulic Basic
Hydraulic Basic
 
EC8DE5D2-3B41-4599-8A5D-AB833F9397F5.pdf
EC8DE5D2-3B41-4599-8A5D-AB833F9397F5.pdfEC8DE5D2-3B41-4599-8A5D-AB833F9397F5.pdf
EC8DE5D2-3B41-4599-8A5D-AB833F9397F5.pdf
 
1 hydraulic troubleshooting
1 hydraulic troubleshooting1 hydraulic troubleshooting
1 hydraulic troubleshooting
 
MOTORISED VALVE ACTUATORS_SANTHIRAJ001.pptx
MOTORISED VALVE ACTUATORS_SANTHIRAJ001.pptxMOTORISED VALVE ACTUATORS_SANTHIRAJ001.pptx
MOTORISED VALVE ACTUATORS_SANTHIRAJ001.pptx
 
On Power Plant Operation cource In Urdu by Khalid ayaz Soomro.pdf
On Power Plant Operation  cource In Urdu by Khalid ayaz Soomro.pdfOn Power Plant Operation  cource In Urdu by Khalid ayaz Soomro.pdf
On Power Plant Operation cource In Urdu by Khalid ayaz Soomro.pdf
 
2004 6.0 l f error de arranque
2004 6.0 l f error de arranque2004 6.0 l f error de arranque
2004 6.0 l f error de arranque
 
Trouble shoot and replace motors.pdf
Trouble shoot and replace motors.pdfTrouble shoot and replace motors.pdf
Trouble shoot and replace motors.pdf
 
Maximizing Generator Lifespan Key Strategies For Effective Maintenance
Maximizing Generator Lifespan Key Strategies For Effective MaintenanceMaximizing Generator Lifespan Key Strategies For Effective Maintenance
Maximizing Generator Lifespan Key Strategies For Effective Maintenance
 
Hydraulic Maintenance and Troubleshooting
Hydraulic Maintenance and TroubleshootingHydraulic Maintenance and Troubleshooting
Hydraulic Maintenance and Troubleshooting
 
Handling of turbine side emergencies
Handling of turbine side emergenciesHandling of turbine side emergencies
Handling of turbine side emergencies
 
Boiler Maintenance.pptx
Boiler Maintenance.pptxBoiler Maintenance.pptx
Boiler Maintenance.pptx
 

Reason Gen Sets V2

  • 1. Common Reasons For Generator Start Failure Understanding How to Properly Maintain Your Standby Power System Presented By: Jason Blacker and Jeremiah Rosenthal
  • 2. BASIC COMPONENTS OF AN EMERGENCY POWER SYSTEM
  • 5. COMMON REASONS FOR GENERATOR START FAILURE Controls Not in “Auto” • Start switch in “Off/Reset” position – Assure System is in “Auto” – Check weekly • “E- Stop” button pushed in – Reset E-stop – Check generator breaker
  • 8. COMMON REASONS FOR GENERATOR START FAILURE Generator Output Circuit Breaker “Open” • Breaker left in “open” or “off” position – Check breaker position during weekly inspection • Breaker tripped due to fault or shunt trip – Check breaker position during weekly inspection – Continues to trip indicates fault or alarm
  • 9. TYPICAL CONTROL PANEL AND CIRCUIT BREAKER
  • 10. COMMON REASONS FOR GENERATOR START FAILURE Battery Failure • Age: 2-3 year life span – Failure rate increases after 3 yrs – Change before failure for uptime assurance – NFPA recommends new at 30 months • Constant charging – Check weekly electrolyte levels • Corroded terminals – Check weekly & clean terminals as needed
  • 11. COMMON REASONS FOR GENERATOR START FAILURE Battery Failure • Charger turned off – Check weekly charger operation • Vibration – Check hold down bracket
  • 12. BATTERY HOLD DOWN & CHARGER
  • 13. COMMON REASONS FOR GENERATOR START FAILURE Low Coolant Level Alarm/ Shutdown • Low coolant level – Assure system is full to manufacturers recommendation • External or internal leak – Check for visible leaks/pooling of coolant • Block heater – Heat causes coolant to evaporate over time
  • 14. COMMON REASONS FOR GENERATOR START FAILURE Engine Block Heater Failure • Indication is a low coolant temp alarm – Poor cooling system maintenance • Sampling – Circuit breaker to heater is off/tripped – Failed heater element – Heater hose leak – Valves in off position – Heater thermostat adjustment • If equipped (typical setting is 80 to 120)
  • 15. COMMON REASONS FOR GENERATOR START FAILURE Leaks – Fuel or Coolant • Coolant leaks – Hose connections and clamps – Radiator core – Water pump • Fuel leaks – Nat Gas/Propane – Diesel: Filters, injection & supply lines
  • 16. COMMON REASONS FOR GENERATOR START FAILURE Oil Leaks and “Wet stacking” • Common oil leaks – Crankcase breather, filters, drain plug, gaskets, & seals – Check oil level weekly • Wet stacking – Caused by running on light load – Results in unburned diesel fuel in exhaust system – Load bank testing solution – NFPA and by most engine manufacturers recommend load bank testing – Load bank test assures system performs under load
  • 17. COMMON REASONS FOR GENERATOR START FAILURE Air In The Fuel System • Infrequent use – Perform weekly test • Line leak – Visual inspection • Faulty system check valve • Fuel storage tank location • Low fuel
  • 18. COMMON REASONS FOR GENERATOR START FAILURE Engine Out of Fuel • Plugged fuel filters with water and contaminants – Change filters annually & test fuel • Mechanical level gauges inaccurate – Visually verify fuel level • Low level alarms failure – check level • System component failure – Check pumps & valves
  • 19.
  • 20. COMMON REASONS FOR GENERATOR START FAILURE “My Generator is Running!” • Well-maintained emergency power systems operate automatically • Once utility power is restored the generator continues to run for a short time – delay timer in the automatic transfer switch assures steady utility power is available • Transfer Switch Indicators
  • 21. AUTO TRANSFER SWTICH PANEL Generator Power Utility Power
  • 22. AUTO TRANSFER SWITCH PANEL Utility Power Generator Power
  • 24. COMMON REASONS FOR GENERATOR START FAILURE The Power Of A Preventative Maintenance Plan A standby power system requires routine maintenance to guarantee emergency power reliability Visit and free inspection offer
  • 25. COMMON REASONS FOR GENERATOR START FAILURE Weekly “Walk Around” Check List Month Comments/Corrective Action Date of Inspection General Condition of engine/generator Condition of belts and hoses Engine Oil Level Coolant Level Coolant Heater Water Pump Radiator Generator Circuit Breaker Closed Battery System Electrolyte Level Connections Charger Exhaust System Fuel System Fuel level Tank Vents
  • 26. Thank You Visit Our Booth Display #1234 Control Panel Generator Automatic Transfer Switch
  • 27. Thank You Peterson Power Systems 503.288.6411