International Journal of Engineering Research and Development
e-ISSN: 2278-067X, p-ISSN: 2278-800X, www.ijerd.com
Volume 8, Issue 9 (September 2013), PP. 18-25
18
Isolated Pico-Hydropower Generation for Power Quality
Improvement Using 24 Pulse Ac-Dc Converter
1
B.Praveena, 2
V.K.R.Mohan Rao, 3
Y.Rambabu
1
PG Scholar,2
Associate Professor, 3
Assistant Professor
1, 2, 3
Holy Mary Institute of Technology & Science
ABSTRACT
A comparative study between the topologies consisting of the Conventional Electronic Load Controller and the
Proposed Electronic Load controller (ELC)has been carried out in this paper for the power Quality Improvement
in a conventional Electronic Load controller used for Isolated pico-hydropower generation using Asynchronous
generator (AG). A polygon wound autotransformer with reduced Kilo Volts ampere rating is employed in the
proposed ELC for reducing the harmonic current reduction in order to meet the power quality requirements as
prescribed by IEEE standard. The conventional ELC employs six-pulse-bridge-rectifier and the Proposed ELC
employs twenty four -pulse-bridge-rectifier. The simulation of conventional Electronic Load Controller (ELC)
and proposed load controller is carried out in MATLAB/SIMULINK with simpower systems tool box.
Keywords:- Electronic load controller (ELC), isolated asynchronous generator (IAG), pico-hydroturbine, and
polygon wound autotransformer.
I. INTRODUCTION
The 6-pulse diode-bridge rectifier suffers from operating problems [1-2], such as poor power factor
―PF‖, injection of harmonic currents into the ac mains, equipment overheating due to harmonic-current
absorption, input ac mains voltage distortion, and malfunction of sensitive electronic equipment due to
electromagnetic interference. In order to prevent the harmonics from negatively affecting the utility lines, an
IEEE Standard 519 and IEC 555-3 [3] has been established to give limits on voltage and current distortions.
This has led to the consistent research in innovation of various configurations of ac–dc converters for mitigating
these harmonics and to comply with these standards.
Several methods based on the principle of increasing the number of pulses in ac-dc converters have
been presented which are simple to implement [4-7]. These methods use two or more converters, where the
harmonics generated by one converter are cancelled by the other converter, by a proper phase shift. To reduce
the transformer rating, multi-pulse converters have been reported in the literature [7]. Increasing the number of
pulses further results in improvement in various power-quality indexes but along with the additional cost of
different converters and increased system complexity. This paper presents a novel reduced-rating transformer
based 24-pulse ac-dc converter applying the same existing 6-pulse converter with addition of pulse
multiplication unit to improve power quality The pulse multiplication unit is achieved by multi-step reactor
instead of the conventional inter phase transformer with three controlled switches. Mathematical analysis and
simulation using MATLAB software is presented for twelve and 24-pulse converters. A comparison between the
two converters ―from power quality indices point of view‖ is held to monitor how much power quality indices
are improved with the increase of number of pulses. These simulation results are verified by experimental
results using the 36-pulse converter with the pulse multiplication technique using a 1 KW proto-type model. A
comparison between conventional 6-pulse and 24-pulse converter is concluded referred to the different power
quality indices to comply with the IEEE 519 and IEC 555-3.
II. SYSTEM DESCRIPTION AND ANALYSIS
Fig. 1 shows the isolated picohydro generating system that consists of an IAG, excitation capacitor,
consumer loads, within the prescribed limits by IEEE standards [8] as (6n ± 1) dominant harmonics are present
in such system. These harmonics cause additional losses in the system, resonance, and failure of the capacitor
bank. In a phase-controlled thyristor-based ELC, the phase angle of back-to-back-connected thyristors is
delayed from 0. to 180. as the consumer load is changed from zero to full load [9]. Due to a delay in firing
angle, it demands additional reactive power loading and injects harmonics in the system. In the controlled bridge
rectifier type of ELC [10], a firing angle is changed from 0. to 180. For single phase and 0. to 120. for three
phase to cover the full range of consumer load from 0% to 100%. In this scheme, six thyristors and their driving
circuits are required, and hence, it is complicated, injects harmonics, and demands additional reactive power.
Isolated Pico-Hydropower Generation for Power Quality Improvement…
19
Some of ELCs have been proposed that are having quality of the active filter and employs pulse width
modulation (PWM) voltage source converter along with the chopper and auxiliary load at dc link [10]–[13] to
eliminate the harmonics and provide the functions of voltage and frequency regulation. However, such types of
controllers make the system costly and complex with complicated control algorithm and simplicity requirement
by the isolated system is lost. Therefore, in this paper, a simple ELC is proposed that regulates the voltage and
frequency without any harmonic distortion at the generator terminals. The proposed controller consists of a 24-
pulse rectifier, a chopper, and an auxiliary load. In place of six-pulse rectifier, a 24-pulse rectifier-based ELC
has negligible harmonic distortion in the generated voltage and current. A comparative study based on
simulation is presented and it is also verified experimentally for both types of ELCs.
Fig.1. IAG system configuration and control strategy of a chopper switch in a six-pulse diode bridge ELC.
Conventional ELC (six-pulse diode rectifier along with the chopper). The diode bridge is used to
convert ac terminal voltage of IAG to dc voltage. The output dc voltage has the ripples, which should be
filtered, and therefore, a filtering capacitor is used to smoothen the dc voltage. An insulated gate bipolar
junction transistor (IGBT) is used as a chopper switch providing the variable dc voltage across the auxiliary
load. When the chopper is switched ON, the current flows through its auxiliary load and consume the difference
power (difference of generated power and consumer load power) that results in a constant load on the IAG, and
hence, constant voltage and frequency at the varying consumer loads. The duty cycle of the chopper is varied by
an analog-controller-based proportional–integral (PI) regulator. The sensed terminal voltage is compared with
reference voltage and error signal is processed through PI controller. The output of PI controller is compared
with fixed Frequency saw tooth wave to generate the varying duty cycle switching signal for the chopper switch.
According to the principle of operation of the system, the suitable value of capacitors is connected to generate
rated voltage at desired power [14]. The input power of the IAG is held constant at varying consumer loads.
Thus, IAG feeds two loads (consumer load + ELC) in parallel such that the total power is constant.
Pgen = PELC + Pload (1)
Where Pgen is generated power by the IAG (which should be kept constant), Pload is consumed power by
consumers, and PELC is the power absorbed by the ELC.
III. PROPOSED 24 PULSE SYSTEM DESCRIPTION
Fig. 2 shows the proposed reduced rating polygon connected autotransformer [15], [16] fed 24-pulse
ac–dc-converter-based ELC for an isolated pico-hydropower generation applications. This configuration needs
one zero-sequence blocking transformer (ZSBT) to ensure independent operation of the two rectifier bridges. It
exhibits high impedance to zero-sequence currents, resulting in 1200
conduction for each diode and also results
in equal current sharing in the output. An inter phase reactor tapped suitably to achieve pulse doubling [17]–[18]
has been connected at the output of the ZSBT. Two rectifiers output voltages Vd1 and Vd2 shown in Fig. 2 are
identical but have a phase shift of 30. (Required for achieving 12-pulse operation), and these voltages contain
ripple of six times the source frequency. The rectifier output voltage Vd is given by
Vd = 0.5 (Vd1 + Vd2) (2)
Vd = 0.5 (Vd1 + Vd2) (3)
Where Vm is an ac voltage ripple of 12 times the source frequency appearing across the tapped
interphase reactor, as shown in Fig. 2.
Isolated Pico-Hydropower Generation for Power Quality Improvement…
20
Fig.2 Proposed 24-pulse ELC for an IAG.
This pulse multiplication arrangement for diode bridge rectifiers has been used for desired pulse
doubling for line current harmonic reduction. The ZSBT helps in achieving independent operation of the two
rectifier bridges, thus eliminating the unwanted conducting sequence of the rectifier diodes. The ZSBT offers
very high impedance for zero sequence current components. However, detailed design of the interphase reactor
and ZSBT has been given in [18] and the same procedure is used in this paper. To achieve the 12-pulse
rectification, the necessary requirement is the generation of two sets of line voltages of equal magnitude that are
30. out of phase with respect to each other (either ±15. or 0. and 30.). From the generator terminal voltages, two
sets of three phase voltages (phase shifted through +150 and -150) are produced. The number of turns or voltage
fraction across each winding of the autotransformer required for +15. and -15. phase shift is calculated by
referring Fig.3 as follows:
VNS1 = VNS2 (4)
Fig. 3. Phasor and winding diagram of proposed 24-pulse autotransformer arrangement for 24-pulse ac–dc
converter for proposed ELC.
Where Vca is the line voltage of 415V. The terms VNS1 and VNS2 are the voltage induced across the
short winding and VNLL is the induced voltage across the long winding of polygon connected autotransformer.
Detailed hardware design of polygon connected autotransformer, ZSBT, and interphase transformer (IPT) are
given in the Appendix along with the complete design of the proposed 24-pulse ELC.
V. MATLAB MODELLING AND SIMULATION RESULTS
A 7.5 kW, 415 V, 50 Hz asynchronous machine is used as an IAG and the ELC is modelled using
available power electronics block set like diode bridge rectifier and a chopper with an auxiliary load and multi
winding transformers are used to create the desired phase shift for 24-pulse converter operation. In the following
sections the detailed comparison of two ELCs are explained.
Here, transient waveforms of the generator voltage (vabc ), generator current (iabc ), capacitor currents
(icabc ), consumer load current (ilabc ), ELC current (ida,idb,idc ), rms value of the generated voltage (vrms ),
frequency (f), speed of the generator (wg ), variation in the load power (Pload ), ELC power (PELC ), and generated
power (Pgen )are given under the sudden application and removal of the consumer loads for both types of ELCs
Isolated Pico-Hydropower Generation for Power Quality Improvement…
21
A. Simulations of 6-pulse ELC
Fig. 5& 6 shows the different transient waveforms of IAG with conventional ELC using six-pulse
diode bridge rectifier. In this the value of the capacitor is selected for generating the rated rms voltage (415 V) at
rated load (7.5 kW). Initially, the consumer load is OFF and the ELC is consuming full 7.5 kW power to an
auxiliary load. At 2 s, a consumer load of 5 kW is switched ON and it is observed that in order to maintain the
constant power at the generator terminal, the current drawn by ELC is reduced, while by removing the consumer
load at 2.3 s, it is again in-creased. Because of using six-pulse bridge-rectifier-based ELC, the distortion in the
generator voltage and current is observed, and the magnitude and frequency of the generated voltage are
controlled. Similar dynamics are performed in case of proposed 24-pulse ELC and explained in Fig. 6 and
discussed in the following section in detail. Fig. 7 shows the harmonic spectra under zero load condition when
conventional ELC draws maximum generated power; here, it is observed that due to nonlinear behaviour of this
ELC, it draws the current having total harmonic distortion (THD) of 37.13% which, in turn, distorts the voltage
(THD of 8.3%) and current (THD of 11.33%) at the generator terminal.
Fig. 4.Simulink model of IAG system configuration and control strategy of a chopper switch in a six pulse diode
bridge ELC.
Fig.5 results of generator voltage, generator current, ELC current, load current and individual phase currents
drawn by ELC respectively for 6 pulse ELC
Isolated Pico-Hydropower Generation for Power Quality Improvement…
22
Fig. 6 results of generator voltage (rms), frequency, speed and power respectively for 6 pulse ELC
(a)
(b)
Fig 7. (a) Harmonic distortion in current drawn due to 6-pulse ELC
(b) Harmonic distortion in generated voltage due to 6-pulse ELC
B. Simulations of 24-pulse ELC
Fig.9 & 10 shows the transient waveforms of IAG using 24-pulse rectifier-based ELC. In similar
manner of conventional ELC, the proposed ELC controls the constant power at generator terminal with variation
of consumer loads. Here, it is observed that the voltage and frequency are maintained at constant value, and at
the same time, the distortion in the generator voltage and current conventional ELC and the distortion in voltage
and current of the generator is negligible compared to conventional ELC. Fig. 11 shows the harmonic spectra of
the ELC current, generator voltage, and generator current, which shows that because of 24-pulse operation of an
ELC, its performance is improved in comparison to conventional ELC and the distortion in voltage and current
of the generator is observed almost negligible which is 0.42% and 0.48%, respectively.
Isolated Pico-Hydropower Generation for Power Quality Improvement…
23
Fig. 8. Simulink model of IAG system configuration and control strategy of a chopper switch in a 24-pulse
diode bridge ELC.
Fig. 9 results of generator voltage, generator current, ELC current, load current and individual phase currents
drawn by ELC respectively for 24 pulse ELC.
Fig. 10 results of generator voltage (rms), frequency, speed and power respectively for 24 pulse ELC.
Isolated Pico-Hydropower Generation for Power Quality Improvement…
24
(a)
(b)
Fig 11. (a) Harmonic distortion in current drawn due to 24-pulse ELC
(b) Harmonic distortion in generated voltage due to 24-pulse ELC
Table.1 Harmonic distortion in current drawn and generated voltage due to 6-pulse and 24-pulse respectively
Variable Total Harmonic Distortion
6-pulse ELC 24-pulse ELC
current 8.28% 0.42%
generated voltage 11.30% 0.48%
V. CONCLUSION
Since the conventional ELC has high total Harmonic Distortion for the generated voltage and current
under any load conditions and it is severe in case of zero consumer load condition due to the non linear behavior
of ELC due to presence of six-pulse diode Rectifier. With the proposed ELC the total harmonic distortion for the
generated voltage and current is low by maintaining constant power thus by improving the regulation of the IAG
and thus improving the Power Quality in case of both balanced and unbalanced loads. The proposed ELC has
been realized using 24-pulse converter and a chopper. A comparative study of both types of ELCs (6-pulse and
24-pulse configured ELC) has been demonstrated on the basis of simulation using standard software
MATLAB/SIMULINK with simpower systems tool box and developing a hardware prototype in the laboratory
environment.
REFERENCES
[1]. Cham, E.J., and Specht, T., ―The ANSI 49 rectifier with phase shift,‖ IEEE Trans. Ind. Applicat., Vol.
IA-20, pp. 615-624, 1984.
[2]. Key, T.S., and Lai, J-S., ―IEEE and International Harmonic Standards Impact on Power Electronics
Equipment Design‖, IEEE Trans. Ind. Application., Vol. IA-19, pp. 430-436, 1983.
[3]. Kim, S., Enjeti, P.N., Packebush, P., and Pitel, I.J., ―A new approach to improve power factor and
reduce harmonics in a three-phase diode rectifier type utility interface,‖ IEEE Trans. Ind. Applicat.,
Vol. 30, pp. 1557-1564, 1994.
[4]. Lee, B.S., Enjeti, P.N., and Pitel, I.J., ―A new 24-pulse diode rectifier system for AC motor drives
provides clean power utility interface with low kVA components,‖ in Conf. Rec. IEEE-IAS Annu.
Meeting, pp. 1024-1031, 1996.
[5]. Singh, B., Garg, V., and Bhuvaneswari, G., ―A novel T-connected autotransformer based 18-pulse AC–
DC converter for harmonic mitigation in adjustable speed induction motor drives,‖ IEEE Trans. Ind.
Electron., Vol. 54, No. 5, pp. 2500-2511, 2007.
[6]. Choi, S., Enjeti, P.N., Lee, H.H., and Pitel, I.J., ―A new active inter phase reactor for 12-pulse rectifiers
provides clean power utility interface,‖ IEEE Trans. Ind. Applicat., Vol. 32, pp. 1304-1311, 1996.
[7]. Villablanca, M., Valle, J.D., Rojas, J., and Rojas, W., ―A modified back-to-back HVdc system for 36-
pulse operation,‖ IEEE Trans. Power Delivery, Vol. 15, pp. 641-645, 2000.
Isolated Pico-Hydropower Generation for Power Quality Improvement…
25
[8]. IEEE Guide for Harmonic Control and Reactive Compensation of Static Power Converters, IEEE
Standard 519-1992.
[9]. L. A. C. Lopes and R. G. Almeida, ―Wind-driven induction generator with voltage and frequency
regulated by a reduced rating voltage source inverter,‖ IEEE Trans. Energy Convers., vol. 21, no. 2, pp.
297–304, Jun. 2006.
[10]. R. S. Bhatia, D. K. Jain, B. Singh, and S. P. Jain, ―Battery energy storage system for power
conditioning,‖ in Proc. Nat. Power Syst. Conf. NPSC- 2004, pp. 86–91.
[11]. B. Singh, S. S. Murthy, and S. Gupta, ―A voltage and frequency controller for self-excited induction
generators,‖ Electr. Power Compon. Syst., vol. 34, pp. 141–157, 2006.
[12]. E. G. Marra and J. A. Pomilo, ―Induction-gene rator-based system providing regulated voltage with
constant frequency,‖ IEEE Trans. Ind. Electron., vol. 47, no. 4, pp. 908–914, Aug. 2000.
[13]. E. G. Marra and J.A. Pomilio, ―Isolated asynchronous generator controlled by a VS-PWM bi-
directional converter for rural application,‖ IEEE Trans. Ind. Appl., vol. 35, no. 4, pp. 877–883,
Jul./Aug. 1999.
[14]. B. Singh, S. S. Murthy, and S. Gupta, ―STATCOM based voltage regulator for isolated asynchronous
generator feeding non-linear loads,‖ IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 1437–1452, Oct.
2006.
[15]. Derek A. Paice, Power Electronic Converter Harmonics—Multipulse Methods for Clean Power. New
York: IEEE Press, 1996.
[16]. B.Wu, High Power Converters and AC Drives. NewYork: Wiley/IEEE Press, Mar. 2006.
[17]. B. Singh, G. Bhuvaneswari, V. Garg, and S. Gairola, ―Pulse multiplication in AC–DC converters for
harmonic mitigation in vector-controlled induction motor drive,‖ IEEE Trans. Energy Convers., vol.
21, no. 2, pp. 342–352, Jun. 2006.
[18]. N. Mohan, T. M. Undeland, and W. P. Robbins, Power Electronics: Converters, Applications and
Design, 3rd ed. Singapore: Willey, 2004.

More Related Content

What's hot

Improved Fuzzy Control Strategy for Power Quality in Distributed Generation’s...
Improved Fuzzy Control Strategy for Power Quality in Distributed Generation’s...Improved Fuzzy Control Strategy for Power Quality in Distributed Generation’s...
Improved Fuzzy Control Strategy for Power Quality in Distributed Generation’s...IOSR Journals
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...MABUSUBANI SHAIK
 
IEEE 2013 12 eee B.tech & m.tech
IEEE  2013 12 eee B.tech & m.techIEEE  2013 12 eee B.tech & m.tech
IEEE 2013 12 eee B.tech & m.techVision Solutions
 
IEEE POWER ELECTRONICS PROJECT TITLE 2015-16
IEEE POWER ELECTRONICS PROJECT TITLE 2015-16IEEE POWER ELECTRONICS PROJECT TITLE 2015-16
IEEE POWER ELECTRONICS PROJECT TITLE 2015-16Spiro Vellore
 
Transformer Less Voltage Quadrupler Based DC-DC Converter with Coupled Induct...
Transformer Less Voltage Quadrupler Based DC-DC Converter with Coupled Induct...Transformer Less Voltage Quadrupler Based DC-DC Converter with Coupled Induct...
Transformer Less Voltage Quadrupler Based DC-DC Converter with Coupled Induct...IJPEDS-IAES
 
Steady-State Analysis of Electronic Load Controller
Steady-State Analysis of Electronic Load ControllerSteady-State Analysis of Electronic Load Controller
Steady-State Analysis of Electronic Load ControllerANURAG YADAV
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...MABUSUBANI SHAIK
 
Power Quality Enhancement Using the Interline Power Flow Controller
Power Quality Enhancement Using the Interline Power Flow ControllerPower Quality Enhancement Using the Interline Power Flow Controller
Power Quality Enhancement Using the Interline Power Flow ControllerIJPEDS-IAES
 
An Improved UPQC Controller to Provide Grid-Voltage Regulation
An Improved UPQC Controller to Provide Grid-Voltage RegulationAn Improved UPQC Controller to Provide Grid-Voltage Regulation
An Improved UPQC Controller to Provide Grid-Voltage RegulationIJMTST Journal
 

What's hot (20)

Ieee 2018 2019 new power electronics titles
Ieee 2018   2019 new power electronics titlesIeee 2018   2019 new power electronics titles
Ieee 2018 2019 new power electronics titles
 
Improved Fuzzy Control Strategy for Power Quality in Distributed Generation’s...
Improved Fuzzy Control Strategy for Power Quality in Distributed Generation’s...Improved Fuzzy Control Strategy for Power Quality in Distributed Generation’s...
Improved Fuzzy Control Strategy for Power Quality in Distributed Generation’s...
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Lz3620532059
Lz3620532059Lz3620532059
Lz3620532059
 
[IJET-V2I3P17] Authors: R.C.Rohini, G.Srividhya
[IJET-V2I3P17] Authors: R.C.Rohini, G.Srividhya[IJET-V2I3P17] Authors: R.C.Rohini, G.Srividhya
[IJET-V2I3P17] Authors: R.C.Rohini, G.Srividhya
 
I010416376
I010416376I010416376
I010416376
 
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
 
IEEE 2013 12 eee B.tech & m.tech
IEEE  2013 12 eee B.tech & m.techIEEE  2013 12 eee B.tech & m.tech
IEEE 2013 12 eee B.tech & m.tech
 
IEEE POWER ELECTRONICS PROJECT TITLE 2015-16
IEEE POWER ELECTRONICS PROJECT TITLE 2015-16IEEE POWER ELECTRONICS PROJECT TITLE 2015-16
IEEE POWER ELECTRONICS PROJECT TITLE 2015-16
 
Transformer Less Voltage Quadrupler Based DC-DC Converter with Coupled Induct...
Transformer Less Voltage Quadrupler Based DC-DC Converter with Coupled Induct...Transformer Less Voltage Quadrupler Based DC-DC Converter with Coupled Induct...
Transformer Less Voltage Quadrupler Based DC-DC Converter with Coupled Induct...
 
SEPIC CONVERTER
SEPIC CONVERTERSEPIC CONVERTER
SEPIC CONVERTER
 
K010418290
K010418290K010418290
K010418290
 
High Gain Non Isolated DC-DC Step-up Converters Integrated with Active and Pa...
High Gain Non Isolated DC-DC Step-up Converters Integrated with Active and Pa...High Gain Non Isolated DC-DC Step-up Converters Integrated with Active and Pa...
High Gain Non Isolated DC-DC Step-up Converters Integrated with Active and Pa...
 
Steady-State Analysis of Electronic Load Controller
Steady-State Analysis of Electronic Load ControllerSteady-State Analysis of Electronic Load Controller
Steady-State Analysis of Electronic Load Controller
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...
 
Power Quality Enhancement Using the Interline Power Flow Controller
Power Quality Enhancement Using the Interline Power Flow ControllerPower Quality Enhancement Using the Interline Power Flow Controller
Power Quality Enhancement Using the Interline Power Flow Controller
 
Time response of FOPID controlled PV based cascaded landsman converter-invert...
Time response of FOPID controlled PV based cascaded landsman converter-invert...Time response of FOPID controlled PV based cascaded landsman converter-invert...
Time response of FOPID controlled PV based cascaded landsman converter-invert...
 
An Improved UPQC Controller to Provide Grid-Voltage Regulation
An Improved UPQC Controller to Provide Grid-Voltage RegulationAn Improved UPQC Controller to Provide Grid-Voltage Regulation
An Improved UPQC Controller to Provide Grid-Voltage Regulation
 

Similar to Isolated Pico-Hydropower ELC for Power Quality

All ieee 2013
All ieee 2013All ieee 2013
All ieee 2013Ecway2004
 
All ieee 2013
All ieee 2013All ieee 2013
All ieee 2013Ecwayt
 
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...Venkata Gowtam Nallamothu
 
All ieee 2013
All ieee 2013All ieee 2013
All ieee 2013Ecwayt
 
All ieee 2013
All ieee 2013All ieee 2013
All ieee 2013Ecway2004
 
All ieee 2013
All ieee 2013All ieee 2013
All ieee 2013Ecwaytech
 
A Novel Power Factor Correction Rectifier for Enhancing Power Quality
A Novel Power Factor Correction Rectifier for Enhancing Power QualityA Novel Power Factor Correction Rectifier for Enhancing Power Quality
A Novel Power Factor Correction Rectifier for Enhancing Power QualityIJPEDS-IAES
 
Modified One Cycle Controlled Scheme for Single-Phase Grid Connected Pv-Fc Hy...
Modified One Cycle Controlled Scheme for Single-Phase Grid Connected Pv-Fc Hy...Modified One Cycle Controlled Scheme for Single-Phase Grid Connected Pv-Fc Hy...
Modified One Cycle Controlled Scheme for Single-Phase Grid Connected Pv-Fc Hy...IOSR Journals
 
Three Phase Twelve Pulse Controlled Rectifier with Reduced Output Current Har...
Three Phase Twelve Pulse Controlled Rectifier with Reduced Output Current Har...Three Phase Twelve Pulse Controlled Rectifier with Reduced Output Current Har...
Three Phase Twelve Pulse Controlled Rectifier with Reduced Output Current Har...paperpublications3
 
Comparison between an Interleaved Boost Converter and CUK Converter Fed BLDC ...
Comparison between an Interleaved Boost Converter and CUK Converter Fed BLDC ...Comparison between an Interleaved Boost Converter and CUK Converter Fed BLDC ...
Comparison between an Interleaved Boost Converter and CUK Converter Fed BLDC ...IJPEDS-IAES
 
Design and Development of Power Electronic Controller for Grid-connected PV A...
Design and Development of Power Electronic Controller for Grid-connected PV A...Design and Development of Power Electronic Controller for Grid-connected PV A...
Design and Development of Power Electronic Controller for Grid-connected PV A...IJAPEJOURNAL
 
Novel high step up dc–dc converter with active coupled-inductor network for a...
Novel high step up dc–dc converter with active coupled-inductor network for a...Novel high step up dc–dc converter with active coupled-inductor network for a...
Novel high step up dc–dc converter with active coupled-inductor network for a...I3E Technologies
 
Low Voltage Energy Harvesting by an Efficient AC-DC Step-Up Converter
Low Voltage Energy Harvesting by an Efficient AC-DC Step-Up ConverterLow Voltage Energy Harvesting by an Efficient AC-DC Step-Up Converter
Low Voltage Energy Harvesting by an Efficient AC-DC Step-Up ConverterIOSR Journals
 
A generalized switching function-based SVM algorithm of single-phase three-le...
A generalized switching function-based SVM algorithm of single-phase three-le...A generalized switching function-based SVM algorithm of single-phase three-le...
A generalized switching function-based SVM algorithm of single-phase three-le...IJECEIAES
 

Similar to Isolated Pico-Hydropower ELC for Power Quality (20)

All ieee 2013
All ieee 2013All ieee 2013
All ieee 2013
 
All ieee 2013
All ieee 2013All ieee 2013
All ieee 2013
 
All ieee 2013
All ieee 2013All ieee 2013
All ieee 2013
 
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
 
All ieee 2013
All ieee 2013All ieee 2013
All ieee 2013
 
All ieee 2013
All ieee 2013All ieee 2013
All ieee 2013
 
All ieee 2013
All ieee 2013All ieee 2013
All ieee 2013
 
All ieee 2013
All ieee 2013All ieee 2013
All ieee 2013
 
All ieee 2013
All ieee 2013All ieee 2013
All ieee 2013
 
E010623545
E010623545E010623545
E010623545
 
A Novel Power Factor Correction Rectifier for Enhancing Power Quality
A Novel Power Factor Correction Rectifier for Enhancing Power QualityA Novel Power Factor Correction Rectifier for Enhancing Power Quality
A Novel Power Factor Correction Rectifier for Enhancing Power Quality
 
Hardware Implementation of Solar Photovoltaic System based Half Bridge Series...
Hardware Implementation of Solar Photovoltaic System based Half Bridge Series...Hardware Implementation of Solar Photovoltaic System based Half Bridge Series...
Hardware Implementation of Solar Photovoltaic System based Half Bridge Series...
 
Modified One Cycle Controlled Scheme for Single-Phase Grid Connected Pv-Fc Hy...
Modified One Cycle Controlled Scheme for Single-Phase Grid Connected Pv-Fc Hy...Modified One Cycle Controlled Scheme for Single-Phase Grid Connected Pv-Fc Hy...
Modified One Cycle Controlled Scheme for Single-Phase Grid Connected Pv-Fc Hy...
 
Three Phase Twelve Pulse Controlled Rectifier with Reduced Output Current Har...
Three Phase Twelve Pulse Controlled Rectifier with Reduced Output Current Har...Three Phase Twelve Pulse Controlled Rectifier with Reduced Output Current Har...
Three Phase Twelve Pulse Controlled Rectifier with Reduced Output Current Har...
 
Comparison between an Interleaved Boost Converter and CUK Converter Fed BLDC ...
Comparison between an Interleaved Boost Converter and CUK Converter Fed BLDC ...Comparison between an Interleaved Boost Converter and CUK Converter Fed BLDC ...
Comparison between an Interleaved Boost Converter and CUK Converter Fed BLDC ...
 
Design and Development of Power Electronic Controller for Grid-connected PV A...
Design and Development of Power Electronic Controller for Grid-connected PV A...Design and Development of Power Electronic Controller for Grid-connected PV A...
Design and Development of Power Electronic Controller for Grid-connected PV A...
 
Novel high step up dc–dc converter with active coupled-inductor network for a...
Novel high step up dc–dc converter with active coupled-inductor network for a...Novel high step up dc–dc converter with active coupled-inductor network for a...
Novel high step up dc–dc converter with active coupled-inductor network for a...
 
Low Voltage Energy Harvesting by an Efficient AC-DC Step-Up Converter
Low Voltage Energy Harvesting by an Efficient AC-DC Step-Up ConverterLow Voltage Energy Harvesting by an Efficient AC-DC Step-Up Converter
Low Voltage Energy Harvesting by an Efficient AC-DC Step-Up Converter
 
A generalized switching function-based SVM algorithm of single-phase three-le...
A generalized switching function-based SVM algorithm of single-phase three-le...A generalized switching function-based SVM algorithm of single-phase three-le...
A generalized switching function-based SVM algorithm of single-phase three-le...
 
A04 05 0110
A04 05 0110A04 05 0110
A04 05 0110
 

More from IJERD Editor

A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service AttacksA Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service AttacksIJERD Editor
 
MEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACEMEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACEIJERD Editor
 
Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...IJERD Editor
 
Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’IJERD Editor
 
Reducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding DesignReducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding DesignIJERD Editor
 
Router 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and VerificationRouter 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and VerificationIJERD Editor
 
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...IJERD Editor
 
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVRMitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVRIJERD Editor
 
Study on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive ManufacturingStudy on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive ManufacturingIJERD Editor
 
Spyware triggering system by particular string value
Spyware triggering system by particular string valueSpyware triggering system by particular string value
Spyware triggering system by particular string valueIJERD Editor
 
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...IJERD Editor
 
Secure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid SchemeSecure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid SchemeIJERD Editor
 
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...IJERD Editor
 
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web CameraGesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web CameraIJERD Editor
 
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...IJERD Editor
 
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...IJERD Editor
 
Moon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF DxingMoon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF DxingIJERD Editor
 
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...IJERD Editor
 
Importance of Measurements in Smart Grid
Importance of Measurements in Smart GridImportance of Measurements in Smart Grid
Importance of Measurements in Smart GridIJERD Editor
 
Study of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powderStudy of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powderIJERD Editor
 

More from IJERD Editor (20)

A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service AttacksA Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
 
MEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACEMEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACE
 
Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...
 
Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’
 
Reducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding DesignReducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding Design
 
Router 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and VerificationRouter 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and Verification
 
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
 
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVRMitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
 
Study on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive ManufacturingStudy on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive Manufacturing
 
Spyware triggering system by particular string value
Spyware triggering system by particular string valueSpyware triggering system by particular string value
Spyware triggering system by particular string value
 
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
 
Secure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid SchemeSecure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid Scheme
 
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
 
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web CameraGesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
 
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
 
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
 
Moon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF DxingMoon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF Dxing
 
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
 
Importance of Measurements in Smart Grid
Importance of Measurements in Smart GridImportance of Measurements in Smart Grid
Importance of Measurements in Smart Grid
 
Study of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powderStudy of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powder
 

Recently uploaded

VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service JamshedpurVIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service JamshedpurSuhani Kapoor
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...lizamodels9
 
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Dave Litwiller
 
Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessAggregage
 
Call Girls in Mehrauli Delhi 💯Call Us 🔝8264348440🔝
Call Girls in Mehrauli Delhi 💯Call Us 🔝8264348440🔝Call Girls in Mehrauli Delhi 💯Call Us 🔝8264348440🔝
Call Girls in Mehrauli Delhi 💯Call Us 🔝8264348440🔝soniya singh
 
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Tina Ji
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdfRenandantas16
 
Non Text Magic Studio Magic Design for Presentations L&P.pptx
Non Text Magic Studio Magic Design for Presentations L&P.pptxNon Text Magic Studio Magic Design for Presentations L&P.pptx
Non Text Magic Studio Magic Design for Presentations L&P.pptxAbhayThakur200703
 
GD Birla and his contribution in management
GD Birla and his contribution in managementGD Birla and his contribution in management
GD Birla and his contribution in managementchhavia330
 
Progress Report - Oracle Database Analyst Summit
Progress  Report - Oracle Database Analyst SummitProgress  Report - Oracle Database Analyst Summit
Progress Report - Oracle Database Analyst SummitHolger Mueller
 
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...lizamodels9
 
Catalogue ONG NUOC PPR DE NHAT .pdf
Catalogue ONG NUOC PPR DE NHAT      .pdfCatalogue ONG NUOC PPR DE NHAT      .pdf
Catalogue ONG NUOC PPR DE NHAT .pdfOrient Homes
 
Vip Female Escorts Noida 9711199171 Greater Noida Escorts Service
Vip Female Escorts Noida 9711199171 Greater Noida Escorts ServiceVip Female Escorts Noida 9711199171 Greater Noida Escorts Service
Vip Female Escorts Noida 9711199171 Greater Noida Escorts Serviceankitnayak356677
 
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,noida100girls
 
Grateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfGrateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfPaul Menig
 
RE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechRE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechNewman George Leech
 
Monte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMMonte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMRavindra Nath Shukla
 
Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni
 

Recently uploaded (20)

VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service JamshedpurVIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
 
Forklift Operations: Safety through Cartoons
Forklift Operations: Safety through CartoonsForklift Operations: Safety through Cartoons
Forklift Operations: Safety through Cartoons
 
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
 
Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for Success
 
Call Girls in Mehrauli Delhi 💯Call Us 🔝8264348440🔝
Call Girls in Mehrauli Delhi 💯Call Us 🔝8264348440🔝Call Girls in Mehrauli Delhi 💯Call Us 🔝8264348440🔝
Call Girls in Mehrauli Delhi 💯Call Us 🔝8264348440🔝
 
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
 
Non Text Magic Studio Magic Design for Presentations L&P.pptx
Non Text Magic Studio Magic Design for Presentations L&P.pptxNon Text Magic Studio Magic Design for Presentations L&P.pptx
Non Text Magic Studio Magic Design for Presentations L&P.pptx
 
GD Birla and his contribution in management
GD Birla and his contribution in managementGD Birla and his contribution in management
GD Birla and his contribution in management
 
Progress Report - Oracle Database Analyst Summit
Progress  Report - Oracle Database Analyst SummitProgress  Report - Oracle Database Analyst Summit
Progress Report - Oracle Database Analyst Summit
 
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
 
Catalogue ONG NUOC PPR DE NHAT .pdf
Catalogue ONG NUOC PPR DE NHAT      .pdfCatalogue ONG NUOC PPR DE NHAT      .pdf
Catalogue ONG NUOC PPR DE NHAT .pdf
 
Vip Female Escorts Noida 9711199171 Greater Noida Escorts Service
Vip Female Escorts Noida 9711199171 Greater Noida Escorts ServiceVip Female Escorts Noida 9711199171 Greater Noida Escorts Service
Vip Female Escorts Noida 9711199171 Greater Noida Escorts Service
 
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
 
Grateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfGrateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdf
 
KestrelPro Flyer Japan IT Week 2024 (English)
KestrelPro Flyer Japan IT Week 2024 (English)KestrelPro Flyer Japan IT Week 2024 (English)
KestrelPro Flyer Japan IT Week 2024 (English)
 
RE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechRE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman Leech
 
Monte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMMonte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSM
 
Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.
 

Isolated Pico-Hydropower ELC for Power Quality

  • 1. International Journal of Engineering Research and Development e-ISSN: 2278-067X, p-ISSN: 2278-800X, www.ijerd.com Volume 8, Issue 9 (September 2013), PP. 18-25 18 Isolated Pico-Hydropower Generation for Power Quality Improvement Using 24 Pulse Ac-Dc Converter 1 B.Praveena, 2 V.K.R.Mohan Rao, 3 Y.Rambabu 1 PG Scholar,2 Associate Professor, 3 Assistant Professor 1, 2, 3 Holy Mary Institute of Technology & Science ABSTRACT A comparative study between the topologies consisting of the Conventional Electronic Load Controller and the Proposed Electronic Load controller (ELC)has been carried out in this paper for the power Quality Improvement in a conventional Electronic Load controller used for Isolated pico-hydropower generation using Asynchronous generator (AG). A polygon wound autotransformer with reduced Kilo Volts ampere rating is employed in the proposed ELC for reducing the harmonic current reduction in order to meet the power quality requirements as prescribed by IEEE standard. The conventional ELC employs six-pulse-bridge-rectifier and the Proposed ELC employs twenty four -pulse-bridge-rectifier. The simulation of conventional Electronic Load Controller (ELC) and proposed load controller is carried out in MATLAB/SIMULINK with simpower systems tool box. Keywords:- Electronic load controller (ELC), isolated asynchronous generator (IAG), pico-hydroturbine, and polygon wound autotransformer. I. INTRODUCTION The 6-pulse diode-bridge rectifier suffers from operating problems [1-2], such as poor power factor ―PF‖, injection of harmonic currents into the ac mains, equipment overheating due to harmonic-current absorption, input ac mains voltage distortion, and malfunction of sensitive electronic equipment due to electromagnetic interference. In order to prevent the harmonics from negatively affecting the utility lines, an IEEE Standard 519 and IEC 555-3 [3] has been established to give limits on voltage and current distortions. This has led to the consistent research in innovation of various configurations of ac–dc converters for mitigating these harmonics and to comply with these standards. Several methods based on the principle of increasing the number of pulses in ac-dc converters have been presented which are simple to implement [4-7]. These methods use two or more converters, where the harmonics generated by one converter are cancelled by the other converter, by a proper phase shift. To reduce the transformer rating, multi-pulse converters have been reported in the literature [7]. Increasing the number of pulses further results in improvement in various power-quality indexes but along with the additional cost of different converters and increased system complexity. This paper presents a novel reduced-rating transformer based 24-pulse ac-dc converter applying the same existing 6-pulse converter with addition of pulse multiplication unit to improve power quality The pulse multiplication unit is achieved by multi-step reactor instead of the conventional inter phase transformer with three controlled switches. Mathematical analysis and simulation using MATLAB software is presented for twelve and 24-pulse converters. A comparison between the two converters ―from power quality indices point of view‖ is held to monitor how much power quality indices are improved with the increase of number of pulses. These simulation results are verified by experimental results using the 36-pulse converter with the pulse multiplication technique using a 1 KW proto-type model. A comparison between conventional 6-pulse and 24-pulse converter is concluded referred to the different power quality indices to comply with the IEEE 519 and IEC 555-3. II. SYSTEM DESCRIPTION AND ANALYSIS Fig. 1 shows the isolated picohydro generating system that consists of an IAG, excitation capacitor, consumer loads, within the prescribed limits by IEEE standards [8] as (6n ± 1) dominant harmonics are present in such system. These harmonics cause additional losses in the system, resonance, and failure of the capacitor bank. In a phase-controlled thyristor-based ELC, the phase angle of back-to-back-connected thyristors is delayed from 0. to 180. as the consumer load is changed from zero to full load [9]. Due to a delay in firing angle, it demands additional reactive power loading and injects harmonics in the system. In the controlled bridge rectifier type of ELC [10], a firing angle is changed from 0. to 180. For single phase and 0. to 120. for three phase to cover the full range of consumer load from 0% to 100%. In this scheme, six thyristors and their driving circuits are required, and hence, it is complicated, injects harmonics, and demands additional reactive power.
  • 2. Isolated Pico-Hydropower Generation for Power Quality Improvement… 19 Some of ELCs have been proposed that are having quality of the active filter and employs pulse width modulation (PWM) voltage source converter along with the chopper and auxiliary load at dc link [10]–[13] to eliminate the harmonics and provide the functions of voltage and frequency regulation. However, such types of controllers make the system costly and complex with complicated control algorithm and simplicity requirement by the isolated system is lost. Therefore, in this paper, a simple ELC is proposed that regulates the voltage and frequency without any harmonic distortion at the generator terminals. The proposed controller consists of a 24- pulse rectifier, a chopper, and an auxiliary load. In place of six-pulse rectifier, a 24-pulse rectifier-based ELC has negligible harmonic distortion in the generated voltage and current. A comparative study based on simulation is presented and it is also verified experimentally for both types of ELCs. Fig.1. IAG system configuration and control strategy of a chopper switch in a six-pulse diode bridge ELC. Conventional ELC (six-pulse diode rectifier along with the chopper). The diode bridge is used to convert ac terminal voltage of IAG to dc voltage. The output dc voltage has the ripples, which should be filtered, and therefore, a filtering capacitor is used to smoothen the dc voltage. An insulated gate bipolar junction transistor (IGBT) is used as a chopper switch providing the variable dc voltage across the auxiliary load. When the chopper is switched ON, the current flows through its auxiliary load and consume the difference power (difference of generated power and consumer load power) that results in a constant load on the IAG, and hence, constant voltage and frequency at the varying consumer loads. The duty cycle of the chopper is varied by an analog-controller-based proportional–integral (PI) regulator. The sensed terminal voltage is compared with reference voltage and error signal is processed through PI controller. The output of PI controller is compared with fixed Frequency saw tooth wave to generate the varying duty cycle switching signal for the chopper switch. According to the principle of operation of the system, the suitable value of capacitors is connected to generate rated voltage at desired power [14]. The input power of the IAG is held constant at varying consumer loads. Thus, IAG feeds two loads (consumer load + ELC) in parallel such that the total power is constant. Pgen = PELC + Pload (1) Where Pgen is generated power by the IAG (which should be kept constant), Pload is consumed power by consumers, and PELC is the power absorbed by the ELC. III. PROPOSED 24 PULSE SYSTEM DESCRIPTION Fig. 2 shows the proposed reduced rating polygon connected autotransformer [15], [16] fed 24-pulse ac–dc-converter-based ELC for an isolated pico-hydropower generation applications. This configuration needs one zero-sequence blocking transformer (ZSBT) to ensure independent operation of the two rectifier bridges. It exhibits high impedance to zero-sequence currents, resulting in 1200 conduction for each diode and also results in equal current sharing in the output. An inter phase reactor tapped suitably to achieve pulse doubling [17]–[18] has been connected at the output of the ZSBT. Two rectifiers output voltages Vd1 and Vd2 shown in Fig. 2 are identical but have a phase shift of 30. (Required for achieving 12-pulse operation), and these voltages contain ripple of six times the source frequency. The rectifier output voltage Vd is given by Vd = 0.5 (Vd1 + Vd2) (2) Vd = 0.5 (Vd1 + Vd2) (3) Where Vm is an ac voltage ripple of 12 times the source frequency appearing across the tapped interphase reactor, as shown in Fig. 2.
  • 3. Isolated Pico-Hydropower Generation for Power Quality Improvement… 20 Fig.2 Proposed 24-pulse ELC for an IAG. This pulse multiplication arrangement for diode bridge rectifiers has been used for desired pulse doubling for line current harmonic reduction. The ZSBT helps in achieving independent operation of the two rectifier bridges, thus eliminating the unwanted conducting sequence of the rectifier diodes. The ZSBT offers very high impedance for zero sequence current components. However, detailed design of the interphase reactor and ZSBT has been given in [18] and the same procedure is used in this paper. To achieve the 12-pulse rectification, the necessary requirement is the generation of two sets of line voltages of equal magnitude that are 30. out of phase with respect to each other (either ±15. or 0. and 30.). From the generator terminal voltages, two sets of three phase voltages (phase shifted through +150 and -150) are produced. The number of turns or voltage fraction across each winding of the autotransformer required for +15. and -15. phase shift is calculated by referring Fig.3 as follows: VNS1 = VNS2 (4) Fig. 3. Phasor and winding diagram of proposed 24-pulse autotransformer arrangement for 24-pulse ac–dc converter for proposed ELC. Where Vca is the line voltage of 415V. The terms VNS1 and VNS2 are the voltage induced across the short winding and VNLL is the induced voltage across the long winding of polygon connected autotransformer. Detailed hardware design of polygon connected autotransformer, ZSBT, and interphase transformer (IPT) are given in the Appendix along with the complete design of the proposed 24-pulse ELC. V. MATLAB MODELLING AND SIMULATION RESULTS A 7.5 kW, 415 V, 50 Hz asynchronous machine is used as an IAG and the ELC is modelled using available power electronics block set like diode bridge rectifier and a chopper with an auxiliary load and multi winding transformers are used to create the desired phase shift for 24-pulse converter operation. In the following sections the detailed comparison of two ELCs are explained. Here, transient waveforms of the generator voltage (vabc ), generator current (iabc ), capacitor currents (icabc ), consumer load current (ilabc ), ELC current (ida,idb,idc ), rms value of the generated voltage (vrms ), frequency (f), speed of the generator (wg ), variation in the load power (Pload ), ELC power (PELC ), and generated power (Pgen )are given under the sudden application and removal of the consumer loads for both types of ELCs
  • 4. Isolated Pico-Hydropower Generation for Power Quality Improvement… 21 A. Simulations of 6-pulse ELC Fig. 5& 6 shows the different transient waveforms of IAG with conventional ELC using six-pulse diode bridge rectifier. In this the value of the capacitor is selected for generating the rated rms voltage (415 V) at rated load (7.5 kW). Initially, the consumer load is OFF and the ELC is consuming full 7.5 kW power to an auxiliary load. At 2 s, a consumer load of 5 kW is switched ON and it is observed that in order to maintain the constant power at the generator terminal, the current drawn by ELC is reduced, while by removing the consumer load at 2.3 s, it is again in-creased. Because of using six-pulse bridge-rectifier-based ELC, the distortion in the generator voltage and current is observed, and the magnitude and frequency of the generated voltage are controlled. Similar dynamics are performed in case of proposed 24-pulse ELC and explained in Fig. 6 and discussed in the following section in detail. Fig. 7 shows the harmonic spectra under zero load condition when conventional ELC draws maximum generated power; here, it is observed that due to nonlinear behaviour of this ELC, it draws the current having total harmonic distortion (THD) of 37.13% which, in turn, distorts the voltage (THD of 8.3%) and current (THD of 11.33%) at the generator terminal. Fig. 4.Simulink model of IAG system configuration and control strategy of a chopper switch in a six pulse diode bridge ELC. Fig.5 results of generator voltage, generator current, ELC current, load current and individual phase currents drawn by ELC respectively for 6 pulse ELC
  • 5. Isolated Pico-Hydropower Generation for Power Quality Improvement… 22 Fig. 6 results of generator voltage (rms), frequency, speed and power respectively for 6 pulse ELC (a) (b) Fig 7. (a) Harmonic distortion in current drawn due to 6-pulse ELC (b) Harmonic distortion in generated voltage due to 6-pulse ELC B. Simulations of 24-pulse ELC Fig.9 & 10 shows the transient waveforms of IAG using 24-pulse rectifier-based ELC. In similar manner of conventional ELC, the proposed ELC controls the constant power at generator terminal with variation of consumer loads. Here, it is observed that the voltage and frequency are maintained at constant value, and at the same time, the distortion in the generator voltage and current conventional ELC and the distortion in voltage and current of the generator is negligible compared to conventional ELC. Fig. 11 shows the harmonic spectra of the ELC current, generator voltage, and generator current, which shows that because of 24-pulse operation of an ELC, its performance is improved in comparison to conventional ELC and the distortion in voltage and current of the generator is observed almost negligible which is 0.42% and 0.48%, respectively.
  • 6. Isolated Pico-Hydropower Generation for Power Quality Improvement… 23 Fig. 8. Simulink model of IAG system configuration and control strategy of a chopper switch in a 24-pulse diode bridge ELC. Fig. 9 results of generator voltage, generator current, ELC current, load current and individual phase currents drawn by ELC respectively for 24 pulse ELC. Fig. 10 results of generator voltage (rms), frequency, speed and power respectively for 24 pulse ELC.
  • 7. Isolated Pico-Hydropower Generation for Power Quality Improvement… 24 (a) (b) Fig 11. (a) Harmonic distortion in current drawn due to 24-pulse ELC (b) Harmonic distortion in generated voltage due to 24-pulse ELC Table.1 Harmonic distortion in current drawn and generated voltage due to 6-pulse and 24-pulse respectively Variable Total Harmonic Distortion 6-pulse ELC 24-pulse ELC current 8.28% 0.42% generated voltage 11.30% 0.48% V. CONCLUSION Since the conventional ELC has high total Harmonic Distortion for the generated voltage and current under any load conditions and it is severe in case of zero consumer load condition due to the non linear behavior of ELC due to presence of six-pulse diode Rectifier. With the proposed ELC the total harmonic distortion for the generated voltage and current is low by maintaining constant power thus by improving the regulation of the IAG and thus improving the Power Quality in case of both balanced and unbalanced loads. The proposed ELC has been realized using 24-pulse converter and a chopper. A comparative study of both types of ELCs (6-pulse and 24-pulse configured ELC) has been demonstrated on the basis of simulation using standard software MATLAB/SIMULINK with simpower systems tool box and developing a hardware prototype in the laboratory environment. REFERENCES [1]. Cham, E.J., and Specht, T., ―The ANSI 49 rectifier with phase shift,‖ IEEE Trans. Ind. Applicat., Vol. IA-20, pp. 615-624, 1984. [2]. Key, T.S., and Lai, J-S., ―IEEE and International Harmonic Standards Impact on Power Electronics Equipment Design‖, IEEE Trans. Ind. Application., Vol. IA-19, pp. 430-436, 1983. [3]. Kim, S., Enjeti, P.N., Packebush, P., and Pitel, I.J., ―A new approach to improve power factor and reduce harmonics in a three-phase diode rectifier type utility interface,‖ IEEE Trans. Ind. Applicat., Vol. 30, pp. 1557-1564, 1994. [4]. Lee, B.S., Enjeti, P.N., and Pitel, I.J., ―A new 24-pulse diode rectifier system for AC motor drives provides clean power utility interface with low kVA components,‖ in Conf. Rec. IEEE-IAS Annu. Meeting, pp. 1024-1031, 1996. [5]. Singh, B., Garg, V., and Bhuvaneswari, G., ―A novel T-connected autotransformer based 18-pulse AC– DC converter for harmonic mitigation in adjustable speed induction motor drives,‖ IEEE Trans. Ind. Electron., Vol. 54, No. 5, pp. 2500-2511, 2007. [6]. Choi, S., Enjeti, P.N., Lee, H.H., and Pitel, I.J., ―A new active inter phase reactor for 12-pulse rectifiers provides clean power utility interface,‖ IEEE Trans. Ind. Applicat., Vol. 32, pp. 1304-1311, 1996. [7]. Villablanca, M., Valle, J.D., Rojas, J., and Rojas, W., ―A modified back-to-back HVdc system for 36- pulse operation,‖ IEEE Trans. Power Delivery, Vol. 15, pp. 641-645, 2000.
  • 8. Isolated Pico-Hydropower Generation for Power Quality Improvement… 25 [8]. IEEE Guide for Harmonic Control and Reactive Compensation of Static Power Converters, IEEE Standard 519-1992. [9]. L. A. C. Lopes and R. G. Almeida, ―Wind-driven induction generator with voltage and frequency regulated by a reduced rating voltage source inverter,‖ IEEE Trans. Energy Convers., vol. 21, no. 2, pp. 297–304, Jun. 2006. [10]. R. S. Bhatia, D. K. Jain, B. Singh, and S. P. Jain, ―Battery energy storage system for power conditioning,‖ in Proc. Nat. Power Syst. Conf. NPSC- 2004, pp. 86–91. [11]. B. Singh, S. S. Murthy, and S. Gupta, ―A voltage and frequency controller for self-excited induction generators,‖ Electr. Power Compon. Syst., vol. 34, pp. 141–157, 2006. [12]. E. G. Marra and J. A. Pomilo, ―Induction-gene rator-based system providing regulated voltage with constant frequency,‖ IEEE Trans. Ind. Electron., vol. 47, no. 4, pp. 908–914, Aug. 2000. [13]. E. G. Marra and J.A. Pomilio, ―Isolated asynchronous generator controlled by a VS-PWM bi- directional converter for rural application,‖ IEEE Trans. Ind. Appl., vol. 35, no. 4, pp. 877–883, Jul./Aug. 1999. [14]. B. Singh, S. S. Murthy, and S. Gupta, ―STATCOM based voltage regulator for isolated asynchronous generator feeding non-linear loads,‖ IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 1437–1452, Oct. 2006. [15]. Derek A. Paice, Power Electronic Converter Harmonics—Multipulse Methods for Clean Power. New York: IEEE Press, 1996. [16]. B.Wu, High Power Converters and AC Drives. NewYork: Wiley/IEEE Press, Mar. 2006. [17]. B. Singh, G. Bhuvaneswari, V. Garg, and S. Gairola, ―Pulse multiplication in AC–DC converters for harmonic mitigation in vector-controlled induction motor drive,‖ IEEE Trans. Energy Convers., vol. 21, no. 2, pp. 342–352, Jun. 2006. [18]. N. Mohan, T. M. Undeland, and W. P. Robbins, Power Electronics: Converters, Applications and Design, 3rd ed. Singapore: Willey, 2004.