1. There are several types of lens materials that can be used in infrared windows, with the choice driven by the application environment and transmission requirements.
2. Common lens materials include germanium, zinc selenide, and sapphire - each with their own transmission properties and temperature ranges.
3. The lens material must be able to withstand the environmental conditions inside the enclosure, have suitable infrared transmission, and meet any certification or safety standards.
LASERSMART™ Laboratories: A Safety Primer WhitepaperJustin Clough
A narrative checklist of considerations when setting up a laser laboratory. While not a complete list, the goal is to guide you away from the most common pitfalls.
The document discusses new NFPA 70E regulations for arc flash labeling that took effect in 2015. It provides guidance on what electrical equipment needs to be labeled, what information needs to appear on labels, and examples of pre-printed labels that comply with the regulations. Key points covered include:
- Electrical equipment like switchboards, panelboards, and motor control centers must be labeled if they require examination, adjustment or maintenance while energized.
- Labels must include the nominal system voltage, arc flash boundary, and either the available incident energy and working distance or minimum arc rating of clothing.
- Brady provides pre-printed labels that meet NFPA 70E requirements and include write-in fields for arc flash information.
The IW Series are the latest generation of infrared windows from CorDEX Instruments that allow thermal imagers to inspect electrical equipment safely and efficiently. The windows are made from industrial-grade materials certified to withstand electric arcs. They have features like a quick locking system and protected lenses that allow for faster inspections both indoors and outdoors. The IW Series windows come in different sizes and are tested and certified to various industry standards for electrical safety.
The IW Series are the latest generation of infrared windows from CorDEX Instruments that allow thermal imagers to inspect electrical equipment safely and efficiently. The windows are made from industrial-grade materials certified to withstand electric arcs. They have features like a quick locking system and protected lenses that allow for faster inspections both indoors and outdoors. The IW Series windows are tested and certified to various industry standards for electrical safety.
PSC is a specialised oilfield PPE distributor in India. Please see attached our product range. For more information, please feel free to call on us on +91-772-9990-661
Power tools present more hazards than hand tools due to their higher operating speeds. Personal protective equipment (PPE) like safety glasses or goggles and earplugs or earmuffs are especially important when using power tools to protect users from flying debris and loud noises. A face shield is recommended for tools like grinders that produce hot metal particles, and cut-resistant gloves cannot fully protect hands from moving blades. Proper safety footwear and loose, jewelry-free clothing should also be worn.
The document describes several ultraviolet room air sanitizers produced by Atlantic Ultraviolet Corporation. It provides specifications for four ceiling or wall-mounted models (RS72, RS140, RS435, RSA760) and two portable models (RSM2680, RSCS280). The units are designed to disinfect air and surfaces using ultraviolet lamps that emit 254nm wavelengths lethal to microbes. They have stainless steel housings, electronic ballasts, and features like sight glasses and filters to safely sanitize occupied spaces. Atlantic Ultraviolet has specialized in beneficial UV applications since 1963.
An inspection of the facility is needed to evaluate arc flash hazards and determine the need for new or replacement labels. Key elements to examine include existing labels for accuracy and legibility, unlabelled equipment, new equipment, and areas where work has been performed. Proper personal protective equipment should be worn during the inspection. Electrical equipment 50V or higher generally requires an arc flash label. IEEE 1584 and NFPA 70E provide calculation methods to determine flash protection boundaries and exposure levels to ensure compliance.
LASERSMART™ Laboratories: A Safety Primer WhitepaperJustin Clough
A narrative checklist of considerations when setting up a laser laboratory. While not a complete list, the goal is to guide you away from the most common pitfalls.
The document discusses new NFPA 70E regulations for arc flash labeling that took effect in 2015. It provides guidance on what electrical equipment needs to be labeled, what information needs to appear on labels, and examples of pre-printed labels that comply with the regulations. Key points covered include:
- Electrical equipment like switchboards, panelboards, and motor control centers must be labeled if they require examination, adjustment or maintenance while energized.
- Labels must include the nominal system voltage, arc flash boundary, and either the available incident energy and working distance or minimum arc rating of clothing.
- Brady provides pre-printed labels that meet NFPA 70E requirements and include write-in fields for arc flash information.
The IW Series are the latest generation of infrared windows from CorDEX Instruments that allow thermal imagers to inspect electrical equipment safely and efficiently. The windows are made from industrial-grade materials certified to withstand electric arcs. They have features like a quick locking system and protected lenses that allow for faster inspections both indoors and outdoors. The IW Series windows come in different sizes and are tested and certified to various industry standards for electrical safety.
The IW Series are the latest generation of infrared windows from CorDEX Instruments that allow thermal imagers to inspect electrical equipment safely and efficiently. The windows are made from industrial-grade materials certified to withstand electric arcs. They have features like a quick locking system and protected lenses that allow for faster inspections both indoors and outdoors. The IW Series windows are tested and certified to various industry standards for electrical safety.
PSC is a specialised oilfield PPE distributor in India. Please see attached our product range. For more information, please feel free to call on us on +91-772-9990-661
Power tools present more hazards than hand tools due to their higher operating speeds. Personal protective equipment (PPE) like safety glasses or goggles and earplugs or earmuffs are especially important when using power tools to protect users from flying debris and loud noises. A face shield is recommended for tools like grinders that produce hot metal particles, and cut-resistant gloves cannot fully protect hands from moving blades. Proper safety footwear and loose, jewelry-free clothing should also be worn.
The document describes several ultraviolet room air sanitizers produced by Atlantic Ultraviolet Corporation. It provides specifications for four ceiling or wall-mounted models (RS72, RS140, RS435, RSA760) and two portable models (RSM2680, RSCS280). The units are designed to disinfect air and surfaces using ultraviolet lamps that emit 254nm wavelengths lethal to microbes. They have stainless steel housings, electronic ballasts, and features like sight glasses and filters to safely sanitize occupied spaces. Atlantic Ultraviolet has specialized in beneficial UV applications since 1963.
An inspection of the facility is needed to evaluate arc flash hazards and determine the need for new or replacement labels. Key elements to examine include existing labels for accuracy and legibility, unlabelled equipment, new equipment, and areas where work has been performed. Proper personal protective equipment should be worn during the inspection. Electrical equipment 50V or higher generally requires an arc flash label. IEEE 1584 and NFPA 70E provide calculation methods to determine flash protection boundaries and exposure levels to ensure compliance.
DEG Licht GmbH produces blue spot safety lights that can be installed on forklifts to warn warehouse personnel of approaching vehicles. Statistics show that 19% of accidents in warehouses are caused by a lack of warning signaling. The blue spot lights project a focused beam of blue light in the direction of travel, allowing workers to see and avoid moving forklifts even outside of their field of vision. This can help reduce accidents by 19% according to one case study. The lights are durable and can withstand wide temperature ranges and harsh environments common in warehouses.
Exposure to an arc flash (the sudden release of heat and light at an electrical fault) frequently results in serious injury, even to workers several feet away from the arc center. Both NFPA and OSHA have specific requirements to address the risk of arc flash injuries.
This bulletin provides sources of information on NFPA, OSHA and ANSI standards related to arc flash hazards, and also describes the approved design of arc flash safety signs and labels.
1. Power tools present greater hazards than hand tools due to their higher speeds of operation. Proper personal protective equipment (PPE) is important for safe use of power tools.
2. Eye protection like safety glasses or goggles is especially important for power tools, as their moving parts can propel small particles faster than hand tools. A face shield is recommended when using tools like grinders due to hot metal particles.
3. Standard work gloves protect hands from minor cuts but not moving blades. Cut-resistant gloves do not protect from moving parts. The best protection is keeping hands on tool handles and guards in place. Anti-vibration gloves reduce vibration from tools like hammer drills.
This document provides guidelines for protecting commonly used interfaces from electrostatic discharge (ESD) and transient voltages. It discusses ESD protection considerations and solutions for automotive interfaces like CAN, LIN, and FlexRay. It also covers general input/output, serial buses, displays, Ethernet, and radio frequency interfaces. For each interface, example protection circuits are shown along with NXP's recommended protection devices that offer high ESD robustness and minimal impact on signal integrity.
This document discusses facility electrical protection solutions from ERICO. It begins by outlining the risks facilities face from lightning strikes, which cause billions in damages annually. It then discusses ERICO's comprehensive approach to facility protection, considering lightning protection, grounding, bonding, and surge protection together. The document provides information on ERICO's products and services for lightning protection air terminals and downconductors, grounding and bonding solutions, surge protection, and design services. It presents ERICO's Six Point Plan for total facility protection and discusses applications for key industries like power generation, telecommunications, aviation, oil and gas, mining, and rail.
The Altair 4X multigas detector provides significant cost savings and safety benefits compared to other detectors. It has a 4-year sensor life and 3-year warranty, reducing replacement and maintenance costs by over 50%. Additional features like motion and instant alarms improve worker safety. The durable design withstands tough industrial environments.
The document provides guidelines for properly labeling electrical equipment to warn of arc flash hazards, in accordance with NFPA 70E and OSHA standards. It recommends labeling with a single worst-case scenario that lists the highest potential incident energy and required PPE. Multiple labels or labels listing varying energy levels/PPE can confuse workers and increase liability. ANSI-standard triangle warning labels are suggested over customized labels. Proper labeling warns of hazards but does not replace the need for work permits, safety programs or training when working on energized equipment.
This document discusses service life recommendations for various types of personal protective equipment (PPE) such as safety glasses, hard hats, harnesses, lanyards, and ropes according to OSHA regulations and manufacturer specifications. It finds that while OSHA does not mandate specific service life durations, manufacturers provide various guidelines ranging from 1 to 10 years depending on the frequency and conditions of use. In general, harnesses and hard hats should be replaced every 5 years, ropes between 2-5 years, and all equipment should be retired if damaged, deteriorated, or exceeding 10 years of age. Inspection criteria and manufacturer guidance take precedence over time alone in determining necessary replacement of PPE.
This document provides instructions for installing and using the LoRa Technology Evaluation Suite, which allows users to evaluate Microchip's LoRa wireless technology. The suite includes a utility application for connecting to LoRa devices, as well as a server application and required redistributables. Users are guided through installing the suite components, setting up a virtual machine environment, launching a Docker container to host the server, and connecting LoRa development devices to evaluate the wireless performance and capabilities. The document also provides overviews of the utility and server applications and their basic functions.
Key considerations when switching to miniature connectorsDesign World
Join us for this panel webinar, in which industry experts will provide insight on selecting, specifying and using miniature connectors safely and reliably in your system designs. Our panelists include David Ptacek, national sales manager and US product manager for Fischer Connectors’ MiniMax series; Steven Lassen, Products and Applications Manager, LEMO USA; Mike Higashikawa, Regional Product Manager, Micro Products Division for Molex Incorporated; and Brendan Dempsey, Business Development Manager at ODU-USA.
Our panel will discuss some of the challenges and misconceptions associated with miniature connectors, covering everything from EMI/EMC to robustness and mating reliability to common applications.
Personal protective equipment.........aryaarya das
This document discusses personal protective equipment (PPE) and focuses on eye and face protection. It notes that nearly 2 million people receive disabling work injuries each year, with over a quarter involving the head, eyes, hands or feet. PPE is designed to protect workers from hazards like chemicals, radiation, impacts and more. The document outlines OSHA standards for employers to assess hazards, provide necessary PPE and training. It details types of eye and face protection like safety glasses, goggles, face shields and welding helmets and notes criteria for selecting the right protection for specific hazards.
Here is our first class work to be posted in our blog.This is Diego Mena's presentation about his father's work. He is a fireman in our town, Benalmádena.
Diego's class is 6 B.
Screen shot from latest customer install shows detailed heat map GUI. Sensors were polling live data within an hour of installation. Another happy customer.
Allied International Emergency provides rescue services across North Central Texas, West Texas, New Mexico, and Southern Oklahoma. Their mission is to provide experienced, certified rescue professionals who adhere to stringent training requirements including EMT certification and 5 years of experience. Their rescue teams are trained to OSHA, NFPA, and other standards to handle confined space and hazardous environment rescues involving risks like entrapment, engulfment, and toxic atmospheres. They focus on safety from consultation through implementation of rescue plans.
Los bomberos en Francia incluyen 248,300 bomberos, 80% de los cuales son voluntarios. Los bomberos operan en ciudades y aeropuertos. El programa JSP permite que jóvenes estudien para convertirse en bomberos voluntarios o profesionales a través de 4 años de entrenamiento físico y académico para obtener un diploma.
El documento describe la importancia de cumplir con las leyes de seguridad e higiene en el trabajo relacionadas con la conformación de brigadas contra incendios, la elaboración de planes de evacuación y la realización de simulacros. También resalta la responsabilidad de los empleadores y profesionales intervinientes en dichos planes.
Firefighter turnout gear consists of a helmet, face mask, gloves, self-contained breathing apparatus, turnout jacket, bunker pants, and boots to protect firefighters from heat, flames, and hazardous materials. The gear uses reflective safety stripes and a self-contained breathing apparatus to keep firefighters safe even in dangerous situations.
The document provides an operations manual for a Rapid Intervention Team (RIT) air pack developed by the Fairfax County Fire & Rescue Department. The RIT pack was designed to address shortcomings in previous models and features components that allow it to supply air to multiple firefighters. It can receive supplemental air from vehicle cascade systems or in-line manifolds. The manual describes the RIT pack's components, daily checks, decontamination procedures, maintenance, and operational roles at different emergency response levels. RIT packs are assigned to rescue vehicles and used to provide air to firefighters until a downed firefighter can be removed from danger.
The document provides an overview of the Princeton Fire Department, including its purpose to educate citizens, roles, budget, operations, and trends. The department's roles include fire protection, suppression, and emergency medical services. It operates one fire station and responds to over 2000 calls annually within its 90 square mile fire district. The budget comes from various sources like ambulance billing and rural fire district taxes, and is used to fund operations and purchase vehicles and equipment.
The document discusses the use of thermal imaging cameras for firefighting tactics including primary search, fire attack, rapid intervention teams, contingencies, overhaul, and the importance of practice. It notes key uses like engine or ladder search patterns for primary search and using thermal layers to find a safe path and fire location for fire attack. It emphasizes using thermal cameras for rapid intervention teams and cautions about potential traps during contingencies. Practice with thermal imaging cameras at every fire is encouraged to gain competence.
El documento presenta un plan de emergencia y evacuación para una institución educativa. Explica conceptos como emergencia, riesgos, y evacuación. Detalla los roles de directivos, personal docente y no docente, alumnos, bomberos y policía en el plan. Incluye secciones sobre organización, capacitación, evaluación e inspección de equipos. Presenta procedimientos para diferentes tipos de emergencias como incendios y sismos.
DEG Licht GmbH produces blue spot safety lights that can be installed on forklifts to warn warehouse personnel of approaching vehicles. Statistics show that 19% of accidents in warehouses are caused by a lack of warning signaling. The blue spot lights project a focused beam of blue light in the direction of travel, allowing workers to see and avoid moving forklifts even outside of their field of vision. This can help reduce accidents by 19% according to one case study. The lights are durable and can withstand wide temperature ranges and harsh environments common in warehouses.
Exposure to an arc flash (the sudden release of heat and light at an electrical fault) frequently results in serious injury, even to workers several feet away from the arc center. Both NFPA and OSHA have specific requirements to address the risk of arc flash injuries.
This bulletin provides sources of information on NFPA, OSHA and ANSI standards related to arc flash hazards, and also describes the approved design of arc flash safety signs and labels.
1. Power tools present greater hazards than hand tools due to their higher speeds of operation. Proper personal protective equipment (PPE) is important for safe use of power tools.
2. Eye protection like safety glasses or goggles is especially important for power tools, as their moving parts can propel small particles faster than hand tools. A face shield is recommended when using tools like grinders due to hot metal particles.
3. Standard work gloves protect hands from minor cuts but not moving blades. Cut-resistant gloves do not protect from moving parts. The best protection is keeping hands on tool handles and guards in place. Anti-vibration gloves reduce vibration from tools like hammer drills.
This document provides guidelines for protecting commonly used interfaces from electrostatic discharge (ESD) and transient voltages. It discusses ESD protection considerations and solutions for automotive interfaces like CAN, LIN, and FlexRay. It also covers general input/output, serial buses, displays, Ethernet, and radio frequency interfaces. For each interface, example protection circuits are shown along with NXP's recommended protection devices that offer high ESD robustness and minimal impact on signal integrity.
This document discusses facility electrical protection solutions from ERICO. It begins by outlining the risks facilities face from lightning strikes, which cause billions in damages annually. It then discusses ERICO's comprehensive approach to facility protection, considering lightning protection, grounding, bonding, and surge protection together. The document provides information on ERICO's products and services for lightning protection air terminals and downconductors, grounding and bonding solutions, surge protection, and design services. It presents ERICO's Six Point Plan for total facility protection and discusses applications for key industries like power generation, telecommunications, aviation, oil and gas, mining, and rail.
The Altair 4X multigas detector provides significant cost savings and safety benefits compared to other detectors. It has a 4-year sensor life and 3-year warranty, reducing replacement and maintenance costs by over 50%. Additional features like motion and instant alarms improve worker safety. The durable design withstands tough industrial environments.
The document provides guidelines for properly labeling electrical equipment to warn of arc flash hazards, in accordance with NFPA 70E and OSHA standards. It recommends labeling with a single worst-case scenario that lists the highest potential incident energy and required PPE. Multiple labels or labels listing varying energy levels/PPE can confuse workers and increase liability. ANSI-standard triangle warning labels are suggested over customized labels. Proper labeling warns of hazards but does not replace the need for work permits, safety programs or training when working on energized equipment.
This document discusses service life recommendations for various types of personal protective equipment (PPE) such as safety glasses, hard hats, harnesses, lanyards, and ropes according to OSHA regulations and manufacturer specifications. It finds that while OSHA does not mandate specific service life durations, manufacturers provide various guidelines ranging from 1 to 10 years depending on the frequency and conditions of use. In general, harnesses and hard hats should be replaced every 5 years, ropes between 2-5 years, and all equipment should be retired if damaged, deteriorated, or exceeding 10 years of age. Inspection criteria and manufacturer guidance take precedence over time alone in determining necessary replacement of PPE.
This document provides instructions for installing and using the LoRa Technology Evaluation Suite, which allows users to evaluate Microchip's LoRa wireless technology. The suite includes a utility application for connecting to LoRa devices, as well as a server application and required redistributables. Users are guided through installing the suite components, setting up a virtual machine environment, launching a Docker container to host the server, and connecting LoRa development devices to evaluate the wireless performance and capabilities. The document also provides overviews of the utility and server applications and their basic functions.
Key considerations when switching to miniature connectorsDesign World
Join us for this panel webinar, in which industry experts will provide insight on selecting, specifying and using miniature connectors safely and reliably in your system designs. Our panelists include David Ptacek, national sales manager and US product manager for Fischer Connectors’ MiniMax series; Steven Lassen, Products and Applications Manager, LEMO USA; Mike Higashikawa, Regional Product Manager, Micro Products Division for Molex Incorporated; and Brendan Dempsey, Business Development Manager at ODU-USA.
Our panel will discuss some of the challenges and misconceptions associated with miniature connectors, covering everything from EMI/EMC to robustness and mating reliability to common applications.
Personal protective equipment.........aryaarya das
This document discusses personal protective equipment (PPE) and focuses on eye and face protection. It notes that nearly 2 million people receive disabling work injuries each year, with over a quarter involving the head, eyes, hands or feet. PPE is designed to protect workers from hazards like chemicals, radiation, impacts and more. The document outlines OSHA standards for employers to assess hazards, provide necessary PPE and training. It details types of eye and face protection like safety glasses, goggles, face shields and welding helmets and notes criteria for selecting the right protection for specific hazards.
Here is our first class work to be posted in our blog.This is Diego Mena's presentation about his father's work. He is a fireman in our town, Benalmádena.
Diego's class is 6 B.
Screen shot from latest customer install shows detailed heat map GUI. Sensors were polling live data within an hour of installation. Another happy customer.
Allied International Emergency provides rescue services across North Central Texas, West Texas, New Mexico, and Southern Oklahoma. Their mission is to provide experienced, certified rescue professionals who adhere to stringent training requirements including EMT certification and 5 years of experience. Their rescue teams are trained to OSHA, NFPA, and other standards to handle confined space and hazardous environment rescues involving risks like entrapment, engulfment, and toxic atmospheres. They focus on safety from consultation through implementation of rescue plans.
Los bomberos en Francia incluyen 248,300 bomberos, 80% de los cuales son voluntarios. Los bomberos operan en ciudades y aeropuertos. El programa JSP permite que jóvenes estudien para convertirse en bomberos voluntarios o profesionales a través de 4 años de entrenamiento físico y académico para obtener un diploma.
El documento describe la importancia de cumplir con las leyes de seguridad e higiene en el trabajo relacionadas con la conformación de brigadas contra incendios, la elaboración de planes de evacuación y la realización de simulacros. También resalta la responsabilidad de los empleadores y profesionales intervinientes en dichos planes.
Firefighter turnout gear consists of a helmet, face mask, gloves, self-contained breathing apparatus, turnout jacket, bunker pants, and boots to protect firefighters from heat, flames, and hazardous materials. The gear uses reflective safety stripes and a self-contained breathing apparatus to keep firefighters safe even in dangerous situations.
The document provides an operations manual for a Rapid Intervention Team (RIT) air pack developed by the Fairfax County Fire & Rescue Department. The RIT pack was designed to address shortcomings in previous models and features components that allow it to supply air to multiple firefighters. It can receive supplemental air from vehicle cascade systems or in-line manifolds. The manual describes the RIT pack's components, daily checks, decontamination procedures, maintenance, and operational roles at different emergency response levels. RIT packs are assigned to rescue vehicles and used to provide air to firefighters until a downed firefighter can be removed from danger.
The document provides an overview of the Princeton Fire Department, including its purpose to educate citizens, roles, budget, operations, and trends. The department's roles include fire protection, suppression, and emergency medical services. It operates one fire station and responds to over 2000 calls annually within its 90 square mile fire district. The budget comes from various sources like ambulance billing and rural fire district taxes, and is used to fund operations and purchase vehicles and equipment.
The document discusses the use of thermal imaging cameras for firefighting tactics including primary search, fire attack, rapid intervention teams, contingencies, overhaul, and the importance of practice. It notes key uses like engine or ladder search patterns for primary search and using thermal layers to find a safe path and fire location for fire attack. It emphasizes using thermal cameras for rapid intervention teams and cautions about potential traps during contingencies. Practice with thermal imaging cameras at every fire is encouraged to gain competence.
El documento presenta un plan de emergencia y evacuación para una institución educativa. Explica conceptos como emergencia, riesgos, y evacuación. Detalla los roles de directivos, personal docente y no docente, alumnos, bomberos y policía en el plan. Incluye secciones sobre organización, capacitación, evaluación e inspección de equipos. Presenta procedimientos para diferentes tipos de emergencias como incendios y sismos.
This document defines smoke and describes the four key attributes of smoke - volume, velocity, density, and color. It explains how reading these attributes can help firefighters understand fire behavior and look for signs of potential hostile fire events like flashover. The document outlines the three-step process for reading smoke: 1) view the smoke attributes from each opening, 2) analyze contributing factors, and 3) determine the rate of change in attributes, which indicates risk to firefighters.
This document discusses how to call and respond to a Mayday distress call as a firefighter. It explains that a Mayday call should be used in emergencies when help is needed, such as during a collapse, fire, or when trapped or lost. The document outlines the steps to call a Mayday, which include transmitting "Mayday, Mayday, Mayday" on the radio, waiting for a response and if none, repeating the call. It also describes using the L.U.N.A.R. protocol to provide location, unit number, name, assignment and resources needed in the response. Firefighters are advised to practice using radios and mentally prepare for Mayday calls.
This document describes the Pittsburgh Drill, which is used to train Rapid Intervention Teams (RITs) to work as an effective team. The drill involves navigating a 150-175lb dummy through a 50ft obstacle course within 20 minutes while on air supplies. Obstacles include climbing over and under obstacles while maintaining the dummy's facemask and air supply. Faster times demonstrate better teamwork and fitness for rescuing firefighters in distress. The current record time is 6 minutes 30 seconds.
Electricity is the second leading cause of death in construction, accounting for over 600 deaths annually. Proper safety procedures and equipment are required to prevent electrical accidents and injuries. Key risks include contacting energized power lines or equipment, using defective tools or cords, and failing to follow lockout/tagout procedures to de-energize circuits before working. Proper grounding, GFCI protection, insulation, and avoiding overloads are vital for electrical safety.
The document discusses how firefighters can prevent Mayday situations through proper situational awareness and training. It describes past line-of-duty deaths where firefighters lacked awareness of changing conditions or needed skills like calling a Mayday. The document outlines how to assess smoke conditions, maintain orientation, recognize worsening fire behavior, and communicate on the fireground to continuously evaluate risk. Maintaining awareness of construction hazards, preplanning buildings, and coordinating efforts between crews can help firefighters operate safely and avoid becoming trapped.
This document discusses the use of thermal imaging cameras (TICs) for firefighter search and rescue. It provides background on how TICs work using infrared technology to see heat signatures. It outlines the basic principles, limitations, and different types of searches that can be conducted with a TIC, including TIC lead searches and landmark searches. The document explains concepts like thermal contrast and image inversion that are important to understand when interpreting TIC images. It also provides specifics on operating the Scott Eagle Imager 160 TIC. The overall purpose is to educate firefighters on how to properly utilize TICs for rapid intervention and locating trapped firefighters.
- Rapid intervention teams (RIT) are required by OSHA regulations to enter immediately dangerous areas to rescue firefighters in distress.
- Studies show it takes an average of 12 minutes to reach a downed firefighter and 22 minutes total to rescue them. Rescues are made more difficult without proper planning and training.
- Proper pre-fire planning, including identifying potential structural hazards, can help commanders deploy RIT teams more effectively to rescue trapped firefighters. Standardized firefighter training in survival skills also improves rescue outcomes. Strict discipline is needed to ensure rescuer safety during stressful rescue operations.
This document outlines standard operating procedures for Rapid Intervention Teams (RIT) and "MAYDAY" procedures. It defines key terms like IDLH and Incipient Stage Fire. It describes RIT composition and duties to track and rescue emergency personnel. It provides guidance for RIT implementation, including equipment, tracking entry teams, and deploying for a trapped firefighter. It also covers procedures for a firefighter to call a MAYDAY and the required response from command and other crews.
The orientation covered the employer, chain of command, battalions, probationary firefighter expectations and milestones, training requirements, general expectations of probationary firefighters, department functions, fire station policies, health and safety, responding to calls, personal vehicles, miscellaneous policies, and radio/PPE use. Probationary firefighters are expected to learn, gain the respect of officers, complete required training, and serve a minimum one-year probationary period before becoming full firefighters. The orientation overviewed the department's structure and policies to prepare new recruits.
El blog describe el servicio de bomberos de la ciudad de Alcorcón, España. Los bomberos de Alcorcón trabajan para proteger a los 166,553 habitantes de la ciudad y responder a emergencias como incendios.
The document is a catalog from Lind Equipment that describes their hazardous location lighting products. Lind Equipment is an expert in portable electrical equipment for hazardous work environments and has been providing explosion proof lighting and other safety equipment for over 60 years. The catalog includes information on their hand lamps, floodlights, string lights, and other hazardous location lighting products. It provides details on the construction, approvals, and options for each product.
Cordex Instruments - IR Window Transmission Guidebookdegarden
This document provides an overview of infrared transmission and how different infrared window types affect temperature readings. It discusses the factors that influence transmission, including reflection, absorption, and the spectral properties of windows and cameras. The document emphasizes that single-point calibrations are not accurate across a range of temperatures and advocates for multi-point calibrations to achieve accurate readings. It also notes that correction maps must be individualized for each infrared window.
3 m edge eg5 intrinsically safe user manual (053 669 rev i)Home
Here are the typical steps to perform a noise assessment with the Edge dosimeter:
1. Identify tasks, jobs, or areas of concern that may have high noise exposure levels. Perform a walk-through and observe worker tasks.
2. Select monitoring locations based on the task analysis. Place the dosimeter on workers in those areas.
3. Program the Edge dosimeter settings based on the relevant noise regulations (e.g. OSHA, MSHA). Configure parameters like run type, criteria levels, exchange rates.
4. Train workers on how to wear and operate the dosimeter properly. Ensure a tight, secure fit on their person.
5. Start monitoring runs when workers enter areas of concern
Aiditec Systems is an innovative technology company specializing in lightning protection systems. They research, develop, manufacture, and distribute advanced lightning protection products. The document discusses their ESE Advance lightning rods. These rods incorporate new technologies to maintain insulation between electrodes and ensure quick deionization after strikes. They have passed certification tests for early streamer emission rods and provide protection radii guarantees. The rods' isolating rain system ensures operation even in extreme rain conditions through insulating sleeves around the electrodes.
Hazardous work areas present special challenges for the workers and businesses that must operate within them. These work areas are often confined rooms or containers like fuel tanks where vapors and gases from work activities can become concentrated to dangerous levels. As well as the obvious dangers posed by inhalation of these contaminants are the not so obvious dangers that can have lethal consequences if not properly addressed. Intrinsically safe lights which are defined by Underwriter Laboratories as basically any electronic circuit that is “incapable” of causing ignition, which puts them in an ultra-high classification outside that of explosion proof lights. When working in confined spaces such as but not limited to boilers, pressure vessels, cargo holds, cargo tanks, ballast tanks, double bottoms, double hull spaces, fuel oil, lube oil, sewage-tanks, pump-rooms, compressor rooms, cofferdams, void spaces, duct keels, inter-barrier spaces and engine crankcases, etc. rely on the Intrinsic safety lighting range from Nightstick. PSC are the official distributors of NightStick for Indian Markets.
A large multinational manufacturer faced challenges detecting sophisticated attacks within its global IT environment and protecting its intellectual property. It used an active monitoring service and Symantec but failed to detect a breach. After a proof of concept where Cybereason detected an APT, the manufacturer deployed Cybereason across 30,000 endpoints. Cybereason provided improved detection of attacks through behavioral analysis, broad visibility of global endpoints, and more efficient investigation through automation compared to the manufacturer's previous solutions.
The document provides information about Cortem Group, an Italian company that specializes in explosion-protected electrical equipment. It discusses Cortem's 40+ years of experience, its product lines including lighting fixtures, junction boxes, and control panels. It also covers Cortem's certifications, quality standards, worldwide partners and distributors, and customized engineered solutions.
Intrinsic safety is a technique used to prevent explosions caused by sparking electrical apparatus in hazardous areas. It works by using safety barriers between safe and hazardous areas to prevent faults from generating high energy sparks that could ignite explosive mixtures. Intrinsically safe circuits are designed and implemented to not produce any sparks at all. Simple low power devices like thermocouples can be used without barriers in hazardous areas. Intrinsic safety is the preferred method for zone 0 areas and offers flexibility in circuit design while eliminating explosion proof junction boxes. However, it is limited to low power applications like instruments and controls.
The document is a user manual for ThermTec's Hunt Series thermal clip-on device. It provides instructions on safely using the device, including not pointing it at intense heat sources. It also details features like the 12μm thermal imaging detector, 1024x768 resolution OLED display, and IP67 protection rating. The manual covers device components, menu operation, recording and sharing capabilities, and maintenance guidelines.
Fire Safety Network for Fertilizers Industries.pdfPremBaboo4
Fire network & Fire prevention device with fire station is essential for all industries. The fire Industries have very dangerous substances and gases that can catch fire at any time. Most of the accidents/injuries are caused by human errors. Industry says, human error accounts for 96% of accidents. The rest takes place due to external conditions and failure factory equipment. In which fertilizers industries account for most of such fatal accidents. Safety is a condition or state of being resulting from the modification of human behavior, and/or designing of the physical environment to reduce the possibility of hazards, thereby reducing accidents. Safety is an ever changing condition in which one attempts to minimize the risk of injury, illness or property damage from the hazards to which one may be exposed. Perfect fire network is must for fertilizers Industries. Life is god's special gift to mankind. It is therefore important to treasure & protect it from all kinds of potential threats. Regardless of the precautions that we take in our day-to-day life, fire accidents are seldom averted. Risky jobs with a potential to put your life at risk can be a cause for concern especially to your family & friends. Moreover,constant exposure to dangerous surroundings increases the chances of enduring major/minor injuries with a likelihood of developing a permanent handicap.
This document provides product information for intrinsically safe lighting products offered by Project Sales Corp. It includes specifications for several flashlight and penlight models that are certified for use in hazardous locations where explosive gases may be present. The document also provides background information on intrinsically safe lighting and definitions of related terms. Project Sales Corp offers over 100 product lines for head-to-toe protection and workplace safety.
Smart Helmet for Industrial Workers SafetyIRJET Journal
This document describes a smart helmet prototype designed to improve safety for industrial workers. The smart helmet contains sensors to measure environmental factors, detect hazardous gases, monitor head impacts, and track the wearer's location. It is connected to monitoring systems via WiFi to provide real-time safety alerts and feedback. The goal is to prevent injuries by providing enhanced visibility, awareness of dangers, and emergency notifications. Key sensors in the prototype include temperature/humidity, gas, air quality, and MEMS sensors connected to a microcontroller. The smart helmet aims to address common industrial hazards while maintaining a lightweight and low-power design suitable for industrial settings.
How to Select an Intrinsically Safe Pressure TransducerSetra Systems
Engineers selecting pressure transducers in hazardous industries must make one more significant consideration beyond performance, reliability, and stability-they must specify units with intrinsically safe circuits. The National Electrical Code defines an intrinsically safe circuit as, "A circuit in which any spark or thermal effect is incapable of causing ignition of a mixture of flammable or combustible material in air under prescribed conditions." In addition, intrinsically safe products are incapable of storing large amounts of energy that might spark an explosion when discharged. These circuits must be used wherever there are combustible gases, vapors, liquids, dust, and/or fibers.
This paper discusses what industries and applications require intrinsically safe systems and the technical considerations for specifying an intrinsically safe pressure transducer.
To turn on the power, press and hold the [POWER/BRILL] key until the startup screen appears. To turn off the power, press and hold the [POWER/BRILL] key until the unit turns off.
1.4 Transmitting, Standby
To transmit radar pulses, press the [MODE] key to select TX. To stop transmitting and receive only, press the [MODE] key to select ST-BY.
1.5 Adjusting Display Contrast, Brilliance
Momentarily press the [POWER/BRILL] key to open the Contrast/Brilliance/Mode dialog box. Use the cursor pad to adjust contrast and brilliance. Press [MENU] to close the dialog
The document discusses fires in automotive manufacturing facilities and solutions for fire detection. It begins by describing devastating fires at BMW and automotive supplier plants and the consequences of disruption. It then discusses the risks of fires from manufacturing processes and standards for fire detection technology in the UK. Finally, it summarizes three key detection options - infrared, aspirating smoke detectors, and video smoke detection - and their effectiveness in the automotive sector.
Inspecting facilities with infrared imaging can improve productivity, safety, and employee morale in three key ways:
1) Infrared inspections can locate potential problems before new systems start up, helping with system testing and lowering equipment replacement costs.
2) Infrared inspections allow maintenance priorities to be set and the quality of repairs to be evaluated, extending equipment life.
3) By enabling predictive maintenance through early problem detection, infrared inspections create a more efficient maintenance program and a stable work environment, boosting employee morale.
Instruction Manual ARMASIGHT DISCOVERY Series NV Binoculars | Optics TradeOptics-Trade
This document provides instructions for preparing and operating the Armasight Discovery night vision bi-ocular. It describes the key parts of the device, specifications for different models, and safety warnings. Users are advised to avoid exposing the device to bright light or moisture, and only use it in low-light conditions with some ambient illumination. The manual outlines proper battery installation and provides tips for safe handling and storage to ensure long-term performance.
Laser Safety Eyewear Product Catalog by Kentek CorporationJustin Clough
Kentek Corporation is respected worldwide as an important source for all laser safety products and services. Kentek offers custom and stock products.
Understanding your laser protective eyewear needs, at Kentek, we know that no two faces are alike, so we can help make your eyewear choice as easy as possible by offering the widest selection of frames and filters.
The document discusses the need for lightning protection systems and describes their key components. It explains how lightning occurs through the separation of positive and negative charges in thunderclouds. Lightning protection aims to control the passage of lightning by capturing strikes on air terminals and safely directing the energy to ground. The document compares methods for determining where to place air terminals, such as the Rolling Sphere Method, and describes the functions of air terminals, downconductors, and grounding systems that make up an effective lightning protection installation.
Similar to 10 Things You Need To Know About Ir Windows Iriss (20)
1. 1 T ig Y u e d o n w
0 hn s o N e T K o
A o tnrrd n o s
b u If e Wid w
a
2. Chapter List
Foreword..................................................................................................................................................................................................................................ii
1. What is an Infrared Window?.............................................................................................................................................................................. 1
2. Infrared Window Lens Materials . .................................................................................................................................................................... 3
3. The Importance of Emissivity in Electrical Thermography . ......................................................................................................... 7
4. Know Your IR Window Transmission ......................................................................................................................................................... 11
5. Field of View (FOV) Through an Infrared Window ........................................................................................................................... 16
6. Proper Installation of an Infrared Window ........................................................................................................................................... 20
7. Certifications and Standards .......................................................................................................................................................................... 25
8. Arc Flash, NFPA & OSHA: Implications on Infrared Inspections ............................................................................................. 29
9. Infrared Window Program Benefits ........................................................................................................................................................... 32
10. Infrared Window Cost-Benefit Analysis . .............................................................................................................................................. 35
i | iriss.com 10 Things You Need To Know About Infrared Windows
4. Chapter 1
What is an Infrared Inspection Window?
Definition:
A window is used to separate environments of differing pressures or temperatures, while allowing
energy at a specified electromagnetic wavelength to pass between the two environments.
An infrared window (also referred to as a viewport, viewing pane, sightglass, port or grill) is a generic
term used to describe an inspection point that is designed to allow infrared radiation to transmit to the
outside environment. Simply put, an infrared (IR) window is a data collection point for a thermal camera.
All IR windows must fulfill the strength, rigidity and environmental requirements of the type of
equipment into which it is installed. It must also be compatible with the infrared equipment being used.
Some IR windows are simply a housing with an open center, and a cover that secures the opening.
Typically, the IR window housing will contain a grill or an optic. The design, size, and material used
are driven by considerations such as the required field-of-view, camera lens compatibility, intended
environment, sealing requirements, and safety considerations.
Infrared Window Classification:
Let’s explore the specific types of infrared
windows:
Viewing Panes
A viewing pane is an IR window that has a
lens secured in the housing. Because the lens
forms a seal between the internal/external
environments, the thermographer is not
directly exposed to energized components
(as per NFPA 70E/CSA Z462 definitions of
“enclosed” and “guarded”). This usually means
that elevated levels of Personal Protective
Equipment (PPE) are not required.
Inspection Grills
An inspection grill is an infrared window
containing a grill or “mesh” in place of a solid
optic. Grills are primarily used in mechanical
applications for machinery guards, or in
instances where operators wish to complete
infrared and ultrasound inspections from the
same access point. As the name implies, when
opened, a grill does not maintain an IP65/NEMA
4 seal; instead, it is a collection of small
openings intended to keep fingers and tools
from breaking the plane of the cabinet. It is
important to understand that a grill will not
maintain an enclosed state for electrical
equipment since it allows the environment of
the energized components to change. Therefore, they would not maintain an “enclosed” condition per
NFPA 70E/CSA Z462, and as such, elevated PPE levels are required per NFPA 70E/ CSA Z462 mandates.
1 | iriss.com 10 Things You Need To Know About Infrared Windows
6. Chapter 2
Infrared Window Lens Materials
There are numerous types of lens materials that can be used in infrared (IR) windows. The specific choice
is usually driven by the application, environment, wavelength, and cost considerations. For example, a
mid-wave R&D application with high ambient temperature requirements may use materials that would
be unsuitable for long wave condition monitoring of industrial applications.
Table 1 details a partial list of possible materials, but not all are suitable for use as an IR window lens.
Table 1: Materials used in IR industry
What is the best Material for an Infrared Window?
Germanium and Zinc Selenide are among the best broadband infrared transmitters available. Sapphire
is a great transmitter in the mid-wave (MWIR) spectrum (sometimes referred to as “short wave”). It is
incredibly durable – yet is non-transmissive in the long wave (LWIR). Ultimately there is no easy answer to
this question because it quite simply depends on the application. In the end, thermographers must give
serious consideration to the IR window’s intended use and operating environment – installing windows
that are not compatible with the intended environment could prove to be a costly exercise should they
fail mechanically or functionally.
Does durability matter?
Will the windows be handled by scientists who will treat the optics like fragile lenses? Or will they be
attached to electric panels that will be removed periodically and placed on cement floors during “house
cleaning” shutdowns?
Mechanical stresses can fracture most crystal optics or degrade the crystalline structure, increasing
refraction and decreasing transmittance. The stresses can take the form of jarring drops, exposure to
high frequency noise or harmonics, or even exposure to environmental vibration. Incompatibility with
mechanical stress is one big reason why most crystals are not considered suitable for industrial
applications and uncontrolled environments.
3 | iriss.com 10 Things You Need To Know About Infrared Windows
8. Chapter 2 CONT’D
However, you don’t need a formula to understand the
concept. If you have ever broken a stick over your knee, you Modulus of Rupture
know it is much easier to break a longer stick than it is to (psi) for Crystals Commonly
break a smaller piece of the same stick. The same is true of Used in IR Windows:
crystals – the bigger the crystal the more fragile it
becomes, unless the thickness of the crystal is increased. BaF2 3,900
However, be aware that increasing the thickness of the CaF2 5,300
materials will decrease the transmittance of that material ZnSe 8,000
and will affect temperature readings (see Chapter 3 for Ge 10,500
details). Sapphire 65,000
The graph below traces the minimum thickness required for
a Calcium Fluoride crystal to resist a given pressure level. Table 3
Table 4: Modulus of Rupture calculations for Calcium Fluoride at various diameters
As Table 4 illustrates, if CaF2is capable of resisting 14.7 psi (1 atmosphere) of pressure, the minimum
thickness required for a two-inch diameter crystal is 2.8mm; a three-inch diameter crystal should be 4.2
mm thick; and a four-inch diameter crystal should be 5.6 mm thick. It is worth noting here that Arc Resis-
tant Switchgear is typically set so that plenum vents open at just 25 psi to redirect the blast forces away
from panels where personnel would be interacting with the equipment. At 25 psi (the minimum force
which a crystal window optic would experience during an arc incident) the two-inch crystal would have
to be 3.7 mm thick; a three-inch crystal would have to be at least 5.5 mm thick; and a four-inch crystal
would require a minimum thickness of 7.3 mm to maintain its integrity. Thinner Calcium Fluoride would
shatter. Unfortunately, no crystal IR windows are even close to that thickness. Therefore, any claims by a
crystal manufacturer to resist the effects of an arc apply only to the integrity of the window housing with
the cover closed, and do not (and cannot) apply to the integrity of the fragile crystal.
5 | iriss.com 10 Things You Need To Know About Infrared Windows
10. Chapter 3
The Importance of Emissivity in Electrical Thermography
A typical factory is full of equipment that requires periodic infrared (IR) inspection. The challenge, as any
thermographer knows, is getting an accurate indication of equipment health. Properly compensating for
the various emissivity values of all the components one encounters on the factory floor is possibly the
most critical factor in performing accurate and meaningful inspections. Even slight errors in emissivity
compensation can lead to significant errors in temperature and ΔT (difference in temperature)
calculations. Electrical cabinets are a good example, as they may contain materials with emissivity values
ranging from 0.07 to 0.95.
The Science of Infrared Thermography
The electromagnetic spectrum is a continuum made up of cosmic rays, gamma rays, X-rays, ultraviolet
light, visible light, infrared radiation, microwaves and radio waves (in order of increasing wavelength and
decreasing power). Infrared is that portion of the spectrum between 0.75μm (microns) and 1000μm in
wavelength, starting just beyond what the human eye is capable of seeing.
All objects above absolute zero emit infrared radiation. As an object heats up, the intensity of emitted
radiation increases exponentially (Stephan-Boltzmann’s Law) and the peak radiation shifts to shorter and
shorter wavelengths (Planck’s Law), moving eventually into the visible spectrum. This is why a hot burner
will glow red (“incandescent”) after it achieves roughly 500°C (923°F).
Figure 1
Today’s radiometric IR imagers are capable of “seeing” and calculating the emitted radiation from a target
object. There are only three sources of this radiation: it can be reflected from other sources; it can be
transmitted through the object from a source behind it; or the radiation can be emitted by the object.
Kirchhoff’s Law
An extension of Kirchhoff’s Law tells us that the sum of the radiation leaving the surface of an object
equals one: expressed as Watts Emitted + Watts Transmitted + Watts Reflected = 1 (or ε+τ+ρ=1).
7 | iriss.com 10 Things You Need To Know About Infrared Windows
12. Chapter 3 CONT’D
The graph in Chart 1 shows how
calculated temperatures can be
adversely affected when the
imager’s emissivity value is set
too high. In this example, the
emissivity of the target is 0.50;
the graph shows the apparent
temperature when the imager’s
emissivity setting is stepped
down from 1.0 to 0.50. When
emissivity is properly compen-
sated for, the actual temperature
is shown to be 12.2° higher.
Magnitude of Error
One of the most misunderstood
Chart 1 concepts in thermography is the
degree to which errors in
emissivity settings (and errors in window transmissivity compensation) will affect temperature and ΔT
(difference in temperature) accuracy. As demonstrated by the Stefan-Boltzmann Law (Figure 5), the
radiated infrared energy emitted by a target surface is exponentially related to the absolute temperature
of that surface.
Therefore, as the temperature increases, radiant
energy increases proportionally by the absolute Stefan-Boltzmann Law
temperature to the 4th power. Incorrect camera
settings such as emissivity and infrared window W = εσΤ4
transmission rates will result in errant temperature
values. Furthermore, because the relationship is Whereas:
exponential, this error will worsen as the component W = Total Radiant Power in Watts/m2
increases in temperature. Consider the effect on ΔT ε = Emissivity (unitless)
comparisons, which are by their nature a comparison σ = Stefan-Boltzmann Constant
between different temperatures. The resulting (1.56X10-8W/m2K4)
calculations are apt to be radically understated, which T4 = Absolute Temperature in Kelvin
could easily lead thermographers to misdiagnose the
severity of a fault. Figure 5
Emissivity Standardization
For some components, it can be difficult to determine the correct emissivity value. In the case of a
highly polished component like a bus bar, the actual emissivity may be so low as to make temperature
measurement impractical. It is strongly recommended that thermographers understand the surface of
the primary targets. Once identified, those surfaces should be treated with a high-emissivity covering so
that all targets have a standardized emissivity. Thermographers can apply electrical tape, high-tempera-
ture paint (such as grill paint), or high-emissivity labels (like the IR-ID labels from IRISS). When all targets
have a standard emissivity, refection issues are minimized and measurement errors from reflected
ambient energy are greatly reduced. High-emissivity targets of varying shapes can also provide a useful
point-of-reference both for the thermographer and the technician making repairs.
9 | iriss.com 10 Things You Need To Know About Infrared Windows
14. Chapter 4
Know Your Infrared Window Transmittance
Maintenance professionals can use infrared (IR) cameras to take both qualitative (image only) and
quantitative (temperature measurement) images. To ensure that quantitative images are accurate,
it is important to understand what other variables in the external environment can lead to possible
measurement errors.
In addition to reflection and emissivity, distance, humidity and camera angle can all play an important
role in accurate temperature measurement. But when thermographers use IR windows, improper
window transmission compensation can easily affect apparent temperature and apparent ΔT calculations
by 30% and more.
Infrared inspection windows have become an industry standard way to facilitate infrared electrical
inspections while increasing both the safety and the efficiency of the inspection process. While window
optics can be made of a variety of different materials, they generally fall into one of two categories:
crystal or polymer. It is important for the thermographer to know the transmission rate of the window
being used. However, some crystal windows that look similar might actually be made from different
materials, causing the transmission rates of two apparently similar windows to be very different. Even the
same crystal material from the same manufacturer may be cut to different thicknesses. This difference
will cause the thicker crystal to have a lower transmission rate than a thinner lens of the same material.
These potential sources of variation underscore the importance of understanding the characteristics
of the inspection window being used.
The graph in Chart 1 below demonstrates the degree to which transmission rates of different materials
will change across the IR spectrum. Note that some materials will be unsuitable for use with a LW camera
(as is the case with sapphire, Al2O3). Other materials, such as Zinc Selenide (ZnSe) are well suited for use
with both MW and LW – these materials also tend to be more expensive for that reason.
Chart 1
11 | iriss.com 10 Things You Need To Know About Infrared Windows
16. Chapter 4 CONT’D
All window optics will filter, or “attenuate” the
amount of infrared radiation that ultimately The “Coffee Cup Test”
reaches the imager. Our research shows that for
calcium fluoride windows the attenuation A simple way to check the transmission rate,
reduces the temperature about 5% for every of an IR window is to do the “coffee cup test”.
millimeter of window thickness (temperatures Note that this test should be completed both
in the range of 60°-120°C). In addition, tilting on initial install – and during regular window
the camera angle 30° to either side of 90° maintenance for windows that use materials
(perpendicular) reduces the temperature that are known to degrade over time.
by an additional 2-3%.
1. Get a cup of warm water, and place a target
Compensate for Transmission of known emissivity on the cup surface
A simple way to check transmission rate, (electrical tape, emissivity label).
is the “Coffee Cup Test” (see Table 3). After
determining the proper transmission rate of a 2. Set the camera’s transmission (if available)
window, make a note of that value and adjust and Emissivity to 1.0.
the camera’s transmission rate (or emissivity
setting) accordingly each time that window is 3. Measure the temperature of the target
used for an inspection. without the window.
The majority of infrared cameras do not have 4. Place the window in front of the camera
the ability to compensate for transmission and complete the exercise again.
losses from an IR window directly; but almost
all software packages do. To make a quick 5. Using either the camera, or the camera
adjustment in the field, simply multiply the reporting software, change the transmission
transmission coefficient by the target emissivity coefficient on the image until the adjusted
to arrive at a “calculated emissivity value,” and temperature is the same as the original
adjust the camera’s emissivity setting to this image temperature.
value. For example, an IR window with a 0.55
transmittance rate and a target with an 6. Record the new transmission rate on the
emissivity of 0.95 (electrical tape) would require window label and in the report template
a camera emissivity setting of 0.49 (0.90 x 0.55 = for future use.
0.495) to properly compensate for both
transmission and emissivity.
Degradation
Once the transmissivity coefficient has been properly determined for an application, it is important to
realize that coefficients of some materials can change over time. Crystals, in particular, are susceptible to
mechanical stress from high frequency noise and vibration. Some crystals, such as those in the Fluoride
family are also hydroscopic; meaning that they will absorb moisture, humidity or industrial solvents
(despite the fact that they are coated with materials to slow the inevitable degradation process). These
mechanical stresses and absorption characteristics of crystals will degrade a crystal window’s
transmission rate over time.
A recent paper on the topic of transmission degradation (“Transmission Stability and Infrared Windows”
by Joe DeMonte) illustrates how this degradation can affect the data accuracy. The research compared a
Calcium Fluoride infrared window to a polymer-based window. Both windows were shown to have a 50%
transmission rate when new. After just two years in a non-aggressive environment, the transmission rate
of the calcium fluoride window had dropped significantly.
13 | iriss.com 10 Things You Need To Know About Infrared Windows
18. Chapter 4 CONT’D
Summary
1. Know the characteristics of the infrared window optic as it pertains to the wavelength of your
camera (MW versus LW).
2. Test the IR window transmittance and document the result.
3. Compensate for the transmission attenuation for accurate temperature calculations.
4. Re-test each window’s transmission rate if the material is known to degrade over time (as with
most crystal optics).
5. Include the windows in the general maintenance of the equipment to which it is attached.
15 | iriss.com 10 Things You Need To Know About Infrared Windows
20. Chapter 5 CONT’D
The illustration in Figure 1 shows the area inside a cabinet that can be viewed through an IR window
using a camera with an 82° FOV lens. A typical switchgear compartment is 20 inches deep, therefore:
D = 2d x (tangent of 41°)
D
D = 2*20 x 0.87 = 34.8 inches
Visible Area Surface
d
IR Window
Panel Cover 41°
Figure 1: Standard FOV calculation
with fixed viewing angle
The calculations in Figure 1 indicate that with an 82° FOV lens, a thermographer can view 34.8 inches
horizontally inside the panel. However, this calculation assumes the thermographer holds the camera
fixed and perpendicular to the window plane. More likely, the thermographer will vary the viewing angle
up to 30° from perpendicular in all directions. This effectively increases the FOV area by a factor of three.
Camera Angled for
2X standard FOV
D = (2*20) x 0.87 x 2
D = 69.6 inches
D = Visible Area
Camera Angled for
3X standard FOV
D = (2*20) x 0.87 x 3
D = 104.4 inches
d = cabinet depth or target distance
Figure 2: Standard FOV calculation
(varying the viewing angle)
17 | iriss.com 10 Things You Need To Know About Infrared Windows
22. Chapter 5 CONT’D
8. Record the results in a table like the one shown in Figure 4. (Note that these figures were taken using a
FLIR P65 IR Camera.) This FOV matrix was calculated using the above technique and then multiplied
by a factor of 3 to give the total WFOV through each type of IRISS IR Window, allowing for roughly a 30°
angle of incidence. Keep your matrix with the camera for future reference.
IR Target Tip: Most thermographers will take FOV
VP50 FOV VP75 FOV VP100 FOV
Distance
measurements at several distances that are
Hor= 13.2 Hor= 16.2 Hor= 19.2
8 inches Ver= 9.9 Ver= 12.9 Ver= 15.9 relevant to the various applications they
Hor= 18.0 Hor= 21.0 Hor= 24.0 monitor. Also, try moving a target as close
12 inches Ver= 13.5 Ver= 16.5 Ver= 19.5 to your camera as possible until you can no
18 inches Hor= 25.0 Hor= 28.0 Hor= 31.0 longer bring the object into focus. This will
Ver= 18.75 Ver= 21.75 Ver= 21.75
show you the camera’s “minimum focus
Hor= 31.5 Hor= 34.5 Hor= 37.5
24 inches Ver= 24.0 Ver= 27.0 Ver= 30.0 distance.” i.e. the closest you can get to a
target and still be in focus. It is very useful to
Figure 4
know your camera’s minimum focus distance,
since some cameras can be more than 24 inches, thereby limiting their use in electrical thermography.
Note: Although the above technique is not 100 % accurate it gives an extremely good result. Try it for
yourself – it is a simple technique that really works!
Rule of Thumb
Based on countless field tests for WFOV with a wide variety of cameras, most cameras have generated a
horizontal WFOV of roughly two to three times (2X to 3X) the distance to the target; and a vertical WFOV
of roughly 1.5X to 2X the distance to the target. This is based on cameras with a standard 24° or similar
lens, using a maximum angle of incidence of 30°.
Therefore, based on this rule of thumb, a window located 20 inches (51 cm) from the intended targets
would allow the thermographer to gather data from points that were separated by 40 to 60 inches (1m
to 1.5m) side-to-side and separated by 30 to 40 inches (0.75 to 1m) top-to-bottom.
Note that it is impractical to use a multiplier in excess of 3X due to the difficulty matching the thermal
image to locations within the panel. Obstructions in the panel may also make it impractical. As
previously mentioned, viewing at too steep an angle can begin to affect other variables such as
emissivity. Therefore, IRISS, inc. recommends a maximum of 3X as a “rule of thumb multiplier.
Summary
1. Every camera has a Field-of-View (FOV) defined in degrees across a horizontal/vertical axis.
Note that the FOV can vary depending on the type of lens used.
2. Image Field of View (IFOV): The smallest detail that can be resolved.
3. Measurement Field of View (MFOV): The smallest detail that can be accurately measured.
4. Window Field of View (WFOV): The largest area that can be viewed through an infrared window
allowing for a maximum angle of incidence of 30° off perpendicular.
5. Rule of thumb for WFOV using a standard camera and lens is roughly 2 to 3 times the distance
from the window to the target.
6. Obstructions, such as phase dividers or cables, inside the cabinet may decrease actual field
of view.
19 | iriss.com 10 Things You Need To Know About Infrared Windows
24. Chapter 6 CONT’D
Installation
Before picking up that drill, it is imperative to consider the following to ensure a successful, safe and
useful installation:
• Internal obstacles:
Seek the permission from the local safety manager before removing internal Lexan TM (Perspex)
covers. In some cases, you may not be able to remove the covers entirely. If this is the case, modify
the covers by drilling or punching holes (without losing the IP2X requirement for some switchgear),
or investigate custom guards that would allow for infrared transmission (such as the IRISS CAP
Series.)
• Internal Cable Routing:
Work from drawings on brand-new switchgear to confirm the Maximum
Minimum
Clearance
internal cable routes. Make sure that contractors do not route Voltage (kV)
In cm
these cables in front of the infrared windows.
4.76 5.5 14
• Dielectric Clearances (distance from energized
8.25 6.5 17
components):
15.0 8.0 20
Where the IR window contains grills, or inspection orifices, it
must comply with IP2X (13mm 0.5”). Safe dielectric clearances 27.0 12.0 30
must be maintained for each window. IEEE C37.20.2, Table 1 38.0 15.0 36
specifies a minimum clearance distance for live components Table 1: from IEEE C37.20.2
(versus maximum rated voltage).
PPE:
Complete a detailed Risk Assessment (identifying all hazards
that may be present during the installation) and a detailed
Method Statement (detailing how the installation will be
performed). Make sure that the installation crew has the
correct levels of PPE to complete the task safely, especially
if the installation involves energized work, in which case an
energized Work Permit will also be required per NFPA 70E/CSA
Z462. All work procedures, assessments and permits must be
outlined in the Risk and Method statement.
Installation Instructions
Ensure that you comply with the Installation Instructions like those in Figure 1, provided by the window
manufacturer. These will provide you with all the necessary information to ensure that the windows
are installed correctly.
Tools
Before starting any installation, double-check to
be sure that all required tools are readily available.
Traditionally, IR window installations take place
during plant shutdowns therefore, you will need
to ensure that you have all the cutters, drills, drill
bits, metal treatments, etc. already kitted and
at-hand (including spares). Remember, that you
will probably not be able to run to a hardware store
to purchase new punches at 2 in the morning! A
complete list of required tools can be obtained Figure 1
from the IR window manufacturer.
21 | iriss.com 10 Things You Need To Know About Infrared Windows
26. Chapter 6 CONT’D
What Can I See Through an Infrared Viewing Pane?
An infrared window allows you to check the condition of electrical conductors and circuit parts. As with
traditional thermographic inspections, the camera is very good at detecting and displaying even slight
temperature differences very clearly. Therefore, when there is an electrical fault producing a temperature
rise, the camera will display the image of the faulty components very clearly. However, if everything is at
temperature equilibrium, it is difficult for the camera to display an image showing much of anything.
Figures 3, 4 and 5 are images taken through an IR window — no apparent faults are present.
Figure 3 Figure 4 Figure 5
Figures 6, 7 and 8 are images taken through an IR window — temperature rise due to load imbalance and
poor connections are evident.
Figure 6 Figure 6 Figure 7
23 | iriss.com 10 Things You Need To Know About Infrared Windows
28. Chapter 7
Certifications and Standards
“What standards and certifications are relevant to infrared (IR) windows?” This is one the most commonly
asked questions when engineers and safety professions begin to investigate IR windows. Trying to sort
through the myriad of UL, cUL, IEEE, CSA and other standards can be a daunting task. This chapter will
attempt to clarify some of the most pertinent standards.
UL50V
The UL 50V classification for Infrared Viewports is the only standard that relates specifically to infrared
windows. It serves more as a classification than an actual standard for performance-of-build characteris-
tics. Specifically it states:
Infrared Viewports are a fixed aperture, consisting of one or more openings or a solid infrared
transmitting media, surrounded by a mounting bezel or frame, that provide a means for the
passage of infrared radiation.
The UL50V classification is actually a mix of two distinctly different product categories: the “infrared
window” (also known as IR sightglasses or IR viewing panes) and the “infrared port.” While both will allow
the thermographer to perform infrared inspections of targets located inside an enclosure or behind a
barrier, they are mechanically very different. Specifically, IR windows provide a barrier to separate the
thermographer from the environment surrounding the target. In contrast, an IR port is essentially a
hole. When opened, it effectively removes the barrier between the thermographer and the target. This
distinction becomes important when considering the Personal Protective Equipment (PPE) implications
of NFPA 70E/CSA Z462 (see Chapter 8).
UL508
UL508 covers industrial control equipment and control panels under 1500 volts. Equipment covered by
these requirements is intended for use in an ambient temperature of 0-40°C (32-104°F) unless specifically
indicated for use in other conditions.
UL 508A
UL508A covers industrial control panels intended for general use, with an operating voltage of 600 or
less. This equipment is intended for installation in ordinary locations, in accordance with the National
Electrical Code (ANSI/NFPA 70), where the ambient temperature does not exceed 40°C (104°F).
UL 746C
UL 746C sets the impact and flammability standards for polymeric materials used in electrical equipment
up to 1500 volts. Any plastic or polymer forming part of an infrared window must pass flammability tests
at room temperature, and must remain intact during an impact test performed at 0°C (32°F). It is worth
noting that of the crystal optics capable of transmitting in the long wave portion of the infrared
spectrum (8μm to 14μm), there are no fluoride-based crystals capable of passing the impact tests required
in 746C. However, because they are classified as “glass” under the standard, they are not required to test
for impact as long as they are thicker than 1.4 mm.
25 | iriss.com 10 Things You Need To Know About Infrared Windows
32. Chapter 8
Arc Flash, NFPA and OSHA: Implications on Infrared Inspections
An arc flash incident is reported every 18 minutes in the US. From these, roughly 20 people per day
sustain arc-induced burns, and 5 to 10 workers suffer incurable third-degree burns over more than half
their body. Sadly, on average, more than one worker a day never goes home – the victim of an arc flash
fatality.
What is an Arc Flash and What are the Risks?
An arc flash is a short circuit through the air that creates an explosion equal in force to one to three sticks
of dynamite. Since most incidents are triggered by some type of human interaction, the same dynamite-
like blast occurs within a few feet of the worker.
Common triggers are 1) dropping tools or panels, 2) making accidental contact with energized parts, or
3) changing the state of the equipment. An arc usually starts as a phase-to-ground short circuit. This
“bolted fault” is one bridged by an object (a wrench for example) with limited current carrying potential.
However, when the initial arc vaporizes the copper conductor, it produces a small, hyper-conductive
cloud of copper plasma and ionized gases. This conductive cloud then forms a bridge changing the short
to phase-to-phase. It is this “unbolted fault” that grows in intensity, producing a blinding flash along with
ultra-high temperatures. The explosion feeds on itself, and the heat converts all materials in the vicinity
to plasma. The copper conductor expands 67,000 times its initial size in a fraction of a second. It is this
rapid expansion that creates the pressure wave that rips apart switchgear and sends molten shrapnel
toward anything in its path.
How do Electrical Hazards Compare to Other EHS Hazards?
Today, many plant safety concerns are well publicized and understood due to aggressive campaigns from
Environmental Health and
Safety (EHS) Departments.
However, electrical safety
has largely been left to the
Electrical Department,
since it is a highly
specialized topic.
Ironically, even though
electrical injuries are less
frequent than typical EHS
issues, they carry far Figure 1
greater consequences.
Modern versions of the W.H. Heinrich Safety Pyramid (Figure 1) shows that for every 10,000 nearmiss
incidents, there are 10 disabling injuries and one fatality. By comparison, 85 near-miss arc flash incidents
will result in six disabling injuries and one fatality. Using the same scale above, 10,000 arc flash events
would result in 706 disabling injuries (compared to 10 in the standard EHS model), and 118 fatalities
(compared to 1).
Similarly, the National Safety Council estimates one fatality for every thirty electrical shocks. This makes
electrocution the fourth leading cause of workplace fatalities (per NFPA 70E; 2009; K.2). Clearly, electrical
hazards should be the focus of awareness and safety campaigns to better protect workers.
29 | iriss.com 10 Things You Need To Know About Infrared Windows
34. Chapter 8 CONT’D
When Should Personnel Utilize PPE?
NFPA 70E/CSA Z462 directs personnel to utilize elevated
levels of PPE when they are exposed to energized electrical
conductors or circuit parts. Even if the panels are closed,
PPE should be worn if there is the potential for an electrical
hazard, such as a change-of-state.
Use of an IR window maintains an IP65/NEMA 4X seal on the
enclosure panel. Therefore, even when open, the window
maintains what NFPA terms an “enclosed” and “guarded”
condition. Additionally, scanning through an IR window is
a noninvasive task that does not create a risk of electrical
Figure 3
hazard (no change-of-state). As long as the thermographer
is confident that the equipment has been properly installed and maintained, and the equipment is not in
danger of changing state. Then, the HRC for using an IR window would be the same level as “reading
a panel meter while operating a meter switch,” which NFPA rates as HRC 0.
Additional Resources:
For a more information on the standards in this chapter, please refer to the following white papers and
web sites:
• For additional information about how NFPA 70E, NFPA 70B and OSHA effect electrical
thermography, see the “Standards Implications on Electrical Thermography” white paper at:
http://www.iriss.com/PDF/new_white_papers/IRISS_NFPA_W_P_Dec08_p.pdf
• For additional information about NFPA 70B, see:
http://www.nfpa.org/aboutthecodes/AboutTheCodes.asp?DocNum=70B
• For additional information about NFPA 70E, see:
http://www.nfpa.org/aboutthecodes/AboutTheCodes.asp?DocNum=70E
• For additional information about OSHA 1910, see:
http://www.osha.gov/SLTC/electrical/standards.html
• For additional information about CSA Z462, see:
http://www.csa.ca/products/occupational/Z462/Default.asp?language=English
Summary
1. Working with energized electrical components is among the most dangerous activities found |
in the workplace.
2. Preventive maintenance standards such as NFPA 70B require infrared surveys of fully loaded
and energized conductors and circuit parts at least annually.
3. OSHA 1910, NFPA 70E and CSA Z462 all require that personnel are not exposed to energized
conductors and circuit parts unless absolutely necessary.
4. If personnel must access energized equipment, they are required to utilize PPE suited for the
level of the hazard/risk of the task they are performing.
5. Infrared windows allow inspections to take place with the cabinet panels closed; thereby
not exposing personnel to energized components and elevated hazard/risks. Therefore, the
HRC level required when performing an IR inspection through a sealed window would be
HRC 0 – the same as taking a meter reading or performing other administrative functions
around enclosed
31 | iriss.com 10 Things You Need To Know About Infrared Windows