November 2015 Prepared by Alan Mason AME Pty
LTD
1
Arc Flash CAT 0
Electric Mining Shovel
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
2
AIM of
PRESENTATION
 Is to show how
–two Electric Mining Shovels
–were modified
–to achieve Arc Flash CAT 0.
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
3
CONTENTS
1. CAT 0 Term
2. Consequences
3. What we know?
4. Analysis is a 3 Step Process
5. Mitigation
6. Equipment
7. Benefits
8. Questions
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
4
TERMS
Arc Fault:
 Is the fault current that travels through air between two
conducting phases or phase to earth with an
uncontrolled release of energy. Generally due to un-
natural causes.
Arc Flash:
 Is a consequence from an Arc Fault but in this subject
is generally understood to also embody all the
consequences of an arc fault.
CAT 0:
 Arc Fault Incident Energy is less than
1.2 cal/cm2 (Heat Energy).
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
5
Arc Fault
Consequences
1. Thermal Burns
2. Electrical Shock
3. Molten Metal
4. Projectiles
5. Blast & Pressure
waves
6. Intense Light (Arc
Flash)
7. Intense Sound
8. Fire
9.Strong Magnetic
Fields
10.Plasma
11.Toxic Gasses
12.Vapours
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
6
Arc Flash
Consequences
Subject to the level of Energy
released the consequences
to :
– a worker will vary from
mild burns to permanent
injury or death.
– equipment may be nil to
catastrophic failure:
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
7
Example: Arc Flash Incident on a
6.6kv Fused Feeder compartment within
the HV Cabinet of an Electric Mining Shovel.
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
8
What we know:
Let Through Energy vs Time
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
9
What we know:
Protection Devices vs Time
Shovel Standard
Fast Protection
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
10
What we know:
Arc Fault Current Time Characteristic
Shovel Standard
Fast Protection
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
11
What we know:
Arc Flash Pressure Rise vs &Time
Shovel Standard
Fast Protection
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
12
What we know:
Arc Flash Incident Energy
E ~ k * V * Ibf * t …….…..Eq:1
d2
 Where:
– E = Incident Energy (Cal/cm2)………Heat Energy
– V = System Voltage (kV)
– t = Arcing Time (seconds)
– d = Working distance from Arc (mm)
– Ibf = Bolted fault Current (kA)
– k = Constant
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
13
Analysis is a
3 Step Process
1. Shovel Single Line Diagram (SLD)
2. Calculate & Analyse
3. Determine CAT 0 measures &
install
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
14
Analysis is a
3 Step Process
Step 1:
Single Line Diagram
PTW
Step 2:
Fault Analysis
IEEE 1584
Step 3
Mitigation
Include details for all:
-Voltages
-Cables (L, CSA, Ez)
-Transformers (kva, Ez)
-Protective Devices
(Type, settings)
-Loads (Motors, etc)
Calculate:
-Bus Fault kA
-Arc Flash Fault kA
-Incident Energy
-Isolation Times
-Arc Flash Boundary
-Arc Flash Category
-Select BUS’s > CAT 0
-Use Hierarchy of Controls
-Reduce Trip times:
• Adjust PD settings
• Select New Equipment
-Recalculate IEEE 1584
-Decide mitigation methods.
-Implement
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
15
Step 1
Step 1:
Single Line Diagram
PTW
Include details for all:
-Voltages
-Cables (L, CSA, Ez)
-Transformers (kva, Ez, tap)
-Protective Devices (Type,
settings)
-Loads (Motors, type) kw, pf
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
UTIL-0001
Init Voltage 1.050 pu
SC Contribution 3P 400.0 MVA
SC Contribution SLG 100.0 MVA
S
XF2-0001
BUS-0001
1780 Amps 3P
1335 Amps SLG
BUS-0002
1636 Amps 3P
1196 Amps SLG
CBL-0002
BUS-0004
14410 Amps 3P
16985 Amps SLG
PD-0001
Frame/Rating 2500.0 A
InterruptingRating 31.5 kA
XLN-0001
November 2015 Prepared by Alan Mason AME Pty
LTD
16
TSS
@ 914 mm
PPE Category 0
Trail Cable
Fuse 200 A
690v
0.1 Cal/cm^2
@ 457 mm
PPE Category 0
433v Bus
0.1 Cal/cm^2
@ 61 mm
PPE Category 0
MCC CB 415v
L&P CB 415v
CBL-0007
MCC 415v
@ 457 mm
PPE Category 0
CBL-0008 CBL-0011
Controls CB 200v
Controls
@ 457 mm
PPE Category 0
L7 Controls
UTIL-1
L&P 415v
@ 457 mm
PPE Category 0
CBL-4
HV Cab Output
@ 914 mm
PPE Category 0
6.6kv Contactor
Arc Flash Relay B0
AFR B4
AFR B5 BUS-40 @ 914 mm
PPE Category 0
CBL-26
PD-0046
BUS-0042 MCC
0.1 Cal/cm^2
@ 457 mm
PPE Category 0
PD-52
CBL-27
MTRI-1
BUS-0043
0.1 Cal/cm^2
@ 457 mm
PPE Category 0
CBL-0028
PD-53
CBL-29
MTRI-2
BUS-0044
@ 457 mm
PPE Category 0
PD-54
CBL-30
MTRI-3
BUS-45
@ 457 mm
PPE Category 0
PD-55
CBL-31
MTRI-4
BUS-46
@ 457 mm
PPE Category 0
PD-56
CBL-32
MTRI-5
BUS-47
@ 457 mm
PPE Category 0
PD-7
CBL-33
L10
CBL-0036
BUS-0051 Light & Power
0.1 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0060PD-0061PD-0062PD-0063
CBL-0037 CBL-0038 CBL-0039 CBL-0040
L11
BUS-0052
@ 457 mm
PPE Category 0
L12
BUS-0053
@ 457 mm
PPE Category 0
L13
BUS-0054
@ 457 mm
PPE Category 0
L14
BUS-0055
@ 457 mm
PPE Category 0
S
P
XF2-6 TSS
BUS-0056
111.4 Cal/cm^2
@ 914 mm
PPE Category Dangerous!
AFR B7
CBL-0041
BUS-0057
@ 914 mm
PPE Category 0
CBL-0042
CBL-0045
BUS-0061
@ 457 mm
PPE Category 0
CBL-0048
BUS-0064
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
S
P
XF2-7 Main Tx
BUS-0066
@ 914 mm
PPE Category 0
TS
P
XF3-4 Aux Tx
BUS-0067
0.1 Cal/cm^2
@ 457 mm
PPE Category 0
MTRI-0008 MTRI-0009 MTRI-0010 MTRI-0011 MTRI-0012 MTRI-0013 MTRI-0014 MTRI-0015
BUS-0076
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0065
PD-0066
PD-0067 PD-0068
BUS-0078
0.4 Cal/cm^2
@ 457 mm
PPE Category 0
CBL-0050
PD-0069
PD-0070 PD-0071
BUS-0079
0.4 Cal/cm^2
@ 457 mm
PPE Category 0
CBL-0051
PD-0072
PD-0073 PD-0074
BUS-0080
0.4 Cal/cm^2
@ 457 mm
PPE Category 0
CBL-0052
PD-0075
PD-0076 PD-0077
BUS-0081
0.4 Cal/cm^2
@ 457 mm
PPE Category 0
CBL-0053
PD-0078
PD-0079 PD-0080
BUS-0082
0.4 Cal/cm^2
@ 457 mm
PPE Category 0
CBL-0054
CBL-0055
BUS-0083
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
BUS-0084
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0081
BUS-0085
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0082
BUS-0086
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0083
BUS-0087
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0084
BUS-0088
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0085
BUS-0089
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0086
BUS-0090
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0087
BUS-0091
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
CBL-0056 CBL-0057
CBL-0058
CBL-0059
CBL-0060
CBL-0061
CBL-0062
CBL-0063
CBL-0064
CBL-0065
CBL-0066 CBL-0067 CBL-0068 CBL-0069 CBL-0070 CBL-0071 CBL-0072 CBL-0073
PD-0089 QTTM
Fuse 200 Amp
BUS-0095
@ 914 mm
PPE Category 0
BUS-0096 @ 914 mm
PPE Category 0
CBL-0075
CBL-0076
BUS-0098
@ 914 mm
PPE Category 0
CBL-0077
PD-0092
Fuse 200 A0
CBL-0078
Shovel Single Line
Diagram
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
Step 1
November 2015 Prepared by Alan Mason AME Pty
LTD
17
Step 2
Step 2:
Fault Analysis
IEEE 1584
Calculate:
-Bus Fault kA
-Arc Flash Fault kA
-Incident Energy
-Isolation Times
-Arc Flash Boundary
-Arc Flash Category
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
18
TSS
@ 914 mm
PPE Category 0
Trail Cable
Fuse 200 A
690v
0.1 Cal/cm^2
@ 457 mm
PPE Category 0
433v Bus
0.1 Cal/cm^2
@ 61 mm
PPE Category 0
MCC CB 415v
L&P CB 415v
CBL-0007
MCC 415v
@ 457 mm
PPE Category 0
CBL-0008 CBL-0011
Controls CB 200v
Controls
@ 457 mm
PPE Category 0
L7 Controls
UTIL-1
L&P 415v
@ 457 mm
PPE Category 0
CBL-4
HV Cab Output
@ 914 mm
PPE Category 0
6.6kv Contactor
Arc Flash Relay B0
AFR B4
AFR B5 BUS-40 @ 914 mm
PPE Category 0
CBL-26
PD-0046
BUS-0042 MCC
0.1 Cal/cm^2
@ 457 mm
PPE Category 0
PD-52
CBL-27
MTRI-1
BUS-0043
0.1 Cal/cm^2
@ 457 mm
PPE Category 0
CBL-0028
PD-53
CBL-29
MTRI-2
BUS-0044
@ 457 mm
PPE Category 0
PD-54
CBL-30
MTRI-3
BUS-45
@ 457 mm
PPE Category 0
PD-55
CBL-31
MTRI-4
BUS-46
@ 457 mm
PPE Category 0
PD-56
CBL-32
MTRI-5
BUS-47
@ 457 mm
PPE Category 0
PD-7
CBL-33
L10
CBL-0036
BUS-0051 Light & Power
0.1 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0060PD-0061PD-0062PD-0063
CBL-0037 CBL-0038 CBL-0039 CBL-0040
L11
BUS-0052
@ 457 mm
PPE Category 0
L12
BUS-0053
@ 457 mm
PPE Category 0
L13
BUS-0054
@ 457 mm
PPE Category 0
L14
BUS-0055
@ 457 mm
PPE Category 0
S
P
XF2-6 TSS
BUS-0056
111.4 Cal/cm^2
@ 914 mm
PPE Category Dangerous!
AFR B7
CBL-0041
BUS-0057
@ 914 mm
PPE Category 0
CBL-0042
CBL-0045
BUS-0061
@ 457 mm
PPE Category 0
CBL-0048
BUS-0064
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
S
P
XF2-7 Main Tx
BUS-0066
@ 914 mm
PPE Category 0
TS
P
XF3-4 Aux Tx
BUS-0067
0.1 Cal/cm^2
@ 457 mm
PPE Category 0
MTRI-0008 MTRI-0009 MTRI-0010 MTRI-0011 MTRI-0012 MTRI-0013 MTRI-0014 MTRI-0015
BUS-0076
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0065
PD-0066
PD-0067 PD-0068
BUS-0078
0.4 Cal/cm^2
@ 457 mm
PPE Category 0
CBL-0050
PD-0069
PD-0070 PD-0071
BUS-0079
0.4 Cal/cm^2
@ 457 mm
PPE Category 0
CBL-0051
PD-0072
PD-0073 PD-0074
BUS-0080
0.4 Cal/cm^2
@ 457 mm
PPE Category 0
CBL-0052
PD-0075
PD-0076 PD-0077
BUS-0081
0.4 Cal/cm^2
@ 457 mm
PPE Category 0
CBL-0053
PD-0078
PD-0079 PD-0080
BUS-0082
0.4 Cal/cm^2
@ 457 mm
PPE Category 0
CBL-0054
CBL-0055
BUS-0083
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
BUS-0084
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0081
BUS-0085
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0082
BUS-0086
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0083
BUS-0087
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0084
BUS-0088
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0085
BUS-0089
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0086
BUS-0090
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
PD-0087
BUS-0091
0.2 Cal/cm^2
@ 457 mm
PPE Category 0
CBL-0056 CBL-0057
CBL-0058
CBL-0059
CBL-0060
CBL-0061
CBL-0062
CBL-0063
CBL-0064
CBL-0065
CBL-0066 CBL-0067 CBL-0068 CBL-0069 CBL-0070 CBL-0071 CBL-0072 CBL-0073
PD-0089 QTTM
Fuse 200 Amp
BUS-0095
@ 914 mm
PPE Category 0
BUS-0096 @ 914 mm
PPE Category 0
CBL-0075
CBL-0076
BUS-0098
@ 914 mm
PPE Category 0
CBL-0077
PD-0092
Fuse 200 A0
CBL-0078
Shovel PTW SLD
showing
Arc Flash CAT Levels
and
Incident Energy
levels.
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
Step 2
November 2015 Prepared by Alan Mason AME Pty
LTD
19
Step 2: Arc Flash Locations
with E>1.2cal/cm2
LIGHT & POWER
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
20
Step 3
Step 3
Mitigation
-Select BUS’s > CAT 0
-Use Hierarchy of Controls
-Reduce Arc Fault Isolation
times:
• Adjust PD settings
• Select New Equipment
-Recalculate IEEE 1584
-Decide mitigation methods
-Installation
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
21
Step 3: PPE and Arc Flash CAT
related to Incident Energy E
25 to 4040Cotton underwear
+ Fire Retardant
Shirt & Pants +
Multilayer Flash suit
4
8 to 2525Cotton underwear
+ Fire Retardant
Shirt & Pants + Fire
Retardant coverall
3
4 to 88Cotton underwear
+ Fire Retardant
Shirt & Pants
2
1.2 to 44Fire Retardant Shirt
& Pants
1
0 to 1.21.2Cotton underwear0
Incident
Energy E
range
cal/cm2
Min Arc
Rating of
PPE
cal/cm2
General PPE
Clothing
Description
Hazard
Risk
CAT
November 2015 Prepared by Alan Mason AME Pty
LTD
22
Step 3:Protective Devices
with adjustable settings
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
23
Step 3:Speed of
Fault Current Isolation
 Demonstrate change of CAT level with time of Arc
isolation using :
– 1.0 sec Standard CB & Fuse protection
– 0.14 sec Standard CB/Relay protection
– 0.065 sec Standard + Arc Flash Systems
– 0.004 sec Standard + AFS + UFES
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
24
00016.6kv TSS LV OutputTSS
00016.6kv Main Tfr PrimaryHV Cab Output
0001208v Aux Tfr CB Cabinet OutputControls
00016.6kv HV Cabinet InputBUS-40
00016.6kv HV Cabinet ContactorBUS-0096
0111415v Light & Power Cabinet InputBUS-0051 L&P
0011415v Machine House Blower 1BUS-0043
0111415v MCC Cabinet InputBUS-0042 MCC
0012433v Aux Tfr CB Cab MCC SupplyMCC 415v
0012433v Aux Tfr CB Cab L&P SupplyL&P 415v
0012433v Aux Tfr CB Cabinet Supply433v Bus
0013208v Aux Tfr CB SupplyBUS-0067
0124690v Drive Inverter InputBUS-0082
0124690v Drive Inverter InputBUS-0081
0124690v Drive Inverter InputBUS-0080
0124690v Drive Inverter InputBUS-0079
0124690v Drive Inverter InputBUS-0078
0114690v Main Tfr Secondary690v
013Dangerous!690v Drive Inverter DC Bus 1BUS-0084
012Dangerous!690v Drive Inverter DC Bus 2BUS-0076
012Dangerous!690v ABB ACS800 Drive InputBUS-0064
Dangerous!Dangerous!Dangerous!Dangerous!66kv TSS HV SupplyBUS-0056
Scenario3
0.004 Sec
Scenario2
0.065 Sec
Scenario1
0.140 Sec
Base Project
1.0Sec
LocationComponent
Step 3: IEEE 1584 Arc Flash CAT Calculation Results
November 2015 Prepared by Alan Mason AME Pty
LTD
25
Step 3:
INSTALLATION BLOCK
DIAGRAM - UFES.
SHOWING:
Earth Switch:
1 x UFES (3 x PSU’s)
Arc Flash Relays:
1 x QRU100
2 x REA101
2 x REA107
Arc Flash Sensors:
1 x Fibre optic Sensor
12 x AFS Point Sensors
Circuit Breaker:
1 x 12kv GE SecoVac VCB
November 2015 Prepared by Alan Mason AME Pty
LTD
26
Operational Sequence
of events with UFES:
1. Arc Flash occurs.
2. Light Sensor sees Arc Flash.
3. Light signal trips Pick-up AFR.
4. Pick-up AFR sends Trip signal to UFES Trip Relay.
5. UFES Trip Relay sends Trip signals to UFES and VCB.
6. UFES shorts Fault Current to Earth in 0.004sec from flash
(Arc Fault extinguished).
7. VCB trips and opens supply 0.060 - 0.080 sec to remove
bolted 3 ph Short Circuit.
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
27
Installed
Arc Flash Equipment
UFES Trip Relay
+ UFES (3 PSU’s)
+ Light Sensors
High speed
Light Sensor
Arc Flash relays
6.6kv VCB (Non
Withdrawable)
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
November 2015 Prepared by Alan Mason AME Pty
LTD
28
UFES
3 x PSU’s
VCB
ARC
FLASH
RELAYS
6.6kv HV Cabinet (Front) 6.6kv HV Cabinet (Rear)
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
Installed Arc Flash Equipment
November 2015 Prepared by Alan Mason AME Pty
LTD
29
Other Arc Flash Mitigating Items
Stand-off
deflector Panels
Arc Flash Relays for 18
Light Point Sensors
Pressure Relief
Valve with Pilot
Wire Switch
6.6kv Lower Isolator Box
6.6kv Cable Reeler Slipring
Box
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
Installed Arc Flash Equipment
November 2015 Prepared by Alan Mason AME Pty
LTD
30
The BENEFITS of using an AFS + UFES are:
1. Arc Flash Fault Current nearly eliminated.
2. CAT 0 (<1.2cal/cm2) obtained.
3. Safest arc flash protection to personnel.
4. Nil damage to Shovel electrics.
5. Shovel down time minimal to nil.
6. Production delay eliminated.
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
In Conclusion
November 2015 Prepared by Alan Mason AME Pty
LTD
31
QUESTIONS
25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015

More Related Content

Viewers also liked

Exploration in the House 2015: NSW Seamless Geology Project: Progress to date...
Exploration in the House 2015: NSW Seamless Geology Project: Progress to date...Exploration in the House 2015: NSW Seamless Geology Project: Progress to date...
Exploration in the House 2015: NSW Seamless Geology Project: Progress to date...NSW Environment and Planning
 
Bebelusii nu cauta scurtaturi si nu tin cont de gura lumii
Bebelusii nu cauta scurtaturi si nu tin cont de gura lumiiBebelusii nu cauta scurtaturi si nu tin cont de gura lumii
Bebelusii nu cauta scurtaturi si nu tin cont de gura lumiiFani Rarinca
 
Komsas soniyah 2015
Komsas soniyah 2015Komsas soniyah 2015
Komsas soniyah 2015lolita riyah
 
Quest learning institute outbound activities
Quest learning institute outbound activitiesQuest learning institute outbound activities
Quest learning institute outbound activitiesQuest Adventure Group
 
Tony Linnane NSW Trade & Investment Mine Safety - new WHS laws for mining
Tony Linnane NSW Trade & Investment Mine Safety - new WHS laws for miningTony Linnane NSW Trade & Investment Mine Safety - new WHS laws for mining
Tony Linnane NSW Trade & Investment Mine Safety - new WHS laws for miningNSW Environment and Planning
 
Intelligent industrial wireless technology cliff rogers
Intelligent industrial wireless technology   cliff rogersIntelligent industrial wireless technology   cliff rogers
Intelligent industrial wireless technology cliff rogersNSW Environment and Planning
 
Exploration in the House 2015: The Importance of the Junior Sector for minera...
Exploration in the House 2015: The Importance of the Junior Sector for minera...Exploration in the House 2015: The Importance of the Junior Sector for minera...
Exploration in the House 2015: The Importance of the Junior Sector for minera...NSW Environment and Planning
 
Exploration in the House 2015: Geology Survey of NSW Overview and highlights ...
Exploration in the House 2015: Geology Survey of NSW Overview and highlights ...Exploration in the House 2015: Geology Survey of NSW Overview and highlights ...
Exploration in the House 2015: Geology Survey of NSW Overview and highlights ...NSW Environment and Planning
 
Calculations with personal
Calculations with personalCalculations with personal
Calculations with personalssnet2
 

Viewers also liked (20)

Exploration in the House 2015: NSW Seamless Geology Project: Progress to date...
Exploration in the House 2015: NSW Seamless Geology Project: Progress to date...Exploration in the House 2015: NSW Seamless Geology Project: Progress to date...
Exploration in the House 2015: NSW Seamless Geology Project: Progress to date...
 
Bebelusii nu cauta scurtaturi si nu tin cont de gura lumii
Bebelusii nu cauta scurtaturi si nu tin cont de gura lumiiBebelusii nu cauta scurtaturi si nu tin cont de gura lumii
Bebelusii nu cauta scurtaturi si nu tin cont de gura lumii
 
ιός
ιόςιός
ιός
 
Komsas soniyah 2015
Komsas soniyah 2015Komsas soniyah 2015
Komsas soniyah 2015
 
Quest learning institute outbound activities
Quest learning institute outbound activitiesQuest learning institute outbound activities
Quest learning institute outbound activities
 
Tony Linnane NSW Trade & Investment Mine Safety - new WHS laws for mining
Tony Linnane NSW Trade & Investment Mine Safety - new WHS laws for miningTony Linnane NSW Trade & Investment Mine Safety - new WHS laws for mining
Tony Linnane NSW Trade & Investment Mine Safety - new WHS laws for mining
 
GSNSW Activities The Year in Review
GSNSW Activities The Year in ReviewGSNSW Activities The Year in Review
GSNSW Activities The Year in Review
 
Intelligent industrial wireless technology cliff rogers
Intelligent industrial wireless technology   cliff rogersIntelligent industrial wireless technology   cliff rogers
Intelligent industrial wireless technology cliff rogers
 
Exploration in the House 2015: The Importance of the Junior Sector for minera...
Exploration in the House 2015: The Importance of the Junior Sector for minera...Exploration in the House 2015: The Importance of the Junior Sector for minera...
Exploration in the House 2015: The Importance of the Junior Sector for minera...
 
CV_KAhmed
CV_KAhmedCV_KAhmed
CV_KAhmed
 
Dr David Sweeting - Update on arcing hazards
Dr David Sweeting - Update on arcing hazardsDr David Sweeting - Update on arcing hazards
Dr David Sweeting - Update on arcing hazards
 
Rtca proximity detection gavin white
Rtca proximity detection   gavin whiteRtca proximity detection   gavin white
Rtca proximity detection gavin white
 
Mark Parcell - History of mining legislation nsw
Mark Parcell - History of mining legislation nswMark Parcell - History of mining legislation nsw
Mark Parcell - History of mining legislation nsw
 
Exploration in the House 2015: Geology Survey of NSW Overview and highlights ...
Exploration in the House 2015: Geology Survey of NSW Overview and highlights ...Exploration in the House 2015: Geology Survey of NSW Overview and highlights ...
Exploration in the House 2015: Geology Survey of NSW Overview and highlights ...
 
Calculations with personal
Calculations with personalCalculations with personal
Calculations with personal
 
The Centre
The CentreThe Centre
The Centre
 
Perspective on New Zealand Smart Meter rollout
Perspective on New Zealand Smart Meter rolloutPerspective on New Zealand Smart Meter rollout
Perspective on New Zealand Smart Meter rollout
 
Collision awareness systems another defence
Collision awareness systems   another defenceCollision awareness systems   another defence
Collision awareness systems another defence
 
Human factors additional paper Ronny Lardner
Human factors additional paper  Ronny LardnerHuman factors additional paper  Ronny Lardner
Human factors additional paper Ronny Lardner
 
Barry Cutting - Booster fans Angus Place Colliery
Barry Cutting  - Booster fans Angus Place CollieryBarry Cutting  - Booster fans Angus Place Colliery
Barry Cutting - Booster fans Angus Place Colliery
 

Similar to Cat 0 shovel Alan Mason

Moulded Case Circuit Breaker (Mccb) & air circuit breaker (acb)
Moulded Case Circuit Breaker (Mccb) & air circuit breaker (acb)Moulded Case Circuit Breaker (Mccb) & air circuit breaker (acb)
Moulded Case Circuit Breaker (Mccb) & air circuit breaker (acb)Hazem El-Henawy
 
ABB passive & active arc fault protection by David Stonebridge
ABB passive & active arc fault protection by David Stonebridge ABB passive & active arc fault protection by David Stonebridge
ABB passive & active arc fault protection by David Stonebridge Keren Meers
 
ABB switchgear safety hazards passive & active arc fault protection by David ...
ABB switchgear safety hazards passive & active arc fault protection by David ...ABB switchgear safety hazards passive & active arc fault protection by David ...
ABB switchgear safety hazards passive & active arc fault protection by David ...Keren Meers
 
Catalog MCCB & ACB Fuji Electric dòng G-TWIN Mới Nhất 2019
Catalog MCCB & ACB Fuji Electric dòng G-TWIN Mới Nhất 2019Catalog MCCB & ACB Fuji Electric dòng G-TWIN Mới Nhất 2019
Catalog MCCB & ACB Fuji Electric dòng G-TWIN Mới Nhất 2019CTY TNHH HẠO PHƯƠNG
 
Fuji thiet bi dien-cataloguemccbfuji-160413042900
Fuji thiet bi dien-cataloguemccbfuji-160413042900Fuji thiet bi dien-cataloguemccbfuji-160413042900
Fuji thiet bi dien-cataloguemccbfuji-160413042900Dien Ha The
 
Fuji thiet bi dien-catalogue-mccb-fuji
Fuji thiet bi dien-catalogue-mccb-fujiFuji thiet bi dien-catalogue-mccb-fuji
Fuji thiet bi dien-catalogue-mccb-fujiThuan Kieu
 
Fuji thiet bi dien-catalogue-mccb-fuji dienhathe.org
Fuji thiet bi dien-catalogue-mccb-fuji dienhathe.orgFuji thiet bi dien-catalogue-mccb-fuji dienhathe.org
Fuji thiet bi dien-catalogue-mccb-fuji dienhathe.orgDien Ha The
 
Fuji thiet bi dien-cataloguemccbfuji-160413042900
Fuji thiet bi dien-cataloguemccbfuji-160413042900Fuji thiet bi dien-cataloguemccbfuji-160413042900
Fuji thiet bi dien-cataloguemccbfuji-160413042900Thuan Kieu
 
Fuji thiet bi dien-cataloguemccbfuji-160413042900 dienhathe.org
Fuji thiet bi dien-cataloguemccbfuji-160413042900 dienhathe.orgFuji thiet bi dien-cataloguemccbfuji-160413042900 dienhathe.org
Fuji thiet bi dien-cataloguemccbfuji-160413042900 dienhathe.orgDien Ha The
 
ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...
ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...
ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...Thorne & Derrick International
 
UFES_Standard_EN_16-9_2017-0612.pdf
UFES_Standard_EN_16-9_2017-0612.pdfUFES_Standard_EN_16-9_2017-0612.pdf
UFES_Standard_EN_16-9_2017-0612.pdfmahmoudMotamedi1
 
Catalog ELCB Fuji Electric dòng G-TWIN Mới Nhất
Catalog ELCB Fuji Electric dòng G-TWIN Mới NhấtCatalog ELCB Fuji Electric dòng G-TWIN Mới Nhất
Catalog ELCB Fuji Electric dòng G-TWIN Mới NhấtCTY TNHH HẠO PHƯƠNG
 
Inductive shielded superconducting fault current limiter: test results for sc...
Inductive shielded superconducting fault current limiter: test results for sc...Inductive shielded superconducting fault current limiter: test results for sc...
Inductive shielded superconducting fault current limiter: test results for sc...Franco Moriconi
 
Catalogue MCCB Fuji - Beeteco.com
Catalogue MCCB Fuji - Beeteco.comCatalogue MCCB Fuji - Beeteco.com
Catalogue MCCB Fuji - Beeteco.comBeeteco
 
02 - Fundamentals of Power Line Carrier.pdf
02 - Fundamentals of Power Line Carrier.pdf02 - Fundamentals of Power Line Carrier.pdf
02 - Fundamentals of Power Line Carrier.pdfkrishnabhardwaj15
 
Fuji thiet bi dien-elcbfuji-160413044256 dienhathe.org
Fuji thiet bi dien-elcbfuji-160413044256 dienhathe.orgFuji thiet bi dien-elcbfuji-160413044256 dienhathe.org
Fuji thiet bi dien-elcbfuji-160413044256 dienhathe.orgDien Ha The
 
Fuji thiet bi dien-elcbfuji-160413044256
Fuji thiet bi dien-elcbfuji-160413044256Fuji thiet bi dien-elcbfuji-160413044256
Fuji thiet bi dien-elcbfuji-160413044256Thuan Kieu
 
Hay tbptatd - sa2005 safety analyzer
Hay   tbptatd - sa2005 safety analyzerHay   tbptatd - sa2005 safety analyzer
Hay tbptatd - sa2005 safety analyzerPhạm Thanh Tùng
 

Similar to Cat 0 shovel Alan Mason (20)

Moulded Case Circuit Breaker (Mccb) & air circuit breaker (acb)
Moulded Case Circuit Breaker (Mccb) & air circuit breaker (acb)Moulded Case Circuit Breaker (Mccb) & air circuit breaker (acb)
Moulded Case Circuit Breaker (Mccb) & air circuit breaker (acb)
 
ABB passive & active arc fault protection by David Stonebridge
ABB passive & active arc fault protection by David Stonebridge ABB passive & active arc fault protection by David Stonebridge
ABB passive & active arc fault protection by David Stonebridge
 
ABB switchgear safety hazards passive & active arc fault protection by David ...
ABB switchgear safety hazards passive & active arc fault protection by David ...ABB switchgear safety hazards passive & active arc fault protection by David ...
ABB switchgear safety hazards passive & active arc fault protection by David ...
 
ABB 太阳能解决方案_ENG
ABB 太阳能解决方案_ENGABB 太阳能解决方案_ENG
ABB 太阳能解决方案_ENG
 
Catalog MCCB & ACB Fuji Electric dòng G-TWIN Mới Nhất 2019
Catalog MCCB & ACB Fuji Electric dòng G-TWIN Mới Nhất 2019Catalog MCCB & ACB Fuji Electric dòng G-TWIN Mới Nhất 2019
Catalog MCCB & ACB Fuji Electric dòng G-TWIN Mới Nhất 2019
 
Fuji thiet bi dien-cataloguemccbfuji-160413042900
Fuji thiet bi dien-cataloguemccbfuji-160413042900Fuji thiet bi dien-cataloguemccbfuji-160413042900
Fuji thiet bi dien-cataloguemccbfuji-160413042900
 
Fuji thiet bi dien-catalogue-mccb-fuji
Fuji thiet bi dien-catalogue-mccb-fujiFuji thiet bi dien-catalogue-mccb-fuji
Fuji thiet bi dien-catalogue-mccb-fuji
 
Fuji thiet bi dien-catalogue-mccb-fuji dienhathe.org
Fuji thiet bi dien-catalogue-mccb-fuji dienhathe.orgFuji thiet bi dien-catalogue-mccb-fuji dienhathe.org
Fuji thiet bi dien-catalogue-mccb-fuji dienhathe.org
 
Fuji thiet bi dien-cataloguemccbfuji-160413042900
Fuji thiet bi dien-cataloguemccbfuji-160413042900Fuji thiet bi dien-cataloguemccbfuji-160413042900
Fuji thiet bi dien-cataloguemccbfuji-160413042900
 
Fuji thiet bi dien-cataloguemccbfuji-160413042900 dienhathe.org
Fuji thiet bi dien-cataloguemccbfuji-160413042900 dienhathe.orgFuji thiet bi dien-cataloguemccbfuji-160413042900 dienhathe.org
Fuji thiet bi dien-cataloguemccbfuji-160413042900 dienhathe.org
 
ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...
ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...
ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...
 
UFES_Standard_EN_16-9_2017-0612.pdf
UFES_Standard_EN_16-9_2017-0612.pdfUFES_Standard_EN_16-9_2017-0612.pdf
UFES_Standard_EN_16-9_2017-0612.pdf
 
Catalog ELCB Fuji Electric dòng G-TWIN Mới Nhất
Catalog ELCB Fuji Electric dòng G-TWIN Mới NhấtCatalog ELCB Fuji Electric dòng G-TWIN Mới Nhất
Catalog ELCB Fuji Electric dòng G-TWIN Mới Nhất
 
Inductive shielded superconducting fault current limiter: test results for sc...
Inductive shielded superconducting fault current limiter: test results for sc...Inductive shielded superconducting fault current limiter: test results for sc...
Inductive shielded superconducting fault current limiter: test results for sc...
 
Contactores ABB
Contactores ABBContactores ABB
Contactores ABB
 
Catalogue MCCB Fuji - Beeteco.com
Catalogue MCCB Fuji - Beeteco.comCatalogue MCCB Fuji - Beeteco.com
Catalogue MCCB Fuji - Beeteco.com
 
02 - Fundamentals of Power Line Carrier.pdf
02 - Fundamentals of Power Line Carrier.pdf02 - Fundamentals of Power Line Carrier.pdf
02 - Fundamentals of Power Line Carrier.pdf
 
Fuji thiet bi dien-elcbfuji-160413044256 dienhathe.org
Fuji thiet bi dien-elcbfuji-160413044256 dienhathe.orgFuji thiet bi dien-elcbfuji-160413044256 dienhathe.org
Fuji thiet bi dien-elcbfuji-160413044256 dienhathe.org
 
Fuji thiet bi dien-elcbfuji-160413044256
Fuji thiet bi dien-elcbfuji-160413044256Fuji thiet bi dien-elcbfuji-160413044256
Fuji thiet bi dien-elcbfuji-160413044256
 
Hay tbptatd - sa2005 safety analyzer
Hay   tbptatd - sa2005 safety analyzerHay   tbptatd - sa2005 safety analyzer
Hay tbptatd - sa2005 safety analyzer
 

More from NSW Environment and Planning

06. how the regulator communicates with the industry
06. how the regulator communicates with the industry06. how the regulator communicates with the industry
06. how the regulator communicates with the industryNSW Environment and Planning
 
Fires on mobile plant refuelling (Ross Stutchbury)
Fires on mobile plant refuelling (Ross Stutchbury)Fires on mobile plant refuelling (Ross Stutchbury)
Fires on mobile plant refuelling (Ross Stutchbury)NSW Environment and Planning
 
Mobile plant rollovers and collisions (Bill McGlynn)
Mobile plant rollovers and collisions (Bill McGlynn)Mobile plant rollovers and collisions (Bill McGlynn)
Mobile plant rollovers and collisions (Bill McGlynn)NSW Environment and Planning
 
Electrical performance presentation (Craig Harris)
Electrical performance presentation (Craig Harris)Electrical performance presentation (Craig Harris)
Electrical performance presentation (Craig Harris)NSW Environment and Planning
 
Where do I stand for fire protection on mobile and transportable equipment an...
Where do I stand for fire protection on mobile and transportable equipment an...Where do I stand for fire protection on mobile and transportable equipment an...
Where do I stand for fire protection on mobile and transportable equipment an...NSW Environment and Planning
 

More from NSW Environment and Planning (20)

12 Small mines report card 2020
12 Small mines report card 202012 Small mines report card 2020
12 Small mines report card 2020
 
11 occupational hygiene monitoring of dust
11 occupational hygiene monitoring of dust11 occupational hygiene monitoring of dust
11 occupational hygiene monitoring of dust
 
09 learning from disasters
09 learning from disasters09 learning from disasters
09 learning from disasters
 
13 explosives awareness
13 explosives awareness13 explosives awareness
13 explosives awareness
 
10 incident reporting to the regulator 2020
10 incident reporting to the regulator 202010 incident reporting to the regulator 2020
10 incident reporting to the regulator 2020
 
08 dust safety and health surveillance
08 dust safety and health surveillance08 dust safety and health surveillance
08 dust safety and health surveillance
 
07 feedback and consultation
07 feedback and consultation07 feedback and consultation
07 feedback and consultation
 
06. how the regulator communicates with the industry
06. how the regulator communicates with the industry06. how the regulator communicates with the industry
06. how the regulator communicates with the industry
 
05 reviewing your SMS
05 reviewing your SMS05 reviewing your SMS
05 reviewing your SMS
 
04. slinging and lifting equipment
04. slinging and lifting equipment04. slinging and lifting equipment
04. slinging and lifting equipment
 
Control focused inspection tools (Mark Smith)
Control focused inspection tools (Mark Smith)Control focused inspection tools (Mark Smith)
Control focused inspection tools (Mark Smith)
 
Central assessment unit CAU(Steve Bentham)
Central assessment unit CAU(Steve Bentham)Central assessment unit CAU(Steve Bentham)
Central assessment unit CAU(Steve Bentham)
 
Autonomous mining equipment (Owen Barry)
Autonomous mining equipment (Owen Barry)Autonomous mining equipment (Owen Barry)
Autonomous mining equipment (Owen Barry)
 
Fires on mobile plant refuelling (Ross Stutchbury)
Fires on mobile plant refuelling (Ross Stutchbury)Fires on mobile plant refuelling (Ross Stutchbury)
Fires on mobile plant refuelling (Ross Stutchbury)
 
Mobile plant rollovers and collisions (Bill McGlynn)
Mobile plant rollovers and collisions (Bill McGlynn)Mobile plant rollovers and collisions (Bill McGlynn)
Mobile plant rollovers and collisions (Bill McGlynn)
 
Metropolitan colliery gas (Dave Gordon)
Metropolitan colliery gas (Dave Gordon)Metropolitan colliery gas (Dave Gordon)
Metropolitan colliery gas (Dave Gordon)
 
Airborne dust update (Mark Shepherd)
Airborne dust update (Mark Shepherd)Airborne dust update (Mark Shepherd)
Airborne dust update (Mark Shepherd)
 
Emergency planning (Matt U'Brien)
Emergency planning (Matt U'Brien)Emergency planning (Matt U'Brien)
Emergency planning (Matt U'Brien)
 
Electrical performance presentation (Craig Harris)
Electrical performance presentation (Craig Harris)Electrical performance presentation (Craig Harris)
Electrical performance presentation (Craig Harris)
 
Where do I stand for fire protection on mobile and transportable equipment an...
Where do I stand for fire protection on mobile and transportable equipment an...Where do I stand for fire protection on mobile and transportable equipment an...
Where do I stand for fire protection on mobile and transportable equipment an...
 

Recently uploaded

How the Congressional Budget Office Assists Lawmakers
How the Congressional Budget Office Assists LawmakersHow the Congressional Budget Office Assists Lawmakers
How the Congressional Budget Office Assists LawmakersCongressional Budget Office
 
Fair Trash Reduction - West Hartford, CT
Fair Trash Reduction - West Hartford, CTFair Trash Reduction - West Hartford, CT
Fair Trash Reduction - West Hartford, CTaccounts329278
 
(DIVYA) Call Girls Wakad ( 7001035870 ) HI-Fi Pune Escorts Service
(DIVYA) Call Girls Wakad ( 7001035870 ) HI-Fi Pune Escorts Service(DIVYA) Call Girls Wakad ( 7001035870 ) HI-Fi Pune Escorts Service
(DIVYA) Call Girls Wakad ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
CBO’s Recent Appeals for New Research on Health-Related Topics
CBO’s Recent Appeals for New Research on Health-Related TopicsCBO’s Recent Appeals for New Research on Health-Related Topics
CBO’s Recent Appeals for New Research on Health-Related TopicsCongressional Budget Office
 
(ANIKA) Call Girls Wadki ( 7001035870 ) HI-Fi Pune Escorts Service
(ANIKA) Call Girls Wadki ( 7001035870 ) HI-Fi Pune Escorts Service(ANIKA) Call Girls Wadki ( 7001035870 ) HI-Fi Pune Escorts Service
(ANIKA) Call Girls Wadki ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
(PRIYA) Call Girls Rajgurunagar ( 7001035870 ) HI-Fi Pune Escorts Service
(PRIYA) Call Girls Rajgurunagar ( 7001035870 ) HI-Fi Pune Escorts Service(PRIYA) Call Girls Rajgurunagar ( 7001035870 ) HI-Fi Pune Escorts Service
(PRIYA) Call Girls Rajgurunagar ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Cunningham Road Call Girls Bangalore WhatsApp 8250192130 High Profile Service
Cunningham Road Call Girls Bangalore WhatsApp 8250192130 High Profile ServiceCunningham Road Call Girls Bangalore WhatsApp 8250192130 High Profile Service
Cunningham Road Call Girls Bangalore WhatsApp 8250192130 High Profile ServiceHigh Profile Call Girls
 
WIPO magazine issue -1 - 2024 World Intellectual Property organization.
WIPO magazine issue -1 - 2024 World Intellectual Property organization.WIPO magazine issue -1 - 2024 World Intellectual Property organization.
WIPO magazine issue -1 - 2024 World Intellectual Property organization.Christina Parmionova
 
VIP High Profile Call Girls Gorakhpur Aarushi 8250192130 Independent Escort S...
VIP High Profile Call Girls Gorakhpur Aarushi 8250192130 Independent Escort S...VIP High Profile Call Girls Gorakhpur Aarushi 8250192130 Independent Escort S...
VIP High Profile Call Girls Gorakhpur Aarushi 8250192130 Independent Escort S...Suhani Kapoor
 
(NEHA) Bhosari Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(NEHA) Bhosari Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(NEHA) Bhosari Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(NEHA) Bhosari Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
The Most Attractive Pune Call Girls Handewadi Road 8250192130 Will You Miss T...
The Most Attractive Pune Call Girls Handewadi Road 8250192130 Will You Miss T...The Most Attractive Pune Call Girls Handewadi Road 8250192130 Will You Miss T...
The Most Attractive Pune Call Girls Handewadi Road 8250192130 Will You Miss T...ranjana rawat
 
(TARA) Call Girls Chakan ( 7001035870 ) HI-Fi Pune Escorts Service
(TARA) Call Girls Chakan ( 7001035870 ) HI-Fi Pune Escorts Service(TARA) Call Girls Chakan ( 7001035870 ) HI-Fi Pune Escorts Service
(TARA) Call Girls Chakan ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
2024: The FAR, Federal Acquisition Regulations - Part 27
2024: The FAR, Federal Acquisition Regulations - Part 272024: The FAR, Federal Acquisition Regulations - Part 27
2024: The FAR, Federal Acquisition Regulations - Part 27JSchaus & Associates
 
Night 7k to 12k Call Girls Service In Navi Mumbai 👉 BOOK NOW 9833363713 👈 ♀️...
Night 7k to 12k  Call Girls Service In Navi Mumbai 👉 BOOK NOW 9833363713 👈 ♀️...Night 7k to 12k  Call Girls Service In Navi Mumbai 👉 BOOK NOW 9833363713 👈 ♀️...
Night 7k to 12k Call Girls Service In Navi Mumbai 👉 BOOK NOW 9833363713 👈 ♀️...aartirawatdelhi
 
Incident Command System xxxxxxxxxxxxxxxxxxxxxxxxx
Incident Command System xxxxxxxxxxxxxxxxxxxxxxxxxIncident Command System xxxxxxxxxxxxxxxxxxxxxxxxx
Incident Command System xxxxxxxxxxxxxxxxxxxxxxxxxPeter Miles
 
Goa Escorts WhatsApp Number South Goa Call Girl … 8588052666…
Goa Escorts WhatsApp Number South Goa Call Girl … 8588052666…Goa Escorts WhatsApp Number South Goa Call Girl … 8588052666…
Goa Escorts WhatsApp Number South Goa Call Girl … 8588052666…nishakur201
 

Recently uploaded (20)

How the Congressional Budget Office Assists Lawmakers
How the Congressional Budget Office Assists LawmakersHow the Congressional Budget Office Assists Lawmakers
How the Congressional Budget Office Assists Lawmakers
 
Fair Trash Reduction - West Hartford, CT
Fair Trash Reduction - West Hartford, CTFair Trash Reduction - West Hartford, CT
Fair Trash Reduction - West Hartford, CT
 
(DIVYA) Call Girls Wakad ( 7001035870 ) HI-Fi Pune Escorts Service
(DIVYA) Call Girls Wakad ( 7001035870 ) HI-Fi Pune Escorts Service(DIVYA) Call Girls Wakad ( 7001035870 ) HI-Fi Pune Escorts Service
(DIVYA) Call Girls Wakad ( 7001035870 ) HI-Fi Pune Escorts Service
 
Call Girls Service Connaught Place @9999965857 Delhi 🫦 No Advance VVIP 🍎 SER...
Call Girls Service Connaught Place @9999965857 Delhi 🫦 No Advance  VVIP 🍎 SER...Call Girls Service Connaught Place @9999965857 Delhi 🫦 No Advance  VVIP 🍎 SER...
Call Girls Service Connaught Place @9999965857 Delhi 🫦 No Advance VVIP 🍎 SER...
 
CBO’s Recent Appeals for New Research on Health-Related Topics
CBO’s Recent Appeals for New Research on Health-Related TopicsCBO’s Recent Appeals for New Research on Health-Related Topics
CBO’s Recent Appeals for New Research on Health-Related Topics
 
(ANIKA) Call Girls Wadki ( 7001035870 ) HI-Fi Pune Escorts Service
(ANIKA) Call Girls Wadki ( 7001035870 ) HI-Fi Pune Escorts Service(ANIKA) Call Girls Wadki ( 7001035870 ) HI-Fi Pune Escorts Service
(ANIKA) Call Girls Wadki ( 7001035870 ) HI-Fi Pune Escorts Service
 
(PRIYA) Call Girls Rajgurunagar ( 7001035870 ) HI-Fi Pune Escorts Service
(PRIYA) Call Girls Rajgurunagar ( 7001035870 ) HI-Fi Pune Escorts Service(PRIYA) Call Girls Rajgurunagar ( 7001035870 ) HI-Fi Pune Escorts Service
(PRIYA) Call Girls Rajgurunagar ( 7001035870 ) HI-Fi Pune Escorts Service
 
Cunningham Road Call Girls Bangalore WhatsApp 8250192130 High Profile Service
Cunningham Road Call Girls Bangalore WhatsApp 8250192130 High Profile ServiceCunningham Road Call Girls Bangalore WhatsApp 8250192130 High Profile Service
Cunningham Road Call Girls Bangalore WhatsApp 8250192130 High Profile Service
 
WIPO magazine issue -1 - 2024 World Intellectual Property organization.
WIPO magazine issue -1 - 2024 World Intellectual Property organization.WIPO magazine issue -1 - 2024 World Intellectual Property organization.
WIPO magazine issue -1 - 2024 World Intellectual Property organization.
 
VIP High Profile Call Girls Gorakhpur Aarushi 8250192130 Independent Escort S...
VIP High Profile Call Girls Gorakhpur Aarushi 8250192130 Independent Escort S...VIP High Profile Call Girls Gorakhpur Aarushi 8250192130 Independent Escort S...
VIP High Profile Call Girls Gorakhpur Aarushi 8250192130 Independent Escort S...
 
(NEHA) Bhosari Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(NEHA) Bhosari Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(NEHA) Bhosari Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(NEHA) Bhosari Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
The Most Attractive Pune Call Girls Handewadi Road 8250192130 Will You Miss T...
The Most Attractive Pune Call Girls Handewadi Road 8250192130 Will You Miss T...The Most Attractive Pune Call Girls Handewadi Road 8250192130 Will You Miss T...
The Most Attractive Pune Call Girls Handewadi Road 8250192130 Will You Miss T...
 
Call Girls In Rohini ꧁❤ 🔝 9953056974🔝❤꧂ Escort ServiCe
Call Girls In  Rohini ꧁❤ 🔝 9953056974🔝❤꧂ Escort ServiCeCall Girls In  Rohini ꧁❤ 🔝 9953056974🔝❤꧂ Escort ServiCe
Call Girls In Rohini ꧁❤ 🔝 9953056974🔝❤꧂ Escort ServiCe
 
The Federal Budget and Health Care Policy
The Federal Budget and Health Care PolicyThe Federal Budget and Health Care Policy
The Federal Budget and Health Care Policy
 
Rohini Sector 37 Call Girls Delhi 9999965857 @Sabina Saikh No Advance
Rohini Sector 37 Call Girls Delhi 9999965857 @Sabina Saikh No AdvanceRohini Sector 37 Call Girls Delhi 9999965857 @Sabina Saikh No Advance
Rohini Sector 37 Call Girls Delhi 9999965857 @Sabina Saikh No Advance
 
(TARA) Call Girls Chakan ( 7001035870 ) HI-Fi Pune Escorts Service
(TARA) Call Girls Chakan ( 7001035870 ) HI-Fi Pune Escorts Service(TARA) Call Girls Chakan ( 7001035870 ) HI-Fi Pune Escorts Service
(TARA) Call Girls Chakan ( 7001035870 ) HI-Fi Pune Escorts Service
 
2024: The FAR, Federal Acquisition Regulations - Part 27
2024: The FAR, Federal Acquisition Regulations - Part 272024: The FAR, Federal Acquisition Regulations - Part 27
2024: The FAR, Federal Acquisition Regulations - Part 27
 
Night 7k to 12k Call Girls Service In Navi Mumbai 👉 BOOK NOW 9833363713 👈 ♀️...
Night 7k to 12k  Call Girls Service In Navi Mumbai 👉 BOOK NOW 9833363713 👈 ♀️...Night 7k to 12k  Call Girls Service In Navi Mumbai 👉 BOOK NOW 9833363713 👈 ♀️...
Night 7k to 12k Call Girls Service In Navi Mumbai 👉 BOOK NOW 9833363713 👈 ♀️...
 
Incident Command System xxxxxxxxxxxxxxxxxxxxxxxxx
Incident Command System xxxxxxxxxxxxxxxxxxxxxxxxxIncident Command System xxxxxxxxxxxxxxxxxxxxxxxxx
Incident Command System xxxxxxxxxxxxxxxxxxxxxxxxx
 
Goa Escorts WhatsApp Number South Goa Call Girl … 8588052666…
Goa Escorts WhatsApp Number South Goa Call Girl … 8588052666…Goa Escorts WhatsApp Number South Goa Call Girl … 8588052666…
Goa Escorts WhatsApp Number South Goa Call Girl … 8588052666…
 

Cat 0 shovel Alan Mason

  • 1. November 2015 Prepared by Alan Mason AME Pty LTD 1 Arc Flash CAT 0 Electric Mining Shovel 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 2. November 2015 Prepared by Alan Mason AME Pty LTD 2 AIM of PRESENTATION  Is to show how –two Electric Mining Shovels –were modified –to achieve Arc Flash CAT 0. 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 3. November 2015 Prepared by Alan Mason AME Pty LTD 3 CONTENTS 1. CAT 0 Term 2. Consequences 3. What we know? 4. Analysis is a 3 Step Process 5. Mitigation 6. Equipment 7. Benefits 8. Questions 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 4. November 2015 Prepared by Alan Mason AME Pty LTD 4 TERMS Arc Fault:  Is the fault current that travels through air between two conducting phases or phase to earth with an uncontrolled release of energy. Generally due to un- natural causes. Arc Flash:  Is a consequence from an Arc Fault but in this subject is generally understood to also embody all the consequences of an arc fault. CAT 0:  Arc Fault Incident Energy is less than 1.2 cal/cm2 (Heat Energy). 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 5. November 2015 Prepared by Alan Mason AME Pty LTD 5 Arc Fault Consequences 1. Thermal Burns 2. Electrical Shock 3. Molten Metal 4. Projectiles 5. Blast & Pressure waves 6. Intense Light (Arc Flash) 7. Intense Sound 8. Fire 9.Strong Magnetic Fields 10.Plasma 11.Toxic Gasses 12.Vapours 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 6. November 2015 Prepared by Alan Mason AME Pty LTD 6 Arc Flash Consequences Subject to the level of Energy released the consequences to : – a worker will vary from mild burns to permanent injury or death. – equipment may be nil to catastrophic failure: 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 7. November 2015 Prepared by Alan Mason AME Pty LTD 7 Example: Arc Flash Incident on a 6.6kv Fused Feeder compartment within the HV Cabinet of an Electric Mining Shovel. 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 8. November 2015 Prepared by Alan Mason AME Pty LTD 8 What we know: Let Through Energy vs Time 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 9. November 2015 Prepared by Alan Mason AME Pty LTD 9 What we know: Protection Devices vs Time Shovel Standard Fast Protection 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 10. November 2015 Prepared by Alan Mason AME Pty LTD 10 What we know: Arc Fault Current Time Characteristic Shovel Standard Fast Protection 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 11. November 2015 Prepared by Alan Mason AME Pty LTD 11 What we know: Arc Flash Pressure Rise vs &Time Shovel Standard Fast Protection 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 12. November 2015 Prepared by Alan Mason AME Pty LTD 12 What we know: Arc Flash Incident Energy E ~ k * V * Ibf * t …….…..Eq:1 d2  Where: – E = Incident Energy (Cal/cm2)………Heat Energy – V = System Voltage (kV) – t = Arcing Time (seconds) – d = Working distance from Arc (mm) – Ibf = Bolted fault Current (kA) – k = Constant 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 13. November 2015 Prepared by Alan Mason AME Pty LTD 13 Analysis is a 3 Step Process 1. Shovel Single Line Diagram (SLD) 2. Calculate & Analyse 3. Determine CAT 0 measures & install 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 14. November 2015 Prepared by Alan Mason AME Pty LTD 14 Analysis is a 3 Step Process Step 1: Single Line Diagram PTW Step 2: Fault Analysis IEEE 1584 Step 3 Mitigation Include details for all: -Voltages -Cables (L, CSA, Ez) -Transformers (kva, Ez) -Protective Devices (Type, settings) -Loads (Motors, etc) Calculate: -Bus Fault kA -Arc Flash Fault kA -Incident Energy -Isolation Times -Arc Flash Boundary -Arc Flash Category -Select BUS’s > CAT 0 -Use Hierarchy of Controls -Reduce Trip times: • Adjust PD settings • Select New Equipment -Recalculate IEEE 1584 -Decide mitigation methods. -Implement 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 15. November 2015 Prepared by Alan Mason AME Pty LTD 15 Step 1 Step 1: Single Line Diagram PTW Include details for all: -Voltages -Cables (L, CSA, Ez) -Transformers (kva, Ez, tap) -Protective Devices (Type, settings) -Loads (Motors, type) kw, pf 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015 UTIL-0001 Init Voltage 1.050 pu SC Contribution 3P 400.0 MVA SC Contribution SLG 100.0 MVA S XF2-0001 BUS-0001 1780 Amps 3P 1335 Amps SLG BUS-0002 1636 Amps 3P 1196 Amps SLG CBL-0002 BUS-0004 14410 Amps 3P 16985 Amps SLG PD-0001 Frame/Rating 2500.0 A InterruptingRating 31.5 kA XLN-0001
  • 16. November 2015 Prepared by Alan Mason AME Pty LTD 16 TSS @ 914 mm PPE Category 0 Trail Cable Fuse 200 A 690v 0.1 Cal/cm^2 @ 457 mm PPE Category 0 433v Bus 0.1 Cal/cm^2 @ 61 mm PPE Category 0 MCC CB 415v L&P CB 415v CBL-0007 MCC 415v @ 457 mm PPE Category 0 CBL-0008 CBL-0011 Controls CB 200v Controls @ 457 mm PPE Category 0 L7 Controls UTIL-1 L&P 415v @ 457 mm PPE Category 0 CBL-4 HV Cab Output @ 914 mm PPE Category 0 6.6kv Contactor Arc Flash Relay B0 AFR B4 AFR B5 BUS-40 @ 914 mm PPE Category 0 CBL-26 PD-0046 BUS-0042 MCC 0.1 Cal/cm^2 @ 457 mm PPE Category 0 PD-52 CBL-27 MTRI-1 BUS-0043 0.1 Cal/cm^2 @ 457 mm PPE Category 0 CBL-0028 PD-53 CBL-29 MTRI-2 BUS-0044 @ 457 mm PPE Category 0 PD-54 CBL-30 MTRI-3 BUS-45 @ 457 mm PPE Category 0 PD-55 CBL-31 MTRI-4 BUS-46 @ 457 mm PPE Category 0 PD-56 CBL-32 MTRI-5 BUS-47 @ 457 mm PPE Category 0 PD-7 CBL-33 L10 CBL-0036 BUS-0051 Light & Power 0.1 Cal/cm^2 @ 457 mm PPE Category 0 PD-0060PD-0061PD-0062PD-0063 CBL-0037 CBL-0038 CBL-0039 CBL-0040 L11 BUS-0052 @ 457 mm PPE Category 0 L12 BUS-0053 @ 457 mm PPE Category 0 L13 BUS-0054 @ 457 mm PPE Category 0 L14 BUS-0055 @ 457 mm PPE Category 0 S P XF2-6 TSS BUS-0056 111.4 Cal/cm^2 @ 914 mm PPE Category Dangerous! AFR B7 CBL-0041 BUS-0057 @ 914 mm PPE Category 0 CBL-0042 CBL-0045 BUS-0061 @ 457 mm PPE Category 0 CBL-0048 BUS-0064 0.2 Cal/cm^2 @ 457 mm PPE Category 0 S P XF2-7 Main Tx BUS-0066 @ 914 mm PPE Category 0 TS P XF3-4 Aux Tx BUS-0067 0.1 Cal/cm^2 @ 457 mm PPE Category 0 MTRI-0008 MTRI-0009 MTRI-0010 MTRI-0011 MTRI-0012 MTRI-0013 MTRI-0014 MTRI-0015 BUS-0076 0.2 Cal/cm^2 @ 457 mm PPE Category 0 PD-0065 PD-0066 PD-0067 PD-0068 BUS-0078 0.4 Cal/cm^2 @ 457 mm PPE Category 0 CBL-0050 PD-0069 PD-0070 PD-0071 BUS-0079 0.4 Cal/cm^2 @ 457 mm PPE Category 0 CBL-0051 PD-0072 PD-0073 PD-0074 BUS-0080 0.4 Cal/cm^2 @ 457 mm PPE Category 0 CBL-0052 PD-0075 PD-0076 PD-0077 BUS-0081 0.4 Cal/cm^2 @ 457 mm PPE Category 0 CBL-0053 PD-0078 PD-0079 PD-0080 BUS-0082 0.4 Cal/cm^2 @ 457 mm PPE Category 0 CBL-0054 CBL-0055 BUS-0083 0.2 Cal/cm^2 @ 457 mm PPE Category 0 BUS-0084 0.2 Cal/cm^2 @ 457 mm PPE Category 0 PD-0081 BUS-0085 0.2 Cal/cm^2 @ 457 mm PPE Category 0 PD-0082 BUS-0086 0.2 Cal/cm^2 @ 457 mm PPE Category 0 PD-0083 BUS-0087 0.2 Cal/cm^2 @ 457 mm PPE Category 0 PD-0084 BUS-0088 0.2 Cal/cm^2 @ 457 mm PPE Category 0 PD-0085 BUS-0089 0.2 Cal/cm^2 @ 457 mm PPE Category 0 PD-0086 BUS-0090 0.2 Cal/cm^2 @ 457 mm PPE Category 0 PD-0087 BUS-0091 0.2 Cal/cm^2 @ 457 mm PPE Category 0 CBL-0056 CBL-0057 CBL-0058 CBL-0059 CBL-0060 CBL-0061 CBL-0062 CBL-0063 CBL-0064 CBL-0065 CBL-0066 CBL-0067 CBL-0068 CBL-0069 CBL-0070 CBL-0071 CBL-0072 CBL-0073 PD-0089 QTTM Fuse 200 Amp BUS-0095 @ 914 mm PPE Category 0 BUS-0096 @ 914 mm PPE Category 0 CBL-0075 CBL-0076 BUS-0098 @ 914 mm PPE Category 0 CBL-0077 PD-0092 Fuse 200 A0 CBL-0078 Shovel Single Line Diagram 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015 Step 1
  • 17. November 2015 Prepared by Alan Mason AME Pty LTD 17 Step 2 Step 2: Fault Analysis IEEE 1584 Calculate: -Bus Fault kA -Arc Flash Fault kA -Incident Energy -Isolation Times -Arc Flash Boundary -Arc Flash Category 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 18. November 2015 Prepared by Alan Mason AME Pty LTD 18 TSS @ 914 mm PPE Category 0 Trail Cable Fuse 200 A 690v 0.1 Cal/cm^2 @ 457 mm PPE Category 0 433v Bus 0.1 Cal/cm^2 @ 61 mm PPE Category 0 MCC CB 415v L&P CB 415v CBL-0007 MCC 415v @ 457 mm PPE Category 0 CBL-0008 CBL-0011 Controls CB 200v Controls @ 457 mm PPE Category 0 L7 Controls UTIL-1 L&P 415v @ 457 mm PPE Category 0 CBL-4 HV Cab Output @ 914 mm PPE Category 0 6.6kv Contactor Arc Flash Relay B0 AFR B4 AFR B5 BUS-40 @ 914 mm PPE Category 0 CBL-26 PD-0046 BUS-0042 MCC 0.1 Cal/cm^2 @ 457 mm PPE Category 0 PD-52 CBL-27 MTRI-1 BUS-0043 0.1 Cal/cm^2 @ 457 mm PPE Category 0 CBL-0028 PD-53 CBL-29 MTRI-2 BUS-0044 @ 457 mm PPE Category 0 PD-54 CBL-30 MTRI-3 BUS-45 @ 457 mm PPE Category 0 PD-55 CBL-31 MTRI-4 BUS-46 @ 457 mm PPE Category 0 PD-56 CBL-32 MTRI-5 BUS-47 @ 457 mm PPE Category 0 PD-7 CBL-33 L10 CBL-0036 BUS-0051 Light & Power 0.1 Cal/cm^2 @ 457 mm PPE Category 0 PD-0060PD-0061PD-0062PD-0063 CBL-0037 CBL-0038 CBL-0039 CBL-0040 L11 BUS-0052 @ 457 mm PPE Category 0 L12 BUS-0053 @ 457 mm PPE Category 0 L13 BUS-0054 @ 457 mm PPE Category 0 L14 BUS-0055 @ 457 mm PPE Category 0 S P XF2-6 TSS BUS-0056 111.4 Cal/cm^2 @ 914 mm PPE Category Dangerous! AFR B7 CBL-0041 BUS-0057 @ 914 mm PPE Category 0 CBL-0042 CBL-0045 BUS-0061 @ 457 mm PPE Category 0 CBL-0048 BUS-0064 0.2 Cal/cm^2 @ 457 mm PPE Category 0 S P XF2-7 Main Tx BUS-0066 @ 914 mm PPE Category 0 TS P XF3-4 Aux Tx BUS-0067 0.1 Cal/cm^2 @ 457 mm PPE Category 0 MTRI-0008 MTRI-0009 MTRI-0010 MTRI-0011 MTRI-0012 MTRI-0013 MTRI-0014 MTRI-0015 BUS-0076 0.2 Cal/cm^2 @ 457 mm PPE Category 0 PD-0065 PD-0066 PD-0067 PD-0068 BUS-0078 0.4 Cal/cm^2 @ 457 mm PPE Category 0 CBL-0050 PD-0069 PD-0070 PD-0071 BUS-0079 0.4 Cal/cm^2 @ 457 mm PPE Category 0 CBL-0051 PD-0072 PD-0073 PD-0074 BUS-0080 0.4 Cal/cm^2 @ 457 mm PPE Category 0 CBL-0052 PD-0075 PD-0076 PD-0077 BUS-0081 0.4 Cal/cm^2 @ 457 mm PPE Category 0 CBL-0053 PD-0078 PD-0079 PD-0080 BUS-0082 0.4 Cal/cm^2 @ 457 mm PPE Category 0 CBL-0054 CBL-0055 BUS-0083 0.2 Cal/cm^2 @ 457 mm PPE Category 0 BUS-0084 0.2 Cal/cm^2 @ 457 mm PPE Category 0 PD-0081 BUS-0085 0.2 Cal/cm^2 @ 457 mm PPE Category 0 PD-0082 BUS-0086 0.2 Cal/cm^2 @ 457 mm PPE Category 0 PD-0083 BUS-0087 0.2 Cal/cm^2 @ 457 mm PPE Category 0 PD-0084 BUS-0088 0.2 Cal/cm^2 @ 457 mm PPE Category 0 PD-0085 BUS-0089 0.2 Cal/cm^2 @ 457 mm PPE Category 0 PD-0086 BUS-0090 0.2 Cal/cm^2 @ 457 mm PPE Category 0 PD-0087 BUS-0091 0.2 Cal/cm^2 @ 457 mm PPE Category 0 CBL-0056 CBL-0057 CBL-0058 CBL-0059 CBL-0060 CBL-0061 CBL-0062 CBL-0063 CBL-0064 CBL-0065 CBL-0066 CBL-0067 CBL-0068 CBL-0069 CBL-0070 CBL-0071 CBL-0072 CBL-0073 PD-0089 QTTM Fuse 200 Amp BUS-0095 @ 914 mm PPE Category 0 BUS-0096 @ 914 mm PPE Category 0 CBL-0075 CBL-0076 BUS-0098 @ 914 mm PPE Category 0 CBL-0077 PD-0092 Fuse 200 A0 CBL-0078 Shovel PTW SLD showing Arc Flash CAT Levels and Incident Energy levels. 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015 Step 2
  • 19. November 2015 Prepared by Alan Mason AME Pty LTD 19 Step 2: Arc Flash Locations with E>1.2cal/cm2 LIGHT & POWER 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 20. November 2015 Prepared by Alan Mason AME Pty LTD 20 Step 3 Step 3 Mitigation -Select BUS’s > CAT 0 -Use Hierarchy of Controls -Reduce Arc Fault Isolation times: • Adjust PD settings • Select New Equipment -Recalculate IEEE 1584 -Decide mitigation methods -Installation 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 21. November 2015 Prepared by Alan Mason AME Pty LTD 21 Step 3: PPE and Arc Flash CAT related to Incident Energy E 25 to 4040Cotton underwear + Fire Retardant Shirt & Pants + Multilayer Flash suit 4 8 to 2525Cotton underwear + Fire Retardant Shirt & Pants + Fire Retardant coverall 3 4 to 88Cotton underwear + Fire Retardant Shirt & Pants 2 1.2 to 44Fire Retardant Shirt & Pants 1 0 to 1.21.2Cotton underwear0 Incident Energy E range cal/cm2 Min Arc Rating of PPE cal/cm2 General PPE Clothing Description Hazard Risk CAT
  • 22. November 2015 Prepared by Alan Mason AME Pty LTD 22 Step 3:Protective Devices with adjustable settings 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 23. November 2015 Prepared by Alan Mason AME Pty LTD 23 Step 3:Speed of Fault Current Isolation  Demonstrate change of CAT level with time of Arc isolation using : – 1.0 sec Standard CB & Fuse protection – 0.14 sec Standard CB/Relay protection – 0.065 sec Standard + Arc Flash Systems – 0.004 sec Standard + AFS + UFES 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 24. November 2015 Prepared by Alan Mason AME Pty LTD 24 00016.6kv TSS LV OutputTSS 00016.6kv Main Tfr PrimaryHV Cab Output 0001208v Aux Tfr CB Cabinet OutputControls 00016.6kv HV Cabinet InputBUS-40 00016.6kv HV Cabinet ContactorBUS-0096 0111415v Light & Power Cabinet InputBUS-0051 L&P 0011415v Machine House Blower 1BUS-0043 0111415v MCC Cabinet InputBUS-0042 MCC 0012433v Aux Tfr CB Cab MCC SupplyMCC 415v 0012433v Aux Tfr CB Cab L&P SupplyL&P 415v 0012433v Aux Tfr CB Cabinet Supply433v Bus 0013208v Aux Tfr CB SupplyBUS-0067 0124690v Drive Inverter InputBUS-0082 0124690v Drive Inverter InputBUS-0081 0124690v Drive Inverter InputBUS-0080 0124690v Drive Inverter InputBUS-0079 0124690v Drive Inverter InputBUS-0078 0114690v Main Tfr Secondary690v 013Dangerous!690v Drive Inverter DC Bus 1BUS-0084 012Dangerous!690v Drive Inverter DC Bus 2BUS-0076 012Dangerous!690v ABB ACS800 Drive InputBUS-0064 Dangerous!Dangerous!Dangerous!Dangerous!66kv TSS HV SupplyBUS-0056 Scenario3 0.004 Sec Scenario2 0.065 Sec Scenario1 0.140 Sec Base Project 1.0Sec LocationComponent Step 3: IEEE 1584 Arc Flash CAT Calculation Results
  • 25. November 2015 Prepared by Alan Mason AME Pty LTD 25 Step 3: INSTALLATION BLOCK DIAGRAM - UFES. SHOWING: Earth Switch: 1 x UFES (3 x PSU’s) Arc Flash Relays: 1 x QRU100 2 x REA101 2 x REA107 Arc Flash Sensors: 1 x Fibre optic Sensor 12 x AFS Point Sensors Circuit Breaker: 1 x 12kv GE SecoVac VCB
  • 26. November 2015 Prepared by Alan Mason AME Pty LTD 26 Operational Sequence of events with UFES: 1. Arc Flash occurs. 2. Light Sensor sees Arc Flash. 3. Light signal trips Pick-up AFR. 4. Pick-up AFR sends Trip signal to UFES Trip Relay. 5. UFES Trip Relay sends Trip signals to UFES and VCB. 6. UFES shorts Fault Current to Earth in 0.004sec from flash (Arc Fault extinguished). 7. VCB trips and opens supply 0.060 - 0.080 sec to remove bolted 3 ph Short Circuit. 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 27. November 2015 Prepared by Alan Mason AME Pty LTD 27 Installed Arc Flash Equipment UFES Trip Relay + UFES (3 PSU’s) + Light Sensors High speed Light Sensor Arc Flash relays 6.6kv VCB (Non Withdrawable) 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015
  • 28. November 2015 Prepared by Alan Mason AME Pty LTD 28 UFES 3 x PSU’s VCB ARC FLASH RELAYS 6.6kv HV Cabinet (Front) 6.6kv HV Cabinet (Rear) 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015 Installed Arc Flash Equipment
  • 29. November 2015 Prepared by Alan Mason AME Pty LTD 29 Other Arc Flash Mitigating Items Stand-off deflector Panels Arc Flash Relays for 18 Light Point Sensors Pressure Relief Valve with Pilot Wire Switch 6.6kv Lower Isolator Box 6.6kv Cable Reeler Slipring Box 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015 Installed Arc Flash Equipment
  • 30. November 2015 Prepared by Alan Mason AME Pty LTD 30 The BENEFITS of using an AFS + UFES are: 1. Arc Flash Fault Current nearly eliminated. 2. CAT 0 (<1.2cal/cm2) obtained. 3. Safest arc flash protection to personnel. 4. Nil damage to Shovel electrics. 5. Shovel down time minimal to nil. 6. Production delay eliminated. 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015 In Conclusion
  • 31. November 2015 Prepared by Alan Mason AME Pty LTD 31 QUESTIONS 25th Electrical Engineering Safety Seminar – Alan Mason – AME Pty Ltd – November 2015