Carel Industries S.p.A.
Improved oil level detection and equalization system for
CO2 high pressure shell hermetic rotary compressor
Giovanni ROSSANESE, Luca MATTIELLO, Willy MUVEGI, Luigi NALINI
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Outline
• Introduction
• Working principle
• Test Rig Description
• Oil Presence Detection– Logic & Test Results
• Oil Equalization Procedure – Logic & Test Results
• Conclusions
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Introduction
• BLDC rotary compressors
→ efficiency and cost effectiveness
→ small/medium cooling capacities → compressor racks
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Introduction
• BLDC rotary compressors
→ efficiency and cost effectiveness
→ small/medium cooling capacities → compressor racks
• Low pressure and low temperature
• Oil is injected into the shell directly
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Introduction
• BLDC rotary compressors
→ efficiency and cost effectiveness
→ small/medium cooling capacities → compressor racks
• Low pressure and low temperature
• Oil is injected into the shell directly
• High pressure and high temperature
• Oil is withdrawn from the shell
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Working Principle
• Expansion of oil/CO2 mixture
2
4
6
8
10
12
200 300 400 500 600
Pressure[MPa]
Enthalpy [kJ/kg]
< 𝑇𝑖𝑛 𝐶𝑂2
𝑇𝑜𝑢𝑡
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Working Principle
• Expansion of oil/CO2 mixture
2
4
6
8
10
12
200 300 400 500 600
Pressure[MPa]
Enthalpy [kJ/kg]
< 𝑇𝑖𝑛 𝐶𝑂2
≈ 𝑇𝑖𝑛 𝑂𝑖𝑙
𝑇𝑜𝑢𝑡
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Working Principle
• Expansion of oil/CO2 mixture
• It requires flow control devices
• Modulating valve is installed at the
compressor oil balance pipe
𝑙𝑜𝑤 𝑓𝑙𝑜𝑤 → 𝑑𝑒𝑡𝑒𝑐𝑡𝑖𝑜𝑛
ℎ𝑖𝑔ℎ 𝑓𝑙𝑜𝑤 → 𝑒𝑞𝑢𝑎𝑙𝑖𝑧𝑎𝑡𝑖𝑜𝑛
2
4
6
8
10
12
200 300 400 500 600
Pressure[MPa]
Enthalpy [kJ/kg]
< 𝑇𝑖𝑛 𝐶𝑂2
≈ 𝑇𝑖𝑛 𝑂𝑖𝑙
𝑇𝑜𝑢𝑡
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Test Rig Description
• CO2 booster system with air-cooled gas
cooler
• Standard industrial control boards,
equipment and instrumentations
• MT/LT – 30 kW/6kW
• PAG oil ISO VG100
• Sight glasses for visual inspection
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Test Rig Description
0
10
20
30
40
50
60
70
80
90
100
0:00 0:30 1:00 1:30 2:00 2:30 3:00 3:30 4:00 4:30 5:00 5:30 6:00 6:30 7:00
Temperature[°C]
DeltaTemperature[K]
Time [mm:ss]
Oil Valve Inlet Temp
Oil Valve ΔT calc
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Oil Presence Detection
• Control predicts the pure CO2 temperature drop at given pressures
by modelling an isenthalpic expansion
(Inputs) 𝑇𝑖𝑛, 𝑃𝑑𝑖s, 𝑃𝑠𝑢𝑐𝑡 → (Output) Δ𝑇𝑐𝑎𝑙𝑐
Rot speed [Hz] = 43 – 48
𝑃𝑑𝑖𝑠𝑐ℎ [MPa] = 7.8
𝑃𝑠𝑢𝑐𝑡 [MPa] = 2.8
0
10
20
30
40
50
60
70
80
90
100
0:00 0:30 1:00 1:30 2:00 2:30 3:00 3:30 4:00 4:30 5:00 5:30 6:00 6:30 7:00
Temperature[°C]
DeltaTemperature[K]
Time [mm:ss]
Oil Valve Inlet Temp
Oil Valve ΔT exp
Oil Valve ΔT calc
Threshold ΔTcalc/n
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Oil Presence Detection
• Control predicts the pure CO2 temperature drop at given pressures
by modelling an isenthalpic expansion
(Inputs) 𝑇𝑖𝑛, 𝑃𝑑𝑖s, 𝑃𝑠𝑢𝑐𝑡 → (Output) Δ𝑇𝑐𝑎𝑙𝑐
• Gradually closing of the valve OD until Δ𝑇𝑒𝑥𝑝 is below the threshold
• Valve OD range 85.4 – 31.3%
Δ𝑇𝑒𝑥𝑝 <
Δ𝑇𝑐𝑎𝑙𝑐
𝑛
Rot speed [Hz] = 43 – 48
𝑃𝑑𝑖𝑠𝑐ℎ [MPa] = 7.8
𝑃𝑠𝑢𝑐𝑡 [MPa] = 2.8
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Test – Working Conditions
MT1 MT2 MT3 MT4 MT5 LT1 LT2
𝑇𝑒𝑣 [°C] -5.0 -5.0 -8.0 -11.0 -15.0 -25.0 -35.0
𝑃𝑑𝑖𝑠 [MPa] 8.0 6.5 9.8 8.0 6.5 2.7 2.7
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
0.6 1.0 1.4 1.8 2.2 2.6 3.0 3.4 3.8 4.2
DischargePressure[MPa]
Suction Pressure [MPa]
Compressor Envelope
MT
LT
Rotation speed 30/60/90 Hz
MT1
MT2MT5
MT4
MT3
LT1LT2
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Oil Missing Detection – Test & Results
Δ𝑇𝑒𝑥𝑝 ≈ Δ𝑇𝑐𝑎𝑙𝑐
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Oil Missing Detection – Test & Results
Δ𝑇𝑒𝑥𝑝 ≈ Δ𝑇𝑐𝑎𝑙𝑐
MT1 MT2 MT3 MT4 MT5 LT1 LT2
𝑇𝑖𝑛 [°C] 88.8 72.4 128.5 108.4 100.4 59.3 82.6
Δ𝑇𝑒𝑥𝑝 [K] 35.1 28.7 35.5 33.8 27.5 9.4 12.5
dev [K] 2.0 0.6 4.7 1.6 0.7 0.4 0.9
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Oil Presence Detection – Test & Results
↑ 𝐶𝑂2
-------
↓ 𝑂𝑖𝑙
• 201 tests collected (165 for MT, 36 for LT)
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Oil Presence Detection – Test & Results
τ < 30 s < 40 s < 60 s
MT 84.2% 93.3% 98.2%
LT 27.8% 58.3% 88.9%
↑ 𝐶𝑂2
-------
↓ 𝑂𝑖𝑙
• 201 tests collected (165 for MT, 36 for LT)
• Short duration reduces efficiency loss (lower gas by–pass)
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Oil Equalization Procedure
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Oil Equalization Procedure
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Oil Equalization Procedure
• Performed only if more than one compressor active and oil detection ends
with not aligned outcomes
• Oil equalization is directly verified
0%
20%
40%
60%
80%
100%
0:00 1:00 2:00 3:00 4:00 5:00 6:00 7:00 8:00 9:00 10:00
OpeningDegree[%]
Time [mm:ss]
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Oil Equalization Procedure – Test & Results
• Test done by manually
forcing the imbalance
• Low rotation speed is
critical
MT LT
𝒓𝒑𝒔 [𝐇𝐳] ✓ Total ✓ Total
30 2 9 11 4 1 5
60 15 0 15 6 0 6
90 14 1 15 6 0 6
• Detection procedure can act as equalization as well
• If the equalization is not effective ( ) → safe operation by oil
refill from the oil separator
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
Conclusions
• Detection and equalization of oil levels for each compressor
• Simple and reliable method based on temperature
measurement during fluid expansion
• Equalization effectiveness is verified for each compressor
(and not presumed)
• Modulation gives other advantages such as
→ short response time
→ limited gas bypass
→ adaptability to current working conditions
• Life test has to be performed
THANK YOU
Giovanni ROSSANESE, Luca MATTIELLO, Willy MUVEGI, Luigi NALINI
Carel Industries S.p.A.
8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
giovanni.rossanese@carel.com, luca.mattiello@carel.com,
willy.muvegi@carel.com, luigi.nalini@carel.com
International Institute
of Refrigeration
www.iifiir.org
Institute International du
Froid
iif-iir@iifiir.org

Improved oil level detection and equalization system for CO2 high pressure shell hermetic rotary compressor

  • 1.
    Carel Industries S.p.A. Improvedoil level detection and equalization system for CO2 high pressure shell hermetic rotary compressor Giovanni ROSSANESE, Luca MATTIELLO, Willy MUVEGI, Luigi NALINI 8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia
  • 2.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Outline • Introduction • Working principle • Test Rig Description • Oil Presence Detection– Logic & Test Results • Oil Equalization Procedure – Logic & Test Results • Conclusions
  • 3.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Introduction • BLDC rotary compressors → efficiency and cost effectiveness → small/medium cooling capacities → compressor racks
  • 4.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Introduction • BLDC rotary compressors → efficiency and cost effectiveness → small/medium cooling capacities → compressor racks • Low pressure and low temperature • Oil is injected into the shell directly
  • 5.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Introduction • BLDC rotary compressors → efficiency and cost effectiveness → small/medium cooling capacities → compressor racks • Low pressure and low temperature • Oil is injected into the shell directly • High pressure and high temperature • Oil is withdrawn from the shell
  • 6.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Working Principle • Expansion of oil/CO2 mixture 2 4 6 8 10 12 200 300 400 500 600 Pressure[MPa] Enthalpy [kJ/kg] < 𝑇𝑖𝑛 𝐶𝑂2 𝑇𝑜𝑢𝑡
  • 7.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Working Principle • Expansion of oil/CO2 mixture 2 4 6 8 10 12 200 300 400 500 600 Pressure[MPa] Enthalpy [kJ/kg] < 𝑇𝑖𝑛 𝐶𝑂2 ≈ 𝑇𝑖𝑛 𝑂𝑖𝑙 𝑇𝑜𝑢𝑡
  • 8.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Working Principle • Expansion of oil/CO2 mixture • It requires flow control devices • Modulating valve is installed at the compressor oil balance pipe 𝑙𝑜𝑤 𝑓𝑙𝑜𝑤 → 𝑑𝑒𝑡𝑒𝑐𝑡𝑖𝑜𝑛 ℎ𝑖𝑔ℎ 𝑓𝑙𝑜𝑤 → 𝑒𝑞𝑢𝑎𝑙𝑖𝑧𝑎𝑡𝑖𝑜𝑛 2 4 6 8 10 12 200 300 400 500 600 Pressure[MPa] Enthalpy [kJ/kg] < 𝑇𝑖𝑛 𝐶𝑂2 ≈ 𝑇𝑖𝑛 𝑂𝑖𝑙 𝑇𝑜𝑢𝑡
  • 9.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Test Rig Description • CO2 booster system with air-cooled gas cooler • Standard industrial control boards, equipment and instrumentations • MT/LT – 30 kW/6kW • PAG oil ISO VG100 • Sight glasses for visual inspection
  • 10.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Test Rig Description
  • 11.
    0 10 20 30 40 50 60 70 80 90 100 0:00 0:30 1:001:30 2:00 2:30 3:00 3:30 4:00 4:30 5:00 5:30 6:00 6:30 7:00 Temperature[°C] DeltaTemperature[K] Time [mm:ss] Oil Valve Inlet Temp Oil Valve ΔT calc 8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Oil Presence Detection • Control predicts the pure CO2 temperature drop at given pressures by modelling an isenthalpic expansion (Inputs) 𝑇𝑖𝑛, 𝑃𝑑𝑖s, 𝑃𝑠𝑢𝑐𝑡 → (Output) Δ𝑇𝑐𝑎𝑙𝑐 Rot speed [Hz] = 43 – 48 𝑃𝑑𝑖𝑠𝑐ℎ [MPa] = 7.8 𝑃𝑠𝑢𝑐𝑡 [MPa] = 2.8
  • 12.
    0 10 20 30 40 50 60 70 80 90 100 0:00 0:30 1:001:30 2:00 2:30 3:00 3:30 4:00 4:30 5:00 5:30 6:00 6:30 7:00 Temperature[°C] DeltaTemperature[K] Time [mm:ss] Oil Valve Inlet Temp Oil Valve ΔT exp Oil Valve ΔT calc Threshold ΔTcalc/n 8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Oil Presence Detection • Control predicts the pure CO2 temperature drop at given pressures by modelling an isenthalpic expansion (Inputs) 𝑇𝑖𝑛, 𝑃𝑑𝑖s, 𝑃𝑠𝑢𝑐𝑡 → (Output) Δ𝑇𝑐𝑎𝑙𝑐 • Gradually closing of the valve OD until Δ𝑇𝑒𝑥𝑝 is below the threshold • Valve OD range 85.4 – 31.3% Δ𝑇𝑒𝑥𝑝 < Δ𝑇𝑐𝑎𝑙𝑐 𝑛 Rot speed [Hz] = 43 – 48 𝑃𝑑𝑖𝑠𝑐ℎ [MPa] = 7.8 𝑃𝑠𝑢𝑐𝑡 [MPa] = 2.8
  • 13.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Test – Working Conditions MT1 MT2 MT3 MT4 MT5 LT1 LT2 𝑇𝑒𝑣 [°C] -5.0 -5.0 -8.0 -11.0 -15.0 -25.0 -35.0 𝑃𝑑𝑖𝑠 [MPa] 8.0 6.5 9.8 8.0 6.5 2.7 2.7 0.0 2.0 4.0 6.0 8.0 10.0 12.0 14.0 0.6 1.0 1.4 1.8 2.2 2.6 3.0 3.4 3.8 4.2 DischargePressure[MPa] Suction Pressure [MPa] Compressor Envelope MT LT Rotation speed 30/60/90 Hz MT1 MT2MT5 MT4 MT3 LT1LT2
  • 14.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Oil Missing Detection – Test & Results Δ𝑇𝑒𝑥𝑝 ≈ Δ𝑇𝑐𝑎𝑙𝑐
  • 15.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Oil Missing Detection – Test & Results Δ𝑇𝑒𝑥𝑝 ≈ Δ𝑇𝑐𝑎𝑙𝑐 MT1 MT2 MT3 MT4 MT5 LT1 LT2 𝑇𝑖𝑛 [°C] 88.8 72.4 128.5 108.4 100.4 59.3 82.6 Δ𝑇𝑒𝑥𝑝 [K] 35.1 28.7 35.5 33.8 27.5 9.4 12.5 dev [K] 2.0 0.6 4.7 1.6 0.7 0.4 0.9
  • 16.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Oil Presence Detection – Test & Results ↑ 𝐶𝑂2 ------- ↓ 𝑂𝑖𝑙 • 201 tests collected (165 for MT, 36 for LT)
  • 17.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Oil Presence Detection – Test & Results τ < 30 s < 40 s < 60 s MT 84.2% 93.3% 98.2% LT 27.8% 58.3% 88.9% ↑ 𝐶𝑂2 ------- ↓ 𝑂𝑖𝑙 • 201 tests collected (165 for MT, 36 for LT) • Short duration reduces efficiency loss (lower gas by–pass)
  • 18.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Oil Equalization Procedure
  • 19.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Oil Equalization Procedure
  • 20.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Oil Equalization Procedure • Performed only if more than one compressor active and oil detection ends with not aligned outcomes • Oil equalization is directly verified 0% 20% 40% 60% 80% 100% 0:00 1:00 2:00 3:00 4:00 5:00 6:00 7:00 8:00 9:00 10:00 OpeningDegree[%] Time [mm:ss]
  • 21.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Oil Equalization Procedure – Test & Results • Test done by manually forcing the imbalance • Low rotation speed is critical MT LT 𝒓𝒑𝒔 [𝐇𝐳] ✓ Total ✓ Total 30 2 9 11 4 1 5 60 15 0 15 6 0 6 90 14 1 15 6 0 6 • Detection procedure can act as equalization as well • If the equalization is not effective ( ) → safe operation by oil refill from the oil separator
  • 22.
    8th IIR Conference:Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia Conclusions • Detection and equalization of oil levels for each compressor • Simple and reliable method based on temperature measurement during fluid expansion • Equalization effectiveness is verified for each compressor (and not presumed) • Modulation gives other advantages such as → short response time → limited gas bypass → adaptability to current working conditions • Life test has to be performed
  • 23.
    THANK YOU Giovanni ROSSANESE,Luca MATTIELLO, Willy MUVEGI, Luigi NALINI Carel Industries S.p.A. 8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, 2019, Ohrid, R. Macedonia giovanni.rossanese@carel.com, luca.mattiello@carel.com, willy.muvegi@carel.com, luigi.nalini@carel.com International Institute of Refrigeration www.iifiir.org Institute International du Froid iif-iir@iifiir.org