IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE)
e-ISSN: 2278-1684,p-ISSN: 2320-334X, Volume 14, Issue 1 Ver. V (Jan. - Feb. 2017), PP 75-82
www.iosrjournals.org
DOI: 10.9790/1684-1401057582 www.iosrjournals.org 75 | Page
Experimental Evaluation of Refrigerant Mixtures as Substitutes
for HFC134a
Dr. Deepak Paliwal
(Mechanical Engineering Department, S. V. Polytechnic College Bhopal, India)
Abstract: Refrigerant R134a base systems has higher GWP value that's why the conversion of same into eco-
friendly system is the major concern for refrigeration industry. This investigation focuses on mixture ratio of
pure hydrocarbon R290 and R600a used in 200 liter domestic refrigeration system by certain changes in mass
ratio of refrigerants. In the present work, first of all the effect of mass ratio of HCM refrigerants on the
performance of the system was investigated. HCM of R600a/R290 (60/40 by wt. %) gave better performance
than that of HCM R600a/R290 (70/30 by wt. %), R600a/R290 (50/50 by wt. %) and R134a.
The mass ratio of HCM (R600a/ R290) refrigerants was optimized for the performance parameter with respect
to evaporating temperature. The COP of R600a/R290 (60/40 by wt. %) mixture was higher than that of
R600a/R290 (50/50 by wt. %) by 21.9% and 17.6% at -5 0
C and 5 0
C evaporative temperature respectively. COP
decreased as propane mass fraction in HCM increased above 40%.
Keywords: Refrigerant, R134a, Pull down, COP, R600a/R290, HCM.
I. Introduction
Refrigeration goes back to ancient times where storage of ice, evaporation of water, and other evaporative
processes were prevailing. More specifically, refrigeration is that branch of science which deals with the process
of decreasing and maintaining the temperature of any space or material below the temperature of the
atmosphere[1]. According to ASHRAE, it is defined as the science of providing and maintaining temperature
below that of surroundings [2]. For the past half century, CFCs have been used extensively in the refrigeration
sector. (CFCs) and hydrochlorofluorocarbons (HCFCs) became the most dominant types of refrigerants due to
their properties of non- corrosiveness, non-flammability, non-toxicity and non-irritability[3].
The problems occurred, when in 1974, Molina and Rowland, reported and published their ozone
depletion hypothesis in which they claimed that the chlorine element catalytically destroyed the ozone layer in
the stratosphere [4]. Since the advent of the Montreal Protocol, however, Refrigeration sector has been find out
solution for ozone depleting substances. Alternative to CFCs refrigerants are HFC-152a, HFC-134a, MP66/39,
HC-290/600a etc. These days, the concern for the greenhouse warming has never been greater. HFC-134a is
non-flammable and has zero ozone depletion potential but serious GWP[5]. Thus, in 1997 the Kyoto Protocol
was signed by many nations calling for the reduction in emissions of greenhouse gases including HFCs. There
has been much resistance in adopting HFC134a for refrigeration equipment by some environmental groups.
European countries are uses hydrocarbon in pure or mixed form on their refrigerator in early of 2000.
Hydrocarbon refrigerants are flammable[6]. They have zero ozone depletion potential and a greenhouse warming
potential approaching zero. Many researchers have reported performance evaluation of hydrocarbon mixtures by
both experimental and simulation methods [1-5]. India and China are the largest refrigerator demanding countries
in the world, have been quite active in the application of hydrocarbons in domestic refrigerators. The assessment of
alternative refrigerants is a difficult task[7]. Several criteria must be considered while selecting alternative
refrigerants. The experimental work carried out in this area is also extensive. Many drop-in tests are being carried
out to check the performance of replacement refrigerant in existing machines, designed for CFCs, HFCs and
HCFCs[8].
II. Literature survey
Y. S. Lee et al.[9] did an experiment and tested Iso-butane in domestic refrigerator. The compressor input
power varies from 230 and 300 W, while the refrigerant charged was about 150 g. It was found that the COP lie
between 0.8 - 3.5 in freezing application. This study focused only on the performance of a VCR system with
R600a as the alternative refrigerants. B. Tashtoush et al. [10] conducted an experiment with the aim to analyze
hydrocarbons (R600/R290/R134a) at various quantities in R12 domestic refrigerator. The results shows that
Butane/Propane/R134a mixtures provide excellent performance parameters, such as COP of refrigerators,
compression power, volumetric efficiency, condenser duty, compressor discharge pressure and temperature,
relative to a 210 g charge of R12. S. Joseph Shekhar et al. [11] had performed experimental analysis on a 165
liter, CFC-12 based domestic refrigerator retrofitted with eco-friendly refrigerant mixture of HFC134a / HC290
/ HC600a without changing the mineral oil. The system had been running successfully for more than 12 months,
Experimental Evaluation of Refrigerant Mixtures As Substitutes For Hfc134a
DOI: 10.9790/1684-1401057582 www.iosrjournals.org 76 | Page
thus it was observed that the new mixture was compatible with mineral oil. The improvement in theoretical
analysis of COP and actual COP were found out from 3 to 12% and 3 to 8%, respectively. M. Fatouh et al. [12]
had used LPG i.e. mixture of 60% propane and 40% commercial butane for drop-in replacement of HFC134a, in
a single evaporator domestic refrigerator with a volume of 10 ft3
. Highest actual COP, lowest on-time ratio and
lowered electric consumption were achieved in LPG refrigerator than that of R134a by 7.6%, 14.3% and 10.8%,
respectively. Hence, it can be concluded that the proposed LPG shown to be an appropriate and long-term
alternative refrigerant to replace R134a in the existing refrigerator. K.Senthil Kumar et al. [13] experimentally
tested HC mixture (30%R290 & 70%R123) and computationally replacing R12 in this work, to overcome the
above said problem, in a refrigerant mixture R290 has been identified as suitable for combination with R123. . It
is observed that the difference of pressure and temperature characteristics disappears as the R290 mass fraction
is increased from 10% to 30% with R123 and the curve almost matches the R12 curve, which symbolized that
mixture 7/3 can exhibits similar properties and could be used as a substitute for CFC-12.
M. Mohanraj et al. [14] studied that domestic refrigerator uses HFC134a as refrigerant, due to its
excellent thermodynamics and thermal- physical properties. But, HFC134a has high global warming potential
(GWP) of 1300. This paper presents experimental results of an energy-efficient hydrocarbons (HC) mixture
consisting of 45% HC290 and 55% HC600a as a drop-in substitute for HFC134a as various mass charges of 40
g, 50 g, 70 g and 90 g in domestic refrigerators. The results practically showed that the 70 g mixture as barrier of
COP, lower power consumption, lower pull-down time and lower discharging temperature than HFC134a. The
miscibility of synthetic oil with HC refrigerant mixture was also found to be good. K. Mani et al. [15] done an
experiment and analyzed that the performance study on a VCR system with the new refrigerant mixture
R290/R600a as a drop-in replacement was with CFC-12 and HFC134a. Experimental results showed that the
refrigerant effect of R290/R600a (68/32 by wt. %) mixture was higher than that of R12 in the range of 19.9% to
50.1% at the lower evaporating temperature and in the range of 21.2 to 28.5% at the higher evaporating
temperatures, respectively. COP of R290/R600a mixture increased from 3.9% to 25.1% at lower evaporating
temperatures than that of R12 and COP of R290/R600a mixture increased from 11.8% to 17.6% at higher
evaporating temperatures to than that of R12. The refrigerant R134a showed slightly lower coefficient of
performance than R12. The R290/R600a (68/32 by wt. %) mixture can be considered as a drop-in replacement
refrigerant for CFC-12 and HFC134a refrigerants.
III. Experimental setup
An experimental set-up for vapor compression refrigeration system was designed to investigate the
performance of R134a, R600a, R600a/R290 (70/30 by wt. %), R600a/R290 (60/40 by wt %) and R600a/R290
(50/50 by wt %) mixture refrigerants. Fig.1 shows actual view of the experimental set-up and Fig.2 shows line
diagram. The system was a 200 liter domestic refrigerator ( with deep freezing capacity ) that was originally
designed for 150g R134a mass of refrigerant. It consists of two loops, the main loop consist of a compressor, a
condenser, a filter-drier, a expansion device and a calorimeter, and second loop consisted of a evaporator
instead of calorimeter with all other main equipments. Hermetically sealed reciprocating compressor
recommended for R134a refrigerant of 200 liter refrigerator (with deep freezing capacity) was used in the
system. A force convection air - cooled condenser was used. Capillary tube of 10 feet length, and 0.036 inches
diameter was used as expansion device in the system. Refrigerating effects of the system calculated by a
calorimeter connected in the main loop. It consisted of a cooling coil of 25 feet length and 5/16 inches diameter,
temperature measuring device, a electric heater by motor and a stirrer rotted for maintaining equal temperature in
the calorimeter. All these devices were properly placed in a insulated plastic container having 10 liter ethylene
glycol. The calorimeter was fitted with an electric heater and a dimmerstat (attached with wattmeter) to calculate
R.E. (heat gain by heater will be equal to heat removed by evaporator coil).
All these 9 thermocouples in the accuracy range of -50 ÂșC to 80 ÂșC with ± 0.1 ÂșC were fitted at inlet and
outlet of all the major components. A drier was used after condenser to absorb moisture present in the
refrigerant. In two pressure gauges, one is compound pressure gauge which is measured from -30 psi to 500 psi
and one normal pressure gauge which is measured form -30 psi to 150 psi with ± 1 psi accuracy fitted at
compressor discharge and suction side, respectively. Compressor power consumption was measured by a
wattmeter with an accuracy of ± 0.5%. Energy consumption by the heating coils (inside calorimeter) was
measured by a wattmeter with an accuracy of ± 0.5 %. Energy supply meter also used to calculate total energy
consumption in KW/hr.
Experimental Evaluation of Refrigerant Mixtures As Substitutes For Hfc134a
DOI: 10.9790/1684-1401057582 www.iosrjournals.org 77 | Page
Figure 1: Actual view of experimental set-up for VCR system.
Figure 2: Line diagram of the experimental set-up for VCR system.
IV. Experimental procedure
The system was evacuated up to the negative pressure -20 psi to eliminate impurities, moisture and
other foreign materials present inside the system by using vacuum pump, which might affect the accuracy of the
experimental set-up. Then the refrigerator was charged in different mass fraction with the help of electronic
weight m/c and charging valves. Initially we used 250g R134a refrigerant to calculate values for base line test.
After that 125g HCM in different mass fractions we used to find out best refrigerant for the system. In all,
measurements are taken when the system reached steady state condition (calorimeter temperature was
maintained for 10 minutes at measured value temperature with the help of dimmerstat).
Temperatures were recorded after every 10 minute interval in 0
C by 9 thermocouples, which are placed
in all major equipments. Pressure at suction and discharge side of the compressor were also measured by two
pressure gauges, after every 10 minute interval. To calculate pull down test system was cooled up from
atmospheric temperature to desired temperature. R.E. at particular evaporating temperature was found by
maintaining calorimeter, at that temperature with the help of heating device. In this process, wattmeter attached
with calorimeter gave R.E. and wattmeter attached with compressor gave power consumption. The process was
repeated for every refrigerants which were tested at all measured evaporating temperature.
Experimental Evaluation of Refrigerant Mixtures As Substitutes For Hfc134a
DOI: 10.9790/1684-1401057582 www.iosrjournals.org 78 | Page
V. Result and Discussion
Experimental results obtained from pull down test with respect to time in minutes and performance
parameters such as refrigerant effect, energy consumption, COP etc. with respect to evaporating temperature
were analyzed for 125 g HCM R600a/R290 (50/50 by wt%), R600a/R290 (60/40 by wt %), R600a/R290 (70/30
by wt. %) and compared these with 250 g R134a refrigerant to optimize mass ratio of the HCM refrigerant for
the system. Experiments were conducted at ambient temperature of 30 ÂșC.
1. Pull down characteristics - Fig.3 shows the variation of calorimeter temperature with respect to time. The
temperature of ethylene glycol (10 liter) was reduced from 20 ÂșC for a period of 60 minute (continuous running
test). The tests were conducted for different lengths of the capillary and refrigerants. In the entire range of
operation minimum temperature was obtained for HCM 50/50. It is due to the fact that with increase in propane
mass fraction, refrigerant mass flow rate increases M. Fatouh et al. [16]. It was observed that of continuous
running test for 60 minutes on VCR system, the lowest temperature in calorimeter was measured to be -5.8 ÂșC
for refrigerant 125 g of R600a/R290 (50/50 by wt.%). The second lowest temperature was observed to be -5.2
ÂșC for 125 g of R600a/R290 (60/40 by wt. %). Calorimeter temperature of 250 g R134a was found to be - 4.5 ÂșC
in 60 minutes continuous running test. Results indicated that the cooling rate increased with the increase of mass
percentage of R290 in refrigerant mixtures due to higher cooling capacity of R290 than other refrigerants. The
nature of the graphs is similar as reported by Chao-Chieh Yu et al. [17].
Fig. 3: Variations of calorimeter temperature with respect to the time (in minutes), at 30 ÂșC ambient temp.
(Continuous Running Test).
2. Refrigerating effect -Fig. 4 shows the effect of evaporating temperatures on the R. E. for the refrigerants 250
g R134, 125 g R600a/R290 (70/30wt.%), 125 g R600a/R290 (60/40 by wt.%) and 125 g R600a/R290 (50/50 by
wt.%), at the capillary length of 10 feet. It was observed that in the tested range of evaporating temperatures, the
R .E. increases with the increase in evaporating temperatures and was found to be maximum for the 125 g
R600a/R290 60/40. It is due to the fact that with increase in propane mass fraction refrigerant mass flow rate
increases M. Fatouh et al. [16,38]. R. E. for HCM R600a/R290 (60/40 by wt. %) was higher than that of R134a
by 10% and 35.8 % ,at -5 ÂșC and 5 ÂșC evaporating temperatures, respectively. The percentage increase in R. E.
for R600a/R290 (60/40 by wt. %) was 13.7% and 7.7% than that of R600a/R290 (50/50 by wt. %), at -5 ÂșC and
5 ÂșC evaporating temperatures, respectively. The percentage increase in R. E. for R600a/R290 (60/40 by wt.%)
was 65% and 21.3% than that of R600a/R290 (70/30 by wt.%), at -5 ÂșC and 5 ÂșC evaporating temperatures,
respectively. Refrigerating effect was found to be higher for R134a at lower evaporating temperature than that
of HCM 70/30 and 50/50, because mass flow rate of refrigerant is directly proposal to R. E. The nature of the
graphs was similar as reported by A. S. Dalkilic et al. [18].
0 10 20 30 40 50 60
-10
-5
0
5
10
15
20
CalorimeterTemperatureC
Time in Minute
R134a (M-250g)
R600a/R290 [70/30 by wt.%](M-125g)
R600a/R290 [60/40 by wt.%](M-125g)
R600a/R290 [50/50 by wt.%](M-125g)
Experimental Evaluation of Refrigerant Mixtures As Substitutes For Hfc134a
DOI: 10.9790/1684-1401057582 www.iosrjournals.org 79 | Page
Fig. 4 : Variations of refrigerating effect with respect to the evaporating temperature, at 30 ÂșC ambient
temperature.
3. Compressor energy consumption - Fig.5 shows the effect of evaporating temperatures on power
consumption for the refrigerants 250 g R134, 125 g R600a/R290 (70/30 by wt.%), 125 g R600a/R290 (60/40 by
wt.%) and 125 g R600a/R290 (50/50 by wt.%), at the capillary length of 10 feet. It was observed that the power
consumption was maximum for the R134a due to its higher mass flow rate. Power consumption was minimum
for the mixture R600a/R290 (70 / 30 wt. %) due to the lower mass percentage of R290 in HCM. It was evident
that the energy consumption by the compressor increased slightly with change in the evaporating temperature.
Energy consumption by the system with refrigerants R134a and R600a/R290 (50/50 by wt %) were higher than
that of R600a/R290 (60/40 by wt.%) by 39.2% and 43.3%, and 7.14% and 9.16%, respectively at -5 ÂșCand 5 ÂșC
evaporating temperatures. It is due to the fact that with increase in propane mass fraction, refrigerant mass flow
rate increases. The mass flow rate is directly proportional to the compressor work.
Fig. 5: Variations of energy consumption with respect to the evaporating temperature, at 30ÂșC ambient
temperature.
-5.0 -2.5 0.0 2.5 5.0
50
75
100
125
150
175
200
225
250
275
RefrigeratingEffect(W)
Evaporating Temperature C
R134a (M-250g)
R600a/R290[70/30 by wt.%](M-125g)
R600a/R290[60/40 by wt.%](M-125g)
R600a/R290[50/50 by wt.%](M-125g)
-5.0 -2.5 0.0 2.5 5.0
80
100
120
140
160
180
200
CompressorWork(W)
Evaporating Temperature C
R134a (M-250g)
R600a/R290 [70/30 by wt.%](M-125g)
R600a/R290 [60/40 by wt.%](M-125g)
R600a/R290 [50/50 by wt.%](M-125g)
Experimental Evaluation of Refrigerant Mixtures As Substitutes For Hfc134a
DOI: 10.9790/1684-1401057582 www.iosrjournals.org 80 | Page
4. Coefficient of performance (COP) -Fig.6 shows the effect of evaporating temperature on the COP for the
refrigerants 250 g R134, 125 g R600a/R290 (70/30 by wt.%), 125 g R600a/R290 (60/40 by wt.%) and 125 g
R600a/R290 (50/50 by wt.%). It was evident that the COP increases considerably with the increase of
evaporating temperature except for R134. It was also observed that the COP was the highest for the refrigerant
R600a/R290 (60/40 by wt.%) than that of other refrigerants. It was also observed that the COP of R600/R290
(60/40 by wt %) mixture was higher than that of R134a by 53.1% and 72.3% at -5 ÂșC and 5 ÂșC evaporating
temperatures, respectively. The COP of HCM R600/R290 (60/40 by wt %) was higher than that of R600a/R290
(50/50 by wt. %) by 21.9% and 17.6% at -5 ÂșC and 5 ÂșC evaporating temperatures, respectively. The COP of
HCM R600/R290 (60/40 by wt. %) was higher than that of HCM R600a/R290 (70/30 by wt.) by 59.1% and
19.3% at -5 ÂșC and 5 ÂșC evaporating temperatures, respectively. It can be seen that the COP decreases as
propane mass fraction in HCM increases above 40%. The main reason behind this trend is the rate of change in
specific work, which is higher than that of cooling effect.
Fig. 6: Variations of coefficient of performance with respect to the evaporating temperature, at 30 ÂșC ambient
temperature.
5. Pressure ratio (P1/P2) - The desirable property of the refrigerant is that pressure should be low due to its
minimize leakages past the compressor piston. The pressure ratio was maximum for the refrigerant R134a and
was minimum for HCM R600a/R290 (70/30 by wt.%) at the capillary length of 10 feet. The pressure ratio for
R600a/R290 is minimum due to its lower mass flow rate.
Fig. 7: Variations of compressor pressure ratio P1/P2 (Discharge / Suction).
-5.0 -2.5 0.0 2.5 5.0
0.25
0.50
0.75
1.00
1.25
1.50
1.75
2.00
2.25
2.50
Coefficientofperformance(COP)
Evaporating Temperature C
R134a (M-250g)
R600a/R290 [70/30 by wt.%](M-125g)
R600a/R290 [60/40 by wt.%](M-125g)
R600a/R290 [50/50 by wt.%](M-125g)
-5.0 -2.5 0.0 2.5 5.0
4
5
6
7
8
9
10
11
12
PressureRatio(P1/P2)
Evaporative Temperature C
R134a (M-250g)
R600a/R290 [70/30 by wt.%](M-125g)
R600a/R290 [60/40 by wt.%](M-125g)
R600a/R290 [50/50 by wt.%](M-125g)
Experimental Evaluation of Refrigerant Mixtures As Substitutes For Hfc134a
DOI: 10.9790/1684-1401057582 www.iosrjournals.org 81 | Page
6. Compressor Discharge Temperature - Compressor Discharge Temperature always be higher for HFC134a
refrigerant but you can see in graphs the value of discharge temperature was quit low for HCM because lower
mass of refrigerants as well as better cooling tendency and lower vapor pressure of R600a in HCM than other
tested refrigerants. This is also give advantage for consumption of lubricating oil also low for HCM.
Fig. 8 : Variations of compressor discharge temperature with respect to the evaporating temperatures.
VI. Conclusion
The lowest temperature in calorimeter was measured to be -5.8 ÂșC for the refrigerant of 125 g of
R600a/R290 (50/50 by wt %) and the second lowest temperature was obtained to be -5.2 ÂșC for 125 g of
R600a/R290 (60/40 by wt. %). R.E. of HCM refrigerant R600a/R290 (60/40 by wt. %) was increased by 10%
and 35.8% than that of R134a, at -5 ÂșC and 5 ÂșC evaporating temperatures, respectively. Percentage increase in
R.E. for R600a/R290 (60/40 by wt. %) was 13.7% and 7.7% than that of R600a/R290 (50/50 by wt. %), at -5 ÂșC
and 5 ÂșC evaporating temperatures, respectively. Power consumption was maximum for R134a due to its higher
mass flow rate. Power consumption was minimum for the mixture R600a/R290 (70/30 by wt. %) due to the
lower mass percentage of R290 present in that. Energy consumption for the refrigerants R134a and R600a/R290
(50/50 by wt. %) was higher than that of R600a/R290 (60/40 by wt. %) by 39.2% and 43.3%, and 7.14% and
9.16%, respectively at -5 ÂșC and 5 ÂșC evaporating temperatures. COP of HCM R600/R290 (60/40 by wt. %) was
higher than that of R134a by 53.1% and 72.3% at -5 ÂșC and 5 ÂșC evaporating temperatures, respectively. COP of
HCM R600/R290 (60/40 by wt. %) mixture was higher than that of R600a/R290 (50/50 by wt. %) by 21.9% and
17.6% at -5 ÂșC and 5 ÂșC evaporating temperatures, respectively. COP decreased as propane mass fraction in
HCM increased above 40%. The pressure ratio was the maximum for the refrigerant R134a and was in
minimum for HCM R600a/R290 (70/30 by wt. %) at the capillary length of 10 feet.
References
[1]. Roy J. Dossat, Principles of refrigeration, 4th
edition. Pearson education (Singapore) Pte. Ltd.,2003, New Delhi.
Manohar Prasad, Refrigeration and air conditioning, 2nd
edition. New Age International publishers, 2010, New Delhi.
[2]. E. Halimic, D. Ross, B. Agnew, A. Anderson, and I. Potts, A comparison of the operating performance of alternative
refrigerants. Applied Thermal Engineering 23 (12) (2003), 1441-1451.
[3]. M. Mohanraj. S. Jayaraj, C. Muraleedharan, Environment friendly alternatives to halogenated refrigerants- a review, Int. Journal
Greenhouse Gas Control 3 (2009), 108-119.
[4]. M. Mohanraj. C. Muraleedharan, S Jayaraj, A review on recent developments in new refrigerant mixtures for vapor compression
based refrigeration air conditioning and heat pump units Int. J Energy. Res 35 (8) (2011), 647-669.
[5]. Kyoto protocol, United Nations Framework Convention on Climate Change, United Nations, New York, USA, 1997.
[6]. Dr. S. Forbes Pearson, “New, Natural and Alternative Refrigerants”, Star refrigeration Limited, 2013 Edinburgh.
[7]. D. Jung, Chong-Bo Kim, Kilhong Song, Byoungjin Park, Testing of propane / iso-butane mixture in domestic refrigerators,
International Journal of Refrigeration, 23 (2000), 517-527.
[8]. Y.S. Lee, C. C. Su, Experimental studies of iso-butane (R600a) as the refrigerant in domestic refrigeration system. Applied Thermal
Engineering 22 (2002), 507-519.
[9]. B. Tashtoush, Tahat, M., Shudeifat, M.A, Experimental study of new refrigerants mixture to replace R12 in domestic refrigerators,
Applied Thermal Engineering 22 (2002), 495-506.
-5.0 -2.5 0.0 2.5 5.0
30
35
40
45
50
55
60
65
70
CompressorDischargeTemperatureC
Evaporating Temperature C
R134a (M-250g)
R600a/R290 [70/30 by wt.%](M-125g)
R600a/R290 [60/40 by wt.%](M-125g)
R600a/R290 [50/50 by wt.%](M-125g)
Experimental Evaluation of Refrigerant Mixtures As Substitutes For Hfc134a
DOI: 10.9790/1684-1401057582 www.iosrjournals.org 82 | Page
[10]. S. J. Sekhar, D. Mohan Lal, and S. Renganarayanan, Improved energy efficiency for CFC domestic refrigerators retrofitted with
ozone-friendly HFC134a/HC refrigerant mixture, International Journal of Thermal Sciences, 43 (3) (2004), 307-314.
[11]. M. Fatouh, M. kafafy, Experimental evaluation of a domestic refrigerator working with LPG, Applied Thermal Engineering 26
(2006), 1593 -1603.
[12]. K. Senthil Kumar, K. Rajagopal, Computational and experimental investigation of low ODP and low GWP HCFC-123 and HC-290
refrigerant mixture alternate to CFC-12, Energy Conversion and Management 48 (2007),3053-3062.
[13]. M. Mohanraj, S. Jayaraj and C. Muraleedharan, Improved energy efficiency for HFC 134a domestic refrigerator retrofitted with
hydrocarbon mixture (HC 290 / HC 600a) as drop-in substitute, Energy for Sustainable Development 11,4 (2007), 29 – 33.
[14]. K. Mani, V. Selladurai, Experimental analysis of a new refrigerant mixture as drop in replacement for CFC12 and HFC 134a,
International Journal of Thermal Sciences 47 (2008), 1490-1495.
[15]. M. Fatouh, M Kafary, Assessment of propane/commercial butane mixtures as possible alternatives to R134a in domestic
refrigerators, Energy Conservation and Management 47 (2006), 2644-2658.
[16]. Chao-Chieh Yu, Tun-Ping Teng, Retrofit assessment of using hydrocarbon refrigerants, Applied Thermal Engineering 66 (2014),
507- 518.
[17]. S. Dalkilic, S. Wongwises, A performance comparison of Vapor-compression refrigeration system using various alternative
refrigerants, International Communications in Heat and Mass Transfer, 37(9),(2010) pp.1340-1349

More Related Content

What's hot

IJREI_Thermodynamic study of R134a in Vapour Compression Refrigeration System...
IJREI_Thermodynamic study of R134a in Vapour Compression Refrigeration System...IJREI_Thermodynamic study of R134a in Vapour Compression Refrigeration System...
IJREI_Thermodynamic study of R134a in Vapour Compression Refrigeration System...Husain Mehdi
 
F0343042051
F0343042051F0343042051
F0343042051ijceronline
 
Styrene methods 2520of-2520-production
Styrene methods 2520of-2520-productionStyrene methods 2520of-2520-production
Styrene methods 2520of-2520-productionkioaudi
 
Influence of Operating Variables on Functional Parameters of Ammonia Synthesi...
Influence of Operating Variables on Functional Parameters of Ammonia Synthesi...Influence of Operating Variables on Functional Parameters of Ammonia Synthesi...
Influence of Operating Variables on Functional Parameters of Ammonia Synthesi...Premier Publishers
 
Optimizing Bunsen burner Performance Using CFD Analysis
Optimizing Bunsen burner Performance Using CFD AnalysisOptimizing Bunsen burner Performance Using CFD Analysis
Optimizing Bunsen burner Performance Using CFD AnalysisIJMER
 
Pyroligneous Liquor Produced at Different Heating Rates in Pyrolysis of Eucal...
Pyroligneous Liquor Produced at Different Heating Rates in Pyrolysis of Eucal...Pyroligneous Liquor Produced at Different Heating Rates in Pyrolysis of Eucal...
Pyroligneous Liquor Produced at Different Heating Rates in Pyrolysis of Eucal...CrimsonpublishersMCDA
 
ChE184b Final Design
ChE184b Final DesignChE184b Final Design
ChE184b Final DesignRussell Wong
 
CHARACTERIZATION AND EMISSION ANALYSIS OF PREMIXED AND PREHEATED POROUS RADIA...
CHARACTERIZATION AND EMISSION ANALYSIS OF PREMIXED AND PREHEATED POROUS RADIA...CHARACTERIZATION AND EMISSION ANALYSIS OF PREMIXED AND PREHEATED POROUS RADIA...
CHARACTERIZATION AND EMISSION ANALYSIS OF PREMIXED AND PREHEATED POROUS RADIA...BIBHUTI BHUSAN SAMANTARAY
 
1 s2.0-s1359431114008047-main
1 s2.0-s1359431114008047-main1 s2.0-s1359431114008047-main
1 s2.0-s1359431114008047-mainCarlos Alberto Bravo
 
The understanding of gas geochemical model to reduce the exploration uncertainty
The understanding of gas geochemical model to reduce the exploration uncertaintyThe understanding of gas geochemical model to reduce the exploration uncertainty
The understanding of gas geochemical model to reduce the exploration uncertaintyRizal Abiyudo
 
EXPERIMENTAL INVESTIGATION ON THERMAL PERFORMANCE OF POROUS RADIANT BURNER AN...
EXPERIMENTAL INVESTIGATION ON THERMAL PERFORMANCE OF POROUS RADIANT BURNER AN...EXPERIMENTAL INVESTIGATION ON THERMAL PERFORMANCE OF POROUS RADIANT BURNER AN...
EXPERIMENTAL INVESTIGATION ON THERMAL PERFORMANCE OF POROUS RADIANT BURNER AN...BIBHUTI BHUSAN SAMANTARAY
 
Ei4301816822
Ei4301816822Ei4301816822
Ei4301816822IJERA Editor
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Improving the Cooling Performance of Automobile Radiator with Ethylene Glycol...
Improving the Cooling Performance of Automobile Radiator with Ethylene Glycol...Improving the Cooling Performance of Automobile Radiator with Ethylene Glycol...
Improving the Cooling Performance of Automobile Radiator with Ethylene Glycol...IRJET Journal
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)ijceronline
 
HEAT TRANSFERCHARACTERISTICS OF A SELF ASPIRATING POROUS RADIANT BURNER FUELE...
HEAT TRANSFERCHARACTERISTICS OF A SELF ASPIRATING POROUS RADIANT BURNER FUELE...HEAT TRANSFERCHARACTERISTICS OF A SELF ASPIRATING POROUS RADIANT BURNER FUELE...
HEAT TRANSFERCHARACTERISTICS OF A SELF ASPIRATING POROUS RADIANT BURNER FUELE...BIBHUTI BHUSAN SAMANTARAY
 

What's hot (20)

IJREI_Thermodynamic study of R134a in Vapour Compression Refrigeration System...
IJREI_Thermodynamic study of R134a in Vapour Compression Refrigeration System...IJREI_Thermodynamic study of R134a in Vapour Compression Refrigeration System...
IJREI_Thermodynamic study of R134a in Vapour Compression Refrigeration System...
 
F0343042051
F0343042051F0343042051
F0343042051
 
Styrene methods 2520of-2520-production
Styrene methods 2520of-2520-productionStyrene methods 2520of-2520-production
Styrene methods 2520of-2520-production
 
Influence of Operating Variables on Functional Parameters of Ammonia Synthesi...
Influence of Operating Variables on Functional Parameters of Ammonia Synthesi...Influence of Operating Variables on Functional Parameters of Ammonia Synthesi...
Influence of Operating Variables on Functional Parameters of Ammonia Synthesi...
 
Optimizing Bunsen burner Performance Using CFD Analysis
Optimizing Bunsen burner Performance Using CFD AnalysisOptimizing Bunsen burner Performance Using CFD Analysis
Optimizing Bunsen burner Performance Using CFD Analysis
 
Group 7
Group 7Group 7
Group 7
 
Pyroligneous Liquor Produced at Different Heating Rates in Pyrolysis of Eucal...
Pyroligneous Liquor Produced at Different Heating Rates in Pyrolysis of Eucal...Pyroligneous Liquor Produced at Different Heating Rates in Pyrolysis of Eucal...
Pyroligneous Liquor Produced at Different Heating Rates in Pyrolysis of Eucal...
 
ChE184b Final Design
ChE184b Final DesignChE184b Final Design
ChE184b Final Design
 
XSEDE15_Poster_Competition
XSEDE15_Poster_CompetitionXSEDE15_Poster_Competition
XSEDE15_Poster_Competition
 
CHARACTERIZATION AND EMISSION ANALYSIS OF PREMIXED AND PREHEATED POROUS RADIA...
CHARACTERIZATION AND EMISSION ANALYSIS OF PREMIXED AND PREHEATED POROUS RADIA...CHARACTERIZATION AND EMISSION ANALYSIS OF PREMIXED AND PREHEATED POROUS RADIA...
CHARACTERIZATION AND EMISSION ANALYSIS OF PREMIXED AND PREHEATED POROUS RADIA...
 
1 s2.0-s1359431114008047-main
1 s2.0-s1359431114008047-main1 s2.0-s1359431114008047-main
1 s2.0-s1359431114008047-main
 
The understanding of gas geochemical model to reduce the exploration uncertainty
The understanding of gas geochemical model to reduce the exploration uncertaintyThe understanding of gas geochemical model to reduce the exploration uncertainty
The understanding of gas geochemical model to reduce the exploration uncertainty
 
EXPERIMENTAL INVESTIGATION ON THERMAL PERFORMANCE OF POROUS RADIANT BURNER AN...
EXPERIMENTAL INVESTIGATION ON THERMAL PERFORMANCE OF POROUS RADIANT BURNER AN...EXPERIMENTAL INVESTIGATION ON THERMAL PERFORMANCE OF POROUS RADIANT BURNER AN...
EXPERIMENTAL INVESTIGATION ON THERMAL PERFORMANCE OF POROUS RADIANT BURNER AN...
 
COW DUNG
COW DUNGCOW DUNG
COW DUNG
 
Ei4301816822
Ei4301816822Ei4301816822
Ei4301816822
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
Improving the Cooling Performance of Automobile Radiator with Ethylene Glycol...
Improving the Cooling Performance of Automobile Radiator with Ethylene Glycol...Improving the Cooling Performance of Automobile Radiator with Ethylene Glycol...
Improving the Cooling Performance of Automobile Radiator with Ethylene Glycol...
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)
 
HEAT TRANSFERCHARACTERISTICS OF A SELF ASPIRATING POROUS RADIANT BURNER FUELE...
HEAT TRANSFERCHARACTERISTICS OF A SELF ASPIRATING POROUS RADIANT BURNER FUELE...HEAT TRANSFERCHARACTERISTICS OF A SELF ASPIRATING POROUS RADIANT BURNER FUELE...
HEAT TRANSFERCHARACTERISTICS OF A SELF ASPIRATING POROUS RADIANT BURNER FUELE...
 
16 4 boston_04-72_0079
16 4 boston_04-72_007916 4 boston_04-72_0079
16 4 boston_04-72_0079
 

Similar to Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a

Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...theijes
 
Performance Comparison of Hydrocarbon Refrigerant as Isobutane R600a and Prop...
Performance Comparison of Hydrocarbon Refrigerant as Isobutane R600a and Prop...Performance Comparison of Hydrocarbon Refrigerant as Isobutane R600a and Prop...
Performance Comparison of Hydrocarbon Refrigerant as Isobutane R600a and Prop...journal ijrtem
 
Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...
Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...
Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...IRJET Journal
 
EXPERIMENTAL STUDY ON A DOMESTIC REFRIGERATOR USING LPG AS A REFRIGARANT
EXPERIMENTAL STUDY ON A DOMESTIC REFRIGERATOR USING LPG AS A REFRIGARANTEXPERIMENTAL STUDY ON A DOMESTIC REFRIGERATOR USING LPG AS A REFRIGARANT
EXPERIMENTAL STUDY ON A DOMESTIC REFRIGERATOR USING LPG AS A REFRIGARANTIAEME Publication
 
IRJET- R134a Refrigerant in Vapour Compression Cycle: A Review Paper
IRJET-  	  R134a Refrigerant in Vapour Compression Cycle: A Review PaperIRJET-  	  R134a Refrigerant in Vapour Compression Cycle: A Review Paper
IRJET- R134a Refrigerant in Vapour Compression Cycle: A Review PaperIRJET Journal
 
Energies 14-00946-v2
Energies 14-00946-v2Energies 14-00946-v2
Energies 14-00946-v2JayakumarA11
 
peer reviewed journals.pdf
peer reviewed journals.pdfpeer reviewed journals.pdf
peer reviewed journals.pdfnareshkotra
 
Catalyst Screening- Single Process Furfural Decarbonylation and Hydrogenation
Catalyst Screening- Single Process Furfural Decarbonylation and HydrogenationCatalyst Screening- Single Process Furfural Decarbonylation and Hydrogenation
Catalyst Screening- Single Process Furfural Decarbonylation and HydrogenationTrent Simonetti
 
Experimental Study of R134a, R406A and R600a Blends as Alternative To Freon 12
Experimental Study of R134a, R406A and R600a Blends as Alternative To Freon 12Experimental Study of R134a, R406A and R600a Blends as Alternative To Freon 12
Experimental Study of R134a, R406A and R600a Blends as Alternative To Freon 12IOSR Journals
 
Performance Comparison of VCRS using Different Refrigerants
Performance Comparison of VCRS using Different RefrigerantsPerformance Comparison of VCRS using Different Refrigerants
Performance Comparison of VCRS using Different Refrigerantsdbpublications
 
IRJET- Comparison of COP of R134A with Hydrocarbons by using VCR Cycle
IRJET- Comparison of COP of R134A with Hydrocarbons by using VCR CycleIRJET- Comparison of COP of R134A with Hydrocarbons by using VCR Cycle
IRJET- Comparison of COP of R134A with Hydrocarbons by using VCR CycleIRJET Journal
 
Experimental Investigation on Adsorption Capacity of a Variety of Activated C...
Experimental Investigation on Adsorption Capacity of a Variety of Activated C...Experimental Investigation on Adsorption Capacity of a Variety of Activated C...
Experimental Investigation on Adsorption Capacity of a Variety of Activated C...IJERA Editor
 
Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...
Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...
Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...inventy
 
IRJET- Performance Analysis of R-134a with ECO Friendly Refrigerant in Va...
IRJET-  	  Performance Analysis of R-134a with ECO Friendly Refrigerant in Va...IRJET-  	  Performance Analysis of R-134a with ECO Friendly Refrigerant in Va...
IRJET- Performance Analysis of R-134a with ECO Friendly Refrigerant in Va...IRJET Journal
 
The use of Cooking Gas as Refrigerant in a Domestic Refrigerator
The use of Cooking Gas as Refrigerant in a Domestic RefrigeratorThe use of Cooking Gas as Refrigerant in a Domestic Refrigerator
The use of Cooking Gas as Refrigerant in a Domestic RefrigeratorIJERA Editor
 
Tesfaye and Patel RP Mater. Proc..pdf
Tesfaye and Patel RP Mater. Proc..pdfTesfaye and Patel RP Mater. Proc..pdf
Tesfaye and Patel RP Mater. Proc..pdfMahaboobPatel2
 

Similar to Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a (20)

Q01245139144
Q01245139144Q01245139144
Q01245139144
 
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...
 
Performance Comparison of Hydrocarbon Refrigerant as Isobutane R600a and Prop...
Performance Comparison of Hydrocarbon Refrigerant as Isobutane R600a and Prop...Performance Comparison of Hydrocarbon Refrigerant as Isobutane R600a and Prop...
Performance Comparison of Hydrocarbon Refrigerant as Isobutane R600a and Prop...
 
Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...
Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...
Performance Evaluation of Domestic Refrigerator Using Eco-Friendly Refrigeran...
 
EXPERIMENTAL STUDY ON A DOMESTIC REFRIGERATOR USING LPG AS A REFRIGARANT
EXPERIMENTAL STUDY ON A DOMESTIC REFRIGERATOR USING LPG AS A REFRIGARANTEXPERIMENTAL STUDY ON A DOMESTIC REFRIGERATOR USING LPG AS A REFRIGARANT
EXPERIMENTAL STUDY ON A DOMESTIC REFRIGERATOR USING LPG AS A REFRIGARANT
 
IRJET- R134a Refrigerant in Vapour Compression Cycle: A Review Paper
IRJET-  	  R134a Refrigerant in Vapour Compression Cycle: A Review PaperIRJET-  	  R134a Refrigerant in Vapour Compression Cycle: A Review Paper
IRJET- R134a Refrigerant in Vapour Compression Cycle: A Review Paper
 
Energies 14-00946-v2
Energies 14-00946-v2Energies 14-00946-v2
Energies 14-00946-v2
 
I1303056370
I1303056370I1303056370
I1303056370
 
peer reviewed journals.pdf
peer reviewed journals.pdfpeer reviewed journals.pdf
peer reviewed journals.pdf
 
Aq26268271
Aq26268271Aq26268271
Aq26268271
 
Catalyst Screening- Single Process Furfural Decarbonylation and Hydrogenation
Catalyst Screening- Single Process Furfural Decarbonylation and HydrogenationCatalyst Screening- Single Process Furfural Decarbonylation and Hydrogenation
Catalyst Screening- Single Process Furfural Decarbonylation and Hydrogenation
 
Experimental Study of R134a, R406A and R600a Blends as Alternative To Freon 12
Experimental Study of R134a, R406A and R600a Blends as Alternative To Freon 12Experimental Study of R134a, R406A and R600a Blends as Alternative To Freon 12
Experimental Study of R134a, R406A and R600a Blends as Alternative To Freon 12
 
Performance Comparison of VCRS using Different Refrigerants
Performance Comparison of VCRS using Different RefrigerantsPerformance Comparison of VCRS using Different Refrigerants
Performance Comparison of VCRS using Different Refrigerants
 
IRJET- Comparison of COP of R134A with Hydrocarbons by using VCR Cycle
IRJET- Comparison of COP of R134A with Hydrocarbons by using VCR CycleIRJET- Comparison of COP of R134A with Hydrocarbons by using VCR Cycle
IRJET- Comparison of COP of R134A with Hydrocarbons by using VCR Cycle
 
Experimental Investigation on Adsorption Capacity of a Variety of Activated C...
Experimental Investigation on Adsorption Capacity of a Variety of Activated C...Experimental Investigation on Adsorption Capacity of a Variety of Activated C...
Experimental Investigation on Adsorption Capacity of a Variety of Activated C...
 
Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...
Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...
Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...
 
IRJET- Performance Analysis of R-134a with ECO Friendly Refrigerant in Va...
IRJET-  	  Performance Analysis of R-134a with ECO Friendly Refrigerant in Va...IRJET-  	  Performance Analysis of R-134a with ECO Friendly Refrigerant in Va...
IRJET- Performance Analysis of R-134a with ECO Friendly Refrigerant in Va...
 
Thermodynamic analysis of_actual_vapour_compression_system_with_r22_and_its_e...
Thermodynamic analysis of_actual_vapour_compression_system_with_r22_and_its_e...Thermodynamic analysis of_actual_vapour_compression_system_with_r22_and_its_e...
Thermodynamic analysis of_actual_vapour_compression_system_with_r22_and_its_e...
 
The use of Cooking Gas as Refrigerant in a Domestic Refrigerator
The use of Cooking Gas as Refrigerant in a Domestic RefrigeratorThe use of Cooking Gas as Refrigerant in a Domestic Refrigerator
The use of Cooking Gas as Refrigerant in a Domestic Refrigerator
 
Tesfaye and Patel RP Mater. Proc..pdf
Tesfaye and Patel RP Mater. Proc..pdfTesfaye and Patel RP Mater. Proc..pdf
Tesfaye and Patel RP Mater. Proc..pdf
 

More from IOSRJMCE

Axial Capacity Enhancement of CFRP Confined Columns Made of Steel Fiber Reinf...
Axial Capacity Enhancement of CFRP Confined Columns Made of Steel Fiber Reinf...Axial Capacity Enhancement of CFRP Confined Columns Made of Steel Fiber Reinf...
Axial Capacity Enhancement of CFRP Confined Columns Made of Steel Fiber Reinf...IOSRJMCE
 
Smart Response Surface Models using Legacy Data for Multidisciplinary Optimiz...
Smart Response Surface Models using Legacy Data for Multidisciplinary Optimiz...Smart Response Surface Models using Legacy Data for Multidisciplinary Optimiz...
Smart Response Surface Models using Legacy Data for Multidisciplinary Optimiz...IOSRJMCE
 
Experimental and Numerical Modal Analysis of a Compressor Mounting Bracket
Experimental and Numerical Modal Analysis of a Compressor Mounting BracketExperimental and Numerical Modal Analysis of a Compressor Mounting Bracket
Experimental and Numerical Modal Analysis of a Compressor Mounting BracketIOSRJMCE
 
Analysis and Design Aspects of Support Measures of Main Caverns of Karuma Hyd...
Analysis and Design Aspects of Support Measures of Main Caverns of Karuma Hyd...Analysis and Design Aspects of Support Measures of Main Caverns of Karuma Hyd...
Analysis and Design Aspects of Support Measures of Main Caverns of Karuma Hyd...IOSRJMCE
 
A Review: Effect of Laser Peening Treatment on Properties And Life Cycle of D...
A Review: Effect of Laser Peening Treatment on Properties And Life Cycle of D...A Review: Effect of Laser Peening Treatment on Properties And Life Cycle of D...
A Review: Effect of Laser Peening Treatment on Properties And Life Cycle of D...IOSRJMCE
 
Simulation and Analysis of Electrolyte Flow Pattern in ECM for L-Shaped Tool ...
Simulation and Analysis of Electrolyte Flow Pattern in ECM for L-Shaped Tool ...Simulation and Analysis of Electrolyte Flow Pattern in ECM for L-Shaped Tool ...
Simulation and Analysis of Electrolyte Flow Pattern in ECM for L-Shaped Tool ...IOSRJMCE
 
Study on Transverse Displacement in Composite Laminated Plates across Thickne...
Study on Transverse Displacement in Composite Laminated Plates across Thickne...Study on Transverse Displacement in Composite Laminated Plates across Thickne...
Study on Transverse Displacement in Composite Laminated Plates across Thickne...IOSRJMCE
 
Study of Forced Convection Heat Transfer with Single phase and mixture phase ...
Study of Forced Convection Heat Transfer with Single phase and mixture phase ...Study of Forced Convection Heat Transfer with Single phase and mixture phase ...
Study of Forced Convection Heat Transfer with Single phase and mixture phase ...IOSRJMCE
 
Eigenvalue Buckling Computation and Impact on Pipeline Wall Thickness and Sub...
Eigenvalue Buckling Computation and Impact on Pipeline Wall Thickness and Sub...Eigenvalue Buckling Computation and Impact on Pipeline Wall Thickness and Sub...
Eigenvalue Buckling Computation and Impact on Pipeline Wall Thickness and Sub...IOSRJMCE
 
Mechanical Analysis of an Ixtle Based Cable for Its Use in Architecture
Mechanical Analysis of an Ixtle Based Cable for Its Use in ArchitectureMechanical Analysis of an Ixtle Based Cable for Its Use in Architecture
Mechanical Analysis of an Ixtle Based Cable for Its Use in ArchitectureIOSRJMCE
 
Application of Artificial Neural Networking for Determining the Plane of Vibr...
Application of Artificial Neural Networking for Determining the Plane of Vibr...Application of Artificial Neural Networking for Determining the Plane of Vibr...
Application of Artificial Neural Networking for Determining the Plane of Vibr...IOSRJMCE
 
Effect of Stiffening System on Building Resistance to Earthquake Forces
Effect of Stiffening System on Building Resistance to Earthquake ForcesEffect of Stiffening System on Building Resistance to Earthquake Forces
Effect of Stiffening System on Building Resistance to Earthquake ForcesIOSRJMCE
 
Resource Optimization of Construction Project Using Primavera P6
Resource Optimization of Construction Project Using Primavera P6Resource Optimization of Construction Project Using Primavera P6
Resource Optimization of Construction Project Using Primavera P6IOSRJMCE
 
Optimization of Electrical Discharge Machining Process Parameters using SCM42...
Optimization of Electrical Discharge Machining Process Parameters using SCM42...Optimization of Electrical Discharge Machining Process Parameters using SCM42...
Optimization of Electrical Discharge Machining Process Parameters using SCM42...IOSRJMCE
 
Efficient Mass Participation Ratio of Building with Basement
Efficient Mass Participation Ratio of Building with BasementEfficient Mass Participation Ratio of Building with Basement
Efficient Mass Participation Ratio of Building with BasementIOSRJMCE
 
Literature Review of Experimental Study on Load Bearing Masonry Wall
Literature Review of Experimental Study on Load Bearing Masonry WallLiterature Review of Experimental Study on Load Bearing Masonry Wall
Literature Review of Experimental Study on Load Bearing Masonry WallIOSRJMCE
 
Structural Design of Concrete Structure Using E-Tabs
Structural Design of Concrete Structure Using E-TabsStructural Design of Concrete Structure Using E-Tabs
Structural Design of Concrete Structure Using E-TabsIOSRJMCE
 
Finite Element Analysis of Opening Plate, Fixed Tube Sheet and Floating Sheet...
Finite Element Analysis of Opening Plate, Fixed Tube Sheet and Floating Sheet...Finite Element Analysis of Opening Plate, Fixed Tube Sheet and Floating Sheet...
Finite Element Analysis of Opening Plate, Fixed Tube Sheet and Floating Sheet...IOSRJMCE
 
Influence of Combine Vertical Irregularities in the Response of Earthquake Re...
Influence of Combine Vertical Irregularities in the Response of Earthquake Re...Influence of Combine Vertical Irregularities in the Response of Earthquake Re...
Influence of Combine Vertical Irregularities in the Response of Earthquake Re...IOSRJMCE
 
Straight Bevel Gears Manufacturing Analysis by Conventional Powder Metallurgy...
Straight Bevel Gears Manufacturing Analysis by Conventional Powder Metallurgy...Straight Bevel Gears Manufacturing Analysis by Conventional Powder Metallurgy...
Straight Bevel Gears Manufacturing Analysis by Conventional Powder Metallurgy...IOSRJMCE
 

More from IOSRJMCE (20)

Axial Capacity Enhancement of CFRP Confined Columns Made of Steel Fiber Reinf...
Axial Capacity Enhancement of CFRP Confined Columns Made of Steel Fiber Reinf...Axial Capacity Enhancement of CFRP Confined Columns Made of Steel Fiber Reinf...
Axial Capacity Enhancement of CFRP Confined Columns Made of Steel Fiber Reinf...
 
Smart Response Surface Models using Legacy Data for Multidisciplinary Optimiz...
Smart Response Surface Models using Legacy Data for Multidisciplinary Optimiz...Smart Response Surface Models using Legacy Data for Multidisciplinary Optimiz...
Smart Response Surface Models using Legacy Data for Multidisciplinary Optimiz...
 
Experimental and Numerical Modal Analysis of a Compressor Mounting Bracket
Experimental and Numerical Modal Analysis of a Compressor Mounting BracketExperimental and Numerical Modal Analysis of a Compressor Mounting Bracket
Experimental and Numerical Modal Analysis of a Compressor Mounting Bracket
 
Analysis and Design Aspects of Support Measures of Main Caverns of Karuma Hyd...
Analysis and Design Aspects of Support Measures of Main Caverns of Karuma Hyd...Analysis and Design Aspects of Support Measures of Main Caverns of Karuma Hyd...
Analysis and Design Aspects of Support Measures of Main Caverns of Karuma Hyd...
 
A Review: Effect of Laser Peening Treatment on Properties And Life Cycle of D...
A Review: Effect of Laser Peening Treatment on Properties And Life Cycle of D...A Review: Effect of Laser Peening Treatment on Properties And Life Cycle of D...
A Review: Effect of Laser Peening Treatment on Properties And Life Cycle of D...
 
Simulation and Analysis of Electrolyte Flow Pattern in ECM for L-Shaped Tool ...
Simulation and Analysis of Electrolyte Flow Pattern in ECM for L-Shaped Tool ...Simulation and Analysis of Electrolyte Flow Pattern in ECM for L-Shaped Tool ...
Simulation and Analysis of Electrolyte Flow Pattern in ECM for L-Shaped Tool ...
 
Study on Transverse Displacement in Composite Laminated Plates across Thickne...
Study on Transverse Displacement in Composite Laminated Plates across Thickne...Study on Transverse Displacement in Composite Laminated Plates across Thickne...
Study on Transverse Displacement in Composite Laminated Plates across Thickne...
 
Study of Forced Convection Heat Transfer with Single phase and mixture phase ...
Study of Forced Convection Heat Transfer with Single phase and mixture phase ...Study of Forced Convection Heat Transfer with Single phase and mixture phase ...
Study of Forced Convection Heat Transfer with Single phase and mixture phase ...
 
Eigenvalue Buckling Computation and Impact on Pipeline Wall Thickness and Sub...
Eigenvalue Buckling Computation and Impact on Pipeline Wall Thickness and Sub...Eigenvalue Buckling Computation and Impact on Pipeline Wall Thickness and Sub...
Eigenvalue Buckling Computation and Impact on Pipeline Wall Thickness and Sub...
 
Mechanical Analysis of an Ixtle Based Cable for Its Use in Architecture
Mechanical Analysis of an Ixtle Based Cable for Its Use in ArchitectureMechanical Analysis of an Ixtle Based Cable for Its Use in Architecture
Mechanical Analysis of an Ixtle Based Cable for Its Use in Architecture
 
Application of Artificial Neural Networking for Determining the Plane of Vibr...
Application of Artificial Neural Networking for Determining the Plane of Vibr...Application of Artificial Neural Networking for Determining the Plane of Vibr...
Application of Artificial Neural Networking for Determining the Plane of Vibr...
 
Effect of Stiffening System on Building Resistance to Earthquake Forces
Effect of Stiffening System on Building Resistance to Earthquake ForcesEffect of Stiffening System on Building Resistance to Earthquake Forces
Effect of Stiffening System on Building Resistance to Earthquake Forces
 
Resource Optimization of Construction Project Using Primavera P6
Resource Optimization of Construction Project Using Primavera P6Resource Optimization of Construction Project Using Primavera P6
Resource Optimization of Construction Project Using Primavera P6
 
Optimization of Electrical Discharge Machining Process Parameters using SCM42...
Optimization of Electrical Discharge Machining Process Parameters using SCM42...Optimization of Electrical Discharge Machining Process Parameters using SCM42...
Optimization of Electrical Discharge Machining Process Parameters using SCM42...
 
Efficient Mass Participation Ratio of Building with Basement
Efficient Mass Participation Ratio of Building with BasementEfficient Mass Participation Ratio of Building with Basement
Efficient Mass Participation Ratio of Building with Basement
 
Literature Review of Experimental Study on Load Bearing Masonry Wall
Literature Review of Experimental Study on Load Bearing Masonry WallLiterature Review of Experimental Study on Load Bearing Masonry Wall
Literature Review of Experimental Study on Load Bearing Masonry Wall
 
Structural Design of Concrete Structure Using E-Tabs
Structural Design of Concrete Structure Using E-TabsStructural Design of Concrete Structure Using E-Tabs
Structural Design of Concrete Structure Using E-Tabs
 
Finite Element Analysis of Opening Plate, Fixed Tube Sheet and Floating Sheet...
Finite Element Analysis of Opening Plate, Fixed Tube Sheet and Floating Sheet...Finite Element Analysis of Opening Plate, Fixed Tube Sheet and Floating Sheet...
Finite Element Analysis of Opening Plate, Fixed Tube Sheet and Floating Sheet...
 
Influence of Combine Vertical Irregularities in the Response of Earthquake Re...
Influence of Combine Vertical Irregularities in the Response of Earthquake Re...Influence of Combine Vertical Irregularities in the Response of Earthquake Re...
Influence of Combine Vertical Irregularities in the Response of Earthquake Re...
 
Straight Bevel Gears Manufacturing Analysis by Conventional Powder Metallurgy...
Straight Bevel Gears Manufacturing Analysis by Conventional Powder Metallurgy...Straight Bevel Gears Manufacturing Analysis by Conventional Powder Metallurgy...
Straight Bevel Gears Manufacturing Analysis by Conventional Powder Metallurgy...
 

Recently uploaded

MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAbhinavSharma374939
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxhumanexperienceaaa
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 

Recently uploaded (20)

MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog Converter
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 

Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a

  • 1. IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-ISSN: 2278-1684,p-ISSN: 2320-334X, Volume 14, Issue 1 Ver. V (Jan. - Feb. 2017), PP 75-82 www.iosrjournals.org DOI: 10.9790/1684-1401057582 www.iosrjournals.org 75 | Page Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a Dr. Deepak Paliwal (Mechanical Engineering Department, S. V. Polytechnic College Bhopal, India) Abstract: Refrigerant R134a base systems has higher GWP value that's why the conversion of same into eco- friendly system is the major concern for refrigeration industry. This investigation focuses on mixture ratio of pure hydrocarbon R290 and R600a used in 200 liter domestic refrigeration system by certain changes in mass ratio of refrigerants. In the present work, first of all the effect of mass ratio of HCM refrigerants on the performance of the system was investigated. HCM of R600a/R290 (60/40 by wt. %) gave better performance than that of HCM R600a/R290 (70/30 by wt. %), R600a/R290 (50/50 by wt. %) and R134a. The mass ratio of HCM (R600a/ R290) refrigerants was optimized for the performance parameter with respect to evaporating temperature. The COP of R600a/R290 (60/40 by wt. %) mixture was higher than that of R600a/R290 (50/50 by wt. %) by 21.9% and 17.6% at -5 0 C and 5 0 C evaporative temperature respectively. COP decreased as propane mass fraction in HCM increased above 40%. Keywords: Refrigerant, R134a, Pull down, COP, R600a/R290, HCM. I. Introduction Refrigeration goes back to ancient times where storage of ice, evaporation of water, and other evaporative processes were prevailing. More specifically, refrigeration is that branch of science which deals with the process of decreasing and maintaining the temperature of any space or material below the temperature of the atmosphere[1]. According to ASHRAE, it is defined as the science of providing and maintaining temperature below that of surroundings [2]. For the past half century, CFCs have been used extensively in the refrigeration sector. (CFCs) and hydrochlorofluorocarbons (HCFCs) became the most dominant types of refrigerants due to their properties of non- corrosiveness, non-flammability, non-toxicity and non-irritability[3]. The problems occurred, when in 1974, Molina and Rowland, reported and published their ozone depletion hypothesis in which they claimed that the chlorine element catalytically destroyed the ozone layer in the stratosphere [4]. Since the advent of the Montreal Protocol, however, Refrigeration sector has been find out solution for ozone depleting substances. Alternative to CFCs refrigerants are HFC-152a, HFC-134a, MP66/39, HC-290/600a etc. These days, the concern for the greenhouse warming has never been greater. HFC-134a is non-flammable and has zero ozone depletion potential but serious GWP[5]. Thus, in 1997 the Kyoto Protocol was signed by many nations calling for the reduction in emissions of greenhouse gases including HFCs. There has been much resistance in adopting HFC134a for refrigeration equipment by some environmental groups. European countries are uses hydrocarbon in pure or mixed form on their refrigerator in early of 2000. Hydrocarbon refrigerants are flammable[6]. They have zero ozone depletion potential and a greenhouse warming potential approaching zero. Many researchers have reported performance evaluation of hydrocarbon mixtures by both experimental and simulation methods [1-5]. India and China are the largest refrigerator demanding countries in the world, have been quite active in the application of hydrocarbons in domestic refrigerators. The assessment of alternative refrigerants is a difficult task[7]. Several criteria must be considered while selecting alternative refrigerants. The experimental work carried out in this area is also extensive. Many drop-in tests are being carried out to check the performance of replacement refrigerant in existing machines, designed for CFCs, HFCs and HCFCs[8]. II. Literature survey Y. S. Lee et al.[9] did an experiment and tested Iso-butane in domestic refrigerator. The compressor input power varies from 230 and 300 W, while the refrigerant charged was about 150 g. It was found that the COP lie between 0.8 - 3.5 in freezing application. This study focused only on the performance of a VCR system with R600a as the alternative refrigerants. B. Tashtoush et al. [10] conducted an experiment with the aim to analyze hydrocarbons (R600/R290/R134a) at various quantities in R12 domestic refrigerator. The results shows that Butane/Propane/R134a mixtures provide excellent performance parameters, such as COP of refrigerators, compression power, volumetric efficiency, condenser duty, compressor discharge pressure and temperature, relative to a 210 g charge of R12. S. Joseph Shekhar et al. [11] had performed experimental analysis on a 165 liter, CFC-12 based domestic refrigerator retrofitted with eco-friendly refrigerant mixture of HFC134a / HC290 / HC600a without changing the mineral oil. The system had been running successfully for more than 12 months,
  • 2. Experimental Evaluation of Refrigerant Mixtures As Substitutes For Hfc134a DOI: 10.9790/1684-1401057582 www.iosrjournals.org 76 | Page thus it was observed that the new mixture was compatible with mineral oil. The improvement in theoretical analysis of COP and actual COP were found out from 3 to 12% and 3 to 8%, respectively. M. Fatouh et al. [12] had used LPG i.e. mixture of 60% propane and 40% commercial butane for drop-in replacement of HFC134a, in a single evaporator domestic refrigerator with a volume of 10 ft3 . Highest actual COP, lowest on-time ratio and lowered electric consumption were achieved in LPG refrigerator than that of R134a by 7.6%, 14.3% and 10.8%, respectively. Hence, it can be concluded that the proposed LPG shown to be an appropriate and long-term alternative refrigerant to replace R134a in the existing refrigerator. K.Senthil Kumar et al. [13] experimentally tested HC mixture (30%R290 & 70%R123) and computationally replacing R12 in this work, to overcome the above said problem, in a refrigerant mixture R290 has been identified as suitable for combination with R123. . It is observed that the difference of pressure and temperature characteristics disappears as the R290 mass fraction is increased from 10% to 30% with R123 and the curve almost matches the R12 curve, which symbolized that mixture 7/3 can exhibits similar properties and could be used as a substitute for CFC-12. M. Mohanraj et al. [14] studied that domestic refrigerator uses HFC134a as refrigerant, due to its excellent thermodynamics and thermal- physical properties. But, HFC134a has high global warming potential (GWP) of 1300. This paper presents experimental results of an energy-efficient hydrocarbons (HC) mixture consisting of 45% HC290 and 55% HC600a as a drop-in substitute for HFC134a as various mass charges of 40 g, 50 g, 70 g and 90 g in domestic refrigerators. The results practically showed that the 70 g mixture as barrier of COP, lower power consumption, lower pull-down time and lower discharging temperature than HFC134a. The miscibility of synthetic oil with HC refrigerant mixture was also found to be good. K. Mani et al. [15] done an experiment and analyzed that the performance study on a VCR system with the new refrigerant mixture R290/R600a as a drop-in replacement was with CFC-12 and HFC134a. Experimental results showed that the refrigerant effect of R290/R600a (68/32 by wt. %) mixture was higher than that of R12 in the range of 19.9% to 50.1% at the lower evaporating temperature and in the range of 21.2 to 28.5% at the higher evaporating temperatures, respectively. COP of R290/R600a mixture increased from 3.9% to 25.1% at lower evaporating temperatures than that of R12 and COP of R290/R600a mixture increased from 11.8% to 17.6% at higher evaporating temperatures to than that of R12. The refrigerant R134a showed slightly lower coefficient of performance than R12. The R290/R600a (68/32 by wt. %) mixture can be considered as a drop-in replacement refrigerant for CFC-12 and HFC134a refrigerants. III. Experimental setup An experimental set-up for vapor compression refrigeration system was designed to investigate the performance of R134a, R600a, R600a/R290 (70/30 by wt. %), R600a/R290 (60/40 by wt %) and R600a/R290 (50/50 by wt %) mixture refrigerants. Fig.1 shows actual view of the experimental set-up and Fig.2 shows line diagram. The system was a 200 liter domestic refrigerator ( with deep freezing capacity ) that was originally designed for 150g R134a mass of refrigerant. It consists of two loops, the main loop consist of a compressor, a condenser, a filter-drier, a expansion device and a calorimeter, and second loop consisted of a evaporator instead of calorimeter with all other main equipments. Hermetically sealed reciprocating compressor recommended for R134a refrigerant of 200 liter refrigerator (with deep freezing capacity) was used in the system. A force convection air - cooled condenser was used. Capillary tube of 10 feet length, and 0.036 inches diameter was used as expansion device in the system. Refrigerating effects of the system calculated by a calorimeter connected in the main loop. It consisted of a cooling coil of 25 feet length and 5/16 inches diameter, temperature measuring device, a electric heater by motor and a stirrer rotted for maintaining equal temperature in the calorimeter. All these devices were properly placed in a insulated plastic container having 10 liter ethylene glycol. The calorimeter was fitted with an electric heater and a dimmerstat (attached with wattmeter) to calculate R.E. (heat gain by heater will be equal to heat removed by evaporator coil). All these 9 thermocouples in the accuracy range of -50 ÂșC to 80 ÂșC with ± 0.1 ÂșC were fitted at inlet and outlet of all the major components. A drier was used after condenser to absorb moisture present in the refrigerant. In two pressure gauges, one is compound pressure gauge which is measured from -30 psi to 500 psi and one normal pressure gauge which is measured form -30 psi to 150 psi with ± 1 psi accuracy fitted at compressor discharge and suction side, respectively. Compressor power consumption was measured by a wattmeter with an accuracy of ± 0.5%. Energy consumption by the heating coils (inside calorimeter) was measured by a wattmeter with an accuracy of ± 0.5 %. Energy supply meter also used to calculate total energy consumption in KW/hr.
  • 3. Experimental Evaluation of Refrigerant Mixtures As Substitutes For Hfc134a DOI: 10.9790/1684-1401057582 www.iosrjournals.org 77 | Page Figure 1: Actual view of experimental set-up for VCR system. Figure 2: Line diagram of the experimental set-up for VCR system. IV. Experimental procedure The system was evacuated up to the negative pressure -20 psi to eliminate impurities, moisture and other foreign materials present inside the system by using vacuum pump, which might affect the accuracy of the experimental set-up. Then the refrigerator was charged in different mass fraction with the help of electronic weight m/c and charging valves. Initially we used 250g R134a refrigerant to calculate values for base line test. After that 125g HCM in different mass fractions we used to find out best refrigerant for the system. In all, measurements are taken when the system reached steady state condition (calorimeter temperature was maintained for 10 minutes at measured value temperature with the help of dimmerstat). Temperatures were recorded after every 10 minute interval in 0 C by 9 thermocouples, which are placed in all major equipments. Pressure at suction and discharge side of the compressor were also measured by two pressure gauges, after every 10 minute interval. To calculate pull down test system was cooled up from atmospheric temperature to desired temperature. R.E. at particular evaporating temperature was found by maintaining calorimeter, at that temperature with the help of heating device. In this process, wattmeter attached with calorimeter gave R.E. and wattmeter attached with compressor gave power consumption. The process was repeated for every refrigerants which were tested at all measured evaporating temperature.
  • 4. Experimental Evaluation of Refrigerant Mixtures As Substitutes For Hfc134a DOI: 10.9790/1684-1401057582 www.iosrjournals.org 78 | Page V. Result and Discussion Experimental results obtained from pull down test with respect to time in minutes and performance parameters such as refrigerant effect, energy consumption, COP etc. with respect to evaporating temperature were analyzed for 125 g HCM R600a/R290 (50/50 by wt%), R600a/R290 (60/40 by wt %), R600a/R290 (70/30 by wt. %) and compared these with 250 g R134a refrigerant to optimize mass ratio of the HCM refrigerant for the system. Experiments were conducted at ambient temperature of 30 ÂșC. 1. Pull down characteristics - Fig.3 shows the variation of calorimeter temperature with respect to time. The temperature of ethylene glycol (10 liter) was reduced from 20 ÂșC for a period of 60 minute (continuous running test). The tests were conducted for different lengths of the capillary and refrigerants. In the entire range of operation minimum temperature was obtained for HCM 50/50. It is due to the fact that with increase in propane mass fraction, refrigerant mass flow rate increases M. Fatouh et al. [16]. It was observed that of continuous running test for 60 minutes on VCR system, the lowest temperature in calorimeter was measured to be -5.8 ÂșC for refrigerant 125 g of R600a/R290 (50/50 by wt.%). The second lowest temperature was observed to be -5.2 ÂșC for 125 g of R600a/R290 (60/40 by wt. %). Calorimeter temperature of 250 g R134a was found to be - 4.5 ÂșC in 60 minutes continuous running test. Results indicated that the cooling rate increased with the increase of mass percentage of R290 in refrigerant mixtures due to higher cooling capacity of R290 than other refrigerants. The nature of the graphs is similar as reported by Chao-Chieh Yu et al. [17]. Fig. 3: Variations of calorimeter temperature with respect to the time (in minutes), at 30 ÂșC ambient temp. (Continuous Running Test). 2. Refrigerating effect -Fig. 4 shows the effect of evaporating temperatures on the R. E. for the refrigerants 250 g R134, 125 g R600a/R290 (70/30wt.%), 125 g R600a/R290 (60/40 by wt.%) and 125 g R600a/R290 (50/50 by wt.%), at the capillary length of 10 feet. It was observed that in the tested range of evaporating temperatures, the R .E. increases with the increase in evaporating temperatures and was found to be maximum for the 125 g R600a/R290 60/40. It is due to the fact that with increase in propane mass fraction refrigerant mass flow rate increases M. Fatouh et al. [16,38]. R. E. for HCM R600a/R290 (60/40 by wt. %) was higher than that of R134a by 10% and 35.8 % ,at -5 ÂșC and 5 ÂșC evaporating temperatures, respectively. The percentage increase in R. E. for R600a/R290 (60/40 by wt. %) was 13.7% and 7.7% than that of R600a/R290 (50/50 by wt. %), at -5 ÂșC and 5 ÂșC evaporating temperatures, respectively. The percentage increase in R. E. for R600a/R290 (60/40 by wt.%) was 65% and 21.3% than that of R600a/R290 (70/30 by wt.%), at -5 ÂșC and 5 ÂșC evaporating temperatures, respectively. Refrigerating effect was found to be higher for R134a at lower evaporating temperature than that of HCM 70/30 and 50/50, because mass flow rate of refrigerant is directly proposal to R. E. The nature of the graphs was similar as reported by A. S. Dalkilic et al. [18]. 0 10 20 30 40 50 60 -10 -5 0 5 10 15 20 CalorimeterTemperatureC Time in Minute R134a (M-250g) R600a/R290 [70/30 by wt.%](M-125g) R600a/R290 [60/40 by wt.%](M-125g) R600a/R290 [50/50 by wt.%](M-125g)
  • 5. Experimental Evaluation of Refrigerant Mixtures As Substitutes For Hfc134a DOI: 10.9790/1684-1401057582 www.iosrjournals.org 79 | Page Fig. 4 : Variations of refrigerating effect with respect to the evaporating temperature, at 30 ÂșC ambient temperature. 3. Compressor energy consumption - Fig.5 shows the effect of evaporating temperatures on power consumption for the refrigerants 250 g R134, 125 g R600a/R290 (70/30 by wt.%), 125 g R600a/R290 (60/40 by wt.%) and 125 g R600a/R290 (50/50 by wt.%), at the capillary length of 10 feet. It was observed that the power consumption was maximum for the R134a due to its higher mass flow rate. Power consumption was minimum for the mixture R600a/R290 (70 / 30 wt. %) due to the lower mass percentage of R290 in HCM. It was evident that the energy consumption by the compressor increased slightly with change in the evaporating temperature. Energy consumption by the system with refrigerants R134a and R600a/R290 (50/50 by wt %) were higher than that of R600a/R290 (60/40 by wt.%) by 39.2% and 43.3%, and 7.14% and 9.16%, respectively at -5 ÂșCand 5 ÂșC evaporating temperatures. It is due to the fact that with increase in propane mass fraction, refrigerant mass flow rate increases. The mass flow rate is directly proportional to the compressor work. Fig. 5: Variations of energy consumption with respect to the evaporating temperature, at 30ÂșC ambient temperature. -5.0 -2.5 0.0 2.5 5.0 50 75 100 125 150 175 200 225 250 275 RefrigeratingEffect(W) Evaporating Temperature C R134a (M-250g) R600a/R290[70/30 by wt.%](M-125g) R600a/R290[60/40 by wt.%](M-125g) R600a/R290[50/50 by wt.%](M-125g) -5.0 -2.5 0.0 2.5 5.0 80 100 120 140 160 180 200 CompressorWork(W) Evaporating Temperature C R134a (M-250g) R600a/R290 [70/30 by wt.%](M-125g) R600a/R290 [60/40 by wt.%](M-125g) R600a/R290 [50/50 by wt.%](M-125g)
  • 6. Experimental Evaluation of Refrigerant Mixtures As Substitutes For Hfc134a DOI: 10.9790/1684-1401057582 www.iosrjournals.org 80 | Page 4. Coefficient of performance (COP) -Fig.6 shows the effect of evaporating temperature on the COP for the refrigerants 250 g R134, 125 g R600a/R290 (70/30 by wt.%), 125 g R600a/R290 (60/40 by wt.%) and 125 g R600a/R290 (50/50 by wt.%). It was evident that the COP increases considerably with the increase of evaporating temperature except for R134. It was also observed that the COP was the highest for the refrigerant R600a/R290 (60/40 by wt.%) than that of other refrigerants. It was also observed that the COP of R600/R290 (60/40 by wt %) mixture was higher than that of R134a by 53.1% and 72.3% at -5 ÂșC and 5 ÂșC evaporating temperatures, respectively. The COP of HCM R600/R290 (60/40 by wt %) was higher than that of R600a/R290 (50/50 by wt. %) by 21.9% and 17.6% at -5 ÂșC and 5 ÂșC evaporating temperatures, respectively. The COP of HCM R600/R290 (60/40 by wt. %) was higher than that of HCM R600a/R290 (70/30 by wt.) by 59.1% and 19.3% at -5 ÂșC and 5 ÂșC evaporating temperatures, respectively. It can be seen that the COP decreases as propane mass fraction in HCM increases above 40%. The main reason behind this trend is the rate of change in specific work, which is higher than that of cooling effect. Fig. 6: Variations of coefficient of performance with respect to the evaporating temperature, at 30 ÂșC ambient temperature. 5. Pressure ratio (P1/P2) - The desirable property of the refrigerant is that pressure should be low due to its minimize leakages past the compressor piston. The pressure ratio was maximum for the refrigerant R134a and was minimum for HCM R600a/R290 (70/30 by wt.%) at the capillary length of 10 feet. The pressure ratio for R600a/R290 is minimum due to its lower mass flow rate. Fig. 7: Variations of compressor pressure ratio P1/P2 (Discharge / Suction). -5.0 -2.5 0.0 2.5 5.0 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 Coefficientofperformance(COP) Evaporating Temperature C R134a (M-250g) R600a/R290 [70/30 by wt.%](M-125g) R600a/R290 [60/40 by wt.%](M-125g) R600a/R290 [50/50 by wt.%](M-125g) -5.0 -2.5 0.0 2.5 5.0 4 5 6 7 8 9 10 11 12 PressureRatio(P1/P2) Evaporative Temperature C R134a (M-250g) R600a/R290 [70/30 by wt.%](M-125g) R600a/R290 [60/40 by wt.%](M-125g) R600a/R290 [50/50 by wt.%](M-125g)
  • 7. Experimental Evaluation of Refrigerant Mixtures As Substitutes For Hfc134a DOI: 10.9790/1684-1401057582 www.iosrjournals.org 81 | Page 6. Compressor Discharge Temperature - Compressor Discharge Temperature always be higher for HFC134a refrigerant but you can see in graphs the value of discharge temperature was quit low for HCM because lower mass of refrigerants as well as better cooling tendency and lower vapor pressure of R600a in HCM than other tested refrigerants. This is also give advantage for consumption of lubricating oil also low for HCM. Fig. 8 : Variations of compressor discharge temperature with respect to the evaporating temperatures. VI. Conclusion The lowest temperature in calorimeter was measured to be -5.8 ÂșC for the refrigerant of 125 g of R600a/R290 (50/50 by wt %) and the second lowest temperature was obtained to be -5.2 ÂșC for 125 g of R600a/R290 (60/40 by wt. %). R.E. of HCM refrigerant R600a/R290 (60/40 by wt. %) was increased by 10% and 35.8% than that of R134a, at -5 ÂșC and 5 ÂșC evaporating temperatures, respectively. Percentage increase in R.E. for R600a/R290 (60/40 by wt. %) was 13.7% and 7.7% than that of R600a/R290 (50/50 by wt. %), at -5 ÂșC and 5 ÂșC evaporating temperatures, respectively. Power consumption was maximum for R134a due to its higher mass flow rate. Power consumption was minimum for the mixture R600a/R290 (70/30 by wt. %) due to the lower mass percentage of R290 present in that. Energy consumption for the refrigerants R134a and R600a/R290 (50/50 by wt. %) was higher than that of R600a/R290 (60/40 by wt. %) by 39.2% and 43.3%, and 7.14% and 9.16%, respectively at -5 ÂșC and 5 ÂșC evaporating temperatures. COP of HCM R600/R290 (60/40 by wt. %) was higher than that of R134a by 53.1% and 72.3% at -5 ÂșC and 5 ÂșC evaporating temperatures, respectively. COP of HCM R600/R290 (60/40 by wt. %) mixture was higher than that of R600a/R290 (50/50 by wt. %) by 21.9% and 17.6% at -5 ÂșC and 5 ÂșC evaporating temperatures, respectively. COP decreased as propane mass fraction in HCM increased above 40%. The pressure ratio was the maximum for the refrigerant R134a and was in minimum for HCM R600a/R290 (70/30 by wt. %) at the capillary length of 10 feet. References [1]. Roy J. Dossat, Principles of refrigeration, 4th edition. Pearson education (Singapore) Pte. Ltd.,2003, New Delhi. Manohar Prasad, Refrigeration and air conditioning, 2nd edition. New Age International publishers, 2010, New Delhi. [2]. E. Halimic, D. Ross, B. Agnew, A. Anderson, and I. Potts, A comparison of the operating performance of alternative refrigerants. Applied Thermal Engineering 23 (12) (2003), 1441-1451. [3]. M. Mohanraj. S. Jayaraj, C. Muraleedharan, Environment friendly alternatives to halogenated refrigerants- a review, Int. Journal Greenhouse Gas Control 3 (2009), 108-119. [4]. M. Mohanraj. C. Muraleedharan, S Jayaraj, A review on recent developments in new refrigerant mixtures for vapor compression based refrigeration air conditioning and heat pump units Int. J Energy. Res 35 (8) (2011), 647-669. [5]. Kyoto protocol, United Nations Framework Convention on Climate Change, United Nations, New York, USA, 1997. [6]. Dr. S. Forbes Pearson, “New, Natural and Alternative Refrigerants”, Star refrigeration Limited, 2013 Edinburgh. [7]. D. Jung, Chong-Bo Kim, Kilhong Song, Byoungjin Park, Testing of propane / iso-butane mixture in domestic refrigerators, International Journal of Refrigeration, 23 (2000), 517-527. [8]. Y.S. Lee, C. C. Su, Experimental studies of iso-butane (R600a) as the refrigerant in domestic refrigeration system. Applied Thermal Engineering 22 (2002), 507-519. [9]. B. Tashtoush, Tahat, M., Shudeifat, M.A, Experimental study of new refrigerants mixture to replace R12 in domestic refrigerators, Applied Thermal Engineering 22 (2002), 495-506. -5.0 -2.5 0.0 2.5 5.0 30 35 40 45 50 55 60 65 70 CompressorDischargeTemperatureC Evaporating Temperature C R134a (M-250g) R600a/R290 [70/30 by wt.%](M-125g) R600a/R290 [60/40 by wt.%](M-125g) R600a/R290 [50/50 by wt.%](M-125g)
  • 8. Experimental Evaluation of Refrigerant Mixtures As Substitutes For Hfc134a DOI: 10.9790/1684-1401057582 www.iosrjournals.org 82 | Page [10]. S. J. Sekhar, D. Mohan Lal, and S. Renganarayanan, Improved energy efficiency for CFC domestic refrigerators retrofitted with ozone-friendly HFC134a/HC refrigerant mixture, International Journal of Thermal Sciences, 43 (3) (2004), 307-314. [11]. M. Fatouh, M. kafafy, Experimental evaluation of a domestic refrigerator working with LPG, Applied Thermal Engineering 26 (2006), 1593 -1603. [12]. K. Senthil Kumar, K. Rajagopal, Computational and experimental investigation of low ODP and low GWP HCFC-123 and HC-290 refrigerant mixture alternate to CFC-12, Energy Conversion and Management 48 (2007),3053-3062. [13]. M. Mohanraj, S. Jayaraj and C. Muraleedharan, Improved energy efficiency for HFC 134a domestic refrigerator retrofitted with hydrocarbon mixture (HC 290 / HC 600a) as drop-in substitute, Energy for Sustainable Development 11,4 (2007), 29 – 33. [14]. K. Mani, V. Selladurai, Experimental analysis of a new refrigerant mixture as drop in replacement for CFC12 and HFC 134a, International Journal of Thermal Sciences 47 (2008), 1490-1495. [15]. M. Fatouh, M Kafary, Assessment of propane/commercial butane mixtures as possible alternatives to R134a in domestic refrigerators, Energy Conservation and Management 47 (2006), 2644-2658. [16]. Chao-Chieh Yu, Tun-Ping Teng, Retrofit assessment of using hydrocarbon refrigerants, Applied Thermal Engineering 66 (2014), 507- 518. [17]. S. Dalkilic, S. Wongwises, A performance comparison of Vapor-compression refrigeration system using various alternative refrigerants, International Communications in Heat and Mass Transfer, 37(9),(2010) pp.1340-1349