Copyright 1999-2019 Dan Dudley
Motors and Motor
Circuit Calculations
2017 NEC Requirements
Copyright 1999-2019 Dan Dudley
2017 NEC Motor Circuit
Requirements and
Calculations
Copyright 1999-2019 Dan Dudley
NEC Motor Calculations
Basic Information
• 430.6(a)(1) Basic Calc information
• Name Plate Values (430.6(a)(2) are only used to size overloads
• Otherwise use T.430.247, 248, 249, & 250
• 430.22(a) Single motor 125% cont. duty (3 hrs. or more)
• T.430.22(e) Note Cont. Duty unless nature of apparatus is otherwise.
Copyright 1999-2019 Dan Dudley
NEC Motor Calculations
Basic Information
• 430.52(c)(1) exception
• Next higher standard size overcurrent protective device.
• 430.62 Feeder O.C. Protection
• Largest S.C. – G.F. Protective device plus the sum of the F.L.C. of all
other motors supplied by the same feeder
• No provision for going UP to next standard size must go down to next
standard size
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Hz
Hp Phases FLC Voltage
Temp
Rise
Service
Factor
Locked
Rotor
Letter
Insulation
Class
Copyright 1999-2019 Dan Dudley
Line side
Nameplate Data
Actuating Coil
Overload Relays
Load Side
Copyright 1999-2019 Dan Dudley
For all other
calculations use
Table values
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
¾ @120 5 @208
Copyright 1999-2019 Dan Dudley
25-208 50 sync – 440 200 - 480
50 HP
Synchronous
440 Volts
200 HP
480 Volts
25 HP
208 Volts
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
What minimum size THHN conductors are required for this
motor ?
Name Plate Not used
430.248: 10hp @ 240v = 50 amps
430.22(a): 50 X 125% = 62.5 amps
310.15(b)(16): 62.5 amps = #4 THHN
10HP 240V 1Φ FLI
44
Copyright 1999-2019 Dan Dudley
What is the minimum ampacity of the branch circuit conductors for a 25 HP ,
480-volt, 3 phase, squirrel cage motor with nameplate FLI of 32.5 amps ?
Name Plate value not used
430.250: 25hp @480v = 34 amps
430.22(a): 34 X 125% = 42.5 amps
310.15(b)(16) : # 6 THHN @60ºC and 55 amps
25HP 480V 3Φ FLI
32.5
Copyright 1999-2019 Dan Dudley
Circuits with more than one Motor
• Step 1.
• Step 2.
• Step 3.
• Decide which motor has largest
FLI rating
(This may not be the largest HP)
• Largest FLI of one motor X 125%
(only increase one)
• Add FLI rating of all other
motors
(straight from tables)
Copyright 1999-2019 Dan Dudley
What is the minimum ampacity of the branch circuit conductors for the
two motors as shown ? 3Æ, 208V
430.250: 5 hp @ 208v = 16.7 amps
430.24: Ampacity = FLI 1st motor X 125% + FLI 2nd motor
Ampacity = 16.7 X 125% + 16.7 = 37.575 amps
5HP 3Φ 208V
5HP 3Φ 208V
Copyright 1999-2019 Dan Dudley
What is the minimum ampacity of the branch circuit conductors supplying the two
motors as shown ? 1Æ, 230V
430.248: 2hp @ 230v = 12 amps
430.248: 5hp @ 230v = 28 amps
Ampacity = Largest FLI X 125% + Second FLI
28 X 125% + 12 = 47 amps
5HP 1Φ 230V 2HP 1Φ 230V
Copyright 1999-2019 Dan Dudley
What is the minimum ampacity of the branch circuit
conductor serving the three motors as shown
above?
10HP 3Φ 480V
Squirrel Cage
25HP 3Φ 480V
Squirrel Cage
30HP 3Φ 480V
Synchronous
Copyright 1999-2019 Dan Dudley
430.250: FLI’s, 3-phase, 480v
10hp Squirrel cage = 14 FLI
25hp Squirrel cage = 34 FLI
30hp Synchronous = 32 FLI
34 X 125% + 14 + 32 = 88.5 amps
10HP 3Φ 480V
Squirrel Cage
25HP 3Φ 480V
Squirrel Cage
30HP 3Φ 480V
Synchronous
Copyright 1999-2019 Dan Dudley
What Size THWN conductors are required for:
1: Ungrounded Conductors
2: Grounded Conductor
3: Grounding Conductor
88.5A
T.310.15(b)(16) & 110.14(c) = #2 THWN Ungrounded 60°C
No Grounded Conductor Required
T.250.122 Grounding Conductor (EGC) = #8 Cu or #6 Al
Design
A
10HP 3Φ 480V
Squirrel Cage
25HP 3Φ 480V
Squirrel Cage
30HP 3Φ 480V
Synchronous
Copyright 1999-2019 Dan Dudley
What is the minimum size branch circuit conductors supplying the motor and
incandescent lighting above ?
430.248: 1hp @ 120v = 16 amps
Lighting: I=W / E = 6000 / 120 = 50 amps
430.24(a): Ampacity = motor FLI X 125% + Lighting I
16 X 125% + 50 = 70 amps
#4 THHN Cu (60°C)
6000 watts
Incandescent Lighting
1HP 1Φ 120V
FLI 12.4
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
81.25
26.25
123.25
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Time Delay Fuses 20HP 3Φ 480V
FLI 29
Copyright 1999-2019 Dan Dudley
Time Delay
Fuses
20HP 3Φ 480V
FLI 29
T.430.250: 20hp = 27 amps
T.430.52: Time Delay Fuse = 175%
Max. O.C. device = 27 X 175% = 47.25 amps
430.52(c)(1) exception #1: Next Larger size permitted
240.6(a) Next Larger Std size = 50 amps
Answer: 50 amp Time Delay Fuse
Copyright 1999-2019 Dan Dudley
Non-Time Delay
Fuses
20HP 3Φ 480V
FLI 29
T.430.250: 20hp = 27 amps
T.430.52: Non-Time Delay Fuse = 300%
Max. O.C. device = 27 X 300% = 81 amps
430.52(c)(1) exception #1: Next Larger size permitted
240.6(a) Next Larger Std size = 90 amps
Answer: 90-amp Non-Time Delay Fuse
Copyright 1999-2019 Dan Dudley
Inverse Time
Breaker
20HP 3Φ 480V
FLI 29
T.430.250: 20hp = 27 amps
T.430.52: Inverse Time Breaker = 250%
Max. O.C. device = 27 X 250% = 67.5 amps
430.52(c)(1) exception 1: Next Larger size permitted
240.6(a) Next Larger Std size = 70 amps
Answer: 70-amp Inverse Time Circuit Breaker
Copyright 1999-2019 Dan Dudley
Selecting Minimum Size Overloads 430.32(A)(1)
n Service Factor
n Less than 1.15 use 115%
n 1.15 or greater use
125%
n No Service Factor Listed
use 115%
n Temperature Rise
n 40°C or less use 125%
n Over 40°C use 115%
n No Temp Listed use
115%
Copyright 1999-2019 Dan Dudley
Selecting Maximum Size Overloads 430.32(C)
n Service Factor
n Less than 1.15 use 130%
n 1.15 or greater use
140%
n No Service Factor Listed
use 130%
n Temperature Rise
n 40°C or less use 140%
n Over 40°C use 130%
n No Temp Listed use
130%
Copyright 1999-2019 Dan Dudley
Solution:
Welder No.1
630.11(a) Nonmotor Generator
Duty cycle 30 Multiplier = 0.55
I=RPCXM
I = 28 amps x 0.55 = 15.4 amps
Welder No.2
630.11(a) Nonmotor Generator
Duty cycle 80 Multiplier = 0.89
I=RPC xM
I = 18 amps x 0.89 = 16.02 amps
630.11(b)
Total = No.1+ No.2
Total = 15.4 + 16.02 = 31.42 amps
Ans. 31.42 amps
RPC 28A
Duty Cycle
30%
RPC 18A
Duty Cycle
80%
Motors with a Duty Cycle - Welders
Copyright 1999-2019 Dan Dudley
Solution:
Nameplate current rating is used.
Table 430.22(e)
FLI 15 min. periodic duty = 90%
Ampacity -Nameplate FLI x 90%
= 24.5 x 90% = 22.05 amps.
Answer: 22.05 amperes
5HP 230V 1Φ
FLI 24.5
Periodic Duty
15 Min
Copyright 1999-2019 Dan Dudley
Solution:
Nameplate FLI is used
430.22(e)
Continuous use, varying duty= 200%
Ampacity = nameplate FLI x 200 %
Ampacity= 16.5 x 200 = 33 amps
Answer: 33 amperes
15HP 230V 3Φ
FLI 16.5
Varying Duty
Copyright 1999-2019 Dan Dudley
Motor Efficiency
• Efficiency = Output / Input
• 5HP, 240V, 1Æ = 28A F.L.C.
T.430.248
• W = E X I = 240V X 28A = 6720 VA
• 6720 VA input and 5712 VA output
• 5712/6720 = .85
• 6720 VA X .85 = 5712 VA output
• 85% efficiency
No motor is 100% efficient
Efficiency = Output / Input
Copyright 1999-2019 Dan Dudley
Motor Duty Rating
n Intermittent Duty = T.430.22(e)
n Nameplate F.L.C. used
n 50HP,480V,3Æ, 15-minute rated elevator motor, Name Plate FLC
=61.2A
n 430.22(e) = 85%
n Name Plate FLC = 61.2 X 85% = 52.02A Branch Circuit
Ampacity
n Conductor Required = #6 (60°C column)
240.6 310.15(b)(16) 110.14
430.52
Copyright 1999-2019 Dan Dudley
Motor Calculations
Practice Questions
30 Minutes
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
25-208 50 sync – 440 200 - 480
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Question 1 Keywords
What size short circuit/ground fault protection is
required for the branch circuit serving motor #1 in
motor diagram #1?
What size short circuit/ground fault protection is
required for the branch circuit serving motor #1 in
motor diagram #1?
We are looking for the smallest fuse or circuit breaker
required to protect motor #1 on Motor Diagram #1.
Copyright 1999-2019 Dan Dudley
Question 2 Keywords
What is the minimum size overloads required for motor #2 on
motor diagram #1 ?
What is the minimum size overloads required for motor #2 on
motor diagram #1 ?
We are looking for the smallest heater/overload size allowed for
motor #2 on motor diagram #1.
Overloads = name plate full load current times either 115% or
125% depending on S.F. and/or Temp Rise.
Copyright 1999-2019 Dan Dudley
Question 3 Keywords
What is the minimum size THHN feeder required for the six motors as
shown on Motor Diagram #1 ?
What is the minimum size THHN feeder required for the six motors as
shown on Motor Diagram #1 ?
We are looking for the smallest legally allowed THHN copper conductor
to feed these 6 motors. Feeder conductor = three steps:
1 find largest FLA motor and multiply by 1.25 (125%)
2. Add FLA of all other motors on same feeder
3. Can’t go up in size = drop down to standard at 240.6

2019_Motor-Calculations NEC 2017........

  • 1.
    Copyright 1999-2019 DanDudley Motors and Motor Circuit Calculations 2017 NEC Requirements
  • 2.
    Copyright 1999-2019 DanDudley 2017 NEC Motor Circuit Requirements and Calculations
  • 3.
    Copyright 1999-2019 DanDudley NEC Motor Calculations Basic Information • 430.6(a)(1) Basic Calc information • Name Plate Values (430.6(a)(2) are only used to size overloads • Otherwise use T.430.247, 248, 249, & 250 • 430.22(a) Single motor 125% cont. duty (3 hrs. or more) • T.430.22(e) Note Cont. Duty unless nature of apparatus is otherwise.
  • 4.
    Copyright 1999-2019 DanDudley NEC Motor Calculations Basic Information • 430.52(c)(1) exception • Next higher standard size overcurrent protective device. • 430.62 Feeder O.C. Protection • Largest S.C. – G.F. Protective device plus the sum of the F.L.C. of all other motors supplied by the same feeder • No provision for going UP to next standard size must go down to next standard size
  • 5.
  • 6.
    Copyright 1999-2019 DanDudley Hz Hp Phases FLC Voltage Temp Rise Service Factor Locked Rotor Letter Insulation Class
  • 7.
    Copyright 1999-2019 DanDudley Line side Nameplate Data Actuating Coil Overload Relays Load Side
  • 8.
    Copyright 1999-2019 DanDudley For all other calculations use Table values
  • 9.
  • 10.
    Copyright 1999-2019 DanDudley ¾ @120 5 @208
  • 11.
    Copyright 1999-2019 DanDudley 25-208 50 sync – 440 200 - 480 50 HP Synchronous 440 Volts 200 HP 480 Volts 25 HP 208 Volts
  • 12.
  • 13.
    Copyright 1999-2019 DanDudley What minimum size THHN conductors are required for this motor ? Name Plate Not used 430.248: 10hp @ 240v = 50 amps 430.22(a): 50 X 125% = 62.5 amps 310.15(b)(16): 62.5 amps = #4 THHN 10HP 240V 1Φ FLI 44
  • 14.
    Copyright 1999-2019 DanDudley What is the minimum ampacity of the branch circuit conductors for a 25 HP , 480-volt, 3 phase, squirrel cage motor with nameplate FLI of 32.5 amps ? Name Plate value not used 430.250: 25hp @480v = 34 amps 430.22(a): 34 X 125% = 42.5 amps 310.15(b)(16) : # 6 THHN @60ºC and 55 amps 25HP 480V 3Φ FLI 32.5
  • 15.
    Copyright 1999-2019 DanDudley Circuits with more than one Motor • Step 1. • Step 2. • Step 3. • Decide which motor has largest FLI rating (This may not be the largest HP) • Largest FLI of one motor X 125% (only increase one) • Add FLI rating of all other motors (straight from tables)
  • 16.
    Copyright 1999-2019 DanDudley What is the minimum ampacity of the branch circuit conductors for the two motors as shown ? 3Æ, 208V 430.250: 5 hp @ 208v = 16.7 amps 430.24: Ampacity = FLI 1st motor X 125% + FLI 2nd motor Ampacity = 16.7 X 125% + 16.7 = 37.575 amps 5HP 3Φ 208V 5HP 3Φ 208V
  • 17.
    Copyright 1999-2019 DanDudley What is the minimum ampacity of the branch circuit conductors supplying the two motors as shown ? 1Æ, 230V 430.248: 2hp @ 230v = 12 amps 430.248: 5hp @ 230v = 28 amps Ampacity = Largest FLI X 125% + Second FLI 28 X 125% + 12 = 47 amps 5HP 1Φ 230V 2HP 1Φ 230V
  • 18.
    Copyright 1999-2019 DanDudley What is the minimum ampacity of the branch circuit conductor serving the three motors as shown above? 10HP 3Φ 480V Squirrel Cage 25HP 3Φ 480V Squirrel Cage 30HP 3Φ 480V Synchronous
  • 19.
    Copyright 1999-2019 DanDudley 430.250: FLI’s, 3-phase, 480v 10hp Squirrel cage = 14 FLI 25hp Squirrel cage = 34 FLI 30hp Synchronous = 32 FLI 34 X 125% + 14 + 32 = 88.5 amps 10HP 3Φ 480V Squirrel Cage 25HP 3Φ 480V Squirrel Cage 30HP 3Φ 480V Synchronous
  • 20.
    Copyright 1999-2019 DanDudley What Size THWN conductors are required for: 1: Ungrounded Conductors 2: Grounded Conductor 3: Grounding Conductor 88.5A T.310.15(b)(16) & 110.14(c) = #2 THWN Ungrounded 60°C No Grounded Conductor Required T.250.122 Grounding Conductor (EGC) = #8 Cu or #6 Al Design A 10HP 3Φ 480V Squirrel Cage 25HP 3Φ 480V Squirrel Cage 30HP 3Φ 480V Synchronous
  • 21.
    Copyright 1999-2019 DanDudley What is the minimum size branch circuit conductors supplying the motor and incandescent lighting above ? 430.248: 1hp @ 120v = 16 amps Lighting: I=W / E = 6000 / 120 = 50 amps 430.24(a): Ampacity = motor FLI X 125% + Lighting I 16 X 125% + 50 = 70 amps #4 THHN Cu (60°C) 6000 watts Incandescent Lighting 1HP 1Φ 120V FLI 12.4
  • 22.
  • 23.
  • 24.
    Copyright 1999-2019 DanDudley 81.25 26.25 123.25
  • 25.
  • 26.
  • 27.
  • 28.
    Copyright 1999-2019 DanDudley Time Delay Fuses 20HP 3Φ 480V FLI 29
  • 29.
    Copyright 1999-2019 DanDudley Time Delay Fuses 20HP 3Φ 480V FLI 29 T.430.250: 20hp = 27 amps T.430.52: Time Delay Fuse = 175% Max. O.C. device = 27 X 175% = 47.25 amps 430.52(c)(1) exception #1: Next Larger size permitted 240.6(a) Next Larger Std size = 50 amps Answer: 50 amp Time Delay Fuse
  • 30.
    Copyright 1999-2019 DanDudley Non-Time Delay Fuses 20HP 3Φ 480V FLI 29 T.430.250: 20hp = 27 amps T.430.52: Non-Time Delay Fuse = 300% Max. O.C. device = 27 X 300% = 81 amps 430.52(c)(1) exception #1: Next Larger size permitted 240.6(a) Next Larger Std size = 90 amps Answer: 90-amp Non-Time Delay Fuse
  • 31.
    Copyright 1999-2019 DanDudley Inverse Time Breaker 20HP 3Φ 480V FLI 29 T.430.250: 20hp = 27 amps T.430.52: Inverse Time Breaker = 250% Max. O.C. device = 27 X 250% = 67.5 amps 430.52(c)(1) exception 1: Next Larger size permitted 240.6(a) Next Larger Std size = 70 amps Answer: 70-amp Inverse Time Circuit Breaker
  • 32.
    Copyright 1999-2019 DanDudley Selecting Minimum Size Overloads 430.32(A)(1) n Service Factor n Less than 1.15 use 115% n 1.15 or greater use 125% n No Service Factor Listed use 115% n Temperature Rise n 40°C or less use 125% n Over 40°C use 115% n No Temp Listed use 115%
  • 33.
    Copyright 1999-2019 DanDudley Selecting Maximum Size Overloads 430.32(C) n Service Factor n Less than 1.15 use 130% n 1.15 or greater use 140% n No Service Factor Listed use 130% n Temperature Rise n 40°C or less use 140% n Over 40°C use 130% n No Temp Listed use 130%
  • 34.
    Copyright 1999-2019 DanDudley Solution: Welder No.1 630.11(a) Nonmotor Generator Duty cycle 30 Multiplier = 0.55 I=RPCXM I = 28 amps x 0.55 = 15.4 amps Welder No.2 630.11(a) Nonmotor Generator Duty cycle 80 Multiplier = 0.89 I=RPC xM I = 18 amps x 0.89 = 16.02 amps 630.11(b) Total = No.1+ No.2 Total = 15.4 + 16.02 = 31.42 amps Ans. 31.42 amps RPC 28A Duty Cycle 30% RPC 18A Duty Cycle 80% Motors with a Duty Cycle - Welders
  • 35.
    Copyright 1999-2019 DanDudley Solution: Nameplate current rating is used. Table 430.22(e) FLI 15 min. periodic duty = 90% Ampacity -Nameplate FLI x 90% = 24.5 x 90% = 22.05 amps. Answer: 22.05 amperes 5HP 230V 1Φ FLI 24.5 Periodic Duty 15 Min
  • 36.
    Copyright 1999-2019 DanDudley Solution: Nameplate FLI is used 430.22(e) Continuous use, varying duty= 200% Ampacity = nameplate FLI x 200 % Ampacity= 16.5 x 200 = 33 amps Answer: 33 amperes 15HP 230V 3Φ FLI 16.5 Varying Duty
  • 37.
    Copyright 1999-2019 DanDudley Motor Efficiency • Efficiency = Output / Input • 5HP, 240V, 1Æ = 28A F.L.C. T.430.248 • W = E X I = 240V X 28A = 6720 VA • 6720 VA input and 5712 VA output • 5712/6720 = .85 • 6720 VA X .85 = 5712 VA output • 85% efficiency No motor is 100% efficient Efficiency = Output / Input
  • 38.
    Copyright 1999-2019 DanDudley Motor Duty Rating n Intermittent Duty = T.430.22(e) n Nameplate F.L.C. used n 50HP,480V,3Æ, 15-minute rated elevator motor, Name Plate FLC =61.2A n 430.22(e) = 85% n Name Plate FLC = 61.2 X 85% = 52.02A Branch Circuit Ampacity n Conductor Required = #6 (60°C column) 240.6 310.15(b)(16) 110.14 430.52
  • 39.
    Copyright 1999-2019 DanDudley Motor Calculations Practice Questions 30 Minutes
  • 40.
  • 41.
  • 42.
    Copyright 1999-2019 DanDudley 25-208 50 sync – 440 200 - 480
  • 43.
  • 44.
  • 45.
  • 46.
  • 47.
  • 48.
  • 49.
  • 50.
  • 51.
  • 52.
    Copyright 1999-2019 DanDudley Question 1 Keywords What size short circuit/ground fault protection is required for the branch circuit serving motor #1 in motor diagram #1? What size short circuit/ground fault protection is required for the branch circuit serving motor #1 in motor diagram #1? We are looking for the smallest fuse or circuit breaker required to protect motor #1 on Motor Diagram #1.
  • 53.
    Copyright 1999-2019 DanDudley Question 2 Keywords What is the minimum size overloads required for motor #2 on motor diagram #1 ? What is the minimum size overloads required for motor #2 on motor diagram #1 ? We are looking for the smallest heater/overload size allowed for motor #2 on motor diagram #1. Overloads = name plate full load current times either 115% or 125% depending on S.F. and/or Temp Rise.
  • 54.
    Copyright 1999-2019 DanDudley Question 3 Keywords What is the minimum size THHN feeder required for the six motors as shown on Motor Diagram #1 ? What is the minimum size THHN feeder required for the six motors as shown on Motor Diagram #1 ? We are looking for the smallest legally allowed THHN copper conductor to feed these 6 motors. Feeder conductor = three steps: 1 find largest FLA motor and multiply by 1.25 (125%) 2. Add FLA of all other motors on same feeder 3. Can’t go up in size = drop down to standard at 240.6