Page 1Status 13.06.2014
---
OPERATING INSTRUCTIONS
(TRANSLATION OF THE ORIGINAL)
SUPPLEMENTARY OPERATING INSTRUCTIONS
FOR YOUR AIR CURTAIN SYSTEM
Serial number:
____________________________
Year:_____________________
Please quote this number when contacting customer service!
Page 2 Status 13.06.2014
Operating Instructions for Controller TLC 700
TLC 700 – Brief description
 Electronic air curtain controller TLC 700 with wired control element (remote control) for 5-
stage or fully adjustable (in conjunction with ECM motors) activation of Teddington air curtain
systems.
 The TLC 700 consists of the control element (remote control) and control board (master
and/or master/slave); the control board is installed in the air curtain.
 A colour touchscreen with graphical presentation of the specific type of installation enables
Teddington air curtain systems to be adjusted simply and accurately to meet all require-
ments.
 The TLC700 is characterised by a simple, self-explanatory menu navigation and program-
ming by means of the integrated installation assistant. The menu navigation is available in
5 languages. Every operating step is explained by an integrated help function.
 Up to 9 air curtain systems can be connected to one control element and addressed
individually or in parallel via the control element (TLC 700).
 Room temperature sensors integrated in the control panel or by means of external
room sensors; sensors to control the heating function to a reduced, programmable
speed level; display of the current room temperature; adjustable night-time tem-
perature reduction.
 Manual/automatic function: automatic function via room thermostat or door con-
tact, automatic switching of stages by external transmitter e.g. external thermo-
stat, wind turbine, IR sensor, building management system (BMS) (0-10V, 0-
20mA). The run-on time is freely programmable, and the speed levels for run-on
and room heating function can be selected separately.
 Integrated week timer with freely selectable programming of switching times for
overriding enable function.
 Summer /winter function: automatic switching between summer/winter function:
automatic switching between summer/winter via external temperature sensor (op-
tion), activation of solenoid valve or pump, room temperature dependant electron-
ic air discharge temperature control (option).
 Integrated filter monitoring function – can be adapted easily on site to operating con-
ditions, can be programmed to evaluate operating hours or external transmitter.
 Key lock with adjustable code can be activated.
 Retrieval of error messages via a battery cached error memory for remote diag-
nostics and assignment of an error message to the individual device concerned.
 Floating enable, operating and error message for simple communication with the
BMS. Output for transmission of the current speed level to the BMS (0-10V).
 Recommended cable for bus cable: J-Y(ST)Y 2x2x0.8 mm² (shielded, twisted
control cable). This guarantees a fault-free transmission up to 400 m. The con-
necting terminals have reverse polarity protection and are short-circuit-proof.
 Dimensions of control element: 135 x 96 x 28 mm
 Made in Germany.
PLEASE
NOTE
Observe all safety instructions in the device operating instructions!
Only adequately trained personnel who meet the requirements set out in the
device operating instructions may work on the installation. It is necessary to
ensure that the main power supply has been turned off before all work.
Page 3Status 13.06.2014
Table of contents
1 Assembly, technical data and eBus diagram ................................................................4
1.1 Assembly information .........................................................................................4
1.2 Wiring information...............................................................................................4
1.3 Technical data of the TLC 700 control element ..................................................6
1.4 Technical data of the TLC 700 master................................................................7
1.5 Technical data of the TLC 700 slave ..................................................................8
1.6 eBus diagram .....................................................................................................9
2 Cable plans and termnals ........................................................................................... 10
2.1 Master terminal plan, AC motors ...................................................................... 10
2.2 Slave terminal plan, AC motors ........................................................................ 11
2.3 Master terminal plan, EC motors ...............................................................................12
2.4 Master terminal plan, EC motors ...............................................................................13
2.5 Master terminal description............................................................................... 14
2.6 Slave terminal description................................................................................. 16
3 Start screen on putting into operation for the first time ............................................... 17
4 Commissioning using the installation assistant........................................................... 18
4.1 Setting the language......................................................................................... 18
4.2 Basic buttons.................................................................................................... 19
4.3 Installation assistant ......................................................................................... 20
4.4 Address installer............................................................................................... 21
4.5 Master systems selection ................................................................................. 22
4.6 Setting the time................................................................................................. 23
4.7 Enable .............................................................................................................. 26
4.8 Summer/winter setting...................................................................................... 27
4.9 Manual/automatic mode setting........................................................................ 32
4.10 Room thermostat setting................................................................................... 38
4.11 Servicing menu................................................................................................. 40
5 Main screen / standard displays ................................................................................. 42
5.1 Standard display depending on the version of air curtain system..................... 42
5.2 Standard display depending on the desired arrangement ................................ 43
5.3 Functions main screen...................................................................................... 45
5.4 Hotkeys on the main screen ............................................................................. 46
5.5 Entry and keypad.............................................................................................. 49
6 Settings menu............................................................................................................. 50
6.1 Setting the language sub-menu........................................................................ 50
6.2 Settings sub-menu............................................................................................ 51
6.3 Setting the time sub-menu................................................................................ 53
6.4 Enable sub-menu ............................................................................................. 53
6.5 Summer/winter setting sub-menu..................................................................... 53
6.6 Manual/automatic setting sub-menu................................................................. 53
6.7 Room thermostat sub-menu ............................................................................. 53
6.8 Electronic air discharge temperature control sub-menu ................................... 54
6.9 Manufacturer level sub-menu ........................................................................... 54
6.10 Servicing sub-menu.......................................................................................... 54
6.11 Error/fault sub-menu......................................................................................... 55
6.12 Contacts and button overview sub-menu.......................................................... 56
Page 4 Status 13.06.2014
Operating Instructions for Controller TLC 700
1 Assembly, technical data and eBus diagram
1.1 Assembly information
Assembly environment: Closed, dry room which is protected from dirt.
Assembly: Wall-mounting with screws and dowels provided. The
two fastening holes are positioned diagonally on two
corners (see drawing).
Alternatively it is possible to assemble directly on a
flush-mounted box. In this case it is necessary to
ensure that only the four-wire connecting cables
of the control element are inside the flush-
mounted box! Installation must be performed by an
electrician; all applicable provisions and regulations of
the responsible electricity supply company must be
complied with.
1.2 Wiring information
eBus networks: A shielded, twisted two-wire cable must be used to set up eBus
networks. The wire shielding must be fastened to the housing of
the air curtain system. The bus cable must have the properties
listed below:
 The cable diameter must be at least 0.8 mm2
.
 The total of all bus cables must not exceed a maximum overall
length of 400 m.
70mm
110 mm
Control element
Page 5Status 13.06.2014
In contrast to the abovementioned eBus networks, a four-wire cable
is used for the wiring of the TLC 700 control element. Two wires
are for the eBus and two for the voltage supply. Details regarding
the cable cross-section and the overall length etc. remain un-
changed.
PLEASE
NOTE
If more than one circuit board (master and/or master/slave) is connected, it
is important for uninterrupted operation that the jumper is not placed on
the same circuit board as the one on which the control element is connect-
ed. For example the control element which provides the supply voltage can
be connected to the master circuit board 1. The jumper which guarantees
the eBus supply must then be placed on master circuit board 2 or slave 1.
It is also important to note that individual master systems in this eBus sys-
tem must not be disconnected from the power supply.
Electrical connection:
Dimensions:
A
B
C
135 mm
96mm28mm
5mm
Supply -
Supply +
eBus –
eBus +
Optional
external
PT1000
sensor
Page 6 Status 13.06.2014
Operating Instructions for Controller TLC 700
Synchronisation: Up to 8 TLC 700 slave circuit boards can be connected to a TLC
700 master circuit board via the eBus interface in order to activate
further air curtain systems synchronously with the master system.
Only one TLC 700 control element can be used per eBus network.
The jumper for the eBus supply may only be placed on a circuit
board (master or slave). The control element should not also be
connected to this circuit board. The maximum number of circuit
boards per eBus is 9, whereby at least one master circuit board
must be connected. The addresses should be adjusted by DIP
switch on the circuit boards.
1.3 Technical data of TLC 700 control element
Electrical connection eBus (max. 24 V, 50 mA DC)
4-wire connection, eBus and voltage supply
4-pole connecting terminal Wire: 0.5 – 2.5 mm² (rigid), 0.5 – 1.5 mm² (flexible) mm²
2-pole connecting terminal Wire: 0.34 – 2.5 mm² (rigid), 0.34 – 1.5 mm² (flexible) mm²
Keypad TFT touch display
TFT display 4.3” colour
Temperature sensor, in-
ternal
NTC
Temperature sensor, ex-
ternal
PT 1000, connection using a 2-pole connecting terminal
Protection class IP 20 in accordance with DIN EN 60529 (VDE 0470-1)
Ambient temperature 0 °C to + 50 °C
Storage temperature -10 °C to + 60 °C
Assembly Wall mounting
Housing material Plastic, ABS, UV resistant
Housing colour White RAL 9016
Dimensions 135mm x 96mm x 28 mm
Weight 185 g
Conformity The control element satisfies the provisions of the Electro-
magnetic Compatibility Directive (2004/108/EC), the Low
Voltage Directive (2006/95/EC) and the harmonised stand-
ards DIN EN 60730-1, DIN EN 60730-2-9, and bears the
CE mark.
Page 7Status 13.06.2014
1.4 Technical data for the TLC 700 master
Supply voltage 230 V AC, 50 Hz
Power input
11 VA
14 VA (with TLC 700 control element)
Fusing
10 A T, microfuse 5 mm x 20 mm
80 mA F, microfuse 5 mm x 20 mm
Interface eBus (max. 24 V / 100 mA DC)
Protection class IP00 in accordance with DIN EN 60529 (VDE 0470-1)
Ambient temperature 0 °C … +50 °C
Storage temperature -10 °C … +60 °C
Max. connecting cross-
sections (see terminal dia-
gram)
2.5 mm² (X1 - X5)
1.0 mm² (X6 - X8)
Digital inputs
7x, floating, switched with switching contact, < 1.5 mA
(12 V)
Analogue inputs
1x, 4 mA … 20 mA DC, < 10 V
1x, 0 V … 10 V DC, < 1mA, 49.4 kΩ
2x, plug-in temperature sensor (NTC, 8.2 kΩ at 25 °C)
for air discharge temperature and outdoor temperature
Selectable fan levels 5 or variable (analogue output)
Analogue outputs 0 V… 10 V DC, < 35mA
Relay outputs (see terminal
diagram)
R1 – R3 / R6 – R10, 8 A, Ʃ I < 10 A, 250 V AC (µ), ohmic
load
R3 / R5, 2 A, 250 V AC (µ), ohmic load
Triac output 200 mA, 250 V AC (µ), ohmic load
Dimensions 240 mm x 108 mm x 48 mm (L x B x H)
Weight 460 g
Conformity The TLC 700 master control unit satisfies the provisions
of the Electromagnetic Compatibility Directive
(2004/108/EC), the Low Voltage Directive (2006/95/EC)
and the harmonised standards DIN EN 60730-1, DIN EN
60730-2-9, and bears the CE mark.
Page 8 Status 13.06.2014
Operating Instructions for Controller TLC 700
1.5 Technical data for the TLC 700 slave
Supply voltage 230 V AC, 50 Hz
Power input 8 VA
Fusing
10 A T, microfuse 5 mm x 20 mm
80 mA F, microfuse 5 mm x 20 mm
Interface eBus (max. 24 V / 100 mA DC)
Protection class IP00 in accordance with DIN EN 60529 (VDE 0470-1)
Ambient temperature 0 °C … +50 °C
Storage temperature -10 °C … +60 °C
Max. connecting cross-
sections (see terminal dia-
gram)
2.5 mm² (X1 – X4)
1.0 mm² (X5 / X6)
Digital inputs
4x, floating, switched with switching contact, < 1.5 mA
(12 V)
Selectable fan levels 5
Relay outputs (see terminal
diagram)
R6 - R10, 8 A, Ʃ I < 10 A, 250 V AC (µ), ohmic load
Dimensions Approx. 240 mm x 108 mm x 48 mm (L x B x H)
Weight 420 g
Conformity The TLC 700 slave control unit satisfies the provisions
of the Electromagnetic Compatibility Directive
(2004/108/EC), the Low Voltage Directive
(2006/95/EC) and the harmonised standards DIN EN
60730-1, DIN EN 60730-2-9, and bears the CE mark.
Page 9Status 13.06.2014
1.6 eBus diagram
Page 10 Status 13.06.2014
Operating Instructions for Controller TLC 700
2 Cable plans and terminals
2.1 Master terminal plan, AC motors
Page 11Status 13.06.2014
2.2 Slave terminal plan, AC motors
Page 12 Status 13.06.2014
Operating Instructions for Controller TLC 700
2.3 Master terminal plan, EC motors
Page 13Status 13.06.2014
2.4 Slave terminal plan, EC motors
Page 14 Status 13.06.2014
Operating Instructions for Controller TLC 700
2.5 Master terminal description
Terminal N: Mains voltage N-conductor (230V / 50 Hz).
Terminal L: Mains voltage L-conductor (230V / 50 Hz).
Terminal 52: Connection of the motor neutral conductor.
Terminal 51: Connection of the motor phase.
Terminal N: Connection of the neutral conductor for the autotransformer.
Terminal L1: Connection of the phase for the transformer.
Terminal L1: Connection of the phase for the circuitry with 57 (if necessary).
Terminal 57: Connection of the transformer tapping with the highest voltage
(e.g. 230 V).
Terminal 56: Connection of the transformer tapping with the 2nd
highest voltage
(e.g. 180 V).
Terminal 55: Connection of the transformer tapping with the 3rd
highest voltage
(e.g. 160 V).
Terminal 54: Connection of the transformer tapping with the 4th
highest voltage
(e.g. 125 V).
Terminal 53: Connection of the transformer tapping with the lowest voltage (e.g. 70 V).
Terminal N: Connection of the pump neutral conductor.
Terminal 9: Connection of the pump phase. The pump is used to transport the
hot water from the boiler to the heater battery in the
air curtain system.
Terminal 32: Connection of the control circuit from the power contactor K1 to
shut down the transformer.
Terminal N: Connection of the pump neutral conductor or connection of the mixer
neutral conductor.
Terminal 33: Connection of the phase to open the mixer. The mixer is used to
adjust the air discharge temperature.
Terminal 34: Connection of the phase to close the mixer.
Terminal PE: Connection of the earth conductor.
Terminal 15: Root of the floating changeover contact for the ext. fault message
(230 V / max. 8 A or extra low voltage).
Terminal 13: If there is no fault, the root from is switched from terminal 15 to terminal
13.
Terminal 14: If a fault is present, the root from is switched from terminal 15 to terminal
14.
Terminal 12: Root of the floating changeover contact for the ext. operating message
(230 V / max. 8 A or extra low voltage).
Terminal 10: If the fan motors are still, then the root is switched from terminal 12
to terminal 10.
Terminal 11: If the fan motors are running, then the root is switched from terminal 12
to terminal X5 / 11.
Terminal 20 & 21: Input for the floating thermal contacts of the fan motors.
Terminal 22 & 23: Input for the floating thermal contacts of the transformer.
Terminal 24 & 25: Input for the floating switch of the filter monitoring.
Terminal 16 & 17: Input for the floating frost protection switch.
Page 15Status 13.06.2014
Terminal 18 & 19: Input for the floating repair switch.
Terminal 35 & 36: Input for the air discharge temperature sensor.
This sensor is an NTC with a specific characteristic curve.
Terminal 37 & 38: Output (0...10 V) to activate fans with 0...10-V input
or as stage operating message. Stage 0 = 1 V, St. 1 = 2.5 V, St. 2 = 4 V,
St. 3 = 5.5 V, St. 4 = 7 V, St. 5 = 8.5V (+/- 0.5 V).
The positive potential lies on terminal 37. Terminal 38 is GND.
Terminal 28 & 29: Input for a floating ext. enabling contact (e.g. DDC).
Terminal 39 & 42: Input (4 ... 20 mA) for the IR sensor. The IR sensor is used to
measure the ground temperature. The fan speed is controlled in
automatic operating mode on the basis of the ground temperature and an
adjusted set point. The positive potential is connected to terminal 39.
Terminal 42 is the common GND connection for the inputs 39, 40 and 41.
Terminal 40 & 42: Input (0 ... 10 V) for specification of a fan speed level in automatic
operating mode (e.g. when using a wind turbine). The fan speed is
controlled in automatic operating mode on the basis of the input
voltage and an adjusted set point. The positive potential is connected to
terminal 40. Terminal 42 is the common GND connection for the inputs
39, 40 and 41.
Terminal 41 & 42: Input for the outdoor temperature sensor. This sensor is
an NTC with a specific characteristic curve. The outdoor
temperature measured influences the fan speed.
Terminal 30 & 31: Input for a floating ext. automatic operating mode contact (e.g. room
thermostat).
Terminal 26 & 27: Input for a floating ext. automatic operating mode contact (e.g. door
contact).
Terminal 1 & 2: Bus connection for the operating element with reverse polarity protection.
Terminal 1 & 2: Bus connection for a master or slave circuit board with reverse polarity
protection.
Terminal 3 & 4: Supply voltage control element.
Setting the master address
Master address
Master 1 0000 0000
Master 2 0000 0001
Master 3 0000 0010
Master 4 0000 0100
Master 5 0000 1000
Master 6 0001 0000
Master 7 0010 0000
Master 8 0100 0000
Master 9 1000 0000
Page 16 Status 13.06.2014
Operating Instructions for Controller TLC 700
2.6 Slave terminal description
Terminal N: Mains voltage N-conductor (230V / 50 Hz).
Terminal L: Mains voltage L-conductor (230V / 50 Hz).
Terminal 52: Connection of the motor neutral conductor.
Terminal 51: Connection of the motor phase.
Terminal N: Connection of the neutral conductor for the auto transformer.
Terminal L1: Connection of the phase for the transformer.
Terminal L1: Connection of the phase for the circuitry with 57 (if necessary).
Terminal 57: Connection of the transformer tapping with the highest voltage (e.g. 230
V).
Terminal 56: Connection of the transformer tapping with the 2nd
highest voltage (e.g. 180 V).
Terminal 55: Connection of the transformer tapping with the 3rd
highest voltage
(e.g. 160 V).
Terminal 54: Connection of the transformer tapping with the 4th
highest voltage
(e.g. 125 V).
Terminal 53: Connection of the transformer tapping with the lowest voltage (e.g. 70 V).
Terminal 32 & N: Connection of the control circuit from the power contactor K1 to
shut down the transformer.
Terminal PE: Connection of the earth conductor.
Terminal 20 & 21: Input for the floating thermal contacts of the fan motors
Terminal 22 & 23: Input for the floating thermal contacts of the transformer.
Terminal 18 & 19: Input for the floating repair switch.
Terminal 16 & 17: Input for the floating frost protection switch.
Terminal 1 & 2: Bus connection for the control element or for a master or slave circuit
board with reverse polarity protection.
Terminal 1 & 2: Bus connection for a master or slave circuit
board with reverse polarity protection.
Setting the slave address
Master assignment of a slave
(the first four Bits)
Slave address
(the last four Bits)
Master 1 0000 Slave 1 0000
Master 2 0001 Slave 2 0001
Master 3 0010 Slave 3 0010
Master 4 0011 Slave 4 0011
Master 5 0100 Slave 5 0100
Master 6 0101 Slave 6 0101
Master 7 0110 Slave 7 0110
Master 8 0111 Slave 8 0111
Example: The slave 4 from master 2, DIP switch address = 0001 0011
Page 17Status 13.06.2014
3 Start screen on putting into operation for the first time
“Installation assistant” screen
This screen is shown when you implement the installation assistant or when you have switched the
system off.
Next button:
By pushing the Next button you can access the “Languages” menu and start the in-
stallation assistant which guides you through the settings menu.
Key button:
The key button activates/deactivates the key lock.
Page 18 Status 13.06.2014
Operating Instructions for Controller TLC 700
4 Commissioning using the installation assistant
4.1 Setting the language
In the “Languages” menu it is possible to set one of the five languages displayed.
When a language has been selected, a blue tick appears next to the selected language and the
heading changes into the selected language.
German is set as standard language.
Back button:
The “Back” button returns you to the last menu accessed.
Next button (is only displayed in the installation assistant):
Pushing the “Next” button takes you to the “Basic buttons” menu.
Information button:
Actuating the “Info” button opens an information screen. This contains a brief expla-
nation of the setting options in the respective menu.
Page 19Status 13.06.2014
4.2 Basic buttons
All buttons which can appear on the individual menu pages are explained on these menu screens.
Scroll buttons:
You can scroll backwards and forwards between “basic buttons” screens using the
scroll buttons.
Next button (is only displayed in the installation assistant):
Pushing the “Next” button takes you to the “Installation assistant” menu.
Page 20 Status 13.06.2014
Operating Instructions for Controller TLC 700
4.3 Installation assistant
This screen is only displayed in the installation assistant. It is an information screen that is intended
to protect against incorrect commissioning.
Back button:
The “Back” button returns you to the last menu accessed.
Next button (is only displayed in the installation assistant):
Pushing the “Next” button takes you to the “Address installer” menu.
Information button:
Actuating the “Info” button opens an information screen. This contains a brief ex-
planation of the setting options in the respective menu.
Cancel assistant button:
The installation procedure can be aborted using this button and you return to the
start screen of the installation assistant again. Previous entries in the installation
assistant are deleted.
Page 21Status 13.06.2014
4.4 Address installer
The contact details of the installer are entered and saved in this menu. This entry is optional, but
advisable. It enables the end user to know at all times who to approach for servicing and repair
work.
Back button:
The “Back” button returns you to the last menu accessed.
Next button (is only displayed in the installation assistant):
Pushing the “Next” button takes you to the “Master systems” menu.
Information button:
Actuating the “Info” button opens an information screen. This contains a brief expla-
nation of the setting options in the respective menu.
Page 22 Status 13.06.2014
Operating Instructions for Controller TLC 700
4.5 Master systems selection
This screen is only displayed in the installation assistant.
In total up to 9 air curtain systems can be controlled/regulated from one control element (remote con-
trol) of the TLC 700 controller. In this menu you can stipulate whether all connected air curtain sys-
tems are to be set with identical basic parameters or whether individual parameters should apply to
each master system. The basic parameters set in the installation assistant can be changed at any
time in the settings menu.
Back button:
The “Back” button returns you to the last menu accessed.
Next button (is only displayed in the installation assistant):
Pushing the “Next” button takes you to the “Setting the time” menu.
Information button:
Actuating the “Info” button opens an information screen. This contains a brief expla-
nation of the setting options in the respective menu.
Master system identical button:
If this button is activated (green), then the values entered subsequently are sent to all
connected systems. Otherwise the number of connected master systems is deter-
mined and the operator must enter the values separately for each system.
Page 23Status 13.06.2014
4.6 Setting the time
Time, date and switching times can be set and specified in this menu. Time and date are already set
in the factory.
Back button:
The “Back” button returns you to the last menu accessed.
Next button (is only displayed in the installation assistant):
Pushing the “Next” button takes you to the “Enable” menu.
Information button:
Actuating the “Info” button opens an information screen. This contains a brief expla-
nation of the setting options in the respective menu.
Activation/deactivation button:
If this button is activated (green), the stored switching times are activated, and the
switching times have priority over manual and automatic operating function. The
stored switching times are not lost when the button is deactivated (red).
Page 24 Status 13.06.2014
Operating Instructions for Controller TLC 700
“Time” button:
You can set the current time in this
screen:
"Hours/minutes"
When you touch one of the time boxes,
a numerical input window opens up so
you can enter the desired time.
“Automatic summer/winter time set-
ting” button:
If this button is set (green), the system
automatically switches between summer
and winter time.
“Date” button:
You can set the current date in this
screen:
“Day/month/year”
If you touch one of the date boxes, a
numerical input window opens up so you
can enter the desired figures.
Page 25Status 13.06.2014
4.6.1 Switching times
“Start time” button:
The switching times are numbered con-
secutively. As with setting the time, a
sub-menu opens to enter the start time.
“Stop time” button:
As with setting the time, a sub-menu
opens to enter the stop time.
“Mon/Tue/Wed/Thur/Fri/Sat/Sun” but-
tons:
Selection of the days on which the start
and stop time should apply. The selected
days are indicated by a tick.
Other switching times can be created. To
do this you must scroll down using the
scroll button. The number in the “switch-
ing times” screen then changes from 01
to 02 etc.
In total 6 switching times can be set per
master system.
“Scrolling forwards and backwards”
button:
You can view the set times using the
scroll button.
Page 26 Status 13.06.2014
Operating Instructions for Controller TLC 700
4.7 Enable
It can be specified in the enable menu whether a key lock function is desired. If so, an individual key
lock code can be stipulated.
Back button:
The “Back” button returns you to the last menu accessed.
Next button (is only displayed in the installation assistant):
Pushing the “Next” button takes you to the “Summer/winter setting” menu.
Information button:
Actuating the “Info” button opens an information screen. This contains a brief expla-
nation of the setting options in the respective menu.
Activate key lock button:
If the key lock function is activated (green), this is displayed in menu screens.
The standard setting is green = activated with code 0000.
Authorisation code button:
When you actuate the button a 4-digit numerical input box opens. You must enter the
authorisation code 1106 here. The authorisation code is always the same, and can-
not be changed.
Page 27Status 13.06.2014
New code for the key lock button:
Important: before you can specify a new code for the key lock, the authorisation code
1106 must first be entered. If the authorisation code is not entered or is entered in-
correctly, the system will not accept the new key lock code!
When you actuate the button, a 4-digit numerical input box opens. You can now en-
ter your desired authorisation code. 0000 is stored as standard.
NB: if you forget the code of an activated key lock, the supply voltage must be briefly
disconnected from the controller. This deactivates the key lock and you can store a
new key lock code.
4.8 Summer/winter setting
The basic summer/winter settings of your air curtain system can be stipulated in this menu.
In summer mode the heating supply from the heating medium is interrupted. The shut-off valve, the
pump or the electronic control valve (optional) are closed or switched off.
In winter mode, the heating supply from the heating medium is enabled. The shut-off valve, the
pump or the electronic control valve (optional) are open or switched on.
Back button:
The “Back” button returns you to the last menu accessed.
Page 28 Status 13.06.2014
Operating Instructions for Controller TLC 700
Next button (is only displayed in the installation assistant):
Pushing the “Next” button takes you to the “Manual/automatic settings” menu.
Information button:
Actuating the “Info” button opens an information screen. This contains a brief expla-
nation of the setting options in the respective menu.
Summer/winter function button:
When this function is activated (green), the air curtain system can be operated both in
summer and winter. If the customer wishes the system to only be operated in one
mode (either just summer or just winter), this can be specified by deactivating the
function (red). Whether only the summer mode or only the winter mode should be
active is defined at the manufacturer level.
4.8.1. Automatic summer/winter changeover
“Temperature entry” button:
The summer/winter changeover is
switched manually by operating
staff by way of standard. If the
optional outdoor temperature sen-
sor is available, the summer/winter
changeover takes place automati-
cally using the specified set point
(e.g. 18 °C).
An additional window opens up to
enter the desired temperature
(standard setting = 18°C) when
you actuate this button.
When you touch the temperature
box, a numerical input window
opens up so you can enter the
desired temperature.
Page 29Status 13.06.2014
4.8.2 Electronic air discharge temperature control
“Room temperature switching”
button
This information button is only dis-
played when the room temperature
switching has been activated in the
settings menu. It cannot be used
to adjust settings.
“Summer (cooling)” button:
This button is only displayed when
the cooling function is activated at
the manufacturer level (standard =
deactivated). The summer (cool-
ing) function is required when the
air curtain system is also to be
used for cooling. In this case the
output signal to the motorised con-
trol valve is reversed. The tem-
perature set point for the summer
mode can be entered here.
“Winter (heating)” button:
The temperature set point for win-
ter mode can be entered here.
General: When you touch the
temperature box, a numerical input
window opens up so you can enter
the desired temperature.
Actual value box:
The current air discharge tempera-
ture of the air curtain system is
displayed here.
Page 30 Status 13.06.2014
Operating Instructions for Controller TLC 700
“Mixer run time” button:
This specifies the run time that the
valve requires from one end posi-
tion to the other end position (fac-
tory setting = 330 sec).
“I-control constant (heating)”
button:
The integral part of the electronic
air discharge temperature control
which influences the control per-
formance can be adjusted here
(setting from 0 to 240 sec., factory
setting = 200 sec.).
“P-control constant (heating)”
button:
The proportional part of the elec-
tronic air discharge temperature
control which influences the con-
trol performance can be adjusted
here (setting from 10 to 1000 %,
factory setting = 500 %).
“Min. valve opening” button:
When a value (greater than 0%) is
entered here, a specific volume of
water flows permanently through
the heater battery. This prevents
the heater battery freezing in the
winter, causing frost damage. This
function is only active in winter
mode!
General: When you touch the nu-
meric keypad, a numerical input
window opens up so you can enter
the desired level.
Page 31Status 13.06.2014
“Set point night-time tempera-
ture reduction” button:
The night-time temperature reduc-
tion is active when this button is
set (green). This function can only
be activated when switching times
have been stored in the timer pro-
gram.
“Winter” button:
The temperature set point (air dis-
charge temperature control) for
night-time temperature reduction
can be entered here.
“I-control constant (heating)”
button:
The integral part of the electronic
air discharge temperature control
which influences the control per-
formance can be adjusted here
(setting from 0 to 240 sec., factory
setting = 200 sec.).
“P-control constant (cooling)”
button:
The proportional part of the elec-
tronic air discharge temperature
control which influences the con-
trol performance can be adjusted
here (setting from 10 to 1000 %,
factory setting = 500 %).
General: When you touch the nu-
meric keypad, a numerical input
window opens up so you can enter
the desired level.
Page 32 Status 13.06.2014
Operating Instructions for Controller TLC 700
4.9 Manual/automatic mode setting
This menu page is displayed with speed or level, depending on which type of motor is installed (AC
or DC). It is set in the factory (Teddington).
Specify the basic manual/automatic mode settings for your air curtain system in this menu.
In manual mode the air curtain system operates permanently at the preselected level. The level can
be set on the control element.
In automatic mode the air curtain system is switched on and off automatically. The level is prese-
lected manually on the control element or optionally automatically.
Back button:
The “Back” button returns you to the last menu accessed.
Next button (is only displayed in the installation assistant):
Pushing the “Next” button takes you to the “Room thermostat” menu.
Information button:
Actuating the “Info” button opens an information screen. This contains a brief expla-
nation of the setting options in the respective menu.
Page 33Status 13.06.2014
Manual/Auto function button:
When this function is activated (green), the air curtain system can be operated in both
manual and automatic operating mode. If the customer wishes the system to be op-
erated in only one mode (either just manual or just automatic), this can be specified
by deactivating (red). It is defined at the manufacturer level whether only manual or
only automatic operating mode should be active.
Automatic run-on button:
You can specify here how long the fans continue to run after the system has been
switched off in automatic mode. This prevents the system being switched on and off
constantly in busy times (adjustable: 0-600 sec, standard = 20 sec).
Level/speed for the run-on button:
By activating this function (green), you can specify a level or a speed for the run-on
time. When you touch the numeric keypad, a numerical input window opens up so
you can enter the desired level.
PLEASE
NOTE
Only one of the four automatic functions described below can be se-
lected! The decision as to which function is best for you depends on
the particular building situation.
“Outdoor temperature sensor” button:
The speed or level switching takes place
automatically here using an optional out-
door temperature sensor. This function is
only active in automatic operating mode.
Button set (green) - “Outdoor tempera-
ture” function is active.
“Summer/winter operation” button:
By activating this function (green), the
system is also controlled automatically
via the outdoor temperature sensor in
summer mode.
“Summer/winter changeover” button:
When this function is activated, the sum-
mer/winter changeover for the speed
control takes place according to the set
point that has been entered (standard
value = 18°C).
Outdoor temperature box:
The current outdoor temperature is dis-
played here.
Page 34 Status 13.06.2014
Operating Instructions for Controller TLC 700
Level/speed box:
Level and speed values for summer and
winter mode can be specified here de-
pending on the outdoor temperature.
The heading “level” or “speed” depends
on the type of motor installed.
If the “Summer/winter operation” button in
the “automatic operating mode outdoor
temperature” screen has been deactivat-
ed (red), the summer column is not
shown. Only entries for the winter mode
can be made therefore.
General: When you touch the numeric
keypad, a numerical input window opens
up so you can enter the desired level.
“Infrared sensor” button:
The speed or level switching takes place
automatically here when using an option-
al infrared sensor. This function is only
active in automatic operating mode.
Button set (green) - “Infrared sensor”
function is active.
“Set point” button:
You can enter the set point for the ground
temperature here.
Actual level box:
The current ground temperature is dis-
played here.
“P-control constant” button:
The proportional part of the electronic
infrared control which influences the con-
trol performance can be adjusted here
(setting from 10 to 1000 %, factory set-
ting = 100 %).
“I-control constant” button:
The integral part of the electronic infrared
control which influences the control per-
formance can be adjusted here (setting
from 0 to 240 sec., factory setting = 10
sec.).
General: When you touch the numeric
keypad, a numerical input window opens
up so you can enter the desired level.
Page 35Status 13.06.2014
“External 0-10V signal” button:
The speed or level switching takes place
automatically here using an external 0-
10V signal (e.g. BMS, wind turbine). This
function is only active in automatic mode.
Button set (green) - “0-10V signal” func-
tion is active.
Actual level box:
The actual value of the external input
signal is displayed here.
“Linear” button:
By activating (green) the linear function in
in automatic operating mode, the output
signal (speed/level) is determined and
generated proportional to the input signal
(0-10 V).
Input 0-10V Level
0-9 % 0
10-29 % 1
30-49 % 2
50-69 % 3
70-89 % 4
90-100 % 5
“PI- control” button:
By activating (green) the PI control func-
tion in automatic operating mode, the
output signal (speed/level) is determined
and generated by the PI control. The PI
control regulates the difference between
the actual value (0-100%/0-10V input)
and the set point value which has been
set using the control element.
“Set point” button:
The set point for the PI control can be set
here. This set point button is only dis-
played when the PI control function has
been activated!
The four input value boxes are re-
quired for the linear function.
“Bottom” input value buttons:
How the input signals are to be shown as
values on the display is specified here.
Example turbine:
Bottom input value 0V (0 km/h)=0%
Top input value 10V (50 km/h)=100%
Page 36 Status 13.06.2014
Operating Instructions for Controller TLC 700
“P-control constant” button:
The proportional part of the PI-control
which influences the control performance
can be adjusted here (setting from 10 to
1000 %, factory setting = 100 %).
P-part: P=10% and ΔU = 0.1 V >> speed
change = 1%
“I-control constant” button:
The integral part of the PI-control which
influences the control performance can
be adjusted here (setting from 0 to 240
sec., factory setting = 10 sec.).
I-part: I = 60 sec., P=100% and ΔU = 0.1
V (constant over 60 sec.) >> speed
change = 1%
General: When you touch the numeric
keypad, a numerical input window opens
up so you can enter the desired level.
“External 0-20mA signal” button:
The speed or level switching takes place
automatically here using an external 0-
20mA signal (e.g. BMS, turbine). This
function is only active in automatic oper-
ating mode.
Button set (green) “0-20mA signal” func-
tion is active.
Actual level box:
The actual value of the external input
signal is displayed here.
“Linear” button:
By activating (green) the linear function in
in automatic operating mode, the output
signal (speed/level) is determined and
generated proportional to the input signal
(0-20 mA).
Input 0-20 mA Level
0-9 % 0
10-29 % 1
30-49 % 2
50-69 % 3
70-89 % 4
90-100 % 5
Page 37Status 13.06.2014
“PI-control” button:
By activating (green) the PI control func-
tion in automatic operating mode, the
output signal (speed/level) is determined
and generated by the PI control. The PI
control regulates the difference between
the actual value (0-100%/0-20mA input)
and the set point value which has been
set using the control element.
“Set point” button:
The set point for the PI control can be set
here. This set point button is only dis-
played when the PI control function has
been activated!
The four input value boxes are re-
quired for the linear function.
“Bottom” input value buttons:
How the input signals are to be shown as
values on the display is specified here.
Example turbine:
Bottom input value 0mA (0 km/h)=0%
Top input value 20mA (50 km/h)=100%
“P-control constant” button:
The proportional part of the PI-control
which influences the control performance
can be adjusted here (setting from 10 to
1000 %, factory setting = 100 %).
P-part: P=10% and ΔU = 0.1 V >> speed
change = 1%
“I-control constant” button:
The integral part of the PI-control which
influences the control performance can
be adjusted here (setting from 0 to 240
sec., factory setting = 10 sec.).
I-part: I = 60 sec., P=100% and ΔU = 0.1
V (constant over 60 sec.) >> speed
change = 1%
General: When you touch the numeric
keypad, a numerical input window opens
up so you can enter the desired level.
Page 38 Status 13.06.2014
Operating Instructions for Controller TLC 700
4.10 Room thermostat setting
Whether the system is to be switched on and off automatically using a room thermostat and there-
fore the heating function is desired is specified using the room thermostat menu. The automatic ac-
tivation via terminals 26 and 27 (door contact) has priority over the room thermostat function!
Back button:
The “Back” button returns you to the last menu accessed.
Information button:
Actuating the “Info” button opens an information screen. This contains a brief expla-
nation of the setting options in the respective menu.
Thermostat button:
The room thermostat function is active (standard = activated) when this button is set
(green).
Internal/external button:
By actuating the internal or external button, you specify whether the internal room
sensor or an external room sensor/external room thermostat is to be used for the
thermostat function. The controller automatically detects whether an external room
sensor or an external room thermostat has been connected.
Page 39Status 13.06.2014
Set point button:
You can enter the set point for the room temperature here. If the room temperature
(actual value) falls below the set point, the system is switched on in automatic mode.
This set point is used for the internal and external room sensor.
Actual value box:
The current room temperature is displayed here.
Base load level/base load speed button:
This function is active when this button is set (green) and the following settings (e.g.
base load level/base load speed) are displayed (standard = deactivated).
Scroll forwards button:
You can scroll to the next settings menu page using this button.
Scroll backwards button:
You can scroll back to the previous settings menu page using this button.
Next button (is only displayed in the installation assistant):
Pushing the “Next” button takes you to the “Servicing” menu.
Depending on which motor has been
connected (AC or EC), “base load level”
or “base load speed” is displayed in the
menu. The AC or EC motor setting is
made by the manufacturer.
“Base load level/base load speed
button:
When the base load level/base load
speed button (previous screen) has been
activated (green), the input box for the
base load level/base load speed appears
in the menu. Using this setting you can
specify a special level/speed for the room
thermostat operation.
“Night-time temperature reduction”
button:
You can set a different night-time room
temperature by activating this function
(green). This function can only be acti-
vated when switching times have been
activated in the timer program.
“Set point” button (is only displayed
when the night-time temperature re-
duction is active):
You can adjust the room temperature at
which the systems should be switched on
at night by actuating the set point button.
This set point is used for the internal and
external room sensor (standard = 16°C).
“Actual value box:
The current room temperature is dis-
played here.
General: When you touch the numeric
keypad, a numerical input window opens
up so you can enter the desired level.
Page 40 Status 13.06.2014
Operating Instructions for Controller TLC 700
4.11 Servicing menu
Whether and how a filter service message is generated is specified in the servicing menu.
Back button:
The “Back” button returns you to the last menu accessed.
Next button (is only displayed in the installation assistant):
Pushing the “Next” button takes you to the main screen and you leave the installation
assistant.
Information button:
Actuating the “Info” button opens an information screen. This contains a brief expla-
nation of the setting options in the respective menu.
Filter servicing button:
This function is active (standard = activated) when this button is set (green) and you
are informed automatically when the next service is due.
Page 41Status 13.06.2014
Internal/external button (is only displayed with activate filter servicing):
By actuating the internal or external button, you can specify whether the service mes-
sage is triggered internally or by an external signal. If the internal button is activated,
the service is generated by a time module (operating hours). If the external button
has been activated, a service message is triggered via an external signalling device
(terminal 24/25).
Actual operating hours display:
Display of the operating hours since the last service. The operating hours are incre-
mental.
Target operating hours button:
Specification of the time interval between servicing units (standard = 500h; you can
and should check this interval and adapt it to your situation. Please refer to the air
curtain operating instructions to find out how to establish the correct interval).
Set to 0 button:
By actuating the “Set to 0 button”, the actual operating hours display is set to 0. The
counting of the operating hours starts from the beginning again.
This completes the installation assistant for the first master system. If you have select-
ed further different master systems, you can now go to the start of the second installa-
tion assistant for the second master system starting with setting the time.
If you have not selected another master system, you go to the main screen for the con-
troller.
Page 42 Status 13.06.2014
Operating Instructions for Controller TLC 700
5 Main screen / standard displays
5.1Standard screen depending on the version of air curtain system
The arrangement of the air curtain system in the display has already been set in
the factory and can be changed by the manufacturer at any time. After implement-
ing the installation assistant, one of the following screens is displayed for each
master system:
“IDW” screen (air roll rotating inwards)
The system selection box only appears if more than one master system is pre-
sent in the system (eBus)!
“ADW” screen (air roll rotating outwards)
Page 43Status 13.06.2014
5.2 Standard display depending on the desired arrangement
“One-sided left” screen
“One-sided right” screen
“Two-sided” screen
Page 44 Status 13.06.2014
Operating Instructions for Controller TLC 700
Please note: System selection can only
take place after implementing the installa-
tion assistant in the main screen!
You can select the system to be adjusted
in this screen.
• Green: System is present and
switched on
• Blue: Selected system
• Orange: System is present but
switched off
• Grey: System is not present
Page 45Status 13.06.2014
5.3 Functions main screen
Key lock button:
The key lock can be activated and deactivated here. Actuating the button opens
a window in which the key lock code can be entered. After entering the code the
display is locked and therefore protected from unauthorised operation. The acti-
vated key lock is displayed by a closed padlock.
Settings menu button:
The settings overview menu is opened using this button:
On/off button:
Switches the master air curtain system off. If more than one master systems
(Multimaster) are connected, all systems are switched off simultaneously by
keeping the button pressed for longer.
Page 46 Status 13.06.2014
Operating Instructions for Controller TLC 700
5.4 Hotkeys on the main screen
The most important basic functions are integrated on the respective main screen by means of
hotkeys. When touched the functions can be opened and changed without having to run
through the settings menu steps etc. Only the functions which have been activated are dis-
played on the main screen!
Functions are stored on these screen systems:
Page 47Status 13.06.2014
Function Symbol which can be
activated on the main
screen
Function subpage which appears
after actuating the symbol
Setting the date
Air discharge tem-
perature
Outdoor temperature
Time
Summer/
winter function
or
Page 48 Status 13.06.2014
Operating Instructions for Controller TLC 700
Speed or level set-
ting
or
Manual/automatic
function
or
System selection
Room temperature
Ground temperature
(Actual value = ground temperature)
Page 49Status 13.06.2014
5.5 Entry and keypad
The operator must be able to store various values in the settings menu pages. For example when
setting the time, press on the value you want to change and this opens a numerical keypad in a sub-
menu. You can enter the new value here and/or delete the existing values again using the “Delete
button”.
A written entry must be stored for other settings. A keypad screen therefore appears for these input
boxes (when touched).
Page 50 Status 13.06.2014
Operating Instructions for Controller TLC 700
6 Settings menu
Actuating the “Settings menu” button on the main screen takes you to this sub-menu. Here you
can adjust all settings that are required for ideal functioning of the air curtain system. Settings from
the installation assistant can likewise be changed here.
Back button:
The “Back” button returns you to the main screen.
6.1 Setting the language sub-menu
Language setting button:
For menu description, see Chapter 41.1, Page 18.
Page 51Status 13.06.2014
6.2 Settings sub-menu
The installed software version (is automatically detected) and the installed hard-
ware version (is likewise automatically detected) are displayed on the first page of
settings.
Back button:
The “Back” button returns you to the last menu accessed.
Information button:
Actuating the “Info” button opens an information screen. This contains a brief
explanation of the setting options in the respective menu.
Scroll forwards button:
You can scroll to the next settings menu page using this button.
The three functions marked above are
only displayed if the electronic air dis-
charge temperature control has been
activated!
“Activate room switching” button:
The room temperature difference is
switched to the air discharge temper-
ature control on activating this func-
tion (green) (standard = deactivated).
“Reinforcement factor” button:
If the current room temperature is
higher than the set room temperature
set point, the air discharge tempera-
ture set point is automatically
changed with the aid of the rein-
forcement factor (standard setting 2).
Example:
Current room temperature 23 °C
Set point room temperature 22 °C
Reinforcement factor 2
Set point air discharge temp. control
37 °C
Page 52 Status 13.06.2014
Operating Instructions for Controller TLC 700
Using the reinforcement factor 2 and
the room temperature variation of
1°C, the set point of the air discharge
temperature is corrected from 37 °C
to 35 °C.
“Minimum set point air discharge
temperature” button:
With this setting you determine the
lowest set point of the electronic air
discharge temperature control
(standard setting 30 °C) which the
room temperature switching calcu-
lates and does not fall below.
General: When you touch the numer-
ic keypad, a numerical input window
opens up so you can enter the de-
sired level.
Scroll forwards button:
You can scroll to the next settings menu page using this button.
“Contact details of installer” but-
ton
Actuating this box takes you to the
sub-menu to change or enter the ad-
dress data of the installer; see Chap-
ter 4.4, Page 21.
“Sleep mode” button
Actuating this box takes you to a sub-
menu in which you can adjust the
sleep mode time. The function is
active when no further operation has
taken place after the set time (stand-
ard setting 15 minutes). The idle
screen appears in the display
(black/grey image). If 0 is entered
here, the sleep mode is deactivated.
To deactivate the function you only
need to touch the screen. Irrespec-
tive of where you were before activa-
tion, after activation you are always
on the main screen.
Page 53Status 13.06.2014
6.3 Setting the time sub-menu
Time setting button:
Menu description see Chapter 4.6 Setting the time, Page 23.
6.4 Enable sub-menu
Enable button:
Menu description see Chapter 4.7 Enable, Page 26.
6.5 Summer/winter setting sub-menu
Summer/winter setting button:
Menu description see Chapter 4.8 Summer/winter setting, Page 27
6.6 Manual/automatic setting sub-menu
Manual/automatic setting button:
Menu description see Chapter 4.9 Manual/automatic mode setting, Page 32
6.7 Room thermostat sub-menu
Room thermostat button:
Menu description see Chapter 4.10 Room thermostat setting, Page 38
Page 54 Status 13.06.2014
Operating Instructions for Controller TLC 700
6.8 Electronic air discharge temperature control sub-menu
Electronic air discharge temperature control button:
Menu description see Chapter 4.8.2 Electronic air discharge temperature control,
Page 29.
6.9 Manufacturer level sub-menu
Manufacturer level button:
Actuating this button takes you to the start screen of the manufacturer level; ac-
cess is reserved for the manufacturer.
6.10 Servicing sub-menu
Servicing button:
Description see Chapter 4.11 Servicing menu, Page 40
Page 55Status 13.06.2014
6.11 Error/fault sub-menu
The faults screen shows you a report of the last faults that have arisen.
If a fault occurs, this is firstly displayed on the main screen.
Once the fault has been rectified, it can be acknowledged using the button .
The fault window is then faded out. The fault can only be acknowledged if you
are on the screen of the respective master system, e.g. the is not displayed if a
fault is present in system 2, but the operator is in the menu of system 1!
Page 56 Status 13.06.2014
Operating Instructions for Controller TLC 700
6.12 Contacts and button overview sub-menu
This menu screen gives you important information about the manufacturer of the
air curtain system, the installer and above all which basic menu buttons you must
be familiar with in order to operate the TLC 700 controller easily.
In this sub-menu you will find all es-
sential information on the manufactur-
er of the air curtain system.
The contact details of the installer are
stored in this sub-menu.
Basic buttons:
Menu description see Chapter 4.2
Basic buttons, Page 19
Page 57Status 13.06.2014
Serial number:
The serial number of your system has
been stored by the manufacturer and
is displayed here.
Page 58 Status 13.06.2014
Operating Instructions for Controller TLC 700
Notes:
Page 59Status 13.06.2014
Notes:
Page 60 Status 13.06.2014
Operating Instructions for Controller TLC 700

More Related Content

What's hot

PLC: Buses industriales y de campo practicas de laboratorio por Jose Miguel R...
PLC: Buses industriales y de campo practicas de laboratorio por Jose Miguel R...PLC: Buses industriales y de campo practicas de laboratorio por Jose Miguel R...
PLC: Buses industriales y de campo practicas de laboratorio por Jose Miguel R...SANTIAGO PABLO ALBERTO
 
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair ManualPERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manualjsnekmse
 
Toro groundsmaster 322 d mower service repair manual
Toro groundsmaster 322 d mower service repair manualToro groundsmaster 322 d mower service repair manual
Toro groundsmaster 322 d mower service repair manualufuusjjfjkskekmem
 
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...jksnmdm
 
Controladores lógicos programables 4ta Edición por Frank D. Petruzella.pdf
Controladores lógicos programables  4ta Edición por Frank D. Petruzella.pdfControladores lógicos programables  4ta Edición por Frank D. Petruzella.pdf
Controladores lógicos programables 4ta Edición por Frank D. Petruzella.pdfSANTIAGO PABLO ALBERTO
 
Innova 3145 Ford OBD1 Code Reader User Manual
Innova 3145 Ford OBD1 Code Reader User ManualInnova 3145 Ford OBD1 Code Reader User Manual
Innova 3145 Ford OBD1 Code Reader User ManualTim Miller
 
Gebruikershandleiding telys 2 besturing 33502019901 0 1
Gebruikershandleiding telys 2 besturing 33502019901 0 1Gebruikershandleiding telys 2 besturing 33502019901 0 1
Gebruikershandleiding telys 2 besturing 33502019901 0 1andescar
 
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...fjskekfseik
 
huong-dan-su-dung-eplan-electric-p8
 huong-dan-su-dung-eplan-electric-p8 huong-dan-su-dung-eplan-electric-p8
huong-dan-su-dung-eplan-electric-p8Con Khủng Long
 
Kode error-dan-manual-kelistrikan-mesin-3 sz-ve-k3-ve
Kode error-dan-manual-kelistrikan-mesin-3 sz-ve-k3-veKode error-dan-manual-kelistrikan-mesin-3 sz-ve-k3-ve
Kode error-dan-manual-kelistrikan-mesin-3 sz-ve-k3-veAgus Irawan
 
Doğal Gaz İşletme Bakım Operatörü (Seviye 4) 11UY0030-4
Doğal Gaz İşletme Bakım Operatörü (Seviye 4) 11UY0030-4Doğal Gaz İşletme Bakım Operatörü (Seviye 4) 11UY0030-4
Doğal Gaz İşletme Bakım Operatörü (Seviye 4) 11UY0030-4Cagandroid
 
Liquiphant m ftl50 endress+hauser datasheet-point level switch
Liquiphant m ftl50 endress+hauser datasheet-point level switchLiquiphant m ftl50 endress+hauser datasheet-point level switch
Liquiphant m ftl50 endress+hauser datasheet-point level switchENVIMART
 
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair ManualPERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manualhfjskefmmmse
 
PLC y Electroneumática: Circuitos Automatismos Eléctricos
PLC y Electroneumática: Circuitos Automatismos EléctricosPLC y Electroneumática: Circuitos Automatismos Eléctricos
PLC y Electroneumática: Circuitos Automatismos EléctricosSANTIAGO PABLO ALBERTO
 
PHÂN TÍCH, ĐÁNH GIÁ RƠLE SEL-311L BẢO VỆ SO LỆCH DỌC ĐƢỜNG DÂY 500KV DI LINH ...
PHÂN TÍCH, ĐÁNH GIÁ RƠLE SEL-311L BẢO VỆ SO LỆCH DỌC ĐƢỜNG DÂY 500KV DI LINH ...PHÂN TÍCH, ĐÁNH GIÁ RƠLE SEL-311L BẢO VỆ SO LỆCH DỌC ĐƢỜNG DÂY 500KV DI LINH ...
PHÂN TÍCH, ĐÁNH GIÁ RƠLE SEL-311L BẢO VỆ SO LỆCH DỌC ĐƢỜNG DÂY 500KV DI LINH ...nataliej4
 
Índice del libro: "Pentesting con Kali Silver Edition" de 0xWord
Índice del libro: "Pentesting con Kali Silver Edition" de 0xWordÍndice del libro: "Pentesting con Kali Silver Edition" de 0xWord
Índice del libro: "Pentesting con Kali Silver Edition" de 0xWordTelefónica
 

What's hot (20)

PLC: Buses industriales y de campo practicas de laboratorio por Jose Miguel R...
PLC: Buses industriales y de campo practicas de laboratorio por Jose Miguel R...PLC: Buses industriales y de campo practicas de laboratorio por Jose Miguel R...
PLC: Buses industriales y de campo practicas de laboratorio por Jose Miguel R...
 
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair ManualPERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
 
Toro groundsmaster 322 d mower service repair manual
Toro groundsmaster 322 d mower service repair manualToro groundsmaster 322 d mower service repair manual
Toro groundsmaster 322 d mower service repair manual
 
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
 
Controladores lógicos programables 4ta Edición por Frank D. Petruzella.pdf
Controladores lógicos programables  4ta Edición por Frank D. Petruzella.pdfControladores lógicos programables  4ta Edición por Frank D. Petruzella.pdf
Controladores lógicos programables 4ta Edición por Frank D. Petruzella.pdf
 
Innova 3145 Ford OBD1 Code Reader User Manual
Innova 3145 Ford OBD1 Code Reader User ManualInnova 3145 Ford OBD1 Code Reader User Manual
Innova 3145 Ford OBD1 Code Reader User Manual
 
Gebruikershandleiding telys 2 besturing 33502019901 0 1
Gebruikershandleiding telys 2 besturing 33502019901 0 1Gebruikershandleiding telys 2 besturing 33502019901 0 1
Gebruikershandleiding telys 2 besturing 33502019901 0 1
 
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
 
huong-dan-su-dung-eplan-electric-p8
 huong-dan-su-dung-eplan-electric-p8 huong-dan-su-dung-eplan-electric-p8
huong-dan-su-dung-eplan-electric-p8
 
Kode error-dan-manual-kelistrikan-mesin-3 sz-ve-k3-ve
Kode error-dan-manual-kelistrikan-mesin-3 sz-ve-k3-veKode error-dan-manual-kelistrikan-mesin-3 sz-ve-k3-ve
Kode error-dan-manual-kelistrikan-mesin-3 sz-ve-k3-ve
 
Dt 4 instalação e manutenção de motores ca
Dt 4   instalação e manutenção de motores caDt 4   instalação e manutenção de motores ca
Dt 4 instalação e manutenção de motores ca
 
Doğal Gaz İşletme Bakım Operatörü (Seviye 4) 11UY0030-4
Doğal Gaz İşletme Bakım Operatörü (Seviye 4) 11UY0030-4Doğal Gaz İşletme Bakım Operatörü (Seviye 4) 11UY0030-4
Doğal Gaz İşletme Bakım Operatörü (Seviye 4) 11UY0030-4
 
Liquiphant m ftl50 endress+hauser datasheet-point level switch
Liquiphant m ftl50 endress+hauser datasheet-point level switchLiquiphant m ftl50 endress+hauser datasheet-point level switch
Liquiphant m ftl50 endress+hauser datasheet-point level switch
 
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair ManualPERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
 
Manual fec standard
Manual fec standardManual fec standard
Manual fec standard
 
Qnet user manual
Qnet user manualQnet user manual
Qnet user manual
 
Manual esquemas Moeller
Manual esquemas MoellerManual esquemas Moeller
Manual esquemas Moeller
 
PLC y Electroneumática: Circuitos Automatismos Eléctricos
PLC y Electroneumática: Circuitos Automatismos EléctricosPLC y Electroneumática: Circuitos Automatismos Eléctricos
PLC y Electroneumática: Circuitos Automatismos Eléctricos
 
PHÂN TÍCH, ĐÁNH GIÁ RƠLE SEL-311L BẢO VỆ SO LỆCH DỌC ĐƢỜNG DÂY 500KV DI LINH ...
PHÂN TÍCH, ĐÁNH GIÁ RƠLE SEL-311L BẢO VỆ SO LỆCH DỌC ĐƢỜNG DÂY 500KV DI LINH ...PHÂN TÍCH, ĐÁNH GIÁ RƠLE SEL-311L BẢO VỆ SO LỆCH DỌC ĐƢỜNG DÂY 500KV DI LINH ...
PHÂN TÍCH, ĐÁNH GIÁ RƠLE SEL-311L BẢO VỆ SO LỆCH DỌC ĐƢỜNG DÂY 500KV DI LINH ...
 
Índice del libro: "Pentesting con Kali Silver Edition" de 0xWord
Índice del libro: "Pentesting con Kali Silver Edition" de 0xWordÍndice del libro: "Pentesting con Kali Silver Edition" de 0xWord
Índice del libro: "Pentesting con Kali Silver Edition" de 0xWord
 

Similar to TLC_700_Controller_unit

Honeywell gsmv-install-guide
Honeywell gsmv-install-guideHoneywell gsmv-install-guide
Honeywell gsmv-install-guideAlarm Grid
 
Siemens catalog hmi-tp070 touch panel
Siemens catalog hmi-tp070 touch panelSiemens catalog hmi-tp070 touch panel
Siemens catalog hmi-tp070 touch panelDien Ha The
 
Siemens catalog hmi-tp070_e
Siemens catalog hmi-tp070_eSiemens catalog hmi-tp070_e
Siemens catalog hmi-tp070_eDien Ha The
 
Manual de Danfoss 2800
Manual de Danfoss 2800Manual de Danfoss 2800
Manual de Danfoss 2800Camilo Avelino
 
Manual Variador Danfoss VLT 2800
Manual Variador Danfoss VLT 2800Manual Variador Danfoss VLT 2800
Manual Variador Danfoss VLT 2800Camilo Avelino
 
controlador manual
controlador manual controlador manual
controlador manual Pedro Roman
 
Cataloge ge 3.control and_automation_dienhathe.com-4_01_vat300_e_title_rev_c
Cataloge ge 3.control and_automation_dienhathe.com-4_01_vat300_e_title_rev_cCataloge ge 3.control and_automation_dienhathe.com-4_01_vat300_e_title_rev_c
Cataloge ge 3.control and_automation_dienhathe.com-4_01_vat300_e_title_rev_cDien Ha The
 
Cataloge ge 3.control and_automation-01_vat300_e_title_rev_c
Cataloge ge 3.control and_automation-01_vat300_e_title_rev_cCataloge ge 3.control and_automation-01_vat300_e_title_rev_c
Cataloge ge 3.control and_automation-01_vat300_e_title_rev_cDien Ha The
 
LifeBreath Operation & Installation Manual max series 500 erv
LifeBreath Operation & Installation Manual max series 500 ervLifeBreath Operation & Installation Manual max series 500 erv
LifeBreath Operation & Installation Manual max series 500 ervOlivier Bessire
 
Simocode dp = manual de parametrização e operação
Simocode dp = manual de parametrização e operaçãoSimocode dp = manual de parametrização e operação
Simocode dp = manual de parametrização e operaçãoconfidencial
 
Ks 50-1-ks-52-1-manual-english
Ks 50-1-ks-52-1-manual-englishKs 50-1-ks-52-1-manual-english
Ks 50-1-ks-52-1-manual-englishjeferson tadeu
 
Ct2000 v english_ver 1.36
Ct2000 v english_ver 1.36Ct2000 v english_ver 1.36
Ct2000 v english_ver 1.36Toàn Huỳnh
 
Cummins onan dggd generator set with power command 2100 controller service re...
Cummins onan dggd generator set with power command 2100 controller service re...Cummins onan dggd generator set with power command 2100 controller service re...
Cummins onan dggd generator set with power command 2100 controller service re...fusjejfjskerekem
 
Cummins onan dggd generator set with power command 2100 controller service re...
Cummins onan dggd generator set with power command 2100 controller service re...Cummins onan dggd generator set with power command 2100 controller service re...
Cummins onan dggd generator set with power command 2100 controller service re...fujsjejfskekkm
 
Cummins onan dghd generator set with power command 2100 controller service re...
Cummins onan dghd generator set with power command 2100 controller service re...Cummins onan dghd generator set with power command 2100 controller service re...
Cummins onan dghd generator set with power command 2100 controller service re...fjsjefkskememe
 
Cummins onan dghd generator set with power command 2100 controller service re...
Cummins onan dghd generator set with power command 2100 controller service re...Cummins onan dghd generator set with power command 2100 controller service re...
Cummins onan dghd generator set with power command 2100 controller service re...fjkskemuiijdmme
 

Similar to TLC_700_Controller_unit (20)

Manual CLP Omron CP1H
Manual CLP Omron CP1HManual CLP Omron CP1H
Manual CLP Omron CP1H
 
Honeywell gsmv-install-guide
Honeywell gsmv-install-guideHoneywell gsmv-install-guide
Honeywell gsmv-install-guide
 
Siemens catalog hmi-tp070 touch panel
Siemens catalog hmi-tp070 touch panelSiemens catalog hmi-tp070 touch panel
Siemens catalog hmi-tp070 touch panel
 
Siemens catalog hmi-tp070_e
Siemens catalog hmi-tp070_eSiemens catalog hmi-tp070_e
Siemens catalog hmi-tp070_e
 
Manual de Danfoss 2800
Manual de Danfoss 2800Manual de Danfoss 2800
Manual de Danfoss 2800
 
Manual Variador Danfoss VLT 2800
Manual Variador Danfoss VLT 2800Manual Variador Danfoss VLT 2800
Manual Variador Danfoss VLT 2800
 
controlador manual
controlador manual controlador manual
controlador manual
 
Omrom e5cn i
Omrom e5cn iOmrom e5cn i
Omrom e5cn i
 
Pci 8158 manual-10
Pci 8158 manual-10Pci 8158 manual-10
Pci 8158 manual-10
 
Cataloge ge 3.control and_automation_dienhathe.com-4_01_vat300_e_title_rev_c
Cataloge ge 3.control and_automation_dienhathe.com-4_01_vat300_e_title_rev_cCataloge ge 3.control and_automation_dienhathe.com-4_01_vat300_e_title_rev_c
Cataloge ge 3.control and_automation_dienhathe.com-4_01_vat300_e_title_rev_c
 
Cataloge ge 3.control and_automation-01_vat300_e_title_rev_c
Cataloge ge 3.control and_automation-01_vat300_e_title_rev_cCataloge ge 3.control and_automation-01_vat300_e_title_rev_c
Cataloge ge 3.control and_automation-01_vat300_e_title_rev_c
 
Q gx developer_e
Q gx developer_eQ gx developer_e
Q gx developer_e
 
LifeBreath Operation & Installation Manual max series 500 erv
LifeBreath Operation & Installation Manual max series 500 ervLifeBreath Operation & Installation Manual max series 500 erv
LifeBreath Operation & Installation Manual max series 500 erv
 
Simocode dp = manual de parametrização e operação
Simocode dp = manual de parametrização e operaçãoSimocode dp = manual de parametrização e operação
Simocode dp = manual de parametrização e operação
 
Ks 50-1-ks-52-1-manual-english
Ks 50-1-ks-52-1-manual-englishKs 50-1-ks-52-1-manual-english
Ks 50-1-ks-52-1-manual-english
 
Ct2000 v english_ver 1.36
Ct2000 v english_ver 1.36Ct2000 v english_ver 1.36
Ct2000 v english_ver 1.36
 
Cummins onan dggd generator set with power command 2100 controller service re...
Cummins onan dggd generator set with power command 2100 controller service re...Cummins onan dggd generator set with power command 2100 controller service re...
Cummins onan dggd generator set with power command 2100 controller service re...
 
Cummins onan dggd generator set with power command 2100 controller service re...
Cummins onan dggd generator set with power command 2100 controller service re...Cummins onan dggd generator set with power command 2100 controller service re...
Cummins onan dggd generator set with power command 2100 controller service re...
 
Cummins onan dghd generator set with power command 2100 controller service re...
Cummins onan dghd generator set with power command 2100 controller service re...Cummins onan dghd generator set with power command 2100 controller service re...
Cummins onan dghd generator set with power command 2100 controller service re...
 
Cummins onan dghd generator set with power command 2100 controller service re...
Cummins onan dghd generator set with power command 2100 controller service re...Cummins onan dghd generator set with power command 2100 controller service re...
Cummins onan dghd generator set with power command 2100 controller service re...
 

TLC_700_Controller_unit

  • 1. Page 1Status 13.06.2014 --- OPERATING INSTRUCTIONS (TRANSLATION OF THE ORIGINAL) SUPPLEMENTARY OPERATING INSTRUCTIONS FOR YOUR AIR CURTAIN SYSTEM Serial number: ____________________________ Year:_____________________ Please quote this number when contacting customer service!
  • 2. Page 2 Status 13.06.2014 Operating Instructions for Controller TLC 700 TLC 700 – Brief description  Electronic air curtain controller TLC 700 with wired control element (remote control) for 5- stage or fully adjustable (in conjunction with ECM motors) activation of Teddington air curtain systems.  The TLC 700 consists of the control element (remote control) and control board (master and/or master/slave); the control board is installed in the air curtain.  A colour touchscreen with graphical presentation of the specific type of installation enables Teddington air curtain systems to be adjusted simply and accurately to meet all require- ments.  The TLC700 is characterised by a simple, self-explanatory menu navigation and program- ming by means of the integrated installation assistant. The menu navigation is available in 5 languages. Every operating step is explained by an integrated help function.  Up to 9 air curtain systems can be connected to one control element and addressed individually or in parallel via the control element (TLC 700).  Room temperature sensors integrated in the control panel or by means of external room sensors; sensors to control the heating function to a reduced, programmable speed level; display of the current room temperature; adjustable night-time tem- perature reduction.  Manual/automatic function: automatic function via room thermostat or door con- tact, automatic switching of stages by external transmitter e.g. external thermo- stat, wind turbine, IR sensor, building management system (BMS) (0-10V, 0- 20mA). The run-on time is freely programmable, and the speed levels for run-on and room heating function can be selected separately.  Integrated week timer with freely selectable programming of switching times for overriding enable function.  Summer /winter function: automatic switching between summer/winter function: automatic switching between summer/winter via external temperature sensor (op- tion), activation of solenoid valve or pump, room temperature dependant electron- ic air discharge temperature control (option).  Integrated filter monitoring function – can be adapted easily on site to operating con- ditions, can be programmed to evaluate operating hours or external transmitter.  Key lock with adjustable code can be activated.  Retrieval of error messages via a battery cached error memory for remote diag- nostics and assignment of an error message to the individual device concerned.  Floating enable, operating and error message for simple communication with the BMS. Output for transmission of the current speed level to the BMS (0-10V).  Recommended cable for bus cable: J-Y(ST)Y 2x2x0.8 mm² (shielded, twisted control cable). This guarantees a fault-free transmission up to 400 m. The con- necting terminals have reverse polarity protection and are short-circuit-proof.  Dimensions of control element: 135 x 96 x 28 mm  Made in Germany. PLEASE NOTE Observe all safety instructions in the device operating instructions! Only adequately trained personnel who meet the requirements set out in the device operating instructions may work on the installation. It is necessary to ensure that the main power supply has been turned off before all work.
  • 3. Page 3Status 13.06.2014 Table of contents 1 Assembly, technical data and eBus diagram ................................................................4 1.1 Assembly information .........................................................................................4 1.2 Wiring information...............................................................................................4 1.3 Technical data of the TLC 700 control element ..................................................6 1.4 Technical data of the TLC 700 master................................................................7 1.5 Technical data of the TLC 700 slave ..................................................................8 1.6 eBus diagram .....................................................................................................9 2 Cable plans and termnals ........................................................................................... 10 2.1 Master terminal plan, AC motors ...................................................................... 10 2.2 Slave terminal plan, AC motors ........................................................................ 11 2.3 Master terminal plan, EC motors ...............................................................................12 2.4 Master terminal plan, EC motors ...............................................................................13 2.5 Master terminal description............................................................................... 14 2.6 Slave terminal description................................................................................. 16 3 Start screen on putting into operation for the first time ............................................... 17 4 Commissioning using the installation assistant........................................................... 18 4.1 Setting the language......................................................................................... 18 4.2 Basic buttons.................................................................................................... 19 4.3 Installation assistant ......................................................................................... 20 4.4 Address installer............................................................................................... 21 4.5 Master systems selection ................................................................................. 22 4.6 Setting the time................................................................................................. 23 4.7 Enable .............................................................................................................. 26 4.8 Summer/winter setting...................................................................................... 27 4.9 Manual/automatic mode setting........................................................................ 32 4.10 Room thermostat setting................................................................................... 38 4.11 Servicing menu................................................................................................. 40 5 Main screen / standard displays ................................................................................. 42 5.1 Standard display depending on the version of air curtain system..................... 42 5.2 Standard display depending on the desired arrangement ................................ 43 5.3 Functions main screen...................................................................................... 45 5.4 Hotkeys on the main screen ............................................................................. 46 5.5 Entry and keypad.............................................................................................. 49 6 Settings menu............................................................................................................. 50 6.1 Setting the language sub-menu........................................................................ 50 6.2 Settings sub-menu............................................................................................ 51 6.3 Setting the time sub-menu................................................................................ 53 6.4 Enable sub-menu ............................................................................................. 53 6.5 Summer/winter setting sub-menu..................................................................... 53 6.6 Manual/automatic setting sub-menu................................................................. 53 6.7 Room thermostat sub-menu ............................................................................. 53 6.8 Electronic air discharge temperature control sub-menu ................................... 54 6.9 Manufacturer level sub-menu ........................................................................... 54 6.10 Servicing sub-menu.......................................................................................... 54 6.11 Error/fault sub-menu......................................................................................... 55 6.12 Contacts and button overview sub-menu.......................................................... 56
  • 4. Page 4 Status 13.06.2014 Operating Instructions for Controller TLC 700 1 Assembly, technical data and eBus diagram 1.1 Assembly information Assembly environment: Closed, dry room which is protected from dirt. Assembly: Wall-mounting with screws and dowels provided. The two fastening holes are positioned diagonally on two corners (see drawing). Alternatively it is possible to assemble directly on a flush-mounted box. In this case it is necessary to ensure that only the four-wire connecting cables of the control element are inside the flush- mounted box! Installation must be performed by an electrician; all applicable provisions and regulations of the responsible electricity supply company must be complied with. 1.2 Wiring information eBus networks: A shielded, twisted two-wire cable must be used to set up eBus networks. The wire shielding must be fastened to the housing of the air curtain system. The bus cable must have the properties listed below:  The cable diameter must be at least 0.8 mm2 .  The total of all bus cables must not exceed a maximum overall length of 400 m. 70mm 110 mm Control element
  • 5. Page 5Status 13.06.2014 In contrast to the abovementioned eBus networks, a four-wire cable is used for the wiring of the TLC 700 control element. Two wires are for the eBus and two for the voltage supply. Details regarding the cable cross-section and the overall length etc. remain un- changed. PLEASE NOTE If more than one circuit board (master and/or master/slave) is connected, it is important for uninterrupted operation that the jumper is not placed on the same circuit board as the one on which the control element is connect- ed. For example the control element which provides the supply voltage can be connected to the master circuit board 1. The jumper which guarantees the eBus supply must then be placed on master circuit board 2 or slave 1. It is also important to note that individual master systems in this eBus sys- tem must not be disconnected from the power supply. Electrical connection: Dimensions: A B C 135 mm 96mm28mm 5mm Supply - Supply + eBus – eBus + Optional external PT1000 sensor
  • 6. Page 6 Status 13.06.2014 Operating Instructions for Controller TLC 700 Synchronisation: Up to 8 TLC 700 slave circuit boards can be connected to a TLC 700 master circuit board via the eBus interface in order to activate further air curtain systems synchronously with the master system. Only one TLC 700 control element can be used per eBus network. The jumper for the eBus supply may only be placed on a circuit board (master or slave). The control element should not also be connected to this circuit board. The maximum number of circuit boards per eBus is 9, whereby at least one master circuit board must be connected. The addresses should be adjusted by DIP switch on the circuit boards. 1.3 Technical data of TLC 700 control element Electrical connection eBus (max. 24 V, 50 mA DC) 4-wire connection, eBus and voltage supply 4-pole connecting terminal Wire: 0.5 – 2.5 mm² (rigid), 0.5 – 1.5 mm² (flexible) mm² 2-pole connecting terminal Wire: 0.34 – 2.5 mm² (rigid), 0.34 – 1.5 mm² (flexible) mm² Keypad TFT touch display TFT display 4.3” colour Temperature sensor, in- ternal NTC Temperature sensor, ex- ternal PT 1000, connection using a 2-pole connecting terminal Protection class IP 20 in accordance with DIN EN 60529 (VDE 0470-1) Ambient temperature 0 °C to + 50 °C Storage temperature -10 °C to + 60 °C Assembly Wall mounting Housing material Plastic, ABS, UV resistant Housing colour White RAL 9016 Dimensions 135mm x 96mm x 28 mm Weight 185 g Conformity The control element satisfies the provisions of the Electro- magnetic Compatibility Directive (2004/108/EC), the Low Voltage Directive (2006/95/EC) and the harmonised stand- ards DIN EN 60730-1, DIN EN 60730-2-9, and bears the CE mark.
  • 7. Page 7Status 13.06.2014 1.4 Technical data for the TLC 700 master Supply voltage 230 V AC, 50 Hz Power input 11 VA 14 VA (with TLC 700 control element) Fusing 10 A T, microfuse 5 mm x 20 mm 80 mA F, microfuse 5 mm x 20 mm Interface eBus (max. 24 V / 100 mA DC) Protection class IP00 in accordance with DIN EN 60529 (VDE 0470-1) Ambient temperature 0 °C … +50 °C Storage temperature -10 °C … +60 °C Max. connecting cross- sections (see terminal dia- gram) 2.5 mm² (X1 - X5) 1.0 mm² (X6 - X8) Digital inputs 7x, floating, switched with switching contact, < 1.5 mA (12 V) Analogue inputs 1x, 4 mA … 20 mA DC, < 10 V 1x, 0 V … 10 V DC, < 1mA, 49.4 kΩ 2x, plug-in temperature sensor (NTC, 8.2 kΩ at 25 °C) for air discharge temperature and outdoor temperature Selectable fan levels 5 or variable (analogue output) Analogue outputs 0 V… 10 V DC, < 35mA Relay outputs (see terminal diagram) R1 – R3 / R6 – R10, 8 A, Ʃ I < 10 A, 250 V AC (µ), ohmic load R3 / R5, 2 A, 250 V AC (µ), ohmic load Triac output 200 mA, 250 V AC (µ), ohmic load Dimensions 240 mm x 108 mm x 48 mm (L x B x H) Weight 460 g Conformity The TLC 700 master control unit satisfies the provisions of the Electromagnetic Compatibility Directive (2004/108/EC), the Low Voltage Directive (2006/95/EC) and the harmonised standards DIN EN 60730-1, DIN EN 60730-2-9, and bears the CE mark.
  • 8. Page 8 Status 13.06.2014 Operating Instructions for Controller TLC 700 1.5 Technical data for the TLC 700 slave Supply voltage 230 V AC, 50 Hz Power input 8 VA Fusing 10 A T, microfuse 5 mm x 20 mm 80 mA F, microfuse 5 mm x 20 mm Interface eBus (max. 24 V / 100 mA DC) Protection class IP00 in accordance with DIN EN 60529 (VDE 0470-1) Ambient temperature 0 °C … +50 °C Storage temperature -10 °C … +60 °C Max. connecting cross- sections (see terminal dia- gram) 2.5 mm² (X1 – X4) 1.0 mm² (X5 / X6) Digital inputs 4x, floating, switched with switching contact, < 1.5 mA (12 V) Selectable fan levels 5 Relay outputs (see terminal diagram) R6 - R10, 8 A, Ʃ I < 10 A, 250 V AC (µ), ohmic load Dimensions Approx. 240 mm x 108 mm x 48 mm (L x B x H) Weight 420 g Conformity The TLC 700 slave control unit satisfies the provisions of the Electromagnetic Compatibility Directive (2004/108/EC), the Low Voltage Directive (2006/95/EC) and the harmonised standards DIN EN 60730-1, DIN EN 60730-2-9, and bears the CE mark.
  • 10. Page 10 Status 13.06.2014 Operating Instructions for Controller TLC 700 2 Cable plans and terminals 2.1 Master terminal plan, AC motors
  • 11. Page 11Status 13.06.2014 2.2 Slave terminal plan, AC motors
  • 12. Page 12 Status 13.06.2014 Operating Instructions for Controller TLC 700 2.3 Master terminal plan, EC motors
  • 13. Page 13Status 13.06.2014 2.4 Slave terminal plan, EC motors
  • 14. Page 14 Status 13.06.2014 Operating Instructions for Controller TLC 700 2.5 Master terminal description Terminal N: Mains voltage N-conductor (230V / 50 Hz). Terminal L: Mains voltage L-conductor (230V / 50 Hz). Terminal 52: Connection of the motor neutral conductor. Terminal 51: Connection of the motor phase. Terminal N: Connection of the neutral conductor for the autotransformer. Terminal L1: Connection of the phase for the transformer. Terminal L1: Connection of the phase for the circuitry with 57 (if necessary). Terminal 57: Connection of the transformer tapping with the highest voltage (e.g. 230 V). Terminal 56: Connection of the transformer tapping with the 2nd highest voltage (e.g. 180 V). Terminal 55: Connection of the transformer tapping with the 3rd highest voltage (e.g. 160 V). Terminal 54: Connection of the transformer tapping with the 4th highest voltage (e.g. 125 V). Terminal 53: Connection of the transformer tapping with the lowest voltage (e.g. 70 V). Terminal N: Connection of the pump neutral conductor. Terminal 9: Connection of the pump phase. The pump is used to transport the hot water from the boiler to the heater battery in the air curtain system. Terminal 32: Connection of the control circuit from the power contactor K1 to shut down the transformer. Terminal N: Connection of the pump neutral conductor or connection of the mixer neutral conductor. Terminal 33: Connection of the phase to open the mixer. The mixer is used to adjust the air discharge temperature. Terminal 34: Connection of the phase to close the mixer. Terminal PE: Connection of the earth conductor. Terminal 15: Root of the floating changeover contact for the ext. fault message (230 V / max. 8 A or extra low voltage). Terminal 13: If there is no fault, the root from is switched from terminal 15 to terminal 13. Terminal 14: If a fault is present, the root from is switched from terminal 15 to terminal 14. Terminal 12: Root of the floating changeover contact for the ext. operating message (230 V / max. 8 A or extra low voltage). Terminal 10: If the fan motors are still, then the root is switched from terminal 12 to terminal 10. Terminal 11: If the fan motors are running, then the root is switched from terminal 12 to terminal X5 / 11. Terminal 20 & 21: Input for the floating thermal contacts of the fan motors. Terminal 22 & 23: Input for the floating thermal contacts of the transformer. Terminal 24 & 25: Input for the floating switch of the filter monitoring. Terminal 16 & 17: Input for the floating frost protection switch.
  • 15. Page 15Status 13.06.2014 Terminal 18 & 19: Input for the floating repair switch. Terminal 35 & 36: Input for the air discharge temperature sensor. This sensor is an NTC with a specific characteristic curve. Terminal 37 & 38: Output (0...10 V) to activate fans with 0...10-V input or as stage operating message. Stage 0 = 1 V, St. 1 = 2.5 V, St. 2 = 4 V, St. 3 = 5.5 V, St. 4 = 7 V, St. 5 = 8.5V (+/- 0.5 V). The positive potential lies on terminal 37. Terminal 38 is GND. Terminal 28 & 29: Input for a floating ext. enabling contact (e.g. DDC). Terminal 39 & 42: Input (4 ... 20 mA) for the IR sensor. The IR sensor is used to measure the ground temperature. The fan speed is controlled in automatic operating mode on the basis of the ground temperature and an adjusted set point. The positive potential is connected to terminal 39. Terminal 42 is the common GND connection for the inputs 39, 40 and 41. Terminal 40 & 42: Input (0 ... 10 V) for specification of a fan speed level in automatic operating mode (e.g. when using a wind turbine). The fan speed is controlled in automatic operating mode on the basis of the input voltage and an adjusted set point. The positive potential is connected to terminal 40. Terminal 42 is the common GND connection for the inputs 39, 40 and 41. Terminal 41 & 42: Input for the outdoor temperature sensor. This sensor is an NTC with a specific characteristic curve. The outdoor temperature measured influences the fan speed. Terminal 30 & 31: Input for a floating ext. automatic operating mode contact (e.g. room thermostat). Terminal 26 & 27: Input for a floating ext. automatic operating mode contact (e.g. door contact). Terminal 1 & 2: Bus connection for the operating element with reverse polarity protection. Terminal 1 & 2: Bus connection for a master or slave circuit board with reverse polarity protection. Terminal 3 & 4: Supply voltage control element. Setting the master address Master address Master 1 0000 0000 Master 2 0000 0001 Master 3 0000 0010 Master 4 0000 0100 Master 5 0000 1000 Master 6 0001 0000 Master 7 0010 0000 Master 8 0100 0000 Master 9 1000 0000
  • 16. Page 16 Status 13.06.2014 Operating Instructions for Controller TLC 700 2.6 Slave terminal description Terminal N: Mains voltage N-conductor (230V / 50 Hz). Terminal L: Mains voltage L-conductor (230V / 50 Hz). Terminal 52: Connection of the motor neutral conductor. Terminal 51: Connection of the motor phase. Terminal N: Connection of the neutral conductor for the auto transformer. Terminal L1: Connection of the phase for the transformer. Terminal L1: Connection of the phase for the circuitry with 57 (if necessary). Terminal 57: Connection of the transformer tapping with the highest voltage (e.g. 230 V). Terminal 56: Connection of the transformer tapping with the 2nd highest voltage (e.g. 180 V). Terminal 55: Connection of the transformer tapping with the 3rd highest voltage (e.g. 160 V). Terminal 54: Connection of the transformer tapping with the 4th highest voltage (e.g. 125 V). Terminal 53: Connection of the transformer tapping with the lowest voltage (e.g. 70 V). Terminal 32 & N: Connection of the control circuit from the power contactor K1 to shut down the transformer. Terminal PE: Connection of the earth conductor. Terminal 20 & 21: Input for the floating thermal contacts of the fan motors Terminal 22 & 23: Input for the floating thermal contacts of the transformer. Terminal 18 & 19: Input for the floating repair switch. Terminal 16 & 17: Input for the floating frost protection switch. Terminal 1 & 2: Bus connection for the control element or for a master or slave circuit board with reverse polarity protection. Terminal 1 & 2: Bus connection for a master or slave circuit board with reverse polarity protection. Setting the slave address Master assignment of a slave (the first four Bits) Slave address (the last four Bits) Master 1 0000 Slave 1 0000 Master 2 0001 Slave 2 0001 Master 3 0010 Slave 3 0010 Master 4 0011 Slave 4 0011 Master 5 0100 Slave 5 0100 Master 6 0101 Slave 6 0101 Master 7 0110 Slave 7 0110 Master 8 0111 Slave 8 0111 Example: The slave 4 from master 2, DIP switch address = 0001 0011
  • 17. Page 17Status 13.06.2014 3 Start screen on putting into operation for the first time “Installation assistant” screen This screen is shown when you implement the installation assistant or when you have switched the system off. Next button: By pushing the Next button you can access the “Languages” menu and start the in- stallation assistant which guides you through the settings menu. Key button: The key button activates/deactivates the key lock.
  • 18. Page 18 Status 13.06.2014 Operating Instructions for Controller TLC 700 4 Commissioning using the installation assistant 4.1 Setting the language In the “Languages” menu it is possible to set one of the five languages displayed. When a language has been selected, a blue tick appears next to the selected language and the heading changes into the selected language. German is set as standard language. Back button: The “Back” button returns you to the last menu accessed. Next button (is only displayed in the installation assistant): Pushing the “Next” button takes you to the “Basic buttons” menu. Information button: Actuating the “Info” button opens an information screen. This contains a brief expla- nation of the setting options in the respective menu.
  • 19. Page 19Status 13.06.2014 4.2 Basic buttons All buttons which can appear on the individual menu pages are explained on these menu screens. Scroll buttons: You can scroll backwards and forwards between “basic buttons” screens using the scroll buttons. Next button (is only displayed in the installation assistant): Pushing the “Next” button takes you to the “Installation assistant” menu.
  • 20. Page 20 Status 13.06.2014 Operating Instructions for Controller TLC 700 4.3 Installation assistant This screen is only displayed in the installation assistant. It is an information screen that is intended to protect against incorrect commissioning. Back button: The “Back” button returns you to the last menu accessed. Next button (is only displayed in the installation assistant): Pushing the “Next” button takes you to the “Address installer” menu. Information button: Actuating the “Info” button opens an information screen. This contains a brief ex- planation of the setting options in the respective menu. Cancel assistant button: The installation procedure can be aborted using this button and you return to the start screen of the installation assistant again. Previous entries in the installation assistant are deleted.
  • 21. Page 21Status 13.06.2014 4.4 Address installer The contact details of the installer are entered and saved in this menu. This entry is optional, but advisable. It enables the end user to know at all times who to approach for servicing and repair work. Back button: The “Back” button returns you to the last menu accessed. Next button (is only displayed in the installation assistant): Pushing the “Next” button takes you to the “Master systems” menu. Information button: Actuating the “Info” button opens an information screen. This contains a brief expla- nation of the setting options in the respective menu.
  • 22. Page 22 Status 13.06.2014 Operating Instructions for Controller TLC 700 4.5 Master systems selection This screen is only displayed in the installation assistant. In total up to 9 air curtain systems can be controlled/regulated from one control element (remote con- trol) of the TLC 700 controller. In this menu you can stipulate whether all connected air curtain sys- tems are to be set with identical basic parameters or whether individual parameters should apply to each master system. The basic parameters set in the installation assistant can be changed at any time in the settings menu. Back button: The “Back” button returns you to the last menu accessed. Next button (is only displayed in the installation assistant): Pushing the “Next” button takes you to the “Setting the time” menu. Information button: Actuating the “Info” button opens an information screen. This contains a brief expla- nation of the setting options in the respective menu. Master system identical button: If this button is activated (green), then the values entered subsequently are sent to all connected systems. Otherwise the number of connected master systems is deter- mined and the operator must enter the values separately for each system.
  • 23. Page 23Status 13.06.2014 4.6 Setting the time Time, date and switching times can be set and specified in this menu. Time and date are already set in the factory. Back button: The “Back” button returns you to the last menu accessed. Next button (is only displayed in the installation assistant): Pushing the “Next” button takes you to the “Enable” menu. Information button: Actuating the “Info” button opens an information screen. This contains a brief expla- nation of the setting options in the respective menu. Activation/deactivation button: If this button is activated (green), the stored switching times are activated, and the switching times have priority over manual and automatic operating function. The stored switching times are not lost when the button is deactivated (red).
  • 24. Page 24 Status 13.06.2014 Operating Instructions for Controller TLC 700 “Time” button: You can set the current time in this screen: "Hours/minutes" When you touch one of the time boxes, a numerical input window opens up so you can enter the desired time. “Automatic summer/winter time set- ting” button: If this button is set (green), the system automatically switches between summer and winter time. “Date” button: You can set the current date in this screen: “Day/month/year” If you touch one of the date boxes, a numerical input window opens up so you can enter the desired figures.
  • 25. Page 25Status 13.06.2014 4.6.1 Switching times “Start time” button: The switching times are numbered con- secutively. As with setting the time, a sub-menu opens to enter the start time. “Stop time” button: As with setting the time, a sub-menu opens to enter the stop time. “Mon/Tue/Wed/Thur/Fri/Sat/Sun” but- tons: Selection of the days on which the start and stop time should apply. The selected days are indicated by a tick. Other switching times can be created. To do this you must scroll down using the scroll button. The number in the “switch- ing times” screen then changes from 01 to 02 etc. In total 6 switching times can be set per master system. “Scrolling forwards and backwards” button: You can view the set times using the scroll button.
  • 26. Page 26 Status 13.06.2014 Operating Instructions for Controller TLC 700 4.7 Enable It can be specified in the enable menu whether a key lock function is desired. If so, an individual key lock code can be stipulated. Back button: The “Back” button returns you to the last menu accessed. Next button (is only displayed in the installation assistant): Pushing the “Next” button takes you to the “Summer/winter setting” menu. Information button: Actuating the “Info” button opens an information screen. This contains a brief expla- nation of the setting options in the respective menu. Activate key lock button: If the key lock function is activated (green), this is displayed in menu screens. The standard setting is green = activated with code 0000. Authorisation code button: When you actuate the button a 4-digit numerical input box opens. You must enter the authorisation code 1106 here. The authorisation code is always the same, and can- not be changed.
  • 27. Page 27Status 13.06.2014 New code for the key lock button: Important: before you can specify a new code for the key lock, the authorisation code 1106 must first be entered. If the authorisation code is not entered or is entered in- correctly, the system will not accept the new key lock code! When you actuate the button, a 4-digit numerical input box opens. You can now en- ter your desired authorisation code. 0000 is stored as standard. NB: if you forget the code of an activated key lock, the supply voltage must be briefly disconnected from the controller. This deactivates the key lock and you can store a new key lock code. 4.8 Summer/winter setting The basic summer/winter settings of your air curtain system can be stipulated in this menu. In summer mode the heating supply from the heating medium is interrupted. The shut-off valve, the pump or the electronic control valve (optional) are closed or switched off. In winter mode, the heating supply from the heating medium is enabled. The shut-off valve, the pump or the electronic control valve (optional) are open or switched on. Back button: The “Back” button returns you to the last menu accessed.
  • 28. Page 28 Status 13.06.2014 Operating Instructions for Controller TLC 700 Next button (is only displayed in the installation assistant): Pushing the “Next” button takes you to the “Manual/automatic settings” menu. Information button: Actuating the “Info” button opens an information screen. This contains a brief expla- nation of the setting options in the respective menu. Summer/winter function button: When this function is activated (green), the air curtain system can be operated both in summer and winter. If the customer wishes the system to only be operated in one mode (either just summer or just winter), this can be specified by deactivating the function (red). Whether only the summer mode or only the winter mode should be active is defined at the manufacturer level. 4.8.1. Automatic summer/winter changeover “Temperature entry” button: The summer/winter changeover is switched manually by operating staff by way of standard. If the optional outdoor temperature sen- sor is available, the summer/winter changeover takes place automati- cally using the specified set point (e.g. 18 °C). An additional window opens up to enter the desired temperature (standard setting = 18°C) when you actuate this button. When you touch the temperature box, a numerical input window opens up so you can enter the desired temperature.
  • 29. Page 29Status 13.06.2014 4.8.2 Electronic air discharge temperature control “Room temperature switching” button This information button is only dis- played when the room temperature switching has been activated in the settings menu. It cannot be used to adjust settings. “Summer (cooling)” button: This button is only displayed when the cooling function is activated at the manufacturer level (standard = deactivated). The summer (cool- ing) function is required when the air curtain system is also to be used for cooling. In this case the output signal to the motorised con- trol valve is reversed. The tem- perature set point for the summer mode can be entered here. “Winter (heating)” button: The temperature set point for win- ter mode can be entered here. General: When you touch the temperature box, a numerical input window opens up so you can enter the desired temperature. Actual value box: The current air discharge tempera- ture of the air curtain system is displayed here.
  • 30. Page 30 Status 13.06.2014 Operating Instructions for Controller TLC 700 “Mixer run time” button: This specifies the run time that the valve requires from one end posi- tion to the other end position (fac- tory setting = 330 sec). “I-control constant (heating)” button: The integral part of the electronic air discharge temperature control which influences the control per- formance can be adjusted here (setting from 0 to 240 sec., factory setting = 200 sec.). “P-control constant (heating)” button: The proportional part of the elec- tronic air discharge temperature control which influences the con- trol performance can be adjusted here (setting from 10 to 1000 %, factory setting = 500 %). “Min. valve opening” button: When a value (greater than 0%) is entered here, a specific volume of water flows permanently through the heater battery. This prevents the heater battery freezing in the winter, causing frost damage. This function is only active in winter mode! General: When you touch the nu- meric keypad, a numerical input window opens up so you can enter the desired level.
  • 31. Page 31Status 13.06.2014 “Set point night-time tempera- ture reduction” button: The night-time temperature reduc- tion is active when this button is set (green). This function can only be activated when switching times have been stored in the timer pro- gram. “Winter” button: The temperature set point (air dis- charge temperature control) for night-time temperature reduction can be entered here. “I-control constant (heating)” button: The integral part of the electronic air discharge temperature control which influences the control per- formance can be adjusted here (setting from 0 to 240 sec., factory setting = 200 sec.). “P-control constant (cooling)” button: The proportional part of the elec- tronic air discharge temperature control which influences the con- trol performance can be adjusted here (setting from 10 to 1000 %, factory setting = 500 %). General: When you touch the nu- meric keypad, a numerical input window opens up so you can enter the desired level.
  • 32. Page 32 Status 13.06.2014 Operating Instructions for Controller TLC 700 4.9 Manual/automatic mode setting This menu page is displayed with speed or level, depending on which type of motor is installed (AC or DC). It is set in the factory (Teddington). Specify the basic manual/automatic mode settings for your air curtain system in this menu. In manual mode the air curtain system operates permanently at the preselected level. The level can be set on the control element. In automatic mode the air curtain system is switched on and off automatically. The level is prese- lected manually on the control element or optionally automatically. Back button: The “Back” button returns you to the last menu accessed. Next button (is only displayed in the installation assistant): Pushing the “Next” button takes you to the “Room thermostat” menu. Information button: Actuating the “Info” button opens an information screen. This contains a brief expla- nation of the setting options in the respective menu.
  • 33. Page 33Status 13.06.2014 Manual/Auto function button: When this function is activated (green), the air curtain system can be operated in both manual and automatic operating mode. If the customer wishes the system to be op- erated in only one mode (either just manual or just automatic), this can be specified by deactivating (red). It is defined at the manufacturer level whether only manual or only automatic operating mode should be active. Automatic run-on button: You can specify here how long the fans continue to run after the system has been switched off in automatic mode. This prevents the system being switched on and off constantly in busy times (adjustable: 0-600 sec, standard = 20 sec). Level/speed for the run-on button: By activating this function (green), you can specify a level or a speed for the run-on time. When you touch the numeric keypad, a numerical input window opens up so you can enter the desired level. PLEASE NOTE Only one of the four automatic functions described below can be se- lected! The decision as to which function is best for you depends on the particular building situation. “Outdoor temperature sensor” button: The speed or level switching takes place automatically here using an optional out- door temperature sensor. This function is only active in automatic operating mode. Button set (green) - “Outdoor tempera- ture” function is active. “Summer/winter operation” button: By activating this function (green), the system is also controlled automatically via the outdoor temperature sensor in summer mode. “Summer/winter changeover” button: When this function is activated, the sum- mer/winter changeover for the speed control takes place according to the set point that has been entered (standard value = 18°C). Outdoor temperature box: The current outdoor temperature is dis- played here.
  • 34. Page 34 Status 13.06.2014 Operating Instructions for Controller TLC 700 Level/speed box: Level and speed values for summer and winter mode can be specified here de- pending on the outdoor temperature. The heading “level” or “speed” depends on the type of motor installed. If the “Summer/winter operation” button in the “automatic operating mode outdoor temperature” screen has been deactivat- ed (red), the summer column is not shown. Only entries for the winter mode can be made therefore. General: When you touch the numeric keypad, a numerical input window opens up so you can enter the desired level. “Infrared sensor” button: The speed or level switching takes place automatically here when using an option- al infrared sensor. This function is only active in automatic operating mode. Button set (green) - “Infrared sensor” function is active. “Set point” button: You can enter the set point for the ground temperature here. Actual level box: The current ground temperature is dis- played here. “P-control constant” button: The proportional part of the electronic infrared control which influences the con- trol performance can be adjusted here (setting from 10 to 1000 %, factory set- ting = 100 %). “I-control constant” button: The integral part of the electronic infrared control which influences the control per- formance can be adjusted here (setting from 0 to 240 sec., factory setting = 10 sec.). General: When you touch the numeric keypad, a numerical input window opens up so you can enter the desired level.
  • 35. Page 35Status 13.06.2014 “External 0-10V signal” button: The speed or level switching takes place automatically here using an external 0- 10V signal (e.g. BMS, wind turbine). This function is only active in automatic mode. Button set (green) - “0-10V signal” func- tion is active. Actual level box: The actual value of the external input signal is displayed here. “Linear” button: By activating (green) the linear function in in automatic operating mode, the output signal (speed/level) is determined and generated proportional to the input signal (0-10 V). Input 0-10V Level 0-9 % 0 10-29 % 1 30-49 % 2 50-69 % 3 70-89 % 4 90-100 % 5 “PI- control” button: By activating (green) the PI control func- tion in automatic operating mode, the output signal (speed/level) is determined and generated by the PI control. The PI control regulates the difference between the actual value (0-100%/0-10V input) and the set point value which has been set using the control element. “Set point” button: The set point for the PI control can be set here. This set point button is only dis- played when the PI control function has been activated! The four input value boxes are re- quired for the linear function. “Bottom” input value buttons: How the input signals are to be shown as values on the display is specified here. Example turbine: Bottom input value 0V (0 km/h)=0% Top input value 10V (50 km/h)=100%
  • 36. Page 36 Status 13.06.2014 Operating Instructions for Controller TLC 700 “P-control constant” button: The proportional part of the PI-control which influences the control performance can be adjusted here (setting from 10 to 1000 %, factory setting = 100 %). P-part: P=10% and ΔU = 0.1 V >> speed change = 1% “I-control constant” button: The integral part of the PI-control which influences the control performance can be adjusted here (setting from 0 to 240 sec., factory setting = 10 sec.). I-part: I = 60 sec., P=100% and ΔU = 0.1 V (constant over 60 sec.) >> speed change = 1% General: When you touch the numeric keypad, a numerical input window opens up so you can enter the desired level. “External 0-20mA signal” button: The speed or level switching takes place automatically here using an external 0- 20mA signal (e.g. BMS, turbine). This function is only active in automatic oper- ating mode. Button set (green) “0-20mA signal” func- tion is active. Actual level box: The actual value of the external input signal is displayed here. “Linear” button: By activating (green) the linear function in in automatic operating mode, the output signal (speed/level) is determined and generated proportional to the input signal (0-20 mA). Input 0-20 mA Level 0-9 % 0 10-29 % 1 30-49 % 2 50-69 % 3 70-89 % 4 90-100 % 5
  • 37. Page 37Status 13.06.2014 “PI-control” button: By activating (green) the PI control func- tion in automatic operating mode, the output signal (speed/level) is determined and generated by the PI control. The PI control regulates the difference between the actual value (0-100%/0-20mA input) and the set point value which has been set using the control element. “Set point” button: The set point for the PI control can be set here. This set point button is only dis- played when the PI control function has been activated! The four input value boxes are re- quired for the linear function. “Bottom” input value buttons: How the input signals are to be shown as values on the display is specified here. Example turbine: Bottom input value 0mA (0 km/h)=0% Top input value 20mA (50 km/h)=100% “P-control constant” button: The proportional part of the PI-control which influences the control performance can be adjusted here (setting from 10 to 1000 %, factory setting = 100 %). P-part: P=10% and ΔU = 0.1 V >> speed change = 1% “I-control constant” button: The integral part of the PI-control which influences the control performance can be adjusted here (setting from 0 to 240 sec., factory setting = 10 sec.). I-part: I = 60 sec., P=100% and ΔU = 0.1 V (constant over 60 sec.) >> speed change = 1% General: When you touch the numeric keypad, a numerical input window opens up so you can enter the desired level.
  • 38. Page 38 Status 13.06.2014 Operating Instructions for Controller TLC 700 4.10 Room thermostat setting Whether the system is to be switched on and off automatically using a room thermostat and there- fore the heating function is desired is specified using the room thermostat menu. The automatic ac- tivation via terminals 26 and 27 (door contact) has priority over the room thermostat function! Back button: The “Back” button returns you to the last menu accessed. Information button: Actuating the “Info” button opens an information screen. This contains a brief expla- nation of the setting options in the respective menu. Thermostat button: The room thermostat function is active (standard = activated) when this button is set (green). Internal/external button: By actuating the internal or external button, you specify whether the internal room sensor or an external room sensor/external room thermostat is to be used for the thermostat function. The controller automatically detects whether an external room sensor or an external room thermostat has been connected.
  • 39. Page 39Status 13.06.2014 Set point button: You can enter the set point for the room temperature here. If the room temperature (actual value) falls below the set point, the system is switched on in automatic mode. This set point is used for the internal and external room sensor. Actual value box: The current room temperature is displayed here. Base load level/base load speed button: This function is active when this button is set (green) and the following settings (e.g. base load level/base load speed) are displayed (standard = deactivated). Scroll forwards button: You can scroll to the next settings menu page using this button. Scroll backwards button: You can scroll back to the previous settings menu page using this button. Next button (is only displayed in the installation assistant): Pushing the “Next” button takes you to the “Servicing” menu. Depending on which motor has been connected (AC or EC), “base load level” or “base load speed” is displayed in the menu. The AC or EC motor setting is made by the manufacturer. “Base load level/base load speed button: When the base load level/base load speed button (previous screen) has been activated (green), the input box for the base load level/base load speed appears in the menu. Using this setting you can specify a special level/speed for the room thermostat operation. “Night-time temperature reduction” button: You can set a different night-time room temperature by activating this function (green). This function can only be acti- vated when switching times have been activated in the timer program. “Set point” button (is only displayed when the night-time temperature re- duction is active): You can adjust the room temperature at which the systems should be switched on at night by actuating the set point button. This set point is used for the internal and external room sensor (standard = 16°C). “Actual value box: The current room temperature is dis- played here. General: When you touch the numeric keypad, a numerical input window opens up so you can enter the desired level.
  • 40. Page 40 Status 13.06.2014 Operating Instructions for Controller TLC 700 4.11 Servicing menu Whether and how a filter service message is generated is specified in the servicing menu. Back button: The “Back” button returns you to the last menu accessed. Next button (is only displayed in the installation assistant): Pushing the “Next” button takes you to the main screen and you leave the installation assistant. Information button: Actuating the “Info” button opens an information screen. This contains a brief expla- nation of the setting options in the respective menu. Filter servicing button: This function is active (standard = activated) when this button is set (green) and you are informed automatically when the next service is due.
  • 41. Page 41Status 13.06.2014 Internal/external button (is only displayed with activate filter servicing): By actuating the internal or external button, you can specify whether the service mes- sage is triggered internally or by an external signal. If the internal button is activated, the service is generated by a time module (operating hours). If the external button has been activated, a service message is triggered via an external signalling device (terminal 24/25). Actual operating hours display: Display of the operating hours since the last service. The operating hours are incre- mental. Target operating hours button: Specification of the time interval between servicing units (standard = 500h; you can and should check this interval and adapt it to your situation. Please refer to the air curtain operating instructions to find out how to establish the correct interval). Set to 0 button: By actuating the “Set to 0 button”, the actual operating hours display is set to 0. The counting of the operating hours starts from the beginning again. This completes the installation assistant for the first master system. If you have select- ed further different master systems, you can now go to the start of the second installa- tion assistant for the second master system starting with setting the time. If you have not selected another master system, you go to the main screen for the con- troller.
  • 42. Page 42 Status 13.06.2014 Operating Instructions for Controller TLC 700 5 Main screen / standard displays 5.1Standard screen depending on the version of air curtain system The arrangement of the air curtain system in the display has already been set in the factory and can be changed by the manufacturer at any time. After implement- ing the installation assistant, one of the following screens is displayed for each master system: “IDW” screen (air roll rotating inwards) The system selection box only appears if more than one master system is pre- sent in the system (eBus)! “ADW” screen (air roll rotating outwards)
  • 43. Page 43Status 13.06.2014 5.2 Standard display depending on the desired arrangement “One-sided left” screen “One-sided right” screen “Two-sided” screen
  • 44. Page 44 Status 13.06.2014 Operating Instructions for Controller TLC 700 Please note: System selection can only take place after implementing the installa- tion assistant in the main screen! You can select the system to be adjusted in this screen. • Green: System is present and switched on • Blue: Selected system • Orange: System is present but switched off • Grey: System is not present
  • 45. Page 45Status 13.06.2014 5.3 Functions main screen Key lock button: The key lock can be activated and deactivated here. Actuating the button opens a window in which the key lock code can be entered. After entering the code the display is locked and therefore protected from unauthorised operation. The acti- vated key lock is displayed by a closed padlock. Settings menu button: The settings overview menu is opened using this button: On/off button: Switches the master air curtain system off. If more than one master systems (Multimaster) are connected, all systems are switched off simultaneously by keeping the button pressed for longer.
  • 46. Page 46 Status 13.06.2014 Operating Instructions for Controller TLC 700 5.4 Hotkeys on the main screen The most important basic functions are integrated on the respective main screen by means of hotkeys. When touched the functions can be opened and changed without having to run through the settings menu steps etc. Only the functions which have been activated are dis- played on the main screen! Functions are stored on these screen systems:
  • 47. Page 47Status 13.06.2014 Function Symbol which can be activated on the main screen Function subpage which appears after actuating the symbol Setting the date Air discharge tem- perature Outdoor temperature Time Summer/ winter function or
  • 48. Page 48 Status 13.06.2014 Operating Instructions for Controller TLC 700 Speed or level set- ting or Manual/automatic function or System selection Room temperature Ground temperature (Actual value = ground temperature)
  • 49. Page 49Status 13.06.2014 5.5 Entry and keypad The operator must be able to store various values in the settings menu pages. For example when setting the time, press on the value you want to change and this opens a numerical keypad in a sub- menu. You can enter the new value here and/or delete the existing values again using the “Delete button”. A written entry must be stored for other settings. A keypad screen therefore appears for these input boxes (when touched).
  • 50. Page 50 Status 13.06.2014 Operating Instructions for Controller TLC 700 6 Settings menu Actuating the “Settings menu” button on the main screen takes you to this sub-menu. Here you can adjust all settings that are required for ideal functioning of the air curtain system. Settings from the installation assistant can likewise be changed here. Back button: The “Back” button returns you to the main screen. 6.1 Setting the language sub-menu Language setting button: For menu description, see Chapter 41.1, Page 18.
  • 51. Page 51Status 13.06.2014 6.2 Settings sub-menu The installed software version (is automatically detected) and the installed hard- ware version (is likewise automatically detected) are displayed on the first page of settings. Back button: The “Back” button returns you to the last menu accessed. Information button: Actuating the “Info” button opens an information screen. This contains a brief explanation of the setting options in the respective menu. Scroll forwards button: You can scroll to the next settings menu page using this button. The three functions marked above are only displayed if the electronic air dis- charge temperature control has been activated! “Activate room switching” button: The room temperature difference is switched to the air discharge temper- ature control on activating this func- tion (green) (standard = deactivated). “Reinforcement factor” button: If the current room temperature is higher than the set room temperature set point, the air discharge tempera- ture set point is automatically changed with the aid of the rein- forcement factor (standard setting 2). Example: Current room temperature 23 °C Set point room temperature 22 °C Reinforcement factor 2 Set point air discharge temp. control 37 °C
  • 52. Page 52 Status 13.06.2014 Operating Instructions for Controller TLC 700 Using the reinforcement factor 2 and the room temperature variation of 1°C, the set point of the air discharge temperature is corrected from 37 °C to 35 °C. “Minimum set point air discharge temperature” button: With this setting you determine the lowest set point of the electronic air discharge temperature control (standard setting 30 °C) which the room temperature switching calcu- lates and does not fall below. General: When you touch the numer- ic keypad, a numerical input window opens up so you can enter the de- sired level. Scroll forwards button: You can scroll to the next settings menu page using this button. “Contact details of installer” but- ton Actuating this box takes you to the sub-menu to change or enter the ad- dress data of the installer; see Chap- ter 4.4, Page 21. “Sleep mode” button Actuating this box takes you to a sub- menu in which you can adjust the sleep mode time. The function is active when no further operation has taken place after the set time (stand- ard setting 15 minutes). The idle screen appears in the display (black/grey image). If 0 is entered here, the sleep mode is deactivated. To deactivate the function you only need to touch the screen. Irrespec- tive of where you were before activa- tion, after activation you are always on the main screen.
  • 53. Page 53Status 13.06.2014 6.3 Setting the time sub-menu Time setting button: Menu description see Chapter 4.6 Setting the time, Page 23. 6.4 Enable sub-menu Enable button: Menu description see Chapter 4.7 Enable, Page 26. 6.5 Summer/winter setting sub-menu Summer/winter setting button: Menu description see Chapter 4.8 Summer/winter setting, Page 27 6.6 Manual/automatic setting sub-menu Manual/automatic setting button: Menu description see Chapter 4.9 Manual/automatic mode setting, Page 32 6.7 Room thermostat sub-menu Room thermostat button: Menu description see Chapter 4.10 Room thermostat setting, Page 38
  • 54. Page 54 Status 13.06.2014 Operating Instructions for Controller TLC 700 6.8 Electronic air discharge temperature control sub-menu Electronic air discharge temperature control button: Menu description see Chapter 4.8.2 Electronic air discharge temperature control, Page 29. 6.9 Manufacturer level sub-menu Manufacturer level button: Actuating this button takes you to the start screen of the manufacturer level; ac- cess is reserved for the manufacturer. 6.10 Servicing sub-menu Servicing button: Description see Chapter 4.11 Servicing menu, Page 40
  • 55. Page 55Status 13.06.2014 6.11 Error/fault sub-menu The faults screen shows you a report of the last faults that have arisen. If a fault occurs, this is firstly displayed on the main screen. Once the fault has been rectified, it can be acknowledged using the button . The fault window is then faded out. The fault can only be acknowledged if you are on the screen of the respective master system, e.g. the is not displayed if a fault is present in system 2, but the operator is in the menu of system 1!
  • 56. Page 56 Status 13.06.2014 Operating Instructions for Controller TLC 700 6.12 Contacts and button overview sub-menu This menu screen gives you important information about the manufacturer of the air curtain system, the installer and above all which basic menu buttons you must be familiar with in order to operate the TLC 700 controller easily. In this sub-menu you will find all es- sential information on the manufactur- er of the air curtain system. The contact details of the installer are stored in this sub-menu. Basic buttons: Menu description see Chapter 4.2 Basic buttons, Page 19
  • 57. Page 57Status 13.06.2014 Serial number: The serial number of your system has been stored by the manufacturer and is displayed here.
  • 58. Page 58 Status 13.06.2014 Operating Instructions for Controller TLC 700 Notes:
  • 60. Page 60 Status 13.06.2014 Operating Instructions for Controller TLC 700