2. BRS2216 Outdoor Power System
2
1
Telecom Power System
Telecom Power SystemTelecom Power System
ACDistributionUnit Rectifier # 1
Control Supervisory
Unit (CSU)
LOAD(Switch,ADSL…E.T.C.)
OutputDCDistributionUnit
LVDS
Rectifier # 3
Rectifier # 2
Rectifier # N
Battery
AC Input
Generator
U.P.S
3. BRS2216 Outdoor Power System
3
Contents
System Overview
Main Feature/Configuration
Outdoor Cabinet Type (1.8M)
Power Distribution configuration (AC,Surge , DC Load , Battery.
Rectifier Power shelf configuration
Rectifier module specification (DP2700)
New Smart CSU controller with LCD Display
System Function Introduction
Delta Remote/Monitor function
-- NRMS monitor software (Mini USB port)
-- Web Server/ SNMP function (Optional)
Q&A
4. BRS2216 Outdoor Power System
4
Delta DPS 2700 Series Power System
Main Features:
AC Input: Optional for three conditions
220Vac, Single phase (Already)
380Vac, Three phases / Five Wire ( Y Connection)
System Capacity: -54Vdc / 150A Max.
IP Protect:Power system Bay: IP54, Equipment Bay: IP55
DC Distribution: Load Breaker Configurations: Breaker (DIN rail ),
Battery Breaker: ~125A Breaker, 2 Positions Max.
LVDB *1 (Standard): 150A on Battery Side
LVDL *1: 150A on Load Side
Rectifier: -54Vdc/50A (DPR2700) *3
Controller: New Smart CSU with LCD
Relay Output: Total 8 Positions, Customer Definable
Local/Remote Monitoring and Control – NRMS software
Local Access: By NRMS via RS232 Interface
Internet Web Server Function: By Web Server Software/SNMP via RJ45 Interface
(Optional)
System Dimension (W*D*H): 55.1” x 33.5” x 71.3” inch / 1400 x 850 x 1810mm
Operating Temperature: 0℃~+55℃(32℉~131℉)
5. BRS2216 Outdoor Power System
5
PDU ( four Configurations)
Rectifier ESR-48/56A
Battery & Base
New Smart CSU (Main Board))
New Smart CSU (Relay Board))
19” Rectifier Shelf (SB-05N/HG A )
160W Heat-exchanger
CCU (Climate
Control Unit )
8. BRS2216 Outdoor Power System
8
CCU
TempSensor
HeatExchanger
AirsysHX160-B1
CSU
FL
TempSensor
Fan Tray
Fan ON/OFF Control
Hi Temp Alarm
Hi Temp Alarm
HEX status Monitoring
FanSpeedControl
(Full speed operation)
Architecture of Cooling Control
Delta Power System Drawing - Cooling
BHEX
9. BRS2216 Outdoor Power System
9
RBS2216 Equipment Bay Configurations
RBS2216
160 W/K Heat Exchanger
Plinth
7pcs of 3-hole Cable Gland reserved
(Details show on later page)
10U(H) Max. Space for
Transmission Equipment
4pcs of M10 insert nuts pre-installed in Bracket
For RBS2216 Installation,
Pitch: 572mm * 307mm
Load capacity(Tray): 300Kg
Micro Switch (Front Door)
Estimated Weight: 140 Kg (With HEX)
(Transmission equipment excluded)
Add markings on base frame for for
RBS2216 installation.
AP29
10mm
10. BRS2216 Outdoor Power System
10
RBS2216 Power System Bays Configurations
Air Filter Frame mounted
on Front Door
Power system
Climate Control Unit
Bottom cable entries
Fan tray mounted on
inside of roof
4U Space for DDF-OVP
2nd
Battery Shelf
1st
Battery Shelf
AC termination
Changeover Switch
Cable gland for DC cables to
equipment bay
Metal duct to AC
termination
External Alarm Terminal
(Battery excluded in cabinet)
(Battery excluded in cabinet)
Estimated Weight: 127 Kg (With Power system)
(Battery strings, DF-OVP excluded)
11. BRS2216 Outdoor Power System
11
Add AC Socket
RBS2216 AC Panel Configurations
Changeover Switch
Phase 1 (with Genset Socket & Changeover Switch):
Implementation: from first batch
Genset Socket
Phase 2 (without Genset Socket & Changeover Switch):
Implementation: TBD (Inventory Concern)
AP36
12. BRS2216 Outdoor Power System
12
DC LightSmoke Sensor
Humidity Sensor
RBS2216 Lights & Sensors
13. BRS2216 Outdoor Power System
13
AC main input Terminal Block
For 3 phases and neutral connections
AC Grounding Bus Bar
4pcs of M6 insert nuts
RBS2216 AC Input Terminations
AC cabling from outside wall
slot (L150mm * W60mm)
through cable glands and metal
wiring ducts to main AC
terminations
3pcs of MG32A 3-hole Cable Gland
For cable range (OD): 5~10mm
14. BRS2216 Outdoor Power System
14
ACMAINSINPUT
1 PHASE 220V 50/60Hz
S T
ACBREAKER3P
N
R PE
SURGE ARRESTER
AC-T&SURGE-T
AC-S&SURGE-S
R
TS
AC-R&SURGE-R
AC-N
N
SURGE-S
SURGE-T
SURGE-R
L N
3P 380Vac Start Type
Main Power AC input Type
1P 220Vac Type
ACMAINSINPUT
3 PHASE 380V + N 50/60Hz
S T
ACBREAKER3P
N
R PE
SURGE ARRESTER
AC-T&SURGE-T
AC-S&SURGE-S
R
TS
AC-R&SURGE-R
AC-N
N
SURGE-S
SURGE-T
SURGE-R
R S T N
15. BRS2216 Outdoor Power System
15
Plate (1pcs):
Pre-install on right side
Design to block unused side
RBS2216 AC Cable Entry on Both Sides
AC cables pass through left side
of plinth.
New requirement:
AC cables can pass through right side of plinth.
AP32
16. BRS2216 Outdoor Power System
16
Rear Cover
Keep clearance between roof and rear
cover to prevent interference
Roof
RBS2216 Roof Installation Improvement
Modify rear cover for roof installation without removing rear covers
(Section View from Right Side)
AP24
17. BRS2216 Outdoor Power System
17
RBS2216 Cable Entries
4pcs of bottom cable
entries reserved
7pcs of side cable
entries reserved
3pcs MG32A 3-hole Cable Gland
For cable range (OD): 5~10mm
For AC Terminations
2pcs of 3-hole Cable Glands
For jumper cable 1/2” (OD 12.5mm)
9pcs of compartment cable
entries reserved
Genset Socket, 32A
3N~(R, S, T, N, PE)
2pcs of 3-hole Cable Glands
For jumper cable 1/4” (OD 6.35mm)
1pce of MG25A 3-hole Cable Gland
For cable range (OD): 2.6~3.6mm
(Delta internal cable)
3pcs MG32A 3-hole Cable Glands
For cable range from (OD 5~10mm)
1pcs MG25A 1-hole Cable Gland
For cable range (OD): 12~16mm
For DC grounding cable
4pcs of MG32A 1-hole Cable
For cable range (OD): 15~22mm
(2E1, Alarm cable, 1 power cable
for MW)
4pcs of MG32A 3-hole Cable Glands
For cable range (OD):5~10mm
(Ericsson’s cables )
18. BRS2216 Outdoor Power System
18
RBS2216 Battery Configurations
2nd
Battery Shelf
Max. Space suitable for
CSB TPX122200 * 4pcs
1st
Battery Shelf
Max. Space suitable for
CSB TPX122200 * 4pcs
Reserved cabling space for
Jumper Cables
19. BRS2216 Outdoor Power System
19
Recommended Spare Parts & Part Numbers
RBS 2216, 1.8M
ESOA150-ABA01
Remark
CU-18A A-S
Climate Control Unit
V
3790335100-S
Controller(NCSU)-LCD Display
V
5505602118-S
Controller(NCSU)-Main Board
V
ESR-48/56A A-S
Rectifier 2700W (DPR2700)
V
3790335000
Temperature Sensor Cable 3M
V
EX-F01 B-S
Fan Tray
V
EX-H01 A-S
Heat Exchanger 22W/K
(Delta HEX)
NA
Air Filter G3
3243139500
V
Heat Exchanger
160W/K
50400000196
V
Model Name
Spare parts
(Delta P/N)
20. BRS2216 Outdoor Power System
20
SMR Shelf 19” H type
SB-05N/HG A DPS 2700 shelf 54V/150A
W x H x D=19 x 1.7 x 11.7 inch =483 x 44 x 297.8 mm
21. BRS2216 Outdoor Power System
21
Features and Benefits
-48V/41.7A, Output; Max. Power 2000W
Wide Input Voltage Range (90V~300V)
Power Factor Correction (>0.99)
Hot-pluggable, All Connectors are at the rear
Compact Size
≅ 24W/in3 (48V) Power Density
Dimension:42mm/1U(H)*125.5mm/2.8U(W)*268mm(D)
Light weight:1.64 Kg (4.4lb)
Horizontal(1U)/Vertical(2.8U) Models Available
High Efficiency: >91% (48V)
Fan cooling and Easy replaceable fan design
Operation temp.:-5oC~+65oC
UL/CUL,TUV/CE Certificated
DP 2000 Series Rectifier
22. BRS2216 Outdoor Power System
22
Rectifier - Interface
I/O Connector
OutputSignalInput
Load Sharing BusIBUSD2
ID digitalIDDD1
ID analogIDAC2
Short pin for well connectionINHC1
Communication groundCGNDB1
RS 485 + communicationRS485+A2
RS 485 – communicationRS485-B2
Signal groundSGNDOA1
DC Output “+”VO+P8-P10
DC Output “-”VO-P5-P7
PrechargeVOPP4
DescriptionSignalPin Number
AC main, frame groundFGP3
AC main, N terminalAC_NP2
AC main, L terminalAC_LP1
DescriptionSignalPin Number
23. BRS2216 Outdoor Power System
23
RS-485
New Smart CSU: DPS 2700 Series
Configuration,
Supervision Terminal Interface
Web/SNMP Card
Ethernet
Configuration,
Supervision
(web browser)
54Vdc/50A
With SMR
Analog
Signal Detection
LCD Display
RS-485 X 3
With SMR
RS-485 With
SMR
Analog
I.D address
24. BRS2216 Outdoor Power System
24
Easy integration with most Delta power systems
Modular system controller
User friendly operating interface
Large 128 x 64 pixel LCD Display
Entry of alarm and system parameters from keypad
High reliable RS-485 communication with Rectifier
Easy system expansion
Easy extendable custom-design I/O board
Complete function support
More then 100 system events log
Temperature & Voltage compensation charging
Smart Battery management
Green Function
Different possibilities for remote monitoring
1 outside communication port (Mini USB) DB9
Local Access monitoring & Control
Web Server Function (RJ-45)
Power System Controller – New Smart CSU
User Interface
25. BRS2216 Outdoor Power System
25
Delta Power System Monitoring & Control
Build in HTTP
Web Server
AC
Distribution Rectifiers
DC Distribution Battery
Management
Environment
Data
Acquisition
Control &
Supervisory
Unit
Client User
Client User
Internet
Telecom Power Manage
Program
Local
Client User
Mini USB
27. BRS2216 Outdoor Power System
27
Web Server Function and Feature (Optional)
Features:
Applied in TCP/IP Internet/Intranet Environment
Complete Supervising to Power System
User-friendly Graphic Interface
Dynamic information presentation
Password function
Multi Language Support
Microsoft Explorer and Netscape SupportMain Screen
Status
Parameter Setting
Alarm
Configuration