2. BRS2111(1.6 M) Outdoor Power System
2
1
Telecom Power System
Telecom Power SystemTelecom Power System
ACDistributionUnit Rectifier # 1
Control Supervisory
Unit (CSU)
LOAD(Switch,ADSL…E.T.C.)
OutputDCDistributionUnit
LVDS
Rectifier # 3
Rectifier # 2
Rectifier # N
Battery
AC Input
Generator
U.P.S
3. BRS2111(1.6 M) Outdoor Power System
3
Contents
System Overview
Main Features /Configuration
Outdoor Cabinet type (1.6 M)
Power Distribution configuration (AC,Surge , DC Load , Battery.
Rectifier Power shelf configuration
Rectifier module specification (DP2700)
New Smart CSU controller with LCD Display
System Function Introduction
Delta Remote/Monitor function
-- NRMS monitor software (RS-232 port)
-- Web Server/ SNMP function (Optional)
Q&A
4. BRS2111(1.6 M) Outdoor Power System
4
Delta DPS 2700 Series Power System
Main Features:
AC Input: Optional for three conditions
1. 220Vac, Single phase (Already)
2. 380Vac, Three phases / Five Wire ( Y Connection)
System Capacity: -54Vdc / 150A Max.
IP Protect:Power Battery Space: IP54, Equipment Space: IP55
DC Distribution: Load Breaker Configurations: Breaker (DIN rail ),
Battery Breaker: ~125A Breaker, 2 Positions Max.
LVDB *1 (Standard): 150A on Battery Side
LVDL *1: 150A on Load Side
Rectifier: -54Vdc/50A (DPR2700) *3
Controller: New Smart CSU with LCD
Relay Output: Total 8 Positions, Customer Definable
Local/Remote Monitoring and Control – NRMS software
− Local Access: By NRMS via RS232 Interface
− Internet Web Server Function: By Web Server Software/SNMP via RJ45 Interface
(Optional)
System Dimension (W*D*H): 55.1” x 29.6” x 29.6” inch / 1600 x 750 x 750mm
Operating Temperature: 0℃~+55℃(32℉~131℉)
5. BRS2111(1.6 M) Outdoor Power System
5
PDU (Several Configurations)
Rectifier ESR-48/56A
Battery & Base
New Smart CSU (Main Board))
New Smart CSU (Relay Board))
19” Rectifier Shelf (SB-05N/HG A )
CCU (Climate
Control Unit )
Fan Tray
8. BRS2111(1.6 M) Outdoor Power System
8
Dimension: W750mm * D750mm * H1600mm
IP54, two-walled aluminum alloy (5052-H32) constructions (Cabinets)
Enclosure/Plinth’s color: Ericsson LMY 904, (NCS2502)
Plinth: Steel with powder coating
Eyebolts inside removable roof
W
H
D
Delta P/N: ESOA150-ABC01
Estimated Weight: 113 Kg (with Power system)
RBS2111 (1.6M) Outdoor System Overviews
9. BRS2111(1.6 M) Outdoor Power System
9
Air filter
Fan Tray mounted on
inside of Roof
Power system
Changeover Switch
Climate Control Unit
(Battery excluded in cabinets)
2nd
Battery Shelf
Max. Space suitable for
CSB TPX122200 * 4pcs
(Battery excluded in cabinets)
1st
Battery Shelf
Max. Space suitable for
CSB TPX122200 * 4pcs
DC Light mounted on
inside of Frame
Smoke Sensor
Humidity Sensor
Genset Socket, 32A
3N~(R,S,T,N ,PE)
RBS2111 (1.6 M) Configurations
10. BRS2111(1.6 M) Outdoor Power System
10
3pcs MG32A 3-hole
For cable range (OD): 5~10mm
1pce MG25A 1-hole
For cable range (OD): 10~16mm
1pce MG32A 1-hole Cable Gland
For cable range (OD): 15~22mm
4pcs of bottom cable
entries reserved
3pcs MG32A 3-hole Cable Gland
For cable range (OD): 5~10mm
For AC Terminations
1pce MG25A 1-hole Cable Gland
For cable range (OD): 12~16mm
For DC grounding cable
5pcs of Side cable entries reserved
RBS2111 (1.6M) Cable Entries
11. BRS2111(1.6 M) Outdoor Power System
11
Grounding BUS Bar
4pcs M6 insert nuts pre-installed fixed on plinth
Loosen screws opening plinth cover
Grounding bus bar Location and Grounding cable path
12. BRS2111(1.6 M) Outdoor Power System
12
Plate (1pcs):
Pre-install on right side
Design to block unused side
RBS2111 (1.6M) AC Cable Entry on Both Sides
AC cables pass through left side
of plinth.
New requirement:
AC cables can pass through right side of plinth.
13. BRS2111(1.6 M) Outdoor Power System
13
Cabinet Mountings
600
83
705Anchor Pattern and Footprint15mm X 4
: Footprint Area
35
550
712
83
35
Installation template (1pcs) for RBS2111
system along with first shipment
(2.1M and 1.6M systems are the same
template.)
14. BRS2111(1.6 M) Outdoor Power System
14
Recommended Spare Parts & Part Numbers
RBS 2111 1.6M
ESOA150-ABC01
Remark
CU-18A A-S
Climate Control Unit
V
3790335100-S
Controller(NCSU)-LCD Display
V
5505602118-S
Controller(NCSU)-Main Board
V
ESR-48/56A A-S
Rectifier 2700W (DPR2700)
V
3790335000
Temperature Sensor Cable 3M
V
EX-F01 B-S
Fan Tray
V
EX-H01 A-S
Heat Exchanger 22W/K
(Delta HEX)
NA
Air Filter G3
3243139500
V
Heat Exchanger
160W/K
50400000196
NA
Model Name
Spare parts
(Delta P/N)
15. BRS2111(1.6 M) Outdoor Power System
15
SMR Shelf 19” H type
SB-05N/HG A DPS 2700 shelf 54V/150A
W x H x D=19 x 1.7 x 11.7 inch =483 x 44 x 297.8 mm
16. BRS2111(1.6 M) Outdoor Power System
16
Features and Benefits
-48V/41.7A, Output; Max. Power 2000W
Wide Input Voltage Range (90V~300V)
Power Factor Correction (>0.99)
Hot-pluggable, All Connectors are at the rear
Compact Size
≅ 24W/in3 (48V) Power Density
Dimension:42mm/1U(H)*125.5mm/2.8U(W)*268mm(D)
Light weight:1.64 Kg (4.4lb)
Horizontal(1U)/Vertical(2.8U) Models Available
High Efficiency: >91% (48V)
Fan cooling and Easy replaceable fan design
Operation temp.:-5oC~+65oC
UL/CUL,TUV/CE Certificated
DP 2000 Series Rectifier
17. BRS2111(1.6 M) Outdoor Power System
17
Rectifier - Interface
I/O Connector
OutputSignalInput
Load Sharing BusIBUSD2
ID digitalIDDD1
ID analogIDAC2
Short pin for well connectionINHC1
Communication groundCGNDB1
RS 485 + communicationRS485+A2
RS 485 – communicationRS485-B2
Signal groundSGNDOA1
DC Output “+”VO+P8-P10
DC Output “-”VO-P5-P7
PrechargeVOPP4
DescriptionSignalPin Number
AC main, frame groundFGP3
AC main, N terminalAC_NP2
AC main, L terminalAC_LP1
DescriptionSignalPin Number
18. BRS2111(1.6 M) Outdoor Power System
18
RS-485
New Smart CSU: DPS 2700 Series
Configuration,
Supervision Terminal Interface
Web/SNMP Card
Ethernet
Configuration,
Supervision
(web browser)
54Vdc/50A
With SMR
Analog
Signal Detection
LCD Display
RS-485 X 3
With SMR
RS-485 With
SMR
Analog
I.D address
19. BRS2111(1.6 M) Outdoor Power System
19
Easy integration with most Delta power systems
Modular system controller
User friendly operating interface
Large 128 x 64 pixel LCD Display
Entry of alarm and system parameters from keypad
High reliable RS-485 communication with Rectifier
Easy system expansion
Easy extendable custom-design I/O board
Complete function support
More then 100 system events log
Temperature & Voltage compensation charging
Smart Battery management
Green Function
Different possibilities for remote monitoring
1 outside communication port (RS-232) DB9
Local Access monitoring & Control
Web Server Function (RJ-45)
Power System Controller – New Smart CSU
User Interface
20. BRS2111(1.6 M) Outdoor Power System
20
Delta Power System Monitoring & Control
Build in HTTP
Web Server
AC
Distribution Rectifiers
DC Distribution Battery
Management
Environment
Data
Acquisition
Control &
Supervisory
Unit
Client User
Client User
Internet
Telecom Power Manage
Program
Local
Client User
Mini USB
22. BRS2111(1.6 M) Outdoor Power System
22
Web Server Function and Feature (Optional)
Features:
Applied in TCP/IP Internet/Intranet Environment
Complete Supervising to Power System
User-friendly Graphic Interface
Dynamic information presentation
Password function
Multi Language Support
Microsoft Explorer and Netscape SupportMain Screen
Status
Parameter Setting
Alarm
Configuration