Ex-3000 SeriesProductDataSheet
User Manual for
Ex-3001
Extinguishing Control Panel
The operation and functions
described in the manual are
available from Software Versions
Ex3001_V2_00 onwards.
Page 2 of 20
Table of Contents
1 INTRODUCTION __________________________________________________________ 3
1.1 Standards ____________________________________________________________ 3
1.2 Cautions and Warnings __________________________________________________ 3
1.3 Description ___________________________________________________________ 3
2 OPERATION _____________________________________________________________ 4
2.1 Introduction ___________________________________________________________ 4
2.1.1 Access Levels _____________________________________________________ 4
2.1.2 Front Panel Controls and Indications ____________________________________ 4
2.1.2.1 Display _________________________________________________________________ 4
2.1.2.2 LED Indications __________________________________________________________ 5
2.1.2.3 Manual Release Button ____________________________________________________ 6
2.1.2.4 Control Buttons___________________________________________________________ 6
2.1.2.5 Menu and Navigation Buttons _______________________________________________ 7
2.1.2.6 Key-Switches ____________________________________________________________ 7
2.1.2.7 Buzzer _________________________________________________________________ 7
2.1.3 Enable Controls ____________________________________________________ 8
2.1.4 Navigating through menus ____________________________________________ 8
2.1.5 Numeric data entry__________________________________________________ 8
2.2 Operating Conditions____________________________________________________ 9
2.2.1 Fire Alarm Condition_________________________________________________ 9
2.2.2 Release / Activated Condition _________________________________________ 9
2.2.3 Hold Condition ____________________________________________________ 11
2.2.4 Abort Condition____________________________________________________ 11
2.2.5 Fault Condition ____________________________________________________ 11
2.2.6 Warning Condition _________________________________________________ 12
2.3 Level 1 Menu Functions ________________________________________________ 12
2.3.1 Enable Controls ___________________________________________________ 12
2.3.2 View ____________________________________________________________ 12
2.3.3 LED Test ________________________________________________________ 12
2.4 Level 2 Menu Functions ________________________________________________ 13
2.4.1 View ____________________________________________________________ 13
2.4.1.1 Faults _________________________________________________________________ 13
2.4.1.2 Disables _______________________________________________________________ 14
2.4.1.3 Warnings ______________________________________________________________ 14
2.4.1.4 Log ___________________________________________________________________ 14
2.4.1.5 Software Versions _______________________________________________________ 15
2.4.2 Test ____________________________________________________________ 15
2.4.2.1 Zones _________________________________________________________________ 15
2.4.2.2 Display ________________________________________________________________ 16
2.4.2.3 Buzzer ________________________________________________________________ 16
2.4.3 Extinguishant Modes _______________________________________________ 17
2.4.3.1 Mode _________________________________________________________________ 17
2.4.3.2 Extract ________________________________________________________________ 17
2.4.4 Disable / Enable ___________________________________________________ 18
2.4.5 Date/Time________________________________________________________ 18
Page 3 of 20
1 Introduction
1.1 Standards
The Ex-3001 Gas Extinguishing Control Panel conforms to the following standards:
BS EN12094-1: 2003 Extinguishing Control Device
BS EN54-2: 1998 Control and Indicating Equipment
BS EN54-4: 1998 Power Supply Equipment
BS EN60950: 2000 Safety of information technology equipment
BS EN50130-4: 1996 Product Family Standard
Electromagnetic Compatibility Directive 89/336/EEC (and the amending directive 92/23/EEC)
Low Voltage Directive 73/23/EEC
1.2 Cautions and Warnings
Only Trained service personnel should undertake the Installation,
Programming and Maintenance of this equipment.
1.3 Description
This manual covers the use and how to operate the Ex-3000 Series Extinguishing Control Panels.
Refer to the Installation Manual (Document No. 680-147) for details of installation, programming
and commissioning of the panel.
The Ex-3001 is a Single Flooding Zone Control Panel with up to three detection zone circuits.
The detection zones are compatible with conventional detectors and call points.
Page 4 of 20
2 Operation
2.1 Introduction
These instructions cover the operation and use of the panels.
2.1.1 Access Levels
The panel operation is protected from inadvertent and erroneous misuse by means of four access
levels. These levels are as follows:
• Level 1 Untrained user
• Level 2 Authorised User
• Level 3 Commissioning, Service and Maintenance
• Level 4 Commissioning, Service and Maintenance – Special Tools Required
This document covers the Level 1 and Level 2 User functions. For details on the installation,
programming and commissioning of the panel, refer to Manual 680-147. Full details are supplied
with any special tools.
• A Level 1 Untrained User can view the current operational condition of the system and may
MUTE the internal buzzer.
• A Level 2 Authorised User can view the operational condition of the system and may MUTE
the internal buzzer. In addition, the RESOUND/SOUND ALARMS, SILENCE and RESET
buttons are enabled and access to the Level 2 Menu functions is available. This requires a
password (or key-switch).
• NOTES: There are up to 4 User ID codes available, each with its own password. The panel
can be configured to automatically cancel access to Level 2 functions after a specified period.
2.1.2 Front Panel Controls and Indications
Key-Switch Assembly
USB
SUPPLY
PSU
Comms PROGRUN
uP MODE
R EBO OT
R elay-1 F IR E
R e la y
R elay-2 FA U LT
R ela y
R S 485 A U X
S up ply
Z O N E
- 1 -
Z O N E
- 2 -
Z O N E
- 3 -
S N D R
- 1 -
S N D R
- 2 -
S N D R
- 3 -
M O D E
S elect
M an ua l
Trig ge r
H O LD A B O RT P ressure
M onitor
VA LV E
M on itor
FL O W
M o nitor
A ctu ator
O utpu t
P ROG
Input-1
PRO G
Input-2
PROG
Input-3
PROG
Input-4
MANUAL ONLY AUTO +
MANUAL
VALVE CLOSEDMANUAL
DISABLED
DISABLED FAULT
TIMER HELD ABORTED
RELEASE
IMMINENT
RELEASED
EXTINGUISHANT
POWER SYSTEM FAULT
TEST SOUNDER DELAYED
DISABLE SOUNDER DISABLED
FAULT SOUNDER FAULT
FIRE SILENCED
GENERAL
- 1 -
DETECTION ZONES
F IR E FA U LT /
T E S T /
D IS A B L E
- 2 -
- 3 -
ESC MENU
WXYZTUVPQRS
GHI JKL MNO
DEFABC
R E S E T
S ILE N CE
M U T E
!
RESOUND /
SOUND
ALARMS
BS EN 54-2: 1998 BS EN 54-4: 1998
BS EN 12094-1: 2003 CLASS-A
EXTINGUISHANT
RELEASE
PULL DOWN AND PRESS BUTTON
Extinguishant StatusNumber ButtonsControl ButtonsGeneral Status
LCD Navigation Buttons Detection Zone Status Manual Release Button
2.1.2.1 Display
The LCD along with the LED Indicators shows the operating status of the system. Examples of
the information presented is shown below:
Page 5 of 20
Normal Display Non-normal Display Typical Menu Display
[System status]
1 of 1 conditions:
DETECTION ZONE3
OPEN CIRCUITSYSTEM NORMAL
22 AUG 2007 16:39:00
[Release status]
UNAFFECTED
[Level 2 Menu]
VIEW .
TEST
MODES
DISABLE / ENABLE
EXIT LEVEL 2
Release Imminent Release Activated Release Complete
RELEASE ACTIVATED
00:00:05 Elapsed
RELEASE ACTIVATED
00:00:24 Elapsed
[Release status]
RELEASE IMMINENT..
-15 GAS RESET INHIBITED
DISCHARGE COMPLETE
(No Flow Detected)
RESET ALLOWED
The display shows a countdown
timer with the amount of time
remaining before the extinguishant
is released.
The display shows the time
elapsed since the extinguishant
release commenced.
2.1.2.2 LED Indications
The LED Status Indications show the basic operational state of the panel and whether the panel
is in a fire alarm, fault, disabled or test condition.
2.1.2.2.1 GENERAL STATUS
Function Colour Description
FIRE Red Indicates that the system has detected a fire alarm condition
FAULT Yellow Indicates that the system has detected a fault condition
DISABLE Yellow Indicates that part of the system has been disabled (i.e. isolated)
TEST Yellow Indicates that part of the system is in a test condition
POWER Green Indicates the presence of power
SILENCED Yellow Indicates that the geneal fire alarm sounders have been silenced
SOUNDER FAULT Yellow Indicates the presence of a fault in either or both of the general fire alarm sounder wiring
circuits
SOUNDER DISABLED Yellow Indicates that either or both of the general fire alarm sounder circuits have been disabled
(i.e. isolated)
DELAYED Yellow Not used
SYSTEM FAULT Yellow Indicates the presence of a system fault
2.1.2.2.2 DETECTION ZONE STATUS
Function Colour Description
FIRE Red Indicates that the system has detected a fire alarm condition in the respecitve zone
FAULT/TEST/DISABLE Yellow Indicates that the system has (flashing indication) detected a fault condition in the respecitve
zone or (steady indication) that the zone is either in a test state or in a disabled state
Page 6 of 20
2.1.2.2.3 EXTINGUISHANT
Function Colour Description
RELEASE IMMINENT Red Indicates (flashing) that the release of extinguishant is imminent. The indication will turn to
steady when the signal to release the extinguishant has been activated.
RELEASED Red Indicates that the release of extinguishant has occurred and the panel has detected the flow
of the extinguishant released.
TIMER HELD Yellow Indicates that the imminent release of extinguishant is temproraily suspended.
ABORTED Yellow Indicates that the imminent release of the extinguishant has been aborted.
DISABLED Yellow Indicates that the extinguishant release control signal has been disabled. The release of
extinguishant is prevented even if a fire alarm or manual release are present.
FAULT Yellow Indicates that the system has detected a fault condition within part of the extinguishing
control device (ECD) circuits. The General Fault LED will also be illuminated.
MANUAL DISABLED Yellow Indicates that one or more buttons for manual release have been disabled.
VALVE CLOSED Yellow Indicates that the extinguishant is blocked by a manual shut-off valve and that there may be
no extinguishant available to suppress a fire – Ensure immediate remedial action is taken to
address the problem.
MANUAL ONLY Yellow Indicates that the extinguishant can only be released by means of a manual release button.
AUTO + MANUAL Yellow Indicates that the extinguishant can be released by both the automatic detection of a fire
alarm and by means of a manual release button.
2.1.2.3 Manual Release Button
To manually release the extinguishant, pull down the flap and press the button marked with the
circle.
2.1.2.4 Control Buttons
Reset
Press to reset the panel from a fire alarm condition and/ or a
gas release sequence.
Only available with
Level 2 Access.
!
Mute
Press to mute the internal buzzer.
Available in both
Level 1 and Level 2
Silence 1
Press to silence the sounders.
Only available with
Level 2 Access.
Resound / Sound Alarms
Press again to re-activate the sounders.
Press to initiate a manual evacuation and sound the alarms.
Only available with
Level 2 Access.
1
SILENCE will silence all sounders except for the flooding zone (protected area) sounders when the system is in the
activated state. Once the extinguishant has been released, it is possible to silence the flooding zone sounders.
Page 7 of 20
2.1.2.5 Menu and Navigation Buttons
Press to scroll through Menu Options.
Press to display more information.
Press to scroll through menu Options.
Press to scroll through lists of zones or devices.
Press to confirm entry of numeric information entry.
Press to confirm selection of a menu option.
Press to change some of the configuration options.
W X Y Z
Used to enter numbers.
E S C
Press to exit the menu functions and return to the
normal display.
E S C M E N U
W X Y ZT U VP Q R S
G H I J K L M N O
D E FA B C
M E N U
Press to show or return to Menu Functions.
2.1.2.6 Key-Switches
One or two key-switches can be fitted to the panel.
The functions of these are programmable and the installer
will have inserted a label to indicate their use.
Typical uses are:
AUTO + MANUAL / MANUAL ONLY Selection
LEVEL 1 / LEVEL 2 ACCESS Selection
Depending on the key-switch mechanism fitted, the key
may be removable in only one position or removable in
both operating positions.
2.1.2.7 Buzzer
The buzzer produces two different sounds to differentiate between fire alarm conditions and fault /
warning conditions.
Condition Operation
Fire Alarm The buzzer operates with a continuous tone.
Fault The buzzer operates intermittently.
Page 8 of 20
2.1.3 Enable Controls
Controls are normally disabled. If a level 2 Access key-switch is fitted use this in preference to
passwords.
To enable the control keys or gain access to the Level 2, press the Menu button. The display
shows the following:
[CONTROLS DISABLED]
ENABLE CONTROLS
VIEW
LED TEST
Enter Your Password Enter Your Password
**
Press the button to select the
‘Enable Controls’ option.
The display prompts for entry of
the password.
Enter the password. As each
number is pressed, an *
character is displayed. Finally,
press the button to confirm.
[Level 2 Menu]
VIEW .
TEST
EXTINGUISH MODES
DISABLE / ENABLE
EXIT LEVEL 2
Enter Your Password
Not Recognized!
The display then shows the Level 2
Menu options.
If the password is incorrect (or if
not entered in time) the above
message is shown.
If a control button is pressed at Level 1, the display prompts for password entry. To continue,
enter the password. If the password is valid, the relevant control function will be activated and the
display will remain at Level 1.
2.1.4 Navigating through menus
When a menu is displayed, use the buttons to highlight the required menu option and then
press the button to select it.
Press the ESC button from within a menu option to return to the previous menu.
The display will revert to the status mode display after 60 seconds on no activity (15 seconds in a
fire alarm condition). Press the Menu button again to return to the menu option.
A programmable timer can be configured to automatically cancel Level 2 access. This time can be
between 1 and 5 minutes. If no buttons are pressed for the timeout period, then Level 2 access
will be cancelled. It will be necessary to re-enter the password to regain access to control and
Level 2 Menu functions.
2.1.5 Numeric data entry
Numbers are entered by moving to the required field, and then typing in the required number,
followed by the button. The display returns to the previous menu.
If the number is entered incorrectly, press the button to clear the entry and then re-enter the
required number. Alternatively, press the ESC button to cancel the number entry and return to the
previous menu.
Page 9 of 20
2.2 Operating Conditions
2.2.1 Fire Alarm Condition
[Fire Detected]
FIRE STARTED: ZONE 1
TOTAL FIRES: 1
[Release Status]
STAGE-1
The display shows location / origin of the fire alarm and the total
number of zones in a fire alarm condition.
If two or more zones enter the fire alarm condition, the display also
shows the location of the last zone to enter a fire alarm condition.
In addition, the General Fire LED and the respective Zone Fire
LED will be illuminated.
[Fire Detected]
FIRE STARTED: ZONE 1
LAST FIRE : ZONE 3
TOTAL FIRES : 2
The status of the extinguishant release is also indicated. If a fire
alarm occurs in a zone that has no effect on the extinguishant
control then the display shows UNAFFECTED.
[Release Status]
STAGE-1
The fire alarm bells / sounders will activate (depending on how they are programmed to respond).
To silence the internal buzzer, press the MUTE button.
To silence the bells, press the SILENCE button (the SILENCED LED will illuminate)2
.
To reset the panel, press the RESET button. If a ‘Reset Control’ menu is presented, use the
buttons to highlight the ‘RESET FIRE & GAS’ option, then press the button to select.
[RESET Control]
RESET FIRE & GAS
RESET GAS ONLY
CANCEL RESET
The Reset Control menu may be presented when the reset control
key is pressed (this is dependant on how the control panel has
been configured by the installer).
Use the buttons to highlight the required option, then use the
button to select the highlighted option.
NOTE: If the programming of the panel is such that the release condition is immediately invoked
on detection of a single fire alarm, then the display will immediately show the release status
information.
2.2.2 Release / Activated Condition
The activated condition is established when one or more fire alarms have occurred or when the
manual release button is pressed.
The number of zones, and which zones, that must be in a fire alarm condition before the activated
condition is invoked depends on the installation programming of the panel.
2
SILENCE will silence all sounders except for the flooding zone (protected area) sounders when the system is in the
activated state. Once the extinguishant has been released, it is possible to silence the flooding zone sounders by pressing
the silence button again.
Page 10 of 20
[Release status]
RELEASE IMMINENT..
-15
When the activated condition is established, the display indicates
that the release is imminent and also shows a countdown timer
with the number of seconds remaining before the extinguishant is
released.
In addition, the Release Imminent LED flashes.
If programmed, the bells / sounders will ring with pulsed alert tone.
RELEASE ACTIVATED
00:00:05 Elapsed
GAS RESET INHIBITED
When the countdown timer has elapsed, the actuating output is
activated to start the release of the extinguishant.
The display now shows the time elapsed since the release of
extinguishant commenced.
In addition, the Release Imminent LED turns ON steady.
RELEASE ACTIVATED
10 Seconds Elapsed
DISCHARGE COMPLETE
(No Flow Detected)
GAS RESET INHIBITED
When the discharge is complete (either time elapsed or flow
detected) the display indicates the discharge is complete.
It is now possible to silence the flooding zone sounders.
RELEASE ACTIVATED
10 Seconds Elapsed
RELEASE CONFIRMED
DISCHARGE COMPLETE
GAS RESET INHIBITED
If confirmed by the detection of the flow of the extinguishant, the
display shows RELEASE CONFIRMED (Released Condition) and
the RELEASED LED turns ON steady.
If previously silenced, the internal buzzer will re-sound. Press the
MUTE button to silence the buzzer.
RELEASE ACTIVATED
20 Seconds Elapsed
DISCHARGE COMPLETE
EXTRACT RUNNING
RESET ALLOWED
When the extinguishant has been fully released (and if
programmed), the panel will either automatically, or will prompt for
manual confirmation, activate the output to control the extract fan.
This is indicated on the display as EXTRACT RUNNING or
PRESS to EXTRACT).
When the discharge is complete, the display prompts that the
panel can be reset.
To reset the panel, press the RESET button. A Reset Control menu may appear – use the
buttons to highlight the appropriate option, then press the button to select.
Section 4.12.2
Reset of the Activated Condition / Release Signal.
NOTE: In accordance with EN 12094-1, the ECD shall not permit a reset until
either the RELEASED condition has been established (flow detected) or until
after a programmable time following activation of the mechanism to release the
extinguishant.
NOTE: Depending on programming, the EXTRACT condition may persist after the panel is reset
for up to 120 minutes. This will be indicated on the normal status display (Extract Running).
Page 11 of 20
Section 4.11
Released Condition.
NOTE: In accordance with EN 12094-1, the activated / release condition may be
established without the detection of a fire alarm or manual release. If the panel
detects the release of extinguishant, it will immediately indicate the released
condition.
2.2.3 Hold Condition
COUNTDOWN ON HOLD
(Remove HOLD resume)
-15
If any hold button is activated, the imminent release countdown is
held for as long as the button is pressed.
The display shows the HOLD condition and the TIMER HELD LED
is illuminated.
When the hold button is released, the panel will resume the imminent release countdown either
from the time remaining or from the maximum time programmed.
2.2.4 Abort Condition
RELEASE ABORTED!
PRESS RESET TO REARM
If an abort button is activated, the imminent release countdown is
aborted.
The display prompts for the panel to be reset and the ABORTED
LED is illuminated.
Ensure that the abort button is de-activated and then press the
RESET button. A Reset Control menu may appear – use the
buttons to highlight the appropriate option, then press the button
to select.
2.2.5 Fault Condition
[System status]
1 of 1 conditions:
DETECTION ZONE3
OPEN CIRCUIT
[Release status]
UNAFFECTED
If the panel detects a fault condition, the display will indicate the
number and nature of the faults. The internal buzzer will sound with
an intermittent tone and the GENERAL FAULT LED and any other
specific FAULT LED indications will be illuminated.
Press the buttons to scroll through the list of faults.
Press the MUTE button to silence the internal buzzer.
NOTE: The fault condition is non-latching (except System Fault) and the indications will
automatically be cleared when the fault is remedied. Press the RESET key to clear a System
Fault - a Reset Control menu may appear – use the buttons to highlight the ‘RESET GAS &
FIRE’ option, then press the button to select.
NOTE: If silenced, the buzzer will re-sound when a new fault occurs.
[System status]
1 of 1 conditions:
DETECTION ZONE3
OPEN CIRCUIT
For service call:
01234 567 890
When the MUTE button is pressed, the bottom two lines of the
display will show the telephone number to call for service (if
programmed) for four seconds.
Page 12 of 20
2.2.6 Warning Condition
[System status]
1 of 1 conditions:
PRESSURE MONITOR
OPEN CIRCUIT
[Release status]
UNAFFECTED
If the panel detects an extinguishant warning condition, the display
will indicate the number and nature of the warnings. The internal
buzzer will sound with an intermittent tone and the GENERAL
FAULT LED and any other specific FAULT LED indications will be
illuminated.
Press the buttons to scroll through the list of faults.
Press the MUTE button to silence the internal buzzer.
2.3 Level 1 Menu Functions
2.3.1 Enable Controls
Controls and User Level-2 Menu functions are normally disabled. Refer to Section 2.1.3 for further
details.
2.3.2 View
On selection, the current status of any Faults, Disablements and Warnings along with the history
Log can be shown. These are the same as the Level-2 View function. Refer to Section 2.4.1 for
further details.
2.3.3 LED Test
On selection, the front panel LED Indicators will be illuminated for a short period of time.
Page 13 of 20
2.4 Level 2 Menu Functions
The following table gives a list of the Level 2 Menu Functions and a brief description for each
function.
Menu Option Sub Menu /
Item
Comments / Description
FAULTS View any current fault conditions recorded.
DISABLES View any current disablement conditions.
WARNINGS View any current extinguishant warnings conditions.
LOG View the history log.
VIEW
SW VERSIONS View the software version installed in the extinguishant control panel
and in remote status indicator panels.
ZONES Test the Detection Zone inputs with/without sounders.
DISPLAY Test the Display, LED Indicators and Buttons.
TEST
BUZZER Test the Buzzer
MANUAL Select Manual Only mode / Auto + Manual modeEXTINGUISH MODES
EXTRACT Turn on the extract output (if configured)
DISABLE / ENABLE -- Disable Zone, Sounder, Input and Output circuits and disable
functions. Enable any current disablement conditions
EXIT LEVEL 2 -- Cancels access to Level 2 menu functions and control key functions.
DATE / TIME -- Allows entry of the current date and time.
COMMISSION -- Engineer use only – requires separate password.
2.4.1 View
[View Menu]
FAULTS .
DISABLES
WARNINGS
LOG
SW VERSIONS
Press the buttons to scroll through the list and press the
button to select the required view option.
[Fault Status]
Nothing to Report
If there are no conditions present, the display will show “Nothing to
Report”.
2.4.1.1 Faults
[Fault Status]
1 of 3
DETECTION ZONE 1 .
>SHORT CIRCUIT .
DETECTION ZONE 2
>OPEN CIRCUIT
If there are fault conditions present, the display will show the
number of conditions and a list of the fault conditions.
Press the buttons to scroll through the list of faults.
Press the ESC button to return to the previous menu.
Page 14 of 20
2.4.1.2 Disables
[Disable List]
Zone 1 DISABLED
Man Release DISABLED
If there are disablement conditions present, the display will show
the number of conditions and a list of the disablements.
Press the buttons to scroll through the list of disablements.
Press the ESC button to return to the previous menu.
2.4.1.3 Warnings
[Warning Status]
1 of 2
VALVE MONITOR INPUT.
>VALVE CLOSED .
PRESSURE MONITOR
>LOW PRESSURE
If there are warning conditions in the extinguishant system present,
the display will show the number of conditions and a list of the
warning conditions.
Press the buttons to scroll through the list of warnings.
Press the ESC button to return to the previous menu.
2.4.1.4 Log
The panel contains a history log of fires, faults and other conditions. This can be filtered to show
only the fire alarm and trigger events that could result in the release of the extinguishant. In
addition, a total fire alarm count is also available.
[Event Log Menu]
ALL EVENTS .
FIRES & TRIGGERS
ALARM COUNT
On selection, a menu is presented to select the required view.
Press the buttons to scroll through the list and press the
button to select the required view option.
Press the ESC button to return to the previous menu.
2.4.1.4.1 View Events
Select either the ALL EVENTS or the FIRES + TRIGGERS option. On selection, the latest
recorded entry is shown. For example:
[Event Log Viewer]
EVENT: 55/55
20/09/2007 10:21:15
CONTROL PANEL
DETECTION ZONE 3
>OPEN CIRCUIT
The upper two lines show the menu option and the number of the
entry currently being viewed.
Press the buttons to scroll through the list of entries.
Press the ESC button to return to the previous menu.
The next four lines show the details of the log entry.
[Event Log Viewer]
EVENT: 41/58
20/09/2007 09:22:18
USER4
DETECTION ZONE 3
>DISABLE
Line 1 – shows the date and time the entry was recorded
Line 2 – shows the origin
Line 3 – shows the circuit / function affected
Line 4 – shows specific details
[Event Log Viewer]
EVENT: 11/58
19/09/2007 12:25:11
CONTROL PANEL
DETECTION ZONE 3
>FIRE ALARM
Line 1 – shows the date and time the entry was recorded
Line 2 – shows the origin
Line 3 – shows the circuit / function affected
Line 4 – shows specific details
Page 15 of 20
In the above examples:
[1] The control panel recognised and recorded an open-circuit fault condition on the wiring of
Detection Zone 3.
[2] User 4 disabled the operation of, and fault reporting from, Detection Zone 3.
[3] The control panel recognised and recorded a fire alarm condition on Detection Zone 3.
2.4.1.4.2 Alarm Counter
Section 7.13
Alarm Counter.
The Panel records the number of times that the fire alarm condition has
occurred at the panel.
ALARM COUNT
0000000004
On selection, the display shows the alarm count.
In the example the panel has entered the fire alarm condition 4
times since it was installed.
Press the ESC button to return to the previous menu.
The panel increments the count by one each time it changes from the normal condition to indicate
a fire alarm condition. Whilst in the fire alarm condition, and until it is reset, further fire alarm
events do not increment the counter.
2.4.1.5 Software Versions
[Software Versions]
PANEL : 99.00
RSI-1 : 99.00
RSI-2 : 99.00
RSI-3 : 99.00
RSI-4 : 99.00
On selection, the display shows a list containing the panel and any
configured remote status indicators along with the version of
software installed in each device.
Press the buttons to scroll through the list of entries.
Press the ESC button to return to the previous menu.
2.4.2 Test
[Test Menu]
ZONES .
DISPLAY
BUZZER
Press the buttons to scroll through the list and press the
button to select the required test option.
2.4.2.1 Zones
The Test Zones function provides the means to implement a one-person walk test in order to test
specific call points or detectors in one or more zones.
To test the detection zone circuits in accordance with the recommended weekly, monthly and
annual test requirements, select the Test – Zones option. The devices connected to the circuit
can then be tested without activating the extinguishing system and release.
Use the test key supplied for testing manual call points and either a heat source or smoke test
aerosol for testing heat detectors / smoke detectors.
Page 16 of 20
[Zone Test Select]
WITHOUT SOUNDERS .
WITH SOUNDERS
On selection, the display prompts for whether the sounders / bells
should ring for a short period (about 10 seconds) when the
detection zone enters a test fire alarm condition.
Press the buttons to scroll through the list and press the
button to select the required test option.
The display then shows a list of the detection zone circuits.
[Zone Test Select]
ZONE 1 TEST OFF.
ZONE 2 TEST OFF
ZONE 3 TEST OFF
Press the buttons to scroll through the list and highlight the
required zone circuit.
Press the button to select between TEST OFF and TEST ON.
To leave the Zone Test menu, press the ESC button. If there are still any zones in a test
condition, the display will show the following options: -
[Zones in Test!]
CANCEL ALL TESTS .
CONTINUE TESTS
Selecting the CANCEL ALL TESTS option will cancel all zone
tests. The Test LED will then extinguish.
Alternatively, it is possible to leave the Zone Test Function with
one or more Zones still in Test by selecting the CONTINUE
TESTS option. This will enable the inspection or use of other menu
functions and return the display to the normal operating mode.
The Test LED will stay illuminated if this option is selected.
2.4.2.2 Display
The Test Display option checks the operation of all the Indicators and the Graphic Display. All of
the Indicators are turned on and the entire display is shown in reverse.
LCD & KEY TEST
1
During this test, it is possible to test the operation of the
, , , , and 0-9 buttons. When a button is pressed, it is
indicated on the display. For example:
Press the ESC button to cancel the test and return to the previous
menu.
2.4.2.3 Buzzer
On selection, the buzzer will sound for approximately 10 seconds.
Page 17 of 20
2.4.3 Extinguishant Modes
[Mode Select]
MODE MANUAL ONLY.
EXTRACT START?
Press the buttons to scroll through the list and highlight the
required option.
2.4.3.1 Mode
The methods for initiating the release of extinguishant can be selected.
Press the button to select between MANUAL ONLY and AUTO + MANUAL.
In AUTO + MANUAL, the release of extinguishant can be
established if either a manual release button is pressed or if
the one or more of the detection zone circuits is activated
due to detection of smoke.
In MANUAL ONLY, the release of extinguishant can only be
established if one of the manual release buttons is pressed.
NOTE: If a key-switch is provided on the front panel, or separately, for this function, then use the
key-switch in preference to the menu option.
2.4.3.2 Extract
If the panel is configured and programmed to provide control of an extract fan then the operation
of the extract fan can be manually controlled via the menu option.
The display is context sensitive and will present different options depending on whether the fan is
on (running) or off.
If the fan is off, the display shows EXTRACT START? – Press the button to start the extract fan
for the pre-programmed time.
If the fan is on, the display shows EXTRACT STOP? – Press the button to stop (turn off) the
extract fan.
NOTE: If a key-switch is provided on the front panel, or separately, for this function, then use the
key-switch in preference to the menu option.
SYSTEM NORMAL
22 AUG 2007 16:39:00
SYSTEM NORMAL
(Manual Only Mode)
22 AUG 2007 16:39:00
Page 18 of 20
2.4.4 Disable / Enable
[Disabled List]
ZONE1 ENABLED.
ZONE2 ENABLED
ZONE3 ENABLED
Man Release ENABLED
Extinguish ENABLED
Press the buttons to scroll through the list and highlight the
required option.
Press the button to select between ENABLED and DISABLED
conditions. If a circuit or function is disabled, then the General
Disabled LED is illuminated along with any specific circuit /
function disablement LED indicators.
The table below lists all of the items that can be disabled.
Item Description Comments
ZONE 1
ZONE 2
ZONE 3
Detection Zones, Zone 1, 2 and 3 Disables any fault reporting on these circuits.
The zone will not enter the fire alarm condition even
if there is smoke present.
Man Release Manual Release of the extinguishant. Prevents the release of extinguishant due to the
activation of any manual release button.
Extinguish The Output to activate the release of
the extinguishant and Sounder
Circuit 3 (Flooding zone sounders).
Disables any fault reporting on the extinguishing
output circuit and flooding zone sounder circuit.
Prevents the operation of the extinguishing output
and flooding zone sounder circuit even if the release
condition is established.
Sounder 1 General Fire Alarm Sounder Output
(circuit 1).
Disables any fault reporting on the sounder-1
circuit.
General fire alarm sounder circuit 1 will remain off
irrespective of the operating condition of the panel.
Sounder 2 General Fire Alarm Sounder Output
(circuit 2).
Disables any fault reporting on the sounder-2
circuit.
General fire alarm sounder circuit 2 will remain off
irrespective of the operating condition of the panel.
Fault Relay The Fault Relay Output Prevents the fault relay output from operating.
Fire Relay The Fire Relay Output Prevents the fire relay output from operating.
Prog Relays All other relay control outputs Prevents all other relay output circuits from
operating.
2.4.5 Date/Time
[Set TIME/DATE]
TIME = 13:25
DATE = 29/09/07
Press the buttons to scroll through the list and highlight the
required option.
Enter the required time or date using the number buttons. Enter all
digits including zeros (i.e. 09 then 09 for 9:09 AM).
After all digits are entered, the time or date is set (if it is a valid time or date).
Page 19 of 20
This page is intentionally left blank.
Page 20 of 20
This page is intentionally left blank.
Document Number: 680-148 Revision: 02
34 Moorland Way : Nelson Park : Cramlington
Northumberland : NE23 1WE
Tel: +44 (0)1670 707 111
Fax: +44 (0)1670 707 222
www.Advel.co.uk Email: Sales@Advel.co.uk

More Related Content

What's hot

Sdmo mics-nexys-control panel-manual
Sdmo mics-nexys-control panel-manualSdmo mics-nexys-control panel-manual
Sdmo mics-nexys-control panel-manualCarlos Callirgos
 
Electronic multi measuring instrument-me96 instruction manual dienhathe.vn
Electronic multi measuring instrument-me96 instruction manual dienhathe.vnElectronic multi measuring instrument-me96 instruction manual dienhathe.vn
Electronic multi measuring instrument-me96 instruction manual dienhathe.vnDien Ha The
 
Mitsubishi ac servos melservo solutions dienhathe.vn
Mitsubishi ac servos melservo solutions dienhathe.vnMitsubishi ac servos melservo solutions dienhathe.vn
Mitsubishi ac servos melservo solutions dienhathe.vnDien Ha The
 
Instruction for updating ind and software umka
Instruction for updating ind and software umka Instruction for updating ind and software umka
Instruction for updating ind and software umka yhonfredy2
 
Xpxmp 18 manual spectra p
Xpxmp 18 manual spectra pXpxmp 18 manual spectra p
Xpxmp 18 manual spectra pspectra-tw
 
Es 50 series-manual
Es 50 series-manualEs 50 series-manual
Es 50 series-manualtatong it
 
A6 v10370250 variable speed drive for pumps and fans sinamics g_en
A6 v10370250 variable speed drive for pumps and fans sinamics g_enA6 v10370250 variable speed drive for pumps and fans sinamics g_en
A6 v10370250 variable speed drive for pumps and fans sinamics g_entekhakko
 
99 Zones GSM Wireless Home Alarm Security System Installation Guide
99 Zones GSM Wireless Home Alarm Security System Installation Guide99 Zones GSM Wireless Home Alarm Security System Installation Guide
99 Zones GSM Wireless Home Alarm Security System Installation Guidesurmall
 
Fanuc 0i operator's manual
Fanuc 0i operator's manualFanuc 0i operator's manual
Fanuc 0i operator's manualCNCDATAN
 
Anritsu site master_s331_a_user_guide
Anritsu site master_s331_a_user_guideAnritsu site master_s331_a_user_guide
Anritsu site master_s331_a_user_guideAlex Salazar
 
Minilux light wired sensor for outdoor mounting 0-10V manual
Minilux light wired sensor for outdoor mounting 0-10V manualMinilux light wired sensor for outdoor mounting 0-10V manual
Minilux light wired sensor for outdoor mounting 0-10V manualDomotica daVinci
 
10 vat300 e_c4-1_rev_b
10 vat300 e_c4-1_rev_b10 vat300 e_c4-1_rev_b
10 vat300 e_c4-1_rev_bDien Ha The
 
Plc MicroSmart manual of IDEC
Plc MicroSmart manual of IDECPlc MicroSmart manual of IDEC
Plc MicroSmart manual of IDECquanglocbp
 

What's hot (20)

Sdmo mics-nexys-control panel-manual
Sdmo mics-nexys-control panel-manualSdmo mics-nexys-control panel-manual
Sdmo mics-nexys-control panel-manual
 
Electronic multi measuring instrument-me96 instruction manual dienhathe.vn
Electronic multi measuring instrument-me96 instruction manual dienhathe.vnElectronic multi measuring instrument-me96 instruction manual dienhathe.vn
Electronic multi measuring instrument-me96 instruction manual dienhathe.vn
 
Mitsubishi ac servos melservo solutions dienhathe.vn
Mitsubishi ac servos melservo solutions dienhathe.vnMitsubishi ac servos melservo solutions dienhathe.vn
Mitsubishi ac servos melservo solutions dienhathe.vn
 
ZME WALLC-S manual
ZME WALLC-S manualZME WALLC-S manual
ZME WALLC-S manual
 
Instruction for updating ind and software umka
Instruction for updating ind and software umka Instruction for updating ind and software umka
Instruction for updating ind and software umka
 
Xpxmp 18 manual spectra p
Xpxmp 18 manual spectra pXpxmp 18 manual spectra p
Xpxmp 18 manual spectra p
 
Es 50 series-manual
Es 50 series-manualEs 50 series-manual
Es 50 series-manual
 
Tài liệu đào tạo simens sinamic G120
Tài liệu đào tạo simens sinamic G120Tài liệu đào tạo simens sinamic G120
Tài liệu đào tạo simens sinamic G120
 
A6 v10370250 variable speed drive for pumps and fans sinamics g_en
A6 v10370250 variable speed drive for pumps and fans sinamics g_enA6 v10370250 variable speed drive for pumps and fans sinamics g_en
A6 v10370250 variable speed drive for pumps and fans sinamics g_en
 
99 Zones GSM Wireless Home Alarm Security System Installation Guide
99 Zones GSM Wireless Home Alarm Security System Installation Guide99 Zones GSM Wireless Home Alarm Security System Installation Guide
99 Zones GSM Wireless Home Alarm Security System Installation Guide
 
Fanuc 0i operator's manual
Fanuc 0i operator's manualFanuc 0i operator's manual
Fanuc 0i operator's manual
 
Paperless recorder user manual
Paperless recorder user manualPaperless recorder user manual
Paperless recorder user manual
 
G120 cu250 s2_kba1_0414_eng_en-us
G120 cu250 s2_kba1_0414_eng_en-usG120 cu250 s2_kba1_0414_eng_en-us
G120 cu250 s2_kba1_0414_eng_en-us
 
2746e usersguide
2746e usersguide2746e usersguide
2746e usersguide
 
Anritsu site master_s331_a_user_guide
Anritsu site master_s331_a_user_guideAnritsu site master_s331_a_user_guide
Anritsu site master_s331_a_user_guide
 
Minilux light wired sensor for outdoor mounting 0-10V manual
Minilux light wired sensor for outdoor mounting 0-10V manualMinilux light wired sensor for outdoor mounting 0-10V manual
Minilux light wired sensor for outdoor mounting 0-10V manual
 
10 vat300 e_c4-1_rev_b
10 vat300 e_c4-1_rev_b10 vat300 e_c4-1_rev_b
10 vat300 e_c4-1_rev_b
 
Plc MicroSmart manual of IDEC
Plc MicroSmart manual of IDECPlc MicroSmart manual of IDEC
Plc MicroSmart manual of IDEC
 
KLM4G1EEHM-B101
KLM4G1EEHM-B101KLM4G1EEHM-B101
KLM4G1EEHM-B101
 
MT50 for LS1024B/ LS2024B/ LS3024B PWM solar controller
MT50 for LS1024B/ LS2024B/ LS3024B PWM solar controllerMT50 for LS1024B/ LS2024B/ LS3024B PWM solar controller
MT50 for LS1024B/ LS2024B/ LS3024B PWM solar controller
 

Similar to Hướng dẫn sử dụng tủ ex-3001 user

Tlk94 Controller
Tlk94 ControllerTlk94 Controller
Tlk94 ControllerJoseph
 
Lt 1040 sum sfc-500 series fire alarm panel
Lt 1040 sum sfc-500 series fire alarm panelLt 1040 sum sfc-500 series fire alarm panel
Lt 1040 sum sfc-500 series fire alarm panelCarlo Caparachin
 
Mini price on off z wave plus everspring
Mini price on  off z wave plus everspringMini price on  off z wave plus everspring
Mini price on off z wave plus everspringDomotica daVinci
 
Wall Controller 4 Buttons rechargeable Remote Z-Wave Plus - Hank manual
Wall Controller	4 Buttons rechargeable Remote Z-Wave Plus - Hank manualWall Controller	4 Buttons rechargeable Remote Z-Wave Plus - Hank manual
Wall Controller 4 Buttons rechargeable Remote Z-Wave Plus - Hank manualDomotica daVinci
 
4603-0001 - LCD Annunciator - 4603-9101.PDF
4603-0001 - LCD Annunciator - 4603-9101.PDF4603-0001 - LCD Annunciator - 4603-9101.PDF
4603-0001 - LCD Annunciator - 4603-9101.PDFSourovSamadder
 
HST New Fire Alarm System
HST New Fire Alarm SystemHST New Fire Alarm System
HST New Fire Alarm Systemssuser7165ec
 
Manual control centre smart friends box - z-wave plus - steinel
Manual control centre   smart friends box - z-wave plus - steinelManual control centre   smart friends box - z-wave plus - steinel
Manual control centre smart friends box - z-wave plus - steinelDomotica daVinci
 
Series One Safety Transmitter, Pressure and Temperature Switch
Series One Safety Transmitter, Pressure and Temperature SwitchSeries One Safety Transmitter, Pressure and Temperature Switch
Series One Safety Transmitter, Pressure and Temperature SwitchIves Equipment
 
Safety Transmitters for Temperature and Pressure
Safety Transmitters for Temperature and PressureSafety Transmitters for Temperature and Pressure
Safety Transmitters for Temperature and PressureMiller Energy, Inc.
 
United Electric One Series Safety Transmitter
United Electric One Series Safety TransmitterUnited Electric One Series Safety Transmitter
United Electric One Series Safety TransmitterMiller Energy, Inc.
 
One Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
One Series Safety Transmitter - Pressure and Temperature Transmitter-SwitchOne Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
One Series Safety Transmitter - Pressure and Temperature Transmitter-SwitchMiller Energy, Inc.
 
Mini jack on off and counter z wave plus everspring
Mini jack on  off and counter z wave plus everspringMini jack on  off and counter z wave plus everspring
Mini jack on off and counter z wave plus everspringDomotica daVinci
 
Mini Socket Dimmer Z-Wave Everspring manual
Mini Socket Dimmer Z-Wave Everspring manualMini Socket Dimmer Z-Wave Everspring manual
Mini Socket Dimmer Z-Wave Everspring manualDomotica daVinci
 
In-wall dimmer module Z-Wave Plus Smart Home Europe manual english
In-wall dimmer module Z-Wave Plus Smart Home Europe manual englishIn-wall dimmer module Z-Wave Plus Smart Home Europe manual english
In-wall dimmer module Z-Wave Plus Smart Home Europe manual englishDomotica daVinci
 
Aeotec Multisensor 7 Manual
Aeotec Multisensor 7 ManualAeotec Multisensor 7 Manual
Aeotec Multisensor 7 ManualDomotica daVinci
 

Similar to Hướng dẫn sử dụng tủ ex-3001 user (20)

Tlk94 Controller
Tlk94 ControllerTlk94 Controller
Tlk94 Controller
 
Lt 1040 sum sfc-500 series fire alarm panel
Lt 1040 sum sfc-500 series fire alarm panelLt 1040 sum sfc-500 series fire alarm panel
Lt 1040 sum sfc-500 series fire alarm panel
 
Mini price on off z wave plus everspring
Mini price on  off z wave plus everspringMini price on  off z wave plus everspring
Mini price on off z wave plus everspring
 
Wall Controller 4 Buttons rechargeable Remote Z-Wave Plus - Hank manual
Wall Controller	4 Buttons rechargeable Remote Z-Wave Plus - Hank manualWall Controller	4 Buttons rechargeable Remote Z-Wave Plus - Hank manual
Wall Controller 4 Buttons rechargeable Remote Z-Wave Plus - Hank manual
 
Philio_pan04_User manual
Philio_pan04_User manualPhilio_pan04_User manual
Philio_pan04_User manual
 
4603-0001 - LCD Annunciator - 4603-9101.PDF
4603-0001 - LCD Annunciator - 4603-9101.PDF4603-0001 - LCD Annunciator - 4603-9101.PDF
4603-0001 - LCD Annunciator - 4603-9101.PDF
 
HST New Fire Alarm System
HST New Fire Alarm SystemHST New Fire Alarm System
HST New Fire Alarm System
 
Mini 2 zones Conventional Fire Alarm Control Panel
Mini 2 zones Conventional Fire Alarm Control PanelMini 2 zones Conventional Fire Alarm Control Panel
Mini 2 zones Conventional Fire Alarm Control Panel
 
Manual control centre smart friends box - z-wave plus - steinel
Manual control centre   smart friends box - z-wave plus - steinelManual control centre   smart friends box - z-wave plus - steinel
Manual control centre smart friends box - z-wave plus - steinel
 
Series One Safety Transmitter, Pressure and Temperature Switch
Series One Safety Transmitter, Pressure and Temperature SwitchSeries One Safety Transmitter, Pressure and Temperature Switch
Series One Safety Transmitter, Pressure and Temperature Switch
 
Safety Transmitters for Temperature and Pressure
Safety Transmitters for Temperature and PressureSafety Transmitters for Temperature and Pressure
Safety Transmitters for Temperature and Pressure
 
United Electric One Series Safety Transmitter
United Electric One Series Safety TransmitterUnited Electric One Series Safety Transmitter
United Electric One Series Safety Transmitter
 
One Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
One Series Safety Transmitter - Pressure and Temperature Transmitter-SwitchOne Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
One Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
 
Manual_AD147_20140728.pdf
Manual_AD147_20140728.pdfManual_AD147_20140728.pdf
Manual_AD147_20140728.pdf
 
Mini jack on off and counter z wave plus everspring
Mini jack on  off and counter z wave plus everspringMini jack on  off and counter z wave plus everspring
Mini jack on off and counter z wave plus everspring
 
Mini Socket Dimmer Z-Wave Everspring manual
Mini Socket Dimmer Z-Wave Everspring manualMini Socket Dimmer Z-Wave Everspring manual
Mini Socket Dimmer Z-Wave Everspring manual
 
In-wall dimmer module Z-Wave Plus Smart Home Europe manual english
In-wall dimmer module Z-Wave Plus Smart Home Europe manual englishIn-wall dimmer module Z-Wave Plus Smart Home Europe manual english
In-wall dimmer module Z-Wave Plus Smart Home Europe manual english
 
Manual Zipato PAB01
Manual Zipato PAB01Manual Zipato PAB01
Manual Zipato PAB01
 
EST3 Forms.pdf
EST3 Forms.pdfEST3 Forms.pdf
EST3 Forms.pdf
 
Aeotec Multisensor 7 Manual
Aeotec Multisensor 7 ManualAeotec Multisensor 7 Manual
Aeotec Multisensor 7 Manual
 

Recently uploaded

VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 

Recently uploaded (20)

VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 

Hướng dẫn sử dụng tủ ex-3001 user

  • 1. Ex-3000 SeriesProductDataSheet User Manual for Ex-3001 Extinguishing Control Panel The operation and functions described in the manual are available from Software Versions Ex3001_V2_00 onwards.
  • 2. Page 2 of 20 Table of Contents 1 INTRODUCTION __________________________________________________________ 3 1.1 Standards ____________________________________________________________ 3 1.2 Cautions and Warnings __________________________________________________ 3 1.3 Description ___________________________________________________________ 3 2 OPERATION _____________________________________________________________ 4 2.1 Introduction ___________________________________________________________ 4 2.1.1 Access Levels _____________________________________________________ 4 2.1.2 Front Panel Controls and Indications ____________________________________ 4 2.1.2.1 Display _________________________________________________________________ 4 2.1.2.2 LED Indications __________________________________________________________ 5 2.1.2.3 Manual Release Button ____________________________________________________ 6 2.1.2.4 Control Buttons___________________________________________________________ 6 2.1.2.5 Menu and Navigation Buttons _______________________________________________ 7 2.1.2.6 Key-Switches ____________________________________________________________ 7 2.1.2.7 Buzzer _________________________________________________________________ 7 2.1.3 Enable Controls ____________________________________________________ 8 2.1.4 Navigating through menus ____________________________________________ 8 2.1.5 Numeric data entry__________________________________________________ 8 2.2 Operating Conditions____________________________________________________ 9 2.2.1 Fire Alarm Condition_________________________________________________ 9 2.2.2 Release / Activated Condition _________________________________________ 9 2.2.3 Hold Condition ____________________________________________________ 11 2.2.4 Abort Condition____________________________________________________ 11 2.2.5 Fault Condition ____________________________________________________ 11 2.2.6 Warning Condition _________________________________________________ 12 2.3 Level 1 Menu Functions ________________________________________________ 12 2.3.1 Enable Controls ___________________________________________________ 12 2.3.2 View ____________________________________________________________ 12 2.3.3 LED Test ________________________________________________________ 12 2.4 Level 2 Menu Functions ________________________________________________ 13 2.4.1 View ____________________________________________________________ 13 2.4.1.1 Faults _________________________________________________________________ 13 2.4.1.2 Disables _______________________________________________________________ 14 2.4.1.3 Warnings ______________________________________________________________ 14 2.4.1.4 Log ___________________________________________________________________ 14 2.4.1.5 Software Versions _______________________________________________________ 15 2.4.2 Test ____________________________________________________________ 15 2.4.2.1 Zones _________________________________________________________________ 15 2.4.2.2 Display ________________________________________________________________ 16 2.4.2.3 Buzzer ________________________________________________________________ 16 2.4.3 Extinguishant Modes _______________________________________________ 17 2.4.3.1 Mode _________________________________________________________________ 17 2.4.3.2 Extract ________________________________________________________________ 17 2.4.4 Disable / Enable ___________________________________________________ 18 2.4.5 Date/Time________________________________________________________ 18
  • 3. Page 3 of 20 1 Introduction 1.1 Standards The Ex-3001 Gas Extinguishing Control Panel conforms to the following standards: BS EN12094-1: 2003 Extinguishing Control Device BS EN54-2: 1998 Control and Indicating Equipment BS EN54-4: 1998 Power Supply Equipment BS EN60950: 2000 Safety of information technology equipment BS EN50130-4: 1996 Product Family Standard Electromagnetic Compatibility Directive 89/336/EEC (and the amending directive 92/23/EEC) Low Voltage Directive 73/23/EEC 1.2 Cautions and Warnings Only Trained service personnel should undertake the Installation, Programming and Maintenance of this equipment. 1.3 Description This manual covers the use and how to operate the Ex-3000 Series Extinguishing Control Panels. Refer to the Installation Manual (Document No. 680-147) for details of installation, programming and commissioning of the panel. The Ex-3001 is a Single Flooding Zone Control Panel with up to three detection zone circuits. The detection zones are compatible with conventional detectors and call points.
  • 4. Page 4 of 20 2 Operation 2.1 Introduction These instructions cover the operation and use of the panels. 2.1.1 Access Levels The panel operation is protected from inadvertent and erroneous misuse by means of four access levels. These levels are as follows: • Level 1 Untrained user • Level 2 Authorised User • Level 3 Commissioning, Service and Maintenance • Level 4 Commissioning, Service and Maintenance – Special Tools Required This document covers the Level 1 and Level 2 User functions. For details on the installation, programming and commissioning of the panel, refer to Manual 680-147. Full details are supplied with any special tools. • A Level 1 Untrained User can view the current operational condition of the system and may MUTE the internal buzzer. • A Level 2 Authorised User can view the operational condition of the system and may MUTE the internal buzzer. In addition, the RESOUND/SOUND ALARMS, SILENCE and RESET buttons are enabled and access to the Level 2 Menu functions is available. This requires a password (or key-switch). • NOTES: There are up to 4 User ID codes available, each with its own password. The panel can be configured to automatically cancel access to Level 2 functions after a specified period. 2.1.2 Front Panel Controls and Indications Key-Switch Assembly USB SUPPLY PSU Comms PROGRUN uP MODE R EBO OT R elay-1 F IR E R e la y R elay-2 FA U LT R ela y R S 485 A U X S up ply Z O N E - 1 - Z O N E - 2 - Z O N E - 3 - S N D R - 1 - S N D R - 2 - S N D R - 3 - M O D E S elect M an ua l Trig ge r H O LD A B O RT P ressure M onitor VA LV E M on itor FL O W M o nitor A ctu ator O utpu t P ROG Input-1 PRO G Input-2 PROG Input-3 PROG Input-4 MANUAL ONLY AUTO + MANUAL VALVE CLOSEDMANUAL DISABLED DISABLED FAULT TIMER HELD ABORTED RELEASE IMMINENT RELEASED EXTINGUISHANT POWER SYSTEM FAULT TEST SOUNDER DELAYED DISABLE SOUNDER DISABLED FAULT SOUNDER FAULT FIRE SILENCED GENERAL - 1 - DETECTION ZONES F IR E FA U LT / T E S T / D IS A B L E - 2 - - 3 - ESC MENU WXYZTUVPQRS GHI JKL MNO DEFABC R E S E T S ILE N CE M U T E ! RESOUND / SOUND ALARMS BS EN 54-2: 1998 BS EN 54-4: 1998 BS EN 12094-1: 2003 CLASS-A EXTINGUISHANT RELEASE PULL DOWN AND PRESS BUTTON Extinguishant StatusNumber ButtonsControl ButtonsGeneral Status LCD Navigation Buttons Detection Zone Status Manual Release Button 2.1.2.1 Display The LCD along with the LED Indicators shows the operating status of the system. Examples of the information presented is shown below:
  • 5. Page 5 of 20 Normal Display Non-normal Display Typical Menu Display [System status] 1 of 1 conditions: DETECTION ZONE3 OPEN CIRCUITSYSTEM NORMAL 22 AUG 2007 16:39:00 [Release status] UNAFFECTED [Level 2 Menu] VIEW . TEST MODES DISABLE / ENABLE EXIT LEVEL 2 Release Imminent Release Activated Release Complete RELEASE ACTIVATED 00:00:05 Elapsed RELEASE ACTIVATED 00:00:24 Elapsed [Release status] RELEASE IMMINENT.. -15 GAS RESET INHIBITED DISCHARGE COMPLETE (No Flow Detected) RESET ALLOWED The display shows a countdown timer with the amount of time remaining before the extinguishant is released. The display shows the time elapsed since the extinguishant release commenced. 2.1.2.2 LED Indications The LED Status Indications show the basic operational state of the panel and whether the panel is in a fire alarm, fault, disabled or test condition. 2.1.2.2.1 GENERAL STATUS Function Colour Description FIRE Red Indicates that the system has detected a fire alarm condition FAULT Yellow Indicates that the system has detected a fault condition DISABLE Yellow Indicates that part of the system has been disabled (i.e. isolated) TEST Yellow Indicates that part of the system is in a test condition POWER Green Indicates the presence of power SILENCED Yellow Indicates that the geneal fire alarm sounders have been silenced SOUNDER FAULT Yellow Indicates the presence of a fault in either or both of the general fire alarm sounder wiring circuits SOUNDER DISABLED Yellow Indicates that either or both of the general fire alarm sounder circuits have been disabled (i.e. isolated) DELAYED Yellow Not used SYSTEM FAULT Yellow Indicates the presence of a system fault 2.1.2.2.2 DETECTION ZONE STATUS Function Colour Description FIRE Red Indicates that the system has detected a fire alarm condition in the respecitve zone FAULT/TEST/DISABLE Yellow Indicates that the system has (flashing indication) detected a fault condition in the respecitve zone or (steady indication) that the zone is either in a test state or in a disabled state
  • 6. Page 6 of 20 2.1.2.2.3 EXTINGUISHANT Function Colour Description RELEASE IMMINENT Red Indicates (flashing) that the release of extinguishant is imminent. The indication will turn to steady when the signal to release the extinguishant has been activated. RELEASED Red Indicates that the release of extinguishant has occurred and the panel has detected the flow of the extinguishant released. TIMER HELD Yellow Indicates that the imminent release of extinguishant is temproraily suspended. ABORTED Yellow Indicates that the imminent release of the extinguishant has been aborted. DISABLED Yellow Indicates that the extinguishant release control signal has been disabled. The release of extinguishant is prevented even if a fire alarm or manual release are present. FAULT Yellow Indicates that the system has detected a fault condition within part of the extinguishing control device (ECD) circuits. The General Fault LED will also be illuminated. MANUAL DISABLED Yellow Indicates that one or more buttons for manual release have been disabled. VALVE CLOSED Yellow Indicates that the extinguishant is blocked by a manual shut-off valve and that there may be no extinguishant available to suppress a fire – Ensure immediate remedial action is taken to address the problem. MANUAL ONLY Yellow Indicates that the extinguishant can only be released by means of a manual release button. AUTO + MANUAL Yellow Indicates that the extinguishant can be released by both the automatic detection of a fire alarm and by means of a manual release button. 2.1.2.3 Manual Release Button To manually release the extinguishant, pull down the flap and press the button marked with the circle. 2.1.2.4 Control Buttons Reset Press to reset the panel from a fire alarm condition and/ or a gas release sequence. Only available with Level 2 Access. ! Mute Press to mute the internal buzzer. Available in both Level 1 and Level 2 Silence 1 Press to silence the sounders. Only available with Level 2 Access. Resound / Sound Alarms Press again to re-activate the sounders. Press to initiate a manual evacuation and sound the alarms. Only available with Level 2 Access. 1 SILENCE will silence all sounders except for the flooding zone (protected area) sounders when the system is in the activated state. Once the extinguishant has been released, it is possible to silence the flooding zone sounders.
  • 7. Page 7 of 20 2.1.2.5 Menu and Navigation Buttons Press to scroll through Menu Options. Press to display more information. Press to scroll through menu Options. Press to scroll through lists of zones or devices. Press to confirm entry of numeric information entry. Press to confirm selection of a menu option. Press to change some of the configuration options. W X Y Z Used to enter numbers. E S C Press to exit the menu functions and return to the normal display. E S C M E N U W X Y ZT U VP Q R S G H I J K L M N O D E FA B C M E N U Press to show or return to Menu Functions. 2.1.2.6 Key-Switches One or two key-switches can be fitted to the panel. The functions of these are programmable and the installer will have inserted a label to indicate their use. Typical uses are: AUTO + MANUAL / MANUAL ONLY Selection LEVEL 1 / LEVEL 2 ACCESS Selection Depending on the key-switch mechanism fitted, the key may be removable in only one position or removable in both operating positions. 2.1.2.7 Buzzer The buzzer produces two different sounds to differentiate between fire alarm conditions and fault / warning conditions. Condition Operation Fire Alarm The buzzer operates with a continuous tone. Fault The buzzer operates intermittently.
  • 8. Page 8 of 20 2.1.3 Enable Controls Controls are normally disabled. If a level 2 Access key-switch is fitted use this in preference to passwords. To enable the control keys or gain access to the Level 2, press the Menu button. The display shows the following: [CONTROLS DISABLED] ENABLE CONTROLS VIEW LED TEST Enter Your Password Enter Your Password ** Press the button to select the ‘Enable Controls’ option. The display prompts for entry of the password. Enter the password. As each number is pressed, an * character is displayed. Finally, press the button to confirm. [Level 2 Menu] VIEW . TEST EXTINGUISH MODES DISABLE / ENABLE EXIT LEVEL 2 Enter Your Password Not Recognized! The display then shows the Level 2 Menu options. If the password is incorrect (or if not entered in time) the above message is shown. If a control button is pressed at Level 1, the display prompts for password entry. To continue, enter the password. If the password is valid, the relevant control function will be activated and the display will remain at Level 1. 2.1.4 Navigating through menus When a menu is displayed, use the buttons to highlight the required menu option and then press the button to select it. Press the ESC button from within a menu option to return to the previous menu. The display will revert to the status mode display after 60 seconds on no activity (15 seconds in a fire alarm condition). Press the Menu button again to return to the menu option. A programmable timer can be configured to automatically cancel Level 2 access. This time can be between 1 and 5 minutes. If no buttons are pressed for the timeout period, then Level 2 access will be cancelled. It will be necessary to re-enter the password to regain access to control and Level 2 Menu functions. 2.1.5 Numeric data entry Numbers are entered by moving to the required field, and then typing in the required number, followed by the button. The display returns to the previous menu. If the number is entered incorrectly, press the button to clear the entry and then re-enter the required number. Alternatively, press the ESC button to cancel the number entry and return to the previous menu.
  • 9. Page 9 of 20 2.2 Operating Conditions 2.2.1 Fire Alarm Condition [Fire Detected] FIRE STARTED: ZONE 1 TOTAL FIRES: 1 [Release Status] STAGE-1 The display shows location / origin of the fire alarm and the total number of zones in a fire alarm condition. If two or more zones enter the fire alarm condition, the display also shows the location of the last zone to enter a fire alarm condition. In addition, the General Fire LED and the respective Zone Fire LED will be illuminated. [Fire Detected] FIRE STARTED: ZONE 1 LAST FIRE : ZONE 3 TOTAL FIRES : 2 The status of the extinguishant release is also indicated. If a fire alarm occurs in a zone that has no effect on the extinguishant control then the display shows UNAFFECTED. [Release Status] STAGE-1 The fire alarm bells / sounders will activate (depending on how they are programmed to respond). To silence the internal buzzer, press the MUTE button. To silence the bells, press the SILENCE button (the SILENCED LED will illuminate)2 . To reset the panel, press the RESET button. If a ‘Reset Control’ menu is presented, use the buttons to highlight the ‘RESET FIRE & GAS’ option, then press the button to select. [RESET Control] RESET FIRE & GAS RESET GAS ONLY CANCEL RESET The Reset Control menu may be presented when the reset control key is pressed (this is dependant on how the control panel has been configured by the installer). Use the buttons to highlight the required option, then use the button to select the highlighted option. NOTE: If the programming of the panel is such that the release condition is immediately invoked on detection of a single fire alarm, then the display will immediately show the release status information. 2.2.2 Release / Activated Condition The activated condition is established when one or more fire alarms have occurred or when the manual release button is pressed. The number of zones, and which zones, that must be in a fire alarm condition before the activated condition is invoked depends on the installation programming of the panel. 2 SILENCE will silence all sounders except for the flooding zone (protected area) sounders when the system is in the activated state. Once the extinguishant has been released, it is possible to silence the flooding zone sounders by pressing the silence button again.
  • 10. Page 10 of 20 [Release status] RELEASE IMMINENT.. -15 When the activated condition is established, the display indicates that the release is imminent and also shows a countdown timer with the number of seconds remaining before the extinguishant is released. In addition, the Release Imminent LED flashes. If programmed, the bells / sounders will ring with pulsed alert tone. RELEASE ACTIVATED 00:00:05 Elapsed GAS RESET INHIBITED When the countdown timer has elapsed, the actuating output is activated to start the release of the extinguishant. The display now shows the time elapsed since the release of extinguishant commenced. In addition, the Release Imminent LED turns ON steady. RELEASE ACTIVATED 10 Seconds Elapsed DISCHARGE COMPLETE (No Flow Detected) GAS RESET INHIBITED When the discharge is complete (either time elapsed or flow detected) the display indicates the discharge is complete. It is now possible to silence the flooding zone sounders. RELEASE ACTIVATED 10 Seconds Elapsed RELEASE CONFIRMED DISCHARGE COMPLETE GAS RESET INHIBITED If confirmed by the detection of the flow of the extinguishant, the display shows RELEASE CONFIRMED (Released Condition) and the RELEASED LED turns ON steady. If previously silenced, the internal buzzer will re-sound. Press the MUTE button to silence the buzzer. RELEASE ACTIVATED 20 Seconds Elapsed DISCHARGE COMPLETE EXTRACT RUNNING RESET ALLOWED When the extinguishant has been fully released (and if programmed), the panel will either automatically, or will prompt for manual confirmation, activate the output to control the extract fan. This is indicated on the display as EXTRACT RUNNING or PRESS to EXTRACT). When the discharge is complete, the display prompts that the panel can be reset. To reset the panel, press the RESET button. A Reset Control menu may appear – use the buttons to highlight the appropriate option, then press the button to select. Section 4.12.2 Reset of the Activated Condition / Release Signal. NOTE: In accordance with EN 12094-1, the ECD shall not permit a reset until either the RELEASED condition has been established (flow detected) or until after a programmable time following activation of the mechanism to release the extinguishant. NOTE: Depending on programming, the EXTRACT condition may persist after the panel is reset for up to 120 minutes. This will be indicated on the normal status display (Extract Running).
  • 11. Page 11 of 20 Section 4.11 Released Condition. NOTE: In accordance with EN 12094-1, the activated / release condition may be established without the detection of a fire alarm or manual release. If the panel detects the release of extinguishant, it will immediately indicate the released condition. 2.2.3 Hold Condition COUNTDOWN ON HOLD (Remove HOLD resume) -15 If any hold button is activated, the imminent release countdown is held for as long as the button is pressed. The display shows the HOLD condition and the TIMER HELD LED is illuminated. When the hold button is released, the panel will resume the imminent release countdown either from the time remaining or from the maximum time programmed. 2.2.4 Abort Condition RELEASE ABORTED! PRESS RESET TO REARM If an abort button is activated, the imminent release countdown is aborted. The display prompts for the panel to be reset and the ABORTED LED is illuminated. Ensure that the abort button is de-activated and then press the RESET button. A Reset Control menu may appear – use the buttons to highlight the appropriate option, then press the button to select. 2.2.5 Fault Condition [System status] 1 of 1 conditions: DETECTION ZONE3 OPEN CIRCUIT [Release status] UNAFFECTED If the panel detects a fault condition, the display will indicate the number and nature of the faults. The internal buzzer will sound with an intermittent tone and the GENERAL FAULT LED and any other specific FAULT LED indications will be illuminated. Press the buttons to scroll through the list of faults. Press the MUTE button to silence the internal buzzer. NOTE: The fault condition is non-latching (except System Fault) and the indications will automatically be cleared when the fault is remedied. Press the RESET key to clear a System Fault - a Reset Control menu may appear – use the buttons to highlight the ‘RESET GAS & FIRE’ option, then press the button to select. NOTE: If silenced, the buzzer will re-sound when a new fault occurs. [System status] 1 of 1 conditions: DETECTION ZONE3 OPEN CIRCUIT For service call: 01234 567 890 When the MUTE button is pressed, the bottom two lines of the display will show the telephone number to call for service (if programmed) for four seconds.
  • 12. Page 12 of 20 2.2.6 Warning Condition [System status] 1 of 1 conditions: PRESSURE MONITOR OPEN CIRCUIT [Release status] UNAFFECTED If the panel detects an extinguishant warning condition, the display will indicate the number and nature of the warnings. The internal buzzer will sound with an intermittent tone and the GENERAL FAULT LED and any other specific FAULT LED indications will be illuminated. Press the buttons to scroll through the list of faults. Press the MUTE button to silence the internal buzzer. 2.3 Level 1 Menu Functions 2.3.1 Enable Controls Controls and User Level-2 Menu functions are normally disabled. Refer to Section 2.1.3 for further details. 2.3.2 View On selection, the current status of any Faults, Disablements and Warnings along with the history Log can be shown. These are the same as the Level-2 View function. Refer to Section 2.4.1 for further details. 2.3.3 LED Test On selection, the front panel LED Indicators will be illuminated for a short period of time.
  • 13. Page 13 of 20 2.4 Level 2 Menu Functions The following table gives a list of the Level 2 Menu Functions and a brief description for each function. Menu Option Sub Menu / Item Comments / Description FAULTS View any current fault conditions recorded. DISABLES View any current disablement conditions. WARNINGS View any current extinguishant warnings conditions. LOG View the history log. VIEW SW VERSIONS View the software version installed in the extinguishant control panel and in remote status indicator panels. ZONES Test the Detection Zone inputs with/without sounders. DISPLAY Test the Display, LED Indicators and Buttons. TEST BUZZER Test the Buzzer MANUAL Select Manual Only mode / Auto + Manual modeEXTINGUISH MODES EXTRACT Turn on the extract output (if configured) DISABLE / ENABLE -- Disable Zone, Sounder, Input and Output circuits and disable functions. Enable any current disablement conditions EXIT LEVEL 2 -- Cancels access to Level 2 menu functions and control key functions. DATE / TIME -- Allows entry of the current date and time. COMMISSION -- Engineer use only – requires separate password. 2.4.1 View [View Menu] FAULTS . DISABLES WARNINGS LOG SW VERSIONS Press the buttons to scroll through the list and press the button to select the required view option. [Fault Status] Nothing to Report If there are no conditions present, the display will show “Nothing to Report”. 2.4.1.1 Faults [Fault Status] 1 of 3 DETECTION ZONE 1 . >SHORT CIRCUIT . DETECTION ZONE 2 >OPEN CIRCUIT If there are fault conditions present, the display will show the number of conditions and a list of the fault conditions. Press the buttons to scroll through the list of faults. Press the ESC button to return to the previous menu.
  • 14. Page 14 of 20 2.4.1.2 Disables [Disable List] Zone 1 DISABLED Man Release DISABLED If there are disablement conditions present, the display will show the number of conditions and a list of the disablements. Press the buttons to scroll through the list of disablements. Press the ESC button to return to the previous menu. 2.4.1.3 Warnings [Warning Status] 1 of 2 VALVE MONITOR INPUT. >VALVE CLOSED . PRESSURE MONITOR >LOW PRESSURE If there are warning conditions in the extinguishant system present, the display will show the number of conditions and a list of the warning conditions. Press the buttons to scroll through the list of warnings. Press the ESC button to return to the previous menu. 2.4.1.4 Log The panel contains a history log of fires, faults and other conditions. This can be filtered to show only the fire alarm and trigger events that could result in the release of the extinguishant. In addition, a total fire alarm count is also available. [Event Log Menu] ALL EVENTS . FIRES & TRIGGERS ALARM COUNT On selection, a menu is presented to select the required view. Press the buttons to scroll through the list and press the button to select the required view option. Press the ESC button to return to the previous menu. 2.4.1.4.1 View Events Select either the ALL EVENTS or the FIRES + TRIGGERS option. On selection, the latest recorded entry is shown. For example: [Event Log Viewer] EVENT: 55/55 20/09/2007 10:21:15 CONTROL PANEL DETECTION ZONE 3 >OPEN CIRCUIT The upper two lines show the menu option and the number of the entry currently being viewed. Press the buttons to scroll through the list of entries. Press the ESC button to return to the previous menu. The next four lines show the details of the log entry. [Event Log Viewer] EVENT: 41/58 20/09/2007 09:22:18 USER4 DETECTION ZONE 3 >DISABLE Line 1 – shows the date and time the entry was recorded Line 2 – shows the origin Line 3 – shows the circuit / function affected Line 4 – shows specific details [Event Log Viewer] EVENT: 11/58 19/09/2007 12:25:11 CONTROL PANEL DETECTION ZONE 3 >FIRE ALARM Line 1 – shows the date and time the entry was recorded Line 2 – shows the origin Line 3 – shows the circuit / function affected Line 4 – shows specific details
  • 15. Page 15 of 20 In the above examples: [1] The control panel recognised and recorded an open-circuit fault condition on the wiring of Detection Zone 3. [2] User 4 disabled the operation of, and fault reporting from, Detection Zone 3. [3] The control panel recognised and recorded a fire alarm condition on Detection Zone 3. 2.4.1.4.2 Alarm Counter Section 7.13 Alarm Counter. The Panel records the number of times that the fire alarm condition has occurred at the panel. ALARM COUNT 0000000004 On selection, the display shows the alarm count. In the example the panel has entered the fire alarm condition 4 times since it was installed. Press the ESC button to return to the previous menu. The panel increments the count by one each time it changes from the normal condition to indicate a fire alarm condition. Whilst in the fire alarm condition, and until it is reset, further fire alarm events do not increment the counter. 2.4.1.5 Software Versions [Software Versions] PANEL : 99.00 RSI-1 : 99.00 RSI-2 : 99.00 RSI-3 : 99.00 RSI-4 : 99.00 On selection, the display shows a list containing the panel and any configured remote status indicators along with the version of software installed in each device. Press the buttons to scroll through the list of entries. Press the ESC button to return to the previous menu. 2.4.2 Test [Test Menu] ZONES . DISPLAY BUZZER Press the buttons to scroll through the list and press the button to select the required test option. 2.4.2.1 Zones The Test Zones function provides the means to implement a one-person walk test in order to test specific call points or detectors in one or more zones. To test the detection zone circuits in accordance with the recommended weekly, monthly and annual test requirements, select the Test – Zones option. The devices connected to the circuit can then be tested without activating the extinguishing system and release. Use the test key supplied for testing manual call points and either a heat source or smoke test aerosol for testing heat detectors / smoke detectors.
  • 16. Page 16 of 20 [Zone Test Select] WITHOUT SOUNDERS . WITH SOUNDERS On selection, the display prompts for whether the sounders / bells should ring for a short period (about 10 seconds) when the detection zone enters a test fire alarm condition. Press the buttons to scroll through the list and press the button to select the required test option. The display then shows a list of the detection zone circuits. [Zone Test Select] ZONE 1 TEST OFF. ZONE 2 TEST OFF ZONE 3 TEST OFF Press the buttons to scroll through the list and highlight the required zone circuit. Press the button to select between TEST OFF and TEST ON. To leave the Zone Test menu, press the ESC button. If there are still any zones in a test condition, the display will show the following options: - [Zones in Test!] CANCEL ALL TESTS . CONTINUE TESTS Selecting the CANCEL ALL TESTS option will cancel all zone tests. The Test LED will then extinguish. Alternatively, it is possible to leave the Zone Test Function with one or more Zones still in Test by selecting the CONTINUE TESTS option. This will enable the inspection or use of other menu functions and return the display to the normal operating mode. The Test LED will stay illuminated if this option is selected. 2.4.2.2 Display The Test Display option checks the operation of all the Indicators and the Graphic Display. All of the Indicators are turned on and the entire display is shown in reverse. LCD & KEY TEST 1 During this test, it is possible to test the operation of the , , , , and 0-9 buttons. When a button is pressed, it is indicated on the display. For example: Press the ESC button to cancel the test and return to the previous menu. 2.4.2.3 Buzzer On selection, the buzzer will sound for approximately 10 seconds.
  • 17. Page 17 of 20 2.4.3 Extinguishant Modes [Mode Select] MODE MANUAL ONLY. EXTRACT START? Press the buttons to scroll through the list and highlight the required option. 2.4.3.1 Mode The methods for initiating the release of extinguishant can be selected. Press the button to select between MANUAL ONLY and AUTO + MANUAL. In AUTO + MANUAL, the release of extinguishant can be established if either a manual release button is pressed or if the one or more of the detection zone circuits is activated due to detection of smoke. In MANUAL ONLY, the release of extinguishant can only be established if one of the manual release buttons is pressed. NOTE: If a key-switch is provided on the front panel, or separately, for this function, then use the key-switch in preference to the menu option. 2.4.3.2 Extract If the panel is configured and programmed to provide control of an extract fan then the operation of the extract fan can be manually controlled via the menu option. The display is context sensitive and will present different options depending on whether the fan is on (running) or off. If the fan is off, the display shows EXTRACT START? – Press the button to start the extract fan for the pre-programmed time. If the fan is on, the display shows EXTRACT STOP? – Press the button to stop (turn off) the extract fan. NOTE: If a key-switch is provided on the front panel, or separately, for this function, then use the key-switch in preference to the menu option. SYSTEM NORMAL 22 AUG 2007 16:39:00 SYSTEM NORMAL (Manual Only Mode) 22 AUG 2007 16:39:00
  • 18. Page 18 of 20 2.4.4 Disable / Enable [Disabled List] ZONE1 ENABLED. ZONE2 ENABLED ZONE3 ENABLED Man Release ENABLED Extinguish ENABLED Press the buttons to scroll through the list and highlight the required option. Press the button to select between ENABLED and DISABLED conditions. If a circuit or function is disabled, then the General Disabled LED is illuminated along with any specific circuit / function disablement LED indicators. The table below lists all of the items that can be disabled. Item Description Comments ZONE 1 ZONE 2 ZONE 3 Detection Zones, Zone 1, 2 and 3 Disables any fault reporting on these circuits. The zone will not enter the fire alarm condition even if there is smoke present. Man Release Manual Release of the extinguishant. Prevents the release of extinguishant due to the activation of any manual release button. Extinguish The Output to activate the release of the extinguishant and Sounder Circuit 3 (Flooding zone sounders). Disables any fault reporting on the extinguishing output circuit and flooding zone sounder circuit. Prevents the operation of the extinguishing output and flooding zone sounder circuit even if the release condition is established. Sounder 1 General Fire Alarm Sounder Output (circuit 1). Disables any fault reporting on the sounder-1 circuit. General fire alarm sounder circuit 1 will remain off irrespective of the operating condition of the panel. Sounder 2 General Fire Alarm Sounder Output (circuit 2). Disables any fault reporting on the sounder-2 circuit. General fire alarm sounder circuit 2 will remain off irrespective of the operating condition of the panel. Fault Relay The Fault Relay Output Prevents the fault relay output from operating. Fire Relay The Fire Relay Output Prevents the fire relay output from operating. Prog Relays All other relay control outputs Prevents all other relay output circuits from operating. 2.4.5 Date/Time [Set TIME/DATE] TIME = 13:25 DATE = 29/09/07 Press the buttons to scroll through the list and highlight the required option. Enter the required time or date using the number buttons. Enter all digits including zeros (i.e. 09 then 09 for 9:09 AM). After all digits are entered, the time or date is set (if it is a valid time or date).
  • 19. Page 19 of 20 This page is intentionally left blank.
  • 20. Page 20 of 20 This page is intentionally left blank. Document Number: 680-148 Revision: 02 34 Moorland Way : Nelson Park : Cramlington Northumberland : NE23 1WE Tel: +44 (0)1670 707 111 Fax: +44 (0)1670 707 222 www.Advel.co.uk Email: Sales@Advel.co.uk