A Division of the City of Idaho Falls “A Community with its own kind of energy”
N-2 Substation Switching Study
Date Author Revision
May 18, 2015 Eric Gubler 0
May 20, 2015 Eric Gubler 1
_________________________________________________________________________________________________
PO Box 50220 Phone: 208-612-8430
140 S Capital Ave. Fax: 208-612-8435
Idaho Falls, ID 83405-0220 www.ifpower.org
N-2 Substation Switching Study
1
TABLE OF CONTENTS
1.0 Purpose...................................................................................................................................... 3
2.0 Data Sources ............................................................................................................................. 3
3.0 Guidelines and Assumptions..................................................................................................... 3
4.0 Summary................................................................................................................................... 3
5.0 Body/Data ................................................................................................................................. 4
5.1 Scenarios that work.............................................................................................................. 5
5.1.1 Rack & Milligan .......................................................................................................... 5
5.1.2 Rack & Sugarmill ........................................................................................................ 6
5.1.3 Rack & Fifteenth St. .................................................................................................... 7
5.1.4 Rack & Westside.......................................................................................................... 8
5.1.5 Milligan & Sugarmill................................................................................................... 9
5.1.6 Milligan & Fifteenth St.............................................................................................. 10
5.1.7 Milligan & York Road............................................................................................... 11
5.1.8 Milligan & Harrison................................................................................................... 12
5.1.9 Milligan & Hatch....................................................................................................... 13
5.1.10 Milligan & Westside................................................................................................ 14
5.1.11 Sugarmill & Fifteenth St.......................................................................................... 15
5.1.12 Sugarmill & York Road........................................................................................... 16
5.1.13 Sugarmill & Westside.............................................................................................. 17
5.1.14 Fifteenth St. & York Road....................................................................................... 18
5.1.15 Fifteenth St. & Westside.......................................................................................... 19
5.1.16 York Road & Westside............................................................................................ 20
5.1.17 Harrison & Westside................................................................................................ 21
5.1.18 Hatch & Westside .................................................................................................... 22
5.2 Scenarios that work with assumptions............................................................................... 23
5.2.1 Rack & Templeview .................................................................................................. 23
5.2.2 Rack & N. Boulevard................................................................................................. 24
5.2.3 Rack & City ............................................................................................................... 25
5.2.4 Rack & York.............................................................................................................. 26
5.2.5 Rack & Harrison ........................................................................................................ 27
5.2.6 Rack & Hatch............................................................................................................. 28
5.2.7 Milligan & Templeview............................................................................................. 29
5.2.8 Milligan & N. Boulevard........................................................................................... 30
N-2 Substation Switching Study
2
5.2.9 Milligan & City.......................................................................................................... 31
5.2.10 Templeview & Sugarmill......................................................................................... 32
5.2.11 Templeview & Fifteenth St...................................................................................... 33
5.2.12 Templeview & City.................................................................................................. 34
5.2.13 Templeview & York Road....................................................................................... 35
5.2.14 Templeview & Harrison .......................................................................................... 36
5.2.15 Templeview & Hatch............................................................................................... 37
5.2.16 Templeview & Westside.......................................................................................... 38
5.2.17 Sugarmill & N. Boulevard....................................................................................... 39
5.2.18 Sugarmill & City...................................................................................................... 40
5.2.19 Fifteenth St. & N. Boulevard................................................................................... 41
5.2.20 Fifteenth St. & City.................................................................................................. 42
5.2.21 Fifteenth St. & Hatch............................................................................................... 43
5.2.22 N. Boulevard & York Road ..................................................................................... 44
5.2.23 N. Boulevard & Harrison......................................................................................... 45
5.2.24 N. Boulevard & Hatch ............................................................................................. 46
5.2.25 N. Boulevard & Westside ........................................................................................ 47
5.2.26 City & York Road.................................................................................................... 48
5.2.27 City & Harrison........................................................................................................ 49
5.2.28 City & Hatch............................................................................................................ 50
5.2.29 City & Westside....................................................................................................... 51
5.2.30 York Road & Harrison............................................................................................. 52
5.2.31 York Road & Hatch ................................................................................................. 53
5.3 Scenarios that do not work................................................................................................. 54
5.3.1 Templeview & N. Boulevard..................................................................................... 54
5.3.2 Sugarmill & Harrison................................................................................................. 54
5.3.3 Sugarmill & Hatch..................................................................................................... 54
5.3.4 Fifteenth St. & Harrison............................................................................................. 54
5.3.5 N. Boulevard & City.................................................................................................. 54
5.3.6 Harrison & Hatch....................................................................................................... 54
6.0 Conclusion .............................................................................................................................. 55
N-2 Substation Switching Study
3
1.0 PURPOSE
The purpose of this study is to create switching procedures for N-2 type situations. An N-2
situation is when any two substations have failed. This study will determine which N-2 situations
can and cannot successfully be handled by the current system. This will indicate weaknesses in
the grid and provide meaningful information for future improvements to the grid. Data from the
study will be divided into three main categories: (1) scenarios that work, (2) scenarios that work
with assumptions, and (3) scenarios that do not work.
2.0 DATA SOURCES
Data needed for creating switching procedures was taken from Idaho Falls Power’s AutoCAD
drawing, IFP-E102 Rev 4, 12.5KV ONE LINE DIAGRAM.
3.0 GUIDELINES AND ASSUMPTIONS
Guidelines and assumptions for the switching procedures were taken from section 4.l of the Load
Forecast Study completed by Ben Jenkins, which states:
Circuit loads ideally to be less than 8.5MW but shall not be greater than 13MW.
Substation loads ideally to be less than 15MW but shall not be greater than 25MW.
For many of the switching procedures it is assumed that the aux bus can be used even when the
rest of the substation is down.
4.0 SUMMARY
Using the current grid, 49 of the 55 possible N-2 type situations may successfully be handled
without interruption to power service. However, 31 of the 45 successful situations currently have
an assumption that the aux bus can be used in the switching procedure. New connections to
Templeview, City, and N. Boulevard’s islanded feeders are needed to remove this dependency.
New connections, switches, and upgraded wire ampacity are also needed at critical points in the
grid to increase grid stability and provide switching procedures for the remaining N-2 situations
that currently cannot be handled.
N-2 Substation Switching Study
4
5.0 BODY/DATA
The following image is a graphical representation of the switching procedures. Each cell in the
table represents one switching procedure. The value in the cell is the combined load, in
Megawatts, that needs to be transferred away from the shutdown substations. The color fill of the
cell indicates how much power is being transferred away from the substations in the procedure in
comparison to other N-2 situations; greener indicates a smaller transfer and redder indicates a
larger transfer. The color of the text represents whether the switching procedure can be
completed (black text), completed with assumptions (light blue text), or if it cannot be completed
(red text). The additional information at the bottom left highlights which substation combinations
cannot be completed.
RACK
SUB-1
MILLIGAN
SUB-3
TEMPLEVIEW
SUB-4
SUGARMILL
SUB-6
FIFTEENTH ST.
SUB-9
N. BOULEVARD
SUB-12
CITY SUB-
13
YORK ROAD
SUB-14
HARRISON
SUB-16
HATCH SUB-
17
WESTSIDE
SUB-18
RACK SUB-1 26.7 26.3 34.7 31.6 37.8 26.0 27.8 29.7 30.8 24.4
MILLIGAN SUB-3 21.8 30.2 27.1 33.3 21.5 23.3 25.2 26.3 19.9
TEMPLEVIEW SUB-4 29.8 26.7 32.9 21.1 22.9 24.8 25.9 19.5
SUGARMILL SUB-6 35.1 41.3 29.5 31.3 33.2 34.3 27.9
FIFTEENTH ST. SUB-9 38.2 26.4 28.2 30.1 31.2 24.8
N. BOULEVARD SUB-12 32.6 34.4 36.3 37.4 31.0
CITY SUB-13 22.6 24.5 25.6 19.2
YORK ROAD SUB-14 26.3 27.4 21.0
HARRISON SUB-16 29.3 22.9
HATCH SUB-17 24.0
WESTSIDE SUB-18
HARRISON
SUGARMILL Switching procedures that work
N. BOULEVARD
HATCH Switching procedures that work with assumptions
TEMPLEVIEW
FIFTEENTH ST. Switching procedures that do not work
CITY
RACK
YORK ROAD
MILLIGAN
WESTSIDE
KEY
1 -(N. Boulevard)
3 - (Hatch, Sugarmill, Fifteenth)
2 -(Hatch, Harrison)
2 -(City, Templeview)
2 -(Harrison, Sugarmill)
0 -()
0 -()
0 -()
1 -(Harrison)
0 -()
1 -(N. Boulevard)
N-2 Substation Switching Study
5
5.1 Scenarios that work
5.1.1 Rack & Milligan
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H33 CLOSED 4B6-1 0.9 0.0 4B5-3 0.6 0.0
4B2-1 OPEN 4B5-1 7.1 0.0 4B4-3 9.9 0.0
4D85 CLOSED 4B4-1 0.5 0.0 4B3-3 0.6 0.0
4B3-1 OPEN 4B3-1 6.2 0.0
4H52 CLOSED 4B2-1 0.9 0.0
4B4-1 OPEN
Transformer
Total
15.6 0.0
Transformer
Total
11.1 0.0
4H16 CLOSED
4H3 OPEN
4H10 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B5-1 OPEN 4B2-9 7.8 7.8 4B2-4 7.7 11.8
4H53 CLOSED 4B3-9 8.2 12.1 4B3-4 0.6 0.6
4B6-1 OPEN 4B4-4 2.4 2.4
4D18 CLOSED
4R5 OPEN
4D24 CLOSED
Transformer
Total
16.0 19.9
Transformer
Total
10.7 14.8
4D29 OPEN
4H46 CLOSED
4B1-3 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-18 8.8 11.7 4B3-14 0.7 1.6
Switching Description: 4B4-14 6.8 6.8
4B5-14 0.0 0.0
4B6-14 2.9 3.8
4B7-14 1.8 8.0
Transformer
Total
8.8 11.7
Transformer
Total
12.2 20.2
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-13 2.1 2.1
4B3-13 3.9 8.5
4B4-13 4.4 7.6
Transformer
Total
10.4 18.2
4B2-14B3-14B4-14B5-14B6-1
WESTSIDE BREAKERS YORK ROAD BREAKERS
CITY BREAKERS
SWITCHING PROCEDURE RACK BREAKERS MILLIGAN BREAKERS
FIFTEENTH ST. BREAKERS TEMPLEVIEW BREAKERS
4B5-3,4B4-3,&4B3-3
4B2-1 transferring to 4B6-14
4B3-1 transferring to 4B7-14
4B4-1 transferring to 4B3-18
4B4-13 taking load off of 4B3-9
4B5-1 transferring to 4B3-9
4B6-1 transferring to 4B3-14
4B2-4 taking load off of 4B4-3
4B3-18 taking load off of 4B4-3
4B3-3 transferring to 4B3-13
4B4-3 transferring to 4B3-13
4B5-3 transferring to 4B3-13
N-2 Substation Switching Study
6
5.1.2 Rack & Sugarmill
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H33 CLOSED 4B6-1 0.9 0.0 4B2-6 7.6 0.0
4B2-1 OPEN 4B5-1 7.1 0.0 4B3-6 6.8 0.0
4H20 CLOSED 4B4-1 0.5 0.0 4B4-6 4.7 0.0
4D52 OPEN 4B3-1 6.2 0.0
4D85 CLOSED 4B2-1 0.9 0.0
4B3-1 OPEN
Transformer
Total
15.6 0.0
Transformer
Total
19.1 0.0
4H36 CLOSED
4B4-1 OPEN
4H16 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H3 OPEN 4B5-3 0.6 1.1 4B2-13 2.1 2.1
4H10 CLOSED 4B4-3 9.9 9.9 4B3-13 3.9 3.9
4B5-1 OPEN 4B3-3 0.6 0.6 4B4-13 4.4 10.4
4H53 CLOSED
4B6-1 OPEN
4H58 CLOSED
Transformer
Total
11.1 11.6
Transformer
Total
10.4 16.4
4H55 OPEN
4H45 CLOSED
4H45 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H5 CLOSED 4B2-16 2.2 2.2 4B4-17 12.0 9.8
4B2-6 OPEN 4B3-16 6.7 11.4 4B3-17 1.0 4.5
4H26 CLOSED 4B4-16 4.6 8.0 4B2-17 2.2 9.0
4S8 OPEN 4B5-16 0.6 0.6
4H49 CLOSED
4B3-6 OPEN
Transformer
Total
14.1 22.2
Transformer
Total
15.2 23.3
4H21 CLOSED
4B4-6 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
Switching Description: 4B3-14 0.7 1.6 4B2-9 7.8 7.8
4B4-14 6.8 6.8 4B3-9 8.2 12.1
4B5-14 0.0 0.0
4B6-14 2.9 3.8
4B7-14 1.8 6.8
Transformer
Total
12.2 19.0
Transformer
Total
16.0 19.9
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-12 11.0 12.3
4B2-12 2.1 2.1
Transformer
Total
13.1 14.4
4B3-64B4-6
4B2-1 transferring to 4B6-14
4B3-1 transferring to 4B4-16 & 4B7-
14
4B4-1 transferring to 4B5-3
4B4-13 taking load off of 4B3-9
4B5-1 transferring to 4B3-9
4B6-1 transferring to 4B3-14
4B4-13 taking load off of 4B3-12
4B3-12 taking load off of 4B2-6
4B2-6 transferring to 4B3-17
4B4-16 taking load off of 4B4-17
4B3-6 transferring to 4B2-17
4B4-6 transferring to 4B3-16
HARRISON BREAKERS HATCH BREAKERS
YORK ROAD BREAKERS FIFTEENTH ST. BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
4B6-14B5-14B2-6
SWITCHING PROCEDURE RACK BREAKERS SUGARMILL BREAKERS
MILLIGAN BREAKERS CITY BREAKERS
4B2-14B3-14B4-1
N-2 Substation Switching Study
7
5.1.3 Rack & Fifteenth St.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H33 CLOSED 4B6-1 0.9 0.0 4B2-9 7.8 0.0
4B2-1 OPEN 4B5-1 7.1 0.0 4B3-9 8.2 0.0
4D85 CLOSED 4B4-1 0.5 0.0
4B3-1 OPEN 4B3-1 6.2 0.0
4H52 CLOSED 4B2-1 0.9 0.0
4B4-1 OPEN
Transformer
Total
15.6 0.0
Transformer
Total
16.0 0.0
4H20 CLOSED
4D52 OPEN
4H30 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H50 OPEN 4B2-16 2.2 2.2 4B3-18 8.8 9.3
4H51 CLOSED 4B3-16 6.7 8.2
4B5-1 OPEN 4B4-16 4.6 11.6
4H53 CLOSED 4B5-16 0.6 0.6
4B6-1 OPEN
4H11 CLOSED
Transformer
Total
14.1 22.6
Transformer
Total
8.8 9.3
4H22 OPEN
4H12 CLOSED
4D39 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H26 CLOSED 4B2-13 2.1 2.1 4B3-14 0.7 1.6
4S8 OPEN 4B3-13 3.9 9.5 4B4-14 6.8 6.8
4H49 CLOSED 4B4-13 4.4 7.0 4B5-14 0.0 0.0
4H42 OPEN 4B6-14 2.9 3.8
4D16 CLOSED 4B7-14 1.8 12.5
4H40 OPEN
Transformer
Total
10.4 18.6
Transformer
Total
12.2 24.7
4H34 CLOSED
4B2-9 OPEN
4H16 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H19 OPEN 4B4-17 12.0 6.2 4B2-6 7.6 7.6
4H8 CLOSED 4B3-17 1.0 1.0 4B3-6 6.8 0.2
4B3-9 OPEN 4B2-17 2.2 8.8 4B4-6 4.7 12.4
Switching Description:
Transformer
Total
15.2 16.0
Transformer
Total
19.1 20.2
SWITCHING PROCEDURE RACK BREAKERS FIFTEENTH ST. BREAKERS
4B2-1
SUGARMILL BREAKERS
4B3-14B2-94B3-9
4B2-1 transferring to 4B6-14
4B3-1 transferring to 4B7-14
4B4-1 transferring to 4B3-18
4B4-16 taking load off of 4B7-14
4B2-9 taking load off of 4B5-1
4B5-1 transferring to 4B7-14
4B6-1 transferring to 4B3-14
4B3-16 taking load off of 4B4-16
4B4-16 taking load off of 4B2-9
4B4-16 taking load off of 4B4-17
4B2-17 taking load off of 4B3-6
4B4-6 taking load off of 4B4-17
4B2-9 transferring to 4B4-6
4B4-13 taking load off of 4B3-9
4B3-9 transferring to 4B3-13
4B6-14B4-1
HARRISON BREAKERS WESTSIDE BREAKERS
CITY BREAKERS YORK ROAD BREAKERS
4B5-1
HATCH BREAKERS
N-2 Substation Switching Study
8
5.1.4 Rack & Westside
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H33 CLOSED 4B6-1 0.9 0.0 4B3-18 8.8 0.0
4B2-1 OPEN 4B5-1 7.1 0.0
4D85 CLOSED 4B4-1 0.5 0.0
4B3-1 OPEN 4B3-1 6.2 0.0
4H36 CLOSED 4B2-1 0.9 0.0
4B4-1 OPEN
Transformer
Total
15.6 0.0
Transformer
Total
8.8 0.0
4H8 CLOSED
4H3 OPEN
4H10 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B5-1 OPEN 4B3-14 0.7 1.6 4B5-3 0.6 9.9
4H53 CLOSED 4B4-14 6.8 6.8 4B4-3 9.9 9.9
4B6-1 OPEN 4B5-14 0.0 0.0 4B3-3 0.6 0.6
4H52 CLOSED 4B6-14 2.9 3.8
4B3-18 OPEN 4B7-14 1.8 8.0
Transformer
Total
12.2 20.2
Transformer
Total
11.1 20.4
Switching Description:
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-13 2.1 2.1 4B2-9 7.8 7.8
4B3-13 3.9 7.1 4B3-9 8.2 12.1
4B4-13 4.4 4.4
Transformer
Total
10.4 13.6
Transformer
Total
16.0 19.9
MILLIGAN BREAKERS
4B6-1
CITY BREAKERS FIFTEENTH ST. BREAKERS
SWITCHING PROCEDURE RACK BREAKERS WESTSIDE BREAKERS
4B2-14B3-14B3-184B4-14B5-1
YORK ROAD BREAKERS
4B2-1 transferring to 4B6-14
4B3-1 transferring to 4B7-14
4B4-1 transferring to 4B5-3
4B3-13 taking load off of 4B3-9
4B5-1 transferring to 4B3-9
4B6-1 transferring to 4B3-14
4B3-18 transferring to 4B5-3
N-2 Substation Switching Study
9
5.1.5 Milligan & Sugarmill
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H46 CLOSED 4B5-3 0.6 0.0 4B2-6 7.6 0.0
4B3-3 OPEN 4B4-3 9.9 0.0 4B3-6 6.8 0.0
4D18 CLOSED 4B3-3 0.6 0.0 4B4-6 4.7 0.0
4D46 OPEN
4D24 CLOSED
4D40 OPEN
Transformer
Total
11.1 0.0
Transformer
Total
19.1 0.0
4H36 CLOSED
4B1-3 OPEN
4H5 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-6 OPEN 4B2-4 7.7 9.8 4B6-1 0.9 0.9
4H7 CLOSED 4B3-4 0.6 0.6 4B5-1 7.1 7.1
4H43 OPEN 4B4-4 2.4 2.4 4B4-1 0.5 6.4
4H26 CLOSED 4B3-1 6.2 6.2
4S8 OPEN 4B2-1 0.9 0.9
4H34 CLOSED
Transformer
Total
10.7 12.8
Transformer
Total
15.6 21.5
4H40 OPEN
4H49 CLOSED
4B3-6 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H21 CLOSED 4B2-13 2.1 2.1 4B2-9 7.8 11.4
4B4-6 OPEN 4B3-13 3.9 4.5 4B3-9 8.2 11.2
4B4-13 4.4 4.4
Switching Description:
Transformer
Total
10.4 11.0
Transformer
Total
16.0 22.6
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-17 12.0 3.2 4B2-16 2.2 2.2
4B3-17 1.0 8.6 4B3-16 6.7 11.4
4B2-17 2.2 9.0 4B4-16 4.6 6.8
4B5-16 0.6 0.6
Transformer
Total
15.2 20.8
Transformer
Total
14.1 21.0
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-18 8.8 11.3
Transformer
Total
8.8 11.3
FIFTEENTH ST. BREAKERS
4B3-3 transferring to 4B3-13
4B2-4 taking load off of 4B4-3
4B3-18 taking load off of 4B4-3
4B4-3 powered through 4B5-3
4B5-3 transferring to 4B4-1
4B2-6 transferring to 4B3-17
4B3-9 taking load off of 4B4-17
4B4-16 taking load off of 4B4-17
4B2-9 taking load off of 4B4-17
4B3-6 transferring to 4B2-17
4B4-6 transferring to 4B3-16
HATCH BREAKERS HARRISON BREAKERS
SWITCHING PROCEDURE MILLIGAN BREAKERS SUGARMILL BREAKERS
4B3-34B5-3&4B4-3
TEMPLEVIEW BREAKERS RACK BREAKERS
WESTSIDE BREAKERS
4B2-64B3-64B4-6
CITY BREAKERS
N-2 Substation Switching Study
10
5.1.6 Milligan & Fifteenth St.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H46 CLOSED 4B5-3 0.6 0.0 4B2-9 7.8 0.0
4B3-3 OPEN 4B4-3 9.9 0.0 4B3-9 8.2 0.0
4D18 CLOSED 4B3-3 0.6 0.0
4D46 OPEN
4D24 CLOSED
4D40 OPEN
Transformer
Total
11.1 0.0
Transformer
Total
16.0 0.0
4H36 CLOSED
4B1-3 OPEN
4H20 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4D52 OPEN 4B2-4 7.7 9.8 4B6-1 0.9 0.9
4H12 CLOSED 4B3-4 0.6 0.6 4B5-1 7.1 7.1
4D12 OPEN 4B4-4 2.4 2.4 4B4-1 0.5 6.4
4D85 CLOSED 4B3-1 6.2 3.9
4D73 OPEN 4B2-1 0.9 0.9
4H13 CLOSED
Transformer
Total
10.7 12.8
Transformer
Total
15.6 19.2
4B2-9 OPEN
4H16 CLOSED
4H19 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H8 CLOSED 4B2-13 2.1 2.1 4B3-18 8.8 11.3
4B3-9 OPEN 4B3-13 3.9 10.1
4B4-13 4.4 7.0
Switching Description:
Transformer
Total
10.4 19.2
Transformer
Total
8.8 11.3
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-14 0.7 0.7 4B2-16 2.2 2.2
4B4-14 6.8 6.8 4B3-16 6.7 6.7
4B5-14 0.0 0.0 4B4-16 4.6 7.0
4B6-14 2.9 2.9 4B5-16 0.6 0.6
4B7-14 1.8 9.5
Transformer
Total
12.2 19.9
Transformer
Total
14.1 16.5
4B3-94B2-9
CITY BREAKERS WESTSIDE BREAKERS
YORK ROAD BREAKERS HARRISON BREAKERS
4B3-3 transferring to 4B3-13
4B2-4 taking load off of 4B4-3
4B3-18 taking load off of 4B4-3
4B4-3 powered through 4B5-3
4B5-3 transferring to 4B4-1
4B4-16 taking load off of 4B3-1
4B4-16 taking load off of 4B2-9
4B7-14 taking load off of 4B3-1
4B2-9 transferring to 4B7-14
4B4-13 taking load off of 4B3-9
4B3-9 transferring to 4B3-13
4B5-3&4B4-3
TEMPLEVIEW BREAKERS RACK BREAKERS
SWITCHING PROCEDURE MILLIGAN BREAKERS FIFTEENTH ST. BREAKERS
4B3-3
N-2 Substation Switching Study
11
5.1.7 Milligan & York Road
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4D18 CLOSED 4B5-3 0.6 0.0 4B3-14 0.7 0.0
4D46 OPEN 4B4-3 9.9 0.0 4B4-14 6.8 0.0
4D24 CLOSED 4B3-3 0.6 0.0 4B5-14 0.0 0.0
4D40 OPEN 4B6-14 2.9 0
4H46 CLOSED 4B7-14 1.8 0
4B1-3 OPEN
Transformer
Total
11.1 0.0
Transformer
Total
12.2 0.0
4H53 CLOSED
4B3-14 OPEN
4D51 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-14 OPEN 4B2-4 7.7 9.8 4B6-1 0.9 1.6
4B5-14
4B5-14 OPEN 4B3-4 0.6 0.6 4B5-1 7.1 7.1
4H20 CLOSED 4B4-4 2.4 2.4 4B4-1 0.5 0.5
4H27 OPEN 4B3-1 6.2 0.6
4H33 CLOSED 4B2-1 0.9 10.6
4B6-14 OPEN
Transformer
Total
10.7 12.8
Transformer
Total
15.6 20.4
4D85 CLOSED
4B7-14 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
Switching Description: 4B2-13 2.1 2.1 4B3-18 8.8 11.3
4B3-13 3.9 10.4
4B4-13 4.4 4.4
Transformer
Total
10.4 16.9
Transformer
Total
8.8 11.3
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-16 2.2 2.2
4B3-16 6.7 6.7
4B4-16 4.6 12.0
4B5-16 0.6 0.6
Transformer
Total
14.1 21.5
4B7-144B6-14
CITY BREAKERS WESTSIDE BREAKERS
4B2-4 taking load off of 4B4-3
4B3-18 taking load off of 4B4-3
4B5-3 powered through 4B3-3
4B4-3 powered through 4B3-3
4B3-3 transferring to 4B3-13
4B3-14 transferring to 4B6-1
4B4-14 transferring to 4B6-14
4B5-14 shut off
4B4-16 taking load off of 4B3-1
4B6-14 transferring to 4B2-1
4B7-14 transferring to 4B4-16
HARRISON BREAKERS
4B4-14
SWITCHING PROCEDURE MILLIGAN BREAKERS YORK ROAD BREAKERS
TEMPLEVIEW BREAKERS RACK BREAKERS
4B5-3,4B4-3,&4B3-34B3-14
N-2 Substation Switching Study
12
5.1.8 Milligan & Harrison
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4D18 CLOSED 4B5-3 0.6 0.0 4B2-16 2.2 0.0
4D46 OPEN 4B4-3 9.9 0.0 4B3-16 6.7 0.0
4D24 CLOSED 4B3-3 0.6 0.0 4B4-16 4.6 0.0
4D40 OPEN 4B5-16 0.6 0
4H46 CLOSED
Transformer
Total
11.1 0.0
Transformer
Total
14.1 0.0
4B1-3 OPEN
4D85 CLOSED
4D72 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H7 CLOSED 4B2-4 7.7 9.8 4B6-1 0.9 0.9
4H43 OPEN 4B3-4 0.6 0.6 4B5-1 7.1 7.1
4H49 CLOSED 4B4-4 2.4 2.4 4B4-1 0.5 0.5
4H42 OPEN 4B3-1 6.2 12.2
4D13 CLOSED 4B2-1 0.9 0.9
4B2-16 OPEN
Transformer
Total
10.7 12.8
Transformer
Total
15.6 21.6
4H21 CLOSED
4B3-16 OPEN
4H20 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-16 OPEN 4B2-13 2.1 2.1 4B2-6 7.6 7.6
4D54 CLOSED 4B3-13 3.9 10.4 4B3-6 6.8 0.2
4B5-16 OPEN 4B4-13 4.4 4.4 4B4-6 4.7 12.0
Transformer
Total
10.4 16.9
Transformer
Total
19.1 19.8
Switching Description:
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-14 0.7 0.7 4B2-9 7.8 7.8
4B4-14 6.8 6.8 4B3-9 8.2 11.2
4B5-14 0.0 0.0
4B6-14 2.9 2.9
4B7-14 1.8 2.6
Transformer
Total
12.2 13.0
Transformer
Total
16.0 19.0
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-18 8.8 11.3 4B4-17 12.0 9.0
4B3-17 1.0 1.0
4B2-17 2.2 8.8
Transformer
Total
8.8 11.3
Transformer
Total
15.2 18.8
4B3-164B4-164B5-164B2-16
CITY BREAKERS SUGARMILL BREAKERS
4B2-4 taking load off of 4B4-3
4B3-18 taking load off of 4B4-3
4B5-3 powered through 4B3-3
4B4-3 powered through 4B3-3
4B3-3 transferring to 4B3-13
4B7-14 taking load off of 4B3-1
4B3-9 taking load off of 4B4-17
4B2-17 taking load off of 4B3-6
4B2-16 transferring to 4B4-16
4B3-16 transferring to 4B4-6
4B4-16 transferring to 4B3-1
4B5-16 transferring to 4B4-6
YORK ROAD BREAKERS FIFTEENTH ST. BREAKERS
WESTSIDE BREAKERS HATCH BREAKERS
SWITCHING PROCEDURE MILLIGAN BREAKERS HARRISON BREAKERS
TEMPLEVIEW BREAKERS RACK BREAKERS
4B5-3,4B4-3,&4B3-3
N-2 Substation Switching Study
13
5.1.9 Milligan & Hatch
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4D18 CLOSED 4B5-3 0.6 0.0 4B4-17 12.0 0.0
4D46 OPEN 4B4-3 9.9 0.0 4B3-17 1.0 0.0
4D24 CLOSED 4B3-3 0.6 0.0 4B2-17 2.2 0.0
4D40 OPEN
4H46 CLOSED
4B1-3 OPEN
Transformer
Total
11.1 0.0
Transformer
Total
15.2 0.0
4H49 CLOSED
4B2-17 OPEN
4H5 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-17 OPEN 4B2-4 7.7 9.8 4B6-1 0.9 0.9
4H13 CLOSED 4B3-4 0.6 0.6 4B5-1 7.1 7.1
4H47 OPEN 4B4-4 2.4 2.4 4B4-1 0.5 0.5
4H16 CLOSED 4B3-1 6.2 9.9
4H3 OPEN 4B2-1 0.9 0.9
4H26 CLOSED
Transformer
Total
10.7 12.8
Transformer
Total
15.6 19.3
4S8 OPEN
4H34 CLOSED
4D69 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H7 CLOSED 4B2-13 2.1 2.1 4B2-6 7.6 8.6
4B4-17 OPEN 4B3-13 3.9 10.4 4B3-6 6.8 9.0
4B4-13 4.4 7.6 4B4-6 4.7 4.7
Switching Description:
Transformer
Total
10.4 20.1
Transformer
Total
19.1 22.3
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-16 2.2 2.2 4B2-9 7.8 9.3
4B3-16 6.7 6.7 4B3-9 8.2 9.6
4B4-16 4.6 6.8
4B5-16 0.6 0.6
Note:
Transformer
Total
14.1 16.3
Transformer
Total
16.0 18.9
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-18 8.8 11.3
Transformer
Total
8.8 11.3
FIFTEENTH ST. BREAKERS
WESTSIDE BREAKERS
Upgrading the 336 ACSR wire
between 4S8 and 4H20 would
simplify the switching procedure.
CITY BREAKERS SUGARMILL BREAKERS
4B2-4 taking load off of 4B4-3
4B3-18 taking load off of 4B4-3
4B5-3 powered through 4B3-3
4B4-3 powered through 4B3-3
4B3-3 transferring to 4B3-13
4B3-1 taking load off of 4B2-9
4B4-13 taking load off of 4B3-9
4B4-17 transferring to 4B2-9, 4B3-9,
& 4B4-16
4B2-17 transferring to 4B3-6
4B3-17 transferring to 4B2-6
HARRISON BREAKERS
SWITCHING PROCEDURE MILLIGAN BREAKERS HATCH BREAKERS
4B5-3,4B4-3,&4B3-3
TEMPLEVIEW BREAKERS RACK BREAKERS
4B2-174B3-174B4-17
N-2 Substation Switching Study
14
5.1.10 Milligan & Westside
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4D18 CLOSED 4B5-3 0.6 0.0 4B3-18 8.8 0.0
4D46 OPEN 4B4-3 9.9 0.0
4D24 CLOSED 4B3-3 0.6 0.0
4D40 OPEN
4H46 CLOSED
4B1-3 OPEN
Transformer
Total
11.1 0.0
Transformer
Total
8.8 0.0
4D85 CLOSED
4H27 OPEN
4H52 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-18 OPEN 4B2-4 7.7 9.8 4B6-1 0.9 0.9
4B3-4 0.6 0.6 4B5-1 7.1 7.1
Switching Description: 4B4-4 2.4 2.4 4B4-1 0.5 11.8
4B3-1 6.2 0.6
4B2-1 0.9 0.9
Transformer
Total
10.7 12.8
Transformer
Total
15.6 21.3
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-13 2.1 2.1 4B3-14 0.7 0.7
4B3-13 3.9 10.4 4B4-14 6.8 6.8
4B4-13 4.4 4.4 4B5-14 0.0 0.0
4B6-14 2.9 2.9
4B7-14 1.8 7.4
Transformer
Total
10.4 16.9
Transformer
Total
12.2 17.8
4B2-4 taking load off of 4B4-3
4B3-18 taking load off of 4B4-3
4B5-3 powered through 4B3-3
4B4-3 powered through 4B3-3
4B3-3 transferring to 4B3-13
4B7-14 taking load off of 4B3-1
4B3-18 transferring to 4B4-1
CITY BREAKERS YORK ROAD BREAKERS
4B3-18
TEMPLEVIEW BREAKERS RACK BREAKERS
SWITCHING PROCEDURE MILLIGAN BREAKERS WESTSIDE BREAKERS
4B5-3,4B4-3,&4B3-3
N-2 Substation Switching Study
15
5.1.11 Sugarmill & Fifteenth St.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H16 CLOSED 4B2-6 7.6 0.0 4B2-9 7.8 0.0
4H3 OPEN 4B3-6 6.8 0.0 4B3-9 8.2 0.0
4H58 CLOSED 4B4-6 4.7 0.0
4H55 OPEN
4H45 CLOSED
4H4 OPEN
Transformer
Total
19.1 0.0
Transformer
Total
16.0 0.0
4H5 CLOSED
4B2-6 OPEN
4H26 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4S8 OPEN 4B2-16 2.2 2.2 4B6-1 0.9 0.9
4H49 CLOSED 4B3-16 6.7 11.4 4B5-1 7.1 12.1
4B3-6 OPEN 4B4-16 4.6 6.8 4B4-1 0.5 0.5
4H21 CLOSED 4B5-16 0.6 0.6 4B3-1 6.2 3.9
4B4-6 OPEN 4B2-1 0.9 0.9
4D85 CLOSED
Transformer
Total
14.1 21.0
Transformer
Total
15.6 18.3
4D73 OPEN
4H13 CLOSED
4B2-9 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H10 CLOSED 4B4-12 0.0 0.0 4B3-14 0.7 0.7
4B3-9 OPEN 4B3-12 11.0 12.3 4B4-14 6.8 6.8
4B2-12 2.1 2.1 4B5-14 0.0 0.0
Switching Description: 4B6-14 2.9 2.9
4B7-14 1.8 11.9
Transformer
Total
13.1 14.4
Transformer
Total
12.2 22.3
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-17 12.0 9.8 4B2-13 2.1 2.1
4B3-17 1.0 4.5 4B3-13 3.9 3.9
4B2-17 2.2 9.0 4B4-13 4.4 10.4
Transformer
Total
15.2 23.3
Transformer
Total
10.4 16.4
N. BOULEVARD 5T1-12
BREAKERS YORK ROAD BREAKERS
CITY BREAKERS
4B2-64B3-64B4-64B2-94B3-9
HARRISON BREAKERS RACK BREAKERS
4B4-13 taking load off of 4B3-9
4B4-13 taking load off of 4B3-12
4B3-12 taking load off of 4B2-6
4B2-6 transferring to 4B3-17
4B4-16 taking load off of 4B4-17
4B3-6 transferring to 4B2-17
4B4-6 transferring to 4B3-16
4B7-14 taking load off of 4B3-1
4B2-9 transferring to 4B7-14
4B3-9 transferring to 4B5-1
SWITCHING PROCEDURE SUGARMILL BREAKERS FIFTEENTH ST. BREAKERS
HATCH BREAKERS
N-2 Substation Switching Study
16
5.1.12 Sugarmill & York Road
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H5 CLOSED 4B2-6 7.6 0.0 4B3-14 0.7 0.0
4B2-6 OPEN 4B3-6 6.8 0.0 4B4-14 6.8 0.0
4H7 CLOSED 4B4-6 4.7 0.0 4B5-14 0.0 0.0
4H43 OPEN 4B6-14 2.9 0.0
4H26 CLOSED 4B7-14 1.8 0.0
4S8 OPEN
Transformer
Total
19.1 0.0
Transformer
Total
12.2 0.0
4H34 CLOSED
4H40 OPEN
4H49 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-6 OPEN 4B6-1 0.9 1.6 4B2-16 2.2 2.2
4H21 CLOSED 4B5-1 7.1 7.1 4B3-16 6.7 11.4
4B4-6 OPEN 4B4-1 0.5 0.0 4B4-16 4.6 6.8
4H53 CLOSED 4B3-1 6.2 8.0 4B5-16 0.6 0.6
4B3-14 OPEN 4B2-1 0.9 0.0
4D51 CLOSED
Transformer
Total
15.6 16.7
Transformer
Total
14.1 21.0
4B4-14 OPEN
4B5-14
4B5-14 OPEN
4H36 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-1 OPEN 4B2-9 7.8 7.8 4B4-17 12.0 6.8
4H4-1 CLOSED 4B3-9 8.2 11.2 4B3-17 1.0 8.6
4H2-1 CLOSED 4B2-17 2.2 9.0
4B2-1 OPEN
4H33 CLOSED
4B6-14 OPEN
Transformer
Total
16.0 19.0
Transformer
Total
15.2 24.4
4D85 CLOSED
4B7-14 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
Switching Description: 4B5-3 0.6 11.7
4B4-3 9.9 9.9
4B3-3 0.6 0.6
Transformer
Total
11.1 22.2
HATCH BREAKERS
SWITCHING PROCEDURE SUGARMILL BREAKERS YORK ROAD BREAKERS
RACK BREAKERS HARRISON BREAKERS
4B3-64B4-64B2-6
FIFTEENTH ST. BREAKERS
MILLIGAN BREAKERS
4B2-6 transferring to 4B3-17
4B3-9 taking load off of 4B4-17
4B4-16 taking load off of 4B4-17
4B2-9 taking load off of 4B4-17
4B3-6 transferring to 4B2-17
4B4-6 transferring to 4B3-16
4B3-14 transferring to 4B6-1
4B4-14 transferring to 4B6-14
4B5-14 shut off
4B4-1 transferring to 4B5-3
4B2-1 transferring to 4B5-3
4B6-14 transferring to 4B5-3
4B7-14 transferring to 4B3-1
4B3-144B4-144B6-144B7-14
N-2 Substation Switching Study
17
5.1.13 Sugarmill & Westside
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H5 CLOSED 4B2-6 7.6 0.0 4B3-18 8.8 0.0
4B2-6 OPEN 4B3-6 6.8 0.0
4H26 CLOSED 4B4-6 4.7 0.0
4S8 OPEN
4H34 CLOSED
4H40 OPEN
Transformer
Total
19.1 0.0
Transformer
Total
8.8 0.0
4H7 CLOSED
4H43 OPEN
4H49 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-6 OPEN 4B6-1 0.9 0.9 4B2-9 7.8 11.4
4H21 CLOSED 4B5-1 7.1 7.1 4B3-9 8.2 11.2
4B4-6 OPEN 4B4-1 0.5 0.0
4H36 CLOSED 4B3-1 6.2 6.2
4D17 OPEN 4B2-1 0.9 0.9
4H52 CLOSED
Transformer
Total
15.6 15.1
Transformer
Total
16.0 22.6
4B3-18 OPEN
Switching Description: Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B5-3 0.6 9.9 4B2-16 2.2 2.2
4B4-3 9.9 9.9 4B3-16 6.7 11.4
4B3-3 0.6 0.6 4B4-16 4.6 6.8
4B5-16 0.6 0.6
Transformer
Total
11.1 20.4
Transformer
Total
14.1 21.0
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-17 12.0 3.2
4B3-17 1.0 8.6
4B2-17 2.2 9.0
Transformer
Total
15.2 20.8
HATCH BREAKERS
4B3-64B4-64B3-18
RACKBREAKERS FIFTEENTH ST. BREAKERS
4B2-6 transferring to 4B3-17
4B4-16 taking load off of 4B4-17
4B2-9 taking load off of 4B4-17
4B3-9 taking load off of 4B4-17
4B3-6 transferring to 4B2-17
4B4-6 transferring to 4B3-16
4B5-3 taking load off of 4B4-1
4B3-18 transferring to 4B5-3
MILLIGAN BREAKERS HARRISON BREAKERS
SWITCHING PROCEDURE SUGARMILL BREAKERS WESTSIDE BREAKERS
4B2-6
N-2 Substation Switching Study
18
5.1.14 Fifteenth St. & York Road
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4D85 CLOSED 4B2-9 7.8 0.0 4B3-14 0.7 0.0
4D72 OPEN 4B3-9 8.2 0.0 4B4-14 6.8 0.0
4H26 CLOSED 4B5-14 0.0 0.0
4S8 OPEN 4B6-14 2.9 0.0
4H20 CLOSED 4B7-14 1.8 0.0
4D73 OPEN
Transformer
Total
16.0 0.0
Transformer
Total
12.2 0.0
4H12 CLOSED
4H47 OPEN
4H9 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H44 OPEN 4B6-1 0.9 1.6 4B4-12 0.0 0.0
4H45 CLOSED 4B5-1 7.1 5.7 4B3-12 11.0 11.8
4H4 OPEN 4B4-1 0.5 0.5 4B2-12 2.1 2.1
4D16 CLOSED 4B3-1 6.2 6.5
4H40 OPEN 4B2-1 0.9 10.6
4H34 CLOSED
Transformer
Total
15.6 24.9
Transformer
Total
13.1 13.9
4B2-9 OPEN
4H49 CLOSED
4H42 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H28 CLOSED 4B2-6 7.6 3.5 4B4-17 12.0 11.0
4D69 OPEN 4B3-6 6.8 0.2 4B3-17 1.0 1.0
4H8 CLOSED 4B4-6 4.7 12.4 4B2-17 2.2 10.4
4H3 OPEN
4H7 CLOSED
4B3-9 OPEN
Transformer
Total
19.1 16.1
Transformer
Total
15.2 22.4
4H53 CLOSED
4B3-14 OPEN
4D51 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-14 OPEN 4B2-16 2.2 2.2 4B2-13 2.1 2.1
4B5-14
4B5-14 OPEN 4B3-16 6.7 6.7 4B3-13 3.9 7.1
4H33 CLOSED 4B4-16 4.6 12.0 4B4-13 4.4 7.7
4B6-14 OPEN 4B5-16 0.6 0.6
4H10 CLOSED
4H50 OPEN
Transformer
Total
14.1 21.5
Transformer
Total
10.4 16.9
4D59 CLOSED
4B7-14 OPEN
RACK BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
SWITCHING PROCEDURE FIFTEENTH ST. BREAKERS YORK ROAD BREAKERS
4B2-9
SUGARMILL BREAKERS HATCH BREAKERS
HARRISON BREAKERS CITY BREAKERS
4B4-144B6-144B7-144B3-94B3-14
N-2 Substation Switching Study
19
5.1.15 Fifteenth St. & Westside
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H20 CLOSED 4B2-9 7.8 0.0 4B3-18 8.8 0.0
4D52 OPEN 4B3-9 8.2 0.0
4H12 CLOSED
4D12 OPEN
4H13 CLOSED
4B2-9 OPEN
Transformer
Total
16.0 0.0
Transformer
Total
8.8 0.0
4H16 CLOSED
4H19 OPEN
4H8 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-9 OPEN 4B6-1 0.9 0.9 4B2-13 2.1 2.1
4H36 CLOSED 4B5-1 7.1 7.1 4B3-13 3.9 9.5
4D17 OPEN 4B4-1 0.5 0.0 4B4-13 4.4 7.0
4H52 CLOSED 4B3-1 6.2 11.6
4B3-18 OPEN 4B2-1 0.9 0.9
Transformer
Total
15.6 20.5
Transformer
Total
10.4 18.6
Switching Description:
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-16 2.2 2.2 4B5-3 0.6 9.9
4B3-16 6.7 6.7 4B4-3 9.9 9.9
4B4-16 4.6 7.0 4B3-3 0.6 0.6
4B5-16 0.6 0.6
Transformer
Total
14.1 16.5
Transformer
Total
11.1 20.4
MILLIGAN BREAKERS4B4-16 taking load off of 4B3-1
4B4-16 taking load off of 4B2-9
4B2-9 transferring to 4B3-1
4B4-13 taking load off of 4B3-9
4B3-9 transferring to 4B3-13
4B5-3 taking load off of 4B4-1
4B3-18 transferring to 4B5-3
SWITCHING PROCEDURE FIFTEENTH ST. BREAKERS WESTSIDE BREAKERS
RACK BREAKERS CITY BREAKERS
4B2-94B3-94B3-18
HARRISON BREAKERS
N-2 Substation Switching Study
20
5.1.16 York Road & Westside
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H53 CLOSED 4B3-14 0.7 0.0 4B3-18 8.8 0.0
4B3-14 OPEN 4B4-14 6.8 0.0
4D51 CLOSED 4B5-14 0.0 0.0
4B4-14 OPEN 4B6-14 2.9 0.0
4B5-14
4B5-14 OPEN 4B7-14 1.8 0.0
4H33 CLOSED
Transformer
Total
12.2 0.0
Transformer
Total
8.8 0.0
4B6-14 OPEN
4H20 CLOSED
4H27 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4D85 CLOSED 4B2-16 2.2 2.2 4B5-3 0.6 9.9
4B7-14 OPEN 4B3-16 6.7 6.7 4B4-3 9.9 9.9
4H36 CLOSED 4B4-16 4.6 12.0 4B3-3 0.6 0.6
4D17 OPEN 4B5-16 0.6 0.6
4H52 CLOSED
4B3-18 OPEN
Transformer
Total
14.1 21.5
Transformer
Total
11.1 20.4
Switching Description:
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B6-1 0.9 1.6
4B5-1 7.1 7.1
4B4-1 0.5 0.0
4B3-1 6.2 0.6
4B2-1 0.9 10.6
Transformer
Total
15.6 19.9
4B4-14
SWITCHING PROCEDURE YORK ROAD BREAKERS WESTSIDE BREAKERS
4B3-144B6-144B7-14
HARRISON BREAKERS MILLIGAN BREAKERS
RACK BREAKERS
4B3-18
4B3-14 transferring to 4B6-1
4B4-14 transferring to 4B6-14
4B5-14 shut off
4B6-14 transferring to 4B2-1
4B4-16 taking load off of 4B3-1
4B7-14 transferring to 4B4-16
4B5-3 taking load off of 4B4-1
4B3-18 transferring to 4B5-3
N-2 Substation Switching Study
21
5.1.17 Harrison & Westside
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4D85 CLOSED 4B2-16 2.2 0.0 4B3-18 8.8 0.0
4D72 OPEN 4B3-16 6.7 0.0
4H7 CLOSED 4B4-16 4.6 0.0
4H43 OPEN 4B5-16 0.6 0.0
4H49 CLOSED
4H42 OPEN
Transformer
Total
14.1 0.0
Transformer
Total
8.8 0.0
4D13 CLOSED
4B2-16 OPEN
4H21 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-16 OPEN 4B3-14 0.7 0.7 4B5-3 0.6 9.9
4H20 CLOSED 4B4-14 6.8 6.8 4B4-3 9.9 9.9
4B4-16 OPEN 4B5-14 0.0 0.0 4B3-3 0.6 0.6
4D54 CLOSED 4B6-14 2.9 2.9
4B5-16 OPEN 4B7-14 1.8 2.6
4H36 CLOSED
Transformer
Total
12.2 13.0
Transformer
Total
11.1 20.4
4D17 OPEN
4H52 CLOSED
4B3-18 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-9 7.8 7.8 4B2-6 7.6 7.6
Switching Description: 4B3-9 8.2 11.2 4B3-6 6.8 0.2
4B4-6 4.7 12.0
Transformer
Total
16.0 19.0
Transformer
Total
19.1 19.8
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-17 12.0 9.0 4B6-1 0.9 0.9
4B3-17 1.0 1.0 4B5-1 7.1 7.1
4B2-17 2.2 8.8 4B4-1 0.5 0.0
4B3-1 6.2 12.2
4B2-1 0.9 0.9
Transformer
Total
15.2 18.8
Transformer
Total
15.6 21.1
4B3-184B2-164B3-164B4-164B5-16
FIFTEENTH ST. BREAKERS SUGARMILL BREAKERS
HATCH BREAKERS RACK BREAKERS
4B7-14 taking load off of 4B3-1
4B3-9 taking load off of 4B4-17
4B2-17 taking load off of 4B3-6
4B2-16 transferring to 4B4-16
4B3-16 transferring to 4B4-6
4B4-16 transferring to 4B3-1
4B5-16 transferring to 4B4-6
4B5-3 taking load off of 4B4-1
4B3-18 transferring to 4B5-3
SWITCHING PROCEDURE HARRISON BREAKERS WESTSIDE BREAKERS
YORK ROAD BREAKERS MILLIGAN BREAKERS
N-2 Substation Switching Study
22
5.1.18 Hatch & Westside
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H49 CLOSED 4B4-17 12.0 0.0 4B3-18 8.8 0.0
4B2-17 OPEN 4B3-17 1.0 0.0
4H5 CLOSED 4B2-17 2.2 0.0
4B3-17 OPEN
4H13 CLOSED
4H47 OPEN
Transformer
Total
15.2 0.0
Transformer
Total
8.8 0.0
4H16 CLOSED
4H3 OPEN
4H26 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4S8 OPEN 4B2-13 2.1 2.1 4B5-3 0.6 9.9
4H34 CLOSED 4B3-13 3.9 3.9 4B4-3 9.9 9.9
4D69 OPEN 4B4-13 4.4 7.6 4B3-3 0.6 0.6
4H7 CLOSED
4B4-17 OPEN
4H36 CLOSED
Transformer
Total
10.4 13.6
Transformer
Total
11.1 20.4
4D17 OPEN
4H52 CLOSED
4B3-18 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-9 7.8 9.3 4B2-6 7.6 8.6
Switching Description: 4B3-9 8.2 9.6 4B3-6 6.8 9.0
4B4-6 4.7 4.7
Transformer
Total
16.0 18.9
Transformer
Total
19.1 22.3
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
Note: 4B2-16 2.2 2.2 4B6-1 0.9 0.9
4B3-16 6.7 6.7 4B5-1 7.1 7.1
4B4-16 4.6 6.8 4B4-1 0.5 0.0
4B5-16 0.6 0.6 4B3-1 6.2 9.9
4B2-1 0.9 0.9
Transformer
Total
14.1 16.3
Transformer
Total
15.6 18.8
4B2-17 transferring to 4B3-6
4B3-17 transferring to 4B2-6
4B3-1 taking load off of 4B2-9
4B4-13 taking load off of 4B3-9
4B4-16 taking load off of 4B4-17
4B2-9 taking load off of 4B4-17
4B4-17 transferring to 4B3-9
4B5-3 taking load off of 4B4-1
4B3-18 transferring to 4B5-3
Upgrading the 336 ACSR wire
between 4S8 and 4H20 would
simplify the switching procedure.
HARRISON BREAKERS RACK BREAKERS
4B3-18
FIFTEENTH ST. BREAKERS SUGARMILL BREAKERS
4B2-174B3-174B4-17
SWITCHING PROCEDURE HATCH BREAKERS WESTSIDE BREAKERS
CITY BREAKERS MILLIGAN BREAKERS
N-2 Substation Switching Study
23
5.2 Scenarios that work with assumptions
5.2.1 Rack & Templeview
Templeview’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H33 CLOSED 4B6-1 0.9 0.0 4B2-4 7.7 0.0
4B2-1 OPEN 4B5-1 7.1 0.0 4B3-4 0.6 0.0
4D85 CLOSED 4B4-1 0.5 0.0 4B4-4 2.4 0.0
4B3-1 OPEN 4B3-1 6.2 0.0
4H52 CLOSED 4B2-1 0.9 0.0
4B4-1 OPEN
Transformer
Total
15.6 0.0
Transformer
Total
10.7 0.0
4H8 CLOSED
4H3 OPEN
4H10 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B5-1 OPEN 4B2-9 7.8 7.8 4B3-18 8.8 9.3
4H53 CLOSED 4B3-9 8.2 12.1
4B6-1 OPEN
4H58 CLOSED
4H55 OPEN
4H9 CLOSED
Transformer
Total
16.0 19.9
Transformer
Total
8.8 9.3
4H44 OPEN
4H1 CLOSED
4B2-4 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-4
4B3-4 CLOSED 4B2-13 2.1 2.1 4B3-14 0.7 1.6
4B4-4 CLOSED 4B3-13 3.9 9.9 4B4-14 6.8 6.8
4H31 CLOSED 4B4-13 4.4 7.7 4B5-14 0.0 0.0
4B1-4 OPEN 4B6-14 2.9 3.8
4B7-14 1.8 8.0
Switching Description:
Transformer
Total
10.4 19.7
Transformer
Total
12.2 20.2
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-12 0.0 0.0 4B7-12 0.8 0.8
4B3-12 11.0 12.6 4B6-12 8.3 11.3
4B2-12 2.1 2.1
Note:
Transformer
Total
13.1 14.7
Transformer
Total
9.1 12.1
4B4-4
4B2-1 transferring to 4B6-14
4B3-1 transferring to 4B7-14
4B4-1 transferring to 4B3-18
4B3-13 taking load off of 4B3-9
4B5-1 transferring to 4B3-9
4B6-1 transferring to 4B3-14
4B3-13 taking load off of 4B3-12
4B4-13 taking load off of 4B3-12
4B2-4 transferring to 4B3-12
4B3-4 powered through 4B4-4
4B4-4 transferring to 4B6-12
N. BOULEVARD 5T1-12
BREAKERS
N. BOULEVARD 5T2-12
BREAKERS
Switching procedure requires the use
of Templeview's auxiliary bus.
4B3-4 needs to be connected to
another circuit.
4B2-4
CITY BREAKERS YORK ROAD BREAKERS
SWITCHING PROCEDURE RACK BREAKERS TEMPLEVIEW BREAKERS
4B2-14B3-14B4-14B5-1
FIFTEENTH ST. BREAKERS WESTSIDE BREAKERS
4B6-1
N-2 Substation Switching Study
24
5.2.2 Rack & N. Boulevard
N. Boulevard’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H33 CLOSED 4B7-12 0.8 0.0 4B4-12 0.0 0.0
4B2-1 OPEN 4B6-12 8.3 0.0 4B3-12 11.0 0.0
4D85 CLOSED 4B2-12 2.1 0.0
4B3-1 OPEN
4H52 CLOSED
4B4-1 OPEN
Transformer
Total
9.1 0.0
Transformer
Total
13.1 0.0
4H8 CLOSED
4H3 OPEN
4H10 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B5-1 OPEN 4B6-1 0.9 0.0 4B2-13 2.1 2.1
4H53 CLOSED 4B5-1 7.1 0.0 4B3-13 3.9 9.9
4B6-1 OPEN 4B4-1 0.5 0.0 4B4-13 4.4 7.7
4H9 CLOSED 4B3-1 6.2 0.0
4H44 OPEN 4B2-1 0.9 0
OLD CUTOUT CLOSED
Transformer
Total
15.6 0.0
Transformer
Total
10.4 19.7
4B2-12 OPEN
4H58 CLOSED
4H55 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H45 CLOSED 4B2-9 7.8 7.8 4B5-3 0.6 0.6
4H2 OPEN 4B3-9 8.2 12.1 4B4-3 9.9 12.7
4H41 CLOSED 4B3-3 0.6 0.6
4D1 OPEN
4H1 CLOSED
4B3-12 OPEN
Transformer
Total
16.0 19.9
Transformer
Total
11.1 13.9
4H31 CLOSED
4B6-12 OPEN
4H12-12 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H13-12 CLOSED 4B3-14 0.7 1.6 4B2-6 7.6 9.5
4B7-12 OPEN 4B4-14 6.8 6.8 4B3-6 6.8 6.8
4B5-14 0.0 0.0 4B4-6 4.7 4.7
Switching Description: 4B6-14 2.9 3.8
4B7-14 1.8 8.0
Transformer
Total
12.2 20.2
Transformer
Total
19.1 21.0
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-4 7.7 10.0 4B3-18 8.8 9.3
4B3-4 0.6 0.6
4B4-4 2.4 11.5
Transformer
Total
10.7 22.1
Transformer
Total
8.8 9.3
Note:
Old Cutout needs to be a switch.
Switching procedure requires the use of
N. Boulevard's auxiliary bus.
4B6-12
SUGARMILL BREAKERSYORK ROAD BREAKERS
4B6-1
FIFTEENTH ST. BREAKERS MILLIGAN BREAKERS
TEMPLEVIEW BREAKERS WESTSIDE BREAKERS
4B2-1 transferring to 4B6-14
4B3-1 transferring to 4B7-14
4B4-1 transferring to 4B3-18
4B3-13 taking load off of 4B3-9
4B5-1 transferring to 4B3-9
4B6-1 transferring to 4B3-14
4B4-13 taking load off of 4B3-12
4B2-12 transferring to 4B3-12
4B3-13 taking load off of 4B3-12
4B2-6 taking load off of 4B3-12
4B4-3 taking load off of 4B2-4
4B3-12 transferring to 4B2-4
4B6-12 transferring to 4B4-4
4B7-12 transferring to 4B4-4
RACK BREAKERS CITY BREAKERS
4B2-1
SWITCHING PROCEDURE
N. BOULEVARD 5T2-12
BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
4B3-14B4-14B5-14B7-124B2-124B3-12
N-2 Substation Switching Study
25
5.2.3 Rack & City
City’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H33 CLOSED 4B6-1 0.9 0.0 4B2-13 2.1 0.0
4B2-1 OPEN 4B5-1 7.1 0.0 4B3-13 3.9 0.0
4H20 CLOSED 4B4-1 0.5 0.0 4B4-13 4.4 0.0
4D73 OPEN 4B3-1 6.2 0.0
4D85 CLOSED 4B2-1 0.9 0.0
4D72 OPEN
Transformer
Total
15.6 0.0
Transformer
Total
10.4 0.0
4D59 CLOSED
4B3-1 OPEN
4H52 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-1 OPEN 4B2-16 2.2 2.2 4B3-18 8.8 9.3
4H30 CLOSED 4B3-16 6.7 6.7
4H50 OPEN 4B4-16 4.6 6.1
4H51 CLOSED 4B5-16 0.6 0.6
4B5-1 OPEN
4H53 CLOSED
Transformer
Total
14.1 15.6
Transformer
Total
8.8 9.3
4B6-1 OPEN
4B2-13
4B2-13 CLOSED
4H46 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-13 CLOSED 4B2-9 7.8 9.2 4B3-14 0.7 1.6
4H16 CLOSED 4B3-9 8.2 12.6 4B4-14 6.8 6.8
4B4-13 OPEN 4B5-14 0.0 0.0
4B1-13 OPEN 4B6-14 2.9 3.8
4B7-14 1.8 12.2
Switching Description:
Transformer
Total
16.0 21.8
Transformer
Total
12.2 24.4
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B5-3 0.6 0.6
4B4-3 9.9 9.9
4B3-3 0.6 6.6
Transformer
Total
11.1 17.1
4B4-134B5-14B6-14B3-14B4-14B3-13
4B2-1 transferring to 4B6-14
4B4-16 taking load off of 4B3-1
4B7-14 taking load off of 4B4-16
4B3-1 transferring to 4B7-14
4B4-1 transferring to 4B3-18
4B2-9 taking load off of 4B5-1
4B5-1 transferring to 4B7-14
4B6-1 transferring to 4B3-14
4B2-13 powered through 4B3-13
4B3-13 transferring to 4B3-3
4B4-13 transferring to 4B3-9
HARRISON BREAKERS WESTSIDE BREAKERS
FIFTEENTH ST. BREAKERS YORK ROAD BREAKERS
MILLIGAN BREAKERS
SWITCHING PROCEDURE RACK BREAKERS CITY BREAKERS
4B2-1
N-2 Substation Switching Study
26
5.2.4 Rack & York
Both Rack and York Road’s aux buses must be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H2-1 CLOSED 4B6-1 0.9 0.0 4B3-14 0.7 0.0
4H4-1 CLOSED 4B5-1 7.1 0.0 4B4-14 6.8 0.0
4B2-1 OPEN 4B4-1 0.5 0.0 4B5-14 0.0 0.0
4H11 CLOSED 4B3-1 6.2 0.0 4B6-14 2.9 0.0
4H22 OPEN 4B2-1 0.9 0.0 4B7-14 1.8 0.0
4H20 CLOSED
Transformer
Total
15.6 0.0
Transformer
Total
12.2 0.0
4B3-1 OPEN
4H36 CLOSED
4B4-1 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H8 CLOSED 4B2-16 2.2 2.2 4B5-3 0.6 11.7
4H3 OPEN 4B3-16 6.7 8.2 4B4-3 9.9 9.9
4H10 CLOSED 4B4-16 4.6 12.7 4B3-3 0.6 0.6
4B5-1 OPEN 4B5-16 0.6 0.6
4H53 CLOSED
4B6-1 OPEN
Transformer
Total
14.1 23.7
Transformer
Total
11.1 22.2
4D85 CLOSED
4B7-14 OPEN
4H33 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B6-14 OPEN 4B2-13 2.1 2.1 4B2-9 7.8 7.8
4B5-14
4B5-14 OPEN 4B3-13 3.9 7.1 4B3-9 8.2 12.1
4D51 CLOSED 4B4-13 4.4 4.4
4B4-14 OPEN
4H3-14 CLOSED
4B3-14 OPEN
Transformer
Total
10.4 13.6
Transformer
Total
16.0 19.9
4H7-14 CLOSED
4B1-14 OPEN
Switching Description:
HARRISON BREAKERS MILLIGAN BREAKERS
CITY BREAKERS FIFTEENTH ST. BREAKERS
4B2-1 transferring to 4B4-1
4B3-16 taking load off of 4B4-16
4B3-1 transferring to 4B4-16
4B4-1 transferring to 4B5-3
4B3-13 taking load off of 4B3-9
4B5-1 transferring to 4B3-9
4B6-1 transferring to 4B3-14
4B7-14 transferring to 4B4-16
4B6-14 transferring to 4B5-3
4B5-14 shut off
4B4-14 transferring to 4B5-3
4B3-14 transferring to 4B4-16
SWITCHING PROCEDURE RACK BREAKERS YORK ROAD BREAKERS
4B2-14B3-14B4-14B5-14B6-14B7-144B6-144B4-144B3-14
N-2 Substation Switching Study
27
5.2.5 Rack & Harrison
Rack’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H33 CLOSED 4B6-1 0.9 0.0 4B2-16 2.2 0.0
4B2-1 OPEN 4B5-1 7.1 0.0 4B3-16 6.7 0.0
4D85 CLOSED 4B4-1 0.5 0.0 4B4-16 4.6 0.0
4D73 OPEN 4B3-1 6.2 0.0 4B5-16 0.6 0
4H3-1 CLOSED 4B2-1 0.9 0.0
4H4-1 CLOSED
Transformer
Total
15.6 0.0
Transformer
Total
14.1 0.0
4B3-1 OPEN
4H36 CLOSED
4B4-1 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H5-1 CLOSED 4B3-14 0.7 1.6 4B5-3 0.6 12.1
4B5-1 OPEN 4B4-14 6.8 6.8 4B4-3 9.9 9.9
4H53 CLOSED 4B5-14 0.0 0.0 4B3-3 0.6 0.6
4B6-1 OPEN 4B6-14 2.9 3.8
4D13 CLOSED 4B7-14 1.8 10.9
4B2-16 OPEN
Transformer
Total
12.2 23.1
Transformer
Total
11.1 22.6
4H49 CLOSED
4H42 OPEN
4H21 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-16 OPEN 4B4-17 12.0 12.0 4B2-6 7.6 7.6
4H20 CLOSED 4B3-17 1.0 1.0 4B3-6 6.8 0.2
4B4-16 OPEN 4B2-17 2.2 8.8 4B4-6 4.7 12.0
4D54 CLOSED
4B5-16 OPEN
Transformer
Total
15.2 21.8
Transformer
Total
19.1 19.8
Switching Description:
4B3-1
4B2-1 transferring to 4B6-14
4B7-14 taking load off of 4B3-1
4B3-1 transferring to 4B4-1
4B4-1 transferring to 4B5-3
4B5-1 transferring to 4B5-3
4B6-1 transferringto 4B3-14
4B2-16 transferring to 4B4-16
4B2-17 taking load off of 4B3-6
4B3-16 transferring to 4B4-6
4B4-16 transferring to 4B7-14
4B5-16 transferring to 4B4-6
SWITCHING PROCEDURE RACK BREAKERS HARRISON BREAKERS
4B2-14B4-1
YORK ROAD BREAKERS MILLIGAN BREAKERS
4B5-14B6-14B2-164B4-164B5-164B3-16
HATCH BREAKERS SUGARMILL BREAKERS
N-2 Substation Switching Study
28
5.2.6 Rack & Hatch
Rack’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H33 CLOSED 4B6-1 0.9 0.0 4B4-17 12.0 0.0
4B2-1 OPEN 4B5-1 7.1 0.0 4B3-17 1.0 0.0
4D85 CLOSED 4B4-1 0.5 0.0 4B2-17 2.2 0.0
4D73 OPEN 4B3-1 6.2 0.0
4H3-1 CLOSED 4B2-1 0.9 0.0
4H4-1 CLOSED
Transformer
Total
15.6 0.0
Transformer
Total
15.2 0.0
4B3-1 OPEN
4H36 CLOSED
4B4-1 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H5-1 CLOSED 4B3-14 0.7 1.6 4B5-3 0.6 12.1
4B5-1 OPEN 4B4-14 6.8 6.8 4B4-3 9.9 9.9
4H53 CLOSED 4B5-14 0.0 0.0 4B3-3 0.6 0.6
4B6-1 OPEN 4B6-14 2.9 3.8
4H49 CLOSED 4B7-14 1.8 4.1
4B2-17 OPEN
Transformer
Total
12.2 16.3
Transformer
Total
11.1 22.6
4H5 CLOSED
4B3-17 OPEN
4H26 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H40 OPEN 4B2-13 2.1 2.1 4B2-9 7.8 7.8
4H8 CLOSED 4B3-13 3.9 7.1 4B3-9 8.2 11.2
4H3 OPEN 4B4-13 4.4 4.4
4H7 CLOSED
4B4-17 OPEN
Transformer
Total
10.4 13.6
Transformer
Total
16.0 19.0
Switching Description:
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-16 2.2 2.2 4B2-6 7.6 8.6
4B3-16 6.7 6.7 4B3-6 6.8 9.0
4B4-16 4.6 10.4 4B4-6 4.7 4.7
4B5-16 0.6 0.6
Transformer
Total
14.1 19.9
Transformer
Total
19.1 22.3
HARRISON BREAKERS SUGARMILL BREAKERS4B2-1 transferring to 4B6-14
4B7-14 taking load off of 4B3-1
4B3-1 transferring to 4B4-1
4B4-1 transferring to 4B5-3
4B5-1 transferring to 4B5-3
4B6-1 transferringto 4B3-14
4B2-17 transferring to 4B3-6
4B3-17 transferring to 4B2-6
4B4-16 taking load off of 4B4-17
4B3-13 taking load off of 4B3-9
4B4-17 transferring to 4B3-9
MILLIGAN BREAKERS
CITY BREAKERS FIFTEENTH ST. BREAKERS
SWITCHING PROCEDURE RACK BREAKERS HATCH BREAKERS
4B2-1
YORK ROAD BREAKERS
4B3-14B4-174B4-14B5-14B6-14B2-174B3-17
N-2 Substation Switching Study
29
5.2.7 Milligan & Templeview
Templeview’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H46 CLOSED 4B5-3 0.6 0.0 4B2-4 7.7 0.0
4B3-3 OPEN 4B4-3 9.9 0.0 4B3-4 0.6 0.0
4D18 CLOSED 4B3-3 0.6 0.0 4B4-4 2.4 0.0
4D46 OPEN
4D24 CLOSED
4D40 OPEN
Transformer
Total
11.1 0.0
Transformer
Total
10.7 0.0
4H36 CLOSED
4B1-3 OPEN
4H58 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H55 OPEN 4B2-6 7.6 9.5 4B6-1 0.9 0.9
4H45 CLOSED 4B3-6 6.8 6.8 4B5-1 7.1 7.1
4H2 OPEN 4B4-6 4.7 4.7 4B4-1 0.5 6.4
4H9 CLOSED 4B3-1 6.2 6.2
4H44 OPEN 4B2-1 0.9 0.9
4H1 CLOSED
Transformer
Total
19.1 21.0
Transformer
Total
15.6 21.5
4B2-4 OPEN
4H3-4 CLOSED
4H4-4 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-4 OPEN 4B2-13 2.1 2.1 4B2-9 7.8 7.8
4H31 CLOSED 4B3-13 3.9 4.5 4B3-9 8.2 11.0
4B4-4 OPEN 4B4-13 4.4 7.7
Switching Description:
Transformer
Total
10.4 14.3
Transformer
Total
16.0 18.8
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-12 0.0 0.0 4B7-12 0.8 0.8
4B3-12 11.0 12.8 4B6-12 8.3 11.3
4B2-12 2.1 2.1
Transformer
Total
13.1 14.9
Transformer
Total
9.1 12.1
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-18 8.8 11.3
Transformer
Total
8.8 11.3
SUGARMILL BREAKERS RACK BREAKERS
CITY BREAKERS FIFTEENTH ST. BREAKERS
4B5-3&4B4-34B2-44B3-4
SWITCHING PROCEDURE MILLIGAN BREAKERS TEMPLEVIEW BREAKERS
4B3-3
N. BOULEVARD 5T1-12
BREAKERS
N. BOULEVARD 5T2-12
BREAKERS
4B3-3 transferring to 4B3-13
4B2-4 taking load off of 4B4-3
4B3-18 taking load off of 4B4-3
4B4-3 powered through 4B5-3
4B5-3 transferring to 4B4-1
4B3-9 taking load off of 4B3-12
4B2-6 taking load off of 4B3-12
4B4-13 taking load off of 4B3-12
4B2-4 transferring to 4B3-12
4B3-4 powered through 4B4-4
4B4-4 transferring to 4B6-12
WESTSIDE BREAKERS
4B4-4
N-2 Substation Switching Study
30
5.2.8 Milligan & N. Boulevard
N. Boulevard’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H46 CLOSED 4B7-12 0.8 0.0 4B4-12 0.0 0.0
4B3-3 OPEN 4B6-12 8.3 0.0 4B3-12 11.0 0.0
4D18 CLOSED 4B2-12 2.1 0.0
4R5 OPEN
4D24 CLOSED
4D29 OPEN
Transformer
Total
9.1 0.0
Transformer
Total
13.1 0.0
4H41 CLOSED
4H29 OPEN
4H36 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B1-3 OPEN 4B5-3 0.6 0.0 4B2-13 2.1 2.1
4H58 CLOSED 4B4-3 9.9 0.0 4B3-13 3.9 10.5
4H55 OPEN 4B3-3 0.6 0.0 4B4-13 4.4 7.7
OLD CUTOUT CLOSED
4B2-12 OPEN
4H8 CLOSED
Transformer
Total
11.1 0.0
Transformer
Total
10.4 20.3
4H3 OPEN
4H9 CLOSED
4H44 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H7 CLOSED 4B2-9 7.8 7.8 4B2-6 7.6 3.5
4H43 OPEN 4B3-9 8.2 8.0 4B3-6 6.8 6.8
4H5 CLOSED 4B4-6 4.7 4.7
4H6 OPEN
4H26 CLOSED
4H40 OPEN
Transformer
Total
16.0 15.8
Transformer
Total
19.1 15.0
4H45 CLOSED
4B3-12 OPEN
4H31 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B6-12 OPEN 4B3-18 8.8 11.2 4B2-4 7.7 9.0
4H12-12 CLOSED 4B3-4 0.6 0.6
4H13-12 CLOSED 4B4-4 2.4 11.5
4B7-12 OPEN
Switching Description:
Transformer
Total
8.8 11.2
Transformer
Total
10.7 21.1
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-16 2.2 2.2 4B6-1 0.9 0.9
4B3-16 6.7 6.7 4B5-1 7.1 7.1
4B4-16 4.6 10.4 4B4-1 0.5 7.3
4B5-16 0.6 0.6 4B3-1 6.2 6.2
4B2-1 0.9 0.9
Transformer
Total
14.1 19.9
Transformer
Total
15.6 22.4
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-17 12.0 3.2
Note:
4B3-17 1.0 12.1
4B2-17 2.2 2.2
Transformer
Total
15.2 17.5
4B2-124B3-12
WESTSIDE BREAKERS
FIFTEENTH ST. BREAKERS
4B7-12 needs to be connected to
another circuit.
Old Cutout needs to be a switch.
TEMPLEVIEW BREAKERS
4B3-3 transferring to 4B3-13
4B2-4 taking load off of 4B4-3
4B3-18 taking load off of 4B4-3
4B4-3 taking load off of 4B2-4
4B4-3 powered through 4B5-3
4B5-3 transferring to 4B4-1
4B3-9 taking load off of 4B3-12
4B2-12 transferring to 4B3-12
4B3-13 taking load off of 4B3-9
4B4-13 taking load off of 4B3-12
4B3-9 taking load off of 4B4-17
4B3-17 taking load off of 4B2-6
4B4-16 taking load off of 4B4-17
4B3-12 transferring to 4B3-17
4B6-12 transferring to 4B4-4
4B7-12 transferring to 4B4-4
HARRISON BREAKERS RACK BREAKERS
4B6-124B7-12
HATCH BREAKERS
SUGARMILL BREAKERS
SWITCHING PROCEDURE
N. BOULEVARD 5T2-12
BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
MILLIGAN BREAKERS CITY BREAKERS
4B3-34B5-3&4B4-3
N-2 Substation Switching Study
31
5.2.9 Milligan & City
City’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H46 CLOSED 4B5-3 0.6 0.0 4B2-13 2.1 0.0
4B3-3 OPEN 4B4-3 9.9 0.0 4B3-13 3.9 0.0
4D18 CLOSED 4B3-3 0.6 0.0 4B4-13 4.4 0.0
4D46 OPEN
4D24 CLOSED
4D40 OPEN
Transformer
Total
11.1 0.0
Transformer
Total
10.4 0.0
4H36 CLOSED
4B1-3 OPEN
4H8 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-13 OPEN 4B2-4 7.7 9.8 4B6-1 0.9 0.9
4H45 CLOSED 4B3-4 0.6 0.6 4B5-1 7.1 7.1
4H2 OPEN 4B4-4 2.4 2.4 4B4-1 0.5 6.4
4H9 CLOSED 4B3-1 6.2 6.2
4B4-13 OPEN 4B2-1 0.9 0.9
Transformer
Total
10.7 12.8
Transformer
Total
15.6 21.5
Switching Description:
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-9 7.8 7.8 4B2-6 7.6 12.3
4B3-9 8.2 12.7 4B3-6 6.8 6.8
4B4-6 4.7 4.7
Transformer
Total
16.0 20.5
Transformer
Total
19.1 23.8
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-12 0.0 0.0 4B3-18 8.8 11.3
4B3-12 11.0 12.8
4B2-12 2.1 2.1
Transformer
Total
13.1 14.9
Transformer
Total
8.8 11.3
4B4-13&4B2-13
FIFTEENTH ST. BREAKERS SUGARMILL BREAKERS4B3-3 transferring to 4B3-13
4B2-4 taking load off of 4B4-3
4B3-18 taking load off of 4B4-3
4B4-3 powered through 4B5-3
4B5-3 transferring to 4B4-1
4B3-13 transferring to 4B3-9
4B2-6 taking load off of 4B3-12
4B2-13 powered through 4B4-13
4B4-13 transferring to 4B3-12
N. BOULEVARD 5T1-12
BREAKERS
WESTSIDE BREAKERS
4B3-13
SWITCHING PROCEDURE MILLIGAN BREAKERS CITY BREAKERS
4B3-34B5-3&4B4-3
TEMPLEVIEW BREAKERS RACK BREAKERS
N-2 Substation Switching Study
32
5.2.10 Templeview & Sugarmill
Templeview’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H58 CLOSED 4B2-4 7.7 0.0 4B2-6 7.6 0.0
4H55 OPEN 4B3-4 0.6 0.0 4B3-6 6.8 0.0
4H9 CLOSED 4B4-4 2.4 0.0 4B4-6 4.7 0.0
4H44 OPEN
4H1 CLOSED
4B2-4 OPEN
Transformer
Total
10.7 0.0
Transformer
Total
19.1 0.0
4B3-4
4B3-4 CLOSED
4B4-4 OPEN
4H31 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B1-4 OPEN 4B4-12 0.0 0.0 4B7-12 0.8 0.8
4H5 CLOSED 4B3-12 11.0 12.6 4B6-12 8.3 11.3
4B2-6 OPEN 4B2-12 2.1 2.1
4H26 CLOSED
4S8 OPEN
4H34 CLOSED
Transformer
Total
13.1 14.7
Transformer
Total
9.1 12.1
4H40 OPEN
4H49 CLOSED
4B3-6 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H21 CLOSED 4B2-13 2.1 2.1 4B2-16 2.2 2.2
4B4-6 OPEN 4B3-13 3.9 3.9 4B3-16 6.7 11.4
4B4-13 4.4 7.7 4B4-16 4.6 6.8
Switching Description: 4B5-16 0.6 0.6
Transformer
Total
10.4 13.7
Transformer
Total
14.1 21.0
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-17 12.0 6.2 4B2-9 7.8 11.4
4B3-17 1.0 8.6 4B3-9 8.2 11.0
4B2-17 2.2 9.0
Note:
Transformer
Total
15.2 23.8
Transformer
Total
16.0 22.4
4B2-64B4-64B3-6
4B3-9 taking load off of 4B3-12
4B4-13 taking load off of 4B3-12
4B2-4 transferring to 4B3-12
4B3-4 powered through 4B4-4
4B4-4 transferring to 4B6-12
4B2-6 transferring to 4B3-17
4B4-16 taking load off of 4B4-17
4B2-9 taking load off of 4B4-17
4B3-6 transferring to 4B2-17
4B4-6 transferring to 4B3-16
4B3-4 needs to be connected to
another circuit.
HATCH BREAKERS FIFTEENTH ST. BREAKERS
CITY BREAKERS HARRISON BREAKERS
SWITCHING PROCEDURE TEMPLEVIEW BREAKERS SUGARMILL BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
4B4-44B2-4
N-2 Substation Switching Study
33
5.2.11 Templeview & Fifteenth St.
Templeview’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H41 CLOSED 4B2-4 7.7 0.0 4B2-9 7.8 0.0
4D1 OPEN 4B3-4 0.6 0.0 4B3-9 8.2 0.0
4H49 CLOSED 4B4-4 2.4 0.0
4H42 OPEN
4H45 CLOSED
Transformer
Total
10.7 0.0
Transformer
Total
16.0 0.0
4H2 OPEN
4H1 CLOSED
4B2-4 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H3-4 CLOSED 4B4-12 0.0 0.0 4B7-12 0.8 0.8
4H4-4 CLOSED 4B3-12 11.0 11.2 4B6-12 8.3 11.3
4B3-4 OPEN 4B2-12 2.1 2.1
4H31 CLOSED
4B4-4 OPEN
Transformer
Total
13.1 13.3
Transformer
Total
9.1 12.1
4H12 CLOSED
4B2-9 OPEN
4H16 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H19 OPEN 4B2-13 2.1 2.1 4B2-16 2.2 2.2
4H8 CLOSED 4B3-13 3.9 9.5 4B3-16 6.7 6.7
4B3-9 OPEN 4B4-13 4.4 7.0 4B4-16 4.6 12.4
4B5-16 0.6 0.6
Switching Description:
Transformer
Total
10.4 18.6
Transformer
Total
14.1 21.9
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-6 7.6 12.3 4B5-3 0.6 0.6
4B3-6 6.8 0.2 4B4-3 9.9 12.7
4B4-6 4.7 4.7 4B3-3 0.6 0.6
Transformer
Total
19.1 17.2
Transformer
Total
11.1 13.9
Note:
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-17 12.0 12.0
4B3-17 1.0 1.0
4B2-17 2.2 8.8
Transformer
Total
15.2 21.8
4B3-4 needs to be connected to
another circuit.
HATCH BREAKERS
CITY BREAKERS HARRISON BREAKERS
4B4-3 taking load off of 4B2-4
4B2-17 taking load off of 4B3-6
4B2-6 taking load off of 4B3-12
4B2-4 transferring to 4B3-12
4B3-4 powered through 4B4-4
4B4-4 transferring to 4B6-12
4B2-9 transferring to 4B4-16
4B4-13 taking load off of 4B3-9
4B3-9 transferring to 4B3-13
SUGARMILL BREAKERS MILLIGAN BREAKERS
SWITCHING PROCEDURE TEMPLEVIEW BREAKERS FIFTEENTH ST. BREAKERS
N. BOULEVARD 5T1-12 N. BOULEVARD 5T1-12
4B2-94B3-94B2-44B3-44B4-4
N-2 Substation Switching Study
34
5.2.12 Templeview & City
Both Templeview and City’s aux buses must be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H41 CLOSED 4B2-4 7.7 0.0 4B2-13 2.1 0.0
4D1 OPEN 4B3-4 0.6 0.0 4B3-13 3.9 0.0
4H49 CLOSED 4B4-4 2.4 0.0 4B4-13 4.4 0.0
4H42 OPEN
4H45 CLOSED
4H2 OPEN
Transformer
Total
10.7 0.0
Transformer
Total
10.4 0.0
4H1 CLOSED
4B2-4 OPEN
4H3-4 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H4-4 CLOSED 4B4-12 0.0 0.0 4B7-12 0.8 0.8
4B3-4 OPEN 4B3-12 11.0 11.2 4B6-12 8.3 11.3
4H31 CLOSED 4B2-12 2.1 2.1
4B4-4 OPEN
4H16 CLOSED
4B4-13 OPEN
Transformer
Total
13.1 13.3
Transformer
Total
9.1 12.1
4H46 CLOSED
4B1-13 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
Switching Description: 4B2-6 7.6 12.3 4B4-17 12.0 12.0
4B3-6 6.8 0.2 4B3-17 1.0 1.0
4B4-6 4.7 4.7 4B2-17 2.2 8.8
Transformer
Total
19.1 17.2
Transformer
Total
15.2 21.8
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
Note: 4B5-3 0.6 0.6 4B2-9 7.8 7.8
4B4-3 9.9 12.7 4B3-9 8.2 12.6
4B3-3 0.6 6.6
Transformer
Total
11.1 19.9
Transformer
Total
16.0 20.4
SWITCHING PROCEDURE TEMPLEVIEW BREAKERS CITY BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
4B2-44B3-44B4-44B4-134B2-13&4B3-13
4B4-3 taking load off of 4B2-4
4B2-17 taking load off of 4B3-6
4B2-6 taking load off of 4B3-12
4B2-4 transferring to 4B3-12
4B3-4 powered through 4B4-4
4B4-4 transferring to 4B6-12
4B4-13 transferring to 4B3-9
4B2-13 powered through 4B3-13
4B3-13 transferring to 4B3-3
SUGARMILL BREAKERS HATCH BREAKERS
MILLIGAN BREAKERS FIFTEENTH ST. BREAKERS
4B3-4 needs to be connected to
another circuit.
4B2-13 needs to be connected to
another circuit.
N-2 Substation Switching Study
35
5.2.13 Templeview & York Road
Templeview’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H41 CLOSED 4B2-4 7.7 0.0 4B3-14 0.7 0.0
4D1 OPEN 4B3-4 0.6 0.0 4B4-14 6.8 0.0
4H49 CLOSED 4B4-4 2.4 0.0 4B5-14 0.0 0.0
4H42 OPEN 4B6-14 2.9 0.0
4H45 CLOSED 4B7-14 1.8 0
4H2 OPEN
Transformer
Total
10.7 0.0
Transformer
Total
12.2 0.0
4H1 CLOSED
4B2-4 OPEN
4H3-4 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H4-4 CLOSED 4B4-12 0.0 0.0 4B7-12 0.8 0.8
4B3-4 OPEN 4B3-12 11.0 11.2 4B6-12 8.3 11.3
4H31 CLOSED 4B2-12 2.1 2.1
4B4-4 OPEN
4H53 CLOSED
4B3-14 OPEN
Transformer
Total
13.1 13.3
Transformer
Total
9.1 12.1
4D51 CLOSED
4B4-14 OPEN
4B5-14
4B5-14 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H8 CLOSED 4B6-1 0.9 1.6 4B5-3 0.6 0.6
4H3 OPEN 4B5-1 7.1 0.0 4B4-3 9.9 12.7
4H10 CLOSED 4B4-1 0.5 0.5 4B3-3 0.6 0.6
4D14 OPEN 4B3-1 6.2 8.0
4H33 CLOSED 4B2-1 0.9 10.6
4B6-14 OPEN
Transformer
Total
15.6 20.7
Transformer
Total
11.1 13.9
4D85 CLOSED
4B7-14 OPEN
Switching Description: Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-17 12.0 12.0 4B2-9 7.8 7.8
4B3-17 1.0 1.0 4B3-9 8.2 12.1
4B2-17 2.2 8.8
Transformer
Total
15.2 21.8
Transformer
Total
16.0 19.9
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-6 7.6 12.3 4B2-13 2.1 2.1
4B3-6 6.8 0.2 4B3-13 3.9 7.1
4B4-6 4.7 4.7 4B4-13 4.4 4.4
Note:
Transformer
Total
19.1 17.2
Transformer
Total
10.4 13.6
4B7-14
4B3-4 needs to be connected to
another circuit.
SUGARMILL BREAKERS CITY BREAKERS
4B3-44B4-44B3-144B4-144B6-14
RACK BREAKERS MILLIGAN BREAKERS
HATCH BREAKERS FIFTEENTH ST. BREAKERS
4B4-3 taking load off of 4B2-4
4B2-17 taking load off of 4B3-6
4B2-6 taking load off of 4B3-12
4B2-4 transferring to 4B3-12
4B3-4 powered through 4B4-4
4B4-4 transferring to 4B6-12
4B3-14 transferring to 4B6-1
4B4-14 transferring to 4B6-14
4B5-14 shut off
4B3-13 taking load off of 4B3-9
4B3-9 taking load off of 4B5-1
4B6-14 transferring to 4B2-1
4B7-14 transferring to 4B3-1
SWITCHING PROCEDURE TEMPLEVIEW BREAKERS YORK ROAD BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
4B2-4
N-2 Substation Switching Study
36
5.2.14 Templeview & Harrison
Templeview’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H58 CLOSED 4B2-4 7.7 0.0 4B2-16 2.2 0.0
4H55 OPEN 4B3-4 0.6 0.0 4B3-16 6.7 0.0
4H9 CLOSED 4B4-4 2.4 0.0 4B4-16 4.6 0.0
4H44 OPEN 4B5-16 0.6 0.0
4H45 CLOSED
4H2 OPEN
Transformer
Total
10.7 0.0
Transformer
Total
14.1 0.0
4H1 CLOSED
4B2-4 OPEN
4H3-4 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H4-4 CLOSED 4B4-12 0.0 0.0 4B7-12 0.8 0.8
4B3-4 OPEN 4B3-12 11.0 10.7 4B6-12 8.3 11.3
4H31 CLOSED 4B2-12 2.1 2.1
4B4-4 OPEN
4D13 CLOSED
4B2-16 OPEN
Transformer
Total
13.1 12.8
Transformer
Total
9.1 12.1
4H8 CLOSED
4H3 OPEN
4H7 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H43 OPEN 4B6-1 0.9 0.9 4B3-14 0.7 0.7
4H49 CLOSED 4B5-1 7.1 7.1 4B4-14 6.8 6.8
4H42 OPEN 4B4-1 0.5 0.5 4B5-14 0.0 0.0
4H21 CLOSED 4B3-1 6.2 12.2 4B6-14 2.9 2.9
4B3-16 OPEN 4B2-1 0.9 0.9 4B7-14 1.8 2.6
4D85 CLOSED
Transformer
Total
15.6 21.6
Transformer
Total
12.2 13.0
4D72 OPEN
4H20 CLOSED
4B4-16 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4D54 CLOSED 4B4-17 12.0 9.0 4B2-9 7.8 7.8
4B5-16 OPEN 4B3-17 1.0 1.0 4B3-9 8.2 8.0
4B2-17 2.2 8.8
Switching Description:
Transformer
Total
15.2 18.8
Transformer
Total
16.0 15.8
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-6 7.6 9.5 4B2-13 2.1 2.1
4B3-6 6.8 0.2 4B3-13 3.9 9.9
4B4-6 4.7 12.0 4B4-13 4.4 7.7
Transformer
Total
19.1 21.7
Transformer
Total
10.4 19.7
Note:
4B3-4 needs to be connected to
another circuit.
HATCH BREAKERS FIFTEENTH ST. BREAKERS
SUGARMILL BREAKERS CITY BREAKERS
4B5-164B4-164B3-16
4B3-9 taking load off of 4B3-12
4B4-13 taking load off of 4B3-12
4B2-6 taking load off of 4B3-12
4B2-4 transferring to 4B3-12
4B3-4 powered through 4B4-4
4B4-4 transferring to 4B6-12
4B2-16 transferring to 4B4-16
4B3-13 taking load off of 4B3-9
4B3-9 taking load off of 4B4-17
4B2-17 taking load off of 4B3-6
4B3-16 transferring to 4B4-6
4B7-14 taking load off of 4B3-1
4B4-16 transferring to 4B3-1
4B5-16 transferring to 4B4-6
4B3-44B4-44B2-16
RACK BREAKERS YORK BREAKERS
SWITCHING PROCEDURE TEMPLEVIEW BREAKERS HARRISON BREAKERS
4B2-4
N. BOULEVARD 5T1-12
BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
N-2 Substation Switching Study
37
5.2.15 Templeview & Hatch
Templeview’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H58 CLOSED 4B2-4 7.7 0.0 4B4-17 12.0 0.0
4H55 OPEN 4B3-4 0.6 0.0 4B3-17 1.0 0.0
4H9 CLOSED 4B4-4 2.4 0.0 4B2-17 2.2 0.0
4H44 OPEN
4H1 CLOSED
4B2-4 OPEN
Transformer
Total
10.7 0.0
Transformer
Total
15.2 0.0
4H3-4 CLOSED
4H4-4 CLOSED
4B3-4 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H31 CLOSED 4B4-12 0.0 0.0 4B7-12 0.8 0.8
4B1-4 OPEN 4B3-12 11.0 12.6 4B6-12 8.3 11.3
4H49 CLOSED 4B2-12 2.1 2.1
4B2-17 OPEN
4H5 CLOSED
4B3-17 OPEN
Transformer
Total
13.1 14.7
Transformer
Total
9.1 12.1
4H26 CLOSED
4H40 OPEN
4H8 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H3 OPEN 4B2-6 7.6 8.6 4B2-13 2.1 2.1
4H7 CLOSED 4B3-6 6.8 9.0 4B3-13 3.9 9.9
4B4-17 OPEN 4B4-6 4.7 4.7 4B4-13 4.4 7.7
Switching Description:
Transformer
Total
19.1 22.3
Transformer
Total
10.4 19.7
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-16 2.2 2.2 4B2-9 7.8 7.8
4B3-16 6.7 6.7 4B3-9 8.2 11.2
4B4-16 4.6 10.4
4B5-16 0.6 0.6
Note:
Transformer
Total
14.1 19.9
Transformer
Total
16.0 19.0
4B3-9 taking load off of 4B3-12
4B4-13 taking load off of 4B3-12
4B2-4 transferring to 4B3-12
4B3-4 powered through 4B4-4
4B4-4 transferring to 4B6-12
4B2-17 transferring to 4B3-6
4B3-17 transferring to 4B2-6
4B4-16 taking load off of 4B4-17
4B3-13 taking load off of 4B3-9
4B4-17 transferring to 4B3-9
4B3-44B4-4
SUGARMILL BREAKERS
4B3-4 needs to be connected to
another circuit.
Upgrading the 336 ACSR wire
between 4S8 and 4H20 would
simplify the switching procedure.
CITY BREAKERS
HARRISON BREAKERS FIFTEENTH ST. BREAKERS
4B2-174B3-174B4-17
SWITCHING PROCEDURE TEMPLEVIEW BREAKERS HATCH BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
4B2-4
N-2 Substation Switching Study
38
5.2.16 Templeview & Westside
Templeview’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H41 CLOSED 4B2-4 7.7 0.0 4B3-18 8.8 0.0
4D1 OPEN 4B3-4 0.6 0.0
4H49 CLOSED 4B4-4 2.4 0.0
4H42 OPEN
4H45 CLOSED
4H2 OPEN
Transformer
Total
10.7 0.0
Transformer
Total
8.8 0.0
4H1 CLOSED
4B2-4 OPEN
4H3-4 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H4-4 CLOSED 4B4-12 0.0 0.0 4B7-12 0.8 0.8
4B3-4 OPEN 4B3-12 11.0 11.2 4B6-12 8.3 11.3
4H31 CLOSED 4B2-12 2.1 2.1
4B4-4 OPEN
4H36 CLOSED
4D17 OPEN
Transformer
Total
13.1 13.3
Transformer
Total
9.1 12.1
4H52 CLOSED
4B3-18 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
Switching Description: 4B6-1 0.9 0.9 4B5-3 0.6 9.9
4B5-1 7.1 7.1 4B4-3 9.9 12.7
4B4-1 0.5 0.0 4B3-3 0.6 0.6
4B3-1 6.2 6.2
4B2-1 0.9 0.9
Transformer
Total
15.6 15.1
Transformer
Total
11.1 23.2
Note: Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-17 12.0 12.0 4B2-6 7.6 12.3
4B3-17 1.0 1.0 4B3-6 6.8 0.2
4B2-17 2.2 8.8 4B4-6 4.7 4.7
Transformer
Total
15.2 21.8
Transformer
Total
19.1 17.2
4B3-4 needs to be connected to
another circuit.
4B3-18
4B4-3 taking load off of 4B2-4
4B2-17 taking load off of 4B3-6
4B2-6 taking load off of 4B3-12
4B2-4 transferring to 4B3-12
4B3-4 powered through 4B4-4
4B4-4 transferring to 4B6-12
4B5-3 taking load off of 4B4-1
4B3-18 transferring to 4B5-3
HATCH BREAKERS SUGARMILL BREAKERS
4B3-44B4-4
RACK BREAKERS MILLIGAN BREAKERS
SWITCHING PROCEDURE TEMPLEVIEW BREAKERS WESTSIDE BREAKERS
4B2-4
N. BOULEVARD 5T1-12
BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
N-2 Substation Switching Study
39
5.2.17 Sugarmill & N. Boulevard
N. Boulevard’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4D85 CLOSED 4B7-12 0.8 0.0 4B4-12 0.0 0.0
4D72 OPEN 4B6-12 8.3 0.0 4B3-12 11.0 0.0
4H20 CLOSED 4B2-12 2.1 0.0
4D81 OPEN
Transformer
Total
9.1 0.0
Transformer
Total
13.1 0.0
4H26 CLOSED
4H40 OPEN
4H21 CLOSED Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-6 OPEN 4B2-4 7.7 10.0 4B2-13 2.1 2.1
4H49 CLOSED 4B3-4 0.6 0.6 4B3-13 3.9 3.9
4B3-6 OPEN 4B4-4 2.4 11.5 4B4-13 4.4 7.7
4H5 CLOSED
Transformer
Total
10.7 22.1
Transformer
Total
10.4 13.7
4B2-6 OPEN
4H12-12 CLOSED
4H13-12 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B7-12 OPEN 4B2-9 7.8 7.8 4B4-17 12.0 6.2
4H31 CLOSED 4B3-9 8.2 12.9 4B3-17 1.0 8.6
4B6-12 OPEN 4B2-17 2.2 9.0
4H58 CLOSED
Transformer
Total
16.0 20.7
Transformer
Total
15.2 23.8
4H2 OPEN
4H9 CLOSED
4H44 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H41 CLOSED 4B3-14 0.7 0.7 4B5-3 0.6 0.6
4D1 OPEN 4B4-14 6.8 6.8 4B4-3 9.9 12.7
4H1 CLOSED 4B5-14 0.0 0.0 4B3-3 0.6 0.6
4B3-12 OPEN 4B6-14 2.9 2.9
OLD CUTOUT CLOSED 4B7-14 1.8 2.6
4B2-12 OPEN
Transformer
Total
12.2 13.0
Transformer
Total
11.1 13.9
Switching Description:
Breaker ID Initial Power Resulting Power Breaker ID Initial Power Resulting Power
4B2-6 7.6 0.0 4B2-16 2.2 2.2
4B3-6 6.8 0.0 4B3-16 6.7 11.4
4B4-6 4.7 0.0 4B4-16 4.6 3.0
4B5-16 0.6 0.6
Transformer
Total
19.1 0.0
Transformer
Total
14.1 17.2
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B6-1 0.9 0.9
4B5-1 7.1 7.1
4B4-1 0.5 0.5
4B3-1 6.2 12.8
Note: 4B2-1 0.9 0.9
Old Cutout needs to be a switch. Transformer
Total
15.6 22.2
RACK BREAKERS
TEMPLEVIEW BREAKERS CITY BREAKERS
HARRISON BREAKERS
SWITCHING PROCEDURE
N. BOULEVARD 5T2-12
BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
SUGARMILL BREAKERS
4B3-12
4B3-1 taking load off of 4B7-14
4B4-16 taking load off of 4B3-1
4B4-16 taking load off of 4B4-17
4B4-6 transferring to 4B3-16
4B3-6 transferring to 4B2-17
4B2-6 transferring to 4B3-17
4B7-12 transferring to 4B6-12
4B6-12 transferring to 4B4-4
4B3-9 taking load off of 4B3-12
4B4-13taking load off of 4B3-12
4B4-3taking load off of 4B2-4
4B3-12 transferring to 4B2-4
4B2-12 transferring to 4B2-4
YORK ROAD BREAKERS MILLIGAN BREAKERS
4B4-64B3-64B7-124B6-124B2-124B2-6
FIFTEENTH ST. BREAKERS HATCH BREAKERS
N-2 Substation Switching Study
40
5.2.18 Sugarmill & City
City’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H5 CLOSED 4B2-6 7.6 0.0 4B2-13 2.1 0.0
4B2-6 OPEN 4B3-6 6.8 0.0 4B3-13 3.9 0.0
4H26 CLOSED 4B4-6 4.7 0.0 4B4-13 4.4 0.0
4H40 OPEN
4H49 CLOSED
4B3-6 OPEN
Transformer
Total
19.1 0.0
Transformer
Total
10.4 0.0
4H21 CLOSED
4B4-6 OPEN
4H16 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-13 OPEN 4B4-17 12.0 6.2 4B2-9 7.8 7.8
4B2-4
4B2-4 CLOSED 4B3-17 1.0 8.6 4B3-9 8.2 12.6
4H46 CLOSED 4B2-17 2.2 9.0
4B1-13 OPEN
Switching Description:
Transformer
Total
15.2 23.8
Transformer
Total
16.0 20.4
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B5-3 0.6 0.6 4B2-16 2.2 2.2
4B4-3 9.9 9.9 4B3-16 6.7 11.4
4B3-3 0.6 6.6 4B4-16 4.6 10.4
Note: 4B5-16 0.6 0.6
Transformer
Total
11.1 17.1
Transformer
Total
14.1 24.6
4B2-13 needs to be powered
through another circuit.
4B2-64B3-64B4-64B4-134B3-13
4B2-6 transferring to 4B3-17
4B4-16 taking load off of 4B4-17
4B3-6 transferring to 4B2-17
4B4-6 transferring to 4B3-16
4B4-13 transferring to 4B3-9
4B2-13 powered through 4B3-13
4B3-13 transferring to
MILLIGAN BREAKERS HARRISON BREAKERS
SWITCHING PROCEDURE SUGARMILL BREAKERS CITY BREAKERS
HATCH BREAKERS FIFTEENTH ST. BREAKERS
N-2 Substation Switching Study
41
5.2.19 Fifteenth St. & N. Boulevard
N. Boulevard’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H20 CLOSED 4B7-12 0.8 0.0 4B4-12 0.0 0.0
4D52 OPEN 4B6-12 8.3 0.0 4B3-12 11.0 0.0
4H12 CLOSED 4B2-12 2.1 0.0
4D12 OPEN
4D85 CLOSED
4D73 OPEN
Transformer
Total
9.1 0.0
Transformer
Total
13.1 0.0
4H13 CLOSED
4B2-9 OPEN
4H8 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H3 OPEN 4B2-9 7.8 0.0 4B2-4 7.7 10.0
4H10 CLOSED 4B3-9 8.2 0.0 4B3-4 0.6 0.6
4B3-9 OPEN 4B4-4 2.4 11.5
4H58 CLOSED
4H55 OPEN
OLD CUTOUT CLOSED
Transformer
Total
16.0 0.0
Transformer
Total
10.7 22.1
4B2-12 OPEN
4H45 CLOSED
4H2 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H9 CLOSED 4B2-6 7.6 9.5 4B5-3 0.6 0.6
4H44 OPEN 4B3-6 6.8 6.8 4B4-3 9.9 12.7
4H41 CLOSED 4B4-6 4.7 4.7 4B3-3 0.6 0.6
4D1 OPEN
4H1 CLOSED
4B3-12 OPEN
Transformer
Total
19.1 21.0
Transformer
Total
11.1 13.9
4H31 CLOSED
4B6-12 OPEN
4H12-12 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H13-12 CLOSED 4B3-14 0.7 0.7 4B6-1 0.9 0.9
4B7-12 OPEN 4B4-14 6.8 6.8 4B5-1 7.1 12.1
4B5-14 0.0 0.0 4B4-1 0.5 0.5
Switching Description: 4B6-14 2.9 2.9 4B3-1 6.2 3.9
4B7-14 1.8 9.5 4B2-1 0.9 0.9
Transformer
Total
12.2 19.9
Transformer
Total
15.6 18.3
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-13 2.1 2.1 4B2-16 2.2 2.2
4B3-13 3.9 9.9 4B3-16 6.7 6.7
4B4-13 4.4 7.7 4B4-16 4.6 7.0
4B5-16 0.6 0.6
Transformer
Total
10.4 19.7
Transformer
Total
14.1 16.5
Note:
Old Cutout needs to be a switch.
4B2-12
RACK BREAKERSYORK ROAD BREAKERS
SUGARMILL BREAKERS
TEMPLEVIEW BREAKERS
CITY BREAKERS HARRISON BREAKERS
4B2-94B3-9
4B4-16 taking load off of 4B3-1
4B4-16 taking load off of 4B2-9
4B7-14 taking load off of 4B3-1
4B2-9 transferring to 4B7-14
4B3-13 taking load off of 4B3-9
4B3-9 transferring to 4B5-1
4B3-13 taking load off of 4B3-12
4B2-12 transferring to 4B3-12
4B2-6 taking load off of 4B3-12
4B4-13 taking load off of 4B3-12
4B4-3 taking load off of 4B2-4
4B3-12 transferring to 4B2-4
4B6-12 transferring to 4B4-4
4B7-12 transferring to 4B4-4
SWITCHING PROCEDURE
N. BOULEVARD 5T2-12
BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
FIFTEENTH ST. BREAKERS
MILLIGAN BREAKERS
4B3-124B6-124B7-12
N-2 Substation Switching Study
42
5.2.20 Fifteenth St. & City
City’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H20 CLOSED 4B2-9 7.8 0.0 4B2-13 2.1 0.0
4D52 OPEN 4B3-9 8.2 0.0 4B3-13 3.9 0.0
4H12 CLOSED 4B4-13 4.4 0.0
4D12 OPEN
4H13 CLOSED
4B2-9 OPEN
Transformer
Total
16.0 0.0
Transformer
Total
10.4 0.0
4H26 CLOSED
4S8 OPEN
4H49 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H42 OPEN 4B6-1 0.9 0.9 4B4-12 0.0 0.0
4D16 CLOSED 4B5-1 7.1 7.1 4B3-12 11.0 10.7
4D69 OPEN 4B4-1 0.5 0.5 4B2-12 2.1 2.1
4H7 CLOSED 4B3-1 6.2 11.6
4B3-9 OPEN 4B2-1 0.9 0.9
4H45 CLOSED
Transformer
Total
15.6 21.0
Transformer
Total
13.1 12.8
4H2 OPEN
4H9 CLOSED
4B4-13 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H46 CLOSED 4B2-6 7.6 12.3 4B4-17 12.0 12.8
4B1-13 OPEN 4B3-6 6.8 0.2 4B3-17 1.0 1.0
4B4-6 4.7 9.9 4B2-17 2.2 8.8
Switching Description:
Transformer
Total
19.1 22.4
Transformer
Total
15.2 22.6
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-16 2.2 2.2 4B5-3 0.6 0.6
4B3-16 6.7 6.7 4B4-3 9.9 9.9
4B4-16 4.6 9.2 4B3-3 0.6 6.6
4B5-16 0.6 0.6
Note:
Transformer
Total
14.1 18.7
Transformer
Total
11.1 17.1
SUGARMILL BREAKERS HATCH BREAKERS
HARRISON BREAKERS MILLIGAN BREAKERS
SWITCHING PROCEDURE FIFTEENTH ST. BREAKERS CITY BREAKERS
RACK BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
4B2-94B3-94B4-134B2-13&4B3-13
4B4-16 taking load off of 4B3-1
4B4-16 taking load off of 4B2-9
4B2-9 transferring to 4B3-1
4B4-16 taking load off of 4B4-17
4B2-17 taking load off of 4B3-6
4B4-6 taking load off of 4B4-17
4B3-9 transferring to 4B4-17
4B2-6 taking load off of 4B3-12
4B4-13 transferring to 4B3-12
4B2-13 powered through 4B3-13
4B3-13 transferring to 4B3-3
4B2-13 needs to be connected to
another circuit.
N-2 Substation Switching Study
43
5.2.21 Fifteenth St. & Hatch
Hatch’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H13 CLOSED 4B2-9 7.8 0.0 4B4-17 12.0 0.0
4H47 OPEN 4B3-9 8.2 0.0 4B3-17 1.0 0.0
4H30 CLOSED 4B2-17 2.2 0.0
4B2-9 OPEN
4H16 CLOSED
4H19 OPEN
Transformer
Total
16.0 0.0
Transformer
Total
15.2 0.0
4H8 CLOSED
4B3-9 OPEN
4B5-17 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H2-17 CLOSED 4B6-1 0.9 0.9 4B4-12 0.0 0.0
4H3-17 CLOSED 4B5-1 7.1 11.2 4B3-12 11.0 11.8
4B2-17 OPEN 4B4-1 0.5 0.5 4B2-12 2.1 2.1
4H5 CLOSED 4B3-1 6.2 9.9
4B3-17 OPEN 4B2-1 0.9 0.9
4H26 CLOSED
Transformer
Total
15.6 23.4
Transformer
Total
13.1 13.9
4H40 OPEN
4H9 CLOSED
4H44 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H45 CLOSED 4B2-6 7.6 6.7 4B2-16 2.2 2.2
4H4 OPEN 4B3-6 6.8 13.0 4B3-16 6.7 6.7
4H28 CLOSED 4B4-6 4.7 4.7 4B4-16 4.6 10.4
4B4-17 OPEN 4B5-16 0.6 0.6
Switching Description:
Transformer
Total
19.1 24.4
Transformer
Total
14.1 19.9
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-13 2.1 2.1
4B3-13 3.9 9.5
4B4-13 4.4 10.3
Transformer
Total
10.4 21.9
HARRISON BREAKERS
CITY BREAKERS
SWITCHING PROCEDURE FIFTEENTH ST. BREAKERS HATCH BREAKERS
RACK BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
4B2-94B3-94B2-174B3-174B4-17
4B3-1 taking load off of 4B2-9
4B2-9 transferring to 4B5-1
4B4-13 taking load off of 4B3-9
4B3-9 transferring to 4B3-13
4B2-17 transferring to 4B3-17
4B3-17 transferring to 4B2-6
4B4-16 taking load off of 4B4-17
4B4-13 taking load off of 4B3-12
4B3-12 taking load off of 4B2-6
4B4-17 transferring to 4B3-6
SUGARMILL BREAKERS
N-2 Substation Switching Study
44
5.2.22 N. Boulevard & York Road
N. Boulevard’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H58 CLOSED 4B7-12 0.8 0.0 4B4-12 0.0 0.0
4H55 OPEN 4B6-12 8.3 0.0 4B3-12 11.0 0.0
OLD CUTOUT CLOSED 4B2-12 2.1 0.0
4B2-12 OPEN
4H8 CLOSED
4H3 OPEN
Transformer
Total
9.1 0.0
Transformer
Total
13.1 0.0
4H45 CLOSED
4H2 OPEN
4H9 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H44 OPEN 4B2-4 7.7 10.0 4B2-13 2.1 2.1
4H41 CLOSED 4B3-4 0.6 0.6 4B3-13 3.9 9.9
4D1 OPEN 4B4-4 2.4 11.5 4B4-13 4.4 7.7
4H1 CLOSED
4B3-12 OPEN
4H31 CLOSED
Transformer
Total
10.7 22.1
Transformer
Total
10.4 19.7
4B6-12 OPEN
4H12-12 CLOSED
4H13-12 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B7-12 OPEN 4B2-9 7.8 7.8 4B2-6 7.6 9.5
4H53 CLOSED 4B3-9 8.2 5.0 4B3-6 6.8 6.8
4B3-14 OPEN 4B4-6 4.7 4.7
4D51 CLOSED
4B4-14 OPEN
4B5-14
4B5-14 OPEN
Transformer
Total
16.0 12.8
Transformer
Total
19.1 21.0
4H33 CLOSED
4B6-14 OPEN
4H20 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H27 OPEN 4B3-14 0.7 0.0 4B5-3 0.6 0.6
4D85 CLOSED 4B4-14 6.8 0.0 4B4-3 9.9 12.7
4B7-14 OPEN 4B5-14 0.0 0.0 4B3-3 0.6 0.6
4B6-14 2.9 0.0
Switching Description: 4B7-14 1.8 0.0
Transformer
Total
12.2 0.0
Transformer
Total
11.1 13.9
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-16 2.2 2.2 4B6-1 0.9 1.6
4B3-16 6.7 6.7 4B5-1 7.1 7.1
4B4-16 4.6 12.0 4B4-1 0.5 0.5
4B5-16 0.6 0.6 4B3-1 6.2 0.6
4B2-1 0.9 10.6
Transformer
Total
14.1 21.5
Transformer
Total
15.6 20.4
Note:
4B3-144B4-144B6-144B7-14
YORK ROAD BREAKERS MILLIGAN BREAKERS
HARRISON BREAKERS RACK BREAKERS
4B3-9 taking load off of 4B3-12
4B2-12 transferring to 4B3-12
4B3-13 taking load off of 4B3-9
4B2-6 taking load off of 4B3-12
4B4-14 taking load off of 4B3-12
4B4-3 taking load off of 4B2-4
4B3-12 transferring to 4B2-4
4B6-12 transferring to 4B4-4
4B7-12 transferring to 4B4-4
4B3-14 transferring to 4B6-1
4B4-14 transferring to 4B6-14
4B5-14 shut off
4B6-14 transferring to 4B2-1
4B4-16 taking load off of 4B3-1
4B7-14 transferring to 4B4-16
4B7-12 needs to be connected to
another circuit.
Old Cutout needs to be a switch.
4B3-12
TEMPLEVIEW BREAKERS CITY BREAKERS
4B6-124B7-12
FIFTEENTH ST. BREAKERS SUGARMILL BREAKERS
SWITCHING PROCEDURE
N. BOULEVARD 5T2-12
BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
4B2-12
N-2 Substation Switching Study
45
5.2.23 N. Boulevard & Harrison
N. Boulevard’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H58 CLOSED 4B7-12 0.8 0.0 4B4-12 0.0 0.0
4H55 OPEN 4B6-12 8.3 0.0 4B3-12 11.0 0.0
OLD CUTOUT CLOSED 4B2-12 2.1 0.0
4B2-12 OPEN
4H8 CLOSED
4H3 OPEN
Transformer
Total
9.1 0.0
Transformer
Total
13.1 0.0
4H45 CLOSED
4H2 OPEN
4H9 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H44 OPEN 4B2-16 2.2 0.0 4B2-13 2.1 2.1
4H41 CLOSED 4B3-16 6.7 0.0 4B3-13 3.9 9.9
4D1 OPEN 4B4-16 4.6 0.0 4B4-13 4.4 7.7
4H1 CLOSED 4B5-16 0.6 0.0
4B3-12 OPEN
4H31 CLOSED
Transformer
Total
14.1 0.0
Transformer
Total
10.4 19.7
4B6-12 OPEN
4H12-12 CLOSED
4H13-12 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B7-12 OPEN 4B2-9 7.8 7.8 4B2-6 7.6 9.5
4D85 CLOSED 4B3-9 8.2 8.0 4B3-6 6.8 0.2
4D72 OPEN 4B4-6 4.7 12.0
4H7 CLOSED
4H43 OPEN
4H49 CLOSED
Transformer
Total
16.0 15.8
Transformer
Total
19.1 21.7
4H42 OPEN
4D13 CLOSED
4B2-16 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H21 CLOSED 4B3-14 0.7 0.7 4B5-3 0.6 0.6
4B3-16 OPEN 4B4-14 6.8 6.8 4B4-3 9.9 12.7
4H20 CLOSED 4B5-14 0.0 0.0 4B3-3 0.6 0.6
4B4-16 OPEN 4B6-14 2.9 2.9
4D54 CLOSED 4B7-14 1.8 2.6
4B5-16 OPEN
Transformer
Total
12.2 13.0
Transformer
Total
11.1 13.9
Switching Description:
Breaker ID Initial Power Resulting Power Breaker ID Initial Power Resulting Power
4B2-4 7.7 10.0 4B4-17 12.0 9.0
4B3-4 0.6 0.6 4B3-17 1.0 1.0
4B4-4 2.4 11.5 4B2-17 2.2 8.8
Transformer
Total
10.7 22.1
Transformer
Total
15.2 18.8
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B6-1 0.9 0.9
4B5-1 7.1 7.1
4B4-1 0.5 0.5
4B3-1 6.2 12.2
4B2-1 0.9 0.9
Note:
Transformer
Total
15.6 21.6
4B4-16
YORK ROAD BREAKERS MILLIGAN BREAKERS
4B2-164B5-164B3-16
4B7-12 needs to be connected to
another circuit.
Old Cutout needs to be a switch.
4B3-9 taking load off of 4B3-12
4B2-12 transferring to 4B3-12
4B3-13 taking load off of 4B3-9
4B2-6 taking load off of 4B3-12
4B4-14 taking load off of 4B3-12
4B4-3 taking load off of 4B2-4
4B3-12 transferring to 4B2-4
4B6-12 transferring to 4B4-4
4B7-12 transferring to 4B4-4
4B7-14 taking load off of 4B3-1
4B3-9 taking load off of 4B4-17
4B2-17 taking load off of 4B3-6
4B2-16 transferring to 4B4-16
4B3-16 transferring to 4B4-6
4B4-16 transferring to 4B3-1
4B5-16 transferring to 4B4-6
4B7-12
FIFTEENTH ST. BREAKERS SUGARMILL BREAKERS
RACK BREAKERS
SWITCHING PROCEDURE
N. BOULEVARD 5T2-12
BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
HARRISON BREAKERS
4B2-124B3-12
TEMPLEVIEW BREAKERS
CITY BREAKERS
HATCH BREAKERS
4B6-12
N-2 Substation Switching Study
46
5.2.24 N. Boulevard & Hatch
N. Boulevard’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H58 CLOSED 4B7-12 0.8 0.0 4B4-12 0.0 0.0
4H55 OPEN 4B6-12 8.3 0.0 4B3-12 11.0 0.0
OLD CUTOUT CLOSED 4B2-12 2.1 0.0
4B2-12 OPEN
4H8 CLOSED
4H3 OPEN
Transformer
Total
9.1 0.0
Transformer
Total
13.1 0.0
4H45 CLOSED
4H2 OPEN
4H9 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H44 OPEN 4B4-17 12.0 0.0 4B2-13 2.1 2.1
4H41 CLOSED 4B3-17 1.0 0.0 4B3-13 3.9 9.9
4D1 OPEN 4B2-17 2.2 0.0 4B4-13 4.4 7.7
4H1 CLOSED
4B3-12 OPEN
Transformer
Total
15.2 0.0
Transformer
Total
10.4 19.7
4H31 CLOSED
4B6-12 OPEN
4H12-12 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H13-12 CLOSED 4B2-9 7.8 7.8 4B2-6 7.6 10.5
4B7-12 OPEN 4B3-9 8.2 11.2 4B3-6 6.8 9.0
4H21 CLOSED 4B4-6 4.7 0.0
4D5 OPEN
Transformer
Total
16.0 19.0
Transformer
Total
19.1 19.5
4H49 CLOSED
4B2-17 OPEN
4H5 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B3-17 OPEN 4B3-14 0.7 0.7 4B5-3 0.6 0.6
4D85 CLOSED 4B4-14 6.8 6.8 4B4-3 9.9 12.7
4D73 OPEN 4B5-14 0.0 0.0 4B3-3 0.6 0.6
4H20 CLOSED 4B6-14 2.9 2.9
4H40 OPEN 4B7-14 1.8 11.5
4H7 CLOSED
Transformer
Total
12.2 21.9
Transformer
Total
11.1 13.9
4B4-17 OPEN
Switching Description: Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-16 2.2 2.2 4B6-1 0.9 0.9
4B3-16 6.7 11.4 4B5-1 7.1 7.1
4B4-16 4.6 3.0 4B4-1 0.5 0.5
4B5-16 0.6 0.6 4B3-1 6.2 3.9
4B2-1 0.9 0.9
Transformer
Total
14.1 17.2
Transformer
Total
15.6 13.3
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-4 7.7 10.0
4B3-4 0.6 0.6
4B4-4 2.4 11.5
Transformer
Total
10.7 22.1
Note:
Old Cutout needs to be a switch.
4B4-17
RACK BREAKERS
YORK ROAD BREAKERS MILLIGAN BREAKERS
4B7-124B2-174B3-17
FIFTEENTH ST. BREAKERS SUGARMILL BREAKERS
4B3-9 taking load off of 4B3-12
4B2-12 transferring to 4B3-12
4B3-13 taking load off of 4B3-9
4B2-6 taking load off of 4B3-12
4B4-14 taking load off of 4B3-12
4B4-3 taking load off of 4B2-4
4B3-12 transferring to 4B2-4
4B6-12 transferring to 4B4-4
4B7-12 transferring to 4B4-4
4B3-16 taking load off of 4B4-6
4B2-17 transferring to 4B3-6
4B3-17 transferring to 4B2-6
4B7-14 taking load off of 4B3-1
4B7-14 taking load off of 4B4-17
4B4-17 transferring to 4B3-9
4B3-124B6-12
SWITCHING PROCEDURE
N. BOULEVARD 5T2-12
BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
HATCH BREAKERS
TEMPLEVIEW BREAKERS
CITY BREAKERS
HARRISON BREAKERS
4B2-12
N-2 Substation Switching Study
47
5.2.25 N. Boulevard & Westside
N. Boulevard’s aux bus needs to be online for this procedure.
Switch Status Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H9 CLOSED 4B7-12 0.8 0.0 4B4-12 0.0 0.0
4H44 OPEN 4B6-12 8.3 0.0 4B3-12 11.0 0.0
OLD CUTOUT CLOSED 4B2-12 2.1 0.0
4B2-12 OPEN
Transformer
Total
9.1 0.0
Transformer
Total
13.1 0.0
4H26 CLOSED
4H40 OPEN
4H5 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H6 OPEN 4B3-18 8.8 0.0 4B5-3 0.6 9.9
4H58 CLOSED 4B4-3 9.9 9.9
4H55 OPEN 4B3-3 0.6 0.6
4H45 CLOSED Transformer 8.8 0.0 Transformer 11.1 20.4
4B3-12 OPEN
4H31 CLOSED
4B6-12 OPEN
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4H12-12 CLOSED 4B2-9 7.8 7.8 4B2-6 7.6 3.5
4H13-12 CLOSED 4B3-9 8.2 11.0 4B3-6 6.8 6.8
4B7-12 OPEN 4B4-6 4.7 4.7
4H36 OPEN
Transformer
Total
16.0 18.8
Transformer
Total
19.1 15.0
4D17 CLOSED
4H52 OPEN
4B3-18 CLOSED
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-13 2.1 2.1 4B2-4 7.7 7.7
Switching Description: 4B3-13 3.9 3.9 4B3-4 0.6 0.6
4B4-13 4.4 7.7 4B4-4 2.4 11.5
Transformer
Total
10.4 13.7
Transformer
Total
10.7 19.8
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW) Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B2-16 2.2 2.2 4B6-1 0.9 0.9
4B3-16 6.7 6.7 4B5-1 7.1 7.1
Note: 4B4-16 4.6 10.4 4B4-1 0.5 0.0
4B5-16 0.6 0.6 4B3-1 6.2 6.2
4B2-1 0.9 0.9
Transformer
Total
14.1 19.9
Transformer
Total
15.6 15.1
Breaker ID
Initial Power
(in MW)
Resulting Power
(in MW)
4B4-17 12.0 6.2
4B3-17 1.0 12.1
4B2-17 2.2 2.2
Transformer
Total
15.2 20.5
SUGARMILL BREAKERS
CITY BREAKERS TEMPLEVIEW BREAKERS
HARRISON BREAKERS RACK BREAKERS
SWITCHING PROCEDURE
N. BOULEVARD 5T2-12
BREAKERS
N. BOULEVARD 5T1-12
BREAKERS
WESTSIDE BREAKERS MILLIGAN BREAKERS
4B2-124B3-124B7-124B6-124B3-18
4B4-13 taking load off of 4B3-12
4B2-12 transferring to 4B3-12
4B4-16 taking load off of 4B4-17
4B3-17 taking load off of 4B2-6
4B3-12 transferring to 4B3-17 & 4B3-9
4B6-12 transferring to 4B4-4
4B7-12 transferring to 4B4-4
4B5-3 taking load off of 4B4-1
4B3-18 transferring to 4B5-3
HATCH BREAKERS
FIFTEENTH ST. BREAKERS
4B7-12 needs to be connected to
another circuit.
Old Cutout needs to be a switch.
Connect 4B7-12 to 4R7.
N-2 Substation Switching Study
N-2 Substation Switching Study
N-2 Substation Switching Study
N-2 Substation Switching Study
N-2 Substation Switching Study
N-2 Substation Switching Study
N-2 Substation Switching Study
N-2 Substation Switching Study

More Related Content

Similar to N-2 Substation Switching Study

AC_Microgrid_Versus_DC_Microgrid_A_Revie.pdf
AC_Microgrid_Versus_DC_Microgrid_A_Revie.pdfAC_Microgrid_Versus_DC_Microgrid_A_Revie.pdf
AC_Microgrid_Versus_DC_Microgrid_A_Revie.pdfDebasree Saha
 
EGR-386 proposal S.I.C.with table of content
EGR-386 proposal S.I.C.with table of contentEGR-386 proposal S.I.C.with table of content
EGR-386 proposal S.I.C.with table of contentMohammad Molani
 
Raffaele Salvucci s111179 Thesis
Raffaele Salvucci s111179 ThesisRaffaele Salvucci s111179 Thesis
Raffaele Salvucci s111179 Thesisraffaele00
 
Design of 450W Solar Battery Charging System
Design of 450W Solar Battery Charging SystemDesign of 450W Solar Battery Charging System
Design of 450W Solar Battery Charging SystemVivek Srinivasan
 
Gate 2020 Electrical Engineering (29 years solution)
Gate 2020 Electrical Engineering (29 years solution)Gate 2020 Electrical Engineering (29 years solution)
Gate 2020 Electrical Engineering (29 years solution)IES Master
 
Lobel proposal for 1 mw crystalline pv solar power plant
Lobel proposal for 1 mw crystalline pv solar power plantLobel proposal for 1 mw crystalline pv solar power plant
Lobel proposal for 1 mw crystalline pv solar power plantL'Obel Solar Power System
 
Automatic Power Factor Detection And Correction using Arduino
Automatic Power Factor Detection And Correction using ArduinoAutomatic Power Factor Detection And Correction using Arduino
Automatic Power Factor Detection And Correction using ArduinoSouvik Dutta
 
The role of energy storage with renewable electricity generation
The role of energy storage with renewable electricity generationThe role of energy storage with renewable electricity generation
The role of energy storage with renewable electricity generationGlenn Klith Andersen
 
assign energy storage COMPLETE
assign energy storage COMPLETEassign energy storage COMPLETE
assign energy storage COMPLETEsteven sweeney
 
FYP Report up to date COMPLETE
FYP Report up to date COMPLETEFYP Report up to date COMPLETE
FYP Report up to date COMPLETEsteven sweeney
 
Design & estimation of rooftop grid tied solar pv system
Design & estimation of rooftop grid tied solar pv systemDesign & estimation of rooftop grid tied solar pv system
Design & estimation of rooftop grid tied solar pv systemSabrina Chowdhury
 
Power Systems analysis with MATPOWER and Simscape Electrical (MATLAB/Simulink)
Power Systems analysis with MATPOWER and Simscape Electrical (MATLAB/Simulink) Power Systems analysis with MATPOWER and Simscape Electrical (MATLAB/Simulink)
Power Systems analysis with MATPOWER and Simscape Electrical (MATLAB/Simulink) Bilal Amjad
 
The bat hat
The bat hatThe bat hat
The bat hatslmnsvn
 
Optimum design and performance for nablus network
Optimum design and performance for nablus networkOptimum design and performance for nablus network
Optimum design and performance for nablus networkslmnsvn
 
Loss of mains protection or anti islanding
Loss of mains protection or anti islandingLoss of mains protection or anti islanding
Loss of mains protection or anti islandingOsama Shahumi
 

Similar to N-2 Substation Switching Study (20)

SEC Final
SEC FinalSEC Final
SEC Final
 
SEC Final
SEC FinalSEC Final
SEC Final
 
AC_Microgrid_Versus_DC_Microgrid_A_Revie.pdf
AC_Microgrid_Versus_DC_Microgrid_A_Revie.pdfAC_Microgrid_Versus_DC_Microgrid_A_Revie.pdf
AC_Microgrid_Versus_DC_Microgrid_A_Revie.pdf
 
EGR-386 proposal S.I.C.with table of content
EGR-386 proposal S.I.C.with table of contentEGR-386 proposal S.I.C.with table of content
EGR-386 proposal S.I.C.with table of content
 
Raffaele Salvucci s111179 Thesis
Raffaele Salvucci s111179 ThesisRaffaele Salvucci s111179 Thesis
Raffaele Salvucci s111179 Thesis
 
FINAL REPORT
FINAL REPORTFINAL REPORT
FINAL REPORT
 
Design of 450W Solar Battery Charging System
Design of 450W Solar Battery Charging SystemDesign of 450W Solar Battery Charging System
Design of 450W Solar Battery Charging System
 
Gate 2020 Electrical Engineering (29 years solution)
Gate 2020 Electrical Engineering (29 years solution)Gate 2020 Electrical Engineering (29 years solution)
Gate 2020 Electrical Engineering (29 years solution)
 
Lobel proposal for 1 mw crystalline pv solar power plant
Lobel proposal for 1 mw crystalline pv solar power plantLobel proposal for 1 mw crystalline pv solar power plant
Lobel proposal for 1 mw crystalline pv solar power plant
 
Automatic Power Factor Detection And Correction using Arduino
Automatic Power Factor Detection And Correction using ArduinoAutomatic Power Factor Detection And Correction using Arduino
Automatic Power Factor Detection And Correction using Arduino
 
The role of energy storage with renewable electricity generation
The role of energy storage with renewable electricity generationThe role of energy storage with renewable electricity generation
The role of energy storage with renewable electricity generation
 
Solar blinds
Solar blindsSolar blinds
Solar blinds
 
assign energy storage COMPLETE
assign energy storage COMPLETEassign energy storage COMPLETE
assign energy storage COMPLETE
 
FYP Report up to date COMPLETE
FYP Report up to date COMPLETEFYP Report up to date COMPLETE
FYP Report up to date COMPLETE
 
Design & estimation of rooftop grid tied solar pv system
Design & estimation of rooftop grid tied solar pv systemDesign & estimation of rooftop grid tied solar pv system
Design & estimation of rooftop grid tied solar pv system
 
Dcgrid2
Dcgrid2Dcgrid2
Dcgrid2
 
Power Systems analysis with MATPOWER and Simscape Electrical (MATLAB/Simulink)
Power Systems analysis with MATPOWER and Simscape Electrical (MATLAB/Simulink) Power Systems analysis with MATPOWER and Simscape Electrical (MATLAB/Simulink)
Power Systems analysis with MATPOWER and Simscape Electrical (MATLAB/Simulink)
 
The bat hat
The bat hatThe bat hat
The bat hat
 
Optimum design and performance for nablus network
Optimum design and performance for nablus networkOptimum design and performance for nablus network
Optimum design and performance for nablus network
 
Loss of mains protection or anti islanding
Loss of mains protection or anti islandingLoss of mains protection or anti islanding
Loss of mains protection or anti islanding
 

N-2 Substation Switching Study

  • 1. A Division of the City of Idaho Falls “A Community with its own kind of energy” N-2 Substation Switching Study Date Author Revision May 18, 2015 Eric Gubler 0 May 20, 2015 Eric Gubler 1 _________________________________________________________________________________________________ PO Box 50220 Phone: 208-612-8430 140 S Capital Ave. Fax: 208-612-8435 Idaho Falls, ID 83405-0220 www.ifpower.org
  • 2. N-2 Substation Switching Study 1 TABLE OF CONTENTS 1.0 Purpose...................................................................................................................................... 3 2.0 Data Sources ............................................................................................................................. 3 3.0 Guidelines and Assumptions..................................................................................................... 3 4.0 Summary................................................................................................................................... 3 5.0 Body/Data ................................................................................................................................. 4 5.1 Scenarios that work.............................................................................................................. 5 5.1.1 Rack & Milligan .......................................................................................................... 5 5.1.2 Rack & Sugarmill ........................................................................................................ 6 5.1.3 Rack & Fifteenth St. .................................................................................................... 7 5.1.4 Rack & Westside.......................................................................................................... 8 5.1.5 Milligan & Sugarmill................................................................................................... 9 5.1.6 Milligan & Fifteenth St.............................................................................................. 10 5.1.7 Milligan & York Road............................................................................................... 11 5.1.8 Milligan & Harrison................................................................................................... 12 5.1.9 Milligan & Hatch....................................................................................................... 13 5.1.10 Milligan & Westside................................................................................................ 14 5.1.11 Sugarmill & Fifteenth St.......................................................................................... 15 5.1.12 Sugarmill & York Road........................................................................................... 16 5.1.13 Sugarmill & Westside.............................................................................................. 17 5.1.14 Fifteenth St. & York Road....................................................................................... 18 5.1.15 Fifteenth St. & Westside.......................................................................................... 19 5.1.16 York Road & Westside............................................................................................ 20 5.1.17 Harrison & Westside................................................................................................ 21 5.1.18 Hatch & Westside .................................................................................................... 22 5.2 Scenarios that work with assumptions............................................................................... 23 5.2.1 Rack & Templeview .................................................................................................. 23 5.2.2 Rack & N. Boulevard................................................................................................. 24 5.2.3 Rack & City ............................................................................................................... 25 5.2.4 Rack & York.............................................................................................................. 26 5.2.5 Rack & Harrison ........................................................................................................ 27 5.2.6 Rack & Hatch............................................................................................................. 28 5.2.7 Milligan & Templeview............................................................................................. 29 5.2.8 Milligan & N. Boulevard........................................................................................... 30
  • 3. N-2 Substation Switching Study 2 5.2.9 Milligan & City.......................................................................................................... 31 5.2.10 Templeview & Sugarmill......................................................................................... 32 5.2.11 Templeview & Fifteenth St...................................................................................... 33 5.2.12 Templeview & City.................................................................................................. 34 5.2.13 Templeview & York Road....................................................................................... 35 5.2.14 Templeview & Harrison .......................................................................................... 36 5.2.15 Templeview & Hatch............................................................................................... 37 5.2.16 Templeview & Westside.......................................................................................... 38 5.2.17 Sugarmill & N. Boulevard....................................................................................... 39 5.2.18 Sugarmill & City...................................................................................................... 40 5.2.19 Fifteenth St. & N. Boulevard................................................................................... 41 5.2.20 Fifteenth St. & City.................................................................................................. 42 5.2.21 Fifteenth St. & Hatch............................................................................................... 43 5.2.22 N. Boulevard & York Road ..................................................................................... 44 5.2.23 N. Boulevard & Harrison......................................................................................... 45 5.2.24 N. Boulevard & Hatch ............................................................................................. 46 5.2.25 N. Boulevard & Westside ........................................................................................ 47 5.2.26 City & York Road.................................................................................................... 48 5.2.27 City & Harrison........................................................................................................ 49 5.2.28 City & Hatch............................................................................................................ 50 5.2.29 City & Westside....................................................................................................... 51 5.2.30 York Road & Harrison............................................................................................. 52 5.2.31 York Road & Hatch ................................................................................................. 53 5.3 Scenarios that do not work................................................................................................. 54 5.3.1 Templeview & N. Boulevard..................................................................................... 54 5.3.2 Sugarmill & Harrison................................................................................................. 54 5.3.3 Sugarmill & Hatch..................................................................................................... 54 5.3.4 Fifteenth St. & Harrison............................................................................................. 54 5.3.5 N. Boulevard & City.................................................................................................. 54 5.3.6 Harrison & Hatch....................................................................................................... 54 6.0 Conclusion .............................................................................................................................. 55
  • 4. N-2 Substation Switching Study 3 1.0 PURPOSE The purpose of this study is to create switching procedures for N-2 type situations. An N-2 situation is when any two substations have failed. This study will determine which N-2 situations can and cannot successfully be handled by the current system. This will indicate weaknesses in the grid and provide meaningful information for future improvements to the grid. Data from the study will be divided into three main categories: (1) scenarios that work, (2) scenarios that work with assumptions, and (3) scenarios that do not work. 2.0 DATA SOURCES Data needed for creating switching procedures was taken from Idaho Falls Power’s AutoCAD drawing, IFP-E102 Rev 4, 12.5KV ONE LINE DIAGRAM. 3.0 GUIDELINES AND ASSUMPTIONS Guidelines and assumptions for the switching procedures were taken from section 4.l of the Load Forecast Study completed by Ben Jenkins, which states: Circuit loads ideally to be less than 8.5MW but shall not be greater than 13MW. Substation loads ideally to be less than 15MW but shall not be greater than 25MW. For many of the switching procedures it is assumed that the aux bus can be used even when the rest of the substation is down. 4.0 SUMMARY Using the current grid, 49 of the 55 possible N-2 type situations may successfully be handled without interruption to power service. However, 31 of the 45 successful situations currently have an assumption that the aux bus can be used in the switching procedure. New connections to Templeview, City, and N. Boulevard’s islanded feeders are needed to remove this dependency. New connections, switches, and upgraded wire ampacity are also needed at critical points in the grid to increase grid stability and provide switching procedures for the remaining N-2 situations that currently cannot be handled.
  • 5. N-2 Substation Switching Study 4 5.0 BODY/DATA The following image is a graphical representation of the switching procedures. Each cell in the table represents one switching procedure. The value in the cell is the combined load, in Megawatts, that needs to be transferred away from the shutdown substations. The color fill of the cell indicates how much power is being transferred away from the substations in the procedure in comparison to other N-2 situations; greener indicates a smaller transfer and redder indicates a larger transfer. The color of the text represents whether the switching procedure can be completed (black text), completed with assumptions (light blue text), or if it cannot be completed (red text). The additional information at the bottom left highlights which substation combinations cannot be completed. RACK SUB-1 MILLIGAN SUB-3 TEMPLEVIEW SUB-4 SUGARMILL SUB-6 FIFTEENTH ST. SUB-9 N. BOULEVARD SUB-12 CITY SUB- 13 YORK ROAD SUB-14 HARRISON SUB-16 HATCH SUB- 17 WESTSIDE SUB-18 RACK SUB-1 26.7 26.3 34.7 31.6 37.8 26.0 27.8 29.7 30.8 24.4 MILLIGAN SUB-3 21.8 30.2 27.1 33.3 21.5 23.3 25.2 26.3 19.9 TEMPLEVIEW SUB-4 29.8 26.7 32.9 21.1 22.9 24.8 25.9 19.5 SUGARMILL SUB-6 35.1 41.3 29.5 31.3 33.2 34.3 27.9 FIFTEENTH ST. SUB-9 38.2 26.4 28.2 30.1 31.2 24.8 N. BOULEVARD SUB-12 32.6 34.4 36.3 37.4 31.0 CITY SUB-13 22.6 24.5 25.6 19.2 YORK ROAD SUB-14 26.3 27.4 21.0 HARRISON SUB-16 29.3 22.9 HATCH SUB-17 24.0 WESTSIDE SUB-18 HARRISON SUGARMILL Switching procedures that work N. BOULEVARD HATCH Switching procedures that work with assumptions TEMPLEVIEW FIFTEENTH ST. Switching procedures that do not work CITY RACK YORK ROAD MILLIGAN WESTSIDE KEY 1 -(N. Boulevard) 3 - (Hatch, Sugarmill, Fifteenth) 2 -(Hatch, Harrison) 2 -(City, Templeview) 2 -(Harrison, Sugarmill) 0 -() 0 -() 0 -() 1 -(Harrison) 0 -() 1 -(N. Boulevard)
  • 6. N-2 Substation Switching Study 5 5.1 Scenarios that work 5.1.1 Rack & Milligan Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H33 CLOSED 4B6-1 0.9 0.0 4B5-3 0.6 0.0 4B2-1 OPEN 4B5-1 7.1 0.0 4B4-3 9.9 0.0 4D85 CLOSED 4B4-1 0.5 0.0 4B3-3 0.6 0.0 4B3-1 OPEN 4B3-1 6.2 0.0 4H52 CLOSED 4B2-1 0.9 0.0 4B4-1 OPEN Transformer Total 15.6 0.0 Transformer Total 11.1 0.0 4H16 CLOSED 4H3 OPEN 4H10 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B5-1 OPEN 4B2-9 7.8 7.8 4B2-4 7.7 11.8 4H53 CLOSED 4B3-9 8.2 12.1 4B3-4 0.6 0.6 4B6-1 OPEN 4B4-4 2.4 2.4 4D18 CLOSED 4R5 OPEN 4D24 CLOSED Transformer Total 16.0 19.9 Transformer Total 10.7 14.8 4D29 OPEN 4H46 CLOSED 4B1-3 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-18 8.8 11.7 4B3-14 0.7 1.6 Switching Description: 4B4-14 6.8 6.8 4B5-14 0.0 0.0 4B6-14 2.9 3.8 4B7-14 1.8 8.0 Transformer Total 8.8 11.7 Transformer Total 12.2 20.2 Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-13 2.1 2.1 4B3-13 3.9 8.5 4B4-13 4.4 7.6 Transformer Total 10.4 18.2 4B2-14B3-14B4-14B5-14B6-1 WESTSIDE BREAKERS YORK ROAD BREAKERS CITY BREAKERS SWITCHING PROCEDURE RACK BREAKERS MILLIGAN BREAKERS FIFTEENTH ST. BREAKERS TEMPLEVIEW BREAKERS 4B5-3,4B4-3,&4B3-3 4B2-1 transferring to 4B6-14 4B3-1 transferring to 4B7-14 4B4-1 transferring to 4B3-18 4B4-13 taking load off of 4B3-9 4B5-1 transferring to 4B3-9 4B6-1 transferring to 4B3-14 4B2-4 taking load off of 4B4-3 4B3-18 taking load off of 4B4-3 4B3-3 transferring to 4B3-13 4B4-3 transferring to 4B3-13 4B5-3 transferring to 4B3-13
  • 7. N-2 Substation Switching Study 6 5.1.2 Rack & Sugarmill Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H33 CLOSED 4B6-1 0.9 0.0 4B2-6 7.6 0.0 4B2-1 OPEN 4B5-1 7.1 0.0 4B3-6 6.8 0.0 4H20 CLOSED 4B4-1 0.5 0.0 4B4-6 4.7 0.0 4D52 OPEN 4B3-1 6.2 0.0 4D85 CLOSED 4B2-1 0.9 0.0 4B3-1 OPEN Transformer Total 15.6 0.0 Transformer Total 19.1 0.0 4H36 CLOSED 4B4-1 OPEN 4H16 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H3 OPEN 4B5-3 0.6 1.1 4B2-13 2.1 2.1 4H10 CLOSED 4B4-3 9.9 9.9 4B3-13 3.9 3.9 4B5-1 OPEN 4B3-3 0.6 0.6 4B4-13 4.4 10.4 4H53 CLOSED 4B6-1 OPEN 4H58 CLOSED Transformer Total 11.1 11.6 Transformer Total 10.4 16.4 4H55 OPEN 4H45 CLOSED 4H45 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H5 CLOSED 4B2-16 2.2 2.2 4B4-17 12.0 9.8 4B2-6 OPEN 4B3-16 6.7 11.4 4B3-17 1.0 4.5 4H26 CLOSED 4B4-16 4.6 8.0 4B2-17 2.2 9.0 4S8 OPEN 4B5-16 0.6 0.6 4H49 CLOSED 4B3-6 OPEN Transformer Total 14.1 22.2 Transformer Total 15.2 23.3 4H21 CLOSED 4B4-6 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) Switching Description: 4B3-14 0.7 1.6 4B2-9 7.8 7.8 4B4-14 6.8 6.8 4B3-9 8.2 12.1 4B5-14 0.0 0.0 4B6-14 2.9 3.8 4B7-14 1.8 6.8 Transformer Total 12.2 19.0 Transformer Total 16.0 19.9 Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-12 11.0 12.3 4B2-12 2.1 2.1 Transformer Total 13.1 14.4 4B3-64B4-6 4B2-1 transferring to 4B6-14 4B3-1 transferring to 4B4-16 & 4B7- 14 4B4-1 transferring to 4B5-3 4B4-13 taking load off of 4B3-9 4B5-1 transferring to 4B3-9 4B6-1 transferring to 4B3-14 4B4-13 taking load off of 4B3-12 4B3-12 taking load off of 4B2-6 4B2-6 transferring to 4B3-17 4B4-16 taking load off of 4B4-17 4B3-6 transferring to 4B2-17 4B4-6 transferring to 4B3-16 HARRISON BREAKERS HATCH BREAKERS YORK ROAD BREAKERS FIFTEENTH ST. BREAKERS N. BOULEVARD 5T1-12 BREAKERS 4B6-14B5-14B2-6 SWITCHING PROCEDURE RACK BREAKERS SUGARMILL BREAKERS MILLIGAN BREAKERS CITY BREAKERS 4B2-14B3-14B4-1
  • 8. N-2 Substation Switching Study 7 5.1.3 Rack & Fifteenth St. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H33 CLOSED 4B6-1 0.9 0.0 4B2-9 7.8 0.0 4B2-1 OPEN 4B5-1 7.1 0.0 4B3-9 8.2 0.0 4D85 CLOSED 4B4-1 0.5 0.0 4B3-1 OPEN 4B3-1 6.2 0.0 4H52 CLOSED 4B2-1 0.9 0.0 4B4-1 OPEN Transformer Total 15.6 0.0 Transformer Total 16.0 0.0 4H20 CLOSED 4D52 OPEN 4H30 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H50 OPEN 4B2-16 2.2 2.2 4B3-18 8.8 9.3 4H51 CLOSED 4B3-16 6.7 8.2 4B5-1 OPEN 4B4-16 4.6 11.6 4H53 CLOSED 4B5-16 0.6 0.6 4B6-1 OPEN 4H11 CLOSED Transformer Total 14.1 22.6 Transformer Total 8.8 9.3 4H22 OPEN 4H12 CLOSED 4D39 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H26 CLOSED 4B2-13 2.1 2.1 4B3-14 0.7 1.6 4S8 OPEN 4B3-13 3.9 9.5 4B4-14 6.8 6.8 4H49 CLOSED 4B4-13 4.4 7.0 4B5-14 0.0 0.0 4H42 OPEN 4B6-14 2.9 3.8 4D16 CLOSED 4B7-14 1.8 12.5 4H40 OPEN Transformer Total 10.4 18.6 Transformer Total 12.2 24.7 4H34 CLOSED 4B2-9 OPEN 4H16 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H19 OPEN 4B4-17 12.0 6.2 4B2-6 7.6 7.6 4H8 CLOSED 4B3-17 1.0 1.0 4B3-6 6.8 0.2 4B3-9 OPEN 4B2-17 2.2 8.8 4B4-6 4.7 12.4 Switching Description: Transformer Total 15.2 16.0 Transformer Total 19.1 20.2 SWITCHING PROCEDURE RACK BREAKERS FIFTEENTH ST. BREAKERS 4B2-1 SUGARMILL BREAKERS 4B3-14B2-94B3-9 4B2-1 transferring to 4B6-14 4B3-1 transferring to 4B7-14 4B4-1 transferring to 4B3-18 4B4-16 taking load off of 4B7-14 4B2-9 taking load off of 4B5-1 4B5-1 transferring to 4B7-14 4B6-1 transferring to 4B3-14 4B3-16 taking load off of 4B4-16 4B4-16 taking load off of 4B2-9 4B4-16 taking load off of 4B4-17 4B2-17 taking load off of 4B3-6 4B4-6 taking load off of 4B4-17 4B2-9 transferring to 4B4-6 4B4-13 taking load off of 4B3-9 4B3-9 transferring to 4B3-13 4B6-14B4-1 HARRISON BREAKERS WESTSIDE BREAKERS CITY BREAKERS YORK ROAD BREAKERS 4B5-1 HATCH BREAKERS
  • 9. N-2 Substation Switching Study 8 5.1.4 Rack & Westside Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H33 CLOSED 4B6-1 0.9 0.0 4B3-18 8.8 0.0 4B2-1 OPEN 4B5-1 7.1 0.0 4D85 CLOSED 4B4-1 0.5 0.0 4B3-1 OPEN 4B3-1 6.2 0.0 4H36 CLOSED 4B2-1 0.9 0.0 4B4-1 OPEN Transformer Total 15.6 0.0 Transformer Total 8.8 0.0 4H8 CLOSED 4H3 OPEN 4H10 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B5-1 OPEN 4B3-14 0.7 1.6 4B5-3 0.6 9.9 4H53 CLOSED 4B4-14 6.8 6.8 4B4-3 9.9 9.9 4B6-1 OPEN 4B5-14 0.0 0.0 4B3-3 0.6 0.6 4H52 CLOSED 4B6-14 2.9 3.8 4B3-18 OPEN 4B7-14 1.8 8.0 Transformer Total 12.2 20.2 Transformer Total 11.1 20.4 Switching Description: Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-13 2.1 2.1 4B2-9 7.8 7.8 4B3-13 3.9 7.1 4B3-9 8.2 12.1 4B4-13 4.4 4.4 Transformer Total 10.4 13.6 Transformer Total 16.0 19.9 MILLIGAN BREAKERS 4B6-1 CITY BREAKERS FIFTEENTH ST. BREAKERS SWITCHING PROCEDURE RACK BREAKERS WESTSIDE BREAKERS 4B2-14B3-14B3-184B4-14B5-1 YORK ROAD BREAKERS 4B2-1 transferring to 4B6-14 4B3-1 transferring to 4B7-14 4B4-1 transferring to 4B5-3 4B3-13 taking load off of 4B3-9 4B5-1 transferring to 4B3-9 4B6-1 transferring to 4B3-14 4B3-18 transferring to 4B5-3
  • 10. N-2 Substation Switching Study 9 5.1.5 Milligan & Sugarmill Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H46 CLOSED 4B5-3 0.6 0.0 4B2-6 7.6 0.0 4B3-3 OPEN 4B4-3 9.9 0.0 4B3-6 6.8 0.0 4D18 CLOSED 4B3-3 0.6 0.0 4B4-6 4.7 0.0 4D46 OPEN 4D24 CLOSED 4D40 OPEN Transformer Total 11.1 0.0 Transformer Total 19.1 0.0 4H36 CLOSED 4B1-3 OPEN 4H5 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-6 OPEN 4B2-4 7.7 9.8 4B6-1 0.9 0.9 4H7 CLOSED 4B3-4 0.6 0.6 4B5-1 7.1 7.1 4H43 OPEN 4B4-4 2.4 2.4 4B4-1 0.5 6.4 4H26 CLOSED 4B3-1 6.2 6.2 4S8 OPEN 4B2-1 0.9 0.9 4H34 CLOSED Transformer Total 10.7 12.8 Transformer Total 15.6 21.5 4H40 OPEN 4H49 CLOSED 4B3-6 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H21 CLOSED 4B2-13 2.1 2.1 4B2-9 7.8 11.4 4B4-6 OPEN 4B3-13 3.9 4.5 4B3-9 8.2 11.2 4B4-13 4.4 4.4 Switching Description: Transformer Total 10.4 11.0 Transformer Total 16.0 22.6 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-17 12.0 3.2 4B2-16 2.2 2.2 4B3-17 1.0 8.6 4B3-16 6.7 11.4 4B2-17 2.2 9.0 4B4-16 4.6 6.8 4B5-16 0.6 0.6 Transformer Total 15.2 20.8 Transformer Total 14.1 21.0 Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-18 8.8 11.3 Transformer Total 8.8 11.3 FIFTEENTH ST. BREAKERS 4B3-3 transferring to 4B3-13 4B2-4 taking load off of 4B4-3 4B3-18 taking load off of 4B4-3 4B4-3 powered through 4B5-3 4B5-3 transferring to 4B4-1 4B2-6 transferring to 4B3-17 4B3-9 taking load off of 4B4-17 4B4-16 taking load off of 4B4-17 4B2-9 taking load off of 4B4-17 4B3-6 transferring to 4B2-17 4B4-6 transferring to 4B3-16 HATCH BREAKERS HARRISON BREAKERS SWITCHING PROCEDURE MILLIGAN BREAKERS SUGARMILL BREAKERS 4B3-34B5-3&4B4-3 TEMPLEVIEW BREAKERS RACK BREAKERS WESTSIDE BREAKERS 4B2-64B3-64B4-6 CITY BREAKERS
  • 11. N-2 Substation Switching Study 10 5.1.6 Milligan & Fifteenth St. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H46 CLOSED 4B5-3 0.6 0.0 4B2-9 7.8 0.0 4B3-3 OPEN 4B4-3 9.9 0.0 4B3-9 8.2 0.0 4D18 CLOSED 4B3-3 0.6 0.0 4D46 OPEN 4D24 CLOSED 4D40 OPEN Transformer Total 11.1 0.0 Transformer Total 16.0 0.0 4H36 CLOSED 4B1-3 OPEN 4H20 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4D52 OPEN 4B2-4 7.7 9.8 4B6-1 0.9 0.9 4H12 CLOSED 4B3-4 0.6 0.6 4B5-1 7.1 7.1 4D12 OPEN 4B4-4 2.4 2.4 4B4-1 0.5 6.4 4D85 CLOSED 4B3-1 6.2 3.9 4D73 OPEN 4B2-1 0.9 0.9 4H13 CLOSED Transformer Total 10.7 12.8 Transformer Total 15.6 19.2 4B2-9 OPEN 4H16 CLOSED 4H19 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H8 CLOSED 4B2-13 2.1 2.1 4B3-18 8.8 11.3 4B3-9 OPEN 4B3-13 3.9 10.1 4B4-13 4.4 7.0 Switching Description: Transformer Total 10.4 19.2 Transformer Total 8.8 11.3 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-14 0.7 0.7 4B2-16 2.2 2.2 4B4-14 6.8 6.8 4B3-16 6.7 6.7 4B5-14 0.0 0.0 4B4-16 4.6 7.0 4B6-14 2.9 2.9 4B5-16 0.6 0.6 4B7-14 1.8 9.5 Transformer Total 12.2 19.9 Transformer Total 14.1 16.5 4B3-94B2-9 CITY BREAKERS WESTSIDE BREAKERS YORK ROAD BREAKERS HARRISON BREAKERS 4B3-3 transferring to 4B3-13 4B2-4 taking load off of 4B4-3 4B3-18 taking load off of 4B4-3 4B4-3 powered through 4B5-3 4B5-3 transferring to 4B4-1 4B4-16 taking load off of 4B3-1 4B4-16 taking load off of 4B2-9 4B7-14 taking load off of 4B3-1 4B2-9 transferring to 4B7-14 4B4-13 taking load off of 4B3-9 4B3-9 transferring to 4B3-13 4B5-3&4B4-3 TEMPLEVIEW BREAKERS RACK BREAKERS SWITCHING PROCEDURE MILLIGAN BREAKERS FIFTEENTH ST. BREAKERS 4B3-3
  • 12. N-2 Substation Switching Study 11 5.1.7 Milligan & York Road Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4D18 CLOSED 4B5-3 0.6 0.0 4B3-14 0.7 0.0 4D46 OPEN 4B4-3 9.9 0.0 4B4-14 6.8 0.0 4D24 CLOSED 4B3-3 0.6 0.0 4B5-14 0.0 0.0 4D40 OPEN 4B6-14 2.9 0 4H46 CLOSED 4B7-14 1.8 0 4B1-3 OPEN Transformer Total 11.1 0.0 Transformer Total 12.2 0.0 4H53 CLOSED 4B3-14 OPEN 4D51 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-14 OPEN 4B2-4 7.7 9.8 4B6-1 0.9 1.6 4B5-14 4B5-14 OPEN 4B3-4 0.6 0.6 4B5-1 7.1 7.1 4H20 CLOSED 4B4-4 2.4 2.4 4B4-1 0.5 0.5 4H27 OPEN 4B3-1 6.2 0.6 4H33 CLOSED 4B2-1 0.9 10.6 4B6-14 OPEN Transformer Total 10.7 12.8 Transformer Total 15.6 20.4 4D85 CLOSED 4B7-14 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) Switching Description: 4B2-13 2.1 2.1 4B3-18 8.8 11.3 4B3-13 3.9 10.4 4B4-13 4.4 4.4 Transformer Total 10.4 16.9 Transformer Total 8.8 11.3 Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-16 2.2 2.2 4B3-16 6.7 6.7 4B4-16 4.6 12.0 4B5-16 0.6 0.6 Transformer Total 14.1 21.5 4B7-144B6-14 CITY BREAKERS WESTSIDE BREAKERS 4B2-4 taking load off of 4B4-3 4B3-18 taking load off of 4B4-3 4B5-3 powered through 4B3-3 4B4-3 powered through 4B3-3 4B3-3 transferring to 4B3-13 4B3-14 transferring to 4B6-1 4B4-14 transferring to 4B6-14 4B5-14 shut off 4B4-16 taking load off of 4B3-1 4B6-14 transferring to 4B2-1 4B7-14 transferring to 4B4-16 HARRISON BREAKERS 4B4-14 SWITCHING PROCEDURE MILLIGAN BREAKERS YORK ROAD BREAKERS TEMPLEVIEW BREAKERS RACK BREAKERS 4B5-3,4B4-3,&4B3-34B3-14
  • 13. N-2 Substation Switching Study 12 5.1.8 Milligan & Harrison Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4D18 CLOSED 4B5-3 0.6 0.0 4B2-16 2.2 0.0 4D46 OPEN 4B4-3 9.9 0.0 4B3-16 6.7 0.0 4D24 CLOSED 4B3-3 0.6 0.0 4B4-16 4.6 0.0 4D40 OPEN 4B5-16 0.6 0 4H46 CLOSED Transformer Total 11.1 0.0 Transformer Total 14.1 0.0 4B1-3 OPEN 4D85 CLOSED 4D72 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H7 CLOSED 4B2-4 7.7 9.8 4B6-1 0.9 0.9 4H43 OPEN 4B3-4 0.6 0.6 4B5-1 7.1 7.1 4H49 CLOSED 4B4-4 2.4 2.4 4B4-1 0.5 0.5 4H42 OPEN 4B3-1 6.2 12.2 4D13 CLOSED 4B2-1 0.9 0.9 4B2-16 OPEN Transformer Total 10.7 12.8 Transformer Total 15.6 21.6 4H21 CLOSED 4B3-16 OPEN 4H20 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-16 OPEN 4B2-13 2.1 2.1 4B2-6 7.6 7.6 4D54 CLOSED 4B3-13 3.9 10.4 4B3-6 6.8 0.2 4B5-16 OPEN 4B4-13 4.4 4.4 4B4-6 4.7 12.0 Transformer Total 10.4 16.9 Transformer Total 19.1 19.8 Switching Description: Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-14 0.7 0.7 4B2-9 7.8 7.8 4B4-14 6.8 6.8 4B3-9 8.2 11.2 4B5-14 0.0 0.0 4B6-14 2.9 2.9 4B7-14 1.8 2.6 Transformer Total 12.2 13.0 Transformer Total 16.0 19.0 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-18 8.8 11.3 4B4-17 12.0 9.0 4B3-17 1.0 1.0 4B2-17 2.2 8.8 Transformer Total 8.8 11.3 Transformer Total 15.2 18.8 4B3-164B4-164B5-164B2-16 CITY BREAKERS SUGARMILL BREAKERS 4B2-4 taking load off of 4B4-3 4B3-18 taking load off of 4B4-3 4B5-3 powered through 4B3-3 4B4-3 powered through 4B3-3 4B3-3 transferring to 4B3-13 4B7-14 taking load off of 4B3-1 4B3-9 taking load off of 4B4-17 4B2-17 taking load off of 4B3-6 4B2-16 transferring to 4B4-16 4B3-16 transferring to 4B4-6 4B4-16 transferring to 4B3-1 4B5-16 transferring to 4B4-6 YORK ROAD BREAKERS FIFTEENTH ST. BREAKERS WESTSIDE BREAKERS HATCH BREAKERS SWITCHING PROCEDURE MILLIGAN BREAKERS HARRISON BREAKERS TEMPLEVIEW BREAKERS RACK BREAKERS 4B5-3,4B4-3,&4B3-3
  • 14. N-2 Substation Switching Study 13 5.1.9 Milligan & Hatch Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4D18 CLOSED 4B5-3 0.6 0.0 4B4-17 12.0 0.0 4D46 OPEN 4B4-3 9.9 0.0 4B3-17 1.0 0.0 4D24 CLOSED 4B3-3 0.6 0.0 4B2-17 2.2 0.0 4D40 OPEN 4H46 CLOSED 4B1-3 OPEN Transformer Total 11.1 0.0 Transformer Total 15.2 0.0 4H49 CLOSED 4B2-17 OPEN 4H5 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-17 OPEN 4B2-4 7.7 9.8 4B6-1 0.9 0.9 4H13 CLOSED 4B3-4 0.6 0.6 4B5-1 7.1 7.1 4H47 OPEN 4B4-4 2.4 2.4 4B4-1 0.5 0.5 4H16 CLOSED 4B3-1 6.2 9.9 4H3 OPEN 4B2-1 0.9 0.9 4H26 CLOSED Transformer Total 10.7 12.8 Transformer Total 15.6 19.3 4S8 OPEN 4H34 CLOSED 4D69 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H7 CLOSED 4B2-13 2.1 2.1 4B2-6 7.6 8.6 4B4-17 OPEN 4B3-13 3.9 10.4 4B3-6 6.8 9.0 4B4-13 4.4 7.6 4B4-6 4.7 4.7 Switching Description: Transformer Total 10.4 20.1 Transformer Total 19.1 22.3 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-16 2.2 2.2 4B2-9 7.8 9.3 4B3-16 6.7 6.7 4B3-9 8.2 9.6 4B4-16 4.6 6.8 4B5-16 0.6 0.6 Note: Transformer Total 14.1 16.3 Transformer Total 16.0 18.9 Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-18 8.8 11.3 Transformer Total 8.8 11.3 FIFTEENTH ST. BREAKERS WESTSIDE BREAKERS Upgrading the 336 ACSR wire between 4S8 and 4H20 would simplify the switching procedure. CITY BREAKERS SUGARMILL BREAKERS 4B2-4 taking load off of 4B4-3 4B3-18 taking load off of 4B4-3 4B5-3 powered through 4B3-3 4B4-3 powered through 4B3-3 4B3-3 transferring to 4B3-13 4B3-1 taking load off of 4B2-9 4B4-13 taking load off of 4B3-9 4B4-17 transferring to 4B2-9, 4B3-9, & 4B4-16 4B2-17 transferring to 4B3-6 4B3-17 transferring to 4B2-6 HARRISON BREAKERS SWITCHING PROCEDURE MILLIGAN BREAKERS HATCH BREAKERS 4B5-3,4B4-3,&4B3-3 TEMPLEVIEW BREAKERS RACK BREAKERS 4B2-174B3-174B4-17
  • 15. N-2 Substation Switching Study 14 5.1.10 Milligan & Westside Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4D18 CLOSED 4B5-3 0.6 0.0 4B3-18 8.8 0.0 4D46 OPEN 4B4-3 9.9 0.0 4D24 CLOSED 4B3-3 0.6 0.0 4D40 OPEN 4H46 CLOSED 4B1-3 OPEN Transformer Total 11.1 0.0 Transformer Total 8.8 0.0 4D85 CLOSED 4H27 OPEN 4H52 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-18 OPEN 4B2-4 7.7 9.8 4B6-1 0.9 0.9 4B3-4 0.6 0.6 4B5-1 7.1 7.1 Switching Description: 4B4-4 2.4 2.4 4B4-1 0.5 11.8 4B3-1 6.2 0.6 4B2-1 0.9 0.9 Transformer Total 10.7 12.8 Transformer Total 15.6 21.3 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-13 2.1 2.1 4B3-14 0.7 0.7 4B3-13 3.9 10.4 4B4-14 6.8 6.8 4B4-13 4.4 4.4 4B5-14 0.0 0.0 4B6-14 2.9 2.9 4B7-14 1.8 7.4 Transformer Total 10.4 16.9 Transformer Total 12.2 17.8 4B2-4 taking load off of 4B4-3 4B3-18 taking load off of 4B4-3 4B5-3 powered through 4B3-3 4B4-3 powered through 4B3-3 4B3-3 transferring to 4B3-13 4B7-14 taking load off of 4B3-1 4B3-18 transferring to 4B4-1 CITY BREAKERS YORK ROAD BREAKERS 4B3-18 TEMPLEVIEW BREAKERS RACK BREAKERS SWITCHING PROCEDURE MILLIGAN BREAKERS WESTSIDE BREAKERS 4B5-3,4B4-3,&4B3-3
  • 16. N-2 Substation Switching Study 15 5.1.11 Sugarmill & Fifteenth St. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H16 CLOSED 4B2-6 7.6 0.0 4B2-9 7.8 0.0 4H3 OPEN 4B3-6 6.8 0.0 4B3-9 8.2 0.0 4H58 CLOSED 4B4-6 4.7 0.0 4H55 OPEN 4H45 CLOSED 4H4 OPEN Transformer Total 19.1 0.0 Transformer Total 16.0 0.0 4H5 CLOSED 4B2-6 OPEN 4H26 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4S8 OPEN 4B2-16 2.2 2.2 4B6-1 0.9 0.9 4H49 CLOSED 4B3-16 6.7 11.4 4B5-1 7.1 12.1 4B3-6 OPEN 4B4-16 4.6 6.8 4B4-1 0.5 0.5 4H21 CLOSED 4B5-16 0.6 0.6 4B3-1 6.2 3.9 4B4-6 OPEN 4B2-1 0.9 0.9 4D85 CLOSED Transformer Total 14.1 21.0 Transformer Total 15.6 18.3 4D73 OPEN 4H13 CLOSED 4B2-9 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H10 CLOSED 4B4-12 0.0 0.0 4B3-14 0.7 0.7 4B3-9 OPEN 4B3-12 11.0 12.3 4B4-14 6.8 6.8 4B2-12 2.1 2.1 4B5-14 0.0 0.0 Switching Description: 4B6-14 2.9 2.9 4B7-14 1.8 11.9 Transformer Total 13.1 14.4 Transformer Total 12.2 22.3 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-17 12.0 9.8 4B2-13 2.1 2.1 4B3-17 1.0 4.5 4B3-13 3.9 3.9 4B2-17 2.2 9.0 4B4-13 4.4 10.4 Transformer Total 15.2 23.3 Transformer Total 10.4 16.4 N. BOULEVARD 5T1-12 BREAKERS YORK ROAD BREAKERS CITY BREAKERS 4B2-64B3-64B4-64B2-94B3-9 HARRISON BREAKERS RACK BREAKERS 4B4-13 taking load off of 4B3-9 4B4-13 taking load off of 4B3-12 4B3-12 taking load off of 4B2-6 4B2-6 transferring to 4B3-17 4B4-16 taking load off of 4B4-17 4B3-6 transferring to 4B2-17 4B4-6 transferring to 4B3-16 4B7-14 taking load off of 4B3-1 4B2-9 transferring to 4B7-14 4B3-9 transferring to 4B5-1 SWITCHING PROCEDURE SUGARMILL BREAKERS FIFTEENTH ST. BREAKERS HATCH BREAKERS
  • 17. N-2 Substation Switching Study 16 5.1.12 Sugarmill & York Road Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H5 CLOSED 4B2-6 7.6 0.0 4B3-14 0.7 0.0 4B2-6 OPEN 4B3-6 6.8 0.0 4B4-14 6.8 0.0 4H7 CLOSED 4B4-6 4.7 0.0 4B5-14 0.0 0.0 4H43 OPEN 4B6-14 2.9 0.0 4H26 CLOSED 4B7-14 1.8 0.0 4S8 OPEN Transformer Total 19.1 0.0 Transformer Total 12.2 0.0 4H34 CLOSED 4H40 OPEN 4H49 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-6 OPEN 4B6-1 0.9 1.6 4B2-16 2.2 2.2 4H21 CLOSED 4B5-1 7.1 7.1 4B3-16 6.7 11.4 4B4-6 OPEN 4B4-1 0.5 0.0 4B4-16 4.6 6.8 4H53 CLOSED 4B3-1 6.2 8.0 4B5-16 0.6 0.6 4B3-14 OPEN 4B2-1 0.9 0.0 4D51 CLOSED Transformer Total 15.6 16.7 Transformer Total 14.1 21.0 4B4-14 OPEN 4B5-14 4B5-14 OPEN 4H36 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-1 OPEN 4B2-9 7.8 7.8 4B4-17 12.0 6.8 4H4-1 CLOSED 4B3-9 8.2 11.2 4B3-17 1.0 8.6 4H2-1 CLOSED 4B2-17 2.2 9.0 4B2-1 OPEN 4H33 CLOSED 4B6-14 OPEN Transformer Total 16.0 19.0 Transformer Total 15.2 24.4 4D85 CLOSED 4B7-14 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Switching Description: 4B5-3 0.6 11.7 4B4-3 9.9 9.9 4B3-3 0.6 0.6 Transformer Total 11.1 22.2 HATCH BREAKERS SWITCHING PROCEDURE SUGARMILL BREAKERS YORK ROAD BREAKERS RACK BREAKERS HARRISON BREAKERS 4B3-64B4-64B2-6 FIFTEENTH ST. BREAKERS MILLIGAN BREAKERS 4B2-6 transferring to 4B3-17 4B3-9 taking load off of 4B4-17 4B4-16 taking load off of 4B4-17 4B2-9 taking load off of 4B4-17 4B3-6 transferring to 4B2-17 4B4-6 transferring to 4B3-16 4B3-14 transferring to 4B6-1 4B4-14 transferring to 4B6-14 4B5-14 shut off 4B4-1 transferring to 4B5-3 4B2-1 transferring to 4B5-3 4B6-14 transferring to 4B5-3 4B7-14 transferring to 4B3-1 4B3-144B4-144B6-144B7-14
  • 18. N-2 Substation Switching Study 17 5.1.13 Sugarmill & Westside Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H5 CLOSED 4B2-6 7.6 0.0 4B3-18 8.8 0.0 4B2-6 OPEN 4B3-6 6.8 0.0 4H26 CLOSED 4B4-6 4.7 0.0 4S8 OPEN 4H34 CLOSED 4H40 OPEN Transformer Total 19.1 0.0 Transformer Total 8.8 0.0 4H7 CLOSED 4H43 OPEN 4H49 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-6 OPEN 4B6-1 0.9 0.9 4B2-9 7.8 11.4 4H21 CLOSED 4B5-1 7.1 7.1 4B3-9 8.2 11.2 4B4-6 OPEN 4B4-1 0.5 0.0 4H36 CLOSED 4B3-1 6.2 6.2 4D17 OPEN 4B2-1 0.9 0.9 4H52 CLOSED Transformer Total 15.6 15.1 Transformer Total 16.0 22.6 4B3-18 OPEN Switching Description: Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B5-3 0.6 9.9 4B2-16 2.2 2.2 4B4-3 9.9 9.9 4B3-16 6.7 11.4 4B3-3 0.6 0.6 4B4-16 4.6 6.8 4B5-16 0.6 0.6 Transformer Total 11.1 20.4 Transformer Total 14.1 21.0 Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-17 12.0 3.2 4B3-17 1.0 8.6 4B2-17 2.2 9.0 Transformer Total 15.2 20.8 HATCH BREAKERS 4B3-64B4-64B3-18 RACKBREAKERS FIFTEENTH ST. BREAKERS 4B2-6 transferring to 4B3-17 4B4-16 taking load off of 4B4-17 4B2-9 taking load off of 4B4-17 4B3-9 taking load off of 4B4-17 4B3-6 transferring to 4B2-17 4B4-6 transferring to 4B3-16 4B5-3 taking load off of 4B4-1 4B3-18 transferring to 4B5-3 MILLIGAN BREAKERS HARRISON BREAKERS SWITCHING PROCEDURE SUGARMILL BREAKERS WESTSIDE BREAKERS 4B2-6
  • 19. N-2 Substation Switching Study 18 5.1.14 Fifteenth St. & York Road Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4D85 CLOSED 4B2-9 7.8 0.0 4B3-14 0.7 0.0 4D72 OPEN 4B3-9 8.2 0.0 4B4-14 6.8 0.0 4H26 CLOSED 4B5-14 0.0 0.0 4S8 OPEN 4B6-14 2.9 0.0 4H20 CLOSED 4B7-14 1.8 0.0 4D73 OPEN Transformer Total 16.0 0.0 Transformer Total 12.2 0.0 4H12 CLOSED 4H47 OPEN 4H9 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H44 OPEN 4B6-1 0.9 1.6 4B4-12 0.0 0.0 4H45 CLOSED 4B5-1 7.1 5.7 4B3-12 11.0 11.8 4H4 OPEN 4B4-1 0.5 0.5 4B2-12 2.1 2.1 4D16 CLOSED 4B3-1 6.2 6.5 4H40 OPEN 4B2-1 0.9 10.6 4H34 CLOSED Transformer Total 15.6 24.9 Transformer Total 13.1 13.9 4B2-9 OPEN 4H49 CLOSED 4H42 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H28 CLOSED 4B2-6 7.6 3.5 4B4-17 12.0 11.0 4D69 OPEN 4B3-6 6.8 0.2 4B3-17 1.0 1.0 4H8 CLOSED 4B4-6 4.7 12.4 4B2-17 2.2 10.4 4H3 OPEN 4H7 CLOSED 4B3-9 OPEN Transformer Total 19.1 16.1 Transformer Total 15.2 22.4 4H53 CLOSED 4B3-14 OPEN 4D51 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-14 OPEN 4B2-16 2.2 2.2 4B2-13 2.1 2.1 4B5-14 4B5-14 OPEN 4B3-16 6.7 6.7 4B3-13 3.9 7.1 4H33 CLOSED 4B4-16 4.6 12.0 4B4-13 4.4 7.7 4B6-14 OPEN 4B5-16 0.6 0.6 4H10 CLOSED 4H50 OPEN Transformer Total 14.1 21.5 Transformer Total 10.4 16.9 4D59 CLOSED 4B7-14 OPEN RACK BREAKERS N. BOULEVARD 5T1-12 BREAKERS SWITCHING PROCEDURE FIFTEENTH ST. BREAKERS YORK ROAD BREAKERS 4B2-9 SUGARMILL BREAKERS HATCH BREAKERS HARRISON BREAKERS CITY BREAKERS 4B4-144B6-144B7-144B3-94B3-14
  • 20. N-2 Substation Switching Study 19 5.1.15 Fifteenth St. & Westside Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H20 CLOSED 4B2-9 7.8 0.0 4B3-18 8.8 0.0 4D52 OPEN 4B3-9 8.2 0.0 4H12 CLOSED 4D12 OPEN 4H13 CLOSED 4B2-9 OPEN Transformer Total 16.0 0.0 Transformer Total 8.8 0.0 4H16 CLOSED 4H19 OPEN 4H8 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-9 OPEN 4B6-1 0.9 0.9 4B2-13 2.1 2.1 4H36 CLOSED 4B5-1 7.1 7.1 4B3-13 3.9 9.5 4D17 OPEN 4B4-1 0.5 0.0 4B4-13 4.4 7.0 4H52 CLOSED 4B3-1 6.2 11.6 4B3-18 OPEN 4B2-1 0.9 0.9 Transformer Total 15.6 20.5 Transformer Total 10.4 18.6 Switching Description: Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-16 2.2 2.2 4B5-3 0.6 9.9 4B3-16 6.7 6.7 4B4-3 9.9 9.9 4B4-16 4.6 7.0 4B3-3 0.6 0.6 4B5-16 0.6 0.6 Transformer Total 14.1 16.5 Transformer Total 11.1 20.4 MILLIGAN BREAKERS4B4-16 taking load off of 4B3-1 4B4-16 taking load off of 4B2-9 4B2-9 transferring to 4B3-1 4B4-13 taking load off of 4B3-9 4B3-9 transferring to 4B3-13 4B5-3 taking load off of 4B4-1 4B3-18 transferring to 4B5-3 SWITCHING PROCEDURE FIFTEENTH ST. BREAKERS WESTSIDE BREAKERS RACK BREAKERS CITY BREAKERS 4B2-94B3-94B3-18 HARRISON BREAKERS
  • 21. N-2 Substation Switching Study 20 5.1.16 York Road & Westside Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H53 CLOSED 4B3-14 0.7 0.0 4B3-18 8.8 0.0 4B3-14 OPEN 4B4-14 6.8 0.0 4D51 CLOSED 4B5-14 0.0 0.0 4B4-14 OPEN 4B6-14 2.9 0.0 4B5-14 4B5-14 OPEN 4B7-14 1.8 0.0 4H33 CLOSED Transformer Total 12.2 0.0 Transformer Total 8.8 0.0 4B6-14 OPEN 4H20 CLOSED 4H27 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4D85 CLOSED 4B2-16 2.2 2.2 4B5-3 0.6 9.9 4B7-14 OPEN 4B3-16 6.7 6.7 4B4-3 9.9 9.9 4H36 CLOSED 4B4-16 4.6 12.0 4B3-3 0.6 0.6 4D17 OPEN 4B5-16 0.6 0.6 4H52 CLOSED 4B3-18 OPEN Transformer Total 14.1 21.5 Transformer Total 11.1 20.4 Switching Description: Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B6-1 0.9 1.6 4B5-1 7.1 7.1 4B4-1 0.5 0.0 4B3-1 6.2 0.6 4B2-1 0.9 10.6 Transformer Total 15.6 19.9 4B4-14 SWITCHING PROCEDURE YORK ROAD BREAKERS WESTSIDE BREAKERS 4B3-144B6-144B7-14 HARRISON BREAKERS MILLIGAN BREAKERS RACK BREAKERS 4B3-18 4B3-14 transferring to 4B6-1 4B4-14 transferring to 4B6-14 4B5-14 shut off 4B6-14 transferring to 4B2-1 4B4-16 taking load off of 4B3-1 4B7-14 transferring to 4B4-16 4B5-3 taking load off of 4B4-1 4B3-18 transferring to 4B5-3
  • 22. N-2 Substation Switching Study 21 5.1.17 Harrison & Westside Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4D85 CLOSED 4B2-16 2.2 0.0 4B3-18 8.8 0.0 4D72 OPEN 4B3-16 6.7 0.0 4H7 CLOSED 4B4-16 4.6 0.0 4H43 OPEN 4B5-16 0.6 0.0 4H49 CLOSED 4H42 OPEN Transformer Total 14.1 0.0 Transformer Total 8.8 0.0 4D13 CLOSED 4B2-16 OPEN 4H21 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-16 OPEN 4B3-14 0.7 0.7 4B5-3 0.6 9.9 4H20 CLOSED 4B4-14 6.8 6.8 4B4-3 9.9 9.9 4B4-16 OPEN 4B5-14 0.0 0.0 4B3-3 0.6 0.6 4D54 CLOSED 4B6-14 2.9 2.9 4B5-16 OPEN 4B7-14 1.8 2.6 4H36 CLOSED Transformer Total 12.2 13.0 Transformer Total 11.1 20.4 4D17 OPEN 4H52 CLOSED 4B3-18 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-9 7.8 7.8 4B2-6 7.6 7.6 Switching Description: 4B3-9 8.2 11.2 4B3-6 6.8 0.2 4B4-6 4.7 12.0 Transformer Total 16.0 19.0 Transformer Total 19.1 19.8 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-17 12.0 9.0 4B6-1 0.9 0.9 4B3-17 1.0 1.0 4B5-1 7.1 7.1 4B2-17 2.2 8.8 4B4-1 0.5 0.0 4B3-1 6.2 12.2 4B2-1 0.9 0.9 Transformer Total 15.2 18.8 Transformer Total 15.6 21.1 4B3-184B2-164B3-164B4-164B5-16 FIFTEENTH ST. BREAKERS SUGARMILL BREAKERS HATCH BREAKERS RACK BREAKERS 4B7-14 taking load off of 4B3-1 4B3-9 taking load off of 4B4-17 4B2-17 taking load off of 4B3-6 4B2-16 transferring to 4B4-16 4B3-16 transferring to 4B4-6 4B4-16 transferring to 4B3-1 4B5-16 transferring to 4B4-6 4B5-3 taking load off of 4B4-1 4B3-18 transferring to 4B5-3 SWITCHING PROCEDURE HARRISON BREAKERS WESTSIDE BREAKERS YORK ROAD BREAKERS MILLIGAN BREAKERS
  • 23. N-2 Substation Switching Study 22 5.1.18 Hatch & Westside Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H49 CLOSED 4B4-17 12.0 0.0 4B3-18 8.8 0.0 4B2-17 OPEN 4B3-17 1.0 0.0 4H5 CLOSED 4B2-17 2.2 0.0 4B3-17 OPEN 4H13 CLOSED 4H47 OPEN Transformer Total 15.2 0.0 Transformer Total 8.8 0.0 4H16 CLOSED 4H3 OPEN 4H26 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4S8 OPEN 4B2-13 2.1 2.1 4B5-3 0.6 9.9 4H34 CLOSED 4B3-13 3.9 3.9 4B4-3 9.9 9.9 4D69 OPEN 4B4-13 4.4 7.6 4B3-3 0.6 0.6 4H7 CLOSED 4B4-17 OPEN 4H36 CLOSED Transformer Total 10.4 13.6 Transformer Total 11.1 20.4 4D17 OPEN 4H52 CLOSED 4B3-18 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-9 7.8 9.3 4B2-6 7.6 8.6 Switching Description: 4B3-9 8.2 9.6 4B3-6 6.8 9.0 4B4-6 4.7 4.7 Transformer Total 16.0 18.9 Transformer Total 19.1 22.3 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) Note: 4B2-16 2.2 2.2 4B6-1 0.9 0.9 4B3-16 6.7 6.7 4B5-1 7.1 7.1 4B4-16 4.6 6.8 4B4-1 0.5 0.0 4B5-16 0.6 0.6 4B3-1 6.2 9.9 4B2-1 0.9 0.9 Transformer Total 14.1 16.3 Transformer Total 15.6 18.8 4B2-17 transferring to 4B3-6 4B3-17 transferring to 4B2-6 4B3-1 taking load off of 4B2-9 4B4-13 taking load off of 4B3-9 4B4-16 taking load off of 4B4-17 4B2-9 taking load off of 4B4-17 4B4-17 transferring to 4B3-9 4B5-3 taking load off of 4B4-1 4B3-18 transferring to 4B5-3 Upgrading the 336 ACSR wire between 4S8 and 4H20 would simplify the switching procedure. HARRISON BREAKERS RACK BREAKERS 4B3-18 FIFTEENTH ST. BREAKERS SUGARMILL BREAKERS 4B2-174B3-174B4-17 SWITCHING PROCEDURE HATCH BREAKERS WESTSIDE BREAKERS CITY BREAKERS MILLIGAN BREAKERS
  • 24. N-2 Substation Switching Study 23 5.2 Scenarios that work with assumptions 5.2.1 Rack & Templeview Templeview’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H33 CLOSED 4B6-1 0.9 0.0 4B2-4 7.7 0.0 4B2-1 OPEN 4B5-1 7.1 0.0 4B3-4 0.6 0.0 4D85 CLOSED 4B4-1 0.5 0.0 4B4-4 2.4 0.0 4B3-1 OPEN 4B3-1 6.2 0.0 4H52 CLOSED 4B2-1 0.9 0.0 4B4-1 OPEN Transformer Total 15.6 0.0 Transformer Total 10.7 0.0 4H8 CLOSED 4H3 OPEN 4H10 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B5-1 OPEN 4B2-9 7.8 7.8 4B3-18 8.8 9.3 4H53 CLOSED 4B3-9 8.2 12.1 4B6-1 OPEN 4H58 CLOSED 4H55 OPEN 4H9 CLOSED Transformer Total 16.0 19.9 Transformer Total 8.8 9.3 4H44 OPEN 4H1 CLOSED 4B2-4 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-4 4B3-4 CLOSED 4B2-13 2.1 2.1 4B3-14 0.7 1.6 4B4-4 CLOSED 4B3-13 3.9 9.9 4B4-14 6.8 6.8 4H31 CLOSED 4B4-13 4.4 7.7 4B5-14 0.0 0.0 4B1-4 OPEN 4B6-14 2.9 3.8 4B7-14 1.8 8.0 Switching Description: Transformer Total 10.4 19.7 Transformer Total 12.2 20.2 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-12 0.0 0.0 4B7-12 0.8 0.8 4B3-12 11.0 12.6 4B6-12 8.3 11.3 4B2-12 2.1 2.1 Note: Transformer Total 13.1 14.7 Transformer Total 9.1 12.1 4B4-4 4B2-1 transferring to 4B6-14 4B3-1 transferring to 4B7-14 4B4-1 transferring to 4B3-18 4B3-13 taking load off of 4B3-9 4B5-1 transferring to 4B3-9 4B6-1 transferring to 4B3-14 4B3-13 taking load off of 4B3-12 4B4-13 taking load off of 4B3-12 4B2-4 transferring to 4B3-12 4B3-4 powered through 4B4-4 4B4-4 transferring to 4B6-12 N. BOULEVARD 5T1-12 BREAKERS N. BOULEVARD 5T2-12 BREAKERS Switching procedure requires the use of Templeview's auxiliary bus. 4B3-4 needs to be connected to another circuit. 4B2-4 CITY BREAKERS YORK ROAD BREAKERS SWITCHING PROCEDURE RACK BREAKERS TEMPLEVIEW BREAKERS 4B2-14B3-14B4-14B5-1 FIFTEENTH ST. BREAKERS WESTSIDE BREAKERS 4B6-1
  • 25. N-2 Substation Switching Study 24 5.2.2 Rack & N. Boulevard N. Boulevard’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H33 CLOSED 4B7-12 0.8 0.0 4B4-12 0.0 0.0 4B2-1 OPEN 4B6-12 8.3 0.0 4B3-12 11.0 0.0 4D85 CLOSED 4B2-12 2.1 0.0 4B3-1 OPEN 4H52 CLOSED 4B4-1 OPEN Transformer Total 9.1 0.0 Transformer Total 13.1 0.0 4H8 CLOSED 4H3 OPEN 4H10 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B5-1 OPEN 4B6-1 0.9 0.0 4B2-13 2.1 2.1 4H53 CLOSED 4B5-1 7.1 0.0 4B3-13 3.9 9.9 4B6-1 OPEN 4B4-1 0.5 0.0 4B4-13 4.4 7.7 4H9 CLOSED 4B3-1 6.2 0.0 4H44 OPEN 4B2-1 0.9 0 OLD CUTOUT CLOSED Transformer Total 15.6 0.0 Transformer Total 10.4 19.7 4B2-12 OPEN 4H58 CLOSED 4H55 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H45 CLOSED 4B2-9 7.8 7.8 4B5-3 0.6 0.6 4H2 OPEN 4B3-9 8.2 12.1 4B4-3 9.9 12.7 4H41 CLOSED 4B3-3 0.6 0.6 4D1 OPEN 4H1 CLOSED 4B3-12 OPEN Transformer Total 16.0 19.9 Transformer Total 11.1 13.9 4H31 CLOSED 4B6-12 OPEN 4H12-12 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H13-12 CLOSED 4B3-14 0.7 1.6 4B2-6 7.6 9.5 4B7-12 OPEN 4B4-14 6.8 6.8 4B3-6 6.8 6.8 4B5-14 0.0 0.0 4B4-6 4.7 4.7 Switching Description: 4B6-14 2.9 3.8 4B7-14 1.8 8.0 Transformer Total 12.2 20.2 Transformer Total 19.1 21.0 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-4 7.7 10.0 4B3-18 8.8 9.3 4B3-4 0.6 0.6 4B4-4 2.4 11.5 Transformer Total 10.7 22.1 Transformer Total 8.8 9.3 Note: Old Cutout needs to be a switch. Switching procedure requires the use of N. Boulevard's auxiliary bus. 4B6-12 SUGARMILL BREAKERSYORK ROAD BREAKERS 4B6-1 FIFTEENTH ST. BREAKERS MILLIGAN BREAKERS TEMPLEVIEW BREAKERS WESTSIDE BREAKERS 4B2-1 transferring to 4B6-14 4B3-1 transferring to 4B7-14 4B4-1 transferring to 4B3-18 4B3-13 taking load off of 4B3-9 4B5-1 transferring to 4B3-9 4B6-1 transferring to 4B3-14 4B4-13 taking load off of 4B3-12 4B2-12 transferring to 4B3-12 4B3-13 taking load off of 4B3-12 4B2-6 taking load off of 4B3-12 4B4-3 taking load off of 4B2-4 4B3-12 transferring to 4B2-4 4B6-12 transferring to 4B4-4 4B7-12 transferring to 4B4-4 RACK BREAKERS CITY BREAKERS 4B2-1 SWITCHING PROCEDURE N. BOULEVARD 5T2-12 BREAKERS N. BOULEVARD 5T1-12 BREAKERS 4B3-14B4-14B5-14B7-124B2-124B3-12
  • 26. N-2 Substation Switching Study 25 5.2.3 Rack & City City’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H33 CLOSED 4B6-1 0.9 0.0 4B2-13 2.1 0.0 4B2-1 OPEN 4B5-1 7.1 0.0 4B3-13 3.9 0.0 4H20 CLOSED 4B4-1 0.5 0.0 4B4-13 4.4 0.0 4D73 OPEN 4B3-1 6.2 0.0 4D85 CLOSED 4B2-1 0.9 0.0 4D72 OPEN Transformer Total 15.6 0.0 Transformer Total 10.4 0.0 4D59 CLOSED 4B3-1 OPEN 4H52 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-1 OPEN 4B2-16 2.2 2.2 4B3-18 8.8 9.3 4H30 CLOSED 4B3-16 6.7 6.7 4H50 OPEN 4B4-16 4.6 6.1 4H51 CLOSED 4B5-16 0.6 0.6 4B5-1 OPEN 4H53 CLOSED Transformer Total 14.1 15.6 Transformer Total 8.8 9.3 4B6-1 OPEN 4B2-13 4B2-13 CLOSED 4H46 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-13 CLOSED 4B2-9 7.8 9.2 4B3-14 0.7 1.6 4H16 CLOSED 4B3-9 8.2 12.6 4B4-14 6.8 6.8 4B4-13 OPEN 4B5-14 0.0 0.0 4B1-13 OPEN 4B6-14 2.9 3.8 4B7-14 1.8 12.2 Switching Description: Transformer Total 16.0 21.8 Transformer Total 12.2 24.4 Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B5-3 0.6 0.6 4B4-3 9.9 9.9 4B3-3 0.6 6.6 Transformer Total 11.1 17.1 4B4-134B5-14B6-14B3-14B4-14B3-13 4B2-1 transferring to 4B6-14 4B4-16 taking load off of 4B3-1 4B7-14 taking load off of 4B4-16 4B3-1 transferring to 4B7-14 4B4-1 transferring to 4B3-18 4B2-9 taking load off of 4B5-1 4B5-1 transferring to 4B7-14 4B6-1 transferring to 4B3-14 4B2-13 powered through 4B3-13 4B3-13 transferring to 4B3-3 4B4-13 transferring to 4B3-9 HARRISON BREAKERS WESTSIDE BREAKERS FIFTEENTH ST. BREAKERS YORK ROAD BREAKERS MILLIGAN BREAKERS SWITCHING PROCEDURE RACK BREAKERS CITY BREAKERS 4B2-1
  • 27. N-2 Substation Switching Study 26 5.2.4 Rack & York Both Rack and York Road’s aux buses must be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H2-1 CLOSED 4B6-1 0.9 0.0 4B3-14 0.7 0.0 4H4-1 CLOSED 4B5-1 7.1 0.0 4B4-14 6.8 0.0 4B2-1 OPEN 4B4-1 0.5 0.0 4B5-14 0.0 0.0 4H11 CLOSED 4B3-1 6.2 0.0 4B6-14 2.9 0.0 4H22 OPEN 4B2-1 0.9 0.0 4B7-14 1.8 0.0 4H20 CLOSED Transformer Total 15.6 0.0 Transformer Total 12.2 0.0 4B3-1 OPEN 4H36 CLOSED 4B4-1 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H8 CLOSED 4B2-16 2.2 2.2 4B5-3 0.6 11.7 4H3 OPEN 4B3-16 6.7 8.2 4B4-3 9.9 9.9 4H10 CLOSED 4B4-16 4.6 12.7 4B3-3 0.6 0.6 4B5-1 OPEN 4B5-16 0.6 0.6 4H53 CLOSED 4B6-1 OPEN Transformer Total 14.1 23.7 Transformer Total 11.1 22.2 4D85 CLOSED 4B7-14 OPEN 4H33 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B6-14 OPEN 4B2-13 2.1 2.1 4B2-9 7.8 7.8 4B5-14 4B5-14 OPEN 4B3-13 3.9 7.1 4B3-9 8.2 12.1 4D51 CLOSED 4B4-13 4.4 4.4 4B4-14 OPEN 4H3-14 CLOSED 4B3-14 OPEN Transformer Total 10.4 13.6 Transformer Total 16.0 19.9 4H7-14 CLOSED 4B1-14 OPEN Switching Description: HARRISON BREAKERS MILLIGAN BREAKERS CITY BREAKERS FIFTEENTH ST. BREAKERS 4B2-1 transferring to 4B4-1 4B3-16 taking load off of 4B4-16 4B3-1 transferring to 4B4-16 4B4-1 transferring to 4B5-3 4B3-13 taking load off of 4B3-9 4B5-1 transferring to 4B3-9 4B6-1 transferring to 4B3-14 4B7-14 transferring to 4B4-16 4B6-14 transferring to 4B5-3 4B5-14 shut off 4B4-14 transferring to 4B5-3 4B3-14 transferring to 4B4-16 SWITCHING PROCEDURE RACK BREAKERS YORK ROAD BREAKERS 4B2-14B3-14B4-14B5-14B6-14B7-144B6-144B4-144B3-14
  • 28. N-2 Substation Switching Study 27 5.2.5 Rack & Harrison Rack’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H33 CLOSED 4B6-1 0.9 0.0 4B2-16 2.2 0.0 4B2-1 OPEN 4B5-1 7.1 0.0 4B3-16 6.7 0.0 4D85 CLOSED 4B4-1 0.5 0.0 4B4-16 4.6 0.0 4D73 OPEN 4B3-1 6.2 0.0 4B5-16 0.6 0 4H3-1 CLOSED 4B2-1 0.9 0.0 4H4-1 CLOSED Transformer Total 15.6 0.0 Transformer Total 14.1 0.0 4B3-1 OPEN 4H36 CLOSED 4B4-1 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H5-1 CLOSED 4B3-14 0.7 1.6 4B5-3 0.6 12.1 4B5-1 OPEN 4B4-14 6.8 6.8 4B4-3 9.9 9.9 4H53 CLOSED 4B5-14 0.0 0.0 4B3-3 0.6 0.6 4B6-1 OPEN 4B6-14 2.9 3.8 4D13 CLOSED 4B7-14 1.8 10.9 4B2-16 OPEN Transformer Total 12.2 23.1 Transformer Total 11.1 22.6 4H49 CLOSED 4H42 OPEN 4H21 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-16 OPEN 4B4-17 12.0 12.0 4B2-6 7.6 7.6 4H20 CLOSED 4B3-17 1.0 1.0 4B3-6 6.8 0.2 4B4-16 OPEN 4B2-17 2.2 8.8 4B4-6 4.7 12.0 4D54 CLOSED 4B5-16 OPEN Transformer Total 15.2 21.8 Transformer Total 19.1 19.8 Switching Description: 4B3-1 4B2-1 transferring to 4B6-14 4B7-14 taking load off of 4B3-1 4B3-1 transferring to 4B4-1 4B4-1 transferring to 4B5-3 4B5-1 transferring to 4B5-3 4B6-1 transferringto 4B3-14 4B2-16 transferring to 4B4-16 4B2-17 taking load off of 4B3-6 4B3-16 transferring to 4B4-6 4B4-16 transferring to 4B7-14 4B5-16 transferring to 4B4-6 SWITCHING PROCEDURE RACK BREAKERS HARRISON BREAKERS 4B2-14B4-1 YORK ROAD BREAKERS MILLIGAN BREAKERS 4B5-14B6-14B2-164B4-164B5-164B3-16 HATCH BREAKERS SUGARMILL BREAKERS
  • 29. N-2 Substation Switching Study 28 5.2.6 Rack & Hatch Rack’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H33 CLOSED 4B6-1 0.9 0.0 4B4-17 12.0 0.0 4B2-1 OPEN 4B5-1 7.1 0.0 4B3-17 1.0 0.0 4D85 CLOSED 4B4-1 0.5 0.0 4B2-17 2.2 0.0 4D73 OPEN 4B3-1 6.2 0.0 4H3-1 CLOSED 4B2-1 0.9 0.0 4H4-1 CLOSED Transformer Total 15.6 0.0 Transformer Total 15.2 0.0 4B3-1 OPEN 4H36 CLOSED 4B4-1 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H5-1 CLOSED 4B3-14 0.7 1.6 4B5-3 0.6 12.1 4B5-1 OPEN 4B4-14 6.8 6.8 4B4-3 9.9 9.9 4H53 CLOSED 4B5-14 0.0 0.0 4B3-3 0.6 0.6 4B6-1 OPEN 4B6-14 2.9 3.8 4H49 CLOSED 4B7-14 1.8 4.1 4B2-17 OPEN Transformer Total 12.2 16.3 Transformer Total 11.1 22.6 4H5 CLOSED 4B3-17 OPEN 4H26 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H40 OPEN 4B2-13 2.1 2.1 4B2-9 7.8 7.8 4H8 CLOSED 4B3-13 3.9 7.1 4B3-9 8.2 11.2 4H3 OPEN 4B4-13 4.4 4.4 4H7 CLOSED 4B4-17 OPEN Transformer Total 10.4 13.6 Transformer Total 16.0 19.0 Switching Description: Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-16 2.2 2.2 4B2-6 7.6 8.6 4B3-16 6.7 6.7 4B3-6 6.8 9.0 4B4-16 4.6 10.4 4B4-6 4.7 4.7 4B5-16 0.6 0.6 Transformer Total 14.1 19.9 Transformer Total 19.1 22.3 HARRISON BREAKERS SUGARMILL BREAKERS4B2-1 transferring to 4B6-14 4B7-14 taking load off of 4B3-1 4B3-1 transferring to 4B4-1 4B4-1 transferring to 4B5-3 4B5-1 transferring to 4B5-3 4B6-1 transferringto 4B3-14 4B2-17 transferring to 4B3-6 4B3-17 transferring to 4B2-6 4B4-16 taking load off of 4B4-17 4B3-13 taking load off of 4B3-9 4B4-17 transferring to 4B3-9 MILLIGAN BREAKERS CITY BREAKERS FIFTEENTH ST. BREAKERS SWITCHING PROCEDURE RACK BREAKERS HATCH BREAKERS 4B2-1 YORK ROAD BREAKERS 4B3-14B4-174B4-14B5-14B6-14B2-174B3-17
  • 30. N-2 Substation Switching Study 29 5.2.7 Milligan & Templeview Templeview’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H46 CLOSED 4B5-3 0.6 0.0 4B2-4 7.7 0.0 4B3-3 OPEN 4B4-3 9.9 0.0 4B3-4 0.6 0.0 4D18 CLOSED 4B3-3 0.6 0.0 4B4-4 2.4 0.0 4D46 OPEN 4D24 CLOSED 4D40 OPEN Transformer Total 11.1 0.0 Transformer Total 10.7 0.0 4H36 CLOSED 4B1-3 OPEN 4H58 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H55 OPEN 4B2-6 7.6 9.5 4B6-1 0.9 0.9 4H45 CLOSED 4B3-6 6.8 6.8 4B5-1 7.1 7.1 4H2 OPEN 4B4-6 4.7 4.7 4B4-1 0.5 6.4 4H9 CLOSED 4B3-1 6.2 6.2 4H44 OPEN 4B2-1 0.9 0.9 4H1 CLOSED Transformer Total 19.1 21.0 Transformer Total 15.6 21.5 4B2-4 OPEN 4H3-4 CLOSED 4H4-4 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-4 OPEN 4B2-13 2.1 2.1 4B2-9 7.8 7.8 4H31 CLOSED 4B3-13 3.9 4.5 4B3-9 8.2 11.0 4B4-4 OPEN 4B4-13 4.4 7.7 Switching Description: Transformer Total 10.4 14.3 Transformer Total 16.0 18.8 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-12 0.0 0.0 4B7-12 0.8 0.8 4B3-12 11.0 12.8 4B6-12 8.3 11.3 4B2-12 2.1 2.1 Transformer Total 13.1 14.9 Transformer Total 9.1 12.1 Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-18 8.8 11.3 Transformer Total 8.8 11.3 SUGARMILL BREAKERS RACK BREAKERS CITY BREAKERS FIFTEENTH ST. BREAKERS 4B5-3&4B4-34B2-44B3-4 SWITCHING PROCEDURE MILLIGAN BREAKERS TEMPLEVIEW BREAKERS 4B3-3 N. BOULEVARD 5T1-12 BREAKERS N. BOULEVARD 5T2-12 BREAKERS 4B3-3 transferring to 4B3-13 4B2-4 taking load off of 4B4-3 4B3-18 taking load off of 4B4-3 4B4-3 powered through 4B5-3 4B5-3 transferring to 4B4-1 4B3-9 taking load off of 4B3-12 4B2-6 taking load off of 4B3-12 4B4-13 taking load off of 4B3-12 4B2-4 transferring to 4B3-12 4B3-4 powered through 4B4-4 4B4-4 transferring to 4B6-12 WESTSIDE BREAKERS 4B4-4
  • 31. N-2 Substation Switching Study 30 5.2.8 Milligan & N. Boulevard N. Boulevard’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H46 CLOSED 4B7-12 0.8 0.0 4B4-12 0.0 0.0 4B3-3 OPEN 4B6-12 8.3 0.0 4B3-12 11.0 0.0 4D18 CLOSED 4B2-12 2.1 0.0 4R5 OPEN 4D24 CLOSED 4D29 OPEN Transformer Total 9.1 0.0 Transformer Total 13.1 0.0 4H41 CLOSED 4H29 OPEN 4H36 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B1-3 OPEN 4B5-3 0.6 0.0 4B2-13 2.1 2.1 4H58 CLOSED 4B4-3 9.9 0.0 4B3-13 3.9 10.5 4H55 OPEN 4B3-3 0.6 0.0 4B4-13 4.4 7.7 OLD CUTOUT CLOSED 4B2-12 OPEN 4H8 CLOSED Transformer Total 11.1 0.0 Transformer Total 10.4 20.3 4H3 OPEN 4H9 CLOSED 4H44 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H7 CLOSED 4B2-9 7.8 7.8 4B2-6 7.6 3.5 4H43 OPEN 4B3-9 8.2 8.0 4B3-6 6.8 6.8 4H5 CLOSED 4B4-6 4.7 4.7 4H6 OPEN 4H26 CLOSED 4H40 OPEN Transformer Total 16.0 15.8 Transformer Total 19.1 15.0 4H45 CLOSED 4B3-12 OPEN 4H31 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B6-12 OPEN 4B3-18 8.8 11.2 4B2-4 7.7 9.0 4H12-12 CLOSED 4B3-4 0.6 0.6 4H13-12 CLOSED 4B4-4 2.4 11.5 4B7-12 OPEN Switching Description: Transformer Total 8.8 11.2 Transformer Total 10.7 21.1 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-16 2.2 2.2 4B6-1 0.9 0.9 4B3-16 6.7 6.7 4B5-1 7.1 7.1 4B4-16 4.6 10.4 4B4-1 0.5 7.3 4B5-16 0.6 0.6 4B3-1 6.2 6.2 4B2-1 0.9 0.9 Transformer Total 14.1 19.9 Transformer Total 15.6 22.4 Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-17 12.0 3.2 Note: 4B3-17 1.0 12.1 4B2-17 2.2 2.2 Transformer Total 15.2 17.5 4B2-124B3-12 WESTSIDE BREAKERS FIFTEENTH ST. BREAKERS 4B7-12 needs to be connected to another circuit. Old Cutout needs to be a switch. TEMPLEVIEW BREAKERS 4B3-3 transferring to 4B3-13 4B2-4 taking load off of 4B4-3 4B3-18 taking load off of 4B4-3 4B4-3 taking load off of 4B2-4 4B4-3 powered through 4B5-3 4B5-3 transferring to 4B4-1 4B3-9 taking load off of 4B3-12 4B2-12 transferring to 4B3-12 4B3-13 taking load off of 4B3-9 4B4-13 taking load off of 4B3-12 4B3-9 taking load off of 4B4-17 4B3-17 taking load off of 4B2-6 4B4-16 taking load off of 4B4-17 4B3-12 transferring to 4B3-17 4B6-12 transferring to 4B4-4 4B7-12 transferring to 4B4-4 HARRISON BREAKERS RACK BREAKERS 4B6-124B7-12 HATCH BREAKERS SUGARMILL BREAKERS SWITCHING PROCEDURE N. BOULEVARD 5T2-12 BREAKERS N. BOULEVARD 5T1-12 BREAKERS MILLIGAN BREAKERS CITY BREAKERS 4B3-34B5-3&4B4-3
  • 32. N-2 Substation Switching Study 31 5.2.9 Milligan & City City’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H46 CLOSED 4B5-3 0.6 0.0 4B2-13 2.1 0.0 4B3-3 OPEN 4B4-3 9.9 0.0 4B3-13 3.9 0.0 4D18 CLOSED 4B3-3 0.6 0.0 4B4-13 4.4 0.0 4D46 OPEN 4D24 CLOSED 4D40 OPEN Transformer Total 11.1 0.0 Transformer Total 10.4 0.0 4H36 CLOSED 4B1-3 OPEN 4H8 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-13 OPEN 4B2-4 7.7 9.8 4B6-1 0.9 0.9 4H45 CLOSED 4B3-4 0.6 0.6 4B5-1 7.1 7.1 4H2 OPEN 4B4-4 2.4 2.4 4B4-1 0.5 6.4 4H9 CLOSED 4B3-1 6.2 6.2 4B4-13 OPEN 4B2-1 0.9 0.9 Transformer Total 10.7 12.8 Transformer Total 15.6 21.5 Switching Description: Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-9 7.8 7.8 4B2-6 7.6 12.3 4B3-9 8.2 12.7 4B3-6 6.8 6.8 4B4-6 4.7 4.7 Transformer Total 16.0 20.5 Transformer Total 19.1 23.8 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-12 0.0 0.0 4B3-18 8.8 11.3 4B3-12 11.0 12.8 4B2-12 2.1 2.1 Transformer Total 13.1 14.9 Transformer Total 8.8 11.3 4B4-13&4B2-13 FIFTEENTH ST. BREAKERS SUGARMILL BREAKERS4B3-3 transferring to 4B3-13 4B2-4 taking load off of 4B4-3 4B3-18 taking load off of 4B4-3 4B4-3 powered through 4B5-3 4B5-3 transferring to 4B4-1 4B3-13 transferring to 4B3-9 4B2-6 taking load off of 4B3-12 4B2-13 powered through 4B4-13 4B4-13 transferring to 4B3-12 N. BOULEVARD 5T1-12 BREAKERS WESTSIDE BREAKERS 4B3-13 SWITCHING PROCEDURE MILLIGAN BREAKERS CITY BREAKERS 4B3-34B5-3&4B4-3 TEMPLEVIEW BREAKERS RACK BREAKERS
  • 33. N-2 Substation Switching Study 32 5.2.10 Templeview & Sugarmill Templeview’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H58 CLOSED 4B2-4 7.7 0.0 4B2-6 7.6 0.0 4H55 OPEN 4B3-4 0.6 0.0 4B3-6 6.8 0.0 4H9 CLOSED 4B4-4 2.4 0.0 4B4-6 4.7 0.0 4H44 OPEN 4H1 CLOSED 4B2-4 OPEN Transformer Total 10.7 0.0 Transformer Total 19.1 0.0 4B3-4 4B3-4 CLOSED 4B4-4 OPEN 4H31 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B1-4 OPEN 4B4-12 0.0 0.0 4B7-12 0.8 0.8 4H5 CLOSED 4B3-12 11.0 12.6 4B6-12 8.3 11.3 4B2-6 OPEN 4B2-12 2.1 2.1 4H26 CLOSED 4S8 OPEN 4H34 CLOSED Transformer Total 13.1 14.7 Transformer Total 9.1 12.1 4H40 OPEN 4H49 CLOSED 4B3-6 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H21 CLOSED 4B2-13 2.1 2.1 4B2-16 2.2 2.2 4B4-6 OPEN 4B3-13 3.9 3.9 4B3-16 6.7 11.4 4B4-13 4.4 7.7 4B4-16 4.6 6.8 Switching Description: 4B5-16 0.6 0.6 Transformer Total 10.4 13.7 Transformer Total 14.1 21.0 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-17 12.0 6.2 4B2-9 7.8 11.4 4B3-17 1.0 8.6 4B3-9 8.2 11.0 4B2-17 2.2 9.0 Note: Transformer Total 15.2 23.8 Transformer Total 16.0 22.4 4B2-64B4-64B3-6 4B3-9 taking load off of 4B3-12 4B4-13 taking load off of 4B3-12 4B2-4 transferring to 4B3-12 4B3-4 powered through 4B4-4 4B4-4 transferring to 4B6-12 4B2-6 transferring to 4B3-17 4B4-16 taking load off of 4B4-17 4B2-9 taking load off of 4B4-17 4B3-6 transferring to 4B2-17 4B4-6 transferring to 4B3-16 4B3-4 needs to be connected to another circuit. HATCH BREAKERS FIFTEENTH ST. BREAKERS CITY BREAKERS HARRISON BREAKERS SWITCHING PROCEDURE TEMPLEVIEW BREAKERS SUGARMILL BREAKERS N. BOULEVARD 5T1-12 BREAKERS N. BOULEVARD 5T1-12 BREAKERS 4B4-44B2-4
  • 34. N-2 Substation Switching Study 33 5.2.11 Templeview & Fifteenth St. Templeview’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H41 CLOSED 4B2-4 7.7 0.0 4B2-9 7.8 0.0 4D1 OPEN 4B3-4 0.6 0.0 4B3-9 8.2 0.0 4H49 CLOSED 4B4-4 2.4 0.0 4H42 OPEN 4H45 CLOSED Transformer Total 10.7 0.0 Transformer Total 16.0 0.0 4H2 OPEN 4H1 CLOSED 4B2-4 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H3-4 CLOSED 4B4-12 0.0 0.0 4B7-12 0.8 0.8 4H4-4 CLOSED 4B3-12 11.0 11.2 4B6-12 8.3 11.3 4B3-4 OPEN 4B2-12 2.1 2.1 4H31 CLOSED 4B4-4 OPEN Transformer Total 13.1 13.3 Transformer Total 9.1 12.1 4H12 CLOSED 4B2-9 OPEN 4H16 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H19 OPEN 4B2-13 2.1 2.1 4B2-16 2.2 2.2 4H8 CLOSED 4B3-13 3.9 9.5 4B3-16 6.7 6.7 4B3-9 OPEN 4B4-13 4.4 7.0 4B4-16 4.6 12.4 4B5-16 0.6 0.6 Switching Description: Transformer Total 10.4 18.6 Transformer Total 14.1 21.9 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-6 7.6 12.3 4B5-3 0.6 0.6 4B3-6 6.8 0.2 4B4-3 9.9 12.7 4B4-6 4.7 4.7 4B3-3 0.6 0.6 Transformer Total 19.1 17.2 Transformer Total 11.1 13.9 Note: Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-17 12.0 12.0 4B3-17 1.0 1.0 4B2-17 2.2 8.8 Transformer Total 15.2 21.8 4B3-4 needs to be connected to another circuit. HATCH BREAKERS CITY BREAKERS HARRISON BREAKERS 4B4-3 taking load off of 4B2-4 4B2-17 taking load off of 4B3-6 4B2-6 taking load off of 4B3-12 4B2-4 transferring to 4B3-12 4B3-4 powered through 4B4-4 4B4-4 transferring to 4B6-12 4B2-9 transferring to 4B4-16 4B4-13 taking load off of 4B3-9 4B3-9 transferring to 4B3-13 SUGARMILL BREAKERS MILLIGAN BREAKERS SWITCHING PROCEDURE TEMPLEVIEW BREAKERS FIFTEENTH ST. BREAKERS N. BOULEVARD 5T1-12 N. BOULEVARD 5T1-12 4B2-94B3-94B2-44B3-44B4-4
  • 35. N-2 Substation Switching Study 34 5.2.12 Templeview & City Both Templeview and City’s aux buses must be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H41 CLOSED 4B2-4 7.7 0.0 4B2-13 2.1 0.0 4D1 OPEN 4B3-4 0.6 0.0 4B3-13 3.9 0.0 4H49 CLOSED 4B4-4 2.4 0.0 4B4-13 4.4 0.0 4H42 OPEN 4H45 CLOSED 4H2 OPEN Transformer Total 10.7 0.0 Transformer Total 10.4 0.0 4H1 CLOSED 4B2-4 OPEN 4H3-4 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H4-4 CLOSED 4B4-12 0.0 0.0 4B7-12 0.8 0.8 4B3-4 OPEN 4B3-12 11.0 11.2 4B6-12 8.3 11.3 4H31 CLOSED 4B2-12 2.1 2.1 4B4-4 OPEN 4H16 CLOSED 4B4-13 OPEN Transformer Total 13.1 13.3 Transformer Total 9.1 12.1 4H46 CLOSED 4B1-13 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) Switching Description: 4B2-6 7.6 12.3 4B4-17 12.0 12.0 4B3-6 6.8 0.2 4B3-17 1.0 1.0 4B4-6 4.7 4.7 4B2-17 2.2 8.8 Transformer Total 19.1 17.2 Transformer Total 15.2 21.8 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) Note: 4B5-3 0.6 0.6 4B2-9 7.8 7.8 4B4-3 9.9 12.7 4B3-9 8.2 12.6 4B3-3 0.6 6.6 Transformer Total 11.1 19.9 Transformer Total 16.0 20.4 SWITCHING PROCEDURE TEMPLEVIEW BREAKERS CITY BREAKERS N. BOULEVARD 5T1-12 BREAKERS N. BOULEVARD 5T1-12 BREAKERS 4B2-44B3-44B4-44B4-134B2-13&4B3-13 4B4-3 taking load off of 4B2-4 4B2-17 taking load off of 4B3-6 4B2-6 taking load off of 4B3-12 4B2-4 transferring to 4B3-12 4B3-4 powered through 4B4-4 4B4-4 transferring to 4B6-12 4B4-13 transferring to 4B3-9 4B2-13 powered through 4B3-13 4B3-13 transferring to 4B3-3 SUGARMILL BREAKERS HATCH BREAKERS MILLIGAN BREAKERS FIFTEENTH ST. BREAKERS 4B3-4 needs to be connected to another circuit. 4B2-13 needs to be connected to another circuit.
  • 36. N-2 Substation Switching Study 35 5.2.13 Templeview & York Road Templeview’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H41 CLOSED 4B2-4 7.7 0.0 4B3-14 0.7 0.0 4D1 OPEN 4B3-4 0.6 0.0 4B4-14 6.8 0.0 4H49 CLOSED 4B4-4 2.4 0.0 4B5-14 0.0 0.0 4H42 OPEN 4B6-14 2.9 0.0 4H45 CLOSED 4B7-14 1.8 0 4H2 OPEN Transformer Total 10.7 0.0 Transformer Total 12.2 0.0 4H1 CLOSED 4B2-4 OPEN 4H3-4 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H4-4 CLOSED 4B4-12 0.0 0.0 4B7-12 0.8 0.8 4B3-4 OPEN 4B3-12 11.0 11.2 4B6-12 8.3 11.3 4H31 CLOSED 4B2-12 2.1 2.1 4B4-4 OPEN 4H53 CLOSED 4B3-14 OPEN Transformer Total 13.1 13.3 Transformer Total 9.1 12.1 4D51 CLOSED 4B4-14 OPEN 4B5-14 4B5-14 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H8 CLOSED 4B6-1 0.9 1.6 4B5-3 0.6 0.6 4H3 OPEN 4B5-1 7.1 0.0 4B4-3 9.9 12.7 4H10 CLOSED 4B4-1 0.5 0.5 4B3-3 0.6 0.6 4D14 OPEN 4B3-1 6.2 8.0 4H33 CLOSED 4B2-1 0.9 10.6 4B6-14 OPEN Transformer Total 15.6 20.7 Transformer Total 11.1 13.9 4D85 CLOSED 4B7-14 OPEN Switching Description: Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-17 12.0 12.0 4B2-9 7.8 7.8 4B3-17 1.0 1.0 4B3-9 8.2 12.1 4B2-17 2.2 8.8 Transformer Total 15.2 21.8 Transformer Total 16.0 19.9 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-6 7.6 12.3 4B2-13 2.1 2.1 4B3-6 6.8 0.2 4B3-13 3.9 7.1 4B4-6 4.7 4.7 4B4-13 4.4 4.4 Note: Transformer Total 19.1 17.2 Transformer Total 10.4 13.6 4B7-14 4B3-4 needs to be connected to another circuit. SUGARMILL BREAKERS CITY BREAKERS 4B3-44B4-44B3-144B4-144B6-14 RACK BREAKERS MILLIGAN BREAKERS HATCH BREAKERS FIFTEENTH ST. BREAKERS 4B4-3 taking load off of 4B2-4 4B2-17 taking load off of 4B3-6 4B2-6 taking load off of 4B3-12 4B2-4 transferring to 4B3-12 4B3-4 powered through 4B4-4 4B4-4 transferring to 4B6-12 4B3-14 transferring to 4B6-1 4B4-14 transferring to 4B6-14 4B5-14 shut off 4B3-13 taking load off of 4B3-9 4B3-9 taking load off of 4B5-1 4B6-14 transferring to 4B2-1 4B7-14 transferring to 4B3-1 SWITCHING PROCEDURE TEMPLEVIEW BREAKERS YORK ROAD BREAKERS N. BOULEVARD 5T1-12 BREAKERS N. BOULEVARD 5T1-12 BREAKERS 4B2-4
  • 37. N-2 Substation Switching Study 36 5.2.14 Templeview & Harrison Templeview’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H58 CLOSED 4B2-4 7.7 0.0 4B2-16 2.2 0.0 4H55 OPEN 4B3-4 0.6 0.0 4B3-16 6.7 0.0 4H9 CLOSED 4B4-4 2.4 0.0 4B4-16 4.6 0.0 4H44 OPEN 4B5-16 0.6 0.0 4H45 CLOSED 4H2 OPEN Transformer Total 10.7 0.0 Transformer Total 14.1 0.0 4H1 CLOSED 4B2-4 OPEN 4H3-4 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H4-4 CLOSED 4B4-12 0.0 0.0 4B7-12 0.8 0.8 4B3-4 OPEN 4B3-12 11.0 10.7 4B6-12 8.3 11.3 4H31 CLOSED 4B2-12 2.1 2.1 4B4-4 OPEN 4D13 CLOSED 4B2-16 OPEN Transformer Total 13.1 12.8 Transformer Total 9.1 12.1 4H8 CLOSED 4H3 OPEN 4H7 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H43 OPEN 4B6-1 0.9 0.9 4B3-14 0.7 0.7 4H49 CLOSED 4B5-1 7.1 7.1 4B4-14 6.8 6.8 4H42 OPEN 4B4-1 0.5 0.5 4B5-14 0.0 0.0 4H21 CLOSED 4B3-1 6.2 12.2 4B6-14 2.9 2.9 4B3-16 OPEN 4B2-1 0.9 0.9 4B7-14 1.8 2.6 4D85 CLOSED Transformer Total 15.6 21.6 Transformer Total 12.2 13.0 4D72 OPEN 4H20 CLOSED 4B4-16 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4D54 CLOSED 4B4-17 12.0 9.0 4B2-9 7.8 7.8 4B5-16 OPEN 4B3-17 1.0 1.0 4B3-9 8.2 8.0 4B2-17 2.2 8.8 Switching Description: Transformer Total 15.2 18.8 Transformer Total 16.0 15.8 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-6 7.6 9.5 4B2-13 2.1 2.1 4B3-6 6.8 0.2 4B3-13 3.9 9.9 4B4-6 4.7 12.0 4B4-13 4.4 7.7 Transformer Total 19.1 21.7 Transformer Total 10.4 19.7 Note: 4B3-4 needs to be connected to another circuit. HATCH BREAKERS FIFTEENTH ST. BREAKERS SUGARMILL BREAKERS CITY BREAKERS 4B5-164B4-164B3-16 4B3-9 taking load off of 4B3-12 4B4-13 taking load off of 4B3-12 4B2-6 taking load off of 4B3-12 4B2-4 transferring to 4B3-12 4B3-4 powered through 4B4-4 4B4-4 transferring to 4B6-12 4B2-16 transferring to 4B4-16 4B3-13 taking load off of 4B3-9 4B3-9 taking load off of 4B4-17 4B2-17 taking load off of 4B3-6 4B3-16 transferring to 4B4-6 4B7-14 taking load off of 4B3-1 4B4-16 transferring to 4B3-1 4B5-16 transferring to 4B4-6 4B3-44B4-44B2-16 RACK BREAKERS YORK BREAKERS SWITCHING PROCEDURE TEMPLEVIEW BREAKERS HARRISON BREAKERS 4B2-4 N. BOULEVARD 5T1-12 BREAKERS N. BOULEVARD 5T1-12 BREAKERS
  • 38. N-2 Substation Switching Study 37 5.2.15 Templeview & Hatch Templeview’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H58 CLOSED 4B2-4 7.7 0.0 4B4-17 12.0 0.0 4H55 OPEN 4B3-4 0.6 0.0 4B3-17 1.0 0.0 4H9 CLOSED 4B4-4 2.4 0.0 4B2-17 2.2 0.0 4H44 OPEN 4H1 CLOSED 4B2-4 OPEN Transformer Total 10.7 0.0 Transformer Total 15.2 0.0 4H3-4 CLOSED 4H4-4 CLOSED 4B3-4 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H31 CLOSED 4B4-12 0.0 0.0 4B7-12 0.8 0.8 4B1-4 OPEN 4B3-12 11.0 12.6 4B6-12 8.3 11.3 4H49 CLOSED 4B2-12 2.1 2.1 4B2-17 OPEN 4H5 CLOSED 4B3-17 OPEN Transformer Total 13.1 14.7 Transformer Total 9.1 12.1 4H26 CLOSED 4H40 OPEN 4H8 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H3 OPEN 4B2-6 7.6 8.6 4B2-13 2.1 2.1 4H7 CLOSED 4B3-6 6.8 9.0 4B3-13 3.9 9.9 4B4-17 OPEN 4B4-6 4.7 4.7 4B4-13 4.4 7.7 Switching Description: Transformer Total 19.1 22.3 Transformer Total 10.4 19.7 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-16 2.2 2.2 4B2-9 7.8 7.8 4B3-16 6.7 6.7 4B3-9 8.2 11.2 4B4-16 4.6 10.4 4B5-16 0.6 0.6 Note: Transformer Total 14.1 19.9 Transformer Total 16.0 19.0 4B3-9 taking load off of 4B3-12 4B4-13 taking load off of 4B3-12 4B2-4 transferring to 4B3-12 4B3-4 powered through 4B4-4 4B4-4 transferring to 4B6-12 4B2-17 transferring to 4B3-6 4B3-17 transferring to 4B2-6 4B4-16 taking load off of 4B4-17 4B3-13 taking load off of 4B3-9 4B4-17 transferring to 4B3-9 4B3-44B4-4 SUGARMILL BREAKERS 4B3-4 needs to be connected to another circuit. Upgrading the 336 ACSR wire between 4S8 and 4H20 would simplify the switching procedure. CITY BREAKERS HARRISON BREAKERS FIFTEENTH ST. BREAKERS 4B2-174B3-174B4-17 SWITCHING PROCEDURE TEMPLEVIEW BREAKERS HATCH BREAKERS N. BOULEVARD 5T1-12 BREAKERS N. BOULEVARD 5T1-12 BREAKERS 4B2-4
  • 39. N-2 Substation Switching Study 38 5.2.16 Templeview & Westside Templeview’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H41 CLOSED 4B2-4 7.7 0.0 4B3-18 8.8 0.0 4D1 OPEN 4B3-4 0.6 0.0 4H49 CLOSED 4B4-4 2.4 0.0 4H42 OPEN 4H45 CLOSED 4H2 OPEN Transformer Total 10.7 0.0 Transformer Total 8.8 0.0 4H1 CLOSED 4B2-4 OPEN 4H3-4 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H4-4 CLOSED 4B4-12 0.0 0.0 4B7-12 0.8 0.8 4B3-4 OPEN 4B3-12 11.0 11.2 4B6-12 8.3 11.3 4H31 CLOSED 4B2-12 2.1 2.1 4B4-4 OPEN 4H36 CLOSED 4D17 OPEN Transformer Total 13.1 13.3 Transformer Total 9.1 12.1 4H52 CLOSED 4B3-18 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) Switching Description: 4B6-1 0.9 0.9 4B5-3 0.6 9.9 4B5-1 7.1 7.1 4B4-3 9.9 12.7 4B4-1 0.5 0.0 4B3-3 0.6 0.6 4B3-1 6.2 6.2 4B2-1 0.9 0.9 Transformer Total 15.6 15.1 Transformer Total 11.1 23.2 Note: Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-17 12.0 12.0 4B2-6 7.6 12.3 4B3-17 1.0 1.0 4B3-6 6.8 0.2 4B2-17 2.2 8.8 4B4-6 4.7 4.7 Transformer Total 15.2 21.8 Transformer Total 19.1 17.2 4B3-4 needs to be connected to another circuit. 4B3-18 4B4-3 taking load off of 4B2-4 4B2-17 taking load off of 4B3-6 4B2-6 taking load off of 4B3-12 4B2-4 transferring to 4B3-12 4B3-4 powered through 4B4-4 4B4-4 transferring to 4B6-12 4B5-3 taking load off of 4B4-1 4B3-18 transferring to 4B5-3 HATCH BREAKERS SUGARMILL BREAKERS 4B3-44B4-4 RACK BREAKERS MILLIGAN BREAKERS SWITCHING PROCEDURE TEMPLEVIEW BREAKERS WESTSIDE BREAKERS 4B2-4 N. BOULEVARD 5T1-12 BREAKERS N. BOULEVARD 5T1-12 BREAKERS
  • 40. N-2 Substation Switching Study 39 5.2.17 Sugarmill & N. Boulevard N. Boulevard’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4D85 CLOSED 4B7-12 0.8 0.0 4B4-12 0.0 0.0 4D72 OPEN 4B6-12 8.3 0.0 4B3-12 11.0 0.0 4H20 CLOSED 4B2-12 2.1 0.0 4D81 OPEN Transformer Total 9.1 0.0 Transformer Total 13.1 0.0 4H26 CLOSED 4H40 OPEN 4H21 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-6 OPEN 4B2-4 7.7 10.0 4B2-13 2.1 2.1 4H49 CLOSED 4B3-4 0.6 0.6 4B3-13 3.9 3.9 4B3-6 OPEN 4B4-4 2.4 11.5 4B4-13 4.4 7.7 4H5 CLOSED Transformer Total 10.7 22.1 Transformer Total 10.4 13.7 4B2-6 OPEN 4H12-12 CLOSED 4H13-12 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B7-12 OPEN 4B2-9 7.8 7.8 4B4-17 12.0 6.2 4H31 CLOSED 4B3-9 8.2 12.9 4B3-17 1.0 8.6 4B6-12 OPEN 4B2-17 2.2 9.0 4H58 CLOSED Transformer Total 16.0 20.7 Transformer Total 15.2 23.8 4H2 OPEN 4H9 CLOSED 4H44 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H41 CLOSED 4B3-14 0.7 0.7 4B5-3 0.6 0.6 4D1 OPEN 4B4-14 6.8 6.8 4B4-3 9.9 12.7 4H1 CLOSED 4B5-14 0.0 0.0 4B3-3 0.6 0.6 4B3-12 OPEN 4B6-14 2.9 2.9 OLD CUTOUT CLOSED 4B7-14 1.8 2.6 4B2-12 OPEN Transformer Total 12.2 13.0 Transformer Total 11.1 13.9 Switching Description: Breaker ID Initial Power Resulting Power Breaker ID Initial Power Resulting Power 4B2-6 7.6 0.0 4B2-16 2.2 2.2 4B3-6 6.8 0.0 4B3-16 6.7 11.4 4B4-6 4.7 0.0 4B4-16 4.6 3.0 4B5-16 0.6 0.6 Transformer Total 19.1 0.0 Transformer Total 14.1 17.2 Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B6-1 0.9 0.9 4B5-1 7.1 7.1 4B4-1 0.5 0.5 4B3-1 6.2 12.8 Note: 4B2-1 0.9 0.9 Old Cutout needs to be a switch. Transformer Total 15.6 22.2 RACK BREAKERS TEMPLEVIEW BREAKERS CITY BREAKERS HARRISON BREAKERS SWITCHING PROCEDURE N. BOULEVARD 5T2-12 BREAKERS N. BOULEVARD 5T1-12 BREAKERS SUGARMILL BREAKERS 4B3-12 4B3-1 taking load off of 4B7-14 4B4-16 taking load off of 4B3-1 4B4-16 taking load off of 4B4-17 4B4-6 transferring to 4B3-16 4B3-6 transferring to 4B2-17 4B2-6 transferring to 4B3-17 4B7-12 transferring to 4B6-12 4B6-12 transferring to 4B4-4 4B3-9 taking load off of 4B3-12 4B4-13taking load off of 4B3-12 4B4-3taking load off of 4B2-4 4B3-12 transferring to 4B2-4 4B2-12 transferring to 4B2-4 YORK ROAD BREAKERS MILLIGAN BREAKERS 4B4-64B3-64B7-124B6-124B2-124B2-6 FIFTEENTH ST. BREAKERS HATCH BREAKERS
  • 41. N-2 Substation Switching Study 40 5.2.18 Sugarmill & City City’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H5 CLOSED 4B2-6 7.6 0.0 4B2-13 2.1 0.0 4B2-6 OPEN 4B3-6 6.8 0.0 4B3-13 3.9 0.0 4H26 CLOSED 4B4-6 4.7 0.0 4B4-13 4.4 0.0 4H40 OPEN 4H49 CLOSED 4B3-6 OPEN Transformer Total 19.1 0.0 Transformer Total 10.4 0.0 4H21 CLOSED 4B4-6 OPEN 4H16 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-13 OPEN 4B4-17 12.0 6.2 4B2-9 7.8 7.8 4B2-4 4B2-4 CLOSED 4B3-17 1.0 8.6 4B3-9 8.2 12.6 4H46 CLOSED 4B2-17 2.2 9.0 4B1-13 OPEN Switching Description: Transformer Total 15.2 23.8 Transformer Total 16.0 20.4 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B5-3 0.6 0.6 4B2-16 2.2 2.2 4B4-3 9.9 9.9 4B3-16 6.7 11.4 4B3-3 0.6 6.6 4B4-16 4.6 10.4 Note: 4B5-16 0.6 0.6 Transformer Total 11.1 17.1 Transformer Total 14.1 24.6 4B2-13 needs to be powered through another circuit. 4B2-64B3-64B4-64B4-134B3-13 4B2-6 transferring to 4B3-17 4B4-16 taking load off of 4B4-17 4B3-6 transferring to 4B2-17 4B4-6 transferring to 4B3-16 4B4-13 transferring to 4B3-9 4B2-13 powered through 4B3-13 4B3-13 transferring to MILLIGAN BREAKERS HARRISON BREAKERS SWITCHING PROCEDURE SUGARMILL BREAKERS CITY BREAKERS HATCH BREAKERS FIFTEENTH ST. BREAKERS
  • 42. N-2 Substation Switching Study 41 5.2.19 Fifteenth St. & N. Boulevard N. Boulevard’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H20 CLOSED 4B7-12 0.8 0.0 4B4-12 0.0 0.0 4D52 OPEN 4B6-12 8.3 0.0 4B3-12 11.0 0.0 4H12 CLOSED 4B2-12 2.1 0.0 4D12 OPEN 4D85 CLOSED 4D73 OPEN Transformer Total 9.1 0.0 Transformer Total 13.1 0.0 4H13 CLOSED 4B2-9 OPEN 4H8 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H3 OPEN 4B2-9 7.8 0.0 4B2-4 7.7 10.0 4H10 CLOSED 4B3-9 8.2 0.0 4B3-4 0.6 0.6 4B3-9 OPEN 4B4-4 2.4 11.5 4H58 CLOSED 4H55 OPEN OLD CUTOUT CLOSED Transformer Total 16.0 0.0 Transformer Total 10.7 22.1 4B2-12 OPEN 4H45 CLOSED 4H2 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H9 CLOSED 4B2-6 7.6 9.5 4B5-3 0.6 0.6 4H44 OPEN 4B3-6 6.8 6.8 4B4-3 9.9 12.7 4H41 CLOSED 4B4-6 4.7 4.7 4B3-3 0.6 0.6 4D1 OPEN 4H1 CLOSED 4B3-12 OPEN Transformer Total 19.1 21.0 Transformer Total 11.1 13.9 4H31 CLOSED 4B6-12 OPEN 4H12-12 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H13-12 CLOSED 4B3-14 0.7 0.7 4B6-1 0.9 0.9 4B7-12 OPEN 4B4-14 6.8 6.8 4B5-1 7.1 12.1 4B5-14 0.0 0.0 4B4-1 0.5 0.5 Switching Description: 4B6-14 2.9 2.9 4B3-1 6.2 3.9 4B7-14 1.8 9.5 4B2-1 0.9 0.9 Transformer Total 12.2 19.9 Transformer Total 15.6 18.3 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-13 2.1 2.1 4B2-16 2.2 2.2 4B3-13 3.9 9.9 4B3-16 6.7 6.7 4B4-13 4.4 7.7 4B4-16 4.6 7.0 4B5-16 0.6 0.6 Transformer Total 10.4 19.7 Transformer Total 14.1 16.5 Note: Old Cutout needs to be a switch. 4B2-12 RACK BREAKERSYORK ROAD BREAKERS SUGARMILL BREAKERS TEMPLEVIEW BREAKERS CITY BREAKERS HARRISON BREAKERS 4B2-94B3-9 4B4-16 taking load off of 4B3-1 4B4-16 taking load off of 4B2-9 4B7-14 taking load off of 4B3-1 4B2-9 transferring to 4B7-14 4B3-13 taking load off of 4B3-9 4B3-9 transferring to 4B5-1 4B3-13 taking load off of 4B3-12 4B2-12 transferring to 4B3-12 4B2-6 taking load off of 4B3-12 4B4-13 taking load off of 4B3-12 4B4-3 taking load off of 4B2-4 4B3-12 transferring to 4B2-4 4B6-12 transferring to 4B4-4 4B7-12 transferring to 4B4-4 SWITCHING PROCEDURE N. BOULEVARD 5T2-12 BREAKERS N. BOULEVARD 5T1-12 BREAKERS FIFTEENTH ST. BREAKERS MILLIGAN BREAKERS 4B3-124B6-124B7-12
  • 43. N-2 Substation Switching Study 42 5.2.20 Fifteenth St. & City City’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H20 CLOSED 4B2-9 7.8 0.0 4B2-13 2.1 0.0 4D52 OPEN 4B3-9 8.2 0.0 4B3-13 3.9 0.0 4H12 CLOSED 4B4-13 4.4 0.0 4D12 OPEN 4H13 CLOSED 4B2-9 OPEN Transformer Total 16.0 0.0 Transformer Total 10.4 0.0 4H26 CLOSED 4S8 OPEN 4H49 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H42 OPEN 4B6-1 0.9 0.9 4B4-12 0.0 0.0 4D16 CLOSED 4B5-1 7.1 7.1 4B3-12 11.0 10.7 4D69 OPEN 4B4-1 0.5 0.5 4B2-12 2.1 2.1 4H7 CLOSED 4B3-1 6.2 11.6 4B3-9 OPEN 4B2-1 0.9 0.9 4H45 CLOSED Transformer Total 15.6 21.0 Transformer Total 13.1 12.8 4H2 OPEN 4H9 CLOSED 4B4-13 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H46 CLOSED 4B2-6 7.6 12.3 4B4-17 12.0 12.8 4B1-13 OPEN 4B3-6 6.8 0.2 4B3-17 1.0 1.0 4B4-6 4.7 9.9 4B2-17 2.2 8.8 Switching Description: Transformer Total 19.1 22.4 Transformer Total 15.2 22.6 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-16 2.2 2.2 4B5-3 0.6 0.6 4B3-16 6.7 6.7 4B4-3 9.9 9.9 4B4-16 4.6 9.2 4B3-3 0.6 6.6 4B5-16 0.6 0.6 Note: Transformer Total 14.1 18.7 Transformer Total 11.1 17.1 SUGARMILL BREAKERS HATCH BREAKERS HARRISON BREAKERS MILLIGAN BREAKERS SWITCHING PROCEDURE FIFTEENTH ST. BREAKERS CITY BREAKERS RACK BREAKERS N. BOULEVARD 5T1-12 BREAKERS 4B2-94B3-94B4-134B2-13&4B3-13 4B4-16 taking load off of 4B3-1 4B4-16 taking load off of 4B2-9 4B2-9 transferring to 4B3-1 4B4-16 taking load off of 4B4-17 4B2-17 taking load off of 4B3-6 4B4-6 taking load off of 4B4-17 4B3-9 transferring to 4B4-17 4B2-6 taking load off of 4B3-12 4B4-13 transferring to 4B3-12 4B2-13 powered through 4B3-13 4B3-13 transferring to 4B3-3 4B2-13 needs to be connected to another circuit.
  • 44. N-2 Substation Switching Study 43 5.2.21 Fifteenth St. & Hatch Hatch’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H13 CLOSED 4B2-9 7.8 0.0 4B4-17 12.0 0.0 4H47 OPEN 4B3-9 8.2 0.0 4B3-17 1.0 0.0 4H30 CLOSED 4B2-17 2.2 0.0 4B2-9 OPEN 4H16 CLOSED 4H19 OPEN Transformer Total 16.0 0.0 Transformer Total 15.2 0.0 4H8 CLOSED 4B3-9 OPEN 4B5-17 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H2-17 CLOSED 4B6-1 0.9 0.9 4B4-12 0.0 0.0 4H3-17 CLOSED 4B5-1 7.1 11.2 4B3-12 11.0 11.8 4B2-17 OPEN 4B4-1 0.5 0.5 4B2-12 2.1 2.1 4H5 CLOSED 4B3-1 6.2 9.9 4B3-17 OPEN 4B2-1 0.9 0.9 4H26 CLOSED Transformer Total 15.6 23.4 Transformer Total 13.1 13.9 4H40 OPEN 4H9 CLOSED 4H44 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H45 CLOSED 4B2-6 7.6 6.7 4B2-16 2.2 2.2 4H4 OPEN 4B3-6 6.8 13.0 4B3-16 6.7 6.7 4H28 CLOSED 4B4-6 4.7 4.7 4B4-16 4.6 10.4 4B4-17 OPEN 4B5-16 0.6 0.6 Switching Description: Transformer Total 19.1 24.4 Transformer Total 14.1 19.9 Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-13 2.1 2.1 4B3-13 3.9 9.5 4B4-13 4.4 10.3 Transformer Total 10.4 21.9 HARRISON BREAKERS CITY BREAKERS SWITCHING PROCEDURE FIFTEENTH ST. BREAKERS HATCH BREAKERS RACK BREAKERS N. BOULEVARD 5T1-12 BREAKERS 4B2-94B3-94B2-174B3-174B4-17 4B3-1 taking load off of 4B2-9 4B2-9 transferring to 4B5-1 4B4-13 taking load off of 4B3-9 4B3-9 transferring to 4B3-13 4B2-17 transferring to 4B3-17 4B3-17 transferring to 4B2-6 4B4-16 taking load off of 4B4-17 4B4-13 taking load off of 4B3-12 4B3-12 taking load off of 4B2-6 4B4-17 transferring to 4B3-6 SUGARMILL BREAKERS
  • 45. N-2 Substation Switching Study 44 5.2.22 N. Boulevard & York Road N. Boulevard’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H58 CLOSED 4B7-12 0.8 0.0 4B4-12 0.0 0.0 4H55 OPEN 4B6-12 8.3 0.0 4B3-12 11.0 0.0 OLD CUTOUT CLOSED 4B2-12 2.1 0.0 4B2-12 OPEN 4H8 CLOSED 4H3 OPEN Transformer Total 9.1 0.0 Transformer Total 13.1 0.0 4H45 CLOSED 4H2 OPEN 4H9 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H44 OPEN 4B2-4 7.7 10.0 4B2-13 2.1 2.1 4H41 CLOSED 4B3-4 0.6 0.6 4B3-13 3.9 9.9 4D1 OPEN 4B4-4 2.4 11.5 4B4-13 4.4 7.7 4H1 CLOSED 4B3-12 OPEN 4H31 CLOSED Transformer Total 10.7 22.1 Transformer Total 10.4 19.7 4B6-12 OPEN 4H12-12 CLOSED 4H13-12 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B7-12 OPEN 4B2-9 7.8 7.8 4B2-6 7.6 9.5 4H53 CLOSED 4B3-9 8.2 5.0 4B3-6 6.8 6.8 4B3-14 OPEN 4B4-6 4.7 4.7 4D51 CLOSED 4B4-14 OPEN 4B5-14 4B5-14 OPEN Transformer Total 16.0 12.8 Transformer Total 19.1 21.0 4H33 CLOSED 4B6-14 OPEN 4H20 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H27 OPEN 4B3-14 0.7 0.0 4B5-3 0.6 0.6 4D85 CLOSED 4B4-14 6.8 0.0 4B4-3 9.9 12.7 4B7-14 OPEN 4B5-14 0.0 0.0 4B3-3 0.6 0.6 4B6-14 2.9 0.0 Switching Description: 4B7-14 1.8 0.0 Transformer Total 12.2 0.0 Transformer Total 11.1 13.9 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-16 2.2 2.2 4B6-1 0.9 1.6 4B3-16 6.7 6.7 4B5-1 7.1 7.1 4B4-16 4.6 12.0 4B4-1 0.5 0.5 4B5-16 0.6 0.6 4B3-1 6.2 0.6 4B2-1 0.9 10.6 Transformer Total 14.1 21.5 Transformer Total 15.6 20.4 Note: 4B3-144B4-144B6-144B7-14 YORK ROAD BREAKERS MILLIGAN BREAKERS HARRISON BREAKERS RACK BREAKERS 4B3-9 taking load off of 4B3-12 4B2-12 transferring to 4B3-12 4B3-13 taking load off of 4B3-9 4B2-6 taking load off of 4B3-12 4B4-14 taking load off of 4B3-12 4B4-3 taking load off of 4B2-4 4B3-12 transferring to 4B2-4 4B6-12 transferring to 4B4-4 4B7-12 transferring to 4B4-4 4B3-14 transferring to 4B6-1 4B4-14 transferring to 4B6-14 4B5-14 shut off 4B6-14 transferring to 4B2-1 4B4-16 taking load off of 4B3-1 4B7-14 transferring to 4B4-16 4B7-12 needs to be connected to another circuit. Old Cutout needs to be a switch. 4B3-12 TEMPLEVIEW BREAKERS CITY BREAKERS 4B6-124B7-12 FIFTEENTH ST. BREAKERS SUGARMILL BREAKERS SWITCHING PROCEDURE N. BOULEVARD 5T2-12 BREAKERS N. BOULEVARD 5T1-12 BREAKERS 4B2-12
  • 46. N-2 Substation Switching Study 45 5.2.23 N. Boulevard & Harrison N. Boulevard’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H58 CLOSED 4B7-12 0.8 0.0 4B4-12 0.0 0.0 4H55 OPEN 4B6-12 8.3 0.0 4B3-12 11.0 0.0 OLD CUTOUT CLOSED 4B2-12 2.1 0.0 4B2-12 OPEN 4H8 CLOSED 4H3 OPEN Transformer Total 9.1 0.0 Transformer Total 13.1 0.0 4H45 CLOSED 4H2 OPEN 4H9 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H44 OPEN 4B2-16 2.2 0.0 4B2-13 2.1 2.1 4H41 CLOSED 4B3-16 6.7 0.0 4B3-13 3.9 9.9 4D1 OPEN 4B4-16 4.6 0.0 4B4-13 4.4 7.7 4H1 CLOSED 4B5-16 0.6 0.0 4B3-12 OPEN 4H31 CLOSED Transformer Total 14.1 0.0 Transformer Total 10.4 19.7 4B6-12 OPEN 4H12-12 CLOSED 4H13-12 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B7-12 OPEN 4B2-9 7.8 7.8 4B2-6 7.6 9.5 4D85 CLOSED 4B3-9 8.2 8.0 4B3-6 6.8 0.2 4D72 OPEN 4B4-6 4.7 12.0 4H7 CLOSED 4H43 OPEN 4H49 CLOSED Transformer Total 16.0 15.8 Transformer Total 19.1 21.7 4H42 OPEN 4D13 CLOSED 4B2-16 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H21 CLOSED 4B3-14 0.7 0.7 4B5-3 0.6 0.6 4B3-16 OPEN 4B4-14 6.8 6.8 4B4-3 9.9 12.7 4H20 CLOSED 4B5-14 0.0 0.0 4B3-3 0.6 0.6 4B4-16 OPEN 4B6-14 2.9 2.9 4D54 CLOSED 4B7-14 1.8 2.6 4B5-16 OPEN Transformer Total 12.2 13.0 Transformer Total 11.1 13.9 Switching Description: Breaker ID Initial Power Resulting Power Breaker ID Initial Power Resulting Power 4B2-4 7.7 10.0 4B4-17 12.0 9.0 4B3-4 0.6 0.6 4B3-17 1.0 1.0 4B4-4 2.4 11.5 4B2-17 2.2 8.8 Transformer Total 10.7 22.1 Transformer Total 15.2 18.8 Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B6-1 0.9 0.9 4B5-1 7.1 7.1 4B4-1 0.5 0.5 4B3-1 6.2 12.2 4B2-1 0.9 0.9 Note: Transformer Total 15.6 21.6 4B4-16 YORK ROAD BREAKERS MILLIGAN BREAKERS 4B2-164B5-164B3-16 4B7-12 needs to be connected to another circuit. Old Cutout needs to be a switch. 4B3-9 taking load off of 4B3-12 4B2-12 transferring to 4B3-12 4B3-13 taking load off of 4B3-9 4B2-6 taking load off of 4B3-12 4B4-14 taking load off of 4B3-12 4B4-3 taking load off of 4B2-4 4B3-12 transferring to 4B2-4 4B6-12 transferring to 4B4-4 4B7-12 transferring to 4B4-4 4B7-14 taking load off of 4B3-1 4B3-9 taking load off of 4B4-17 4B2-17 taking load off of 4B3-6 4B2-16 transferring to 4B4-16 4B3-16 transferring to 4B4-6 4B4-16 transferring to 4B3-1 4B5-16 transferring to 4B4-6 4B7-12 FIFTEENTH ST. BREAKERS SUGARMILL BREAKERS RACK BREAKERS SWITCHING PROCEDURE N. BOULEVARD 5T2-12 BREAKERS N. BOULEVARD 5T1-12 BREAKERS HARRISON BREAKERS 4B2-124B3-12 TEMPLEVIEW BREAKERS CITY BREAKERS HATCH BREAKERS 4B6-12
  • 47. N-2 Substation Switching Study 46 5.2.24 N. Boulevard & Hatch N. Boulevard’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H58 CLOSED 4B7-12 0.8 0.0 4B4-12 0.0 0.0 4H55 OPEN 4B6-12 8.3 0.0 4B3-12 11.0 0.0 OLD CUTOUT CLOSED 4B2-12 2.1 0.0 4B2-12 OPEN 4H8 CLOSED 4H3 OPEN Transformer Total 9.1 0.0 Transformer Total 13.1 0.0 4H45 CLOSED 4H2 OPEN 4H9 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H44 OPEN 4B4-17 12.0 0.0 4B2-13 2.1 2.1 4H41 CLOSED 4B3-17 1.0 0.0 4B3-13 3.9 9.9 4D1 OPEN 4B2-17 2.2 0.0 4B4-13 4.4 7.7 4H1 CLOSED 4B3-12 OPEN Transformer Total 15.2 0.0 Transformer Total 10.4 19.7 4H31 CLOSED 4B6-12 OPEN 4H12-12 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H13-12 CLOSED 4B2-9 7.8 7.8 4B2-6 7.6 10.5 4B7-12 OPEN 4B3-9 8.2 11.2 4B3-6 6.8 9.0 4H21 CLOSED 4B4-6 4.7 0.0 4D5 OPEN Transformer Total 16.0 19.0 Transformer Total 19.1 19.5 4H49 CLOSED 4B2-17 OPEN 4H5 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B3-17 OPEN 4B3-14 0.7 0.7 4B5-3 0.6 0.6 4D85 CLOSED 4B4-14 6.8 6.8 4B4-3 9.9 12.7 4D73 OPEN 4B5-14 0.0 0.0 4B3-3 0.6 0.6 4H20 CLOSED 4B6-14 2.9 2.9 4H40 OPEN 4B7-14 1.8 11.5 4H7 CLOSED Transformer Total 12.2 21.9 Transformer Total 11.1 13.9 4B4-17 OPEN Switching Description: Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-16 2.2 2.2 4B6-1 0.9 0.9 4B3-16 6.7 11.4 4B5-1 7.1 7.1 4B4-16 4.6 3.0 4B4-1 0.5 0.5 4B5-16 0.6 0.6 4B3-1 6.2 3.9 4B2-1 0.9 0.9 Transformer Total 14.1 17.2 Transformer Total 15.6 13.3 Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-4 7.7 10.0 4B3-4 0.6 0.6 4B4-4 2.4 11.5 Transformer Total 10.7 22.1 Note: Old Cutout needs to be a switch. 4B4-17 RACK BREAKERS YORK ROAD BREAKERS MILLIGAN BREAKERS 4B7-124B2-174B3-17 FIFTEENTH ST. BREAKERS SUGARMILL BREAKERS 4B3-9 taking load off of 4B3-12 4B2-12 transferring to 4B3-12 4B3-13 taking load off of 4B3-9 4B2-6 taking load off of 4B3-12 4B4-14 taking load off of 4B3-12 4B4-3 taking load off of 4B2-4 4B3-12 transferring to 4B2-4 4B6-12 transferring to 4B4-4 4B7-12 transferring to 4B4-4 4B3-16 taking load off of 4B4-6 4B2-17 transferring to 4B3-6 4B3-17 transferring to 4B2-6 4B7-14 taking load off of 4B3-1 4B7-14 taking load off of 4B4-17 4B4-17 transferring to 4B3-9 4B3-124B6-12 SWITCHING PROCEDURE N. BOULEVARD 5T2-12 BREAKERS N. BOULEVARD 5T1-12 BREAKERS HATCH BREAKERS TEMPLEVIEW BREAKERS CITY BREAKERS HARRISON BREAKERS 4B2-12
  • 48. N-2 Substation Switching Study 47 5.2.25 N. Boulevard & Westside N. Boulevard’s aux bus needs to be online for this procedure. Switch Status Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H9 CLOSED 4B7-12 0.8 0.0 4B4-12 0.0 0.0 4H44 OPEN 4B6-12 8.3 0.0 4B3-12 11.0 0.0 OLD CUTOUT CLOSED 4B2-12 2.1 0.0 4B2-12 OPEN Transformer Total 9.1 0.0 Transformer Total 13.1 0.0 4H26 CLOSED 4H40 OPEN 4H5 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H6 OPEN 4B3-18 8.8 0.0 4B5-3 0.6 9.9 4H58 CLOSED 4B4-3 9.9 9.9 4H55 OPEN 4B3-3 0.6 0.6 4H45 CLOSED Transformer 8.8 0.0 Transformer 11.1 20.4 4B3-12 OPEN 4H31 CLOSED 4B6-12 OPEN Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4H12-12 CLOSED 4B2-9 7.8 7.8 4B2-6 7.6 3.5 4H13-12 CLOSED 4B3-9 8.2 11.0 4B3-6 6.8 6.8 4B7-12 OPEN 4B4-6 4.7 4.7 4H36 OPEN Transformer Total 16.0 18.8 Transformer Total 19.1 15.0 4D17 CLOSED 4H52 OPEN 4B3-18 CLOSED Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-13 2.1 2.1 4B2-4 7.7 7.7 Switching Description: 4B3-13 3.9 3.9 4B3-4 0.6 0.6 4B4-13 4.4 7.7 4B4-4 2.4 11.5 Transformer Total 10.4 13.7 Transformer Total 10.7 19.8 Breaker ID Initial Power (in MW) Resulting Power (in MW) Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B2-16 2.2 2.2 4B6-1 0.9 0.9 4B3-16 6.7 6.7 4B5-1 7.1 7.1 Note: 4B4-16 4.6 10.4 4B4-1 0.5 0.0 4B5-16 0.6 0.6 4B3-1 6.2 6.2 4B2-1 0.9 0.9 Transformer Total 14.1 19.9 Transformer Total 15.6 15.1 Breaker ID Initial Power (in MW) Resulting Power (in MW) 4B4-17 12.0 6.2 4B3-17 1.0 12.1 4B2-17 2.2 2.2 Transformer Total 15.2 20.5 SUGARMILL BREAKERS CITY BREAKERS TEMPLEVIEW BREAKERS HARRISON BREAKERS RACK BREAKERS SWITCHING PROCEDURE N. BOULEVARD 5T2-12 BREAKERS N. BOULEVARD 5T1-12 BREAKERS WESTSIDE BREAKERS MILLIGAN BREAKERS 4B2-124B3-124B7-124B6-124B3-18 4B4-13 taking load off of 4B3-12 4B2-12 transferring to 4B3-12 4B4-16 taking load off of 4B4-17 4B3-17 taking load off of 4B2-6 4B3-12 transferring to 4B3-17 & 4B3-9 4B6-12 transferring to 4B4-4 4B7-12 transferring to 4B4-4 4B5-3 taking load off of 4B4-1 4B3-18 transferring to 4B5-3 HATCH BREAKERS FIFTEENTH ST. BREAKERS 4B7-12 needs to be connected to another circuit. Old Cutout needs to be a switch. Connect 4B7-12 to 4R7.