The document summarizes research conducted to evaluate the drainage capabilities and heat loss of different inverted roof assemblies. Tests were performed using a calibrated hot box to simulate winter temperature conditions. Various inverted roof assemblies were tested that included different drainage layer configurations, insulation orientations, and gaps between insulation boards. Test results showed that the majority of rainwater drained at the membrane level regardless of assembly configuration. Introducing gaps between insulation boards increased drainage rates. Assembly configuration was also found to impact the overall effective thermal performance, with increased heat loss observed when the drainage layer was removed and insulation was in direct contact with the roof membrane.
The building envelope is physical separator between the exterior and the interior of the building and fenestration systems.
Envelope design strongly affects the visual and thermal comfort of the occupants, as well as energy consumption in the building.
The DOE Building Technologies (BT) Program has targeted the strategic goal of developing the next generation of
building envelope systems, with the ultimate objective of reducing the space conditioning requirements attributable
to attics by 50% compared to Building America (BA) regional baseline new construction. During 2005/06 computer
modeling and dynamic lab and field experiments lead to a new paradigm for designing thermally active building
envelopes. To meet BT’s goal, Oak Ridge National Lab’s Building Envelope Program (BEP) has worked with
several industries, universities, and collaborated with a sister national laboratory to merge key technologies into
prototype components for building envelopes.
This Presentation talks about low cooling strategies for buildings viz. radiant heating/cooling, geothermal heat exchange, rock beds and ground tunnel with examples and climate consideration.
The building envelope is physical separator between the exterior and the interior of the building and fenestration systems.
Envelope design strongly affects the visual and thermal comfort of the occupants, as well as energy consumption in the building.
The DOE Building Technologies (BT) Program has targeted the strategic goal of developing the next generation of
building envelope systems, with the ultimate objective of reducing the space conditioning requirements attributable
to attics by 50% compared to Building America (BA) regional baseline new construction. During 2005/06 computer
modeling and dynamic lab and field experiments lead to a new paradigm for designing thermally active building
envelopes. To meet BT’s goal, Oak Ridge National Lab’s Building Envelope Program (BEP) has worked with
several industries, universities, and collaborated with a sister national laboratory to merge key technologies into
prototype components for building envelopes.
This Presentation talks about low cooling strategies for buildings viz. radiant heating/cooling, geothermal heat exchange, rock beds and ground tunnel with examples and climate consideration.
Unlike most cooling systems in California which circulate cold air to maintain comfort most radiant cooling system circulate cool water through ceiling wall, or floor panels from that water is then absorbed by the occupants and interior spaces.
This is a slideshow given at the Passive House Alliance Minneapolis- St. Paul chapter fall lecture series in October 2013. After a basic Passive House introduction it showcases the design process for Western Technical College's 24th St. Passive House project in La Crosse, WI
First Passive House Retrofit in a Cold Climate: The MinnePHit HouseTE Studio
This presentation was given by Tim Delhey Eian of TE Studio on Tuesday, September 23rd, at the 2014 NAPHN Passive House Conference in Portland, Maine. It showcases the first cold climate Passive House retrofit (EnerPHit) project which TE Studio designed, and the Passivhaus Institut in Darmstadt (Germany) certified as a pilot EnerPHit project.
Lecture given at the May 5, 2021 Passive House Accelerator event illustrating the Lexington Pkwy Passive House Plus in St. Paul, Minnesota TE Studio Architecture
Following the St Brigid's Sustainable Homes Tour, this presentation was prepared for VCE Environmental Science students. It outlines the considerations for sustainable living in SW Victoria.
While work is ongoing to further define the benefits of what has been termed Above-Sheathing Ventilation (ASV), the significance of this information is likely to create a very strong impetus for change in how tile roofs are installed.
Unlike most cooling systems in California which circulate cold air to maintain comfort most radiant cooling system circulate cool water through ceiling wall, or floor panels from that water is then absorbed by the occupants and interior spaces.
This is a slideshow given at the Passive House Alliance Minneapolis- St. Paul chapter fall lecture series in October 2013. After a basic Passive House introduction it showcases the design process for Western Technical College's 24th St. Passive House project in La Crosse, WI
First Passive House Retrofit in a Cold Climate: The MinnePHit HouseTE Studio
This presentation was given by Tim Delhey Eian of TE Studio on Tuesday, September 23rd, at the 2014 NAPHN Passive House Conference in Portland, Maine. It showcases the first cold climate Passive House retrofit (EnerPHit) project which TE Studio designed, and the Passivhaus Institut in Darmstadt (Germany) certified as a pilot EnerPHit project.
Lecture given at the May 5, 2021 Passive House Accelerator event illustrating the Lexington Pkwy Passive House Plus in St. Paul, Minnesota TE Studio Architecture
Following the St Brigid's Sustainable Homes Tour, this presentation was prepared for VCE Environmental Science students. It outlines the considerations for sustainable living in SW Victoria.
While work is ongoing to further define the benefits of what has been termed Above-Sheathing Ventilation (ASV), the significance of this information is likely to create a very strong impetus for change in how tile roofs are installed.
A Pitched Roof with Forced Ventilation to Limit
Solar Gains by Enrico Caffagni, Antonio Libbra, Alberto Muscio* and Luca Tarozzi in Advancements in Civil Engineering & Technology
Cool Roofs Are Ready to Save Energy, Cool Urban Heat Islands, and Help Slow G...Tony Loup
U.S. Department of Energy Building Technologies Program fact sheet about cool roofs, including how they work, the energy-saving benefits, and how to buy and select cool roofs.
this power point discuses about pcm material s and recently applications on green house
and introduce kind of pcm system
this power point priority created by some other authors
With the façade embodying up to 35% of the construction costs as well as being hugely accountable for the buildings' response to climate change, it has never been so important to understand which façade solutions deliver not only a cost effective and sustainable façade, but also one that is aesthetically pleasing and technically performing.
Building services (Passive Cooling Techniques) for Architectural studentsChad Minott
Passive cooling has several methods of cooling a structure specifically the Caribbean region. This essay will help students gain a greater understanding of ways to approach in cooling a building within the Caribbean.
Building materials used for the walls of simple houses in lower-middle-class areas in Indonesia are currently dominated by brick. This study proposes that soil-paper blocks coated with calcium silicate board may be a suitable alternative, with high embodied energy and density. The research aims to obtain an optimal wall thickness to provide protection against cooling and embodied energy in low income houses, as well as against the temperature conditions in these buildings in highland and lowland areas. Determination of wall thickness is performed by simulation of a 9 m2 building model with thick variables. Cooling calculations involved the use of Archipak software. Temperature measurements were carried out using a data logger on a sample of soil-paper blocks. The results indicate that the optimal wall thickness for protection against cooling and embodied energy is 8 cm. Soil-paper block has a lower density than brick. The use of calcium silicate boards does not affect the internal temperature of a low income house, but they can be used as protection against rainwater and as a substitute for wall plastering.
COLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdfKamal Acharya
The College Bus Management system is completely developed by Visual Basic .NET Version. The application is connect with most secured database language MS SQL Server. The application is develop by using best combination of front-end and back-end languages. The application is totally design like flat user interface. This flat user interface is more attractive user interface in 2017. The application is gives more important to the system functionality. The application is to manage the student’s details, driver’s details, bus details, bus route details, bus fees details and more. The application has only one unit for admin. The admin can manage the entire application. The admin can login into the application by using username and password of the admin. The application is develop for big and small colleges. It is more user friendly for non-computer person. Even they can easily learn how to manage the application within hours. The application is more secure by the admin. The system will give an effective output for the VB.Net and SQL Server given as input to the system. The compiled java program given as input to the system, after scanning the program will generate different reports. The application generates the report for users. The admin can view and download the report of the data. The application deliver the excel format reports. Because, excel formatted reports is very easy to understand the income and expense of the college bus. This application is mainly develop for windows operating system users. In 2017, 73% of people enterprises are using windows operating system. So the application will easily install for all the windows operating system users. The application-developed size is very low. The application consumes very low space in disk. Therefore, the user can allocate very minimum local disk space for this application.
Courier management system project report.pdfKamal Acharya
It is now-a-days very important for the people to send or receive articles like imported furniture, electronic items, gifts, business goods and the like. People depend vastly on different transport systems which mostly use the manual way of receiving and delivering the articles. There is no way to track the articles till they are received and there is no way to let the customer know what happened in transit, once he booked some articles. In such a situation, we need a system which completely computerizes the cargo activities including time to time tracking of the articles sent. This need is fulfilled by Courier Management System software which is online software for the cargo management people that enables them to receive the goods from a source and send them to a required destination and track their status from time to time.
Welcome to WIPAC Monthly the magazine brought to you by the LinkedIn Group Water Industry Process Automation & Control.
In this month's edition, along with this month's industry news to celebrate the 13 years since the group was created we have articles including
A case study of the used of Advanced Process Control at the Wastewater Treatment works at Lleida in Spain
A look back on an article on smart wastewater networks in order to see how the industry has measured up in the interim around the adoption of Digital Transformation in the Water Industry.
Forklift Classes Overview by Intella PartsIntella Parts
Discover the different forklift classes and their specific applications. Learn how to choose the right forklift for your needs to ensure safety, efficiency, and compliance in your operations.
For more technical information, visit our website https://intellaparts.com
Cosmetic shop management system project report.pdfKamal Acharya
Buying new cosmetic products is difficult. It can even be scary for those who have sensitive skin and are prone to skin trouble. The information needed to alleviate this problem is on the back of each product, but it's thought to interpret those ingredient lists unless you have a background in chemistry.
Instead of buying and hoping for the best, we can use data science to help us predict which products may be good fits for us. It includes various function programs to do the above mentioned tasks.
Data file handling has been effectively used in the program.
The automated cosmetic shop management system should deal with the automation of general workflow and administration process of the shop. The main processes of the system focus on customer's request where the system is able to search the most appropriate products and deliver it to the customers. It should help the employees to quickly identify the list of cosmetic product that have reached the minimum quantity and also keep a track of expired date for each cosmetic product. It should help the employees to find the rack number in which the product is placed.It is also Faster and more efficient way.
Final project report on grocery store management system..pdfKamal Acharya
In today’s fast-changing business environment, it’s extremely important to be able to respond to client needs in the most effective and timely manner. If your customers wish to see your business online and have instant access to your products or services.
Online Grocery Store is an e-commerce website, which retails various grocery products. This project allows viewing various products available enables registered users to purchase desired products instantly using Paytm, UPI payment processor (Instant Pay) and also can place order by using Cash on Delivery (Pay Later) option. This project provides an easy access to Administrators and Managers to view orders placed using Pay Later and Instant Pay options.
In order to develop an e-commerce website, a number of Technologies must be studied and understood. These include multi-tiered architecture, server and client-side scripting techniques, implementation technologies, programming language (such as PHP, HTML, CSS, JavaScript) and MySQL relational databases. This is a project with the objective to develop a basic website where a consumer is provided with a shopping cart website and also to know about the technologies used to develop such a website.
This document will discuss each of the underlying technologies to create and implement an e- commerce website.
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Dr.Costas Sachpazis
Terzaghi's soil bearing capacity theory, developed by Karl Terzaghi, is a fundamental principle in geotechnical engineering used to determine the bearing capacity of shallow foundations. This theory provides a method to calculate the ultimate bearing capacity of soil, which is the maximum load per unit area that the soil can support without undergoing shear failure. The Calculation HTML Code included.
Explore the innovative world of trenchless pipe repair with our comprehensive guide, "The Benefits and Techniques of Trenchless Pipe Repair." This document delves into the modern methods of repairing underground pipes without the need for extensive excavation, highlighting the numerous advantages and the latest techniques used in the industry.
Learn about the cost savings, reduced environmental impact, and minimal disruption associated with trenchless technology. Discover detailed explanations of popular techniques such as pipe bursting, cured-in-place pipe (CIPP) lining, and directional drilling. Understand how these methods can be applied to various types of infrastructure, from residential plumbing to large-scale municipal systems.
Ideal for homeowners, contractors, engineers, and anyone interested in modern plumbing solutions, this guide provides valuable insights into why trenchless pipe repair is becoming the preferred choice for pipe rehabilitation. Stay informed about the latest advancements and best practices in the field.
Automobile Management System Project Report.pdfKamal Acharya
The proposed project is developed to manage the automobile in the automobile dealer company. The main module in this project is login, automobile management, customer management, sales, complaints and reports. The first module is the login. The automobile showroom owner should login to the project for usage. The username and password are verified and if it is correct, next form opens. If the username and password are not correct, it shows the error message.
When a customer search for a automobile, if the automobile is available, they will be taken to a page that shows the details of the automobile including automobile name, automobile ID, quantity, price etc. “Automobile Management System” is useful for maintaining automobiles, customers effectively and hence helps for establishing good relation between customer and automobile organization. It contains various customized modules for effectively maintaining automobiles and stock information accurately and safely.
When the automobile is sold to the customer, stock will be reduced automatically. When a new purchase is made, stock will be increased automatically. While selecting automobiles for sale, the proposed software will automatically check for total number of available stock of that particular item, if the total stock of that particular item is less than 5, software will notify the user to purchase the particular item.
Also when the user tries to sale items which are not in stock, the system will prompt the user that the stock is not enough. Customers of this system can search for a automobile; can purchase a automobile easily by selecting fast. On the other hand the stock of automobiles can be maintained perfectly by the automobile shop manager overcoming the drawbacks of existing system.
drainage capabilities and heat loss of different inverted roof assemblies
1. Matthew Pel, B.Tech., Eng.L. is a Building Science Consultant and Principal at Morrison Hershfield, Vancouver, BC.
Derek Budde B.A.Sc. EIT is a Building Science Consultant at Morrison Hershfield, Vancouver, BC
Drainage Capabilities and Heat Loss
of Different Inverted Roof
Assemblies
Matthew Pel, B.Tech., Eng.L. Derek Budde, B.A.Sc. EIT
ABSTRACT
Energy use in buildings throughout North America has attracted significant attention over the past decade. In cold marine climates, rainwater
management is also a critical aspect of the building enclosure and energy performance. Various drainage practices used for low slope inverted roofing are
often designed without quantified data available regarding the cold rain affects on the thermal performance of the systems.
The effect of cold water under the roof insulation and its impact on the effective thermal performance in inverted roofs is well researched. The aim of this
project was to develop a better understanding of the impact of cold rain events on the effective thermal performance of inverted roofs in an effort to develop
best practice inverted roofs design guidelines.
The project included the construction of a ‘calibrated hot box’ to mimic the temperature difference between interior and exterior winter conditions. The
evaluated roof assemblies consist of typical inverted roofs (membrane, drainage layer, insulation, filter fabric and ballast). Evaluation was conducted with
different variables including rain rates, insulation orientation, insulation gaps, and different types of drainage mats and the exclusion of drainage mat
below the insulation. Later evaluations included a loose-laid moisture shedding layer above the insulation and changing the roof slope.
Evaluations have indicated that although the drainage capacity and leakage rates of different roof assemblies depend on a number of factors, the majority
of rainwater drains at the membrane level in all test scenarios. Based on the analysis completed, the results show that different drainage scenarios do have
an impact on the overall effective thermal performance of inverted roof assemblies. The most significant heat loss and unexpected results was the increased
heat loss when the drainage mat was removed and insulation was in direct contact with the roofing membrane.
INTRODUCTION
Energy use in buildings throughout the Pacific Northwest and North America has attracted significant
attention over the past decade. In British Columbia, rainwater management is also a critical aspect of designing a
durable building envelope. Various drainage practices used in low slope inverted roofs (i.e. grooved insulation,
drainage mat, vapour permeable water resistant barrier, etc.) are often used without much quantified information
available as to the thermal performance of the systems when exposed to rainfall. The affect of water under the
insulation and its impact on the thermal performance in inverted roofs is well researched over the past several decades
2. (Cold Region Research and Engineering Laboratory March 1976. Protected Membrane Roofs in Cold; Cold Region
Research and Engineering Laboratory, April 1977. Observations and Analysis of Protected Membrane Roofing
Systems).
Drainage of water within an inverted roof assembly, on the other hand, has not been extensively evaluated,
including draining at insulation levels or at the membrane level and how different drainage options affect the thermal
performance of the roof assembly resulting from cold rain bypassing the insulation.
Inverted roofs assemblies are commonly used within the Pacific Northwest area and are generally applied
directly to concrete for a variety of reasons:
Thermal protection of the roofing membrane and minimizing thermal cycling
Eliminating roofing membrane exposure to ultra violet radiation
Speed of construction and ability to install roofing membrane shortly after roof structure is completed
This study included the following tasks:
1. Literature review of past research related to heat loss in low slope inverted roof assemblies and drainage
rates
2. Evaluation of impact of different drainage scenarios on the rainfall drainage capability at the membrane
level and at the insulation level
3. Assessing the impact of different drainage scenarios on the thermal performance of the roof during rain
periods
METHODOLOGY AND TESTING EQUIPMENT
Hot Box Construction
In this research project, an insulated hot box was constructed and calibrated to provide a temperature
difference across different inverted roof assemblies to mimic an in-situ roof (refer to Figure 1 for hot box section) .
The hot box apparatus was constructed in two pieces, the base and lid, and is wood framed. The hot box is designed
and constructed to reduce air leakage within the chamber and minimize thermal bridging at the sides at bottom.
Continuous layers of self-adhering membrane were installed over the framed hot box with 150mm of adhered rigid
extruded polystyrene insulation. To seal the lid to the base a double layer of foam gasket is installed to reduce air
leakage and increase the thermal resistance.
3. Since the pattern or location of water flow under the insulation is unknown and cannot be confirmed, a
continuous aluminum base (Figure 2) was installed prior to the roofing membrane installation to help average out and
more evenly distribute the localized heat loss paths through the roof assembly.
Drains for the roof assembly (hot box lid) were provided at the membrane level and the insulation level
(Figure 2), allowing for measurement of drainage and water temperature. Figure 3 shows the completed hot box with
a partial inverted roof assembly installed.
Figure 2 – Hot Box Aluminum Base Figure 3 – Hot Box with Roof Insulation
Roof Assemblies and Drainage Options
Typical components of an inverted roof assembly (from bottom to top of the system) include a
waterproofing membrane, drainage layer, insulation, filter fabric and ballast. Multiple variations of the above
described assembly can be used depending on the design intent and/or consultant. Inverted roof assemblies and
drainage options commonly used in the Pacific Northwest include:
Figure 1 – Insulated Hot Box Section
Location of aluminum base
4. Table 1 – Inverted Roof Assembly Component Options
Waterproofing Membrane
2-Ply SBS membrane
Monolithic hot rubber membrane
Monolithic cold applied urethane
Drainage Layer
Solid core drainage mat
Open drainage mat (filament type/percolating)
Grooved insulation panels
No dedicated drainage (insulation directly on roofing membrane)
Insulation
1-layer of extruded polystyrene
2-layers of extruded polystyrene (with staggered joints)
Ballast
Gravel ballast
Concrete paving slabs
Soil and vegetation
Based on the past research, conventional roof design and building science principles, it is assumed that an
inverted roof with a drainage layer between the insulation and roofing membrane provides the most effective drainage
but the least effective thermal performance. This approach allows water to drain through the insulation and freely
flow over the roofing membrane leading to rainwater cooling and increased heat loss (H.M. Kunzel & K.Kiebl, 1996).
Inverted roofs with the insulation in direct contact with the roofing membrane (no drainage layer) provides the least
effective drainage but the most effective thermal performance. This approach relies on water draining on the surface
of the insulation panels or through small joints or gaps in the insulation. To minimize the numerous inverted roof
assembly options, the testing considered the most and least effective drainage scenarios as noted above.
Sensors and Instruments
To collect data during the testing, the hot box was equipped with instruments to record the following:
1. Heat Flux Sensors –W/m² (Concept Engineering, F-Series)
a. Heat flux through the roof assembly
2. Temperature Sensors – °C (Campbell Scientific, Model 109)
a. Ambient air temperature inside the hot box
b. Ambient air temperature outside the hot box
c. Surface temperature on the underside of the roof assembly
d. Water temperature – Flow in (simulated rainwater temperature)
e. Water temperature – Flow out low (membrane level)
f. Water temperature – Flow out high (insulation level)
3. Flow Meter – mm/hr (Omega Engineering, FLR1000 Series)
a. Rain rate
4. Pressure Sensor – Litres (Omega Engineering, Model PX309)
a. Cumulative flow at membrane and insulation level (pressure converted to litres)
5. A number of measures were in place during this study to ensure the results are repeatable and to minimize the
potential experimental error, they include:
Redundant sensors were installed
Multiple re-tests were completed
Heat loss through roof assembly was compared with water temperature increase (conservation of energy)
Scenarios and Variables
As noted in the Roof Assemblies and Drainage Options section (above), the most and least effective drainage
options and the most efficient thermal performance options were considered in testing to determine the upper and
the lower bounds of heat loss rates. Within these roof assemblies various scenarios were considered. Test scenarios
were developed to isolate individual variables related to roof assembly components and installation. As previously
noted, it is commonly thought that the best thermally performing inverted roof assembly is when the insulation is in
intimate contact with the roof membrane. It is also commonly thought that the best drainage provision for an
inverted roof assembly is when drainage mat is provided as a cavity between the roof membrane and the insulation.
The primary objective of this study was to compare and evaluate the heat loss through an inverted roof assembly,
including or omitting drainage space at the membrane level.
We recognize the variance in installation of individual roof components, such as insulation thickness and
changes in environmental conditions, like temperature differences and rainfall rates, may impact the performance of
the roof assembly differently. This study provides a comparison of varying drainage scenarios while holding all other
variables and bounded conditions constant.
Construction variances in the installation of rigid extruded polystyrene insulation, such as the orientation of
the boards relative to roof slope (long side of insulation panel is parallel or perpendicular direction to slope) and the
tightness of insulation boards joints (no gaps or gaps) were considered. It is important to recognize that often these
variables are encountered unavoidably but are within standard construction tolerances. For instance, when roofs have
centrally located roof drains, half the insulation boards may run parallel to the slope and half run perpendicular.
Boards may be installed with tight shiplapped joints in the summer; however, in the winter gaps would be present due
to shrinkage of the insulation.
The expansion/contraction of the insulation boards was calculated using the following:
∆𝐿 = 𝛼𝐿ₒ∆𝑇
Where: ΔL = Change in length of specimen (expansion/contraction); ΔL= mm (in)
α = Coefficient of Thermal Expansion; α= 6.3 x 10ˉ² mm/m °C (3.5 x 10ˉ5 in/in °F)
L0 = Initial Length of Board; Width 600mm (24”), Length 1200mm (48”)
ΔT = Final Temperature – Initial Temperature; 21°C - 1°C= 20 °C (68°F)
The shrinkage of the board (lengthwise) was calculated to be approximately 1.5mm or (1/16”). The
shrinkage of the board (widthwise) was calculated to be approximately 0.75mm (1/32”). For testing
purposes, tight board joints were used to simulate best case conditions and 1.5mm gaps were used to simulate
worst case conditions.
6. Environmental conditions like temperatures and wind may also affect the performance of the inverted roof
assembly. Rainfall rates directly correlate to the amount of water running over the roof, and at different rates it was
hypothesized that there may be more flow of water on top of the insulation versus at the roof membrane level.
Considering the information described above, the testing procedures for the project included the following
variables: insulation direction (parallel or perpendicular to roof slope) (Figures 4 and 5), gaps between insulation
boards (Figure 6) rainfall rate, and inclusion or exclusion of a drainage mat at the membrane level. To measure the
affect of these variables, each test was performed with a single variable change.
Figure 4 – Insulation Boards Parallel Figure 5 – Insulation Boards Perpendicular
Figure 6 – Insulation Board Gaps
7. Testing Results
The four main roof assemblies with different scenarios were tested as part of this study. Overall, 37 different
tests were completed changing one variable to measure the difference. The following are the tested roof assemblies
and variables that were added to create the different scenarios:
Table 2 – Tested Roof Assemblies
Inverted Roof Assembly Rainfall Rate Insulation
Orientation
Contact between
Adjacent Insulation
Boards
1. With Drainage Mat
50mm gravel ballast
Filter fabric
100mm of insulation (2-layers of 50mm)
Drainage mat
Roofing membrane
2mm/hr
3mm/hr
4mm/hr
Parallel
Perpendicular
1.5mm Insulation Gaps
No Gaps
2. No Drainage Mat
50mm gravel ballast
Filter fabric
10mm of insulation (2-layers of 50mm)
Roofing membrane
2mm/hr
3mm/hr
4mm/hr
Parallel
Perpendicular
1.5mm Insulation Gaps
No Gaps
3. Open Drainage Mat
50mm gravel ballast
Filter fabric
100mm of insulation (2-layers of 50mm)
Drainage mat
Roofing membrane
2mm/hr
3mm/hr
4mm/hr
Parallel
Perpendicular
1.5mm Insulation Gaps
No Gaps
4. No Drainage Mat – Weather Resistant
Barrier
50mm gravel ballast
Vapour permeable water resistant barrier
100mm of insulation (2-layers of 50mm)
Roofing membrane
4mm/hr Perpendicular 1.5mm Insulation Gaps
Each test yielded measurements for temperature of the simulated rainwater entering and exiting the roof
assembly, cumulative flow of water above and below insulation (drainage rates), and heat flux through each sensor.
The temperature change of the simulated rainwater was graphed to illustrate change over time (Figure 8). Water
accumulation from above and below the insulation was graphed to illustrate cumulative flow over time (Figure 7).
Data from heat flux sensors were graphed individually as well as averaged to illustrate average heat loss through the
roof assembly over time.
8. Drainage Rates
The total drainage amount, or the ‘cumulative flow’, of water was measured at the membrane level (referred
to as flow ‘Low’) and at the top of the insulation level (referred to as flow ‘High’) were recorded throughout the tests.
The roof assemblies were also tested with and without 1.5mm gaps in the insulation. To measure the volume of water
at the flow ‘High’ and flow ‘Low’, a pressure sensor, taking a reading every 5 seconds, was installed at the bottom of a
catch basin and converted to litres. Water accumulation was plotted on a volume (litres, vertical axis) versus time
(hours, horizontal axis) graph. Figure 7 below illustrates typical results.
Drainage rate is the percentage of water draining at the membrane level and is calculated by the following equation:
x 100%
% 𝐹𝑙𝑜𝑤 𝐿𝑜𝑤 =
𝐶𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝐹𝑙𝑜𝑤 𝐿𝑜𝑤
𝐶𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝐹𝑙𝑜𝑤 𝐿𝑜𝑤 + 𝐶𝑢𝑚𝑢𝑙𝑎𝑡𝑖𝑣𝑒 𝐹𝑙𝑜𝑤 𝐻𝑖𝑔ℎ
Where: % Flow ‘Low’ represents drainage rate
Cumulative Flow ‘Low’ = Total flow at membrane level, Litres
Cumulative Flow ‘High’ = Total flow above insulation, Litres
Results. Drainage rates were compared for various drainage scenarios and changes in variables. The biggest
affect to drainage rates was the presence of gaps in insulation panel joints. In tests where board joints were tight, a
smaller percentage of water was able to reach the membrane level. The presence of 1.5mm gaps in board joints
resulted in more water flowing to the membrane and draining at the membrane level. As illustrated above,
introducing gaps in the board joints resulted in an increase of 13% leakage rate (water drainage to the roofing
membrane) of water when compared to the same assembly with no gaps in the insulation.
Figure 7 – Drainage Rates and Cumulative Flow With and Without 1.5mm Insulation Gaps
9. It is important to note that in tests where no gaps were present the majority of water still leaked to the
membrane level. This suggests that the majority of water is bypassing the insulation.
Temperature Readings
Temperatures were measured and the hot box assembly was at steady state prior to test starting, as a baseline.
Temperature was plotted on a temperature (°C, vertical axis) versus time (hours, horizontal axis) graph for each
sensor. The following temperature measurements were obtained throughout the tests:
Water temperature at ‘flow in’ or the water supply, (purple curve)
Ambient temperature of the room, (green curve)
Air temperature inside the hot box, (red and blue curves)
Water temperature at the ‘High’ outflow (above insulation), (light blue curve)
Water temperature at the ‘Low’ outflow (waterproofing membrane level), (orange curve)
Figure 8 - Represents temperatures during and following a simulated rainfall event on an inverted roof assembly:
Referencing Figure 8 above, there is a constant 18°C temperature difference across the roof assembly prior to
the start of the rainfall event. This is visible on the left of the zero time mark. After the rainfall event starts, a short
delay occurs as the water accumulates on the gravel ballast, begins to percolate and drain through the system as
resistance and surface tension of water is overcome.
As the simulated rainwater drains through the roof assembly a portion is diverted to the roof membrane level
through joints between the insulation boards. This water flows below the insulation and contacts the roof membrane
(when no drainage mat is present). Heat is transferred from the heated space below through the roof deck resulting in
Exterior Air Temperatures &
Water Temperature at Flow ‘High’
Water Temperature at Flow ‘Low’
Hot Box Temperatures
Δ18°C
Figure 8 – Temperature Readings
10. temperature increase. This is apparent in the spike of the ‘water temperature at flow Low’ trend line in the Figure 8
(orange line). As this water is gaining heat from the roof structure below, the interior hot box temperatures are
reduced over time as visible in Figure 8 (red and blue lines).
The portion of the simulated rainfall that remains on the upper surface of the insulation boards flows to the
upper drain and is identified as ‘flow-out High’. As noted in Figure 8 (light blue line) above, there is very little change
in this water temperature as the rainfall event progresses. Water flowing on top of the insulation is not subject to the
same surface temperature difference and therefore does not gain much heat.
It was observed that the more water remains in intimate contact with the roof membrane the greater the
temperature increase of the outflow water at the membrane level (flow ‘Low’) and the greater heat flux through the
test assembly.
Heat Flux
Heat flux sensors are arranged in a 3x3 equally spaced grid (Figures 10 and 11) to provide individual readings
of heat flux through the associated roof area. Each sensor measured the flux through a 600mm x 600mm area, and
produced data readings every 5 seconds. Heat flux density (W/m2, vertical axis) was graphed versus time (hours,
horizontal axis) producing a typical group of testing data as follows.
High Flow at Drain
Mid Roof
High Side
Figure 9 – Typical Heat Flux Readings
11. Results. Heat flux sensors located near the scupper drain (Figure 9) on the roof assembly (low point),
receive the most water flow over the sensor as this is the low-spot of the roof. Therefore, these roof areas have the
highest heat flow. This is illustrated in flux sensor P8 (light blue) above. Sensors located in the mid-roof or mid-slope
area receive less volume of water flow than at the drain. This is illustrated in the group of sensors labelled ‘mid roof’,
above. Sensors located at the high-side of the roof receive little or no water flow over them. As such, the heat flux
increase through that roof area is low.
All testing completed shows that as the simulated rainwater percolates through the roof assembly and reaches
the membrane level it continually accumulates and absorbs energy (increases heat flow) as it flows over the membrane
towards the drain. It was observed that the more volume of water that flows over a given roof area (at the membrane
level) directly corresponds to an increase in overall heat loss.
Figure 10 – Layout of Heat Flux Sensors Figure 11 – Location of Heat Flux Sensors on Underside of Hot Lid
Average Heat Flux Increase
Ten heat flux sensors (9 locations, 1 redundant) were averaged to create a single trend line for each test.
Variables between tests were then compared to determine the effects.
Insulation Board Orientation
Insulation boards were varied to be oriented either parallel to the roof slope or perpendicular (Figures 4 and 5
above). The following graph illustrates two tests, one with the insulation boards oriented parallel and the other
perpendicular to the roof slope (all other variables remained the same). As noted in Drainage Rates section above, it
was expected that increased simulated rainwater would reach the membrane level flow ‘Low’ when the insulation
boards are perpendicular to the roof slope. As noted in Figure 12, increased heat flow was recorded through the
tested roof assembly with perpendicular insulation boards.
12. Results. The study shows that the orientation of the insulation boards affects the thermal performance of
the roof assembly. When insulation boards (2-layers of 50mm insulation with staggered joints) were oriented
perpendicular to the roof slope, the water travelling on top of the insulation boards encountered more joints where it
was diverted down to the membrane level. This increased the amount of water flowing over the surface of the
membrane which increased the heat flow through the roof assembly. When panel joints were parallel to the roof
slope, water was able to run over the insulation board surface for a much longer distance and time before trickling
down to the membrane level. For the test illustrated in Figure 12, insulation boards’ oriented perpendicular
performed approximately 50% less efficiently than insulation boards in parallel orientation.
Often the orientation of insulation boards on a roof compared to the roof slope direction is unavoidable.
The majority of flat roofs have centrally located drains; therefore, it could be expected that general board orientation
would be approximately 50% and 50% perpendicular to the slope.
Figure 12 – Average Heat Flux Readings with Different Insulation Direction
13. Insulation Board Joints
The affect of insulation board joint size was measured by running tests with tight board joints or with 1.5mm
gaps, to mimic construction tolerances and/or shrinkage of panels in cold conditions. A comparison of tight joints
versus gapped joints is provided on the following graph:
Results. The findings illustrated in this graph show that the increase in the average heat flux through the roof
assembly when insulation is gapped, is small. This follows the previous findings where the majority of water drains at
the membrane level regardless of how tight the insulation board joints are, resulting in similar heat loss measurements
for these tests.
Figure 13 – Average Heat Flux Readings with Different Insulation Joints
14. Drainage Mat vs. No Drainage Mat
It is commonly thought that the best thermally performing inverted roof assembly has the insulation in
intimate contact with the roofing membrane. The theory is that the presence of a drainage mat between the insulation
and the roof membrane creates an air cavity diminishing the effective insulation value and allows a space for flow of
cold rain.
The graph below illustrates typical test results for inclusion or exclusion of drainage mat. A solid-core
drainage mat was used, which is comprised of a solid polyethylene dimple board and filter fabric facer.
.
Results. Contrary to expectations, it was observed that the increase in heat flux through the roof assembly
during a rain event was greater if drainage mat was omitted. The red trend line in the graph is the average heat flux
through the roof assembly including a solid core drainage mat, while the blue trend line is excluding a drainage mat.
For the test illustrated in Figure 14, it was observed that during the rain event the overall heat flux through
the roof increased by approximately 75% with the presence of a drainage mat. When the drainage mat was excluded
in the roof assembly, with all other testing parameters remaining the same, the heat flux increased an additional 40%.
It is theorized that the observed performance of included or excluded drainage mat may be associated with
the direct contact between the water, flowing under the insulation and on top of the roof membrane. When a solid
Figure 14 – Average Heat Flux Readings With and Without Drainage Mat
75%
40%
15. core drainage mat is provided under the insulation, the water flows on the polyethylene core to the roof drains. This
provides one level of separation from direct contact with the roof membrane. In the case when drainage mat is
omitted, the water is in intimate contact with the roof membrane resulting in a higher heat transfer.
Open-Core (Filament Type/Percolating) Drainage Mat
To build on the theory of water flow over the solid core drainage mat, rainfall tests were performed with an
open-core or percolating drainage mat. The open-core drainage mat is comprised of non-woven polyethylene mesh
molded into a dimple profile with a filter fabric facer.
The graph below illustrates typical findings for tests including open-core drainage mat (purple line), solid-core
(red line), and no drainage mat (blue line).
Results. It was observed that the thermal performance of the roof assembly with an open-core drainage mat
is less efficient than a solid core drainage mat, but more efficient than the system without drainage mat. The test
results in Figure 15 show heat loss through the roof assembly increasing by approximately 20% during the rain event
with an open core drainage mat installed when compared to a roof assembly with a solid core drainage mat.
Figure 15 – Average Heat Flux Readings with Open Drainage Mat
75%
20%
16. It is theorized that the solid-core drainage mat provides an additional layer of separation from the roofing
membrane. Reducing the direct water contact with the roofing membrane reduces heat transfer. Where the open-
core drainage allows water to flow directly over the roofing membrane thus increasing heat transfer.
Water Resistant Weather Barrier Overlay
The final testing scenario included the installation of a loose-laid water resistant weather barrier (WRWB)
over the insulation, in lieu of filter fabric. The WRWB that was used is a non-woven polyolefin-based sheet and is
vapour permeable. The sheet was installed directly over the insulation and taped and sealed to the scupper drains (Dr.
Steve Johnston, 2015; Holger Merkel, 2011). Gravel ballast was installed over the sheet. Given the expectation that
very little water would run past the overlay sheet and reach the membrane level, a drainage mat was omitted under the
insulation.
The effect of the WRWB on the thermal performance of the roof assembly is illustrated with the grey trend
line in Figure 16 below:
0
2
4
6
8
10
12
14
16
18
20
-2 -1 0 1 2 3 4 5 6 7 8
HeatFlux–W/m²
Time - Hours
Average Heat Flux- No Drainage Mat Average Heat Flux- With Drainage Mat
Average Heat Flux - WRWB Filament Drain Mat
Results. As shown in Figure 16, the increase in heat flux through the roof assembly with the presence of a WRWB
sheet over the insulation is less than 5%. This minimal increase can be attributed to a small leakage of water to the
membrane level, likely caused from detailing of the sheet membrane at the scupper drains. By installing a waterproof
Figure 16 – Average Heat Flux Readings with Water Resistant Barrier Overlay
17. sheet above the insulation, the vast majority of water is directed to the drains and is prevented from reaching the roof
membrane level.
Equivalent Insulation Value Reduction
The heat flux density increase through the inverted roof assembly can be transferred into an equivalent
reduction in effective insulation value of the assembly through the following equation:
𝑅𝑆𝐼 𝐸𝑓𝑓 =
∆𝑇
𝑄 𝐴
Where: RSIeff = Thermal Resistance Value of Roof Assembly; W/m2K
ΔT = Final Temperature – Initial Temperature; ΔT= 21°C-1°C= 20°C
QA = Heat Flux per unit Area; W/m2
Applying this equation to the test data outlined in the Water Resistant Weather Barrier Overlay section, the
heat flux density increases were converted into effective RSI decrease as follows.
0
0.5
1
1.5
2
2.5
3
-2 -1 0 1 2 3 4 5 6 7 8
RSI-W/m²K
Time- Hours
RSI- No Drain mat RSI- Drain Mat RSI- WRWB RSI-Filament Drainage Mat
Figure 17 – Average RSI Reduction
18. The roof assembly began with an effective insulation value of approximately RSI 2.6 (R15) at steady-state,
which was calculated based on the thermal resistance of the roof assembly components and losses due to thermal
bridging. It is notable that the effective decrease in insulation value for the following testing scenarios are:
No drainage mat- Loss of approx. RSI 1.5 (R9)
Open-core drainage mat- Loss of approx. RSI 1.4 (R8)
Solid-core drainage mat- Loss of approx. RSI 1.2 (R7)
Waterproof sheet overlay- Loss of less than RSI 0.2 (<R1)
SUMMARY
The drainage capacity of different roof assemblies depends on a number of factors; however, in all the test
scenarios the majority of rainwater runoff drains at the membrane level. The quantity of water that drains at the
membrane level and from the top surface of the insulation largely depends on the following factors:
1. Insulation panel direction. The leakage rates are reduced when the insulation panels are installed parallel to
the slope.
2. Gaps between insulation panels. The thermal contraction of insulation panels during colder months increases
the leakage rates.
Based on the testing completed, despite the small sample size, the results show that different drainage scenarios
do have an impact on the thermal performance of inverted roof assemblies. Insulation panel direction, rainfall rates
and insulation board direction all affected the thermal performance of inverted roof assemblies. The most significant
heat loss and unexpected result was the increased heat loss when the drainage mat was removed and the insulation
was in direct contact with the roofing membrane. Prior to the testing, it was thought that a drainage mat installed
under the insulation would increase air movement and water drainage at the membrane level reducing the thermal
performance of the inverted roof assembly. The contact between rainwater and the roofing membrane is a significant
factor that increases heat flow through inverted roofs. As expected, installing a WRWB layer over the insulation
significantly reduces water drainage under the insulation and improves the thermal performance of the inverted roof.
The findings show the effective thermal performance (from most to least efficient) of inverted roof assemblies is
1. Inverted assembly with no drainage mat under the insulation and a vapour permeable layer over the insulation
2. Inverted assembly with a solid core drainage mat under the insulation
3. Inverted assembly with insulation in direct contact with the roofing membrane
19. ACKNOWLEDGMENTS
This research project was prepared by Morrison Hershfield and funded by the Homeowner Protection Office, a
branch of BC Housing. Special thanks is extended to Dow Building Solutions for providing technical and
construction expertise for the development of solutions outlined in this report. Roofing products for this project
were supplied by Soprema Canada and installed by Pacific Waterproofing Ltd.
REFERENCES
1. Dr. Steve Johnson, Dow Building Solutions, September 2015. Making U-value Calculations for Inverted Flat Roofs.
2. Dow Building Solutions, Updated January 2013. Insulating Inverted Flat Roofs with STYROFOAM Solutions: Basic
Principles.
3. British Board or Agreement, January 2011. Inverted Roof – Drainage and U Value Corrections.
4. H.M. Kunzel and K. Kiebl, Fraunhofer-Institute of Building Physics (Germany), 1996. Assessing Precipitation Heat
Losses of Protected Membrane Roofs.
5. Holger Merkel, Ph.D. (undated). Inverted Roofs with Reduced Heat Losses Due to a Water-Repellent Separating Layer.
6. BBS Institute, University of Denmark, Fraunhofer, Vienna U. (undated) Requirements of Inverted Roofs with a Drainage
Layer.
7. Cold Region Research and Engineering Laboratory, April 1977. Observations and Analysis of Protected Membrane Roofing
Systems.
8. Cold Region Research and Engineering Laboratory March 1976. Protected Membrane Roofs in Cold Regions.