SlideShare a Scribd company logo
1
A
presentation
ON
RRVPNL, 132 KV GSS (GIS) OLD POWER HOUSE
JODHPUR (RAJ.)
submitted in partial fulfilment
for the award of the Degree of
BACHELOR OF TECHNOLOGY
(Rajasthan Technical University, Kota)
IN
Department of Electrical Engineering
Submitted To : Submitted By:
Mr. Vikas Bhalla Harish kumar
Assistant Professor EnrolmentNo.:
12ECTEE019
GAS INSULATED SUBSTATION
BY:
HARISH KUMAR
ELECTRICAL
ENGINEERING
1510-15
2
3
4
5
CONTENTS:
Substation
Conventional substations (AIS)
Limitations of AIS
The need for GIS
Introduction to GIS
Properties of SF6
GIS assembly
Advantages of GIS
Design features
Drawbacks
SF6 – Environmental concerns
SF6 /N2 mixtures
Future trends in GIS
Conclusion.
6
SUBSTATION:
• An assembly of apparatus installed to control
transmission and distribution of electric power.
A : P R I M A R Y P O W E R L I N E S ' S I D E B : S E C O N D A R Y P O W E R L I N E S ' S I D E
1 . P R I M A R Y P O W E R L I N E S 2 . G R O U N D W I R E 3 . O V E R H E A D L I N E S 4 . T R A N S F O R M E R
F O R M E A S U R E M E N T O F E L E C T R I C V O L T A G E 5 . D I S C O N N E C T S W I T C H 6 . C I R C U I T
B R E A K E R 7 . C U R R E N T T R A N S F O R M E R 8 . L I G H T N I N G A R R E S T E R 9 . M A I N
T R A N S F O R M E R 1 0 . C O N T R O L B U I L D I N G 1 1 . S E C U R I T Y F E N C E 1 2 . S E C O N D A R Y P O W E R
L I N E S
7
AIR INSULATED SUBSTATION(AIS):
Air used as a dielectric.
Normally used for outdoor substations.
In very few cases used for indoor substations.
Easy to expand (in case that space is not an
issue)
Excellent overview, simple handling and easy
access.
8
LIMITATIONS OF AIS:
Large dimensions due to statutory clearances and
poor dielectric strength of air.
Insulation deterioration with ambient conditions and
susceptibility to pollutants.
Wastage of space.
Life of steel structures degrades.
Seismic instability.
Large planning & execution time.
Regular maintenance of the substation required.
9
10
INTRODUCTION TO GAS INSULATED
SUBSTATION
What is GIS?
 A gas insulated substation is an electrical substation in which the major
structures are contained in a sealed environment with sulfur
hexafluoride gas (SF6) as the insulating medium.
Where and why Gas Insulated Substations
are used ?
 Gas Insulated Substations are used where there is space for providing
the substation is expensive in large cities and towns. In normal
substation the clearances between the phase to phase and phase to
ground is very large. Due to this, large space is required for the normal
or Air Insulated Substation (AIS).
 But the dielectric strength of SF6 gas is higher compared to the air, the
clearances required for phase to phase and phase to ground for all
equipments are quite lower. Hence, the overall size of each equipment
and the complete substation is reduced to about 10% of the
conventional air insulated substation
THE NEED FOR G.I.S:
Non availability of sufficient space.
Difficult climatic and seismic conditions at site.
Urban site (high rise building).
High altitudes.
Limitations of AIS.
11
GAS INSULATED SUBSTATION:
Introduction:
Compact, multi-component assembly.
Enclosed in a ground metallic housing.
Sulphur Hexaflouride (SF6) gas – the primary
insulating medium.
(SF6) gas- superior dielectric properties used at
moderate pressure for phase to phase and phase to
ground insulation
Preferred for voltage ratings of 72.5 kV, 145 kV, 300 kV
and 420 kV and above.
Various equipments like Circuit Breakers, Bus-Bars,
Isolators, Load Break Switches, Current
Transformers, Voltage Transformers, Earthing
Switches, etc. housed in metal enclosed modules
filled with SF6 gas.
12
PROPERTIES OF SF6:
• N O N - TO X I C , V E RY S TA B L E
C H E M I C A L LY.
• M A N - M A D E .
• L I F E T I M E – V E RY L O N G ( 8 0 0 TO
3 2 0 0 Y E A R S ! ) .
• I N S U L AT I N G P R O P E RT I E S 3 - T I M E S
T H AT O F A I R .
• C O L O R L E S S & H E AV I E R T H A N A I R .
• A L M O S T WAT E R I N S O L U B L E .
• N O N I N F L A M M A B L E .
13
14
Kalisindh Thermal Power
GIS ASSEMBLY:
ESSENTIAL PARTS OF GIS:
1. Bus bar
2. Circuit Breaker
3. Disconnector (line or bus)
4. Earthing switch (line or bus)
5. Current transformer (feeder / bus)
6. Voltage transformer (feeder/ bus)
7. Feeder Disconnector
8. Feeder Earthing switch
9. Lightning / Surge Arrester
10. Cable termination
11. Control Panel.
15
16
BUS BAR
 When a number of lines operating at the same voltage have to
directly connect electrically bus bar are used as the common
electrical component.
 There are following bus at the 132 gss:-
• 132 kv main bus bar
• 132 kv auxiliary bus bar
ISOLATOR
 Isolator is used to break the circuit under off-load
where as on-load circuit breaking is done by circuit
breaker
 Isolators are classified as:-
• Off load isolator
• On load isolator
17
18
CIRCUIT BREAKER
An automatic switch that stops the flow of
electric current in a suddenly overloaded
or otherwise abnormally stressed electric
circuit.
Types of circuit breaker:-
• Vaccum circuit breaker
• SF6 Circuit breaker
• Air blast circuit breaker
• Oil circuit breaker
19
CIRCUIT BREAKER OPERATION
MECHANISM
20
INSULATOR
Barrier insulator: The GIS is sectionalized into
individual gas compartments by means of gas-
tight barrier insulators. By this, the impact of
extension or internal faults on the overall
installation is reduced to a minimum, and control,
supervision and maintenance are greatly eased.
All flange connections are sealed by means of
age-resistant O-rings. Due to the gas tight design
of the insulators no leakage between
components can occur.
Support insulator: Support insulators are used
to mechanically support the conductors. They
mainly used for long SF6 bus duct connection.
21
22
CURRENT TRANSFORMER
Current transformer is used for measurement
of alternating electric current.
The objective of C.T. is :-
Reduce the scale of the metering scale.
Insulated the measuring instrument from
voltage.
• Used for protective system
23
24
POTENTIAL TRANSFORMER
Potential transformer is used for step down the
line voltage.
PT is connected in prallel with line.
Secondary voltage of the PT is generally 110v.
25
26
CAPACITOR
VOLTAGE
TRANSFORMER
 A capacitor voltage transformer
consists of a Capacitor Voltage
Divider (CVD) and an inductive
Intermediate Voltage Transformer
(IVT).
 The rated voltage of the complete
capacitor voltage transformer
determines the ratio at the capacitor
voltage divider.
 It is more convenient to make an
Inductive voltage transformer for
lower voltage levels and let the CVD
take care of the high voltage.
LIGHTENING ARRESTER
27
28
LIGTHNING ARRESTOR
Lightening arrester is used to protect the power station
sub station and transmission line against the voltage
wave reaching there.
It is also known as surge diverter which is connected
between line and earth to divert the incoming high
voltage to earth.
 It is the first equipment in a substation.
Generally arresters are connected in parallel with the
equipment to be protected, typically between phase and
earth for three phase installations.
29
GIS ASSEMBLY:
30
31
Supervisory Control And Data Acquisition
(SCADA)
 Supervisory Control and Data Acquisition (SCADA) offers the
ease of monitoring of sensors placed at distances, from one central
location.
 SCADA systems are used to monitor and control a plant or equipment
in industries such as telecommunications, water and waste control,
energy, oil and gas refining and transportation.
 A SCADA system gathers information, such as where a leak on a
pipeline has occurred, transfers the information back to a central site,
alerting the home station that the leak has occurred, carrying out
necessary analysis and control, such as determining if the leak is
critical, and displaying the information in a logical and organized
fashion.
 SCADA systems can be relatively simple, such as one that monitors
environmental conditions of a small office building, or incredibly
complex, such as a system that monitors all the activity in a nuclear
power plant or the activity of a municipal water system.
 SCADA systems were first used in the 1960s.
SCADA CONTROL ROOM
32
LARGE SCADA DISPLAY
33
ADVANTAGES :
Occupies very less space (1/10th) compared to
ordinary substations.
Hence, most preferred where area for substation
is small (eg: Cities)
Most reliable compared to Air Insulated
Substations.
Number of outages due to the fault is less
Maintenance Free.
Can be assembled at workshop and modules can
be commissioned in the plant easily.
Pollution free
Explosion proof & fire proof installation
Increased safety
Easy operation & long life 34
DESIGN CHALLENGES:
1 . S A F E T Y :
• O P T I M I Z I N G O P E R AT I N G E L E C T R I C A L
S T R E S S E S T O S A F E L E V E L S B Y B E T T E R
I N T E R E L E C T R O D E S PA C I N G .
• I N C R E A S I N G T H E G A S V O L U M E A N D T H E
T H E R M A L I N E R T I A O F T H E S Y S T E M T O
E N H A N C E C O O L I N G A N D R E T A I N
I N S U L AT I O N S T R E N G T H .
2 . H I G H R E L I A B I L I T Y :
• S U P E R I O R C O N T A C T S Y S T E M S F O R
C I R C U I T B R E A K E R S A N D
D I S C O N N E C T O R S .
• M U LT I - C O N T A C T A N D F R I C T I O N F R E E
S U R F A C E S I N C O R P O R AT E D F O R L O N G
O P E R AT I N G C Y C L E S .
• R U G G E D , T I M E P R O V E N O P E R AT I N G
D R I V E S U S E D .
35
GIS FAILURE STATISTICS:
57.30%
18.10%
12.40%
12.30%
INSULATION FAILURE
MECHANICAL
TROUBLE
GAS LEAK
OTHERS
36
MAIN DRAWBACKS:
• H I G H C O S T C O M PA R E D T O
C O N V E N T I O N A L S U B S TAT I O N ( A I S ) .
• E X C E S S I V E D A M A G E I N C A S E O F
I N T E R N A L FA U LT.
• D I A G N O S I S O F I N T E R N A L FA U LT A N D
R E C T I F Y I N G TA K E S V E R Y L O N G T I M E
( H I G H O U TA G E T I M E ) .
• S F 6 G A S P R E S S U R E M U S T B E
M O N I T O R E D I N E A C H C O M PA R T M E N T.
• R E D U C T I O N I N T H E P R E S S U R E O F
T H E S F 6 G A S I N A N Y
M O D U L E R E S U LT S I N F L A S H
O V E R A N D FA U LT S .
• S F 6 C A U S E S O Z O N E D E P L E T I O N A N D
G L O B A L WA R M I N G .
37
SF6 – ENVIRONMENTAL CONCERNS:
• C U R R E N T LY, 8 0 % U S E D B Y
E L E C T R I C A L P O W E R I N D U S T RY.
• O T H E R U S E S – M I C R O -
E L E C T R O N I C S ; A L & M G
P R O D U C T I O N .
• 7 0 0 0 M E T R I C TO N S / Y R I N 1 9 9 3 .
• R E A C H E D 1 0 , 0 0 0 M E T R I C TO N S / Y R
B Y 2 0 1 0 .
• T W O A R E A S O F H E A LT H A N D
E N V I R O N M E N TA L I M PA C T:
I . T H R O U G H I T S N O R M A L U S E I N A
W O R K P L A C E – A R C I N G
B Y P R O D U C T S .
I I . G L O B A L E N V I R O N M E N TA L I M PA C T 38
SF6/N2 MIXTURES FOR GIS?
• S F 6 G A S – S P E C I F I C A L LY M E N T I O N E D
I N K Y O T O P R O T O C O L .
• S M A L L Q U A N T I T I E S O F S F 6 I N N 2 C A N
I M P R O V E D I E L E C T R I C S T R E N G T H
D R A S T I C A L LY.
• A L L O F T H E D I E L E C T R I C S T R E N G T H
O F S F 6 , N E A R LY, C A N B E A C H I E V E D
B Y A D D I N G L E S S T H A N 2 0 % S F 6 I N T O
N 2 .
• S F 6 / N 2 M I X T U R E S L E S S
S U S C E P T I B L E T O E F F E C T S O F F I E L D
N O N U N I F O R M I T Y T H A N P U R E S F 6 .
• T H U S M I T I G AT I N G T H E E F F E C T S O F
PA R T I C L E S A N D S U R FA C E
P R O T R U S I O N S .
39
FUTURE TRENDS:
• C O M PA C T D E S I G N O F S W I T C H
G E A R B Y U S I N G T H R E E P H A S E
M O D U L E S .
• U S E O F VA C U U M C I R C U I T B R E A K E R
C E L L S I N T H E M E D I U M H I G H
V O LTA G E G I S .
• O P T I M I Z AT I O N O F G I S D E S I G N TO
A L L O W E A S I E R M A I N T E N A N C E .
• D E V E L O P M E N T O F D C G I S F O R
I N C O R P O R AT I N G I N TO E X PA N D I N G
N AT I O N A L / I N T E R N AT I O N A L H V D C
S Y S T E M S .
• S E A R C H F O R R E P L A C E M E N T
G A S E S F O R S F 6 . 40
CONCLUSION:
• G I S – N E C E S S A R Y F O R E X T R A H V &
U LT R A H V
• S O M E I M P O R TA N T A R E A S T O B E
S T U D I E D I N C L U D E :
• M O R E C O N S E R VAT I V E D E S I G N .
• I M P R O V E D G A S H A N D L I N G .
• D E C O M P O S I T I O N P R O D U C T
M A N A G E M E N T T E C H N I Q U E S .
• A C H I E V I N G & M A I N TA I N I N G H I G H
L E V E L S O F AVA I L A B I L I T Y R E Q U I R E –
M O R E I N T E G R AT E D A P P R O A C H T O
Q U A L I T Y C O N T R O L B Y B O T H U S E R S
A N D M A N U FA C T U R E S .
41
42

More Related Content

What's hot

Cooling System.pptx
Cooling System.pptxCooling System.pptx
Cooling System.pptx
NajmulMithun
 
Air washer
Air washerAir washer
Air washer
Belal Bin Neyaz
 
Blue star package units
Blue star package unitsBlue star package units
Blue star package units
Kumar Ramaiah
 
PPT on Indian railway (LHB coaches)
PPT on Indian  railway (LHB coaches)PPT on Indian  railway (LHB coaches)
PPT on Indian railway (LHB coaches)
kalyan kumar
 
HVAC operation and Maintenance
HVAC operation and Maintenance HVAC operation and Maintenance
HVAC operation and Maintenance
AC Repair Local
 
All water, air water systems
All water, air water systemsAll water, air water systems
All water, air water systemsAsan Ibrahim
 
COMMON RAIL DIESEL INJECTION (CRDI;CRDe)
COMMON RAIL DIESEL INJECTION (CRDI;CRDe)COMMON RAIL DIESEL INJECTION (CRDI;CRDe)
COMMON RAIL DIESEL INJECTION (CRDI;CRDe)
Ananda Murugan M
 
HVAC Fundamentals
HVAC  FundamentalsHVAC  Fundamentals
HVAC Fundamentals
GAUTAM KOPPALA (JORGE)
 
HVAC Cooling Load Calculation
HVAC Cooling Load CalculationHVAC Cooling Load Calculation
HVAC Cooling Load Calculation
Orange Slides
 
Combustion chambers-and-performance
Combustion chambers-and-performanceCombustion chambers-and-performance
Combustion chambers-and-performance
manojg1990
 
Study on Coach interior fittings of ICF and LHB coaches
Study on Coach interior fittings of ICF and LHB coachesStudy on Coach interior fittings of ICF and LHB coaches
Study on Coach interior fittings of ICF and LHB coaches
rakeshmanthu
 
Heat ventilation and air conditioning (hvac)
Heat ventilation and air conditioning (hvac)Heat ventilation and air conditioning (hvac)
Heat ventilation and air conditioning (hvac)
Satish kumar Hiremath
 
HVAC introduction
HVAC introductionHVAC introduction
HVAC introduction
Tushar Mistry
 
Condenser and Cooling Tower Power Plant Engineering
Condenser and Cooling Tower Power Plant EngineeringCondenser and Cooling Tower Power Plant Engineering
Condenser and Cooling Tower Power Plant Engineering
Ajaypalsinh Barad
 
Packaged air conditioners
Packaged air conditioners Packaged air conditioners
Packaged air conditioners
Ar.ADITYA GOEL
 
HVAC - Concept & Components
HVAC - Concept & ComponentsHVAC - Concept & Components
HVAC - Concept & Components
Umang Patel
 
Heat Load Calculation
Heat Load CalculationHeat Load Calculation
Heat Load CalculationJitendra Jha
 
Air conditioning
Air conditioningAir conditioning
Air conditioning
Andhra University
 

What's hot (20)

Cooling System.pptx
Cooling System.pptxCooling System.pptx
Cooling System.pptx
 
Air washer
Air washerAir washer
Air washer
 
Blue star package units
Blue star package unitsBlue star package units
Blue star package units
 
PPT on Indian railway (LHB coaches)
PPT on Indian  railway (LHB coaches)PPT on Indian  railway (LHB coaches)
PPT on Indian railway (LHB coaches)
 
HVAC operation and Maintenance
HVAC operation and Maintenance HVAC operation and Maintenance
HVAC operation and Maintenance
 
All water, air water systems
All water, air water systemsAll water, air water systems
All water, air water systems
 
COMMON RAIL DIESEL INJECTION (CRDI;CRDe)
COMMON RAIL DIESEL INJECTION (CRDI;CRDe)COMMON RAIL DIESEL INJECTION (CRDI;CRDe)
COMMON RAIL DIESEL INJECTION (CRDI;CRDe)
 
HVAC Fundamentals
HVAC  FundamentalsHVAC  Fundamentals
HVAC Fundamentals
 
HVAC Cooling Load Calculation
HVAC Cooling Load CalculationHVAC Cooling Load Calculation
HVAC Cooling Load Calculation
 
Combustion chambers-and-performance
Combustion chambers-and-performanceCombustion chambers-and-performance
Combustion chambers-and-performance
 
Maintenance report of Condensate Extraction Pump (KSB)
Maintenance report of Condensate Extraction Pump (KSB)Maintenance report of Condensate Extraction Pump (KSB)
Maintenance report of Condensate Extraction Pump (KSB)
 
Study on Coach interior fittings of ICF and LHB coaches
Study on Coach interior fittings of ICF and LHB coachesStudy on Coach interior fittings of ICF and LHB coaches
Study on Coach interior fittings of ICF and LHB coaches
 
Heat ventilation and air conditioning (hvac)
Heat ventilation and air conditioning (hvac)Heat ventilation and air conditioning (hvac)
Heat ventilation and air conditioning (hvac)
 
HVAC introduction
HVAC introductionHVAC introduction
HVAC introduction
 
Condenser and Cooling Tower Power Plant Engineering
Condenser and Cooling Tower Power Plant EngineeringCondenser and Cooling Tower Power Plant Engineering
Condenser and Cooling Tower Power Plant Engineering
 
Packaged air conditioners
Packaged air conditioners Packaged air conditioners
Packaged air conditioners
 
HVAC - Concept & Components
HVAC - Concept & ComponentsHVAC - Concept & Components
HVAC - Concept & Components
 
Heat Load Calculation
Heat Load CalculationHeat Load Calculation
Heat Load Calculation
 
Gas turbine
Gas turbine Gas turbine
Gas turbine
 
Air conditioning
Air conditioningAir conditioning
Air conditioning
 

Viewers also liked

Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substationsharique_64
 
132 gss ppt
132 gss ppt132 gss ppt
132 gss ppt
hunk143
 
27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations
Mugdha Jhanjhote
 
Gas insulated substation 1
Gas insulated substation 1Gas insulated substation 1
Gas insulated substation 1
Ronal Parmar
 
Gis substation
Gis substationGis substation
Gis substation
Asif Eqbal
 
132 kv gss
132 kv gss132 kv gss
132 kv gss
Rajneesh Budania
 
Mit ppt 132/33kv ppt
Mit ppt 132/33kv pptMit ppt 132/33kv ppt
Mit ppt 132/33kv ppt
Mithilesh Kumar
 
Sub stations-air insulated substations
Sub stations-air insulated substationsSub stations-air insulated substations
Sub stations-air insulated substations
bhanu lucky
 
Gas insulated substation.
Gas insulated substation.Gas insulated substation.
Gas insulated substation.
Pêrsêûs Sâîf
 
Summer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Summer Training presentation on 132/33 KV sub-station Minto park, AllahabadSummer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Summer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Sudhir Cement Industries Pvt. Ltd. Meerut
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentation
Kamal Mittal
 
Substation overview
Substation overviewSubstation overview
Substation overview
BHAGWAN PRASAD
 

Viewers also liked (13)

Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 
132 gss ppt
132 gss ppt132 gss ppt
132 gss ppt
 
27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations
 
Gas insulated substation 1
Gas insulated substation 1Gas insulated substation 1
Gas insulated substation 1
 
Gis substation
Gis substationGis substation
Gis substation
 
132 kv gss
132 kv gss132 kv gss
132 kv gss
 
Mit ppt 132/33kv ppt
Mit ppt 132/33kv pptMit ppt 132/33kv ppt
Mit ppt 132/33kv ppt
 
GIS-NESCL-6
GIS-NESCL-6GIS-NESCL-6
GIS-NESCL-6
 
Sub stations-air insulated substations
Sub stations-air insulated substationsSub stations-air insulated substations
Sub stations-air insulated substations
 
Gas insulated substation.
Gas insulated substation.Gas insulated substation.
Gas insulated substation.
 
Summer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Summer Training presentation on 132/33 KV sub-station Minto park, AllahabadSummer Training presentation on 132/33 KV sub-station Minto park, Allahabad
Summer Training presentation on 132/33 KV sub-station Minto park, Allahabad
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentation
 
Substation overview
Substation overviewSubstation overview
Substation overview
 

Similar to GSS (GIS) OLD POWER HOUSE JODHPUR

Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
RaushanKumar582
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Power System Operation
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
himanshu kumar
 
Chapter 11 Introduction to Gas Insulation Substation (GIS).pptx
Chapter 11 Introduction to Gas Insulation Substation (GIS).pptxChapter 11 Introduction to Gas Insulation Substation (GIS).pptx
Chapter 11 Introduction to Gas Insulation Substation (GIS).pptx
borapring
 
Gases insulation powerstation
Gases  insulation powerstationGases  insulation powerstation
Gases insulation powerstation
raja sukumar
 
Gis ppt (gas insulated sub station) deepak kumar kannaujiya,
Gis ppt (gas insulated sub station)  deepak kumar kannaujiya,Gis ppt (gas insulated sub station)  deepak kumar kannaujiya,
Gis ppt (gas insulated sub station) deepak kumar kannaujiya,
Sameer Kumar
 
Seminar on Gas Insulated Substation
Seminar on Gas Insulated SubstationSeminar on Gas Insulated Substation
Seminar on Gas Insulated Substation
Soumya Raj Poddar
 
Substation
Substation Substation
Substation
SanjayMk11
 
Internship ppt(santhosh).pptx
Internship ppt(santhosh).pptxInternship ppt(santhosh).pptx
Internship ppt(santhosh).pptx
Basavarajbanakar6
 
GIS (Gas-Insulated Substation) by Bharat & Shanni
GIS (Gas-Insulated Substation) by Bharat & ShanniGIS (Gas-Insulated Substation) by Bharat & Shanni
GIS (Gas-Insulated Substation) by Bharat & Shanni
BHARATKUMAR RATHOD
 
GIS PRESENTATION.pdf
GIS PRESENTATION.pdfGIS PRESENTATION.pdf
GIS PRESENTATION.pdf
AyazAhmadKhan3
 
Substation_fundamental.pptx
Substation_fundamental.pptxSubstation_fundamental.pptx
Substation_fundamental.pptx
Satish Pydimarla
 
GIS(GAS INSULATED SUBSTATION)
GIS(GAS  INSULATED  SUBSTATION) GIS(GAS  INSULATED  SUBSTATION)
GIS(GAS INSULATED SUBSTATION)
suneel kumar Aggela
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
Ajay Kuriakose
 
Gagan
GaganGagan
Gas insulated substation 2
Gas insulated substation 2Gas insulated substation 2
Gas insulated substation 2
naga pooja
 
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWARFACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
ashwini kumar
 
GIS 400kv substation
GIS  400kv substationGIS  400kv substation
GIS 400kv substation
Anbarasu Balakrishnan
 

Similar to GSS (GIS) OLD POWER HOUSE JODHPUR (20)

Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 
Chapter 11 Introduction to Gas Insulation Substation (GIS).pptx
Chapter 11 Introduction to Gas Insulation Substation (GIS).pptxChapter 11 Introduction to Gas Insulation Substation (GIS).pptx
Chapter 11 Introduction to Gas Insulation Substation (GIS).pptx
 
Gases insulation powerstation
Gases  insulation powerstationGases  insulation powerstation
Gases insulation powerstation
 
Gis ppt (gas insulated sub station) deepak kumar kannaujiya,
Gis ppt (gas insulated sub station)  deepak kumar kannaujiya,Gis ppt (gas insulated sub station)  deepak kumar kannaujiya,
Gis ppt (gas insulated sub station) deepak kumar kannaujiya,
 
Seminar on Gas Insulated Substation
Seminar on Gas Insulated SubstationSeminar on Gas Insulated Substation
Seminar on Gas Insulated Substation
 
Ppt
PptPpt
Ppt
 
Substation
Substation Substation
Substation
 
Internship ppt(santhosh).pptx
Internship ppt(santhosh).pptxInternship ppt(santhosh).pptx
Internship ppt(santhosh).pptx
 
GIS (Gas-Insulated Substation) by Bharat & Shanni
GIS (Gas-Insulated Substation) by Bharat & ShanniGIS (Gas-Insulated Substation) by Bharat & Shanni
GIS (Gas-Insulated Substation) by Bharat & Shanni
 
GIS PRESENTATION.pdf
GIS PRESENTATION.pdfGIS PRESENTATION.pdf
GIS PRESENTATION.pdf
 
Substation_fundamental.pptx
Substation_fundamental.pptxSubstation_fundamental.pptx
Substation_fundamental.pptx
 
GIS(GAS INSULATED SUBSTATION)
GIS(GAS  INSULATED  SUBSTATION) GIS(GAS  INSULATED  SUBSTATION)
GIS(GAS INSULATED SUBSTATION)
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 
Gagan
GaganGagan
Gagan
 
Deepak kumar
Deepak kumarDeepak kumar
Deepak kumar
 
Gas insulated substation 2
Gas insulated substation 2Gas insulated substation 2
Gas insulated substation 2
 
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWARFACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
 
GIS 400kv substation
GIS  400kv substationGIS  400kv substation
GIS 400kv substation
 

GSS (GIS) OLD POWER HOUSE JODHPUR

  • 1. 1 A presentation ON RRVPNL, 132 KV GSS (GIS) OLD POWER HOUSE JODHPUR (RAJ.) submitted in partial fulfilment for the award of the Degree of BACHELOR OF TECHNOLOGY (Rajasthan Technical University, Kota) IN Department of Electrical Engineering Submitted To : Submitted By: Mr. Vikas Bhalla Harish kumar Assistant Professor EnrolmentNo.: 12ECTEE019
  • 2. GAS INSULATED SUBSTATION BY: HARISH KUMAR ELECTRICAL ENGINEERING 1510-15 2
  • 3. 3
  • 4. 4
  • 5. 5
  • 6. CONTENTS: Substation Conventional substations (AIS) Limitations of AIS The need for GIS Introduction to GIS Properties of SF6 GIS assembly Advantages of GIS Design features Drawbacks SF6 – Environmental concerns SF6 /N2 mixtures Future trends in GIS Conclusion. 6
  • 7. SUBSTATION: • An assembly of apparatus installed to control transmission and distribution of electric power. A : P R I M A R Y P O W E R L I N E S ' S I D E B : S E C O N D A R Y P O W E R L I N E S ' S I D E 1 . P R I M A R Y P O W E R L I N E S 2 . G R O U N D W I R E 3 . O V E R H E A D L I N E S 4 . T R A N S F O R M E R F O R M E A S U R E M E N T O F E L E C T R I C V O L T A G E 5 . D I S C O N N E C T S W I T C H 6 . C I R C U I T B R E A K E R 7 . C U R R E N T T R A N S F O R M E R 8 . L I G H T N I N G A R R E S T E R 9 . M A I N T R A N S F O R M E R 1 0 . C O N T R O L B U I L D I N G 1 1 . S E C U R I T Y F E N C E 1 2 . S E C O N D A R Y P O W E R L I N E S 7
  • 8. AIR INSULATED SUBSTATION(AIS): Air used as a dielectric. Normally used for outdoor substations. In very few cases used for indoor substations. Easy to expand (in case that space is not an issue) Excellent overview, simple handling and easy access. 8
  • 9. LIMITATIONS OF AIS: Large dimensions due to statutory clearances and poor dielectric strength of air. Insulation deterioration with ambient conditions and susceptibility to pollutants. Wastage of space. Life of steel structures degrades. Seismic instability. Large planning & execution time. Regular maintenance of the substation required. 9
  • 10. 10 INTRODUCTION TO GAS INSULATED SUBSTATION What is GIS?  A gas insulated substation is an electrical substation in which the major structures are contained in a sealed environment with sulfur hexafluoride gas (SF6) as the insulating medium. Where and why Gas Insulated Substations are used ?  Gas Insulated Substations are used where there is space for providing the substation is expensive in large cities and towns. In normal substation the clearances between the phase to phase and phase to ground is very large. Due to this, large space is required for the normal or Air Insulated Substation (AIS).  But the dielectric strength of SF6 gas is higher compared to the air, the clearances required for phase to phase and phase to ground for all equipments are quite lower. Hence, the overall size of each equipment and the complete substation is reduced to about 10% of the conventional air insulated substation
  • 11. THE NEED FOR G.I.S: Non availability of sufficient space. Difficult climatic and seismic conditions at site. Urban site (high rise building). High altitudes. Limitations of AIS. 11
  • 12. GAS INSULATED SUBSTATION: Introduction: Compact, multi-component assembly. Enclosed in a ground metallic housing. Sulphur Hexaflouride (SF6) gas – the primary insulating medium. (SF6) gas- superior dielectric properties used at moderate pressure for phase to phase and phase to ground insulation Preferred for voltage ratings of 72.5 kV, 145 kV, 300 kV and 420 kV and above. Various equipments like Circuit Breakers, Bus-Bars, Isolators, Load Break Switches, Current Transformers, Voltage Transformers, Earthing Switches, etc. housed in metal enclosed modules filled with SF6 gas. 12
  • 13. PROPERTIES OF SF6: • N O N - TO X I C , V E RY S TA B L E C H E M I C A L LY. • M A N - M A D E . • L I F E T I M E – V E RY L O N G ( 8 0 0 TO 3 2 0 0 Y E A R S ! ) . • I N S U L AT I N G P R O P E RT I E S 3 - T I M E S T H AT O F A I R . • C O L O R L E S S & H E AV I E R T H A N A I R . • A L M O S T WAT E R I N S O L U B L E . • N O N I N F L A M M A B L E . 13
  • 15. GIS ASSEMBLY: ESSENTIAL PARTS OF GIS: 1. Bus bar 2. Circuit Breaker 3. Disconnector (line or bus) 4. Earthing switch (line or bus) 5. Current transformer (feeder / bus) 6. Voltage transformer (feeder/ bus) 7. Feeder Disconnector 8. Feeder Earthing switch 9. Lightning / Surge Arrester 10. Cable termination 11. Control Panel. 15
  • 16. 16 BUS BAR  When a number of lines operating at the same voltage have to directly connect electrically bus bar are used as the common electrical component.  There are following bus at the 132 gss:- • 132 kv main bus bar • 132 kv auxiliary bus bar ISOLATOR  Isolator is used to break the circuit under off-load where as on-load circuit breaking is done by circuit breaker  Isolators are classified as:- • Off load isolator • On load isolator
  • 17. 17
  • 18. 18 CIRCUIT BREAKER An automatic switch that stops the flow of electric current in a suddenly overloaded or otherwise abnormally stressed electric circuit. Types of circuit breaker:- • Vaccum circuit breaker • SF6 Circuit breaker • Air blast circuit breaker • Oil circuit breaker
  • 20. 20 INSULATOR Barrier insulator: The GIS is sectionalized into individual gas compartments by means of gas- tight barrier insulators. By this, the impact of extension or internal faults on the overall installation is reduced to a minimum, and control, supervision and maintenance are greatly eased. All flange connections are sealed by means of age-resistant O-rings. Due to the gas tight design of the insulators no leakage between components can occur. Support insulator: Support insulators are used to mechanically support the conductors. They mainly used for long SF6 bus duct connection.
  • 21. 21
  • 22. 22
  • 23. CURRENT TRANSFORMER Current transformer is used for measurement of alternating electric current. The objective of C.T. is :- Reduce the scale of the metering scale. Insulated the measuring instrument from voltage. • Used for protective system 23
  • 24. 24
  • 25. POTENTIAL TRANSFORMER Potential transformer is used for step down the line voltage. PT is connected in prallel with line. Secondary voltage of the PT is generally 110v. 25
  • 26. 26 CAPACITOR VOLTAGE TRANSFORMER  A capacitor voltage transformer consists of a Capacitor Voltage Divider (CVD) and an inductive Intermediate Voltage Transformer (IVT).  The rated voltage of the complete capacitor voltage transformer determines the ratio at the capacitor voltage divider.  It is more convenient to make an Inductive voltage transformer for lower voltage levels and let the CVD take care of the high voltage.
  • 28. 28 LIGTHNING ARRESTOR Lightening arrester is used to protect the power station sub station and transmission line against the voltage wave reaching there. It is also known as surge diverter which is connected between line and earth to divert the incoming high voltage to earth.  It is the first equipment in a substation. Generally arresters are connected in parallel with the equipment to be protected, typically between phase and earth for three phase installations.
  • 29. 29
  • 31. 31 Supervisory Control And Data Acquisition (SCADA)  Supervisory Control and Data Acquisition (SCADA) offers the ease of monitoring of sensors placed at distances, from one central location.  SCADA systems are used to monitor and control a plant or equipment in industries such as telecommunications, water and waste control, energy, oil and gas refining and transportation.  A SCADA system gathers information, such as where a leak on a pipeline has occurred, transfers the information back to a central site, alerting the home station that the leak has occurred, carrying out necessary analysis and control, such as determining if the leak is critical, and displaying the information in a logical and organized fashion.  SCADA systems can be relatively simple, such as one that monitors environmental conditions of a small office building, or incredibly complex, such as a system that monitors all the activity in a nuclear power plant or the activity of a municipal water system.  SCADA systems were first used in the 1960s.
  • 34. ADVANTAGES : Occupies very less space (1/10th) compared to ordinary substations. Hence, most preferred where area for substation is small (eg: Cities) Most reliable compared to Air Insulated Substations. Number of outages due to the fault is less Maintenance Free. Can be assembled at workshop and modules can be commissioned in the plant easily. Pollution free Explosion proof & fire proof installation Increased safety Easy operation & long life 34
  • 35. DESIGN CHALLENGES: 1 . S A F E T Y : • O P T I M I Z I N G O P E R AT I N G E L E C T R I C A L S T R E S S E S T O S A F E L E V E L S B Y B E T T E R I N T E R E L E C T R O D E S PA C I N G . • I N C R E A S I N G T H E G A S V O L U M E A N D T H E T H E R M A L I N E R T I A O F T H E S Y S T E M T O E N H A N C E C O O L I N G A N D R E T A I N I N S U L AT I O N S T R E N G T H . 2 . H I G H R E L I A B I L I T Y : • S U P E R I O R C O N T A C T S Y S T E M S F O R C I R C U I T B R E A K E R S A N D D I S C O N N E C T O R S . • M U LT I - C O N T A C T A N D F R I C T I O N F R E E S U R F A C E S I N C O R P O R AT E D F O R L O N G O P E R AT I N G C Y C L E S . • R U G G E D , T I M E P R O V E N O P E R AT I N G D R I V E S U S E D . 35
  • 36. GIS FAILURE STATISTICS: 57.30% 18.10% 12.40% 12.30% INSULATION FAILURE MECHANICAL TROUBLE GAS LEAK OTHERS 36
  • 37. MAIN DRAWBACKS: • H I G H C O S T C O M PA R E D T O C O N V E N T I O N A L S U B S TAT I O N ( A I S ) . • E X C E S S I V E D A M A G E I N C A S E O F I N T E R N A L FA U LT. • D I A G N O S I S O F I N T E R N A L FA U LT A N D R E C T I F Y I N G TA K E S V E R Y L O N G T I M E ( H I G H O U TA G E T I M E ) . • S F 6 G A S P R E S S U R E M U S T B E M O N I T O R E D I N E A C H C O M PA R T M E N T. • R E D U C T I O N I N T H E P R E S S U R E O F T H E S F 6 G A S I N A N Y M O D U L E R E S U LT S I N F L A S H O V E R A N D FA U LT S . • S F 6 C A U S E S O Z O N E D E P L E T I O N A N D G L O B A L WA R M I N G . 37
  • 38. SF6 – ENVIRONMENTAL CONCERNS: • C U R R E N T LY, 8 0 % U S E D B Y E L E C T R I C A L P O W E R I N D U S T RY. • O T H E R U S E S – M I C R O - E L E C T R O N I C S ; A L & M G P R O D U C T I O N . • 7 0 0 0 M E T R I C TO N S / Y R I N 1 9 9 3 . • R E A C H E D 1 0 , 0 0 0 M E T R I C TO N S / Y R B Y 2 0 1 0 . • T W O A R E A S O F H E A LT H A N D E N V I R O N M E N TA L I M PA C T: I . T H R O U G H I T S N O R M A L U S E I N A W O R K P L A C E – A R C I N G B Y P R O D U C T S . I I . G L O B A L E N V I R O N M E N TA L I M PA C T 38
  • 39. SF6/N2 MIXTURES FOR GIS? • S F 6 G A S – S P E C I F I C A L LY M E N T I O N E D I N K Y O T O P R O T O C O L . • S M A L L Q U A N T I T I E S O F S F 6 I N N 2 C A N I M P R O V E D I E L E C T R I C S T R E N G T H D R A S T I C A L LY. • A L L O F T H E D I E L E C T R I C S T R E N G T H O F S F 6 , N E A R LY, C A N B E A C H I E V E D B Y A D D I N G L E S S T H A N 2 0 % S F 6 I N T O N 2 . • S F 6 / N 2 M I X T U R E S L E S S S U S C E P T I B L E T O E F F E C T S O F F I E L D N O N U N I F O R M I T Y T H A N P U R E S F 6 . • T H U S M I T I G AT I N G T H E E F F E C T S O F PA R T I C L E S A N D S U R FA C E P R O T R U S I O N S . 39
  • 40. FUTURE TRENDS: • C O M PA C T D E S I G N O F S W I T C H G E A R B Y U S I N G T H R E E P H A S E M O D U L E S . • U S E O F VA C U U M C I R C U I T B R E A K E R C E L L S I N T H E M E D I U M H I G H V O LTA G E G I S . • O P T I M I Z AT I O N O F G I S D E S I G N TO A L L O W E A S I E R M A I N T E N A N C E . • D E V E L O P M E N T O F D C G I S F O R I N C O R P O R AT I N G I N TO E X PA N D I N G N AT I O N A L / I N T E R N AT I O N A L H V D C S Y S T E M S . • S E A R C H F O R R E P L A C E M E N T G A S E S F O R S F 6 . 40
  • 41. CONCLUSION: • G I S – N E C E S S A R Y F O R E X T R A H V & U LT R A H V • S O M E I M P O R TA N T A R E A S T O B E S T U D I E D I N C L U D E : • M O R E C O N S E R VAT I V E D E S I G N . • I M P R O V E D G A S H A N D L I N G . • D E C O M P O S I T I O N P R O D U C T M A N A G E M E N T T E C H N I Q U E S . • A C H I E V I N G & M A I N TA I N I N G H I G H L E V E L S O F AVA I L A B I L I T Y R E Q U I R E – M O R E I N T E G R AT E D A P P R O A C H T O Q U A L I T Y C O N T R O L B Y B O T H U S E R S A N D M A N U FA C T U R E S . 41
  • 42. 42