International Journal of Modern Engineering Research (IJMER)
                     www.ijmer.com          Vol.3, Issue.1, Jan-Feb. 2013 pp-250-253      ISSN: 2249-6645

                     Use of Hydrocarbons and Other Blends as Refrigerant

                             Mohd. Aasim Nazeer Ahmad Quraishi, 1 U. S.Wankhede2
            1
                M. Tech. IV Semester, Heat Power Engineering, G. H. Raisoni College of Engineering, Nagpur-440016,
            2
                Professor, Mechanical Engineering Department, G. H. Raisoni College of Engineering, Nagpur-440016.

Abstract: This paper presents a study of different environmental friendly refrigerants of either hydrocarbon or Hydro fluoro
carbons (HFC) class. Hydrocarbons (HCs) have zero ODP and very low GWP whereas HFCs have zero ODP but a quite
higher GWP. Almost in all the cases, when R-134a was replaced with HCs the COP of the system was improved, ON time
ratio and energy consumption was reduced. Due to a higher value of latent heat of HCs, the amount of refrigerant charge
was also reduced as compared with HFC-134a. When hydro chloro fluoro carbons (HCFCs) were replaced with HFCs the
system delivered a poor performance with increased energy consumption. When nano particles were added to the
refrigerant, system delivered better performance with reduced energy consumption than that of pure refrigerant.

Keywords: TEWI, ON time ratio, Pull down time.

                                                       I. Introduction
         The most commonly used refrigerants in the late 1800s and in the early 1900s were natural refrigerants such as
ammonia, carbon dioxide, sulphur dioxide and methyl chloride. All these refrigerants were found to be toxic or hazardous. In
1928, a safer class of alternative refrigerants became available with the invention of chlorofluorocarbons (CFCs) and hydro
chloro fluorocarbons (HCFCs). CFCs and HCFCs have many suitable properties such as stability, non–toxicity, non–
flammable, good material compatibility and good thermodynamic properties, which led to their common wide spread use by
both consumers and industries around the globe, especially as refrigerants in air–conditioning and refrigeration systems.
         Results from many researches show that ozone layer is being depleted due to the presence of chlorine in the
stratosphere. The general consensus for the cause of this is that CFCs and HCFCs are large class of chlorine containing
chemicals, which migrate to the stratosphere where they react with ozone. Later, chlorine atoms continue to convert more
ozone to oxygen. The discovery of the depletion of the earth’s ozone layer, which shields the earth’s surface from UV
radiation, has resulted in a series of international treaties demanding a gradual phase out of halogenated fluids. The CFCs
have been banned in developed countries since 1996, and in 2030, producing and using of CFCs will be prohibited
completely in the entire world. Also, the partially halogenated HCFCs are bound to be prohibited in the near future.
         The researches are going on to find out some alternate refrigerants which does not harm to the environment and the
protective ozone layer. Research has shown that hydrocarbons are good alternative to existing refrigerants.

                                          II. Refrigerants under Considerations
          Hydrocarbons, propane (R–290) and isobutane (R–600a) were among the first refrigerants, but due to their
flammability and safety purposes, their use was abandoned and the direction of researches was shifted towards a safer and
inert class of refrigerants. Thus the use of HCs as a refrigerant is not a new technology. Since 15 years, hydrocarbon and
their blends are again being used at commercial scale [1].
          Isobutane (R–600a) is the most frequently used hydrocarbon refrigerant. In Europe it is the most dominating
refrigerant in domestic refrigerators. In 2004, the use of isobutane and its blend was 33% in domestic refrigerators and
freezers at global level. Propane (R–290) and propene (R–1270) are widely being used in heat pumps, air conditioners and
commercial refrigeration systems. Butane (R–600) is also under consideration but it has not been used commercially.
Pentane and pentene also have the potential to be used as refrigerant and they are to be considered as the replacement to R–
11 in centrifugal systems [2].

                                        PROPERTIES OF REFRIGERANTS AT 40OC
                                            M         Tbp     Ttr    Tcr    hfg                    l        v
     Ref.              No.       Formula
                                            (kg/kmol) (OC)    (OC)   (OC)   (kJ/kg)                (kg/m3)   (kg/m3)
                                 CH–(CH3)                     –
     Isobutane         R600a                58.12     –11.67         134.67 311.4                  530.0     13.667
                                 3                            159.59
                                 CH3–                         –
     Propane           R290                 44.096    –42.09         96.675 306.51                 467.07    30.202
                                 CH2–CH3                      187.67
                                 CH2=CH–
     Propene           R1270                42.08     –47.69  –185.2 92.42  303.14                 476.66    35.708
                                 CH3
     R134a             R134a     CF3–CH2F 102.03      –26.074 –103.3 101.06 163.02                 1146.7    50.085
                                                              –
     R22               R22       CHClF2     86.468    –40.81         96.145 166.6                  1128.5    66.193
                                                              157.42
                                                              –
     Ammonia           R717      NH3        17.03     –33.327        132.25 1099.31                579.44    12.034
                                                              77.655


                                                            www.ijmer.com                                        250 | Page
International Journal of Modern Engineering Research (IJMER)
                www.ijmer.com          Vol.3, Issue.1, Jan-Feb. 2013 pp-250-253      ISSN: 2249-6645

Ref.              Refrigerant name                    no.               Refrigerant number
Formula           Chemical formula                    M                 Molecular weight
Tbp               Normal boiling point                Ttr               Triple point
Tcr               Critical temperature                hfg               Latent heat of vaporization
 l               Liquid density                       v               Vapor density

                                                 III. Literature Survey
a) Replacement of R-22 with HFCs
          A trial was performed by Rocca and Panno [3] to replace R22 with new HFC refrigerants and the performance was
compared with R–22. The plant working efficiency was first estimated with R–22 and then with three new HFC refrigerants,
R–417a, R–422a and R–422d. The experimental results showed that R–22 has the least energy consumption among all the
refrigerants under trial. Results also reveal that the three HFC refrigerants can replace R–22 without any change in lubricant
or without any modification in the system and the accessories. These refrigerants also provide the safe and reliable working
conditions. The results also verified that despite these advantages, the performance of the new tested HFCs was not as
efficient as with R–22.
          Experimentation was made to replace R–22 with a new refrigerant R–422d by Aprea et al. [4]. The experiment was
carried out under three different operating conditions. The experimental results showed that COP of the system with R–422d
was 20% lower than that of using R–22, the reason behind is high vapor density that also leads to lower cooling capacity and
increased energy consumption. The discharge pressure was 15% higher than that of R–22 but it was under design limit. The
discharge temperature was 20OC lower which offers a longer compressor life. The improvement in heat exchange by
condenser in order to improve the performance was carried out by using a fan. Increasing the fan speed only by 20%
improved COP in the range of 14.5–23.5%.
          Llopis et al. [5] replaced R–22 by two refrigerants HFC–422a and HFC–417b in medium and low evaporating
temperatures. The test was conducted in a two stage refrigerating plant equipped with subcooling. The evaporator and
condenser temperature range were –31OC to 17OC and 30OC to 48OC respectively. The experimental results showed that with
the use of new refrigerants, the refrigerant mass flow rate need to be incremented. The new refrigerants also lead to lower
specific refrigerating effect that tends to reduced cooling capacity. This reduction in the plant capacity was much more than
expected from the theoretical analysis.

b) Replacement of R-134a with other HFCs
          Bolaji [6] carried out a trial on domestic refrigerator designed to work with R–134a and replaced it by R–152a and
R–32 which have zero ODP and low GWP. The performance with the new refrigerant was evaluated and compared with R–
134a. The result showed that the average COP obtained with R–152a was 4.7% higher while average COP with R–32 was
8.5% lower as compared to R–134a. The energy consumption by the system was also reduced. The compressor consumed
4.0% and 3.2% lesser energy with R–152a as compared to the energy consumption with R–134a and R–32 respectively. The
design temperature and pull down time using R–152a and R–134a were achieved earlier than using R–32. The discharge
pressure of R–152a was about 0.8% less than that of R–134a while the discharge pressure using R–32 was the highest with
average value of 8.1% and 7.2% higher than those of R–134a and R–152a respectively. In general, the system performed
better than the other two refrigerants this shows that R–152a can be used to replace R–134a in domestic refrigerators.
          A trial was made by Khorshid et al. [7] on domestic refrigerator to replace R–134a by two different blends one as
R–134a (6.61%), R–32 (5.64%) and R–152a (87.75%) and the other as R–32 (15.34%), R–600a (8.79%) and R–152a
(75.87%). The results of the test show that COP was improved by 11.93% and 2.07% by using the former and latter
respectively as compared with R–134a. The new refrigerant blends have zero ODP and low GWP of the order of 242 and
200 respectively.
                                         IV. Replacement of R-134a with HCs
         Jwo et al. [8] used a blend of R–290 and R–600a instead of R–134a. The experiment was performed on a 440 liters
domestic refrigerator. During test refrigerant R–134a was replaced with varied mass of hydrocarbon blends. The results
show that refrigerating effect was improved by using hydrocarbon blends. The refrigerator which was designed to work with
150 gm of R–134a gave best result with 90 gm of hydrocarbon refrigerant that implies a reduction of 40% in refrigerant
charge. The design temperature was obtained quicker when the mixture of R–290 and R–600a was used that reduced the
individual working time, hence the total working time per month was lesser than by using R–134a. On average, the new
refrigerant mixture offers a better refrigerating behavior and reduces the energy consumption by 4.4%.
         Rasti et al. [9] substituted R–134a with R–436a (mixture of R–290 and R–600a with a mass ratio of 56/44) in a 238
liter domestic refrigerator without any modification in the system. The compressor was charged with different amount of R–
436a. The various results of the experiment showed that the refrigerant R–436a has better performance compared to R–134a
considering various parameters. The ON time ratio was reduced by 13% when R–436a was used. The energy consumption
per day was reduced by 5.3%. The refrigerant charge required in case of R–134a was 105g and the optimum amount of
refrigerant for R–436a was 55g which implies a saving of 48% in refrigerant charge. The evaporator inlet temperature was
reduced by 3.5oC. The energy efficiency index was raised from E to D. The results also showed that Total Equivalent
Warming Impact (TEWI) of R–436a is 11.8% lesser than R–134a. Thus R–436a appears to be a good replacement for R–
134a.

                                                            www.ijmer.com                                          251 | Page
International Journal of Modern Engineering Research (IJMER)
                   www.ijmer.com          Vol.3, Issue.1, Jan-Feb. 2013 pp-250-253      ISSN: 2249-6645

        Sattar et al. [10] used a domestic refrigerator to conduct trial which was designed to work with R–134a. The trial
was conducted to check the possibility of using hydrocarbons as refrigerants. Pure butane, isobutane and mixture of butane,
isobutane and propane were used as alternate refrigerants. The performance of the system was compared with R–134a. The
compressor consumed 3% and 2% lesser energy when iso butane and butane were used at 28 oC ambient condition. The
amount of refrigerant charge with R–134a was 140 gm and it was reduced to 70 gm with the pure hydrocarbon and its blends
which exhibits a saving of 50% in refrigerant charge. The trials were performed without any alteration in the system that
shows the possibility of using hydrocarbons and their blends without any modification.

                              V. Replacement of Pure Refrigerant with Nano Refrigerant
          Shengshan Bi et al. [11] made use of TiO2–R600a nano refrigerant in a domestic refrigerator without any system
modification. The experimentation was performed using TiO2–R600a with 0.1 g/lit and 0.5 g/lit of TiO2 nano particles
concentrations. The performance was compared with pure R-600a. The design temperatures were obtained at a quicker rate
with TiO2–R600a nano refrigerant. The energy consumptions were reduced by 5.94% and 9.60% with the concentrations as
0.1 g/lit and 0.5 g/lit of TiO2 nano particles respectively. All the results obtained exhibited that TiO2–R600a nano refrigerant
worked safely and normally in the refrigerator with better performance than pure R–600a system. Thus TiO2–R600a nano
refrigerant may be used in domestic refrigerator with better performance and lower energy consumption without any
alteration of the system.
          Saidur et al. [12] conducted experiment with HFC–134a in domestic refrigerator with TiO2 nano particles. The
results showed that this nano refrigerant gave better performance. The energy consumption of HFC–134a refrigerant using
mineral oil and nano particles mixture as lubricant was lesser than with pure HFC–134a and it saved 26.1% energy with
0.1% mass fraction TiO2 nano particles compared to the HFC–134a. 60% HFC–134a with mineral oil and 0.1% wt Al 2O3
nano particles gave optimal performance. The power consumption was reduced by 2.4% and the COP was improved by
4.4%. It has been identified that fundamental properties of nano fluids change drastically and depend upon the concentration
of suspension of the nano particles in the base fluid.

                                                         VI. Conclusions
         As per the Kyoto and Montreal protocols, the harmful refrigerants are to be phased out and are to be replaced with
alternate environmental friendly refrigerants. The objective of this paper is to evaluate different environmental friendly
refrigerant. On the basis of collecting information, the following conclusions may be drawn.
         HFCs can replace R-22 without any modification in the system. Despite having the advantage of zero ODP, the
system delivers the poor performance with increased energy consumption as compared with R-22. Hydrocarbons and their
various blends may replace R-134a without any system modifications. COP of the system is improved with reduced energy
consumption. ON time ratio and pull down time are also reduced. The system requires to be charged with 40% to 50% lesser
amount of refrigerant due to a quite higher value of latent heat of hydrocarbons.
         When nano particles are added to the refrigerants, thermo physical properties change drastically and depend on the
concentration of the nano particles. Nano refrigerant can be used in the refrigeration system without any modifications. The
system delivers better performance than with pure refrigerant; the energy consumption is also reduced. However optimum
blend composition for maximum performance of the system is not much studied. Research work for deciding the
concentration of blends has to be undertaken to have better performance of the system.

                                                              References
[1]     Jose M. Corberan, Jacobo Segurado, Daniel Colbourne, Jose Gonzalvez, Review of standards for the use of hydrocarbon refrigerants
        in A/C, heat pump and refrigeration equipment, International Journal of Refrigeration 31 (2008) 748–756.
[2]     Bjorn Palm, Hydrocarbons as refrigerants in small heat pump and refrigeration systems – A review, International Journal of
        Refrigeration 31 (2008) 552–563.
[3]     Vincenzo La Rocca, Giuseppe Panno, Experimental performance evaluation of a vapour compression refrigerating plant when
        replacing R22 with alternative refrigerants Applied Energy 88 (2011) 2809–2815.
[4]     Ciro Aprea, Angelo Maiorino, Rita Mastrullo, Change in energy performance as a result of a R–422d retrofit: An experimental
        analysis for a vapor compression refrigeration plant for a walk in cooler, Applied Energy 88, (2011) 4742–4748.
[5]     R. Llopis, R. Cabello, D. Sánchez, E. Torella, J. Patino, J. G. Sánchez, Experimental evaluation of HCFC–22 replacement by the
        drop-in fluids HFC-422a and HFC-417b for low temperature refrigeration applications, Applied Thermal Engineering 31 (2011)
        1323–1331.
[6]     B. O. Bolaji, Experimental study of R152a and R32 to replace R134a in a domestic refrigerator, Energy 35 (2010) 3793–3798.
[7]     E. Khorshid, B. Alshiraan, A. Alsairafi, A. Alzemi, A. Allahddad, Performance investigation on new refrigerant mixture (2011).
[8]     Ching Song Jwo, Chen–Ching Ting, Wei–Ru Wang, Efficiency analysis of home refrigerators by replacing hydrocarbon
        refrigerants, Measurement 42 (2009) 697–701.
[9]     M. Rasti M.S. Hatamipour, S.F. Aghmiri, M. Tavakoli, Enhancement of domestic refrigerator’s energy efficiency index using a
        hydrocarbon mixture refrigerant, Measurement 45 (2012) 1807–1813.
[10]    M. A. Sattar, R. Saidur, H. H. Masjuki, Performance investigation of domestic refrigerator using pure hydrocarbons and blends of
        hydrocarbons as refrigerants, World Academy of Science, Engineering and Technology 29 (2007) 223–228.
[11]   Shengshan Bi, Kai Guo, Zhigang Liu, Jiangtao Wu, Performance of a domestic refrigerator using TiO2–R600a nano–refrigerant as
        working fluid, Energy Conversion and Management 52 (2011) 733–737.
[12]    R. Saidur, S.N. Kazi, M.S. Hossain, M.M. Rahman, H.A. Mohammed, A review on the performance of nano particles suspended
        with refrigerants and lubricating oils in refrigeration systems, Renewable and Sustainable Energy Reviews 15 (2011) 310–323.


                                                                www.ijmer.com                                               252 | Page

More Related Content

What's hot

Combustion engineering summer 2019
Combustion engineering summer 2019Combustion engineering summer 2019
Combustion engineering summer 2019Yuri Melliza
 
Alternative refrigerants
Alternative  refrigerantsAlternative  refrigerants
Alternative refrigerantsLatif Elahi
 
Combustion & Flue Gas Analysis
Combustion & Flue Gas AnalysisCombustion & Flue Gas Analysis
Combustion & Flue Gas AnalysisAmit Makwana
 
Important Conversion Factors in Petroleum Technology
Important Conversion Factors in Petroleum Technology Important Conversion Factors in Petroleum Technology
Important Conversion Factors in Petroleum Technology Muhammed Fuad Al-Barznji
 
3 Things You Should Know About the Changing Refrigeration Climate
3 Things You Should Know About the Changing Refrigeration Climate3 Things You Should Know About the Changing Refrigeration Climate
3 Things You Should Know About the Changing Refrigeration ClimateAllison Banko
 
Alternative to HCFC in air conditioning equipment as split
Alternative to HCFC in air conditioning equipment as split Alternative to HCFC in air conditioning equipment as split
Alternative to HCFC in air conditioning equipment as split UNEP OzonAction
 
007 fuels and combustion
007 fuels and combustion007 fuels and combustion
007 fuels and combustionphysics101
 
Combustion tutorial
Combustion tutorialCombustion tutorial
Combustion tutorialKumar
 
Treinamento da tecnologia invert
Treinamento da tecnologia invertTreinamento da tecnologia invert
Treinamento da tecnologia invertAgassis Rodrigues
 
SYNGAS PRODUCTION BY DRY REFORMING OF METHANE OVER CO-PRECIPITATED CATALYSTS
SYNGAS PRODUCTION BY DRY REFORMING OF METHANE OVER CO-PRECIPITATED CATALYSTSSYNGAS PRODUCTION BY DRY REFORMING OF METHANE OVER CO-PRECIPITATED CATALYSTS
SYNGAS PRODUCTION BY DRY REFORMING OF METHANE OVER CO-PRECIPITATED CATALYSTSIAEME Publication
 
PRESENTATION ON PLANT DESIGN FOR MANUFACTURING OF HYDROGEN
PRESENTATION ON PLANT DESIGN FOR MANUFACTURING OF HYDROGENPRESENTATION ON PLANT DESIGN FOR MANUFACTURING OF HYDROGEN
PRESENTATION ON PLANT DESIGN FOR MANUFACTURING OF HYDROGENPriyam Jyoti Borah
 
Catalyst Screening- Single Process Furfural Decarbonylation and Hydrogenation
Catalyst Screening- Single Process Furfural Decarbonylation and HydrogenationCatalyst Screening- Single Process Furfural Decarbonylation and Hydrogenation
Catalyst Screening- Single Process Furfural Decarbonylation and HydrogenationTrent Simonetti
 
Thermo catalytic decomposition of methane over Pd/AC and Pd/CB catalysts for ...
Thermo catalytic decomposition of methane over Pd/AC and Pd/CB catalysts for ...Thermo catalytic decomposition of methane over Pd/AC and Pd/CB catalysts for ...
Thermo catalytic decomposition of methane over Pd/AC and Pd/CB catalysts for ...IJERA Editor
 
008 gaseous fuels
008 gaseous fuels008 gaseous fuels
008 gaseous fuelsphysics101
 
MET 401 Chapter 3 fuels_and_combustion
MET 401 Chapter 3 fuels_and_combustionMET 401 Chapter 3 fuels_and_combustion
MET 401 Chapter 3 fuels_and_combustionIbrahim AboKhalil
 
Alternative refrigerants
Alternative refrigerantsAlternative refrigerants
Alternative refrigerantspranav teli
 

What's hot (19)

Combustion engineering summer 2019
Combustion engineering summer 2019Combustion engineering summer 2019
Combustion engineering summer 2019
 
Orsat apparatus
Orsat apparatusOrsat apparatus
Orsat apparatus
 
Refrigerant
RefrigerantRefrigerant
Refrigerant
 
Alternative refrigerants
Alternative  refrigerantsAlternative  refrigerants
Alternative refrigerants
 
Combustion & Flue Gas Analysis
Combustion & Flue Gas AnalysisCombustion & Flue Gas Analysis
Combustion & Flue Gas Analysis
 
RESEARCH PAPER
RESEARCH PAPERRESEARCH PAPER
RESEARCH PAPER
 
Important Conversion Factors in Petroleum Technology
Important Conversion Factors in Petroleum Technology Important Conversion Factors in Petroleum Technology
Important Conversion Factors in Petroleum Technology
 
3 Things You Should Know About the Changing Refrigeration Climate
3 Things You Should Know About the Changing Refrigeration Climate3 Things You Should Know About the Changing Refrigeration Climate
3 Things You Should Know About the Changing Refrigeration Climate
 
Alternative to HCFC in air conditioning equipment as split
Alternative to HCFC in air conditioning equipment as split Alternative to HCFC in air conditioning equipment as split
Alternative to HCFC in air conditioning equipment as split
 
007 fuels and combustion
007 fuels and combustion007 fuels and combustion
007 fuels and combustion
 
Combustion tutorial
Combustion tutorialCombustion tutorial
Combustion tutorial
 
Treinamento da tecnologia invert
Treinamento da tecnologia invertTreinamento da tecnologia invert
Treinamento da tecnologia invert
 
SYNGAS PRODUCTION BY DRY REFORMING OF METHANE OVER CO-PRECIPITATED CATALYSTS
SYNGAS PRODUCTION BY DRY REFORMING OF METHANE OVER CO-PRECIPITATED CATALYSTSSYNGAS PRODUCTION BY DRY REFORMING OF METHANE OVER CO-PRECIPITATED CATALYSTS
SYNGAS PRODUCTION BY DRY REFORMING OF METHANE OVER CO-PRECIPITATED CATALYSTS
 
PRESENTATION ON PLANT DESIGN FOR MANUFACTURING OF HYDROGEN
PRESENTATION ON PLANT DESIGN FOR MANUFACTURING OF HYDROGENPRESENTATION ON PLANT DESIGN FOR MANUFACTURING OF HYDROGEN
PRESENTATION ON PLANT DESIGN FOR MANUFACTURING OF HYDROGEN
 
Catalyst Screening- Single Process Furfural Decarbonylation and Hydrogenation
Catalyst Screening- Single Process Furfural Decarbonylation and HydrogenationCatalyst Screening- Single Process Furfural Decarbonylation and Hydrogenation
Catalyst Screening- Single Process Furfural Decarbonylation and Hydrogenation
 
Thermo catalytic decomposition of methane over Pd/AC and Pd/CB catalysts for ...
Thermo catalytic decomposition of methane over Pd/AC and Pd/CB catalysts for ...Thermo catalytic decomposition of methane over Pd/AC and Pd/CB catalysts for ...
Thermo catalytic decomposition of methane over Pd/AC and Pd/CB catalysts for ...
 
008 gaseous fuels
008 gaseous fuels008 gaseous fuels
008 gaseous fuels
 
MET 401 Chapter 3 fuels_and_combustion
MET 401 Chapter 3 fuels_and_combustionMET 401 Chapter 3 fuels_and_combustion
MET 401 Chapter 3 fuels_and_combustion
 
Alternative refrigerants
Alternative refrigerantsAlternative refrigerants
Alternative refrigerants
 

Viewers also liked

Cd31336341
Cd31336341Cd31336341
Cd31336341IJMER
 
Study of Flexible Lift Mechanism for Press Shop
Study of Flexible Lift Mechanism for Press ShopStudy of Flexible Lift Mechanism for Press Shop
Study of Flexible Lift Mechanism for Press ShopIJMER
 
A New Bi-level Program Based on Unblocked Reliability for a Continuous Road N...
A New Bi-level Program Based on Unblocked Reliability for a Continuous Road N...A New Bi-level Program Based on Unblocked Reliability for a Continuous Road N...
A New Bi-level Program Based on Unblocked Reliability for a Continuous Road N...IJMER
 
A Study of Wind Turbine Blade Power Enhancement Using Aerodynamic Properties
A Study of Wind Turbine Blade Power Enhancement Using  Aerodynamic Properties A Study of Wind Turbine Blade Power Enhancement Using  Aerodynamic Properties
A Study of Wind Turbine Blade Power Enhancement Using Aerodynamic Properties IJMER
 
Compensation for Inverter Nonlinearity Using Trapezoidal Voltage
Compensation for Inverter Nonlinearity Using Trapezoidal  VoltageCompensation for Inverter Nonlinearity Using Trapezoidal  Voltage
Compensation for Inverter Nonlinearity Using Trapezoidal VoltageIJMER
 
An Investigative Review on Thermal Characterization of Hybrid Metal Matrix C...
An Investigative Review on Thermal Characterization of Hybrid  Metal Matrix C...An Investigative Review on Thermal Characterization of Hybrid  Metal Matrix C...
An Investigative Review on Thermal Characterization of Hybrid Metal Matrix C...IJMER
 
Experimental Investigation of Performance and Emission Characteristics of Bi...
Experimental Investigation of Performance and Emission  Characteristics of Bi...Experimental Investigation of Performance and Emission  Characteristics of Bi...
Experimental Investigation of Performance and Emission Characteristics of Bi...IJMER
 
Cn31386390
Cn31386390Cn31386390
Cn31386390IJMER
 
An Enhanced Security System for Web Authentication
An Enhanced Security System for Web Authentication An Enhanced Security System for Web Authentication
An Enhanced Security System for Web Authentication IJMER
 
A Bayesian Probit Online Model Framework for Auction Fraud Detection
A Bayesian Probit Online Model Framework for Auction Fraud DetectionA Bayesian Probit Online Model Framework for Auction Fraud Detection
A Bayesian Probit Online Model Framework for Auction Fraud DetectionIJMER
 
A Note on a Three Variables Analogue of Bessel Polynomials
A Note on a Three Variables Analogue of Bessel PolynomialsA Note on a Three Variables Analogue of Bessel Polynomials
A Note on a Three Variables Analogue of Bessel PolynomialsIJMER
 
Turnstile S-Shaped Dipole and Swastika Wire Antennas for VHF and UHF Applica...
Turnstile S-Shaped Dipole and Swastika Wire Antennas for VHF  and UHF Applica...Turnstile S-Shaped Dipole and Swastika Wire Antennas for VHF  and UHF Applica...
Turnstile S-Shaped Dipole and Swastika Wire Antennas for VHF and UHF Applica...IJMER
 
Implementation of Six Sigma Using DMAIC Methodology in Small Scale Industries...
Implementation of Six Sigma Using DMAIC Methodology in Small Scale Industries...Implementation of Six Sigma Using DMAIC Methodology in Small Scale Industries...
Implementation of Six Sigma Using DMAIC Methodology in Small Scale Industries...IJMER
 
A Novel Key Management Paradigm for Broadcasting to Remote Cooperative Groups
A Novel Key Management Paradigm for Broadcasting to Remote  Cooperative GroupsA Novel Key Management Paradigm for Broadcasting to Remote  Cooperative Groups
A Novel Key Management Paradigm for Broadcasting to Remote Cooperative GroupsIJMER
 
Advanced Micro-Grids
Advanced Micro-Grids Advanced Micro-Grids
Advanced Micro-Grids IJMER
 
Dr3211721175
Dr3211721175Dr3211721175
Dr3211721175IJMER
 
Experimental Method to Analyse Limit Load in Pressure Vessel
Experimental Method to Analyse Limit Load in Pressure VesselExperimental Method to Analyse Limit Load in Pressure Vessel
Experimental Method to Analyse Limit Load in Pressure VesselIJMER
 
Performance and Emissions Analysis Using Diesel and Tsome Blends
Performance and Emissions Analysis Using Diesel and Tsome  BlendsPerformance and Emissions Analysis Using Diesel and Tsome  Blends
Performance and Emissions Analysis Using Diesel and Tsome BlendsIJMER
 
Design and Analysis of Vapour Absorbing Machine
Design and Analysis of Vapour Absorbing MachineDesign and Analysis of Vapour Absorbing Machine
Design and Analysis of Vapour Absorbing MachineIJMER
 
Cg32955961
Cg32955961Cg32955961
Cg32955961IJMER
 

Viewers also liked (20)

Cd31336341
Cd31336341Cd31336341
Cd31336341
 
Study of Flexible Lift Mechanism for Press Shop
Study of Flexible Lift Mechanism for Press ShopStudy of Flexible Lift Mechanism for Press Shop
Study of Flexible Lift Mechanism for Press Shop
 
A New Bi-level Program Based on Unblocked Reliability for a Continuous Road N...
A New Bi-level Program Based on Unblocked Reliability for a Continuous Road N...A New Bi-level Program Based on Unblocked Reliability for a Continuous Road N...
A New Bi-level Program Based on Unblocked Reliability for a Continuous Road N...
 
A Study of Wind Turbine Blade Power Enhancement Using Aerodynamic Properties
A Study of Wind Turbine Blade Power Enhancement Using  Aerodynamic Properties A Study of Wind Turbine Blade Power Enhancement Using  Aerodynamic Properties
A Study of Wind Turbine Blade Power Enhancement Using Aerodynamic Properties
 
Compensation for Inverter Nonlinearity Using Trapezoidal Voltage
Compensation for Inverter Nonlinearity Using Trapezoidal  VoltageCompensation for Inverter Nonlinearity Using Trapezoidal  Voltage
Compensation for Inverter Nonlinearity Using Trapezoidal Voltage
 
An Investigative Review on Thermal Characterization of Hybrid Metal Matrix C...
An Investigative Review on Thermal Characterization of Hybrid  Metal Matrix C...An Investigative Review on Thermal Characterization of Hybrid  Metal Matrix C...
An Investigative Review on Thermal Characterization of Hybrid Metal Matrix C...
 
Experimental Investigation of Performance and Emission Characteristics of Bi...
Experimental Investigation of Performance and Emission  Characteristics of Bi...Experimental Investigation of Performance and Emission  Characteristics of Bi...
Experimental Investigation of Performance and Emission Characteristics of Bi...
 
Cn31386390
Cn31386390Cn31386390
Cn31386390
 
An Enhanced Security System for Web Authentication
An Enhanced Security System for Web Authentication An Enhanced Security System for Web Authentication
An Enhanced Security System for Web Authentication
 
A Bayesian Probit Online Model Framework for Auction Fraud Detection
A Bayesian Probit Online Model Framework for Auction Fraud DetectionA Bayesian Probit Online Model Framework for Auction Fraud Detection
A Bayesian Probit Online Model Framework for Auction Fraud Detection
 
A Note on a Three Variables Analogue of Bessel Polynomials
A Note on a Three Variables Analogue of Bessel PolynomialsA Note on a Three Variables Analogue of Bessel Polynomials
A Note on a Three Variables Analogue of Bessel Polynomials
 
Turnstile S-Shaped Dipole and Swastika Wire Antennas for VHF and UHF Applica...
Turnstile S-Shaped Dipole and Swastika Wire Antennas for VHF  and UHF Applica...Turnstile S-Shaped Dipole and Swastika Wire Antennas for VHF  and UHF Applica...
Turnstile S-Shaped Dipole and Swastika Wire Antennas for VHF and UHF Applica...
 
Implementation of Six Sigma Using DMAIC Methodology in Small Scale Industries...
Implementation of Six Sigma Using DMAIC Methodology in Small Scale Industries...Implementation of Six Sigma Using DMAIC Methodology in Small Scale Industries...
Implementation of Six Sigma Using DMAIC Methodology in Small Scale Industries...
 
A Novel Key Management Paradigm for Broadcasting to Remote Cooperative Groups
A Novel Key Management Paradigm for Broadcasting to Remote  Cooperative GroupsA Novel Key Management Paradigm for Broadcasting to Remote  Cooperative Groups
A Novel Key Management Paradigm for Broadcasting to Remote Cooperative Groups
 
Advanced Micro-Grids
Advanced Micro-Grids Advanced Micro-Grids
Advanced Micro-Grids
 
Dr3211721175
Dr3211721175Dr3211721175
Dr3211721175
 
Experimental Method to Analyse Limit Load in Pressure Vessel
Experimental Method to Analyse Limit Load in Pressure VesselExperimental Method to Analyse Limit Load in Pressure Vessel
Experimental Method to Analyse Limit Load in Pressure Vessel
 
Performance and Emissions Analysis Using Diesel and Tsome Blends
Performance and Emissions Analysis Using Diesel and Tsome  BlendsPerformance and Emissions Analysis Using Diesel and Tsome  Blends
Performance and Emissions Analysis Using Diesel and Tsome Blends
 
Design and Analysis of Vapour Absorbing Machine
Design and Analysis of Vapour Absorbing MachineDesign and Analysis of Vapour Absorbing Machine
Design and Analysis of Vapour Absorbing Machine
 
Cg32955961
Cg32955961Cg32955961
Cg32955961
 

Similar to Bp31250253

Recent research on combustion and NOx emission control at Donghua University
Recent research on combustion and NOx emission control at Donghua UniversityRecent research on combustion and NOx emission control at Donghua University
Recent research on combustion and NOx emission control at Donghua Universityyaxin Su
 
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...theijes
 
peer reviewed journals.pdf
peer reviewed journals.pdfpeer reviewed journals.pdf
peer reviewed journals.pdfnareshkotra
 
Experimental Study of R134a, R406A and R600a Blends as Alternative To Freon 12
Experimental Study of R134a, R406A and R600a Blends as Alternative To Freon 12Experimental Study of R134a, R406A and R600a Blends as Alternative To Freon 12
Experimental Study of R134a, R406A and R600a Blends as Alternative To Freon 12IOSR Journals
 
Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...
Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...
Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...IRJET Journal
 
IRJET- R134a Refrigerant in Vapour Compression Cycle: A Review Paper
IRJET-  	  R134a Refrigerant in Vapour Compression Cycle: A Review PaperIRJET-  	  R134a Refrigerant in Vapour Compression Cycle: A Review Paper
IRJET- R134a Refrigerant in Vapour Compression Cycle: A Review PaperIRJET Journal
 
Literature Review of Mineral Carbonations of steel slag.pptx
Literature Review of Mineral Carbonations of steel slag.pptxLiterature Review of Mineral Carbonations of steel slag.pptx
Literature Review of Mineral Carbonations of steel slag.pptxsandeepsharma432939
 
Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a
Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134aExperimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a
Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134aIOSRJMCE
 
Seminar-Sathomoy.pptx
Seminar-Sathomoy.pptxSeminar-Sathomoy.pptx
Seminar-Sathomoy.pptxAnikaPandey8
 
ammonia National Fertilizer Limited Bathinda
ammonia National Fertilizer Limited Bathindaammonia National Fertilizer Limited Bathinda
ammonia National Fertilizer Limited BathindaDngL611667
 
conversion from HCFC to hydrocarbons
conversion from HCFC to hydrocarbonsconversion from HCFC to hydrocarbons
conversion from HCFC to hydrocarbonsUNEP OzonAction
 
Ammonia production from natural gas, haldor topsoe process
Ammonia production from natural gas, haldor topsoe processAmmonia production from natural gas, haldor topsoe process
Ammonia production from natural gas, haldor topsoe processGaurav Soni
 
Amm plant description
Amm plant descriptionAmm plant description
Amm plant descriptionameermudasar
 
Performance Comparison of Hydrocarbon Refrigerant as Isobutane R600a and Prop...
Performance Comparison of Hydrocarbon Refrigerant as Isobutane R600a and Prop...Performance Comparison of Hydrocarbon Refrigerant as Isobutane R600a and Prop...
Performance Comparison of Hydrocarbon Refrigerant as Isobutane R600a and Prop...journal ijrtem
 
Pollutant abatement of nitrogen based fuel effluents over mono
Pollutant abatement of nitrogen based fuel effluents over monoPollutant abatement of nitrogen based fuel effluents over mono
Pollutant abatement of nitrogen based fuel effluents over monoimplax
 
Tesfaye and Patel RP Mater. Proc..pdf
Tesfaye and Patel RP Mater. Proc..pdfTesfaye and Patel RP Mater. Proc..pdf
Tesfaye and Patel RP Mater. Proc..pdfMahaboobPatel2
 

Similar to Bp31250253 (20)

Q01245139144
Q01245139144Q01245139144
Q01245139144
 
Refrigerant
RefrigerantRefrigerant
Refrigerant
 
Recent research on combustion and NOx emission control at Donghua University
Recent research on combustion and NOx emission control at Donghua UniversityRecent research on combustion and NOx emission control at Donghua University
Recent research on combustion and NOx emission control at Donghua University
 
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...
 
peer reviewed journals.pdf
peer reviewed journals.pdfpeer reviewed journals.pdf
peer reviewed journals.pdf
 
Experimental Study of R134a, R406A and R600a Blends as Alternative To Freon 12
Experimental Study of R134a, R406A and R600a Blends as Alternative To Freon 12Experimental Study of R134a, R406A and R600a Blends as Alternative To Freon 12
Experimental Study of R134a, R406A and R600a Blends as Alternative To Freon 12
 
Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...
Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...
Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...
 
IRJET- R134a Refrigerant in Vapour Compression Cycle: A Review Paper
IRJET-  	  R134a Refrigerant in Vapour Compression Cycle: A Review PaperIRJET-  	  R134a Refrigerant in Vapour Compression Cycle: A Review Paper
IRJET- R134a Refrigerant in Vapour Compression Cycle: A Review Paper
 
Literature Review of Mineral Carbonations of steel slag.pptx
Literature Review of Mineral Carbonations of steel slag.pptxLiterature Review of Mineral Carbonations of steel slag.pptx
Literature Review of Mineral Carbonations of steel slag.pptx
 
Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a
Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134aExperimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a
Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a
 
Seminar-Sathomoy.pptx
Seminar-Sathomoy.pptxSeminar-Sathomoy.pptx
Seminar-Sathomoy.pptx
 
ammonia National Fertilizer Limited Bathinda
ammonia National Fertilizer Limited Bathindaammonia National Fertilizer Limited Bathinda
ammonia National Fertilizer Limited Bathinda
 
conversion from HCFC to hydrocarbons
conversion from HCFC to hydrocarbonsconversion from HCFC to hydrocarbons
conversion from HCFC to hydrocarbons
 
Ammonia production from natural gas, haldor topsoe process
Ammonia production from natural gas, haldor topsoe processAmmonia production from natural gas, haldor topsoe process
Ammonia production from natural gas, haldor topsoe process
 
Amm plant description
Amm plant descriptionAmm plant description
Amm plant description
 
Performance Comparison of Hydrocarbon Refrigerant as Isobutane R600a and Prop...
Performance Comparison of Hydrocarbon Refrigerant as Isobutane R600a and Prop...Performance Comparison of Hydrocarbon Refrigerant as Isobutane R600a and Prop...
Performance Comparison of Hydrocarbon Refrigerant as Isobutane R600a and Prop...
 
Pollutant abatement of nitrogen based fuel effluents over mono
Pollutant abatement of nitrogen based fuel effluents over monoPollutant abatement of nitrogen based fuel effluents over mono
Pollutant abatement of nitrogen based fuel effluents over mono
 
V4408114122
V4408114122V4408114122
V4408114122
 
Tesfaye and Patel RP Mater. Proc..pdf
Tesfaye and Patel RP Mater. Proc..pdfTesfaye and Patel RP Mater. Proc..pdf
Tesfaye and Patel RP Mater. Proc..pdf
 
Md. habibur rahman
Md. habibur rahmanMd. habibur rahman
Md. habibur rahman
 

More from IJMER

A Study on Translucent Concrete Product and Its Properties by Using Optical F...
A Study on Translucent Concrete Product and Its Properties by Using Optical F...A Study on Translucent Concrete Product and Its Properties by Using Optical F...
A Study on Translucent Concrete Product and Its Properties by Using Optical F...IJMER
 
Developing Cost Effective Automation for Cotton Seed Delinting
Developing Cost Effective Automation for Cotton Seed DelintingDeveloping Cost Effective Automation for Cotton Seed Delinting
Developing Cost Effective Automation for Cotton Seed DelintingIJMER
 
Study & Testing Of Bio-Composite Material Based On Munja Fibre
Study & Testing Of Bio-Composite Material Based On Munja FibreStudy & Testing Of Bio-Composite Material Based On Munja Fibre
Study & Testing Of Bio-Composite Material Based On Munja FibreIJMER
 
Hybrid Engine (Stirling Engine + IC Engine + Electric Motor)
Hybrid Engine (Stirling Engine + IC Engine + Electric Motor)Hybrid Engine (Stirling Engine + IC Engine + Electric Motor)
Hybrid Engine (Stirling Engine + IC Engine + Electric Motor)IJMER
 
Fabrication & Characterization of Bio Composite Materials Based On Sunnhemp F...
Fabrication & Characterization of Bio Composite Materials Based On Sunnhemp F...Fabrication & Characterization of Bio Composite Materials Based On Sunnhemp F...
Fabrication & Characterization of Bio Composite Materials Based On Sunnhemp F...IJMER
 
Geochemistry and Genesis of Kammatturu Iron Ores of Devagiri Formation, Sandu...
Geochemistry and Genesis of Kammatturu Iron Ores of Devagiri Formation, Sandu...Geochemistry and Genesis of Kammatturu Iron Ores of Devagiri Formation, Sandu...
Geochemistry and Genesis of Kammatturu Iron Ores of Devagiri Formation, Sandu...IJMER
 
Experimental Investigation on Characteristic Study of the Carbon Steel C45 in...
Experimental Investigation on Characteristic Study of the Carbon Steel C45 in...Experimental Investigation on Characteristic Study of the Carbon Steel C45 in...
Experimental Investigation on Characteristic Study of the Carbon Steel C45 in...IJMER
 
Non linear analysis of Robot Gun Support Structure using Equivalent Dynamic A...
Non linear analysis of Robot Gun Support Structure using Equivalent Dynamic A...Non linear analysis of Robot Gun Support Structure using Equivalent Dynamic A...
Non linear analysis of Robot Gun Support Structure using Equivalent Dynamic A...IJMER
 
Static Analysis of Go-Kart Chassis by Analytical and Solid Works Simulation
Static Analysis of Go-Kart Chassis by Analytical and Solid Works SimulationStatic Analysis of Go-Kart Chassis by Analytical and Solid Works Simulation
Static Analysis of Go-Kart Chassis by Analytical and Solid Works SimulationIJMER
 
High Speed Effortless Bicycle
High Speed Effortless BicycleHigh Speed Effortless Bicycle
High Speed Effortless BicycleIJMER
 
Integration of Struts & Spring & Hibernate for Enterprise Applications
Integration of Struts & Spring & Hibernate for Enterprise ApplicationsIntegration of Struts & Spring & Hibernate for Enterprise Applications
Integration of Struts & Spring & Hibernate for Enterprise ApplicationsIJMER
 
Microcontroller Based Automatic Sprinkler Irrigation System
Microcontroller Based Automatic Sprinkler Irrigation SystemMicrocontroller Based Automatic Sprinkler Irrigation System
Microcontroller Based Automatic Sprinkler Irrigation SystemIJMER
 
On some locally closed sets and spaces in Ideal Topological Spaces
On some locally closed sets and spaces in Ideal Topological SpacesOn some locally closed sets and spaces in Ideal Topological Spaces
On some locally closed sets and spaces in Ideal Topological SpacesIJMER
 
Intrusion Detection and Forensics based on decision tree and Association rule...
Intrusion Detection and Forensics based on decision tree and Association rule...Intrusion Detection and Forensics based on decision tree and Association rule...
Intrusion Detection and Forensics based on decision tree and Association rule...IJMER
 
Natural Language Ambiguity and its Effect on Machine Learning
Natural Language Ambiguity and its Effect on Machine LearningNatural Language Ambiguity and its Effect on Machine Learning
Natural Language Ambiguity and its Effect on Machine LearningIJMER
 
Evolvea Frameworkfor SelectingPrime Software DevelopmentProcess
Evolvea Frameworkfor SelectingPrime Software DevelopmentProcessEvolvea Frameworkfor SelectingPrime Software DevelopmentProcess
Evolvea Frameworkfor SelectingPrime Software DevelopmentProcessIJMER
 
Material Parameter and Effect of Thermal Load on Functionally Graded Cylinders
Material Parameter and Effect of Thermal Load on Functionally Graded CylindersMaterial Parameter and Effect of Thermal Load on Functionally Graded Cylinders
Material Parameter and Effect of Thermal Load on Functionally Graded CylindersIJMER
 
Studies On Energy Conservation And Audit
Studies On Energy Conservation And AuditStudies On Energy Conservation And Audit
Studies On Energy Conservation And AuditIJMER
 
An Implementation of I2C Slave Interface using Verilog HDL
An Implementation of I2C Slave Interface using Verilog HDLAn Implementation of I2C Slave Interface using Verilog HDL
An Implementation of I2C Slave Interface using Verilog HDLIJMER
 
Discrete Model of Two Predators competing for One Prey
Discrete Model of Two Predators competing for One PreyDiscrete Model of Two Predators competing for One Prey
Discrete Model of Two Predators competing for One PreyIJMER
 

More from IJMER (20)

A Study on Translucent Concrete Product and Its Properties by Using Optical F...
A Study on Translucent Concrete Product and Its Properties by Using Optical F...A Study on Translucent Concrete Product and Its Properties by Using Optical F...
A Study on Translucent Concrete Product and Its Properties by Using Optical F...
 
Developing Cost Effective Automation for Cotton Seed Delinting
Developing Cost Effective Automation for Cotton Seed DelintingDeveloping Cost Effective Automation for Cotton Seed Delinting
Developing Cost Effective Automation for Cotton Seed Delinting
 
Study & Testing Of Bio-Composite Material Based On Munja Fibre
Study & Testing Of Bio-Composite Material Based On Munja FibreStudy & Testing Of Bio-Composite Material Based On Munja Fibre
Study & Testing Of Bio-Composite Material Based On Munja Fibre
 
Hybrid Engine (Stirling Engine + IC Engine + Electric Motor)
Hybrid Engine (Stirling Engine + IC Engine + Electric Motor)Hybrid Engine (Stirling Engine + IC Engine + Electric Motor)
Hybrid Engine (Stirling Engine + IC Engine + Electric Motor)
 
Fabrication & Characterization of Bio Composite Materials Based On Sunnhemp F...
Fabrication & Characterization of Bio Composite Materials Based On Sunnhemp F...Fabrication & Characterization of Bio Composite Materials Based On Sunnhemp F...
Fabrication & Characterization of Bio Composite Materials Based On Sunnhemp F...
 
Geochemistry and Genesis of Kammatturu Iron Ores of Devagiri Formation, Sandu...
Geochemistry and Genesis of Kammatturu Iron Ores of Devagiri Formation, Sandu...Geochemistry and Genesis of Kammatturu Iron Ores of Devagiri Formation, Sandu...
Geochemistry and Genesis of Kammatturu Iron Ores of Devagiri Formation, Sandu...
 
Experimental Investigation on Characteristic Study of the Carbon Steel C45 in...
Experimental Investigation on Characteristic Study of the Carbon Steel C45 in...Experimental Investigation on Characteristic Study of the Carbon Steel C45 in...
Experimental Investigation on Characteristic Study of the Carbon Steel C45 in...
 
Non linear analysis of Robot Gun Support Structure using Equivalent Dynamic A...
Non linear analysis of Robot Gun Support Structure using Equivalent Dynamic A...Non linear analysis of Robot Gun Support Structure using Equivalent Dynamic A...
Non linear analysis of Robot Gun Support Structure using Equivalent Dynamic A...
 
Static Analysis of Go-Kart Chassis by Analytical and Solid Works Simulation
Static Analysis of Go-Kart Chassis by Analytical and Solid Works SimulationStatic Analysis of Go-Kart Chassis by Analytical and Solid Works Simulation
Static Analysis of Go-Kart Chassis by Analytical and Solid Works Simulation
 
High Speed Effortless Bicycle
High Speed Effortless BicycleHigh Speed Effortless Bicycle
High Speed Effortless Bicycle
 
Integration of Struts & Spring & Hibernate for Enterprise Applications
Integration of Struts & Spring & Hibernate for Enterprise ApplicationsIntegration of Struts & Spring & Hibernate for Enterprise Applications
Integration of Struts & Spring & Hibernate for Enterprise Applications
 
Microcontroller Based Automatic Sprinkler Irrigation System
Microcontroller Based Automatic Sprinkler Irrigation SystemMicrocontroller Based Automatic Sprinkler Irrigation System
Microcontroller Based Automatic Sprinkler Irrigation System
 
On some locally closed sets and spaces in Ideal Topological Spaces
On some locally closed sets and spaces in Ideal Topological SpacesOn some locally closed sets and spaces in Ideal Topological Spaces
On some locally closed sets and spaces in Ideal Topological Spaces
 
Intrusion Detection and Forensics based on decision tree and Association rule...
Intrusion Detection and Forensics based on decision tree and Association rule...Intrusion Detection and Forensics based on decision tree and Association rule...
Intrusion Detection and Forensics based on decision tree and Association rule...
 
Natural Language Ambiguity and its Effect on Machine Learning
Natural Language Ambiguity and its Effect on Machine LearningNatural Language Ambiguity and its Effect on Machine Learning
Natural Language Ambiguity and its Effect on Machine Learning
 
Evolvea Frameworkfor SelectingPrime Software DevelopmentProcess
Evolvea Frameworkfor SelectingPrime Software DevelopmentProcessEvolvea Frameworkfor SelectingPrime Software DevelopmentProcess
Evolvea Frameworkfor SelectingPrime Software DevelopmentProcess
 
Material Parameter and Effect of Thermal Load on Functionally Graded Cylinders
Material Parameter and Effect of Thermal Load on Functionally Graded CylindersMaterial Parameter and Effect of Thermal Load on Functionally Graded Cylinders
Material Parameter and Effect of Thermal Load on Functionally Graded Cylinders
 
Studies On Energy Conservation And Audit
Studies On Energy Conservation And AuditStudies On Energy Conservation And Audit
Studies On Energy Conservation And Audit
 
An Implementation of I2C Slave Interface using Verilog HDL
An Implementation of I2C Slave Interface using Verilog HDLAn Implementation of I2C Slave Interface using Verilog HDL
An Implementation of I2C Slave Interface using Verilog HDL
 
Discrete Model of Two Predators competing for One Prey
Discrete Model of Two Predators competing for One PreyDiscrete Model of Two Predators competing for One Prey
Discrete Model of Two Predators competing for One Prey
 

Bp31250253

  • 1. International Journal of Modern Engineering Research (IJMER) www.ijmer.com Vol.3, Issue.1, Jan-Feb. 2013 pp-250-253 ISSN: 2249-6645 Use of Hydrocarbons and Other Blends as Refrigerant Mohd. Aasim Nazeer Ahmad Quraishi, 1 U. S.Wankhede2 1 M. Tech. IV Semester, Heat Power Engineering, G. H. Raisoni College of Engineering, Nagpur-440016, 2 Professor, Mechanical Engineering Department, G. H. Raisoni College of Engineering, Nagpur-440016. Abstract: This paper presents a study of different environmental friendly refrigerants of either hydrocarbon or Hydro fluoro carbons (HFC) class. Hydrocarbons (HCs) have zero ODP and very low GWP whereas HFCs have zero ODP but a quite higher GWP. Almost in all the cases, when R-134a was replaced with HCs the COP of the system was improved, ON time ratio and energy consumption was reduced. Due to a higher value of latent heat of HCs, the amount of refrigerant charge was also reduced as compared with HFC-134a. When hydro chloro fluoro carbons (HCFCs) were replaced with HFCs the system delivered a poor performance with increased energy consumption. When nano particles were added to the refrigerant, system delivered better performance with reduced energy consumption than that of pure refrigerant. Keywords: TEWI, ON time ratio, Pull down time. I. Introduction The most commonly used refrigerants in the late 1800s and in the early 1900s were natural refrigerants such as ammonia, carbon dioxide, sulphur dioxide and methyl chloride. All these refrigerants were found to be toxic or hazardous. In 1928, a safer class of alternative refrigerants became available with the invention of chlorofluorocarbons (CFCs) and hydro chloro fluorocarbons (HCFCs). CFCs and HCFCs have many suitable properties such as stability, non–toxicity, non– flammable, good material compatibility and good thermodynamic properties, which led to their common wide spread use by both consumers and industries around the globe, especially as refrigerants in air–conditioning and refrigeration systems. Results from many researches show that ozone layer is being depleted due to the presence of chlorine in the stratosphere. The general consensus for the cause of this is that CFCs and HCFCs are large class of chlorine containing chemicals, which migrate to the stratosphere where they react with ozone. Later, chlorine atoms continue to convert more ozone to oxygen. The discovery of the depletion of the earth’s ozone layer, which shields the earth’s surface from UV radiation, has resulted in a series of international treaties demanding a gradual phase out of halogenated fluids. The CFCs have been banned in developed countries since 1996, and in 2030, producing and using of CFCs will be prohibited completely in the entire world. Also, the partially halogenated HCFCs are bound to be prohibited in the near future. The researches are going on to find out some alternate refrigerants which does not harm to the environment and the protective ozone layer. Research has shown that hydrocarbons are good alternative to existing refrigerants. II. Refrigerants under Considerations Hydrocarbons, propane (R–290) and isobutane (R–600a) were among the first refrigerants, but due to their flammability and safety purposes, their use was abandoned and the direction of researches was shifted towards a safer and inert class of refrigerants. Thus the use of HCs as a refrigerant is not a new technology. Since 15 years, hydrocarbon and their blends are again being used at commercial scale [1]. Isobutane (R–600a) is the most frequently used hydrocarbon refrigerant. In Europe it is the most dominating refrigerant in domestic refrigerators. In 2004, the use of isobutane and its blend was 33% in domestic refrigerators and freezers at global level. Propane (R–290) and propene (R–1270) are widely being used in heat pumps, air conditioners and commercial refrigeration systems. Butane (R–600) is also under consideration but it has not been used commercially. Pentane and pentene also have the potential to be used as refrigerant and they are to be considered as the replacement to R– 11 in centrifugal systems [2]. PROPERTIES OF REFRIGERANTS AT 40OC M Tbp Ttr Tcr hfg l v Ref. No. Formula (kg/kmol) (OC) (OC) (OC) (kJ/kg) (kg/m3) (kg/m3) CH–(CH3) – Isobutane R600a 58.12 –11.67 134.67 311.4 530.0 13.667 3 159.59 CH3– – Propane R290 44.096 –42.09 96.675 306.51 467.07 30.202 CH2–CH3 187.67 CH2=CH– Propene R1270 42.08 –47.69 –185.2 92.42 303.14 476.66 35.708 CH3 R134a R134a CF3–CH2F 102.03 –26.074 –103.3 101.06 163.02 1146.7 50.085 – R22 R22 CHClF2 86.468 –40.81 96.145 166.6 1128.5 66.193 157.42 – Ammonia R717 NH3 17.03 –33.327 132.25 1099.31 579.44 12.034 77.655 www.ijmer.com 250 | Page
  • 2. International Journal of Modern Engineering Research (IJMER) www.ijmer.com Vol.3, Issue.1, Jan-Feb. 2013 pp-250-253 ISSN: 2249-6645 Ref. Refrigerant name no. Refrigerant number Formula Chemical formula M Molecular weight Tbp Normal boiling point Ttr Triple point Tcr Critical temperature hfg Latent heat of vaporization  l Liquid density  v Vapor density III. Literature Survey a) Replacement of R-22 with HFCs A trial was performed by Rocca and Panno [3] to replace R22 with new HFC refrigerants and the performance was compared with R–22. The plant working efficiency was first estimated with R–22 and then with three new HFC refrigerants, R–417a, R–422a and R–422d. The experimental results showed that R–22 has the least energy consumption among all the refrigerants under trial. Results also reveal that the three HFC refrigerants can replace R–22 without any change in lubricant or without any modification in the system and the accessories. These refrigerants also provide the safe and reliable working conditions. The results also verified that despite these advantages, the performance of the new tested HFCs was not as efficient as with R–22. Experimentation was made to replace R–22 with a new refrigerant R–422d by Aprea et al. [4]. The experiment was carried out under three different operating conditions. The experimental results showed that COP of the system with R–422d was 20% lower than that of using R–22, the reason behind is high vapor density that also leads to lower cooling capacity and increased energy consumption. The discharge pressure was 15% higher than that of R–22 but it was under design limit. The discharge temperature was 20OC lower which offers a longer compressor life. The improvement in heat exchange by condenser in order to improve the performance was carried out by using a fan. Increasing the fan speed only by 20% improved COP in the range of 14.5–23.5%. Llopis et al. [5] replaced R–22 by two refrigerants HFC–422a and HFC–417b in medium and low evaporating temperatures. The test was conducted in a two stage refrigerating plant equipped with subcooling. The evaporator and condenser temperature range were –31OC to 17OC and 30OC to 48OC respectively. The experimental results showed that with the use of new refrigerants, the refrigerant mass flow rate need to be incremented. The new refrigerants also lead to lower specific refrigerating effect that tends to reduced cooling capacity. This reduction in the plant capacity was much more than expected from the theoretical analysis. b) Replacement of R-134a with other HFCs Bolaji [6] carried out a trial on domestic refrigerator designed to work with R–134a and replaced it by R–152a and R–32 which have zero ODP and low GWP. The performance with the new refrigerant was evaluated and compared with R– 134a. The result showed that the average COP obtained with R–152a was 4.7% higher while average COP with R–32 was 8.5% lower as compared to R–134a. The energy consumption by the system was also reduced. The compressor consumed 4.0% and 3.2% lesser energy with R–152a as compared to the energy consumption with R–134a and R–32 respectively. The design temperature and pull down time using R–152a and R–134a were achieved earlier than using R–32. The discharge pressure of R–152a was about 0.8% less than that of R–134a while the discharge pressure using R–32 was the highest with average value of 8.1% and 7.2% higher than those of R–134a and R–152a respectively. In general, the system performed better than the other two refrigerants this shows that R–152a can be used to replace R–134a in domestic refrigerators. A trial was made by Khorshid et al. [7] on domestic refrigerator to replace R–134a by two different blends one as R–134a (6.61%), R–32 (5.64%) and R–152a (87.75%) and the other as R–32 (15.34%), R–600a (8.79%) and R–152a (75.87%). The results of the test show that COP was improved by 11.93% and 2.07% by using the former and latter respectively as compared with R–134a. The new refrigerant blends have zero ODP and low GWP of the order of 242 and 200 respectively. IV. Replacement of R-134a with HCs Jwo et al. [8] used a blend of R–290 and R–600a instead of R–134a. The experiment was performed on a 440 liters domestic refrigerator. During test refrigerant R–134a was replaced with varied mass of hydrocarbon blends. The results show that refrigerating effect was improved by using hydrocarbon blends. The refrigerator which was designed to work with 150 gm of R–134a gave best result with 90 gm of hydrocarbon refrigerant that implies a reduction of 40% in refrigerant charge. The design temperature was obtained quicker when the mixture of R–290 and R–600a was used that reduced the individual working time, hence the total working time per month was lesser than by using R–134a. On average, the new refrigerant mixture offers a better refrigerating behavior and reduces the energy consumption by 4.4%. Rasti et al. [9] substituted R–134a with R–436a (mixture of R–290 and R–600a with a mass ratio of 56/44) in a 238 liter domestic refrigerator without any modification in the system. The compressor was charged with different amount of R– 436a. The various results of the experiment showed that the refrigerant R–436a has better performance compared to R–134a considering various parameters. The ON time ratio was reduced by 13% when R–436a was used. The energy consumption per day was reduced by 5.3%. The refrigerant charge required in case of R–134a was 105g and the optimum amount of refrigerant for R–436a was 55g which implies a saving of 48% in refrigerant charge. The evaporator inlet temperature was reduced by 3.5oC. The energy efficiency index was raised from E to D. The results also showed that Total Equivalent Warming Impact (TEWI) of R–436a is 11.8% lesser than R–134a. Thus R–436a appears to be a good replacement for R– 134a. www.ijmer.com 251 | Page
  • 3. International Journal of Modern Engineering Research (IJMER) www.ijmer.com Vol.3, Issue.1, Jan-Feb. 2013 pp-250-253 ISSN: 2249-6645 Sattar et al. [10] used a domestic refrigerator to conduct trial which was designed to work with R–134a. The trial was conducted to check the possibility of using hydrocarbons as refrigerants. Pure butane, isobutane and mixture of butane, isobutane and propane were used as alternate refrigerants. The performance of the system was compared with R–134a. The compressor consumed 3% and 2% lesser energy when iso butane and butane were used at 28 oC ambient condition. The amount of refrigerant charge with R–134a was 140 gm and it was reduced to 70 gm with the pure hydrocarbon and its blends which exhibits a saving of 50% in refrigerant charge. The trials were performed without any alteration in the system that shows the possibility of using hydrocarbons and their blends without any modification. V. Replacement of Pure Refrigerant with Nano Refrigerant Shengshan Bi et al. [11] made use of TiO2–R600a nano refrigerant in a domestic refrigerator without any system modification. The experimentation was performed using TiO2–R600a with 0.1 g/lit and 0.5 g/lit of TiO2 nano particles concentrations. The performance was compared with pure R-600a. The design temperatures were obtained at a quicker rate with TiO2–R600a nano refrigerant. The energy consumptions were reduced by 5.94% and 9.60% with the concentrations as 0.1 g/lit and 0.5 g/lit of TiO2 nano particles respectively. All the results obtained exhibited that TiO2–R600a nano refrigerant worked safely and normally in the refrigerator with better performance than pure R–600a system. Thus TiO2–R600a nano refrigerant may be used in domestic refrigerator with better performance and lower energy consumption without any alteration of the system. Saidur et al. [12] conducted experiment with HFC–134a in domestic refrigerator with TiO2 nano particles. The results showed that this nano refrigerant gave better performance. The energy consumption of HFC–134a refrigerant using mineral oil and nano particles mixture as lubricant was lesser than with pure HFC–134a and it saved 26.1% energy with 0.1% mass fraction TiO2 nano particles compared to the HFC–134a. 60% HFC–134a with mineral oil and 0.1% wt Al 2O3 nano particles gave optimal performance. The power consumption was reduced by 2.4% and the COP was improved by 4.4%. It has been identified that fundamental properties of nano fluids change drastically and depend upon the concentration of suspension of the nano particles in the base fluid. VI. Conclusions As per the Kyoto and Montreal protocols, the harmful refrigerants are to be phased out and are to be replaced with alternate environmental friendly refrigerants. The objective of this paper is to evaluate different environmental friendly refrigerant. On the basis of collecting information, the following conclusions may be drawn. HFCs can replace R-22 without any modification in the system. Despite having the advantage of zero ODP, the system delivers the poor performance with increased energy consumption as compared with R-22. Hydrocarbons and their various blends may replace R-134a without any system modifications. COP of the system is improved with reduced energy consumption. ON time ratio and pull down time are also reduced. The system requires to be charged with 40% to 50% lesser amount of refrigerant due to a quite higher value of latent heat of hydrocarbons. When nano particles are added to the refrigerants, thermo physical properties change drastically and depend on the concentration of the nano particles. Nano refrigerant can be used in the refrigeration system without any modifications. The system delivers better performance than with pure refrigerant; the energy consumption is also reduced. However optimum blend composition for maximum performance of the system is not much studied. Research work for deciding the concentration of blends has to be undertaken to have better performance of the system. References [1] Jose M. Corberan, Jacobo Segurado, Daniel Colbourne, Jose Gonzalvez, Review of standards for the use of hydrocarbon refrigerants in A/C, heat pump and refrigeration equipment, International Journal of Refrigeration 31 (2008) 748–756. [2] Bjorn Palm, Hydrocarbons as refrigerants in small heat pump and refrigeration systems – A review, International Journal of Refrigeration 31 (2008) 552–563. [3] Vincenzo La Rocca, Giuseppe Panno, Experimental performance evaluation of a vapour compression refrigerating plant when replacing R22 with alternative refrigerants Applied Energy 88 (2011) 2809–2815. [4] Ciro Aprea, Angelo Maiorino, Rita Mastrullo, Change in energy performance as a result of a R–422d retrofit: An experimental analysis for a vapor compression refrigeration plant for a walk in cooler, Applied Energy 88, (2011) 4742–4748. [5] R. Llopis, R. Cabello, D. Sánchez, E. Torella, J. Patino, J. G. Sánchez, Experimental evaluation of HCFC–22 replacement by the drop-in fluids HFC-422a and HFC-417b for low temperature refrigeration applications, Applied Thermal Engineering 31 (2011) 1323–1331. [6] B. O. Bolaji, Experimental study of R152a and R32 to replace R134a in a domestic refrigerator, Energy 35 (2010) 3793–3798. [7] E. Khorshid, B. Alshiraan, A. Alsairafi, A. Alzemi, A. Allahddad, Performance investigation on new refrigerant mixture (2011). [8] Ching Song Jwo, Chen–Ching Ting, Wei–Ru Wang, Efficiency analysis of home refrigerators by replacing hydrocarbon refrigerants, Measurement 42 (2009) 697–701. [9] M. Rasti M.S. Hatamipour, S.F. Aghmiri, M. Tavakoli, Enhancement of domestic refrigerator’s energy efficiency index using a hydrocarbon mixture refrigerant, Measurement 45 (2012) 1807–1813. [10] M. A. Sattar, R. Saidur, H. H. Masjuki, Performance investigation of domestic refrigerator using pure hydrocarbons and blends of hydrocarbons as refrigerants, World Academy of Science, Engineering and Technology 29 (2007) 223–228. [11] Shengshan Bi, Kai Guo, Zhigang Liu, Jiangtao Wu, Performance of a domestic refrigerator using TiO2–R600a nano–refrigerant as working fluid, Energy Conversion and Management 52 (2011) 733–737. [12] R. Saidur, S.N. Kazi, M.S. Hossain, M.M. Rahman, H.A. Mohammed, A review on the performance of nano particles suspended with refrigerants and lubricating oils in refrigeration systems, Renewable and Sustainable Energy Reviews 15 (2011) 310–323. www.ijmer.com 252 | Page