Overview of Fire Alarm
Overview of Fire Alarm
Systems and
Systems and
Maintenance
Maintenance
Mr. David Goh
Vice President – Fire Safety Managers’ Association
Convener of Working Group for CP 10 : 2005
Er. Matthew Kwek
Committee Member – Fire Safety Managers’ Association
P.E., R.I.(M&E), FSE
By
1
1 Fire Alarm Systems
Fire Alarm Systems –
– A Quick Introduction
A Quick Introduction
a.
a. Why use a Fire Alarm System?
Why use a Fire Alarm System?
b.
b. Is Fire Alarm System a mandatory requirement?
Is Fire Alarm System a mandatory requirement?
c.
c. What is a Fire Alarm System made up of?
What is a Fire Alarm System made up of?
2
2 Types of Fire Alarm Systems in use today
Types of Fire Alarm Systems in use today
a.
a. Non
Non –
– Addressable
Addressable
b.
b. Addressable
Addressable
c.
c. Hybrid
Hybrid
3 Maintenance
3 Maintenance
a.
a. Regular testing and Inspection
Regular testing and Inspection
b.
b. False Alarm Management
False Alarm Management
c.
c. Common Maintenance Problems And
Common Maintenance Problems And
Troubleshooting
Troubleshooting
CONTENTS
Why use a Fire Alarm System?
Why use a Fire Alarm System?
• A fire alarm system is intended to enable a fire to
be detected at a sufficiently early stage so that
people who are at risk can be made safe either by
escaping from the fire, or by the fire being
extinguished (also to prevent extensive property
damage). Neither of these measures can be used
until people are made aware of fire.
• The effectiveness of the fire detection and alarm
system depends on the stage of the fire at which it
is operated. In order for all the occupants to escape
without too much difficulty, an early alarm should
operate before the escape routes becomes smoke-
logged to such an extent as will cause occupants to
have difficulty finding their way out of the building.
1. Fire Alarm Systems
1. Fire Alarm Systems –
– A Quick Introduction
A Quick Introduction
1. Fire Alarm Systems
1. Fire Alarm Systems –
– A Quick Introduction
A Quick Introduction
Why use a Fire Alarm System?
Why use a Fire Alarm System?
Fire Alarm Systems are used to protect life and property.
It protects by:
a. detecting a fire at an early stage
b. alerting and evacuating occupants
c. notifying the relevant personnel
d. activating auxiliary functions e.g. smoke controls, lift homing etc
e. identifying and guiding fire fighters
1. Fire Alarm Systems
1. Fire Alarm Systems –
– A Quick Introduction
A Quick Introduction
Is Fire Alarm System a mandatory
Is Fire Alarm System a mandatory
requirement?
requirement?
Mandatory
Mandatory -
- By the relevant authority
By the relevant authority
Non
Non-
-mandatory
mandatory -
- By Building Owner, Landlord &
By Building Owner, Landlord &
Insurance etc.
Insurance etc.
The requirements are specified in :
The requirements are specified in :
-
- Code of Practice for Fire Precautions in Buildings 2007
Code of Practice for Fire Precautions in Buildings 2007
(Fire Code 2007)
(Fire Code 2007) –
– by SCDF
by SCDF
-
- Code of Practice for Installation and Servicing of Electrical Fi
Code of Practice for Installation and Servicing of Electrical Fire
re
Alarm System
Alarm System
(SS CP10
(SS CP10-
-2005)
2005) –
– by Spring Singapore
by Spring Singapore
What is a Fire Alarm System made up of?
What is a Fire Alarm System made up of?
1. Fire Alarm Systems
1. Fire Alarm Systems –
– A Quick Introduction
A Quick Introduction
Components forming the System
Components forming the System-
- 9 Items
9 Items
1.
1. Smoke / Heat
Smoke / Heat Detectors (
Detectors (Fire Detectors
Fire Detectors)
)
2.
2. Alarm Panels (
Alarm Panels (Control and Indicating Equipment
Control and Indicating Equipment)
)
3.
3. Alarm Bells (
Alarm Bells (Fire Alarm Devices
Fire Alarm Devices)
)
4.
4. Manual Call Points
Manual Call Points
5.
5. DECAM Panel (
DECAM Panel (Fire Services
Fire Services Signalling
Signalling Transmitter
Transmitter)
)
6.
6. DECAM Station (
DECAM Station (Alarm Monitoring Station
Alarm Monitoring Station)
)
7.
7. Extinguishing Panels (
Extinguishing Panels (Control for automatic fire protection equipment
Control for automatic fire protection equipment)
)
8.
8. Gas/Sprinkler (
Gas/Sprinkler (Automatic fire protection equipment
Automatic fire protection equipment)
)
9.
9. Charger/Battery (
Charger/Battery (Power Supply Equipment
Power Supply Equipment)
)
1. Fire Alarm Systems
1. Fire Alarm Systems –
– A Quick Introduction
A Quick Introduction
What is a Fire Alarm System made up of?
What is a Fire Alarm System made up of?
DECAMS
FIRE
Fire Detectors
Fire Detectors
Manual Call Points
Manual Call Points
Control & Indicating
Control & Indicating
Equipment
Equipment
Fire Alarm Device
Fire Alarm Device
Fire Alarm Signal
Fault Signal
Fire Service
Fire Service
SignallingTransmitter
SignallingTransmitter
Alarm Monitoring
Alarm Monitoring
Station
Station
Control for Automatic
Control for Automatic
Fire Protection Equipment
Fire Protection Equipment
Automatic
Automatic
Fire Protection
Fire Protection
Equipment
Equipment
Power Supply Equipment
Power Supply Equipment
Types of Fire Alarm Systems
Types of Fire Alarm Systems
in use today
in use today
2. Types of Fire Alarm Systems in use today
2. Types of Fire Alarm Systems in use today
Non
Non-
-Addressable System
Addressable System
-
- also commonly known as
also commonly known as “
“conventional
conventional”
”
-
- fire detectors are wired to the panel in groups known as zone
fire detectors are wired to the panel in groups known as zone
-
- identification of alarm status by zone
identification of alarm status by zone
-
- fire detectors indicates either
fire detectors indicates either “
“Fire
Fire”
” or
or “
“Normal
Normal”
” status only
status only
-
- system only indicate events but without event recording
system only indicate events but without event recording
feature
feature
s s
s
s
s
s
s
s
s
s
Zone 1 Zone 2
Zone 2
Zone 1
Zone 1
Fire
Zone 2
Fire
Typical Non
Typical Non-
-Addressable Fire Alarm System
Addressable Fire Alarm System
Configuration
Configuration
2. Types of Fire Alarm Systems in use today
2. Types of Fire Alarm Systems in use today
Fire Protection
Fire Protection
System Status
System Status
Elevator recall
Elevator recall
Essential Extract Fans, pressurization fans etc
Essential Extract Fans, pressurization fans etc
Release escape doors
Release escape doors
Release normally open fire doors
Release normally open fire doors
Public Address system announcements
Public Address system announcements
Others as required
Others as required
AC Power
AC Power
FS
FS
FS
FS
FS
FS
2. Types of Fire Alarm Systems in use today
2. Types of Fire Alarm Systems in use today
Addressable System
Addressable System
-
- each fire detector is provided with an address
each fire detector is provided with an address
-
- identification of alarm status by zone and by address
identification of alarm status by zone and by address
-
- fire detectors indicates various condition such as smoke
fire detectors indicates various condition such as smoke
level
level
-
- indicates and records system events
indicates and records system events
Zone 1 Zone 2
Zone 2
Zone 1 s s
s
s
s
s
s
s
s
s
Zone 2
Zone 1
Zone 1 Fire
Detector 4
s
Typical Addressable Fire Alarm System
Typical Addressable Fire Alarm System
Configuration
Configuration
2. Types of Fire Alarm Systems in use today
2. Types of Fire Alarm Systems in use today
Elevator recall
Elevator recall
Essential Extract Fans, pressurization fans etc
Essential Extract Fans, pressurization fans etc
Release escape doors
Release escape doors
Release normally open fire doors
Release normally open fire doors
Public Address system announcements
Public Address system announcements
Others as required
Others as required
AC Power
AC Power
FS
FS
Fire Protection
Fire Protection
System Status
System Status
2. Types of Fire Alarm Systems in use today
2. Types of Fire Alarm Systems in use today
Hybrid System
Hybrid System
(conventional + addressable)
(conventional + addressable)
-
- a combination of features from both addressable and
a combination of features from both addressable and
non
non-
-addressable systems
addressable systems
-
- either built from a basic conventional system with add
either built from a basic conventional system with add-
-on
on
hardwire addressable features
hardwire addressable features
-
- or built from an addressable system with conventional module
or built from an addressable system with conventional module
-
- event recording and alarm management feature
event recording and alarm management feature
2. Types of Fire Alarm Systems in use today
2. Types of Fire Alarm Systems in use today
Typical Hybrid Fire Alarm System Configuration
Typical Hybrid Fire Alarm System Configuration
( conventional with hardwire addressable add
( conventional with hardwire addressable add-
-on)
on)
RS232 Cable
Colour Graphics
Station
Note Book
Hand-Held
Printer
Palm PDA
Built-in
Printer
Interface Options
Address
lines
Zone
Signal
Conventional devices – any reputable manufacturer
HyBrid
2. Types of Fire Alarm Systems in use today
2. Types of Fire Alarm Systems in use today
Typical Hybrid Fire Alarm System Configuration
Typical Hybrid Fire Alarm System Configuration
( conventional with hardwire addressable add
( conventional with hardwire addressable add-
-on)
on)
FS
FS
Fire Protection
Fire Protection
System Status
System Status
Elevator recall
Elevator recall
Essential Extract Fans, pressurization fans etc
Essential Extract Fans, pressurization fans etc
Release escape doors
Release escape doors
Release normally open fire doors
Release normally open fire doors
Public Address system announcements
Public Address system announcements
Others as required
Others as required
AC Power
AC Power
FS
FS
FS
FS
2. Types of Fire Alarm Systems in use today
2. Types of Fire Alarm Systems in use today
Typical Hybrid Fire Alarm System Configuration
Typical Hybrid Fire Alarm System Configuration
( addressable with conventional module add
( addressable with conventional module add-
-on)
on)
Elevator recall
Elevator recall
Essential Extract Fans, pressurization fans etc
Essential Extract Fans, pressurization fans etc
Release escape doors
Release escape doors
Release normally open fire doors
Release normally open fire doors
Public Address system announcements
Public Address system announcements
Others as required
Others as required
FS
FS
Fire Protection
Fire Protection
System Status
System Status
AC Power
AC Power
Maintenance
Maintenance
5. Maintenance
5. Maintenance
Maintenance
Maintenance
• Regular Testing and Inspection
• False Alarm Management
• Common Maintenance Problems And
Troubleshooting
5. Maintenance
5. Maintenance
Maintenance
Maintenance
Objectives
a. to ensure continuous reliability of the fire alarm
system
Responsibility
a. building owner or owner representatives
• to engage manufacturer’s representative or
• competent contractor
• owner representative with suitable experience
and special training
5. Maintenance
5. Maintenance
Regular Testing and Inspection
Regular Testing and Inspection
As per SS : CP10-2005 Requirements
• Daily Check
• Weekly Test
• Monthly Test
• Annual Test
5. Maintenance
5. Maintenance
Regular Testing and Inspection
Regular Testing and Inspection
Daily Checks
- Checks to ensure system is operating normally.
- Rectify and record any faults found
Weekly Tests
- Checks to ensure signal to monitoring station are functioning
- Check battery and voltage conditions
- Rectify and record any faults
Monthly Tests
- Simulate fire and fault conditions on all zones
- Check that power supply, indicator, alarm outputs etc are operating
correctly
- Rectify and record any faults
Yearly Tests
- All monthly tests
- Test 20 percent of all detectors over as many zones as possible such that all
detectors will be check over a 5 year period
- Test interlocking circuits to ancillary equipment
- Check and cleaning of dirty detectors
- Rectify and record any faults
INITIALS
DATE
COMPLETED
FOLLOWUP ACTION
INITIALS
REMARKS
DESCRIPTION OF
EVENTS
TIME
DATE
Building Name
Address
Log Record
5. Maintenance
5. Maintenance
5. Maintenance
5. Maintenance
False Alarm Management
False Alarm Management
1. false alarm causes disruption to the normal operation
of business and create a drain to the fire services
2. responsibility for reducing false alarms rest with
every party involved in
- specification
- design
- installation
- commissioning
- management at the operation level
- maintenance
of the fire alarm system
5. Maintenance
5. Maintenance
False Alarm Management
False Alarm Management
Category of False Alarms
Unwanted Alarms / False Alarm
a. environmental influences
b. fire like phenomena
c. inappropriate action by people in building
d. accidental damage
e. alarms arising out of faulty equipment
5. Maintenance
5. Maintenance
False Alarm Management
False Alarm Management
Common Causes of False Alarms
• fumes from cooking process
• steam from bathrooms, showers etc
• tobacco smoke
• dust ( whether built up over time or not)
• insects
• incense, candle
• high humidity
• accidental damage (manual call point)
• aerosol spray
• high air velocities
• water egress
• testing or maintenance of the system without proper
disablement.
• arises from fault in equipment
5. Maintenance
5. Maintenance
False Alarm Management
False Alarm Management
Recommendations
a. system designer should ensure that that the system design
takes into account of the guidance provided the Code of
Practices
b. installer identifies any circumstances that might lead to a high
rate of false alarm and inform the designer, or user
accordingly
c. at commissioning, checks should be carried out to ensure
there is no obvious potential for an unacceptable level of false
alarms
d. the designer and supplier should jointly provide sufficient
information to user who may not be familiar with the
technology of the Fire Alarm system.
5. Maintenance
5. Maintenance
False Alarm Management
False Alarm Management
Recommendations – cont’d
e. the user should arrange for suitable investigation and if
appropriate, action to be taken on every occasion that a
false alarm occurs and record the details which should
include the following details :
- date & time
- identity and location of device
- category of false alarm
- reason for false alarm (if known)
- activity in the area ( if the reason of false alarm is
unknown)
- action taken
- the person responsible for recording the information
False Alarm Management
False Alarm Management
Some Useful Tools to help
Some Useful Tools to help
minimize False Alarms
minimize False Alarms
5. Maintenance
5. Maintenance
False Alarm management
False Alarm management
HIGH
1
2
3
4
LOW
Sensitivity Settings
• This is a feature normally in both addressable and non
addressable type Fire Alarm System.
• Addressable – Adjusted from Panel
• Non-Addressable – Physical Device Selection
5. Maintenance
5. Maintenance
5. Maintenance
5. Maintenance
20
Alarm retard
state
140 (min)
320 (max)
Alarm confirmation
state
Receipt of
1st alarm
signal
0
Normal
state
Normal
state Time (s)
Auto reset
Of 1st alarm
signal
False Alarm Management
False Alarm Management
To reduce the effects of transient environmental conditions which
may cause various types of detectors to be activated, an automatic
fire alarm system may be provided with an alarm verification
feature, subject to the approval of the relevant authority.
The following components of the fire alarm system shall not be
subject to this feature;
a) Alarm Zone facilities containing only manual call points;
b) Circuit between sub-alarm panels and the main alarm panels;
c) Detectors used to activate fire suppression systems;
d) Detectors installed in high risk areas; and
e) Alarm zone circuits from fire suppression systems.
False Alarm Management
False Alarm Management
Sensor Auto Contamination Adjustments
5. Maintenance
5. Maintenance
Auto
adjusted
alarm level
Rising idle
level due to
Contamination
Initial
alarm
point
ANALOGUE
LEVEL
TIME
MONTHS
Initial
idle
level
Common Maintenance Problems
Common Maintenance Problems
4 Storey High Atrium that is protected by point type
smoke detectors
Problem:
Problem:
Detectors cannot be tested
Detectors cannot be tested
Faulty detectors cannot be reach for replacement
Faulty detectors cannot be reach for replacement
Detector insensitive due to the mounting height exceeding
Detector insensitive due to the mounting height exceeding
10metre
10metre
Solution :
Solution :
Select an alternative detection system
Select an alternative detection system
Able to comply with the Listed Installation Requirements
Able to comply with the Listed Installation Requirements
Easy to maintain without having to access from the atrium
Easy to maintain without having to access from the atrium
Floor
Floor
Common Maintenance Problems
Common Maintenance Problems
5. Maintenance
5. Maintenance
5. Maintenance
5. Maintenance
5. Maintenance
5. Maintenance
5. Maintenance
5. Maintenance
Thank You
Thank You
for
for
your attention
your attention

More Related Content

Similar to fire alarm Automatic Fire Detection and Alarm Systems

cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
nipunwijewardhana
 
Codigos y perifericos rep 2001
Codigos y perifericos rep 2001Codigos y perifericos rep 2001
Codigos y perifericos rep 2001
Jesus Ciau
 
Fire alarm system_nec_september[1]
Fire alarm system_nec_september[1]Fire alarm system_nec_september[1]
Fire alarm system_nec_september[1]
Jennifer Kleinhenz
 
Fire alarm system_nec_september[1]
Fire alarm system_nec_september[1]Fire alarm system_nec_september[1]
Fire alarm system_nec_september[1]
Jennifer Kleinhenz
 

Similar to fire alarm Automatic Fire Detection and Alarm Systems (20)

Fire alarm systems
Fire alarm systemsFire alarm systems
Fire alarm systems
 
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
 
Design of alarm using pir sensor for
Design of alarm using pir sensor forDesign of alarm using pir sensor for
Design of alarm using pir sensor for
 
Fire detection system operation
Fire detection system operationFire detection system operation
Fire detection system operation
 
Fire alarm and bildge alarm system
Fire alarm and bildge alarm systemFire alarm and bildge alarm system
Fire alarm and bildge alarm system
 
Fire alarm , detection and suppression system
Fire alarm , detection and suppression systemFire alarm , detection and suppression system
Fire alarm , detection and suppression system
 
fire detection and alarm system
fire detection and alarm systemfire detection and alarm system
fire detection and alarm system
 
Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?
 
Codigos y perifericos rep 2001
Codigos y perifericos rep 2001Codigos y perifericos rep 2001
Codigos y perifericos rep 2001
 
Bluetooth Based Fire Detection and Robust Protection System By Using Arduino
Bluetooth Based Fire Detection and Robust Protection System By Using ArduinoBluetooth Based Fire Detection and Robust Protection System By Using Arduino
Bluetooth Based Fire Detection and Robust Protection System By Using Arduino
 
Fire Detection and Alarm System (FDAS).pptx
Fire Detection and Alarm System (FDAS).pptxFire Detection and Alarm System (FDAS).pptx
Fire Detection and Alarm System (FDAS).pptx
 
Fire alarm system_nec_september[1]
Fire alarm system_nec_september[1]Fire alarm system_nec_september[1]
Fire alarm system_nec_september[1]
 
Fire alarm system_nec_september[1]
Fire alarm system_nec_september[1]Fire alarm system_nec_september[1]
Fire alarm system_nec_september[1]
 
FIRE ALARM SYSTEM.pdf
FIRE ALARM SYSTEM.pdfFIRE ALARM SYSTEM.pdf
FIRE ALARM SYSTEM.pdf
 
Fire Alarm System.pdf
Fire Alarm System.pdfFire Alarm System.pdf
Fire Alarm System.pdf
 
optical beam security system
optical beam security systemoptical beam security system
optical beam security system
 
Fire Alarm Response Indicator in Delhi.pptx
Fire Alarm Response Indicator in Delhi.pptxFire Alarm Response Indicator in Delhi.pptx
Fire Alarm Response Indicator in Delhi.pptx
 
Basic of fire protection system, fire control types and types of agents to ex...
Basic of fire protection system, fire control types and types of agents to ex...Basic of fire protection system, fire control types and types of agents to ex...
Basic of fire protection system, fire control types and types of agents to ex...
 
Class 1 | NFPA 72 | Overview Fire Alarm System
Class 1 | NFPA 72 | Overview Fire Alarm SystemClass 1 | NFPA 72 | Overview Fire Alarm System
Class 1 | NFPA 72 | Overview Fire Alarm System
 
Home alarm system
Home alarm systemHome alarm system
Home alarm system
 

More from Prantik Adhar Samanta (7)

CIVIL FDN.DRG.FOR 3200 DIA.CEMENT SILO.ELSA CONCRETE-Model-Model.pdf
CIVIL FDN.DRG.FOR 3200 DIA.CEMENT  SILO.ELSA CONCRETE-Model-Model.pdfCIVIL FDN.DRG.FOR 3200 DIA.CEMENT  SILO.ELSA CONCRETE-Model-Model.pdf
CIVIL FDN.DRG.FOR 3200 DIA.CEMENT SILO.ELSA CONCRETE-Model-Model.pdf
 
shear force and bending moment diagram
shear force and  bending  moment diagramshear force and  bending  moment diagram
shear force and bending moment diagram
 
Two Pile Group.pdf
Two Pile Group.pdfTwo Pile Group.pdf
Two Pile Group.pdf
 
Helical Staircase.pdf
Helical Staircase.pdfHelical Staircase.pdf
Helical Staircase.pdf
 
Rectangular Tapered Footing ITI 15.12.22 F1.pdf
Rectangular Tapered Footing ITI 15.12.22 F1.pdfRectangular Tapered Footing ITI 15.12.22 F1.pdf
Rectangular Tapered Footing ITI 15.12.22 F1.pdf
 
Lecture22.pdf
Lecture22.pdfLecture22.pdf
Lecture22.pdf
 
46636317 floor-load
46636317 floor-load46636317 floor-load
46636317 floor-load
 

Recently uploaded

AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
ankushspencer015
 

Recently uploaded (20)

(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICSUNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 

fire alarm Automatic Fire Detection and Alarm Systems

  • 1. Overview of Fire Alarm Overview of Fire Alarm Systems and Systems and Maintenance Maintenance Mr. David Goh Vice President – Fire Safety Managers’ Association Convener of Working Group for CP 10 : 2005 Er. Matthew Kwek Committee Member – Fire Safety Managers’ Association P.E., R.I.(M&E), FSE By
  • 2. 1 1 Fire Alarm Systems Fire Alarm Systems – – A Quick Introduction A Quick Introduction a. a. Why use a Fire Alarm System? Why use a Fire Alarm System? b. b. Is Fire Alarm System a mandatory requirement? Is Fire Alarm System a mandatory requirement? c. c. What is a Fire Alarm System made up of? What is a Fire Alarm System made up of? 2 2 Types of Fire Alarm Systems in use today Types of Fire Alarm Systems in use today a. a. Non Non – – Addressable Addressable b. b. Addressable Addressable c. c. Hybrid Hybrid 3 Maintenance 3 Maintenance a. a. Regular testing and Inspection Regular testing and Inspection b. b. False Alarm Management False Alarm Management c. c. Common Maintenance Problems And Common Maintenance Problems And Troubleshooting Troubleshooting CONTENTS
  • 3. Why use a Fire Alarm System? Why use a Fire Alarm System? • A fire alarm system is intended to enable a fire to be detected at a sufficiently early stage so that people who are at risk can be made safe either by escaping from the fire, or by the fire being extinguished (also to prevent extensive property damage). Neither of these measures can be used until people are made aware of fire. • The effectiveness of the fire detection and alarm system depends on the stage of the fire at which it is operated. In order for all the occupants to escape without too much difficulty, an early alarm should operate before the escape routes becomes smoke- logged to such an extent as will cause occupants to have difficulty finding their way out of the building. 1. Fire Alarm Systems 1. Fire Alarm Systems – – A Quick Introduction A Quick Introduction
  • 4. 1. Fire Alarm Systems 1. Fire Alarm Systems – – A Quick Introduction A Quick Introduction Why use a Fire Alarm System? Why use a Fire Alarm System? Fire Alarm Systems are used to protect life and property. It protects by: a. detecting a fire at an early stage b. alerting and evacuating occupants c. notifying the relevant personnel d. activating auxiliary functions e.g. smoke controls, lift homing etc e. identifying and guiding fire fighters
  • 5. 1. Fire Alarm Systems 1. Fire Alarm Systems – – A Quick Introduction A Quick Introduction Is Fire Alarm System a mandatory Is Fire Alarm System a mandatory requirement? requirement? Mandatory Mandatory - - By the relevant authority By the relevant authority Non Non- -mandatory mandatory - - By Building Owner, Landlord & By Building Owner, Landlord & Insurance etc. Insurance etc. The requirements are specified in : The requirements are specified in : - - Code of Practice for Fire Precautions in Buildings 2007 Code of Practice for Fire Precautions in Buildings 2007 (Fire Code 2007) (Fire Code 2007) – – by SCDF by SCDF - - Code of Practice for Installation and Servicing of Electrical Fi Code of Practice for Installation and Servicing of Electrical Fire re Alarm System Alarm System (SS CP10 (SS CP10- -2005) 2005) – – by Spring Singapore by Spring Singapore
  • 6. What is a Fire Alarm System made up of? What is a Fire Alarm System made up of? 1. Fire Alarm Systems 1. Fire Alarm Systems – – A Quick Introduction A Quick Introduction Components forming the System Components forming the System- - 9 Items 9 Items 1. 1. Smoke / Heat Smoke / Heat Detectors ( Detectors (Fire Detectors Fire Detectors) ) 2. 2. Alarm Panels ( Alarm Panels (Control and Indicating Equipment Control and Indicating Equipment) ) 3. 3. Alarm Bells ( Alarm Bells (Fire Alarm Devices Fire Alarm Devices) ) 4. 4. Manual Call Points Manual Call Points 5. 5. DECAM Panel ( DECAM Panel (Fire Services Fire Services Signalling Signalling Transmitter Transmitter) ) 6. 6. DECAM Station ( DECAM Station (Alarm Monitoring Station Alarm Monitoring Station) ) 7. 7. Extinguishing Panels ( Extinguishing Panels (Control for automatic fire protection equipment Control for automatic fire protection equipment) ) 8. 8. Gas/Sprinkler ( Gas/Sprinkler (Automatic fire protection equipment Automatic fire protection equipment) ) 9. 9. Charger/Battery ( Charger/Battery (Power Supply Equipment Power Supply Equipment) )
  • 7. 1. Fire Alarm Systems 1. Fire Alarm Systems – – A Quick Introduction A Quick Introduction What is a Fire Alarm System made up of? What is a Fire Alarm System made up of? DECAMS FIRE Fire Detectors Fire Detectors Manual Call Points Manual Call Points Control & Indicating Control & Indicating Equipment Equipment Fire Alarm Device Fire Alarm Device Fire Alarm Signal Fault Signal Fire Service Fire Service SignallingTransmitter SignallingTransmitter Alarm Monitoring Alarm Monitoring Station Station Control for Automatic Control for Automatic Fire Protection Equipment Fire Protection Equipment Automatic Automatic Fire Protection Fire Protection Equipment Equipment Power Supply Equipment Power Supply Equipment
  • 8. Types of Fire Alarm Systems Types of Fire Alarm Systems in use today in use today
  • 9. 2. Types of Fire Alarm Systems in use today 2. Types of Fire Alarm Systems in use today Non Non- -Addressable System Addressable System - - also commonly known as also commonly known as “ “conventional conventional” ” - - fire detectors are wired to the panel in groups known as zone fire detectors are wired to the panel in groups known as zone - - identification of alarm status by zone identification of alarm status by zone - - fire detectors indicates either fire detectors indicates either “ “Fire Fire” ” or or “ “Normal Normal” ” status only status only - - system only indicate events but without event recording system only indicate events but without event recording feature feature s s s s s s s s s s Zone 1 Zone 2 Zone 2 Zone 1 Zone 1 Fire Zone 2 Fire
  • 10. Typical Non Typical Non- -Addressable Fire Alarm System Addressable Fire Alarm System Configuration Configuration 2. Types of Fire Alarm Systems in use today 2. Types of Fire Alarm Systems in use today Fire Protection Fire Protection System Status System Status Elevator recall Elevator recall Essential Extract Fans, pressurization fans etc Essential Extract Fans, pressurization fans etc Release escape doors Release escape doors Release normally open fire doors Release normally open fire doors Public Address system announcements Public Address system announcements Others as required Others as required AC Power AC Power FS FS FS FS FS FS
  • 11. 2. Types of Fire Alarm Systems in use today 2. Types of Fire Alarm Systems in use today Addressable System Addressable System - - each fire detector is provided with an address each fire detector is provided with an address - - identification of alarm status by zone and by address identification of alarm status by zone and by address - - fire detectors indicates various condition such as smoke fire detectors indicates various condition such as smoke level level - - indicates and records system events indicates and records system events Zone 1 Zone 2 Zone 2 Zone 1 s s s s s s s s s s Zone 2 Zone 1 Zone 1 Fire Detector 4 s
  • 12. Typical Addressable Fire Alarm System Typical Addressable Fire Alarm System Configuration Configuration 2. Types of Fire Alarm Systems in use today 2. Types of Fire Alarm Systems in use today Elevator recall Elevator recall Essential Extract Fans, pressurization fans etc Essential Extract Fans, pressurization fans etc Release escape doors Release escape doors Release normally open fire doors Release normally open fire doors Public Address system announcements Public Address system announcements Others as required Others as required AC Power AC Power FS FS Fire Protection Fire Protection System Status System Status
  • 13. 2. Types of Fire Alarm Systems in use today 2. Types of Fire Alarm Systems in use today Hybrid System Hybrid System (conventional + addressable) (conventional + addressable) - - a combination of features from both addressable and a combination of features from both addressable and non non- -addressable systems addressable systems - - either built from a basic conventional system with add either built from a basic conventional system with add- -on on hardwire addressable features hardwire addressable features - - or built from an addressable system with conventional module or built from an addressable system with conventional module - - event recording and alarm management feature event recording and alarm management feature
  • 14. 2. Types of Fire Alarm Systems in use today 2. Types of Fire Alarm Systems in use today Typical Hybrid Fire Alarm System Configuration Typical Hybrid Fire Alarm System Configuration ( conventional with hardwire addressable add ( conventional with hardwire addressable add- -on) on) RS232 Cable Colour Graphics Station Note Book Hand-Held Printer Palm PDA Built-in Printer Interface Options Address lines Zone Signal Conventional devices – any reputable manufacturer HyBrid
  • 15. 2. Types of Fire Alarm Systems in use today 2. Types of Fire Alarm Systems in use today Typical Hybrid Fire Alarm System Configuration Typical Hybrid Fire Alarm System Configuration ( conventional with hardwire addressable add ( conventional with hardwire addressable add- -on) on) FS FS Fire Protection Fire Protection System Status System Status Elevator recall Elevator recall Essential Extract Fans, pressurization fans etc Essential Extract Fans, pressurization fans etc Release escape doors Release escape doors Release normally open fire doors Release normally open fire doors Public Address system announcements Public Address system announcements Others as required Others as required AC Power AC Power FS FS FS FS
  • 16. 2. Types of Fire Alarm Systems in use today 2. Types of Fire Alarm Systems in use today Typical Hybrid Fire Alarm System Configuration Typical Hybrid Fire Alarm System Configuration ( addressable with conventional module add ( addressable with conventional module add- -on) on) Elevator recall Elevator recall Essential Extract Fans, pressurization fans etc Essential Extract Fans, pressurization fans etc Release escape doors Release escape doors Release normally open fire doors Release normally open fire doors Public Address system announcements Public Address system announcements Others as required Others as required FS FS Fire Protection Fire Protection System Status System Status AC Power AC Power
  • 18. 5. Maintenance 5. Maintenance Maintenance Maintenance • Regular Testing and Inspection • False Alarm Management • Common Maintenance Problems And Troubleshooting
  • 19. 5. Maintenance 5. Maintenance Maintenance Maintenance Objectives a. to ensure continuous reliability of the fire alarm system Responsibility a. building owner or owner representatives • to engage manufacturer’s representative or • competent contractor • owner representative with suitable experience and special training
  • 20. 5. Maintenance 5. Maintenance Regular Testing and Inspection Regular Testing and Inspection As per SS : CP10-2005 Requirements • Daily Check • Weekly Test • Monthly Test • Annual Test
  • 21. 5. Maintenance 5. Maintenance Regular Testing and Inspection Regular Testing and Inspection Daily Checks - Checks to ensure system is operating normally. - Rectify and record any faults found Weekly Tests - Checks to ensure signal to monitoring station are functioning - Check battery and voltage conditions - Rectify and record any faults Monthly Tests - Simulate fire and fault conditions on all zones - Check that power supply, indicator, alarm outputs etc are operating correctly - Rectify and record any faults Yearly Tests - All monthly tests - Test 20 percent of all detectors over as many zones as possible such that all detectors will be check over a 5 year period - Test interlocking circuits to ancillary equipment - Check and cleaning of dirty detectors - Rectify and record any faults
  • 23. 5. Maintenance 5. Maintenance False Alarm Management False Alarm Management 1. false alarm causes disruption to the normal operation of business and create a drain to the fire services 2. responsibility for reducing false alarms rest with every party involved in - specification - design - installation - commissioning - management at the operation level - maintenance of the fire alarm system
  • 24. 5. Maintenance 5. Maintenance False Alarm Management False Alarm Management Category of False Alarms Unwanted Alarms / False Alarm a. environmental influences b. fire like phenomena c. inappropriate action by people in building d. accidental damage e. alarms arising out of faulty equipment
  • 25. 5. Maintenance 5. Maintenance False Alarm Management False Alarm Management Common Causes of False Alarms • fumes from cooking process • steam from bathrooms, showers etc • tobacco smoke • dust ( whether built up over time or not) • insects • incense, candle • high humidity • accidental damage (manual call point) • aerosol spray • high air velocities • water egress • testing or maintenance of the system without proper disablement. • arises from fault in equipment
  • 26. 5. Maintenance 5. Maintenance False Alarm Management False Alarm Management Recommendations a. system designer should ensure that that the system design takes into account of the guidance provided the Code of Practices b. installer identifies any circumstances that might lead to a high rate of false alarm and inform the designer, or user accordingly c. at commissioning, checks should be carried out to ensure there is no obvious potential for an unacceptable level of false alarms d. the designer and supplier should jointly provide sufficient information to user who may not be familiar with the technology of the Fire Alarm system.
  • 27. 5. Maintenance 5. Maintenance False Alarm Management False Alarm Management Recommendations – cont’d e. the user should arrange for suitable investigation and if appropriate, action to be taken on every occasion that a false alarm occurs and record the details which should include the following details : - date & time - identity and location of device - category of false alarm - reason for false alarm (if known) - activity in the area ( if the reason of false alarm is unknown) - action taken - the person responsible for recording the information
  • 28. False Alarm Management False Alarm Management Some Useful Tools to help Some Useful Tools to help minimize False Alarms minimize False Alarms 5. Maintenance 5. Maintenance
  • 29. False Alarm management False Alarm management HIGH 1 2 3 4 LOW Sensitivity Settings • This is a feature normally in both addressable and non addressable type Fire Alarm System. • Addressable – Adjusted from Panel • Non-Addressable – Physical Device Selection 5. Maintenance 5. Maintenance
  • 30. 5. Maintenance 5. Maintenance 20 Alarm retard state 140 (min) 320 (max) Alarm confirmation state Receipt of 1st alarm signal 0 Normal state Normal state Time (s) Auto reset Of 1st alarm signal False Alarm Management False Alarm Management To reduce the effects of transient environmental conditions which may cause various types of detectors to be activated, an automatic fire alarm system may be provided with an alarm verification feature, subject to the approval of the relevant authority. The following components of the fire alarm system shall not be subject to this feature; a) Alarm Zone facilities containing only manual call points; b) Circuit between sub-alarm panels and the main alarm panels; c) Detectors used to activate fire suppression systems; d) Detectors installed in high risk areas; and e) Alarm zone circuits from fire suppression systems.
  • 31. False Alarm Management False Alarm Management Sensor Auto Contamination Adjustments 5. Maintenance 5. Maintenance Auto adjusted alarm level Rising idle level due to Contamination Initial alarm point ANALOGUE LEVEL TIME MONTHS Initial idle level
  • 32. Common Maintenance Problems Common Maintenance Problems
  • 33. 4 Storey High Atrium that is protected by point type smoke detectors Problem: Problem: Detectors cannot be tested Detectors cannot be tested Faulty detectors cannot be reach for replacement Faulty detectors cannot be reach for replacement Detector insensitive due to the mounting height exceeding Detector insensitive due to the mounting height exceeding 10metre 10metre Solution : Solution : Select an alternative detection system Select an alternative detection system Able to comply with the Listed Installation Requirements Able to comply with the Listed Installation Requirements Easy to maintain without having to access from the atrium Easy to maintain without having to access from the atrium Floor Floor Common Maintenance Problems Common Maintenance Problems 5. Maintenance 5. Maintenance
  • 37. Thank You Thank You for for your attention your attention