Pt C, Ch 2, Sec 2
24 Bureau Veritas April 2007
SECTION 2 GENERAL DESIGN REQUIREMENTS
1 Environmental conditions
1.1 General
1.1.1 The electrical components of installations are to be
designed and constructed to operate satisfactorily under the
environmental conditions on board.
In particular, the conditions shown in the tables in this Arti-
cle are to be taken into account.
Note 1: The environmental conditions are characterised by:
• one set of variables including climatic conditions (e.g. ambient
air temperature and humidity), conditions dependent upon
chemically active substances (e.g. salt mist) or mechanically
active substances (e.g. dust or oil), mechanical conditions (e.g.
vibrations or inclinations) and conditions dependent upon
electromagnetic noise and interference, and
• another set of variables dependent mainly upon location on
vessels, operational patterns and transient conditions.
1.2 Ambient air temperatures
1.2.1 For ships classed for unrestricted navigation, the
ambient air temperature ranges shown in Tab 1 are applica-
ble in relation to the various locations of installation.
Table 1 : Ambient air temperature
1.2.2 For ships classed for service in specific zones, the
Society may accept different ranges for the ambient air tem-
perature (e.g. for ships operating outside the tropical belt,
the maximum ambient air temperature may be assumed as
equal to + 40°C instead of + 45°C).
1.3 Humidity
1.3.1 For ships classed for unrestricted service, the humid-
ity ranges shown in Tab 2 are applicable in relation to the
various locations of installation.
Table 2 : Humidity
1.4 Sea water temperatures
1.4.1 The temperatures shown in Tab 3 are applicable to
ships classed for unrestricted service.
Table 3 : Water temperature
1.4.2 For ships classed for service in specific zones, the
Society may accept different values for the sea water tem-
perature (e.g. for ships operating outside the tropical belt,
the maximum sea water temperature may be assumed as
equal to + 25°C instead of + 32°C).
1.5 Salt mist
1.5.1 The applicable salt mist content in the air is to be
1mg/m3
.
1.6 Inclinations
1.6.1 The inclinations applicable are those shown in Tab 4.
The Society may consider deviations from these angles of
inclination taking into consideration the type, size and serv-
ice conditions of the ships.
1.7 Vibrations
1.7.1 In relation to the location of the electrical compo-
nents, the vibration levels given in Tab 5 are to be assumed.
1.7.2 The natural frequencies of the equipment, their sus-
pensions and their supports are to be outside the frequency
ranges specified.
Where this is not possible using a suitable constructional
technique, the equipment vibrations are to be dumped so as
to avoid unacceptable amplifications.
2 Quality of power supply
2.1 General
2.1.1 All electrical components supplied from the main
and emergency systems are to be so designed and manufac-
tured that they are capable of operating satisfactorily under
the normally occuring variations in voltage and frequency
specified from [2.2] to [2.4].
2.2 a.c. distribution systems
2.2.1 For alternating current components the voltage and
frequency variations of power supply shown in Tab 6 are to
be assumed.
Location Temperature range, in °C
Enclosed spaces + 5 + 45
Inside consoles or fitted on com-
bustion engines and similar
+ 5 + 55
Air conditioned areas + 5 + 40
Exposed decks − 25 + 45
Location Humidity
General 95% at 55°C
Air conditioned areas Different values may be considered
on a case by case basis
Coolant Temperature range, in °C
Sea water 0 + 32
Pt C, Ch 2, Sec 2
April 2007 Bureau Veritas 25
Table 4 : Inclination of ship
Table 5 : Vibration levels
Table 6 : Voltage and frequency variations of
power supply in a.c.
2.3 d.c. distribution systems
2.3.1 For direct current components the power supply vari-
ations shown in Tab 7 are to be assumed.
Table 7 : Voltage variations in d.c.
2.3.2 For direct current components supplied by electrical
battery the following voltage variations are to be assumed:
• +30% to −25% for components connected to the bat-
tery during charging (see Note 1)
• +20% to −25% for components not connected to the
battery during charging.
Note 1: Different voltage variations as determined by the charg-
ing/discharging characteristics, including ripple voltage from the
charging device, may be considered.
2.3.3 Any special system, e.g. electronic circuits, whose
function cannot operate satisfactorily within the limits
shown in the tables should not be supplied directly from the
system but by alternative means, e.g. through stabilized
supply.
2.4 Harmonic distortions
2.4.1 For components intended for systems without sub-
stantially static converter loads and supplied by synchro-
nous generators, it is assumed that the total voltage
harmonic distortion does not exceed 5%, and the single
harmonic does not exceed 3% of the nominal voltage.
Type of machinery, equipment or component
Angles of inclination, in degrees (1)
Athwartship Fore-and-aft
static dynamic (4) static dynamic (5)
Machinery and equipment relative to main electrical power installation 15 22,5 5 7,5
Machinery and equipment relative to the emergency power installation
and crew and passenger safety systems of the ship (e.g. emergency source
of power, emergency fire pumps, etc.)
22,5 (2) 22,5 (2) 10 10
Switchgear and associated electrical and electronic components and
remote control systems (3)
22,5 22,5 10 10
(1) Athwartship and fore-and-aft angles may occur simultaneously in their most unfavourable combination.
(2) In the case of gas carriers or chemical tankers, the emergency power supply must also remain operable with the ship flooded to
a final athwartship inclination up to a maximum of 30°.
(3) No undesired switching operations or functional changes may occur up to an angle of inclination of 45°.
(4) The period of dynamic inclination may be assumed equal to 10 s.
(5) The period of dynamic inclination may be assumed equal to 5 s.
Location
Frequency range,
in Hz
Displacement
amplitude, in mm
Acceleration
amplitude g
Machinery spaces, command and control stations, accommodation
spaces, exposed decks, cargo spaces
from 2,0 to 13,2 1,0 −
from 13,2 to 100 − 0,7
On air compressors, on diesel engines and similar
from 2,0 to 25,0 1,6 −
from 25,0 to 100 − 4,0
Masts
from 2,0 to 13,2 3,0 −
from 13,2 to 50 − 2,1
Parameter
Variations
Continuous Transient
Voltage + 6% − 10% ± 20% (recovery time: 1,5 s)
Frequency ± 5% ± 10% (recovery time: 5 s)
Note 1: For alternating current components supplied by
emergency generating sets, different variations may be con-
sidered.
Parameters Variations
Voltage tolerance (continuous) ± 10%
Voltage cyclic variation 5%
Voltage ripple (a.c. r.m.s. over steady d.c.
voltage)
10%

More Related Content

Similar to ship rules

offshore structural design detailed engineering fixed plate form
offshore structural design detailed engineering fixed plate formoffshore structural design detailed engineering fixed plate form
offshore structural design detailed engineering fixed plate form
khalidsiddig8
 
Download-manuals-ground water-manual-gw-volume3designmanualhydro-meteorology
 Download-manuals-ground water-manual-gw-volume3designmanualhydro-meteorology Download-manuals-ground water-manual-gw-volume3designmanualhydro-meteorology
Download-manuals-ground water-manual-gw-volume3designmanualhydro-meteorology
hydrologyproject001
 
Download-manuals-ground water-manual-gw-volume3designmanualhydro-meteorology
 Download-manuals-ground water-manual-gw-volume3designmanualhydro-meteorology Download-manuals-ground water-manual-gw-volume3designmanualhydro-meteorology
Download-manuals-ground water-manual-gw-volume3designmanualhydro-meteorology
hydrologyproject001
 
EEHA - Electrical Equipment in Hazardous areas
EEHA - Electrical Equipment in Hazardous areasEEHA - Electrical Equipment in Hazardous areas
EEHA - Electrical Equipment in Hazardous areas
Kannan Palanisamy
 
JORGE LUIS ROJAS BARNETT
JORGE LUIS ROJAS BARNETT JORGE LUIS ROJAS BARNETT
JORGE LUIS ROJAS BARNETT
Jorge Luis Rojas Barnett
 
A QUICK ESTIMATION METHOD TO DETERMINE HOT RECYCLE REQUIREMENTS FOR CENTRIFUG...
A QUICK ESTIMATION METHOD TO DETERMINE HOT RECYCLE REQUIREMENTS FOR CENTRIFUG...A QUICK ESTIMATION METHOD TO DETERMINE HOT RECYCLE REQUIREMENTS FOR CENTRIFUG...
A QUICK ESTIMATION METHOD TO DETERMINE HOT RECYCLE REQUIREMENTS FOR CENTRIFUG...
Vijay Sarathy
 
Fr a140 e
Fr a140 eFr a140 e
Fr a140 e
Toàn Huỳnh
 
satellite design requirements
satellite design requirementssatellite design requirements
satellite design requirements
Exploring Career Opportunities Internationally
 
DOT 2002 Functional Approach to Flow Assurance
DOT 2002 Functional Approach to Flow AssuranceDOT 2002 Functional Approach to Flow Assurance
DOT 2002 Functional Approach to Flow Assurance
Jean-Francois Saint-Marcoux
 
MTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptxMTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptx
rajkumarmaurya31
 
SG104136BEN_B07_Brochure_UR6-10-15 T_0415
SG104136BEN_B07_Brochure_UR6-10-15 T_0415SG104136BEN_B07_Brochure_UR6-10-15 T_0415
SG104136BEN_B07_Brochure_UR6-10-15 T_0415
Patrick Volluz
 
Download-manuals-surface water-manual-sw-volume3fieldmanualhydro-meteorology...
 Download-manuals-surface water-manual-sw-volume3fieldmanualhydro-meteorology... Download-manuals-surface water-manual-sw-volume3fieldmanualhydro-meteorology...
Download-manuals-surface water-manual-sw-volume3fieldmanualhydro-meteorology...
hydrologyproject0
 
Download-manuals-surface water-manual-sw-volume3fieldmanualhydro-meteorology...
 Download-manuals-surface water-manual-sw-volume3fieldmanualhydro-meteorology... Download-manuals-surface water-manual-sw-volume3fieldmanualhydro-meteorology...
Download-manuals-surface water-manual-sw-volume3fieldmanualhydro-meteorology...
hydrologyproject001
 
Overload capacity of power transformers
Overload capacity of power transformersOverload capacity of power transformers
Overload capacity of power transformers
Leonardo ENERGY
 
Generator rotor earth fault protection
Generator rotor earth fault protectionGenerator rotor earth fault protection
Generator rotor earth fault protection
Aditya Parmar
 
Hager Guide to Surge Protection.pdf
Hager Guide to Surge Protection.pdfHager Guide to Surge Protection.pdf
Hager Guide to Surge Protection.pdf
slipargolok1
 
IRJET - Measurement and Analysis of the Voltage Current Characteristic of a M...
IRJET - Measurement and Analysis of the Voltage Current Characteristic of a M...IRJET - Measurement and Analysis of the Voltage Current Characteristic of a M...
IRJET - Measurement and Analysis of the Voltage Current Characteristic of a M...
IRJET Journal
 
Electricty wiring code 2016
Electricty wiring code 2016Electricty wiring code 2016
Electricty wiring code 2016
Manikandan Mani
 
434 15
434 15434 15
IRJET- Systematic Steps in Overhauling of a Transformer
IRJET- Systematic Steps in Overhauling of a TransformerIRJET- Systematic Steps in Overhauling of a Transformer
IRJET- Systematic Steps in Overhauling of a Transformer
IRJET Journal
 

Similar to ship rules (20)

offshore structural design detailed engineering fixed plate form
offshore structural design detailed engineering fixed plate formoffshore structural design detailed engineering fixed plate form
offshore structural design detailed engineering fixed plate form
 
Download-manuals-ground water-manual-gw-volume3designmanualhydro-meteorology
 Download-manuals-ground water-manual-gw-volume3designmanualhydro-meteorology Download-manuals-ground water-manual-gw-volume3designmanualhydro-meteorology
Download-manuals-ground water-manual-gw-volume3designmanualhydro-meteorology
 
Download-manuals-ground water-manual-gw-volume3designmanualhydro-meteorology
 Download-manuals-ground water-manual-gw-volume3designmanualhydro-meteorology Download-manuals-ground water-manual-gw-volume3designmanualhydro-meteorology
Download-manuals-ground water-manual-gw-volume3designmanualhydro-meteorology
 
EEHA - Electrical Equipment in Hazardous areas
EEHA - Electrical Equipment in Hazardous areasEEHA - Electrical Equipment in Hazardous areas
EEHA - Electrical Equipment in Hazardous areas
 
JORGE LUIS ROJAS BARNETT
JORGE LUIS ROJAS BARNETT JORGE LUIS ROJAS BARNETT
JORGE LUIS ROJAS BARNETT
 
A QUICK ESTIMATION METHOD TO DETERMINE HOT RECYCLE REQUIREMENTS FOR CENTRIFUG...
A QUICK ESTIMATION METHOD TO DETERMINE HOT RECYCLE REQUIREMENTS FOR CENTRIFUG...A QUICK ESTIMATION METHOD TO DETERMINE HOT RECYCLE REQUIREMENTS FOR CENTRIFUG...
A QUICK ESTIMATION METHOD TO DETERMINE HOT RECYCLE REQUIREMENTS FOR CENTRIFUG...
 
Fr a140 e
Fr a140 eFr a140 e
Fr a140 e
 
satellite design requirements
satellite design requirementssatellite design requirements
satellite design requirements
 
DOT 2002 Functional Approach to Flow Assurance
DOT 2002 Functional Approach to Flow AssuranceDOT 2002 Functional Approach to Flow Assurance
DOT 2002 Functional Approach to Flow Assurance
 
MTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptxMTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptx
 
SG104136BEN_B07_Brochure_UR6-10-15 T_0415
SG104136BEN_B07_Brochure_UR6-10-15 T_0415SG104136BEN_B07_Brochure_UR6-10-15 T_0415
SG104136BEN_B07_Brochure_UR6-10-15 T_0415
 
Download-manuals-surface water-manual-sw-volume3fieldmanualhydro-meteorology...
 Download-manuals-surface water-manual-sw-volume3fieldmanualhydro-meteorology... Download-manuals-surface water-manual-sw-volume3fieldmanualhydro-meteorology...
Download-manuals-surface water-manual-sw-volume3fieldmanualhydro-meteorology...
 
Download-manuals-surface water-manual-sw-volume3fieldmanualhydro-meteorology...
 Download-manuals-surface water-manual-sw-volume3fieldmanualhydro-meteorology... Download-manuals-surface water-manual-sw-volume3fieldmanualhydro-meteorology...
Download-manuals-surface water-manual-sw-volume3fieldmanualhydro-meteorology...
 
Overload capacity of power transformers
Overload capacity of power transformersOverload capacity of power transformers
Overload capacity of power transformers
 
Generator rotor earth fault protection
Generator rotor earth fault protectionGenerator rotor earth fault protection
Generator rotor earth fault protection
 
Hager Guide to Surge Protection.pdf
Hager Guide to Surge Protection.pdfHager Guide to Surge Protection.pdf
Hager Guide to Surge Protection.pdf
 
IRJET - Measurement and Analysis of the Voltage Current Characteristic of a M...
IRJET - Measurement and Analysis of the Voltage Current Characteristic of a M...IRJET - Measurement and Analysis of the Voltage Current Characteristic of a M...
IRJET - Measurement and Analysis of the Voltage Current Characteristic of a M...
 
Electricty wiring code 2016
Electricty wiring code 2016Electricty wiring code 2016
Electricty wiring code 2016
 
434 15
434 15434 15
434 15
 
IRJET- Systematic Steps in Overhauling of a Transformer
IRJET- Systematic Steps in Overhauling of a TransformerIRJET- Systematic Steps in Overhauling of a Transformer
IRJET- Systematic Steps in Overhauling of a Transformer
 

Recently uploaded

ITSM Integration with MuleSoft.pptx
ITSM  Integration with MuleSoft.pptxITSM  Integration with MuleSoft.pptx
ITSM Integration with MuleSoft.pptx
VANDANAMOHANGOUDA
 
SCALING OF MOS CIRCUITS m .pptx
SCALING OF MOS CIRCUITS m                 .pptxSCALING OF MOS CIRCUITS m                 .pptx
SCALING OF MOS CIRCUITS m .pptx
harshapolam10
 
Asymmetrical Repulsion Magnet Motor Ratio 6-7.pdf
Asymmetrical Repulsion Magnet Motor Ratio 6-7.pdfAsymmetrical Repulsion Magnet Motor Ratio 6-7.pdf
Asymmetrical Repulsion Magnet Motor Ratio 6-7.pdf
felixwold
 
5G Radio Network Througput Problem Analysis HCIA.pdf
5G Radio Network Througput Problem Analysis HCIA.pdf5G Radio Network Througput Problem Analysis HCIA.pdf
5G Radio Network Througput Problem Analysis HCIA.pdf
AlvianRamadhani5
 
Bituminous road construction project based learning report
Bituminous road construction project based learning reportBituminous road construction project based learning report
Bituminous road construction project based learning report
CE19KaushlendraKumar
 
OOPS_Lab_Manual - programs using C++ programming language
OOPS_Lab_Manual - programs using C++ programming languageOOPS_Lab_Manual - programs using C++ programming language
OOPS_Lab_Manual - programs using C++ programming language
PreethaV16
 
Transformers design and coooling methods
Transformers design and coooling methodsTransformers design and coooling methods
Transformers design and coooling methods
Roger Rozario
 
Determination of Equivalent Circuit parameters and performance characteristic...
Determination of Equivalent Circuit parameters and performance characteristic...Determination of Equivalent Circuit parameters and performance characteristic...
Determination of Equivalent Circuit parameters and performance characteristic...
pvpriya2
 
An Introduction to the Compiler Designss
An Introduction to the Compiler DesignssAn Introduction to the Compiler Designss
An Introduction to the Compiler Designss
ElakkiaU
 
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
upoux
 
UNIT 4 LINEAR INTEGRATED CIRCUITS-DIGITAL ICS
UNIT 4 LINEAR INTEGRATED CIRCUITS-DIGITAL ICSUNIT 4 LINEAR INTEGRATED CIRCUITS-DIGITAL ICS
UNIT 4 LINEAR INTEGRATED CIRCUITS-DIGITAL ICS
vmspraneeth
 
Zener Diode and its V-I Characteristics and Applications
Zener Diode and its V-I Characteristics and ApplicationsZener Diode and its V-I Characteristics and Applications
Zener Diode and its V-I Characteristics and Applications
Shiny Christobel
 
Mechanical Engineering on AAI Summer Training Report-003.pdf
Mechanical Engineering on AAI Summer Training Report-003.pdfMechanical Engineering on AAI Summer Training Report-003.pdf
Mechanical Engineering on AAI Summer Training Report-003.pdf
21UME003TUSHARDEB
 
SENTIMENT ANALYSIS ON PPT AND Project template_.pptx
SENTIMENT ANALYSIS ON PPT AND Project template_.pptxSENTIMENT ANALYSIS ON PPT AND Project template_.pptx
SENTIMENT ANALYSIS ON PPT AND Project template_.pptx
b0754201
 
Accident detection system project report.pdf
Accident detection system project report.pdfAccident detection system project report.pdf
Accident detection system project report.pdf
Kamal Acharya
 
Object Oriented Analysis and Design - OOAD
Object Oriented Analysis and Design - OOADObject Oriented Analysis and Design - OOAD
Object Oriented Analysis and Design - OOAD
PreethaV16
 
smart pill dispenser is designed to improve medication adherence and safety f...
smart pill dispenser is designed to improve medication adherence and safety f...smart pill dispenser is designed to improve medication adherence and safety f...
smart pill dispenser is designed to improve medication adherence and safety f...
um7474492
 
Open Channel Flow: fluid flow with a free surface
Open Channel Flow: fluid flow with a free surfaceOpen Channel Flow: fluid flow with a free surface
Open Channel Flow: fluid flow with a free surface
Indrajeet sahu
 
Power Electronics- AC -AC Converters.pptx
Power Electronics- AC -AC Converters.pptxPower Electronics- AC -AC Converters.pptx
Power Electronics- AC -AC Converters.pptx
Poornima D
 
原版制作(Humboldt毕业证书)柏林大学毕业证学位证一模一样
原版制作(Humboldt毕业证书)柏林大学毕业证学位证一模一样原版制作(Humboldt毕业证书)柏林大学毕业证学位证一模一样
原版制作(Humboldt毕业证书)柏林大学毕业证学位证一模一样
ydzowc
 

Recently uploaded (20)

ITSM Integration with MuleSoft.pptx
ITSM  Integration with MuleSoft.pptxITSM  Integration with MuleSoft.pptx
ITSM Integration with MuleSoft.pptx
 
SCALING OF MOS CIRCUITS m .pptx
SCALING OF MOS CIRCUITS m                 .pptxSCALING OF MOS CIRCUITS m                 .pptx
SCALING OF MOS CIRCUITS m .pptx
 
Asymmetrical Repulsion Magnet Motor Ratio 6-7.pdf
Asymmetrical Repulsion Magnet Motor Ratio 6-7.pdfAsymmetrical Repulsion Magnet Motor Ratio 6-7.pdf
Asymmetrical Repulsion Magnet Motor Ratio 6-7.pdf
 
5G Radio Network Througput Problem Analysis HCIA.pdf
5G Radio Network Througput Problem Analysis HCIA.pdf5G Radio Network Througput Problem Analysis HCIA.pdf
5G Radio Network Througput Problem Analysis HCIA.pdf
 
Bituminous road construction project based learning report
Bituminous road construction project based learning reportBituminous road construction project based learning report
Bituminous road construction project based learning report
 
OOPS_Lab_Manual - programs using C++ programming language
OOPS_Lab_Manual - programs using C++ programming languageOOPS_Lab_Manual - programs using C++ programming language
OOPS_Lab_Manual - programs using C++ programming language
 
Transformers design and coooling methods
Transformers design and coooling methodsTransformers design and coooling methods
Transformers design and coooling methods
 
Determination of Equivalent Circuit parameters and performance characteristic...
Determination of Equivalent Circuit parameters and performance characteristic...Determination of Equivalent Circuit parameters and performance characteristic...
Determination of Equivalent Circuit parameters and performance characteristic...
 
An Introduction to the Compiler Designss
An Introduction to the Compiler DesignssAn Introduction to the Compiler Designss
An Introduction to the Compiler Designss
 
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
 
UNIT 4 LINEAR INTEGRATED CIRCUITS-DIGITAL ICS
UNIT 4 LINEAR INTEGRATED CIRCUITS-DIGITAL ICSUNIT 4 LINEAR INTEGRATED CIRCUITS-DIGITAL ICS
UNIT 4 LINEAR INTEGRATED CIRCUITS-DIGITAL ICS
 
Zener Diode and its V-I Characteristics and Applications
Zener Diode and its V-I Characteristics and ApplicationsZener Diode and its V-I Characteristics and Applications
Zener Diode and its V-I Characteristics and Applications
 
Mechanical Engineering on AAI Summer Training Report-003.pdf
Mechanical Engineering on AAI Summer Training Report-003.pdfMechanical Engineering on AAI Summer Training Report-003.pdf
Mechanical Engineering on AAI Summer Training Report-003.pdf
 
SENTIMENT ANALYSIS ON PPT AND Project template_.pptx
SENTIMENT ANALYSIS ON PPT AND Project template_.pptxSENTIMENT ANALYSIS ON PPT AND Project template_.pptx
SENTIMENT ANALYSIS ON PPT AND Project template_.pptx
 
Accident detection system project report.pdf
Accident detection system project report.pdfAccident detection system project report.pdf
Accident detection system project report.pdf
 
Object Oriented Analysis and Design - OOAD
Object Oriented Analysis and Design - OOADObject Oriented Analysis and Design - OOAD
Object Oriented Analysis and Design - OOAD
 
smart pill dispenser is designed to improve medication adherence and safety f...
smart pill dispenser is designed to improve medication adherence and safety f...smart pill dispenser is designed to improve medication adherence and safety f...
smart pill dispenser is designed to improve medication adherence and safety f...
 
Open Channel Flow: fluid flow with a free surface
Open Channel Flow: fluid flow with a free surfaceOpen Channel Flow: fluid flow with a free surface
Open Channel Flow: fluid flow with a free surface
 
Power Electronics- AC -AC Converters.pptx
Power Electronics- AC -AC Converters.pptxPower Electronics- AC -AC Converters.pptx
Power Electronics- AC -AC Converters.pptx
 
原版制作(Humboldt毕业证书)柏林大学毕业证学位证一模一样
原版制作(Humboldt毕业证书)柏林大学毕业证学位证一模一样原版制作(Humboldt毕业证书)柏林大学毕业证学位证一模一样
原版制作(Humboldt毕业证书)柏林大学毕业证学位证一模一样
 

ship rules

  • 1. Pt C, Ch 2, Sec 2 24 Bureau Veritas April 2007 SECTION 2 GENERAL DESIGN REQUIREMENTS 1 Environmental conditions 1.1 General 1.1.1 The electrical components of installations are to be designed and constructed to operate satisfactorily under the environmental conditions on board. In particular, the conditions shown in the tables in this Arti- cle are to be taken into account. Note 1: The environmental conditions are characterised by: • one set of variables including climatic conditions (e.g. ambient air temperature and humidity), conditions dependent upon chemically active substances (e.g. salt mist) or mechanically active substances (e.g. dust or oil), mechanical conditions (e.g. vibrations or inclinations) and conditions dependent upon electromagnetic noise and interference, and • another set of variables dependent mainly upon location on vessels, operational patterns and transient conditions. 1.2 Ambient air temperatures 1.2.1 For ships classed for unrestricted navigation, the ambient air temperature ranges shown in Tab 1 are applica- ble in relation to the various locations of installation. Table 1 : Ambient air temperature 1.2.2 For ships classed for service in specific zones, the Society may accept different ranges for the ambient air tem- perature (e.g. for ships operating outside the tropical belt, the maximum ambient air temperature may be assumed as equal to + 40°C instead of + 45°C). 1.3 Humidity 1.3.1 For ships classed for unrestricted service, the humid- ity ranges shown in Tab 2 are applicable in relation to the various locations of installation. Table 2 : Humidity 1.4 Sea water temperatures 1.4.1 The temperatures shown in Tab 3 are applicable to ships classed for unrestricted service. Table 3 : Water temperature 1.4.2 For ships classed for service in specific zones, the Society may accept different values for the sea water tem- perature (e.g. for ships operating outside the tropical belt, the maximum sea water temperature may be assumed as equal to + 25°C instead of + 32°C). 1.5 Salt mist 1.5.1 The applicable salt mist content in the air is to be 1mg/m3 . 1.6 Inclinations 1.6.1 The inclinations applicable are those shown in Tab 4. The Society may consider deviations from these angles of inclination taking into consideration the type, size and serv- ice conditions of the ships. 1.7 Vibrations 1.7.1 In relation to the location of the electrical compo- nents, the vibration levels given in Tab 5 are to be assumed. 1.7.2 The natural frequencies of the equipment, their sus- pensions and their supports are to be outside the frequency ranges specified. Where this is not possible using a suitable constructional technique, the equipment vibrations are to be dumped so as to avoid unacceptable amplifications. 2 Quality of power supply 2.1 General 2.1.1 All electrical components supplied from the main and emergency systems are to be so designed and manufac- tured that they are capable of operating satisfactorily under the normally occuring variations in voltage and frequency specified from [2.2] to [2.4]. 2.2 a.c. distribution systems 2.2.1 For alternating current components the voltage and frequency variations of power supply shown in Tab 6 are to be assumed. Location Temperature range, in °C Enclosed spaces + 5 + 45 Inside consoles or fitted on com- bustion engines and similar + 5 + 55 Air conditioned areas + 5 + 40 Exposed decks − 25 + 45 Location Humidity General 95% at 55°C Air conditioned areas Different values may be considered on a case by case basis Coolant Temperature range, in °C Sea water 0 + 32
  • 2. Pt C, Ch 2, Sec 2 April 2007 Bureau Veritas 25 Table 4 : Inclination of ship Table 5 : Vibration levels Table 6 : Voltage and frequency variations of power supply in a.c. 2.3 d.c. distribution systems 2.3.1 For direct current components the power supply vari- ations shown in Tab 7 are to be assumed. Table 7 : Voltage variations in d.c. 2.3.2 For direct current components supplied by electrical battery the following voltage variations are to be assumed: • +30% to −25% for components connected to the bat- tery during charging (see Note 1) • +20% to −25% for components not connected to the battery during charging. Note 1: Different voltage variations as determined by the charg- ing/discharging characteristics, including ripple voltage from the charging device, may be considered. 2.3.3 Any special system, e.g. electronic circuits, whose function cannot operate satisfactorily within the limits shown in the tables should not be supplied directly from the system but by alternative means, e.g. through stabilized supply. 2.4 Harmonic distortions 2.4.1 For components intended for systems without sub- stantially static converter loads and supplied by synchro- nous generators, it is assumed that the total voltage harmonic distortion does not exceed 5%, and the single harmonic does not exceed 3% of the nominal voltage. Type of machinery, equipment or component Angles of inclination, in degrees (1) Athwartship Fore-and-aft static dynamic (4) static dynamic (5) Machinery and equipment relative to main electrical power installation 15 22,5 5 7,5 Machinery and equipment relative to the emergency power installation and crew and passenger safety systems of the ship (e.g. emergency source of power, emergency fire pumps, etc.) 22,5 (2) 22,5 (2) 10 10 Switchgear and associated electrical and electronic components and remote control systems (3) 22,5 22,5 10 10 (1) Athwartship and fore-and-aft angles may occur simultaneously in their most unfavourable combination. (2) In the case of gas carriers or chemical tankers, the emergency power supply must also remain operable with the ship flooded to a final athwartship inclination up to a maximum of 30°. (3) No undesired switching operations or functional changes may occur up to an angle of inclination of 45°. (4) The period of dynamic inclination may be assumed equal to 10 s. (5) The period of dynamic inclination may be assumed equal to 5 s. Location Frequency range, in Hz Displacement amplitude, in mm Acceleration amplitude g Machinery spaces, command and control stations, accommodation spaces, exposed decks, cargo spaces from 2,0 to 13,2 1,0 − from 13,2 to 100 − 0,7 On air compressors, on diesel engines and similar from 2,0 to 25,0 1,6 − from 25,0 to 100 − 4,0 Masts from 2,0 to 13,2 3,0 − from 13,2 to 50 − 2,1 Parameter Variations Continuous Transient Voltage + 6% − 10% ± 20% (recovery time: 1,5 s) Frequency ± 5% ± 10% (recovery time: 5 s) Note 1: For alternating current components supplied by emergency generating sets, different variations may be con- sidered. Parameters Variations Voltage tolerance (continuous) ± 10% Voltage cyclic variation 5% Voltage ripple (a.c. r.m.s. over steady d.c. voltage) 10%